Documente Academic
Documente Profesional
Documente Cultură
SFERE - TA CO/81 - A 04/11 - Any data in this documentation may be modified without prior notice.
LCD console
Software MC Vision
console
User handbook
http: //www.sfere-net.com
e-mail: info@sfere-net.com
Th
en
e fri
dly
fac
r
e
t
n
Summary
Summary
1 . INTRODUCTION
p2
2 . SPACE REQUIREMENTS
p5
3 . WIRING
p6
p7
p7
p7
p8
p8
p9
p9
p10
p10
p11
p16
p22
p16
p16
p16
p17
p17
p18
p18
p19
p20
p22
p22
p23
p23
p23
p24
p24
p24
p24
p 24
p24
p25
p25
p26
p26
6 . ERROR MESSAGES
6.1 Blinking of the LED ON
p26
p26
p26
8 . LEXIQUE
p26
9 . ANNEXE: MODBUS
9.1 Table of the Modbus addresses
9.2 Description of the born Modbus functions
9.3 Reading in double integer format
9.4 CRC 16 calculation algorythm
p31
p31
p32
p33
p33
p1
1. INTRODUCTION
The series C offers a complete range of fully programmable measure interfaces,
either with the console or by PC via the configuration software.
The series C accepts 2 types of consoles :
the old generation with 4 electroluminescent alphanumerical green digits,
the new generation with rear-lit graphical LCD.
The LCD allow the visualisation of 4 pieces of information:
- the value of the measure (5 mm high),
- the unit of the displayed measure, *
- the value of the analog output or the name of the product (TAG), *
- the status of the relay outputs and the RS485 communication. *
*(3.5 mm high)
This console with LCD also allows showing these information vertically or horizontally according to the sense in which the converter is mounted.
Input features common to the series C10, C 305U, C 405U,
C 805U, C3011/3211, C4001/3211F
- thermocouple inputs (J, K, B, R, S, T, E, N, L, W, W3, WRE5)
- sensor inputs: Pt100, Ni 100
- resistive sensors: caliber 0-400 and 0-2 k (0-8 k optional)
- potentiometers: from 100 to 10 k
Input features specific to the series C10
- a DC unidirectionnal current or voltage input:
0-100 mV, 0-1V, 0-10V, 0-300V, 0-20mA.
Input features specific to the series C 305U, C 405U,
C 805U, C3011/3211, C3012/3212 et C4001/3211F/3212F
- a DC bidirectionnal current or voltage input:
100 mV, 1V, 10V, 300V, 20mA.
Input features specific to the series C4001/3211F/3212F
- fast acquisition, allowing a response time of the analog and relay outputs < 20 ms.
AVAILABLE OPTIONS: (specify on order)
Series C10
- Insulated analog output A:
Programmable output: active or passive current, or voltage.
- Relay output R:
2 relays - Mode setpoint or window.
Recording of the alarms.
Time delay and hysteresis adjustable on each setpoint.
Alarm messages.
Series C 305/405/805U
- Insulated analog output A :
Active current or voltage output (specify on order)
- Output 4 relays R4 :
1 NO contact
Input features
C
3012
3212
Coding
ARN
Inputs:
C10
C 305U/405U/805U
C 3011/3211
C3012/3212
C4001/3211F/3212F
C 10
C 3011/3012
A
A
C3211/3212
C 4001
C 3211F/3212F
C XXXX
3011/
305U/
405U/
805U/
3211/
4001/
AR
AR
R
AR
R
Types of
INPUTS
Measure range
adjustable from:
Permanent
overload
mA
100mA
Intrinsic
error
Console
resolution
IInput
impedance
10 A
Max. drop
3211F/3212F
Type
10
ARN
N
ARN
0.9V
1V
50V
Thermocouples
Standard IEC 581
J
K
B
R
S
T
E
N
L
W
W3
WRE5
-160/1200
-270/1370
200/1820
-50/1770
-50/1770
-270/410
-120/1000
0/1300
-150/910
1000/2300
0/2480
0/2300
-256/2192
-454/2498
392/3308
-58/3218
-58/3218
-454/770
-184/1832
-32/2372
-238/1670
1832/4172
32/4496
32/4172
-200/850
-328/1562
-60/260
-76/500
-200/270
-328/518
10 V
1 mV
the MR
600V
C 305U
The standard C 305U has a programmable insulated active or passive current or voltage analog output.
