Documente Academic
Documente Profesional
Documente Cultură
L. Li et al.: Condition Assessment of Power Transformers Using a Synthetic Analysis Method Based on Association Rule
ABSTRACT
Condition assessment for power transformer requires not only integrating the known
artificial intelligence (AI) technology, but also exploiting the interrelation of the measured
data. According to the association rule of information data and the variable weight
synthesizing theory of factor spaces, an assessment method of transformer condition was
proposed in this paper. Via analyzing the interrelation of the independent status
parameters (ISP) and transformer fault types, the set of synthetic status parameters (SSP)
can be built up. For avoiding interference from subjective experience, association rule
theory was used to calculate the constant weight coefficients (CWC) of the ISPs. Since the
true transformer condition may not always be accurately reflected under the condition of
CWCs of a few SSPs, the method of variable weight synthesizing was used for computing
the variable weight coefficients (VWC) of the SSPs. Then, combining with the existing
maintenance procedures, a preferable condition assessing system of power transformer
was proposed. Operational example proved the condition assessing system may reflect the
real operation condition of power transformer.
Index Terms Transformer, association rule, condition assessment, variable weight.
INTRODUCTION
2053
the empirical advices of SGCC staff. For other power grids, the
construction of ISPs and SSPs should be open. At last, the
SSPs of a power transformer listed in this paper may
be constructed as shown in Table 1.
Table 1. Mapping table of ISPs and SSPs of power transformer.
SSP
ISP
1Moistened insulation
2 Core fault
3 Overheating
4 Winding fault
5 Partial discharge
6 Oil-flow discharge
7 Arc discharge
8 Insulation aging
9 Oil deterioration
1)
2)
3)
4)
5)
polarisation index
6)
volume resistivity
7)
8)
1)
2)
3)
4)
1)
2)
3)
4)
1)
4)
1)
2)
3)
4)
5)
6)
1)
2)
3)
volume resistivity
4)
5)
1)
2)
3)
4)
1)
2)
3)
4)
5)
6)
volume resistivity
1)
2)
3)
4)
5)
6) volume resistivity
Note: (1) In this table, it is for the ISPs from DGA with *, and the
remaining from routine/preventive electrical tests.
2054
L. Li et al.: Condition Assessment of Power Transformers Using a Synthetic Analysis Method Based on Association Rule
probability of P B A :
support A B P A B
P A B
C A B P B A
(1)
P A
100%
(2)
Item set B j =
Ai , j B j
Dj
100%
Ai , j D j
Dj
100%
(3)
P Ai , j B j
P Ai , j
Ai , j B j D
Ai , j D
Ai , j B j
Ai , j
(4)
100%
2055
wvj
wj
xj
x
p 1
(6)
where wvj and x j are the VWC and score of the j -th
SSP, respectively, m is the number of SSPs, w j is the
CWC of the j -th SSP.
If the balanced factor is pulled into the formation of
variable weight synthesizing mode, the variable weight
formula can be obtained as [26-27]:
wvj w j xj 1
w
p 1
xp 1
(7)
2056
L. Li et al.: Condition Assessment of Power Transformers Using a Synthetic Analysis Method Based on Association Rule
i -th ISP
is the score of the
(when xi , j 0 , xi , j 0 ; when xi , j 100 , xi , j 100 ), y is
the warning value of this ISP. If the status parameter gives
the attention value y z , then y 1.3 y z if y z y f , or
y y z 1.3 if y z y f . y f is the initial value of status
where
n j
i 1
xi, j w i, j
(9)
T x j wvj
(10)
j 1
80-100
60-80
20-60
0-20
operating condition
Normal
Attention
Abnormal
Serious
6 EXAMPLE ANALYSIS
A 220 kV main transformer used in the substation of
Southwest China is taken as for example. The model of this
transformer is SFPS9-150000 kVA/220 kV. A routine test
was performed on April 17th 2010. We collected the data of
ISPs which mentioned in Table1, and show those as the
measured values in Table 3. The relative attention and initial
values are listed too.
Table 3. One set sample of measured data of ISPs.
