7SA611 V4_6 Var_prn

SIMATIC

TLD / NJP Temp / 7SA611 V4.6


Var/7SA611 V04.62.01

30.12.14 13:10:26

TLD / NJP Temp / 7SA611 V4.6 Var


MLFB:
7SA61115AB327PR4---------------Parameter set version:
V04.61.06
Device path: C:\Siemens\Digsi4\D4PROJ\Tld\P7DI\GV\ST\00000053
Author:
Creation date:
30.12.14 12:29:23
Last modified:
30.12.14 12:29:47
Operating mode:
Online
Comment:
Setting values in:
Secondary value description

PRINT - CONTENTS
1
2
2.1
3
3.1
3.2
3.3
4
4.1
5
5.1
5.2
5.3
5.4
5.5
5.6
5.7
5.8
5.9
5.10
5.11
5.12
5.13
5.14
5.15
5.16
5.17
5.18
5.19
5.20
5.21
5.22
5.23

Device Configuration .................................................................................................................................................................3


General Device Settings ...........................................................................................................................................................4
Group Device ............................................................................................................................................................................4
Power System Data 1 ...............................................................................................................................................................5
Group Power System Data 1; Group Transformers ..................................................................................................................
5
Group Power System Data 1; Group Power System .................................................................................................................
5
Group Power System Data 1; Group Breaker ...........................................................................................................................
6
Oscillographic Fault Records ....................................................................................................................................................7
Group Oscillographic Fault Records .........................................................................................................................................
7
Settings groups .........................................................................................................................................................................8
Group Power System Data 2; Group Power System .................................................................................................................
8
Group Power System Data 2; Group Line Status ......................................................................................................................
8
Group Power System Data 2; Group Trip 1-/3-pole ..................................................................................................................
9
Group Distance protection, general settings; Group General ...................................................................................................
9
Group Distance protection, general settings; Group Earth faults ..............................................................................................
9
Group Distance protection, general settings; Group Time Delays ..........................................................................................
10
Group Distance zones (quadrilateral); Group Zone Z1 ...........................................................................................................
10
Group Distance zones (quadrilateral); Group Zone Z1B-exten. ..............................................................................................
10
Group Distance zones (quadrilateral); Group Zone Z2 ...........................................................................................................
11
Group Distance zones (quadrilateral); Group Zone Z3 ...........................................................................................................
11
Group Distance zones (quadrilateral); Group Zone Z4 ...........................................................................................................
11
Group Distance zones (quadrilateral); Group Zone Z5 ...........................................................................................................
12
Group Power Swing ................................................................................................................................................................12
Group Teleprotection for Distance prot. ..................................................................................................................................
12
Group DTT Direct Transfer Trip ..............................................................................................................................................12
Group Instantaneous HighSpeed SOTF Overcurrent .............................................................................................................
13
Group Backup overcurrent; Group General ............................................................................................................................
13
Group Backup overcurrent; Group I>> ....................................................................................................................................
13
Group Backup overcurrent; Group I> ......................................................................................................................................
14
Group Backup overcurrent; Group Inverse .............................................................................................................................
14
Group Backup overcurrent; Group I - STUB ............................................................................................................................
14
Group Measurement Supervision; Group Balance / Summ. ...................................................................................................
15
Group Measurement Supervision; Group Fuse Fail. Mon. ......................................................................................................
15
Page 1 of 23

7SA611 V4_6 Var_prn

SIMATIC
5.25
5.26
5.27
5.28
5.29
5.30
5.31
5.32
5.33
5.34
5.35
5.36
5.37
5.38
5.39
5.40
5.41
5.42
5.43
6

TLD / NJP Temp / 7SA611 V4.6


Var/7SA611 V04.62.01

30.12.14 13:10:26

Group Measurement Supervision; Group Load Angle ............................................................................................................


