Technical Specification of Electrical System for AR Jeans Producer Factory

Technical Requirement and Specification


Project Information:
AR Jeans Producer factory building.

Transformer Specification:
Supply, installation, testing and commissioning of following Oil Immersed Transformer technical data has
follows:
Three phased Oil Immersed transformers, ground mounted, indoor use, with standard accessories.
Designmanufacturing, routine tests & tolerances according to IEC76 & 726 standards.
Routine tests and first filling oil included.
Design, manufacturing, routine tests & tolerances
according to IEC 76 standards.
Standard fittings :
4 flat bi-directional rollers.

2 lifting lug
2 earthing points.
1 rating plate(on HV side)
1 Bucholz Relay.
1 Silica Gel with Box,
1 Temperature Meter.
HV connections : porcelain bushing
LV connections : porcelain bushing, without cable box.
Rated power in KVA
: 1250 kVA
Frequency
: 50Hz
System voltage
: 12KV
Primary voltage
: 1100
HV tapping by links(off circuit) in
: 2.5%, 5%, -7.5%
Secondary voltage
: 415V
HV impulse KV peak in KV
: 75 kV
Power frequency KV rms
: 28 kV
Vector group
: DYN11
Max. ambient temp. in Deg. C
: 40
Altitude lower thank in meter
: 1000
Temp. rise in winding/oil in Deg. C
: 65/55
No load loss
: 1100 W
Load loss at 75 Deg. C
: 10500W
Impedance voltage
: 5.5%

Page 1 of 1
Consultant: Electro-Mechanical Control Services (eMcS)