Measured
Initial values
Attention
ISP
values ( yi , j )
( yf )
values ( yz )
dielectric loss factor of
oil
1.7%
4%
0.5%
12.1 mg/L
25 mg/L
3.5 mg/L
55 kV
35 kV
58 kV
absorptance of
insulation resistance
1.61
1.3
polarisation index
2.03
1.5
2.5
5510 m
310 m
60109 m
359 ppm
150 ppm
6.1 ppm
3.8A
0.1A
0.01A
200 M
100 M
1000 M
92 ppm
65 ppm
2.3 ppm
52 ppm
50 L/L
4.8 ppm
1.5%
4%
1%
12%/month
100%/month
31%/month
200%/month
1.2%
3%
1%
0.36%
0.8%
0.17%
1.4%
5%
1%
5 ppm
72 pC
500 pC
30 pC
1.6%
3%
1%
18.5 ppm
100 ppm
8.7 ppm
0.07 A
1 A
0.02 A
0.05 mg/L
0.2 mg/L
polymerization degree
of insulating paper
900
250
1000
volume resistivity
H2 (hydrogen content
in oil)
core grounding current
insulation resistance
of core
C2H6 (ethane content
in oil)
C2H4 (ethylene
content in oil)
difference of winding
DC-Resistance
production rate of
carbon monoxide
(CO)
production rate of
carbon dioxide (CO2)
increment of winding
short-circuit
impedance
winding dielectric loss
increment of winding
capacitance
C2H2 (acetylene
content in oil)
partial discharge
magnitude
total oil dissolved gas
content
CH4 (methane content
in oil)
oil-flow electrostatic
current in neutral point
2057
Moistened
insulation
Number of
fault
89
ISP
Total beyond-index
frequency of ISP
Beyond-index frequency of
ISP in all fault of SSP
CWC
wi , j
Support
Level
374
88
0.0640
0.9888
237
87
0.0998
0.9775
162
82
0.1376
0.9213
absorptance of insulation
resistance
76
72
0.2575
0.8090
polarisation index
71
65
0.2488
0.7303
volume resistivity
340
66
0.0528
0.7416
349
82
0.0639
0.9213
262
73
0.0757
0.8202
109
105
0.3945
0.9375
262
102
0.1594
0.9107
142
99
0.2855
0.8839
222
87
0.1605
0.7768
267
94
0.1399
0.9691
99
87
0.3491
0.8969
98
89
0.3608
0.9175
222
84
0.1503
0.8660
101
98
0.3641
0.9608
208
95
0.1714
0.9314
99
97
0.3677
0.9510
349
90
0.0968
0.8824
190
85
0.1917
1.0000
356
78
0.0939
0.9176
349
76
0.0933
0.8941
93
81
0.3733
0.9529
267
71
0.1140
0.8353
237
74
0.1338
0.8706
oil-flow electrostatic
current in neutral point
94
92
0.4627
1.0000
374
85
0.1075
0.9239
volume resistivity
340
89
0.1238
0.9674
356
83
0.1102
0.9022
198
82
0.1958
0.8913
267
95
0.2170
0.9048
190
94
0.3018
0.8952
349
92
0.1608
0.8762
198
104
0.3204
0.9905
117
112
0.2904
0.9825
Overheating
112
97
insulation resistance of
core
*C2H6 (ethane content in
oil)
*C2H4 (ethylene content in
oil)
difference of winding
DC-Resistance
* production rate of carbon
monoxide (CO)
* production rate of carbon
dioxide (CO2)
*C2H4 (ethylene content in
oil)
increment of winding
short-circuit impedance
winding dielectric loss
Winding fault
Partial
discharge
Oil-flow
discharge
Arc discharge
Insulation
102
85
92
105
114
increment of winding
capacitance
*H2 (hydrogen content in
oil)
partial discharge
magnitude
* total oil dissolved gas
content
*H2 (hydrogen content in
oil)
*CH4 (methane content in
oil)
difference of winding
DC-Resistance
CONTINUED
2058
L. Li et al.: Condition Assessment of Power Transformers Using a Synthetic Analysis Method Based on Association Rule
TABLE 4. CONTINUED
aging
374
101
0.0819
0.8860
356
102
0.0869
0.8947
112
110
0.2979
0.9649
208
106
0.1546
0.9298
volume resistivity
340
99
0.0883
0.8684
374
88
0.1336
0.9778
237
71
0.1701
0.7889
162
73
0.2558
0.8111
262
82
0.1777
0.9111
356
79
0.1260
0.8778
340
82
0.1369
0.9111
Oil
90
deterioration
insulation resistance of
core
* total oil dissolved gas
content
volume resistivity
SSP
Score ( x j )
VWC ( w )
Moistened insulation
61.93
0.0572
Core fault
5.59
0.6331
Overheating
79.03
0.0448
Winding fault
81.39
0.0435
Partial discharge
79.09
0.0448
Oil-flow discharge
92.07
0.0385
Arc discharge
79.29
0.0447
Insulation aging
82.68
0.0428
Oil deterioration
69.85
0.0507
data
types
fault
data
set
normal
data
set
known
data
sets
Serious
Abnormal
0-20
20-60
60-70
70-80
80-100
54
11
36
46
42
Attention
Normal
The data in Table 5 are put into equation (10), then the
final score of the transformer is calculated as T =31.86.
