Fm
Comfort
Controller
CC 6400
Remote communication
over telephone network
Fm
Comfort
Controller
CC 6400
Carrier
Management
Terminal
CONTENTS
The cover photographs are for illustration only, and have no contractual significance whatsoever.
The manufacturer reserves the right to change the appearance and design of the units at any time without notice.
2
CONTENTS (contd)
1 - SAFETY CONSIDERATIONS
1.1 - General
Installing, commissioning and servicing the various components
which make up the Maestro control system can be dangerous
unless certain aspects of the system are taken into account,
such as the presence of mains electricity and hot or chilled
water in the air conditioning equipment.
Only specially trained technicians and installers who have
been fully trained on the product concerned are authorised to
install, commission and service this equipment.
During servicing work, it is essential to apply all the recommendations and instructions given in service leaflets, on labels or
in the instructions delivered with the equipment, and to
comply with any other relevant safety notices.
It is important to comply with all the safety rules and regulations
currently in force. Wear eye protectors and work gloves.
Take extreme care when moving or positioning equipment.
1.2 - Precautions against electrocution
Only electricians who are qualified to the level recommended
by the IEC (International Electrotechnical Commission) in its
standard IEC 364, corresponding to Europe HD 384, France
NFC 15 100 and UK IEE Wiring Regulation, may have access to
electrical components. In particular it is obligatory to disconnect
all electrical power supplies to the unit or its accessories
before carrying out any work. Disconnect the main power
supply with the standard isolating switch (not supplied by
Carrier).
IMPORTANT: The components which make up the Maestro
control system include items of electronic equipment. As such,
they may generate or be disturbed by electromagnetic interference unless they are installed and used in accordance with
these instructions. The components making up the Maestro
control system conform to the requirements of electromagnetic
compatibility in residential and industrial areas. They also
comply with the low-voltage directive.
1.3 - General installation recommendations
IMPORTANT: There must be a power disconnection device
upstream of the controller and Power Module (this may take
the form of a double-pole circuit breaker, for instance). If
necessary, an easily operated emergency stop device (such as
a punch-button switch) must cut off the power to all
equipment. These safety devices shall be dimensioned and
installed in accordance with IEC Recommendation 364,
corresponding to Europe HD 384, France NFC 15 100 and
UK IEE Wiring Regulation. These devices are not supplied by
Carrier.
IMPORTANT: When replacing a Maestro controller please
verify the configuration of the variable or three-speed type
fan motor assembly, before connecting it to the controller.
In general terms the following rules must be applied:
1.4 - Conformity
This equipment has been declared to be in conformity with the
main requirements of the directive by virtue of using the
following standards:
two-pipe or four-pipe,
3.1 - Architecture
The minimum control system consists of a control module (Zc)
and a temperature sensor (not supplied by Carrier).
Secondary bus
Master
Slave
Zui bus
Zui bus
Slave
Zone A
Master
Others
Zui bus
Zui bus
Zone B
Primary bus
BMS
Fm
Fm
Slave
Master
Key:
Fm
Floor Manager
Zc
Zone Controller
Zui
Zone User Interface
(microterminal)
BMS Building Management System
Secondary bus
Zui bus
Slave
Zui bus
Zui
Others
Slave
Zui
Zui bus
Zui bus
Zui
Zui
Zone A
Fm (optional)
Secondary bus
Master Zc
Slave Zc
Other Zcs
Master Zc
Other Zcs
Master Zc
Other Zcs
Local bus 1
Local bus n
Master Pm
Slave Pm
Slave Pm
Other Pms
Local bus 2
Zui bus
Zui bus
Zui bus
Master Pm
Zui bus
Zui
Key:
Fm Floor Manager
Zc Zone Controller
Pm Power Module
Zui Zone User Interface
(microterminal)
Zui
Other Pms
Master Pm
Zui bus
Zui bus
Zui
Zui
Zui
Zui
The second coding wheel (RS2) selects the tens: 0, 10, 20, 30,
40, 50, 60, 70, 80, 90.
A local bus can include several Power Modules and the same
number of master controllers.
The maximum number of slave Power Modules that can be
associated with a master Power Module is 58:
Cable screening to
be connected to
building earth
Zone
Controller
side
Secondary bus
Bus side
Detail Power
Module side
local bus
Detail Zone
Controller side
local bus
Cable screening to
be connected to
building earth
Not supplied by
Carrier
In all cases one and only one device shall be configured to add
line termination impedance to the bus. This shall generally be
the last device on the bus.