16
Group Teleprotection for Earth fault overcurr. .........................................................................................................................
16
Group Automatic Reclosure; Group General ..........................................................................................................................
16
Group Automatic Reclosure; Group 1st AR-cyle .....................................................................................................................
17
Group Automatic Reclosure; Group 3pTRIP/DLC/RDT ..........................................................................................................
17
Group Automatic Reclosure; Group Start AR with.. ................................................................................................................
17
Group Synchronism and Voltage Check; Group General .......................................................................................................
18
Group Synchronism and Voltage Check; Group with AR ........................................................................................................
18
Group Synchronism and Voltage Check; Group Man.Close+CNTRL
.....................................................................................
19
Group Voltage Protection; Group U> Phase-Earth .................................................................................................................
19
Group Voltage Protection; Group U> Phase-Phase ................................................................................................................
19
Group Voltage Protection; Group 3U0> or Ux> .......................................................................................................................
20
Group Voltage Protection; Group U> Postive Seq. .................................................................................................................
20
Group Voltage Protection; Group U> Negative Seq ................................................................................................................
20
Group Voltage Protection; Group U< Phase-Earth .................................................................................................................
21
Group Voltage Protection; Group U< Phase-Phase ................................................................................................................
21
Group Voltage Protection; Group U< Postive Seq. .................................................................................................................
21
Group Fault Locator ................................................................................................................................................................22
Group Thermal Overload ........................................................................................................................................................22
Time Synchronization ..............................................................................................................................................................23

Page 2 of 23

7SA611 V4_6 Var_prn


Device Configuration
TLD / NJP Temp / 7SA611 V4.6
Var/7SA611 V04.62.01

SIMATIC

30.12.14 13:10:26

Device Configuration

1
No.

Function

Scope

0103 Setting Group Change Option

Disabled

0110 Trip mode

1-/3pole

0114 Distance protection pickup program

Z< (quadrilateral)

0120 Power Swing detection

Enabled

0121 Teleprotection for Distance prot.

PUTT (acceleration with Pickup)

0122 DTT Direct Transfer Trip

Enabled

0124 Instantaneous HighSpeed SOTF Overcurrent

Enabled

0125 Weak Infeed (Trip and/or Echo)

Disabled

0126 Backup overcurrent

Time Overcurrent Curve IEC

0131 Earth fault overcurrent

Disabled

0132 Teleprotection for Earth fault overcurr.

Directional Comparison Pickup

0133 Auto-Reclose Function

1 AR-cycle

0134 Auto-Reclose control mode

with Trip and Action time

0135 Synchronism and Voltage Check

Enabled

0136 Over / Underfrequency Protection

Disabled

0137 Under / Overvoltage Protection

Enabled

0138 Fault Locator

Enabled

0139 Breaker Failure Protection

Disabled

0140 Trip Circuit Supervision

Disabled

0142 Thermal overload protection

Enabled

Page 3 of 23

7SA611 V4_6 Var_prn


General Device Settings
TLD / NJP Temp / 7SA611 V4.6
Var/7SA611 V04.62.01

SIMATIC
2

General Device Settings

2.1

Group Device

30.12.14 13:10:26

Group Device
No.

Settings

Value

Group

0610 Fault Display on LED / LCD

Display Targets on every Pickup

All

0640 Start image Default Display

image 1

All

Page 4 of 23

7SA611 V4_6 Var_prn


Power System Data 1
TLD / NJP Temp / 7SA611 V4.6
Var/7SA611 V04.62.01

SIMATIC
3

Power System Data 1

3.1

Group Power System Data 1; Group Transformers

30.12.14 13:10:26

Group Power System Data 1; Group Transformers


No.

Settings

Value

Group

0201

CT Starpoint

towards Line

All

0203

Rated Primary Voltage

220.0 kV

All

0204

Rated Secondary Voltage (Ph-Ph)

110 V

All

0205

CT Rated Primary Current

500 A

All

0206

CT Rated Secondary Current

1A

All

0210

U4 voltage transformer is

not connected All

0211

Matching ratio Phase-VT To Open-Delta-VT

1.73

All

0212

VT connection for Usy2

L1-L2

All

0214A Angle adjustment Usy2-Usy1

All

0215

Matching ratio Usy1 / Usy2

1.00

All

0220

I4 current transformer is

not connected All

0221

Matching ratio I4/Iph for CT's

1.000

3.2

Group Power System Data 1; Group Power System

All

Group Power System Data 1; Group Power System


No.