C 405U
Resistive sensors
from 100 to 10 k
Potentiometer*
C 805U
1M
1 mV
(5)
0.05% of
(4)
< 0.1% of
the MR
10mV
(2)
<0.1%
of the MR
<0.1%
of the MR
0.1C /
0.1F
1 M
0.1C /
0.1F
Current
250A
Special linearisation
programming
up to 20 points
<0.1%
of the MR
(0.5% for
0-2K)
A 12 A pulsed current
allows the detection of line or
sensor rupture
Line resistance <
10 and R. max. 400
Thermic drift <150ppm /C
(see 3)
p3
General features
Rejection
relays
C4001
C3211F/
3212F
C4001
C3211F/
3212F
2 ms
5 ms
45 ms
20 ms
20 ms
20.0 ms
40 ms
65 ms
55 ms
55 ms
50 Hz
100 ms
200 ms
200 ms
215 ms
215 ms
50Hz/60Hz
Galvanic partition:
2kV-50 Hz-1 min between supply, inputs, relay outputs, analog outputs and digital output
C 3011/3012/4001
: 1kV-50Hz-1min between analog and digital output
C 3211/3212/3211F/3212F
: 1kV-50Hz-1min between 2 analog outputs
C3211N /3212N/3211FN/3212FN: 1kV-50Hz-1min between the 2 analog outputs
1 kV-50Hz-1min between digital output and analog outputs
Max. operating range
Power draw
Dielectric
withstanding
3.5 W max.
6 VA max.
For the inputs with 2 measures (Tc, Pt100, ni 100 and potentiometer) the 2nd measure is performed every minute. During this measure the max. response time on the relays or the analog
output increases by 5 ms, 20 ms or 100 ms according to the value of the programmed cycle
time (2ms, 20 ms, 100 ms).
If the sensor rupture detection is being used (mV and t inputs), add 2ms to the response time
of the outputs.
Conform with standards IEC 61000-6-4 on rejections and IEC 61000-6-2 on immunity
(in industrial environment) IEC 61000-4-2 level 3, IEC 61000-4-3 level 3,
IEC 61000-4-4 level 4, IEC 61000-4-6 level 3.
CE marking according to the directive EMC 89-336.
C 10
Co
de
40
(3)
1
C
32
11
/
3
21
C
1F
32
12
/32
12
F
01
2/
C3
05
U
5U
40
C 5U
10
C
30
11
C
3
80
C
Programming:
Types
of OUTPUTS
current
Voltage
2 analog insulated Current or
voltage
1 analog
Features
2 change-over relays
4 relays /1 NO contact
(3) The relay outputs R and the digital data link N are not available simultaneously.
(4) The digital data link N and the voltage output A are not available simultaneously.
p4
2. SPACE REQUIREMENTS
Upper connector
A3 A2 A1
Voltage presence
Led ON
E6 .........E1
22.5
22.5
26.5
26.5
Relay 1
Relay 2
75
console plug
PC connection
plug
x
22,5
120
S10 ......................... S1
Lower connector
p5
3. WIRING
connectors
SUPPLY
INPUTS
A3 A2 A1
Anal. output 1
1V
10V
mV
mA
OFF2
C2
OFF1
C1
ON2
Relay 2
ON1
Relay 1
+
+
Tc
PT100 3 wire
PT100 2 wire (T2-T1)
T1: cold sensor
T2: hot sensor
1
2
0-4/20mA mA
active +
or
V
0-10V
mA
~
-
300V
Anal. output 2
2 relay outputs
S10 S9 S8 S7 S6 S5 S4 S3 S2 S1
E6 E5 E4 E3 E2 E1
+
~
DC +
AC
Potentiometer
Version with 2 insulated independent analog outputs and insulated digital data link RS485.
Analog output 1
Analog output 2
mA
0-10V
0-4/20mA
active
mA
0-4/20mA
active
Lr
2-wire transmitter
connector
2 relay outputs
Anal. output
S10 S9 S8 S7 S6 S5 S4 S3 S2 S1
+
mA
0-4/20mA
active
OFF2
C2
ON2
Relay 2
OFF1
C1
ON1
Relay 1
Lr
0-4/20 mA passive
external source 30V max.
0-10V
B
Data link
RS485 for
C 3011/3012
ARN
or C 4001ARN
C 3211F/3212F N
0-10V
Data link
RS485
Lr
0-4/20mA passive
external source 30Vmax.
Lower
Analog outp.
S10 S9 S8 S7 S6 S5 S4 S3 S2 S1
+
mA
0-10V
0-4/20mA
active
Lr
0-4/20 mA passive
external source 30V max.
p6
Graphical LCD
Analog output
S10 S9 S8 S7 S6 S5 S4 S3 S2 S1
+ 0-4/20 mA
or
0-10 V
C4
mA
active
C3
T4
C2
T3
C1
T2
T1
Indication
of the
measure
sign or the
programming parameters
For a C 805U, the type of the analog output (mA ou V) must be specified on order.
1 2 3 4
2413
M
Indication
of the alarm
status of
relay 1
Indication of
the
alarm status
of relay 2
-1.234
Bar
12.04mA
.)) .)) .
M
M
M
Reading convention:
Entering of a parameter:
First start by increasing or decreasing
6888 the 1st digit and the sign: from -9 to +9.
