IEC 61850 Breaker Failure Demo IED Configuration

Guidelines
Timeline

ICD files due from each participant device (due July 25)
o only those devices can be part of the CIGRE demo
System engineering - Siemens, possibly others? (Begin Aug 1)
o Preliminary SCD/CID files for import into IED Config Tools (Aug 8)
o Second round of ICD files due (Aug 15)
o Final SCD/CID files available for testing (Aug 20)
Setup and test at Cigre (Sunday, Aug 24, 9AM)

ICD File
Pre-defined Dataset and pre-configured GOOSE Control Blocks (GCBs) to be included
in the ICD files
Otherwise specify what SCD should put into the dataset (specific FCDA statements).
See details below for Addressing, DataSets, and GOOSE publisher/subscriber info.

Dataset
Dataset of GOOSE must include data listed in sections below, but can include
additional data chosen by vendors.

Addressing
Each vendor will have a range of addresses to use. X is unique participation ID (from
Table 1) and Y is ordinal number of device from each vendor (first in SCL is 0, next is
1, etc.)
GOOSE addresses are 01-0C-CD-01-00-XY where XY in hex
SV addresses are 01-0C-CD-04-00-XY where XY in hex
IP addresses: 172.16.XX.YY (in decimal)
Netmask: 255.255.0.0
GOOSE APPID is 0x00XY where XY in hex
SV APPID is 0x40XY where XY in hex
VLAN ID is ZERO, VLAN Priority=4 for GOOSE/SV
GoID is Vendor_Device_XY

Table 1: Addressing by Vendor


Vendor

IED

0-15 (0-F)

PCS-9611

IED Number
(Z)
1

PCS-221

IRV-F0A6M

IRV -X0A6M

NR
2

0-15 (0-F)

ZIV
Schneider

0-15 (0-F)

MicomP642

SEL

0-15 (0-F)

SEL-751

0-15 (0-F)

AX-S4 61850 IED


Simulator

0-15 (0-F)

SIPROTEC4 7SJ80

SISCO

Siemens

Client

GOOSE Monitor

AX-S4 61850 Client

SIPROTEC5 - 7UT8
7

0-15 (0-F)

DNV GL

10

Client Simulator

UniCA 61850 Analyzer

HMI - Client

GOOSE Monitor

IED Simulator
8

0-15 (0-F)

0-15 (0-F)

SUBNET

Triangle
MicroWorks

Anvil IED Simulator

11

Bay Controller
Demo

12

10 (A)

0-15 (0-F)

F650

13

11 (B)

0-15 (0-F)

CB Controller

14

GE

Omicron

Hammer - Client

GOOSE Publishing/Subscribing
See Figure 1 below for an illustration of GOOSE messaging.
Each IED publishes 1 GOOSE for breaker failure with their own dataset but including
RBRF.OpEx
Each IED subscribes to 3 types of GOOSE messages:
Initiate: IEDs to subscribe to 3 different Extern GOOSE as input to PTRC
each Extern publishes a GOOSE with DataSet that includes multiple PIOCZ.Op
(Z=1-14, one for each IED according to IED Number in Table 1)
Breaker Failure: IEDs to subscribe to GOOSE from every other IED with
DataSet to include RBRF.OpEx
Reset (close breakers): IEDs to subscribe to 3 different Extern GOOSE as
input to XCBR Externs publishes CSWI.OpCls in broadcast GOOSE to all IEDs
Subscribers make observable the status and/or the Boolean of the SPS.stVal (this
means that each IED must show the status of the breaker position, failure, etc. on
the front panel in some fashion)
Vendors to specify (in writing) how to set up SCD file for subscriptions to external
GOOSE to show the state of the Boolean(s).
If possible, the Inputs/ExtRef section(s) should be set up within the ICD file to assist
the system configurator.

Figure 1: Breaker Failure IED Configuration

Breaker Failure Steps


1. Extern broadcasts initiate GOOSE to all IDEs PIOCZ.Op is set by Extern to
initiate breaker trip on one IED (Z=1-14, chose one IED to initiate demo according to
IED Number in Table 1)
2. PTRC reports Trip and sends message to RBFR1 and (either message to XCBR or
GOOSE to external XCBR1
3. XCBR sends Position (Pos) signals to RBRF or sends GOOSE to RBRF
4. If Discrepancy continues long enough (or change in Pos not detected by RBRF)
then RBRF broadcasts GOOSE to all IEDs (Breaker_Fail)
5. Extern sends CSWI.OpCls, CSWI.OpCls.q, and CSWI.OpCls.genral to all IEDs to
close breaker and reset demo (otherwise IED can attempt an auto re-close 30
seconds after breaker failure trip)

Extern GOOSE Messages


Each Extern will publish one GOOSE with the DataSet including:
Multiple PIOCZ.Op, PIOCZ.Op.q, and PIOCZ.Op.general (Z=1-14, one PIOC.Op for
each of the IEDs according to IED Number in Table 1)
CSWI.OpCls, CSWI.OpCls.q, and CSWI.OpCls.genral
Op, q, and general are included because some devices can only subscribe to simple
datatypes and some devices will not subscribe to simple types unless both value
and quality are present. IED to to use PIOC.Op as input to PTRC. IED can choose
which data is used for subscription.
CSWI.OpCls is used to reset the breaker failure scenario (1 GOOSE to set TRUE and
a second GOOSE about 1 second later to set it FALSE. IED to subscribe to this
GOOSE as input to XCBR. IED can choose which data is used for subscription.
All of these objects will be published in the same GOOSE (to reduce the number of
GOOSE configurations required for each participating device)
IED will subscribe to up to 3 total Extern GOOSE (1 from TMW, 1 from SISCO, 1 from
Omicron)