Settings

Value

Group

0207 System Starpoint is

Solid Earthed

All

0230 Rated Frequency

50 Hz

All

0235 Phase Sequence

L1 L2 L3

All

0236 Distance measurement unit

km

All

0237 Setting format for zero seq.comp. format

Zero seq. comp. factor K0 and angle(K0)

All

Page 5 of 23

7SA611 V4_6 Var_prn


Group Power System Data 1; Group Breaker
TLD / NJP Temp / 7SA611 V4.6
Var/7SA611 V04.62.01

SIMATIC
3.3

30.12.14 13:10:26

Group Power System Data 1; Group Breaker

Group Power System Data 1; Group Breaker


No.
0239

Settings
Closing (operating) time of CB

Value

Group

0.09 sec All

0240A Minimum TRIP Command Duration

0.10 sec All

0241A Maximum Close Command Duration

0.30 sec All

0242

1.00 sec All

Dead Time for CB test-autoreclosure

Page 6 of 23

7SA611 V4_6 Var_prn


Oscillographic Fault Records
TLD / NJP Temp / 7SA611 V4.6
Var/7SA611 V04.62.01

SIMATIC
4

Oscillographic Fault Records

4.1

Group Oscillographic Fault Records

30.12.14 13:10:26

Group Oscillographic Fault Records


No.

Settings

Value

Group

0402A Waveform Capture

Save with Pickup All

0403A Scope of Waveform Data

Fault event

All

0410

Max. length of a Waveform Capture Record

2.00 sec

All

0411

Captured Waveform Prior to Trigger

0.25 sec

All

0412

Captured Waveform after Event

0.10 sec

All

0415

Capture Time via Binary Input

0.50 sec

All

Page 7 of 23

7SA611 V4_6 Var_prn


Settings groups
TLD / NJP Temp / 7SA611 V4.6
Var/7SA611 V04.62.01

SIMATIC
5

Settings groups

5.1

Group Power System Data 2; Group Power System

30.12.14 13:10:26

Group Power System Data 2; Group Power System


No.

Settings

Value

Group

1103 Measurement: Full Scale Voltage (100%)

220.0 kV

1104 Measurement: Full Scale Current (100%)

500 A

1105 Line Angle

85

1211 Angle of inclination, distance charact.

85

1107 P,Q operational measured values sign

not reversed

1110 x' - Line Reactance per length unit

0.0830 Ohm / km A

1111 Line Length

80.8 km

1120 Zero seq. comp. factor K0 for zone Z1

0.736

1121 Zero seq. comp. angle for zone Z1

-13.17

1122 Zero seq.comp.factor K0,higher zones >Z1

0.736

1123 Zero seq. comp. angle, higher zones >Z1

-13.17

5.2

Group Power System Data 2; Group Line Status

Group Power System Data 2; Group Line Status


No.

Settings

Value

Group

1130A Pole Open Current Threshold

0.10 A

1131A Pole Open Voltage Threshold

30 V

1132A Seal-in Time after ALL closures

0.10 sec

1133A minimal time for line open before SOTF

0.10 sec

1134

Recognition of Line Closures with

Current OR Voltage or Manual close BI

1135

RESET of Trip Command

with CBaux open AND I < PoleOpenCurrent

1136

open pole detector

OFF

1140A CT Saturation Threshold

40.0 A

1150A Seal-in Time after MANUAL closures

0.30 sec

1151

Manual CLOSE COMMAND generation

NO

1152

MANUAL Closure Impulse after CONTROL

<none>

All

Page 8 of 23

7SA611 V4_6 Var_prn


Group Power System Data 2; Group Trip 1-/3-pole
TLD / NJP Temp / 7SA611 V4.6
Var/7SA611 V04.62.01

SIMATIC
5.3

30.12.14 13:10:26

Group Power System Data 2; Group Trip 1-/3-pole

Group Power System Data 2; Group Trip 1-/3-pole


No.
1155

Settings
3 pole coupling

Group

with Trip A

1156A Trip type with 2phase faults

5.4

Value

3pole

Group Distance protection, general settings; Group General

Group Distance protection, general settings; Group General


No.

Settings

Value

Group

1201

Distance protection

ON

1202

Phase Current threshold for dist. meas.

0.10 A

1211

Angle of inclination, distance charact.

85

1208

Series compensated line

NO

1232

Instantaneous trip after SwitchOnToFault

with Pickup (non-directional)

1241

R load, minimum Load Impedance (ph-e)

19.410 Ohm

1242

PHI load, maximum Load Angle (ph-e)

56

1243

R load, minimum Load Impedance (ph-ph)

34.620 Ohm

1244

PHI load, maximum Load Angle (ph-ph)

56

1317A Single pole trip for faults in Z2

YES

1357

Z1B enabled before 1st AR (int. or ext.)

NO

5.5

Group Distance protection, general settings; Group Earth faults

Group Distance protection, general settings; Group Earth faults


No.