6588
6528
6520
and
p7
M
Exit from a submenu to access
next menu /
access to the
programming
exit menu
Move through
the menus:
downwards, or
decrease the value
shown
Validation of
the displayed
parameter, or
access to a
submenu
SIMU
PCOD
move
(analog
output)
GENE
PROG
menus
CLrA
access code
CODE
8 888
If code
correct, access
to the programming menu
see page 8
If code
incorrect,
message
appears
NO
Authorized by
access code
p11
p11
JBUS
p12
REL
p13
LOAD
Display
Simulation Deleting of Teleloading
Programming
of the access simulation of the analog the recorded of programalarms
(see p23)
ming files
outputs
code
(see p24)
Authorized by
(see p24)
(see p23)
(see p22)
DISP
ANA
PrDI
(relay output)
READ
(relay / analog
output)
vertical
p9
SECU
scroll
INP
NAME
SAVE
p11
p15
p15
Note:
In mode programming, the instrument will automatically revert to measure
with the previous configuration if no key is pressed during 1min.
Note:
Press M to go on to the next menu
Downwards move /
decrease
p8
INP
a. Process signals
INP
mA
voltage input
current input
voltage input only
1V
10V
100m
300V
2WIR
YES NO
DISP
CAL
to t sensors
resistive sensors
TYPE
Beware:
The measure range (uni or bidirectionnal scale) depends on the value entered for
the parameters dINP and FINP (see page 10).
If the value of dINP and FINP is negative the converter will operate with a bidirectionnal input scale.
If the values of dINP and FINP are both positive the converter will operate with a
unidirectionnal input scale.
Connection of the mA
sensor:
Choose
if a
mA passive sensor is
connected between
terminals E6 and E3
(2-wire transmitter)
YES
p9
CJ-E
external
CJ-I
CJC*
TC-T
(2)
compensation
TC-E
TCW5
TCW3
TC-R
TC-B
TC-L
TC-W
TC-S
internal
or
8K
optional
DISP
Note:
Press
(2)
-888.8
If no shifting
YES
NO
ADJ
2K
CJ-T
400
TC-N
TC-J
TC-K
If thermocouple
oF
RTD **
oC
TC
ni 100
if resistance
CJC
RTD
CAL
POT
TC--
To
RES
temperature inputs
CAPT
TEMP
C10
C 305U C 405U C 805U
C3011/3211 C4001/3211F/3212F
process
signals
INP
temperature signals
process signals
INP
C10
C 305U C 405U C 805U
C3011/3211 C4001/3211F/3212F
c. Resistive sensors
b. Temperature signals
Downwards move /
decrease
DISP
* cold junction compensation, except
thermocouple B which is only in CJ-E.
p10
in mV, V or mA
according to the
type
20.0m 100m
(C 4001 ou 3211F/3212F)
integration indice
ANA
0000
or
JBUS
or
REL
or
SECU
dOUT
according to options
= 4 mA
F.OUT
dOdI
= 20.00mA
F.OdI
= 20.0
= 100.0
When the transmitter shows the value 20C then the value of the analog output will be 4 mA
When the transmitter shows the value 100C then the value of the analog output will be 20 mA
Eg.: in mode indicator with PARA INP or in mode transmitter
INP
= mA
dOUT
= 4 mA
F.OUT
= 20 mA
dOdI
= 6.0 mA
F.OdI
= 20.00 mA
When the value of the current measured on the input is 6.0 mA, the value of the analog output will be 4 mA.
When the value of the current measured on the input is 20.0 mA, the value of the analog output will be 20 mA.
SECU
or
REL
or
If the transmitter is in mode indicator (SCALE YES), you can choose to assign the analog output to the input
measure (PARA INP) or the displayed measure (PARA DISP).
Eg.: in mode indicator (SCALE YES) with PARA DISP
-88.88
F.DIS
JBUS
according to options
-88.88
YES
-88.88
-88.88
dDIS
(1)
NO
-88.88
F.OdI
-88.88
full scale
in mV, V or mA
according to the
type
-88.88
(1)
dOdI
-88.88
F.INP
(1)
(4)
down scale
-88.88
dINP
-88.88
Only if
Scale YES
F.OUT
(1)
-88.88
-88.88
ROOT
(1)
linear function
PARA
INP DISP
1o
(4)
0.1o
-88.88
0020
LIN
special linear
function
SEGT
2ms
FILT
T.MES
rES
dOUT
(4)
CUT
display resolution
1 or 1/10th of degree
Y19
Y00
--.--
temperature input
ANA
(see p15)
X19
YES and
LCD console
OUt.I
X00
NB
if SCALE
OUt.U
FUNC
POIN
UNIT
Bar
UNIT
Bar
YES
TYPE
NO
Parametering of a
physical display
YES : mode indicator
NO : mode transmitter
parameter proposed
if YES validated
Enter the unit of the
displayed measure
(see the list p32)
SCAL
DISP
C10/ C 305U
C 805U
C3011/3012
C4001
DISP
ANA
Downward move /
decrease
p11
NONE
REL
or
SECU
= 100,0
F.OUT
= 4 mA
= 20 mA
dOdI
dOUT
= 6.0 mA
F.OdI
= mA
1200
ON : typical delay
75ms
ON
REL
or
OFF
SECU
F.OdI
= 20,0
DEL
or
When the transmitter shows the value 20C then the value of the analog output will be 4 mA.