10
Two-pipe
Cooling
Heating
Fan motor
with
changeover
Water valve
Water valve
with
changeover
Water valve
Water valve
PTC electric
heater
with
changeover
Water valve
Water valve
Shielded
Three-speed
electric heater
with
changeover
Water valve
Water valve
Water valve
without
changeover
Water valve
without
changeover
Water valve
PTC electric
heater
Three-speed or
variable speed
without
changeover
Water valve
Shielded
electric heater
Three-speed
Three-speed or
variable speed
Three-speed or
variable speed
Three-speed or
variable speed
Three-speed or
variable speed
Four-pipe
Cooling
Heating
without
changeover
Water valve
Water valve
without
changeover
Water valve
Water valve
without
changeover
Water valve
Water valve
without
changeover
Water valve
Water valve
Additional
heating
Fan motor
Three-speed or
variable speed
PTC electric
heater
Shielded
electric
heater
Water valve
Three-speed or
variable speed
Three-speed
Three-speed or
variable speed
A potentiometer (0 to 100 kOhms) for resetting the setpoint value (wall-mounted thermostat),
11
12
Card
Sensor
Dimensions: 85 x 63 x 23 mm
J1
reference mark
T3 on label
Not supplied
by Carrier
Screening to be connected to
the terminal unit
14
Technical characteristics:
J1
reference mark
T3 on label
15
Technical characteristics:
J1
reference mark
T2 on label
16
Off
Cooling
Fan only
Heating
Air change
Defrost
Room drying
The operating mode is determined by the controller by reference
to the measured temperature relative to the configured
setpoint, or by a forced mode or by an external action (such as
window status, changeover mode, etc.).
3.2.3.1 - How the controller operates in Occupied mode
This mode is used to maintain the comfort conditions required
during periods when the air conditioned zone is occupied. To
achieve this, it keeps the temperature within the dead band,
that is, a given range on either side of the displayed setpoint.
The main control parameters are as follows:
Occupied setpoints,
Maximum value
Occupied setpoint
20C
15C
30C
2.5C
1C
8C
1.5C
0C
6C
Occupied setpoint
configured
Cooling
Fan only
Heating
Air change
Defrost
Room drying
In cooling mode, the chilled water valve output is activated. The
type of control law applied to a variable speed fan is Integrated
Proportional (IP). Fan speed is controlled by phase splitting.
The control law applied to a three-speed fan allows automatic
switching between fan speeds 1, 2 or 3 in relation to ambient
temperature and setpoint.
In fan only mode, the heating and chilled water valve outputs
are disabled.
A variable speed fan delivers the minimum flow rates of cold
and warm air defined in the parameters.
A three-speed fan operates at its minimum speed.
In heating mode, the type of control law applied to the fan is
Integrated Proportional (IP). The heating output is activated.
If additional heating has been configured, it will be used at
maximum capacity if the heat output is not enough to maintain
the temperature within the dead band.
The type of control law applied to a variable speed fan is
Integrated Proportional (IP). Fan speed is controlled by phase
splitting.
The control law applied to a three-speed fan allows automatic
switching between fan speeds 1, 2 or 3 in relation to ambient
temperature and setpoint.
Desired setpoint
Temperature
User
reset
Dead band/2
Dead band/2
17
It provides the air conditioned zone with a rapid air change. This
mode may be cancelled manually at any time, or automatically
after a definable timeout.
While this mode is operating, the fan is activated at maximum
speed (100%) and the cooling valve output is activated.
The defrost and room drying modes take priority over other
operating modes.
Operating
mode
For
Fan
speed
variation
Cooling
2 min
+1
Cooling
3 min
-1
Cooling
At once
Minimum
speed
Heating
2 min
+1
Heating
3 min
-1
Heating
At once
Minimum
speed
Heating
At once
Maximum
speed
SpCont - DBOcc/4
SpCont + DBOcc/4
SpCont + 3/8 DBOcc
SpCont - DBOcc/2
SpCont + DBOcc/2
Temperature
(C)
Time 2
Time 1
Time 3
Key:
SpCont = Occupied Setpoint + User Reset
DBOcc = Occupied Dead Band
Cooling mode
Time 1: Waiting time before authorisation to use fan algorithm in cooling mode
Time 2: Waiting time before authorisation to use fan algorithm in heating mode
Time 3: Waiting time before authorisation to use additional heating
20C
15C
30C
2.5C
14C
Unoccupied setpoint
Configured setpoint
Temperature
Dead band/2
Dead band/2
Cooling
Off
Heating
Defrost
Room drying
In the Off mode, the fan is stopped and the outputs for heating
and cooling are disabled.
In cooling mode, the output for the chilled water valve is
activated.
A variable speed fan delivers the maximum flow rate of cold
air defined in the parameters.
A three-speed fan runs at its maximum speed.
The defrost and room drying modes take priority over other
operating modes.
SpUnocc
e
Temperature
Heating mode
Key:
SpUnocc: Unoccupied Setpoint
DBUnocc: Unoccupied Dead Band
e: Hysteresis 1C
Off mode
Cooling mode
Defrost setpoint
Default value
Minimum value
Maximum value
7C
4C
14C
SpDF + e
SpDF
Temperature
Heating mode
Defrost mode
Key:
SpDf: Defrost Setpoint
e: Hysteresis 1C
20
NOTE: Information received from the water distribution network takes priority over a reading from a temperature sensor.