Settings

Value

Group

1203

3I0 threshold for neutral current pickup

0.10 A

1204

3U0 threshold zero seq. voltage pickup

10 V

1207A 3I0>-pickup-stabilisation (3I0> /Iphmax)

0.10

1209A criterion of earth fault recognition

3I0> OR 3U0> A

1221A Loop selection with 2Ph-E faults

all loops

Page 9 of 23

7SA611 V4_6 Var_prn


Group Distance protection, general settings; Group Time Delays
TLD / NJP Temp / 7SA611 V4.6
Var/7SA611 V04.62.01
SIMATIC
5.6

30.12.14 13:10:26

Group Distance protection, general settings; Group Time Delays

Group Distance protection, general settings; Group Time Delays


No.

Settings

Value

Group

1210 Condition for zone timer start

with distance pickup A

1305 T1-1phase, delay for single phase faults

0.00 sec

1306 T1multi-ph, delay for multi phase faults

0.00 sec

1315 T2-1phase, delay for single phase faults

0.40 sec

1316 T2multi-ph, delay for multi phase faults

0.40 sec

1325 T3 delay

0.80 sec

1335 T4 delay

1.20 sec

1345 T5 delay

4.00 sec

1355 T1B-1phase, delay for single ph. faults

0.00 sec

1356 T1B-multi-ph, delay for multi ph. faults

0.00 sec

5.7

Group Distance zones (quadrilateral); Group Zone Z1

Group Distance zones (quadrilateral); Group Zone Z1


No.

Settings

Value

Group

1301 Operating mode Z1

Forward

1302 R(Z1), Resistance for ph-ph-faults

2.982 Ohm A

1303 X(Z1), Reactance

5.365 Ohm A

1304 RE(Z1), Resistance for ph-e faults

6.721 Ohm A

1305 T1-1phase, delay for single phase faults

0.00 sec

1306 T1multi-ph, delay for multi phase faults

0.00 sec

1307 Zone Reduction Angle (load compensation)

5.8

Group Distance zones (quadrilateral); Group Zone Z1B-exten.

Group Distance zones (quadrilateral); Group Zone Z1B-exten.


No.

Settings

Value

Group

1351 Operating mode Z1B (overrreach zone)

Forward

1352 R(Z1B), Resistance for ph-ph-faults

2.982 Ohm A

1353 X(Z1B), Reactance

8.048 Ohm A

1354 RE(Z1B), Resistance for ph-e faults

6.721 Ohm A

1355 T1B-1phase, delay for single ph. faults

0.00 sec

1356 T1B-multi-ph, delay for multi ph. faults

0.00 sec

1357 Z1B enabled before 1st AR (int. or ext.)

NO

A
Page 10 of 23

7SA611 V4_6 Var_prn


Group Distance zones (quadrilateral); Group Zone Z1B-exten.
TLD / NJP Temp / 7SA611 V4.6
Var/7SA611 V04.62.01
SIMATIC

5.9

30.12.14 13:10:26

Group Distance zones (quadrilateral); Group Zone Z2

Group Distance zones (quadrilateral); Group Zone Z2


No.

Settings

Value

Group

1311

Operating mode Z2

Forward

1312

R(Z2), Resistance for ph-ph-faults

3.729 Ohm

1313

X(Z2), Reactance

10.364 Ohm A

1314

RE(Z2), Resistance for ph-e faults

9.932 Ohm

1315

T2-1phase, delay for single phase faults

0.40 sec

1316

T2multi-ph, delay for multi phase faults

0.40 sec

YES

1317A Single pole trip for faults in Z2

5.10

Group Distance zones (quadrilateral); Group Zone Z3

Group Distance zones (quadrilateral); Group Zone Z3


No.

Settings

Value

Group

1321 Operating mode Z3

Forward

1322 R(Z3), Resistance for ph-ph-faults

4.236 Ohm

1323 X(Z3), Reactance

12.680 Ohm A

1324 RE(Z3), Resistance for ph-e faults

11.032 Ohm A

1325 T3 delay

0.80 sec

5.11

Group Distance zones (quadrilateral); Group Zone Z4

Group Distance zones (quadrilateral); Group Zone Z4


No.

Settings

Value

Group

1331 Operating mode Z4

Reverse

1332 R(Z4), Resistance for ph-ph-faults

0.120 Ohm A

1333 X(Z4), Reactance

1.342 Ohm A

1334 RE(Z4), Resistance for ph-e faults

1.056 Ohm A

1335 T4 delay

1.20 sec

Page 11 of 23

7SA611 V4_6 Var_prn


Group Distance zones (quadrilateral); Group Zone Z5
TLD / NJP Temp / 7SA611 V4.6
Var/7SA611 V04.62.01
SIMATIC
5.12

30.12.14 13:10:26

Group Distance zones (quadrilateral); Group Zone Z5

Group Distance zones (quadrilateral); Group Zone Z5


No.