When the transmitter shos the value 100C then the value of the analog output will be 20 mA.
Eg.: in mode indicator with PARA INP or in mode transmitter
INP
L-H
according to options
dOdI
= 20,00mA
2400
-88.88
F.OUT
H-L
If the transmitter is in mode indicator (SCALE YES), then you can choose to assign the analog output to the
input measure (PARA INP) or to the displayed measure (PARA DISP).
Eg.: in mode indicator (SCALE YES) with PARA DISP
= 4 mA
ODD
JBUS
dOUT
FORM
EVEN
-88.88
4800
PAR
-88.88
9600
F.Od1
19.2K
dOd1
(4)
transmission speed
(4)
F.OU1
-88.88
JBUS
(4)
DISP
-8888
INP
BAUD
slave number
dOU1
PARA
SLAV
ANA 2
OU1.I
JBUS
or
Communication parameters
OU1.U
ANA
TYP1
ANA 1
C 3211/3212
C 3211F/3212F
ANA
Analog outputs
= 20,00 mA
When the value of the current measured on the input is 6.0 mA, the value of the analog output will be 4 mA.
When the value of the current measured on the input is 20.0 mA, the value of the analog output will be 20 mA.
Downwards move /
decrease
p12
OUT.U
NO
option 2 relays
LO
HI
OFF: self-diagnosis
inactive on the relay
In case of selfdiagnosis error
LO : relay de-activated
HI : relay active
LO
OFF
HI
X: 2 to 4 accord. to option
NO
-88.88
PrDI
REPL
OUT.U
or
YES
OUT.I
REL2
YES
ABCD
X: 2 to 4 accord. to option
YES
OFF
RELX
or C405U,
C805u (4 relays)
ON
HI
NO
REL1
OFF
dIAG.
HI
000.0
NO
MESI
hysteresis
LO
YES
REPL
MEM1
or
04.00
LO
OFF
OUT.I
SECU
if input mV or t
OFF
RELX
OFF
LED1
REL1
access to SP1.1
access to SP1
if mode setpoint programmed (5) choice of the relay
operating mode:
mode setpoint or
02.00
window
(see page 18)
if mode window programmed
02.00
ON
mode window
mode setpoint
00.00
TIM1
CAPT
HYS1
REL
RUPT
SP2.1
SP1.1
DISP
(5)
OFF
SECU
INP
MOD1
SP 1
PARA
ON
de-activated
REL4
idem
REL1
REL3
AL.1
active
Safeties
idem
REL1
REL2
alarm
idem
REL1
REL1
REL
00.00<rEPLI<22.00 (mA)
00.00<rEPLI<11.00 (V)
p13
Safeties
C 3211/3212
C 3211F/3212F
SECU
NO
NO
OU2.U
or
YES
REP2
2 analog outputs
NO
HI
OU2.U
or
OU1.U
or
LO
YES
OU2.I
HI
OU1.I
LO
OFF: self-diagnosis
inactive on the relay
In case of selfdiagnosis error
LO: relay de-activated
HI: relay active
OFF
REP1
YES
REP2
NO
REL2
OU2.I
2 analog outputs
OFF
OU1.U
HI
REL1
or
LO
YES
REP1
HI
option 2
relays
option 2 relays
LO
OFF
OU1.I
dIAG.
if input mV or t
OFF
REL2
OFF
ON
REL1
SECU
CAPT
RUPT
SECU
Safeties
C 3211/3212
C 3211F/3212F
PrDI
p14
LdIG
0010
NULL
OFF
ABCD
SAVE
NAME
SAVE
YES
NO
NAME
ON
NO
NAME
enforced to 0
YES
IDLE
OFF
NULL
ON
not enfor. to 0
OFF
NAME
ANA
NAME
ON
ANA
IDLE
NO
NAME
90
YES
LdIG
LIN3
0005
on 4 levels
VIEW
1111
LIGH
BRGT
BRGT
PrDI
PrDI
PrDI
Programing of the display parameters for the console with green electroluminescent display
SAVE
revert to
measure
display
p15
Example 1: For a 4/20 mA signal from a level sensor on a tank, the following
programming is displayed:
in the menu INP: TYPE = mA
in the menu DISP: SCALE YES, POIN = _ _ _ . _ FUNC = LIN, dINP = 4.00 ,
F.INP = 20.00, dDIS = 000.0, F.DIS =300.0
CUT = NO for:
4 mA from the sensor, display = 000.0 m3*
12 mA from the sensor, display = 150.0 m3
20 mA from the sensor, display = 300.0 m3
* m3 is the unit of the physical magnitude, and can appear on the LCD graphical console
For the temperature input, when the resolution is changed from RES=1C to
RES = 0.1C or the contrary, the user does not need to modify all the display related parameters again.
(on the console you will need to enter the 4 digits and the place of the decimal
point for each parameter).
mA
or voltage
ROOT
The function square root tends to amplify the background noise of the input
signal when getting near zero.
To avoid the ripples caused by this noise, simply programme a cut-off value (in
display points).