21
Description
Default
value
Fan type
0 to 1800s
This parameter allows the fan motor
0
command to take place at a different time in
relation to the valve opening command.
0/1/2/3 (0 = none/1 = PTC electric heater/2
= shielded electric heater/3 = water valve)
Heat Type
0 to 1800s
This parameter allows the fan motor
0
command to take place at a different time in
relation to the valve opening command.
0/1/2/3 (0 = none/1 = PTC electric heater/2
= shielded electric heater/3 = water valve)
No/Yes
Defines whether there is a sensor for the
0
Chilled Leaving Water Temperature (CLWT)
on the terminal unit.
HLWT/CHG Sensor
Present
No/Yes
Defines whether there is a sensor for the
0
Hot Leaving Water Temperature (HLWT), or
for changeover (CHG).
8 ASCII characters
Information about the test carried out in the
factor y.
Native Language
22
Parameter
Description
Master Address
Loadshed Enabled
No/Yes
Defines whether load shedding function is authorised.
No
Control Temp
Sensor
-7.0 to 7.0C
Correction applied to the return air or ambient
temperature measurement (reset).
This correction enables a positive or negative reset to
be permanently applied to the room temperature or
return air temperature sensor reading.
0.0
Delta T Control
Select
(Not applicable)
Changeover Enable
0/1 (No/Yes)
Defines authorisation of changeover mode (applies to
two-pipe terminal unit only)
Threshold
Temperature
10 to 40C
The threshold temperature for changeover mode.
Below threshold temperature, the water is treated as
cold and the controller is authorised to operate in
cooling mode.
Above threshold temperature, the water is treated as
hot and the controller is authorised to operate in
heating mode.
18
Enable Delay
0 to 30 min
Delay before authorising additional heating to be
star ted.
Purge Duration
1 to 15 min
Duration of room air renewal mode.
During this period the chilled water valve is activated
and the fan motor is operated at its maximum speed
(100%).
Cooling Minimum
Speed
Heating Minimum
Speed
Cooling Maximum
Speed
Parameter
Description
Default
value
Occupied Setpoint
15.0 to 30.0C
Setpoint for occupied mode
20.0
1.0 to 8.0C
Dead band for occupied mode
2.5
Unoccupied Setpoint
15.0 to 30.0C
Setpoint for unoccupied mode
20.0
2.5 to 14.0C
Dead band for unoccupied mode
10.0
4.0 to 14.0C
Setpoint for defrost mode
7.0
0.0 to 2.0C
Value of setpoint reset step.
The user interface allows the setpoint to be
changed by reset steps. The reset can vary 0.5
from -3 to +3 compared with the setpoint
value. This value is the reset step value
expressed in degrees Celsius.
(Not applicable)
12
(Not applicable)
40
Description
Default value
Device Name
8 ASCII characters
The name of the device concerned
(optional)
Description
24 ASCII characters
Description (optional)
Location
24 ASCII characters
Location (optional)
16 ASCII characters
The last two figures correspond to CSA - SRthe controller version (not
42F22C11
modifiable)
Model Number
20 ASCII characters
(not modifiable)
Serial Number
12 ASCII characters
(not modifiable)
40
Reference Number
24 ASCII characters
(not modifiable)
40
Bus Number
1 to 239
Number of secondar y bus to which 1
the controller is assigned.
Heating Maximum
Speed
Proportional Gain
(variable speed fan)
0.0 to 20.0
IP propor tional gain for variable speed fan.
7.0
Integral Gain
(variable speed fan)
0.0 to 5.0
IP integral gain for variable speed fan.
0.7
Proportional Gain
(shielded electric
heater)
0.0 to 20.0
IP propor tional gain for shielded electric heater.
1.0
Integral Gain
(shielded electric
heater)
0.0 to 5.0
IP integral gain for shielded electric heater.
1.0
0/1 (No/Yes)
Defines authorisation to select fan speed from Zone
User Interface.
0/1 (No/Yes)
Defines authorisation to display ambient temperature
on Zone User Interface.
0/1 (No/Yes)
Defines authorisation to display outdoor ambient
temperature on Zone User Interface.
0/1 (No/Yes)
Defines whether 'window' icon is displayed when
window is open.
Version 1.1
38400
23
Parameter
Description
Re-Alarm Time
0 - 1440 min
Timeout for re-issuing alarms when
they are acknowledged by the BMS.
They will be re-issued at the end of the
0
period specified in this parameter if still
present. If this parameter is set at 0 it
means that no alarms will be re-issued
over the bus after acknowledgement.