Settings

Value

Group

1341 Operating mode Z5

Inactive

1342 R(Z5), Resistance for ph-ph-faults

6.000 Ohm A

1343 X(Z5)+, Reactance for Forward direction

6.000 Ohm A

1344 RE(Z5), Resistance for ph-e faults

6.000 Ohm A

1345 T5 delay

4.00 sec

1346 X(Z5)-, Reactance for Reverse direction

2.000 Ohm A

5.13

Group Power Swing

Group Power Swing


No.

Settings

Value

Group

2002 Power Swing Operating mode

Z2 and higher blocked

2006 Power swing trip

NO

2007 Trip delay after Power Swing Blocking

0.80 sec

5.14

Group Teleprotection for Distance prot.

Group Teleprotection for Distance prot.


No.

Settings

Value

Group

2101

Teleprotection for Distance protection

ON

2102

Type of Line

Two Terminals A

2103A Time for send signal prolongation

5.15

0.05 sec

A
A

Group DTT Direct Transfer Trip

Group DTT Direct Transfer Trip


No.

Settings

Value

Group

2201 Direct Transfer Trip (DTT)

ON

2202 Trip Time Delay

0.01 sec A

Page 12 of 23

7SA611 V4_6 Var_prn


Group DTT Direct Transfer Trip
TLD / NJP Temp / 7SA611 V4.6
Var/7SA611 V04.62.01

SIMATIC

5.16

30.12.14 13:10:26

Group Instantaneous HighSpeed SOTF Overcurrent

Group Instantaneous HighSpeed SOTF Overcurrent


No.

Settings

Value Group

2401 Inst. High Speed SOTF-O/C is

ON

2404 I>>> Pickup

2.50 A A

5.17

Group Backup overcurrent; Group General

Group Backup overcurrent; Group General


No.

Settings

Value

Group

2601 Operating mode

ON:only active with Loss of VT sec. cir.

2680 Trip time delay after SOTF

0.00 sec

5.18

Group Backup overcurrent; Group I>>

Group Backup overcurrent; Group I>>


No.

Settings

Value

Group

2610 Iph>> Pickup

2.30 A

2611 T Iph>> Time delay

0.00 sec A

2612 3I0>> Pickup

0.76 A

2613 T 3I0>> Time delay

0.06 sec A

2614 Instantaneous trip via Teleprot./BI

YES

2615 Instantaneous trip after SwitchOnToFault

YES

Page 13 of 23

7SA611 V4_6 Var_prn


Group Backup overcurrent; Group I>
TLD / NJP Temp / 7SA611 V4.6
Var/7SA611 V04.62.01

SIMATIC
5.19

30.12.14 13:10:26

Group Backup overcurrent; Group I>

Group Backup overcurrent; Group I>


No.

Settings

Value

Group

2620 Iph> Pickup

2.30 A

2621 T Iph> Time delay

0.00 sec A

2622 3I0> Pickup

0.76 A

2623 T 3I0> Time delay

0.06 sec A

2624 Instantaneous trip via Teleprot./BI

YES

2625 Instantaneous trip after SwitchOnToFault

YES

5.20

A
A

Group Backup overcurrent; Group Inverse

Group Backup overcurrent; Group Inverse


No.

Settings

Value

Group

2640 Ip> Pickup

0.88 A

2642 T Ip Time Dial

0.10 sec

2646 T Ip Additional Time Delay

0.00 sec

2650 3I0p Pickup

0.07 A

2652 T 3I0p Time Dial

0.10 sec

2656 T 3I0p Additional Time Delay

0.00 sec

2660 IEC Curve

Normal Inverse A

2670 Instantaneous trip via Teleprot./BI

YES

2671 Instantaneous trip after SwitchOnToFault

YES

5.21

Group Backup overcurrent; Group I - STUB

Group Backup overcurrent; Group I - STUB


No.

