Sunteți pe pagina 1din 20

Current Transformers

SM6 24 cubicles

Feasibility range
and referenced types

Catalogue 2004
Number: C019 rev. 1
pag. 1/20

CONTENTS

CURRENT TRANSFORMER
RECOMMENDATIONS FOR THE USE OF TABLES AND TECHNICALS NOTES

Page 3,4,5 and 6

PANEL TYPE CRM


REFERENCED TYPES

ARJP1/N2 F
ARJP2/N2 F

Page 7
Page 11

CONFIGURED TYPES

ARJP1/N1 F and ARJP1/N2 F


ARJP2/N1 F, ARJP2/N2 F and ARJP2/N3 F

Page 8 and 9
Page 12 and 13

REFERENCED TYPES

ARJP1/N2 F

Page 7

CONFIGURED TYPES

ARJP1/N1 F and ARJP1/N2 F

Page 8 and 9

PANEL TYPE QMC

PANEL TYPE DMV-A, DMV-D, IMC


REFERENCED TYPES

ARJP2/N2 F

Page 11

CONFIGURED TYPES

ARJP1/N1 F and ARJP1/N2 F


ARJP2/N1 F, ARJP2/N2 F and ARJP2/N3 F

Page 8 and 9
Page 12 and 13

PANELS TYPE 1250A

DM1-A, DM1-D, DM1-W, DM1-Z, GBC-A, GBC-B, DMV-A, DMV-D

REFERENCED TYPES

ARJP3/N2 F

Page 15

CONFIGURED TYPES

ARJP3/N1 F, ARJP3/N2 F and ARJP3/N3 F

Page 16

PANELS TYPE DM1-A, DM1-D, DM1-W, DM2, GBC-A, GBC-B


REFERENCED TYPES

ARM3/N2 F

Page 18

CONFIGURED TYPES

ARM3/N1 F and ARM3/N2 F

Page 19

NOTE:

N1, N2 and N3 MEAN THE NUMBER OF SECONDARIES


F MEANS THAT THERE IS NOT BASE PLATE

pag. 2/20

CURRENT TRANSFORMERS

PREFERABLY USE the equipment selected and marked as REFERENCED

RECOMMENDATIONS FOR THE USE OF THE


FEASIBILITY AND COMPUTATION SUPPORTS

_______________

CHECK NEEDS AND NECESSARY INFORMATION


ACCURATELY

USE EQUIPMENT MARKED AS REFERENCE

CHECK READLY AVAILABLE FEASIBILITY SECTIONS


DIRECTLY
TO APPLY KEYS TO FEASIBILITY TABLES
CORRECTLY, PLEASE SEE ON PAGE 4

USE ALSO ELONET TO CHECK FEASIBILITY

CONSULT US IF FEASIBILITY RANGE IS NOT


AVAILABLE OR FOR OTHERS CHARACTERISTICS

pag. 3/20

KEYS TO THE VARIOUS TABLES TO DEFINE FEASIBILITY

1)

Define Ipn rated primary current


Use primary values defined by standard (IEC):
10, 12,5, 20, 25, 30, 40, 50, 60 and 75 A and their decimal multiples.

2)

Define Ith rated short-time thermal current for 1 second


Short-circuit current usually lasts 1 second.
Should this value be different (equal to a lenght "t"), calculate the following:

Ith (for 1 sec.) = Ith x t


example:

3)

25 kA for 3 sec. >> 25 x 3 = 43,3 kA for 1 sec.

Calculate coefficient "K"


The above reperesents the key to the various tables

Ith for 1 sec.

K=
example:

4)

Ipn

Ipn = 100 A , Ith = 12,5 kA 1 sec. >> K = 12500 / 100 = 125

Finding position on the table


Locate column "K" and stop on the line corresponding to a value higher than K.
example:

5)

K calculate value = 125 >> ligne K = 150

Check feasibility
A possible current transformer will feature the performances shown in the columns
identified by boxes :
For perotection secondary is true, only for choosing in the catalogue, the following formule:

VA x FL = constant
example: 10VA 5P10 ( VA x FL= 10 x 10= 100 ) >> 5VA 5P20 ( VA x FL= 5 x 20= 100 )

pag. 4/20

TECHNICAL NOTES
Diagrams of the terminals markings according to IEC standard.