Alarm Routing
Override
possible
Occupied
No/Yes
No
Operating Mode
Purge/Off/Fan/Heating/Cooling/Frost/Drying No
Changeover Mode
None/Cool/Heat
Master/Slave Status
None/Master/Slave
Configured status: Master only/Master with No
Slave(s)/Slave
Variable
0-11111111
This parameter defines the device(s)
that will take alarms generated by the
controller into account and
acknowledge them: 1 = authorised, 0 =
not authorised.
11010000
| b7 | b6 | b5 | b4 | b3 | b2 | b1 | b0 |
bit 7 = 1 => Local alarm (e.g. BMS)
bit 6 = 1 => Autodial Gateway
bit 5 = 1 => OTIS Gateway
bit 4 = 1 => Translator
bit 3 to 0 => Reser ved
No/Yes
Defines whether the Alarm Summar y
message is enabled.
If this parameter is YES, it allows a
single alarm message to be generated
Summary Alarm Enable over the secondar y bus, containing a
No
summar y of all the alarms detected.
If this parameter is NO, the number of
alarm messages generated over the
secondar y bus can be the same as the
number of alarms detected.
No
Temperature Status
Space Temperature
Description
Default
value
Time
00.00
Day of Week
(1 to 7)
(1: Monday, 2: Tuesday .... 7: Sunday)
...
Holiday Today
0 or 1
Defines public holidays
Month
1 to 12
Day of Month
1 to 31
Year
0 to 99
(nnn.nC)
This is the temperature readout from the
temperature sensor in the Zone User
Interface or the wall-mounted thermostat,
or from the room temperature sensor. It is
expressed in degrees Celsius.
Yes
(nnn.nC)
This is the temperature readout from the
Return Air Temperature
return air temperature sensor. It is
expressed in degrees Celsius.
Yes
(nnn.nC)
This is the temperature readout from the
chilled water temperature sensor.
Expressed in degrees Celsius.
Yes
HLWT/Changeover
Temp
(nnn.nC)
This is the temperature readout from the
hot water temperature sensor or
changeover temperature sensor.
Expressed in degrees Celsius.
Yes
Outside Air
Temperature
(nnn.nC)
This value is not a control parameter but is
for information only. It may be displayed on
the Zone User Interface microterminal,
depending on the status of configuration
Yes
parameter "Zui OAT Icon". The only way
this value can be written is by overriding
this entr y in the controller. Expressed in
degrees Celsius.
Control Temperature
(nnn.nC)
This is the return air temperature or room
temperature according to the "Control
Temp Sensor" parameter. A correction may
Yes
be applied to this temperature by the
control sensor bias parameter. This
temperature is the temperature to be
controlled. Expressed in degrees Celsius.
Control Point
(nnn.nC)
This is the Occupied setpoint, reset from
the desired value by the user in Occupied
mode. It is the Unoccupied or Defrost
No
setpoint in Unoccupied mode and Defrost
operating mode respectively. Expressed in
degrees Celsius.
(nnn.nC)
This is the Occupied dead band in
Occupied mode. It is the Unoccupied dead No
band in Unoccupied mode. Expressed in
degrees Celsius.
Reset Position
-3 to 3
Number of reset steps from the setpoint
desired by the user.
Reset Value
(n.nC)
Reset value desired by the user, derived
from the product of the "reset position" and No
the value of the "setpoint reset step".
Expressed in degrees Celsius.
If there is a mains power failure, they are lost and will return
to their default values when power is restored.
24
No
Variable
Description
Override
possible
Cooling Status
b7
On/Off
This determines whether the chilled water
valve is activated.
Yes
Heating Output
On/Off
This determines whether the heating output
is activated (hot water valve or electric
heater).
Yes
0 to 100%
Duty cycle for activation of the shielded
electric heater. One cycle equals 5 minutes.
Yes
100% means the heater is activated all the
time. 50% means that the heater is activated
for 2 minutes 30 seconds in every 5 minutes.
Cooling Output
On/Off
This determines whether the additional
heating output is activated (hot water valve
or electric heater).
Yes
b6
b5
b4
b3
b2
b1
b0
Fan Status
Fan Type
Variable/Three Speeds
Fan Mode
Manual/Auto
Fan mode is manual if fan speed is given by
the user from the Zone User Interface and
not by the controller. For the variable speed
No
fan this applies in "Air Renewal" (Purge)
operating mode. For the three-speed fan it
applies when the user selects fan speed 1, 2
or 3.
0/1/2/3
Fan speed on the three-speed fan.
(Stop/Speed 1 (lowest)/Speed 2/Speed 3
(highest))
Yes
0 to 100%
A fan speed of 100% on the variable speed
fan corresponds to the maximum speed of
the fan motor.
The power supplied to the fan motor is then
equal to the available single-phase mains
voltage.
Yes
Zc Status Flags
No
No
Close/Open
Status of star t-stop contact connected to the Yes
controller (closed/open)
Window/Drain Ct Status
Close/Open
Status of window contact and/or drain pan
alarm threshold contact (closed/open)
Yes
No/Yes
Defrost mode active yes/no.