If the display is below this value it will be held at the down scale (if the full input
scale > down input scale) or at the full scale (if the full input scale < down input
scale).
Special linearisation:
SEGT
All the programming parameters are entered with their own decimal, independent
from this parameter POIN.
POIN is the maximum number of decimals which you wish to display. In case of
overstepping of the display capacity, the instrument will automatically reduce the
number of decimals.
eg.: POIN = - - . - Number
Display
0
00.00
1
01.00
5
05.00
52,3
52.30
121,1
121.1
1300
1300.
The parameter POIN is to be considered as the position of the decimal point for the
display of the measure in the case of an input different from temperature.
Note : An exit from mode programming with saving of the configuration (SAVE,
YES) will automatically reset to zero the min. and the max., as well as the recording of alarms.
After SAVE, YES the console will show WAIT during the converer re-initialisation
phase.
Note 1: The values of the abscisses (x) must go increasing: value of X00
< value of X01...
Note 2: In special linearisation and in mode transmitter (SCALE NO),
the displayed measure is the measure linearised by the programming of
points. The undeformed input measure can always be accessed by the
function direct measure (see p26) on the console or on the variable
Input on the software.
Example:
For a layed cylindric tank, 1 meter high (h) and 1 meter long (l); a 0-20
mA linear sensor measures the height of the liquid surface line:
0 meter -> 0 mA (empty tank) 1 meter -> 20 mA (full tank)
with cos /2 = ( R - h ) / R a n d sin /2 = C/2R
Empty tank volume = 0.000
Full tank volume = 0.785
Volume = L [
R (ray)
R /360 - C(R-h)/2]
(R)
h
(height)
C (chord)
th)
ng
le
L(
0
2
4
6
8
10
12
14
16
18
20
Height
m
Angle
Degree
Chord
m
0.0
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
0.9
1.0
0.00
73.74
106.26
132.84
156.93
180.00
203.07
227.16
253.74
286.76
360.00
0.00
0.60
0.80
0.92
0.98
1.00
0.98
0.92
0.70
0.60
0.00
Volume
m3
Y00
Y01
Y02
Y03
Y04
Y05
Y06
Y07
Y08
Y09
Y10
0.000
0.041
0.112
0.198
0.293
0.393
0.492
0.587
0.674
0.745
0.785
Outputs
in mA
00.00
01.04
02.85
05.04
07.47
10.00
12.54
14.96
17.17
18.98
20.00
Programming :
dINP = 0 mA = X00
F.INP = 20 mA = X10
nb = 11
d.disp = 0.000 m3 =Y00
F.disp = 0.785 m3 =Y10
Programming from X00 to
X10 and from Y00 to Y10
according to the table.
X
input (mA)
height (m)
indice of X
ANA
(C 3x) and
ANA 1
ANA 2
(C 32x)
dOUT dOU1
F.OUT F.OU1
dOdI dOd1
F.OdI F.Od1
dOU2
F.OU2
dOd2
F.Od2
p17
- If the mode indicator (SCALE YES) is selected, the setting of the parameters
dOdI and FOdI is in display points or in input scale points according to PARA.
Mode setpoint
- If the mode transmitter (SCALE NO) is selected, the setting of the parameters dOdI and FOdI is in input scale points.
C 3011/3012ARN
C 4001ARN
C 3211/3212N
C 3211F/3212FN
BAUD
PAR
FORM
Transmission parity
Transmission format (rank of the bytes in a transmitted
integer)
DEL Delay before any response
Complete description of the option MOBDUS in the annexe
MODBUS/JBUS.
Including: the table of modbus addresses, the used functions, the
description of the configuration bytes and the advanced functions.
2 relay outputs
REL1
REL2
ON
OFF
AL.X
ON
OFF
ON
or
setpoint
OFF
setpoint
Legend:
ON coil supplied
OFF coil not supplied
SPX
SPX
DISP
Mode window
ON
OFF
setpoints
SP1.X
ON
OFF
or
setpt
ON
OFF setpt
SP1.X
SP2.X
SP2.X
LEdx
ON
OFF
MODx
HYSx
Mode setpoint
led still
led lit
SP.X SP.X
- HYSx
p18
Mode window
led lit
led still
SP1.X SP1.X
-HYSx
SP2.X
SP2.X
led still
+HYSx
Coding:
1 : Programming error
4 : Offset error
8 : Input calibration error
16 : Output calibration error
64 : Upper or lower electrical overstepping of the input.
If the instrument detects for instance an offset error (4) and a programming error (1) the value of the error code will be 5 (4+1).
On the relays:
No influence on the relay in case of self-diagnosis error.
OFF
LO
HI
Sensor rupture
RUPT
The sensor rupture can be detected on mV, Tc, Pt100, Ni100, resistance
and current inputs if down and full scale > 3.5 mA.
HI
Note : the led is either still or lit according to its programming in the
menu REL.
On the analog output
If a return value has been programmed
0 and 22 mA (current output)
Value between:
0 and 11 V (voltage output)
or
p19
OPEN
Note : The sensor rupture detection has a priority over the selfdiagnosis.