SINGLE RATIO
P1

P2

P1

S1

S2

1S1

CT with ONE
SECONDARY WINDING

P2

1S2

2S1

2S2

P1

1S1

CT with TWO
SECONDARY WINDINGS

P2

1S2 2S1
n da

2S2

3S1
dn

3S2

CT with THREE
SECONDARY WINDINGS

F WARNING !
The secondary open winding of a CT is dangereus!
The unused secondary windings of a CT must be short-circuited.
pag. 5/20

Current transformer with DOUBLE RATIO through primary coulping.


types ARM3
Burden values are the same for both ratios.
P1

C1

C2

P2

SERIAL PRIMARY COUPLING


LOW RATIO

P1

C1

C2

P2

PARALLEL PRIMARY COUPLING


HIGH RATIO

Current transformer with DOUBLE RATIO through connection on secondary.


types ARJP1, ARJP2, ARJP3

P1

S1

S2

P2

P1

S3

1S1

CT with ONE SECONDARY WINDING

P2

1S2

1S3 2S1

2S2

2S3

CT with TWO SECONDARY WINDINGS

S1-S2 LOW RATIO


S1-S3 HIGH RATIO

1S1-1S2 2S1- 2S2


1S1-1S3 2S1- 2S3

LOW RATIO
HIGH RATIO

H
Burden values are different for each of the two ratios

F WARNING !
The secondary open winding of a CT is dangereus!
The unused secondary windings of a CT must be short-circuited.
pag. 6/20

REFERENCED CURRENT TRANSFORMERS


Type ARJP1/N2 F
Panel type CRM - QMC

Dimensions

Drawing n H 103441

Characteristics

Standard reference IEC 60044-1


Rated highest voltage : 24 kV
Rated continous thermal current 1,2 x In
Frequency 50 and 60 Hz

CTs type ARJP1/N2F


Reference
number

Ratio

Short-time current
I th
t
(kA)
(s)

(A/A)

1st secondary

2nd secondary

51238639F0

10/5-5

1,2

15 VA cl. 0,5 Fs<10

2,5 VA 5P20

51238640F0

20/5-5

2,4

15 VA cl. 0,5 Fs<10

2,5 VA 5P20

51238641F0

30/5-5

3,6

15 VA cl. 0,5 Fs<10

2,5 VA 5P20

51238643F0

50/5-5

15 VA cl. 0,5 Fs<10

2,5 VA 5P20

51238644F0

75/5-5

10

15 VA cl. 0,5 Fs<10

2,5 VA 5P20

51238645F0

100/5-5

10

15 VA cl. 0,5 Fs<10

2,5 VA 5P20

51238646F0

150/5-5

10

15 VA cl. 0,5 Fs<10

2,5 VA 5P20

51238647F0

200/5-5

10

15 VA cl. 0,5 Fs<10

2,5 VA 5P20

For others characteristics see next page.


pag. 7/20

CONFIGURED CURRENT TRANSFORMER


Type ARJP1/N1 F - ARJP1/N2 F
Single Primary Ratio SR
Panels type CRM, DMV-A, DMV-D, IMC, QMC
Dimensions

Drawing n H 103441

Characteristics Standard reference IEC 60044-1


Rated highest voltage : 7,2 - 12 - 17,5 - 24 KV
Rated continous thermal current 1,2 x In
Frequency 50 or 60 Hz
Rated secondary current standard 5 or 1 A.
Table of options:
N of secondaries for CT

STANDARD TYPE

ARJP1/N1 F

ARJP1/N2 F
1st measure secondary

Classe 0,5 Fs = 10
VA
alternatively

5 7,5 10 15 20 20 30 30 30 30 30

"K"

Ipn

measure secondary

protection secondary

2nd protection secondary

K=Ith/Ipn

Rated primary

Ith max

current [A]

Cl. 0,5 Fs=10


VA

Cl. 5P Fl=10
VA

Cl. 5P Fl=10
VA

25 kA for 1s

SR

100

10 to 800

150

10 to 150

200

10 to 100

250

10 to 100

300

10 to 75

400

10 to 50

7,5 10 15 20 30 50 5 7,5 10 15 20 30 50 5 5 5 7,5 5 10 10 15 20 30 50

For others characteristics please contact us.


pag. 8/20

CONFIGURED CURRENT TRANSFORMER


Type ARJP1/N1 F
Double Primary Ratio DR
Panels type CRM, DMV-A, DMV-D, IMC, QMC
Dimensions

Drawing n H 103441

Characteristics

Standard reference IEC 60044-1


Rated highest voltage : 7,2 - 12 - 17,5 - 24 KV
Rated continous thermal current 1,2 x In
Frequency 50 or 60 Hz
Rated secondary current standard 5 or 1 A.
Double primary ratio through connection to secondary.