This operating mode can be triggered by
overriding this entry in the controller.
Yes
Loadshed In Effect
No/Yes
Validates the load shedding function.
If Yes, heating outputs of the electric heater
type are disabled.
If No, heating outputs of the electric heater
type are authorised.
Yes
b7
Yes
b6
b5
b4
b3
b2
b1
b0
Variable
Description
Mail Flag
On/Off
Status of lighting output on master Power Module.
On/Off
Power Module 1 Socket Status of controlled output socket on master Power
Module.
Power Module 2 Light
On/Off
Status of lighting output on slave 1 Power Module.
On/Off
Power Module 2 Socket Status of controlled output socket on slave 1 Power
Module.
No/Yes
This value is not a control parameter but is
for information only. It will be displayed on
the Zone User Interface microterminal as a
Yes
small flashing icon in the form of an
envelope if set at Yes. This value can only be
written by overriding this entry in the
controller.
On/Off
Status of lighting output on slave 2 Power Module.
On/Off
Power Module 3 Socket Status of controlled output socket on slave 2 Power
Module.
Power Module 4 Light
On/Off
Status of lighting output on slave 3 Power Module.
On/Off
Power Module 4 Socket Status of controlled output socket on slave 3 Power
Module.
Description
Alarm 1
Alarm 2
Alarm 3
Alarm 4
A slave controller has not received a control temperature from the master
controller for 10 min. This alarm goes away when the slave controller once
again receives a control temperature.
Alarm 5
The water level in the condensate drain pan has reached the alarm
threshold. This alarm goes away when the water level in the condensate
drain pan drops below the alarm threshold again.
Alarm 6
Incorrect chilled water leaving temperature. This alarm goes away when the
temperature measurement is correct once again.
Alarm 7
Incorrect hot water leaving temperature. This alarm goes away when the
temperature measurement is correct once again.
Alarm 8
Alarm 9
3.2.9 - Troubleshooting
The following table lists the main problems that may be met
and how they can be remedied:
26
Symptom
Remedy
Controller in Off
operating mode instead
of room drying
Unexpected controller
operation
1 - Check connections
2 - Check controller address (controller bus number
default is 1)
3 - Check communication speed of controller or Carrier
tool (controller communication speed default is 38400
baud)
4 - In event of defective communication with Carrier tool,
check that TS232/RS485 conver ter is capable of 38400
baud communication
5 - In event of defective communication with Carrier tool,
add line termination impedance over the bus then cancel
it after configuration.
IMPORTANT: The MAESTRO control system is a communication system with the ability to drive a large number of devices.
It is therefore advisable to pay special attention to all connections and the paths of the communication buses around the
system.
3.2.10 - Controller connections
IMPORTANT: A system is provided for maintaining and/or
locking out each electric cable that enters or leaves the
controller. This maintenance system depends on the terminal
unit delivered with the controller. It is described in the selection
and installation manual for each terminal unit.
3.2.10.1 - Controller power supply
The controller is powered from a single-phase mains network
at 230 VAC ( 10%) 50 Hz.
The recommended connection cable for the controller (J7) is
of the type: Earth - Neutral - Line 3 G 1.5 mm2.
It must meet the quality and installation standards of IEC
Recommendation 364 corresponding to Europe HD 384,
France NFC 15 100, UK IEE Wiring Regulation.
Temperature sensors
These sensors do not require special connectors (clip terminals).
27
Secondary bus
The male connector (J9) is used to connect the controller to slave
controllers, to a Floor Manager or to a Building Management
System. The secondary bus (J9) is connected using a 3-pin
female WIELAND connector - Ref. 25 320 3353-0.
Local bus
The male connector (J5) is used to connect a Power Module.
Zone Controller
Cable shielding to be
J5 local connected to terminal unit
side
bus
casing
Not supplied
by Carrier
local bus
Zone Controller
side
J5 local bus
Key:
Blanc = White
Bleu = Blue
Jaune = Yellow
NOTES: The voltage on the outputs for fan (J3), hot water
valve (J4A) and chilled water valve (J4B) is always the
same as the single-phase mains voltage (regardless of their
status) whenever they are not assigned a load (e.g. fan, valve
servomotor).
An operating controller or commands from the Zone User
Interface, Power Module, Floor Manager or master controller
(in the case of a slave controller) are used to power these
outputs up or down.
The voltage on the outputs for fan, hot water valve,
chilled water valve and additional heating is always the
same as the single-phase mains voltage if they are not
connected, regardless of the type of command received.
3.2.11 - Technical characteristics
3.2.11.1 - Electrical characteristics
The Zc controller takes its power from the low tension 230 VAC
mains supply.