T.MES
CAPT
ON
OFF
SECU
POIN
RES
dD I S
F.D I S
FILT
10
200* 400 600 1.0s 1.5s 2.0s 2.5s 3.0s 3.5s 4s 4.5s
The digital filtering increases the response time only if the chosen acquisition time
is 100 ms.
For an acquisition time T.MES of 2 or 20ms the digital filtering has no influence on the response time. Its value stabilises the measure result for small signal
variations.
Analog output
Value of the FILT
CUT
10
100 ms 200 400 600 1s 1.5s 2.0s 2.5s 3.0s 3.5s 4.0s 4.5s
For the maximum response time of the relay outputs, add15 ms to the table of the analog
output response times.
Caution: The response times may undergo variations in case of internal selfcalibration: the instrument will at some times perform an internal self-calibration
in order to catch up with any drifts of its components. During this operation the
response time of the instrument can be increased by 5 ms, 20 ms or 100 ms
(depending on the programmed cycle time value).
During the phases of teleloading of configuration with the console, the response times are no more garanteed.
These self-calibrations are performed every 10 seconds during the 10 minutes
following a setting on tension (stabilisation time of the components).
For the inputs with 2 measures (thermocouples, Pt 100, Ni 100 and potentiometer), the 2nd measure is performed every minute.
During this measure, the maximum response time on the relays or the analog
output increases by 5 ms, 20 ms or 100 ms according to the value of the programmed cycle time (2 ms, 20 ms or 100 ms).
The input Pt100 is available only with an acquisition time T.MES of
100ms.
Sensor rupture (input mV, thermocouples or resistance with caliber 400 ): add
2 ms to the response time of the analog and relay outputs if you are using the
sensor rupture detection: CAPT ON in the menu RUPT (SECU)
p20
Programmable cycle
time ms
2
20
100
5
40
200
relay
20
55
215
7
42
202
22
57
217
10
60
300
25
75
315
(1)In case of variation of the input signal during a phase of self-calibration or measurement of channel 2 (if input thermocouple, Pt 100, Ni 100 or potentiometer).
BRGT
GENE
ERxx
or
OPEN
----
BRGT
LIGH
VIEW
LIN3
Strongest brightness
SIMU
LdIG
NULL
NAME
ANA
NULL
YES
p21
READ
INP
DISP
ANA
JBUS
REL
SEC U
PrDI
NAME
INFO
Submenu
INFO
READ
and
If no key is pressed during 20 s., the instrument will revert to measure display.
During the reading of the programming, the C will carry on mesuring and
managing its output options.
C
3011
ARN
(1)
- : standard version
A: analog output
R: relay output
N: digital data link
no
xxxx
PROG
xx.xx
ORIG
PC-x
CSUM
65F2
0 0 0 0
x x x x
0 to 5
6 to 9
0 to 5
6 to 9
0 to 5
6to 9
0 to 5
6 to 9
Factory code
Access to the display shifting
No access
Access to the display and output simulations
No access
Access to the teleloading of files
No access
Access to a quick entering of alarm setpoints
No access
4.10
Programming of a new access code with the
console
PCOD
OLD
if code correct
(old)
NEW
NO
p22
SIMU
M Press Menu to
revert to the
measure display.
Value of the
display
Entering of a new
display value
a/ 1 analog output
(current or voltage output)
GENE
M Press Menu to
revert to the
measure display
GENE
M Press Menu to
revert to the
measure
display.
SIMU
if
10 / C 305U
805U
3011/3012
4001
M Press Menu to
revert to the
measure display.
Value of the
output
if
Value of the
output
GEN 2
if
Value of the
output
C 3211N/3212N
C 3211F/3212FN
GENE
M Press Menu to
GEN 1
revert to the
measure display.
GEN 1
if
revert to the
measure display.
M Press menu to
Enter the value
to be injected
GEN 1
GENE
if
C 3211/3212
C 3211F/
Value of the
output
GEN 2
GEN 2
if
Value of the
output
Note: The instrument will carry on measuring during the simulation. Only the output selected by GEN 1 (output 1) or GEN 2 (output 2) will no longer react to the measure, the other output will
follow the evolving of the measured input.
p23
4.11.3 Menu
CLrA
M not deleted.
CLrA
Deleting of the recorded
alarms, and revert to
measure display.
Reminder: If no key is pressed during 20 s.,
the instrument will revert to measure display.
Note: A revert from mode programming with saving of the configuration
will delete the recorded alarms.
4.11.4 Menu
LOAD
LOAD
READ
CONS
COPY
ER R
PROG
Co
if transfer
correct
WAI T
Co
if transfer
incorrect
ER R
during
1s.
OK
PROG
or
OPT
Co
Co
ERR
PROG
ERR
OPT
Eg.: a file from a C 3011 A can not be copied into a C 3011 AR. For
the teleloading in the direction
C o to be possible, the receiving
converter must have the same input and output options as the converter
on which the programming file has been copied.