Compared with Table 2, this score shows that the
transformer condition is abnormal. And the score of Core
fault is only 5.59, significantly lower than the other SSPs,
which indicated that the transformer may go wrong in the
core or fixture. When power-cut detection on April 19th
2010, it was discovered that there was a little metal impurity
on the bottom of the transformer oil tank. This may cause
the unstable multiple grounding and part overheating.
For further verification, 100 sets of the historical
measured data, whose conditions are known, are sampled.
Among them, based on fault reports, it is known that 54 sets
of data were for fault condition. The remaining are in
normal. As space is limited, the detail calculating process of
all 100 sets cannot be represented. Like the measured values
in Table 3, these data are put into the condition assessing
steps, respectively. The calculated scores are distributed in
Table 6.
It can be seen from Table 6 that in all 54 known failure
data sets, the proposed assessment method can judge that 11
sets are in the serious condition, 36 sets are in the abnormal
state, 7 sets are in the attention condition. But the scores of
the 7 sets are close to 60 which are leaned to be abnormal.
While, in all 46 known normal data sets, 42 sets are
assessed in the normal condition, 4 sets are in the attention
condition, and the scores of the 4 sets are close to 80 which
are leaned to be normal. Assessment results are basically
consistent with the known actual situation, which proves
that the method described in this paper can accurately
reflect the operating condition of power transformers.
7 CONCLUSIONS
Condition-based maintenance of power transformers is
significant for the reliability improvement of the power grid.
The contributions of this article are summarized as following:
(1) Transformer condition assessment system is
established based on data mining for routine/preventive test.
REFERENCES
[1] M. Wang, A.J. Vandermaar, and K.D. Srivastava, Review of
condition assessment of power transformer in service, IEEE
Electr. Insul. Mag., Vol.18, No. 6, pp.12-25, 2002.
[2] T. K. Saha, Review of modern diagnostic techniques for assessing
insulation condition in aged transformers, IEEE Trans. Dielectr.
Electr. Insul., Vol. 10, No. 5, pp.903-917, 2003.
[3] T. K. Saha, Review of time-domain polarization measurements for
assessing insulation condition in aged transformers, IEEE Trans.
Power Delivery, Vol. 18, No.4, pp. 1293-1301, 2003.
[4] H. Ma, T.K. Saha, and C. Ekanayake, Statistical learning
techniques and their applications for condition assessment of
power transformer, IEEE Trans. Dielectr. Electr. Insul., Vol. 19,
No. 2, pp.481-489, 2012.
[5] IEEE Guide for the Interpretation of Gases Generated in
Oil-Immersed Transformers, IEEE Standard C57.104-2008, 2009.
[6] International Standard IEC 60599-1999, Mineral oil-impregnated
electrical equipment in service-Guide to the interpretation of
dissolved and free gases analysis.
[7] Chinese National Standard GB/T7252-2001, Guide to the analysis
and the diagnosis of gases dissolved in transformer oil.
[8] Y. C. Huang, Condition assessment of power transformers using
genetic-based neural networks, IEE Proc. Sci. Measur. Tech. Vol.
150, No. 1, pp. 19-24, 2003.
[9] K. Tomsovic, M. Tapper, and T. Ingvasrsson, Performance
evaluation of a transformer condition monitoring expert system,
presented at the International Council on Large Electric Systems
(CIGR), Berlin, Federal Republic of Germany, 1993.
[10] Z. Wang, Y. Liu, and P.J. Griffin, Neural net and expert system
diagnose transformer faults, IEEE Computer Applications in
Power, Vol. 13, No. 1, pp. 50-55, 2000.
[11] T. Jiang, J. Li, Y. Zheng, C. X. Sun, Improved bagging algorithm
for pattern recognition in UHF signals of partial discharges,
Energies, Vol.4, No. 4, pp.10871101, 2011.
[12] A. P. Chen, C. C. Lin, Fuzzy approaches for fault diagnosis of
transformers, Fuzzy Sets Syst., Vol.118, No.1, pp.139151,
2001.
[13] R. Naresh, V. Sharma, M. Vashisth, An integrated neural fuzzy
approach for fault diagnosis of transformers, IEEE Trans. Power
Delivery, Vol. 23, No.4, pp.2017-2014, 2008.
[14] R. J. Liao, H. B. Zheng, S. Grzybowski, An integrated
decision-making model for condition assessment of power
transformers using fuzzy approach and evidential reasoning,
IEEE Trans. Power Delivery, Vol. 26, No.2, pp. 2111-2118, 2011.
2059
2060
L. Li et al.: Condition Assessment of Power Transformers Using a Synthetic Analysis Method Based on Association Rule
Zhang Deng was born in Hubei province, China, in
1985. He received the M.S. degree from the College
of electrical & electronic engineering, Huazhong
University of Science and Technology (HUST) in
2013. He has been working as an engineer in
Dongguan Power Supply Bureau, China Southern
Power Grid, Guangdong Province.