Settings

Value

Group

2630 Iph> STUB Pickup

4.00 A

2631 T Iph STUB Time delay

30.00 sec A

2632 3I0> STUB Pickup

4.00 A

2633 T 3I0 STUB Time delay

30.00 sec A

2634 Instantaneous trip via Teleprot./BI

YES

2635 Instantaneous trip after SwitchOnToFault

NO

Page 14 of 23

7SA611 V4_6 Var_prn


Group Measurement Supervision; Group Balance / Summ.
TLD / NJP Temp / 7SA611 V4.6
Var/7SA611 V04.62.01
SIMATIC
5.22

30.12.14 13:10:26

Group Measurement Supervision; Group Balance / Summ.

Group Measurement Supervision; Group Balance / Summ.


No.

Settings

2901

Measurement Supervision

Value Group
ON

2902A Voltage Threshold for Balance Monitoring

50 V

2903A Balance Factor for Voltage Monitor

0.75

2904A Current Balance Monitor

0.30 A A

2905A Balance Factor for Current Monitor

0.50

2906A Summated Current Monitoring Threshold

0.10 A A

2907A Summated Current Monitoring Factor

0.10

2908A T Balance Factor for Voltage Monitor

5 sec

2909A T Current Balance Monitor

20 sec A

5.23

Group Measurement Supervision; Group Fuse Fail. Mon.

Group Measurement Supervision; Group Fuse Fail. Mon.


No.
2910

Settings
Fuse Failure Monitor

Value

Group

ON

2911A Minimum Voltage Threshold U>

30 V

2912A Maximum Current Threshold I<

0.10 A

2913A Maximum Voltage Threshold U< (3phase)

5V

2914A Delta Current Threshold (3phase)

0.20 A

2915

OFF

Voltage Failure Supervision

2916A Delay Voltage Failure Supervision

5.24

0.00 sec A

Group Measurement Supervision; Group VT mcb

Group Measurement Supervision; Group VT mcb


No.

Settings

2921 VT mcb operating time

Value Group
10 ms A

Page 15 of 23

7SA611 V4_6 Var_prn


Group Measurement Supervision; Group Load Angle
TLD / NJP Temp / 7SA611 V4.6
Var/7SA611 V04.62.01
SIMATIC
5.25

30.12.14 13:10:26

Group Measurement Supervision; Group Load Angle

Group Measurement Supervision; Group Load Angle


No.

Settings

Value Group

2941 Limit setting PhiA

200

2942 Limit setting PhiB

340

2943 Minimum value I1>

0.05 A A

2944 Minimum value U1>

20 V

5.26

Group Teleprotection for Earth fault overcurr.

Group Teleprotection for Earth fault overcurr.


No.

Settings

Value

Group

3201

Teleprotection for Earth Fault O/C

OFF

3202

Line Configuration

Two Terminals A

3203A Time for send signal prolongation

0.05 sec

3209A Transient Block.: Duration external flt.

0.04 sec

3210A Transient Block.: Blk.T. after ext. flt.

0.05 sec

5.27

Group Automatic Reclosure; Group General

Group Automatic Reclosure; Group General


No.

Settings

Value

Group

3401

Auto-Reclose function

ON

3402

CB ready interrogation at 1st trip

YES

3403

Reclaim time after successful AR cycle

3.00 sec

3404

AR blocking duration after manual close

0.00 sec

3406

Evolving fault recognition

with Trip

3407

Evolving fault (during the dead time)

starts 3pole AR-cycle A

3408

AR start-signal monitoring time

0.20 sec

3409

Circuit Breaker (CB) Supervision Time

3.00 sec

3410

Send delay for remote close command

0.80 sec

0.80 sec

3411A Maximum dead time extension

Page 16 of 23

7SA611 V4_6 Var_prn


Group Automatic Reclosure; Group 1st AR-cyle
TLD / NJP Temp / 7SA611 V4.6
Var/7SA611 V04.62.01

SIMATIC
5.28

30.12.14 13:10:26

Group Automatic Reclosure; Group 1st AR-cyle

Group Automatic Reclosure; Group 1st AR-cyle


No.

Settings

Value

Group

3450 Start of AR allowed in this cycle

YES

3451 Action time

0.20 sec A

3456 Dead time after 1pole trip

0.80 sec A

3457 Dead time after 3pole trip

0.50 sec A

3458 Dead time after evolving fault

1.00 sec A

3459 CB ready interrogation before reclosing

YES

3460 Request for synchro-check after 3pole AR

YES

5.29

Group Automatic Reclosure; Group 3pTRIP/DLC/RDT

Group Automatic Reclosure; Group 3pTRIP/DLC/RDT


No.