Inputs
4 holes 6
It can be connected:
Control functions;
Control functions;
J5 local bus
Key:
Blanc = White
Bleu = Blue
Jaune = Yellow
31
Dimensions: 135 x 67 x 27 mm
32
Wall-mounted thermostat
Dimensions: 80 x 80 x 44 mm
J1 analogue inputs
3.4.1.1 - Outputs
The following apply to the external Power Module:
There is also a window blind command output (FRANCIAFLEX brand ) with a 24 VDC power supply.
3.4.1.2 - Inputs
An external Power Module can detect when a window is open,
as can the controller. The window status is transmitted to its
associated controller which then determines which operating
mode to apply.
The direction in which the window contact works can be
defined by parameter:
34
35
There is another power outlet capable of providing singlephase power for an additional lighting source, having
either a remotely controlled or conventional dimmer (see
chapter 3.4.8.1 - Electrical characteristics).
3.4.2.2 - Inputs
An internal Power Module has neither logical nor analogue
inputs.
Pin 1: signal
Pin 2: 0 V
Pin 3: signal +
The Zui bus connector on the Zone User Interface has four
pins:
Pin 1: signal +
Pin 2: 0 V
Pin 3: signal
Pin 4: VEE (positive (+) terminal of the user interface
power supply)
Description
Default
value
Light
0/1 (Absent/Present)
Declares the presence or absence of
lighting connected to the Power Module
Description
Default value
Bus Number
1 to 128
This must be the same as the
address of the master controller to
which the Power Module is
attached (coding wheels)
Element Number
1 to 99
Bus element number (for
explanation see below)
Baud Rate
19200
Communication speed (not
modifiable)
19200
Priority
2
2
Communication protocol parameter
(not modifiable)
16 characters
Software version (not modifiable)
Name
8 characters
Name of device (optional)
Description
24 characters
Description of device (optional)
Location
24 characters
Physical location of device
(optional)
CSA-SR-xxxxxx
Blind Inclination
Socket Control
0/1/2
(Absence of any controlled output
connected to the Power Module.
/Presence of a controlled output
1
connected to the Power Module.
/Presence of a controlled output
connected to the Power Module and to a
remotely controlled dimmer.)
Zui Led On
0/1 (No/Yes)
Authorisation for back-lighting of the
translucent ON/OFF button on the Zone
User Interface
0/1/2/3
If the Power Module is the master, this
parameter represents the number of
slaves that the Zone User Interface
connected to it can control.
If the Power Module is a slave, this
parameter is 0.
Attached Slave
Window Contact
0/1
(Window contact Normally Open/Window 0
contact Normally Closed)
5 to 99
Parameter
Description
Default
value
0/1 (No/Yes)
0
The "End Termination Line" variable is
read-only. It results from reading the
micro-switch located under the
transparent window on the terminal block.
If this micro-switch is in the ON position it
adds an impedance of 120 ohms on the
bus.
Rotary Element
Address
0 to 99
*
The "Power Module Address" variable is
read-only. This parameter corresponds to
the Power Module address given with the
aid of the two coding wheels that can be
seen through the transparent window on
the terminal block.
37
3.4.6 - Troubleshooting
The following table lists the main problems that may be met
and how they can be remedied:
Symptom
Remedy
1 - Faulty PROM
1 - Check connections.
2 - Check Power Module address.
3 - In event of defective communication
with Carrier tool, check that RS232/RS485
conver ter is capable of 19200 baud
communication.
4 - In event of defective communication
with Carrier tool, add line termination
impedance over the bus then cancel it
after configuration.
Zone Controller
side
J5 local
bus
Cable shielding to be
connected to terminal unit
casing
Not supplied
by Carrier
J7 local
bus
Key:
Blanc = White
Bleu = Blue
Jaune = Yellow
39
Lighting output (J4 - J5) 230 VAC (10%) - 1.3 A - 50 Hz 300 Watts resistive incandescent distributed over two
outputs.
(Qualified lighting: REGIANI 6416 non-compensated.
For any other type of lighting please contact Carrier as
distributors).
4 holes 6
All of these functions are accessible locally by using the builtin screen and keypad.
Fm address 10
Secondary bus
Master Zc
address = 1
Slave Zc
address = 8
Master Zc
address = 3
Wall-mounted
thermostat
Zone 1
ZUI
Zone 2
ZUI
Key:
Fm
Floor Manager
Zc
Zone Controller
Pm
Power Module
Zui
Zone User Interface
(microterminal)
Zone 1
Zone 1 is air conditioned by two terminal units of the ICM
type (Individual Comfort Module). They are two-pipe systems
with changeover + additional PTC electric heater. The fan is
variable speed. A condensate drain pan level detector contact is
installed on the ICMs. Zone 1 is a conference room.
Zone 2
Zone 2 is air conditioned by one two-pipe terminal unit with
changeover + additional PTC electric heater. The fan is the
independent three-speed type. Zone 2 is an office.