The file stored in the console can be read by validating choice READ
CONS . In this case the organigramme for reading the programming
file is the same as for the programming of the instrument. (see p8)
Reminder: if no key is pressed during 20 s. or if you press M
the instrument will revert to the measure display.
Display of
the measure
Display of
the measure
INF
SUP
02.00
08.00
CLrM
p24
Note: A revert from mode programming with saving of the configuration will reset the min. and max. value to zero.
On the contrary, if the 2 settings are performed, the slope and the offset
will be corrected in order to obtain the required result.
example:
For a PT100 input for 0C, the obtained display is -000.3
For 500C the obtained display is 0500.2. To correct this display, the
display down scale must be shifted by 3 points to obtain 000.0 and the
display full scale by -2 points to obtain 0500.0.
note: Only for temperature inputs:
From the menu READ, the performed scale shiftings can be visualised in
the submenu INP:
offset
shifting
= shifting by
1 point with
ADJ
or
ADJ
OFFS
000.3
slope and
offset
shifting
= shifting by
2 points
with
ADJ
and
ADJ
dDIS
-000.3
ADJ
000.3
F.DIS
500.2
ADJ
-000.2
p25
Press keys
and M to visualise the signal directly, without processing:
scale factor, square root, linearisation
The converter will then show the message SP.x or SPx.x alternating
with the value of the corresponding setpoint.
The value of the various setpoints can be accessed by
and
These setpoints can then be modified (if access code < 6000 (see p22))
by pressing
When the setpoint is adjusted press
ding menu.
Once all setpoints are adjusted, simply press M and the converter
will revert to mode measure, taking the new values into account.
If no key is pressed during 60 s. the converter will revert to the measure
display without modification of the value of the setpoints.
6. ERROR MESSAGES
Measure in overstepping
----
OPEN
Sensor rupture
OL
ERR1
Self-diagnosis error
(see p19)
SIMU
or
---GENE
8. LEXIQUE
Messages shown by the converter in mode programming and/or in
mode reading:
General access
LOAD
READ
PROG
CODE
ERxx
Option 2 relays
2000
OPEN
- or by pressing simultaneously on
Slow blinking:
Sensor rupture detected (display
ERxx
PCOD
SIMU
GENE
CLrA
p26
Inputs
Access to the submenu programming of the input
INP
TYPE Type of input
V Voltage input
mA Current input
TEMP Temperature input
POT Potentiometer input
RES Resistance input
Potentiometer input and resistance input
POT
RES
CAL Choice of the resistance caliber
400
2 k
8 k
Voltage and current input
CAL
mA
10V
300V
100m
1V
2WIR
Temperature input
TEMP
CJ-T
ni 100
NI100 input
T
C
F
ADJ
OFFS
dDIS
ADJ
FDIS
ADJ
Celsius degrees
Farenheit degrees
Input shifting
Offset shifting
Slope and offset shifting, display down scale
Ajusting of the display down scale
Slope and offset shifting, display full scale
Ajusting of the display full scale
Display parameters
with green electroluminescent display
ON
Active
OFF
Inactive
p27
Display parameters
with LCD
NULL
SCAL
UNIT
POIN
FUNC
OFF
ON
Active
OFF
Inactive
--.--
LIN
Linear
NB
Xxx
Yxx
ROOT
SEGT
YES
NO
IDLE
DISP
NAME
LdIG
Display
dINP
F.INP
dDIS
FDIS
CUT
RES
0.1
1
FILT
UNIT
T.MES
Resolution 1 degree
Integration indice
Choice of 4 characters to define the display unit
Measure acquisition time programmable: 2 ms, 20
ms, 100 ms
p28
Analog output
OUt.U OU1.U
OUt.I OU2.I
dOUT
F.OUT
dOdI
F.OdI
dOU1
F.OU1
dOd1
F.Od1
PARA
INP
DISP
dOU2
F.OU2
dOd2
F.Od2
Relay outputs: x : 1 to 4
REL
REL.x
AL.x
PARA
INP
DISP
ON
Activation
OFF
De-activation
JBUS
SLAV
BAUD
FORM
DEL
Possible speeds
Possible speeds
NONE
EVEN
ODD
MSB transmitted first
Delay 75ms
OFF
Delay 20ms
Mode window
LEDx
MESx
Mode setpoints
MEM.x
- -I_ _
-I_ _I-
HYSx
TIM.x
ON
_ _I- -
SPx
SP1.X
SP2.X
Transmission parity
H-L
L-H
_I- -I_
Transmission speed
1200
19.2K
PAR
MODx
ON
OFF
YES
Recording
Recording of alarm X
NO
No recording
NO
No message
Alarm message
YES
Message
p29
Safeties
SECU
RUPT
SAVE
YES
WAIT
OUT.U
OU1.U OU1.I
YES
INFO
REPL
REP1
NO
No return value
OUT.U
LO
HI
OU1.U OU1.I
YES
REPL
REP1
OUT.I
xxxx
xxx
PC-X
65F2
DIAG.