Settings

Value

Group

3430 3pole TRIP by AR

YES

3431 Dead Line Check or Reduced Dead Time

Without

3438 Supervision time for dead/ live voltage

0.10 sec A

3440 Voltage threshold for live line or bus

48 V

3441 Voltage threshold for dead line or bus

30 V

5.30

Group Automatic Reclosure; Group Start AR with..

Group Automatic Reclosure; Group Start AR with..


No.

Settings

Value Group

3420 AR with distance protection

YES

3421 AR with switch-onto-fault overcurrent

NO

3424 AR with direct transfer trip

NO

3425 AR with back-up overcurrent

NO

Page 17 of 23

7SA611 V4_6 Var_prn


Group Synchronism and Voltage Check; Group General
TLD / NJP Temp / 7SA611 V4.6
Var/7SA611 V04.62.01
SIMATIC
5.31

30.12.14 13:10:26

Group Synchronism and Voltage Check; Group General

Group Synchronism and Voltage Check; Group General


No.

Settings

Value

Group

3501 Synchronism and Voltage Check function

ON

3502 Voltage threshold dead line / bus

5V

3503 Voltage threshold live line / bus

105 V

3504 Maximum permissible voltage

115 V

3507 Maximum duration of synchronism-check

1.00 sec A

3508 Synchronous condition stability timer

0.00 sec A

3509 Synchronizable circuit breaker

Breaker

5.32

All

Group Synchronism and Voltage Check; Group with AR

Group Synchronism and Voltage Check; Group with AR


No.

Settings

Value

Group

3510

Operating mode with AR

with consideration of CB closing time

3511

Maximum voltage difference

4.0 V

3512

Maximum frequency difference

0.05 Hz

3513

Maximum angle difference

3515A AR at Usy2>, Usy1>, and Synchr.

YES

3516

AR at Usy1< and Usy2>

NO

3517

AR at Usy1> and Usy2<

NO

3518

AR at Usy1< and Usy2<

NO

3519

Override of any check before AR

NO

Page 18 of 23

7SA611 V4_6 Var_prn


Group Synchronism and Voltage Check; Group Man.Close+CNTRL
TLD / NJP Temp / 7SA611 V4.6
Var/7SA611 V04.62.01
SIMATIC
5.33

30.12.14 13:10:26

Group Synchronism and Voltage Check; Group Man.Close+CNTRL

Group Synchronism and Voltage Check; Group Man.Close+CNTRL


No.

Settings

Value

Group

3530

Operating mode with Man.Cl

without consideration of CB closing time

3531

Maximum voltage difference

4.0 V

3532

Maximum frequency difference

0.04 Hz

3533

Maximum angle difference

3535A Manual Close at Usy2>, Usy1>, and Synchr

YES

3536

Manual Close at Usy1< and Usy2>

NO

3537

Manual Close at Usy1> and Usy2<

NO

3538

Manual Close at Usy1< and Usy2<

NO

3539

Override of any check before Man.Cl

NO

5.34

Group Voltage Protection; Group U> Phase-Earth

Group Voltage Protection; Group U> Phase-Earth


No.

Settings

Value

Group

3701

Operating mode Uph-e overvoltage prot.

ON

3702

Uph-e> Pickup

69.8 V

3703

T Uph-e> Time Delay

3.00 sec A

3704

Uph-e>> Pickup

76.2 V

3705

T Uph-e>> Time Delay

0.00 sec A

3709A Uph-e>(>) Reset ratio

5.35

0.98

A
A

Group Voltage Protection; Group U> Phase-Phase

Group Voltage Protection; Group U> Phase-Phase


No.

Settings

Value

Group

3711

Operating mode Uph-ph overvoltage prot.

ON

3712

Uph-ph> Pickup

121.0 V

3713

T Uph-ph> Time Delay

3.00 sec A

3714

Uph-ph>> Pickup

132.0 V

3715

T Uph-ph>> Time Delay

0.00 sec A

3719A Uph-ph>(>) Reset ratio

0.98

A
A

Page 19 of 23

7SA611 V4_6 Var_prn


Group Voltage Protection; Group 3U0> or Ux>
TLD / NJP Temp / 7SA611 V4.6
Var/7SA611 V04.62.01

SIMATIC
5.36

30.12.14 13:10:26

Group Voltage Protection; Group 3U0> or Ux>

Group Voltage Protection; Group 3U0> or Ux>


No.