41
Zc (Address 1)
0 (variable
speed)
Zone 2
Zc (Address 8)
0 (variable
speed)
Parameter
Zc (Address 1)
Zone 2
Zc (Address 8)
Zc (Address 3)
Occupied Setpoint
21.0C
21.0C
21.0C
2.5C
2.5C
2.5C
1 (Three speed)
Unoccupied Setpoint
18.0C
18.0C
18.0C
4.0C
4.0C
4.0C
Zc (Address 3)
Heat Type
0 (None)
0 (None)
0 (None)
12.0C
12.0C
12.0C
0.2C
0.2C
0.2C
1 (PTC electric
heater)
1 (PTC electric
heater)
1 (PTC electric
heater)
12C
12C
12C
40C
40C
40C
0 (No)
0 (No)
0 (No)
HLWT/CHG Sensor
Present
1 (Yes)
1 (Yes)
1 (Yes)
Window/Drain Pan
Type
2 (Condensate
drain pan
contact NO)
2 (Condensate
drain pan
contact NO)
0 (Window
contact NO)
8 ASCII
characters
8 ASCII
characters
8 ASCII
characters
Native Language
0 (English)
0 (English)
0 (English)
Zone 2
Parameter
Zc (Address 1)
Zc (Address 8)
Master Address
2 (Zone User
Interface)
2 (Zone User
Interface)
Zone 1
Zone 2
Parameter
Zc (Address 1)
Zc (Address 8)
Zc (Address 3)
Device Name
(optional)
(optional)
(optional)
Description
(optional)
(optional)
(optional)
Location
(optional)
(optional)
(optional)
(not modifiable)
(not modifiable)
(not modifiable)
Model Number
(not modifiable)
(not modifiable)
(not modifiable)
Serial Number
(not modifiable)
(not modifiable)
(not modifiable)
Reference Number
(not modifiable)
(not modifiable)
(not modifiable)
Bus Number
10
10
10
1 (wall-mounted
thermostat)
38400 baud
38400 baud
38400 baud
Zc (Address 3)
0 (Never)
0 (Never)
0 (Never)
Loadshed Enabled
No
No
No
0 (Room
temperature sensor
in Zone User
Interface)
0 (Room
temperature
sensor in wallmounted
thermostat)
0.0C
0.0C
0.0C
0 (No)
0 (No)
0 (No)
Changeover Enable
1 (Yes)
1 (Yes)
1 (Yes)
Threshold Temperature
18C
18C
18C
Enable Delay
10 min
10 min
10 min
Purge Duration
6 min
6 min
6 min
30%
30%
30%
30%
30%
30%
90%
90%
90%
70%
70%
70%
Proportional Gain
(variable fan speed)
7.0
7.0
7.0
0.7
0.7
0.7
Proportional Gain
(shielded electric heater)
6.0 (not
significant)
0.6 (not
significant)
1 (Yes)
1 (Yes)
1 (Yes) (not
significant)
1 (Yes)
1 (Yes)
1 (Yes) (not
significant)
0 (No)
0 (No)
0 (No) (not
significant)
1 (Yes)
1 (Yes)
1 (Yes) (not
significant)
42
Zone 2
Parameter
Zc (Address 1)
Zc (Address 8)
Zc (Address 3)
Re-Alarm Time
15 min
15 min
15 min
Alarm Routing
1000 0000
1000 0000
1000 0000
Yes
Yes
Zone 2
Parameter
Zc (Address 1)
Zc (Address 8)
Zc (Address 3)
Time
(11 :30)
(11 :30)
(11 :30)
Day of Week
(1) (Monday)
(1) (Monday)
(1) (Monday)
Holiday Today
Month
Day of Month
11
11
11
Year
99
99
99
Secondary bus
Master Zc
address = 1
Master Zc
address = 3
Slave Zc
address = 8
Local bus
Master Pm
address = 59
Slave Pm
address = 6
Master Pm
address = 5
Zui bus
Zui bus
Slave Pm
address = 54
ZUI
Key:
Fm
Zc
Pm
Zui
ZUI
Zone 2
Zone 1
ZUI
Floor Manager
Zone Controller
Power Module
Zone User Interface (microterminal)
Zone 1
Zone 1 is air conditioned by two terminal units of the ATM
type (Air Treatment Module). They are two-pipe systems
without changeover + PTC electric heater.
Zone 2
Parameter
Zc (Address 1)
Fan type
0
0
(variable speed) (variable
speed)
1
(three-speed)
Zone 2
Zone 2 is air conditioned by one two-pipe Fan Coil terminal
unit without changeover + shielded electric heater with return
air temperature sensor.