Value K=Ith/Ipn must de fixed in comparison with the smaller rated primary current ratio .
Values of outputs are gived for the smaller ratio, for the high ratio they are the double.
Table of options:
N of secondaries for CT

STANDARD TYPE

ARJP1/N1 F

alternatively

"K"

Ipn

measure secondary

protection secondary

K=Ith/Ipn

Rated
primary

Class 0,5
Fs = 10

Class 5P
Fl = 10

Ith max

current [A]

VA

VA

25 kA for 1s

DR

100

10-20 to 400-800

150

10-20 to 150-300

200

10-20 to 100-200

250

10-20 to 100-200

300

10-20 to 75-150

400

10-20 to 50-100

7 , 5 10 15 2 0 3 0 5 0 5 7,5 1 0 1 5 2 0 30 50

For others characteristics please contact us.


pag. 9/20

REFERENCED CURRENT TRANSFORMERS


Type ARJP2/N2 F
Dimensions

Drawing n H 103442

Characteristics

Standard reference IEC 60044-1


Rated highest voltage : 24 kV
Rated continous thermal current 1,2 x In
Frequency 50 and 60 Hz

Panel type CRM


CTs type ARJP2/N2F
Reference
number

Ratio

Short-time current
I th
t
(kA)
(s)

(A/A)
51238223F0

50 / 5-5

25

1st secondary

2nd secondary

10VA cl.0,5 Fs10

2,5VA 5P20

Panels type DMV-A, DMV-D, IMC


CTs type ARJP2/N2F
Reference
number

Ratio

Short-time current
I th
t

1st secondary

2nd secondary

(A/A)

(kA)

(s)

51238223F0

50 / 5-5

25

10VA cl.0,5 Fs10

2,5VA 5P20

51238224F0

100 / 5-5

25

15VA cl.0,5 Fs10

2,5VA 5P20

51238225F0

200 / 5-5

25

15VA cl.0,5 Fs10

5VA 5P20

51238226F0

400 / 5-5

25

15VA cl.0,5 Fs10

5VA 5P20

3730519

600 / 5-5

25

20VA cl.0,5 Fs<10

7,5VA 5P20

For others characteristics see next page.


pag. 11/20

CONFIGURED CURRENT TRANSFORMER


Type ARJP2/N1 F - ARJP2/N2 F - ARJP2/N3 F
Single Primary Ratio SR
Panels type CRM, DMV-A, DMV-D, IMC
Dimensions

Drawing n H 103442

Characteristics

Standard reference IEC 60044-1


Rated highest voltage : 7,2 - 12 - 17,5 - 24 KV
Rated continous thermal current 1,2 x In
Frequency 50 or 60 Hz
Rated secondary current standard 5 or 1 A.

Table of options:
n of secondaries for CT

STANDARD TYPE

ARJP2/N1 F

ARJP2/N2 F

ARJP2/N3 F
1st measure sec.

Class 0,5
Fs = 10
VA
5 10 15 20 30
2nd protection sec.

Class 0,5
Fs = 10
VA

Class 5P
Fl = 10
VA

5 7,5 10 15 20 20 30 30 30 30 30 5

alternatively

"K"

1st measure secondary

5 7,5 10 15

Ipn

measure secondary

protection secondary

2nd protection secondary

3rd protection sec.

K=Ith/Ipn

Rated

Ith max

current [A]

Class 0,5
Fs = 10
VA

Class 5P
Fl = 10
VA

Class 5P
FI = 10
VA

Class 5P
Fl = 15
VA

25 kA for 1sec.