Settings

Value

Group

3721

Operating mode 3U0 (or Ux) overvoltage

OFF

3722

3U0> Pickup (or Ux>)

30.0 V

3723

T 3U0> Time Delay (or T Ux>)

2.00 sec A

3724

3U0>> Pickup (or Ux>>)

50.0 V

3725

T 3U0>> Time Delay (or T Ux>>)

1.00 sec A

3728A 3U0>(>): Stabilization 3U0-Measurement

ON

3729A 3U0>(>) Reset ratio (or Ux)

0.95

5.37

Group Voltage Protection; Group U> Postive Seq.

Group Voltage Protection; Group U> Postive Seq.


No.

Settings

Value

Group

3731

Operating mode U1 overvoltage prot.

OFF

3732

U1> Pickup

150.0 V

3733

T U1> Time Delay

2.00 sec A

3734

U1>> Pickup

175.0 V

3735

T U1>> Time Delay

1.00 sec A

3739A U1>(>) Reset ratio

5.38

0.98

A
A

Group Voltage Protection; Group U> Negative Seq

Group Voltage Protection; Group U> Negative Seq


No.

Settings

Value

Group

3741

Operating mode U2 overvoltage prot.

OFF

3742

U2> Pickup

30.0 V

3743

T U2> Time Delay

2.00 sec A

3744

U2>> Pickup

50.0 V

3745

T U2>> Time Delay

1.00 sec A

3749A U2>(>) Reset ratio

0.98

A
A

Page 20 of 23

7SA611 V4_6 Var_prn


Group Voltage Protection; Group U< Phase-Earth
TLD / NJP Temp / 7SA611 V4.6
Var/7SA611 V04.62.01

SIMATIC
5.39

30.12.14 13:10:26

Group Voltage Protection; Group U< Phase-Earth

Group Voltage Protection; Group U< Phase-Earth


No.

Settings

Value

Group

3751

Operating mode Uph-e undervoltage prot.

OFF

3752

Uph-e< Pickup

30.0 V

3753

T Uph-e< Time Delay

2.00 sec A

3754

Uph-e<< Pickup

10.0 V

3755

T Uph-e<< Time Delay

1.00 sec A

3758

Current supervision (Uph-e)

ON

1.05

3759A Uph-e<(<) Reset ratio

5.40

Group Voltage Protection; Group U< Phase-Phase

Group Voltage Protection; Group U< Phase-Phase


No.

Settings

Value

Group

3761

Operating mode Uph-ph undervoltage prot.

OFF

3762

Uph-ph< Pickup

50.0 V

3763

T Uph-ph< Time Delay

2.00 sec A

3764

Uph-ph<< Pickup

17.0 V

3765

T Uph-ph<< Time Delay

1.00 sec A

3768

Current supervision (Uph-ph)

ON

1.05

3769A Uph-ph<(<) Reset ratio

5.41

Group Voltage Protection; Group U< Postive Seq.

Group Voltage Protection; Group U< Postive Seq.


No.

Settings

Value

Group

3771

Operating mode U1 undervoltage prot.

OFF

3772

U1< Pickup

30.0 V

3773

T U1< Time Delay

2.00 sec A

3774

U1<< Pickup

10.0 V

3775

T U1<< Time Delay

1.00 sec A

3778

Current supervision (U1)

ON

1.05

3779A U1<(<) Reset ratio

Page 21 of 23

7SA611 V4_6 Var_prn


Group Fault Locator
TLD / NJP Temp / 7SA611 V4.6
Var/7SA611 V04.62.01

SIMATIC
5.42

30.12.14 13:10:26

Group Fault Locator

Group Fault Locator


No.

Settings

Value

Group

3802 Start fault locator with Pickup A


3806 Load Compensation

5.43

NO

Group Thermal Overload

Group Thermal Overload


No.

Settings

Value

Group

4201 Thermal overload protection

ON

4202 K-Factor

0.86

4203 Time constant

45.0 min

4204 Thermal Alarm Stage

90 %

4205 Current Overload Alarm setpoint

0.85 A

4206 Method of Acquiring Temperature

Theta Max A

Page 22 of 23

7SA611 V4_6 Var_prn


Time Synchronization
SIMATIC
6

TLD / NJP Temp / 7SA611 V4.6


Var/7SA611 V04.62.01

30.12.14 13:10:26

Time Synchronization

Source of time synchronization: IEC 60870-5-103


Fault indication after: 10 Min.
Time format for display German
Offset to time signal: 00:00
Time zone offset to GMT: +01:00

Page 23 of 23