REL.X
OFF
No saving
n0
PROG
ORIG
CSUM
Return value
REP2
NO
Awaiting transfer
C
3011
ARN
Saving
HI
OUT.I
PCOD
OLD
NEW
NO
NO
No return value
Return value
REP2
p30
LOAD
READ
COPY
Co
Transfer of programming
Indicates a writing of programming from the C to the
console (saving of a file)
Co
ERR
ERR
PROG
OPT
Other functions
Display of the minimum value
INF
SUP
CLrM
CLrA
CONS
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
Measures
The following parameters: measure of the sensor primary, final measure,
final measure min. and max. and the values of the analog outputs are
transmitted as a module and a unit associated with a position of the decimal point.
Eg.:
Word address Decimal value
10 094
12 289
Coding
module
dec. point / unit
BYTE
Sensor rupture
tYPE
0
1
Error messages
ERR1
OPEN
2000
OL
---ERxx
ERR
9. ANNEXE : MODBUS
point
BYTE
p31
Request sequence:
Table of units
Unit
Code
000
001
002
003
004
005
006
007
008
009
010
011
012
013
014
015
016
017
018
019
020
021
022
V
KV
A
KA
W
KW
MW
GW
VAr
KVAR
MVAR
GVAR
VA
KVA
MVA
GVA
Wh
KWh
MWh
GWh
VARh
KVARh
Code
Unit
023
024
025
026
027
028
029
030
031
032
033
034
035
MVARh
GVARh
Hz
Khz
Deg
Ohms
Kohms
h
mn
s
%
cos PHI
to 099 free
Code
100
101
102
103
104
105
106
107
108
109
110
111
112
113
114
115
116
117
118
119
120
121
Unit
Code
Unit
Code
Unit
C
F
%
mm
cm
m
km
mBar
Bar
Pa
Kpa
Kg/cm2
PSI
mCE
l/s
l/mn
l/h
m3/s
m3/mn
m3/h
tr/s
rad/s
122
123
124
125
126
127
128
129
130
131
132
133
134
135
136
137
138
139
140
141
142
143
mm/s
cm/s
m/s
m/mn
m/h
mm3
cm3
m3
g
kg
t
l
hl
Rpm
CP/mn
PH
mV AC
V AC
KV AC
mA AC
A AC
KA AC
144
145
146
147
148
149
150
151
152
153
154
155
156
157
158
159
160
161
162
163
164
165
166
mV DC
V DC
KV DC
mA DC
A DC
KA DC
Ohms
Kohms
Mohms
US.gal/s
US.gal/min
US.gal/h
US.gal
lb
C
imp
CP
mA
A
mA.h
A.h
V
mV
bit 8
bit 3
Slave Function
3 or 4
number
1 byte
Nbr of words
MSB
LSB
2 bytes
MSB
LSB
2 bytes
CRC 16
1 byte
2 bytes
Response sequence:
Slave Function
3 or 4
number
1 byte
Number
of read
bytes
1 byte
1 byte
LSB
MSB
LSB
2 bytes
2 bytes
bit 0
1 byte
2 bytes
2 bytes
1 byte
n bytes
Response sequence:
programming error
offset error
input calibration error
output calibration error
sensor rupture
measure overload
bit 0
bit 15
bit 3
bit 0
Numbr of
Slave Function 1st word
words to CRC 16
number
16
address
be enfor.
1 byte
1=relay ON
1=alarm recorded
2 bytes
2 bytes
1 byte
2 byte
2 bytes
2 bytes
Response sequence:
Slave Function
numbre
6
1=led lit
1=led blinking: mode
1 byte
1 byte
1 byte
1 byte
Address Value of
of the the word CRC 16
word to be enf.
2 bytes
2 bytes
Exception pattern:
Slave
number
Function
requested with
MSB=1
Error
code
CRC 16
1 byte
1 byte
1 byte
2 bytes
2 bytes
p32
03
Slave
number
Reading
of n
words
2
Address
byte 3
byte 4
CRC 16
measure
19
136
CRC 16
byte 1
byte 2
byte 3
byte 4
2 bytes
Number of words
byte 1
byte 2
0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 1 0 0 11 1 0 0 0 1 0 0 0
0
19
136
Sign : 0 positive
1 negative
no
n= n+1
no
measure
254
236
120
255
255
CRC 16
byte 1
byte 2
byte 3
byte 4
2 bytes
byte 3
byte 4
11111111
11111111
byte 1
byte 2
111 0 11 0 0 0 1111 0 0 0
Inversion
byte 4
byte 1
byte 2
0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 1 0 0 11 1 0 0 0 0 111
byte 3
byte 4
byte 1
byte 2
Adding +1 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 1 0 0 1 1 1 0 0 0 1 0 0 0
0
19
n>7
yes
next byte
no
end of sequence
yes
CRC poly CRC
carry
136
yes
END
Note 3:
The CRC16 calculation applies to all bytes in the sequence (except CRC16).
Note 4:
Caution! In the CRC 16, the 1st sent byte is the LSB.
Example: Sequence 1-3-0-75-0-2 CRC16 = 180-29 (the values are
decimal).
p33