Heat Type
1 (PTC electric
heater)
1 (PTC electric
heater)
2 (shielded
electric heater)
Zc (Address 8) Zc (Address 3)
0 (None)
0 (None)
0 (None)
0 (No)
0 (No)
0 (No)
HLWT/CHG Sensor
Present
0 (No)
0 (No)
0 (No)
0 (window
contact NO)
0 (window
contact NO)
8 ASCII
characters
8 ASCII
characters
8 ASCII
characters
Native Language
0 (English)
0 (English)
0 (English)
43
Zone 2
Zone 2
Parameter
Zc (Address 1)
Zc (Address 8)
Zc (Address 3)
Parameter
Zc (Address 1)
Zc (Address 8)
Zc (Address 3)
Master Address
Device Name
(optional)
(optional)
(optional)
0 (Power Module)
Description
(optional)
(optional)
(optional)
0 (Never)
0 (Never)
0 (Never)
Location
(optional)
(optional)
(optional)
(not modifiable)
(not modifiable)
(not modifiable)
Model Number
(not modifiable)
(not modifiable)
(not modifiable)
Loadshed Enabled
Yes
Yes
Yes
Control Temp
Sensor
0 (Room
temperature
sensor in Zone
User Interface)
1 (Return air
temperature
sensor in terminal
unit)
Serial Number
(not modifiable)
(not modifiable)
(not modifiable)
Reference Number
(not modifiable)
(not modifiable)
(not modifiable)
0.0C
0.0C
0.0C
Bus Number
Delta T Control
Select
0 (No)
0 (No)
0 (No)
38400 baud
38400 baud
38400 baud
Changeover Enable
0 (No)
0 (No)
0 (No)
Threshold
Temperature
18C (not
significant)
18C (not
significant)
18C (not
significant)
Enable Delay
4 min (not
significant)
4 min (not
significant)
4 min (not
significant)
Purge Duration
6 min
6 min
6 min (not
significant)
Cooling Minimum
Speed
30%
30%
30% (not
significant)
Heating Minimum
Speed
30%
30%
30% (not
significant)
Cooling Maximum
Speed
90%
90%
90% (not
significant)
Heating Maximum
Speed
70%
70%
70% (not
significant)
Proportional Gain
(variable speed fan)
7.0
7.0
7.0 (not
significant)
Integral Gain
(variable speed fan)
0.7
0.7
0.7 (not
significant)
Proportional Gain
(shielded electric
heater)
6.0 (not
significant)
6.0 (not
significant)
6.0
Integral Gain
(shielded electric
heater)
0.6 (not
significant)
0.6 (not
significant)
0.6
1 (Yes)
1 (Yes)
1 (Yes)
1 (Yes)
1 (Yes)
1 (Yes)
0 (No)
0 (No)
0 (No)
1 (Yes)
1 (Yes)
1 (Yes)
Zone 2
Parameter
Zc (Address 1)
Zc (Address 8)
Zc (Address 3)
Occupied Setpoint
21.0C
21.0C
21.0C
2.5C
2.5C
2.5C
Unoccupied Setpoint
18.0C
18.0C
18.0C
4.0C
4.0C
12.0C
12.0C
12.0C
0.2C
0.2C
0.2C
12C
12C
12C
40C
40C
40C
44
Zone 2
Parameter
Zc (Address 1)
Zc (Address 8)
Zc (Address 3)
Re-Alarm Time
0 min
0 min
0 min
Alarm Routing
No
No
Zone 2
Parameter
Zc (Address 1)
Zc (Address 8)
Zc (Address 3)
Time
(11 :30)
(11 :30)
(11 :30
Day of Week
(1) (Monday)
(1) (Monday)
(1) (Monday)
Holiday Today
Month
Day of Month
11
11
11
Year
99
99
99
Zone 1
Zone 2
Zone 1
Zone 2
Parameter
Pm 5
Pm 54
Pm 6
Pm 59
Parameter
Pm 5
Pm 54
Pm 6
Pm 59
Bus Number
Light
1 (Present)
1 (Present)
1 (Present)
1 (Present)
Element
Number
Blind Move
Up/Down
0 (Not
authorised)
Baud Rate
19200 (not
modifiable)
19200 (not
modifiable)
19200 (not
modifiable)
19200 (not
modifiable)
Blind
Inclination
0 (Not
authorised)
Priority
2 (not
modifiable)
2 (not
modifiable)
2 (not
modifiable)
2 (not
modifiable)
0 (Absent)
0 (Absent)
0 (Absent)
Zui Led On
1 (Yes)
1 (Yes)
1 (Yes)
Attached Slave 2
1 (Yes)
16 characters
(not
modifiable)
16 characters
(not
modifiable)
16 characters
(not
modifiable)
Name
(optional)
(optional)
(optional)
(optional)
Window
Contact
1 (Window
contact NC)
1 (Window
contact NC)
1 (Window
contact NC)
0 (Window
contact NO)
Description
(optional)
(optional)
(optional)
(optional)
1 (Yes)
1 (Yes)
1 (Yes)
Location
(optional)
(optional)
(optional)
(optional)
Window Icon
For Purge
0 (Not
significant)
45
46
47