Front Panel Configuration


PTRC also has input from internal logic driven from front panel pushbutton for local
trip initiation.
Each vendor can chose how to display breaker status, breaker failure, GOOSE
messaging on front panel

Breaker Simulation
IED will need to simulate breaker operation including failure condition
Vendors may also choose to bring a physical breaker.
The concept is for booth visitors to have a visual indication of the breaker operation

Other System Configuration


If vendors wish to instantiate the same device multiple times, they should inform
Joe, Bruce, and Cedric
Switch vendors to set up switches to pass all GOOSE MACs to all devices and block
all SV except to those devices needing SV.

GOOSE Details for System Configuration


MAC XXX is SISCO Extern
MAC YYY is TMW Extern
MAC ZZZ is Omicron Extern
IED Number (Z) is defined in Table 1 and summarized here:

PCS-9611

IED Number
(Z)
1

PCS-221

IRV-F0A6M

IRV -X0A6M

Schneider

MicomP642

SEL

SEL-751

SISCO

AX-S4 61850 IED Simulator

SIPROTEC4 - 7SJ80

SIPROTEC5 - 7UT8

IED Simulator

10

Anvil IED Simulator

11

Bay Controller Demo

12

F650

13

Vendor
NR

ZIV

Siemens
DNV GL
Triangle MicroWorks
GE

IED

Omicron

CB Controller

14

Extern1 MAC=XXX GOOSE dataset:


CSWI.opCls.general (for reset of all IEDs)
PIOC1.Op.general
PIOC2.Op.general
PIOC3.Op.general
....
PIOC14.Op.general
Extern2 MAC=YYY Goose dataset:
CSWI.opCls.general (for reset of all IEDs)
PIOC1.Op.general
PIOC2.Op.general
PIOC3.Op.general
....
PIOC14.Op.general

Extern2 MAC=ZZZ Goose dataset:


CSWI.opCls.general (for reset of all IEDs)
PIOC1.Op.general
PIOC2.Op.general
PIOC3.Op.general
....
PIOC14.Op.general

IED 1 publishes GOOSE at XY Address defined in Addressing Section


with dataset: RBRF.OpEx.general
IED 2 publishes GOOSE at XY Address defined in Addressing Section
with dataset: RBRF.OpEx.general
IED 3 publishes GOOSE at XY Address defined in Addressing Section
with dataset: RBRF.OpEx.general

Vendor 14, IED 1 publishes GOOSE at XY Address defined in Addressing Section


with dataset: RBRF.OpEx.general

IED 1 subscribes to GOOSE at:


MAC XXX: PIOC1.Op.general - feeds to their PTRC
MAX XXX: CSWI.opCls.general - feeds to XCBR close
MAC YYY: PIOC1.Op.general - feeds to their PTRC
MAX YYY: CSWI.opCls.general - feeds to XCBR close
MAC ZZZ: PIOC1.Op.general - feeds to their PTRC
MAX ZZZ: CSWI.opCls.general - feeds to XCBR close
MAC for IED 2: RBRF.OpEx.general - feeds to their PTRC
MAC for IED 3: RBRF.OpEx.general - feeds to their PTRC
MAC for IED 4: RBRF.OpEx.general - feeds to their PTRC

MAC for IED 14: RBRF1.OpEx.general - feeds to their PTRC


IED 2 subscribes to GOOSE at:
MAC XXX: PIOC2.Op.general - feeds to their PTRC
MAX XXX: CSWI.opCls.general - feeds to XCBR close
MAC YYY: PIOC2.Op.general - feeds to their PTRC
MAX YYY: CSWI.opCls.general - feeds to XCBR close
MAC ZZZ: PIOC2.Op.general - feeds to their PTRC
MAX ZZZ: CSWI.opCls.general - feeds to XCBR close
MAC for IED 1: RBRF.OpEx.general - feeds to their PTRC
MAC for IED 3: RBRF.OpEx.general - feeds to their PTRC
MAC for IED 4: RBRF.OpEx.general - feeds to their PTRC

MAC for IED 14: RBRF1.OpEx.general - feeds to their PTRC


IED 3 subscribes to Extern XXX, Extern YYY, Extern ZZZ, IED 1, IED 2, IED 4, ...
IED 14

IED 13 subscribes to Extern XXX, Extern YYY, Extern ZZZ, IED 1, IED 2, IED 3, ...
IED 12, IED 14
IED 14 subscribes to Extern XXX, Extern YYY, Extern ZZZ, IED 1, IED 2, IED 3, ...
IED 12, IED 13

RCB and Client Configuration


The following Clients will subscribe to Report Control Blocks (RCBs) from the IEDs
(IED vendors will provide names of the RCBs that are relevant for the demo)
Vendor

Client

SISCO

AX-S4 61850 Client

DNV GL

Client Simulator

SUBNET

HMI - Client

Triangle MicroWorks

Hammer - Client

At a minimum the RCBs for the demo should include:

RBRF (Str, OpEx, OpIn)


PTRC (Str, Tr, Op)
XCBR (Pos)