SR

100
150
200
250
300
400
500

10 to 800
10 to 300
10 to 250
10 to 200
10 to 150
10 to 100
10 to 100

primary

7,5 10 15 20 30 50 5 7,5 10 15 20 30 50 5

5 7,5 5 10 10 15 20 30 50 5

5 7,5 10 15

Switch to smaller type ARJP1

For others characteristics please contact us.


pag. 12/20

CONFIGURED CURRENT TRANSFORMER


Type ARJP2/N1 F - ARJP2/N2 F
Double Primary Ratio DR
Panels type CRM, DMV-A, DMV-D, IMC
Dimensions

Drawing n H 103442

Characteristics

Standard reference IEC 60044-1


Rated highest voltage : 7,2 - 12 - 17,5 - 24 KV
Rated continous thermal current 1,2 x In
Frequency 50 or 60 Hz
Rated secondary current standard 5 or 1 A.
Double primary ratio through connection to secondary.

Value K=Ith/Ipn must de fixed in comparison with the smaller rated primary current ratio .
Values of outputs are gived for the smaller ratio, for the high ratio they are the double.

Table of options:
N of secondaries for CT

STANDARD TYPE

ARJP2/N1 F

ARJP2/N2 F
1st measure secondary

Cl. 0,5 Fs=10


VA
alternatively

5 7,5 1 0 1 5 2 0 2 0 3 0 3 0 3 0 3 0 3 0

"K"

Ipn

measure secondary

protection secondary

2nd protection secondary

K=Ith/Ipn

Rated primary

Ith max

current [A]

Cl. 0,5 Fs=10


VA

Cl. 5P Fl=10
VA

Cl. 5P Fl=10
VA

25 kA for 1s

DR

7,5 1 0 1 5 2 0 3 0 5 0

5 7,5 1 0 1 5 2 0 3 0 5 0

100

10-20 to 400-800

150

10-20 to 150-300

200

10-20 to 100-200

250

10-20 to 100-200

300

10-20 to 75-150

400

10-20 to 50-100

500

10-20 to 50-100

5 7,5

5 10 10 15 20 30 50

Switch to the smaller type ARJP1

For others characteristics please contact us.


pag. 13/20

REFERENCED CURRENT TRANSFORMERS


Type ARJP3/N2 F
Panels type DM1-A 1250A, DM1-D 1250A, DM1-W 1250A, DM1-Z 1250A,
GBC-A 1250A, GBC-B 1250A, DMV-A 1250A, DMV-D 1250A

Dimensions

Drawing n H 103443

Characteristics Standard reference IEC 60044-1


Rated highest voltage : 24 kV
Rated continous thermal current 1,2 x In
Frequency 50 and 60 Hz

CTs type ARJP3/N2F


Reference
number

Ratio

Short-time current
I th
t

1st secondary

2nd secondary

(A/A)

(kA)

(s)

3730521

1000 / 5-5

25

30 VA cl. 0,5 Fs<10

10 VA 5P20

3730522

1250 / 5-5

25

30 VA cl. 0,5 Fs<10

10 VA 5P20

3730525

1000 / 1-1

25

30 VA cl. 0,5 Fs<10

10 VA 5P20

3730526

1250 / 1-1

25

30 VA cl. 0,5 Fs<10

10 VA 5P20

For others characteristics see next page.


pag. 15/20

CONFIGURED CURRENT TRANSFORMER


Type ARJP3/N1 F - ARJP3/N2 F - ARJP3/N3 F
Single and Double Primary Ratio
Panels type DM1-A 1250A, DM1-D 1250A, DM1-W 1250A, DM1-Z 1250A,
GBC-A 1250A, GBC-B 1250A, DMV-A 1250A, DMV-D 1250A
Dimensions

Drawing n H 103443

Characteristics

Standard reference IEC 60044-1


Rated highest voltage : 7,2 - 12 - 17,5 - 24 KV
Rated continous thermal current 1,2 x In
Frequency 50 or 60 Hz
Rated secondary current standard 5 or 1 A.
Double primary ratio through connection to secondary.

Values of outputs are gived for the smaller ratio, for the high ratio they are the double.

Table of options:
N of secondaries for CT

STANDARD TYPE

ARJP3/N1 F

ARJP3/N2 F

ARJP3/N3 F
1st measure sec.

Cl. 0,5 Fs=10


VA
5 10 15 20 30

alternatively

1st measure secondary

2nd protection sec.

Class 0,5
VA

Cl. 5P Fl=10
VA

5 7,5 10 15 20 20 30 30 30 30 30 5

5 7,5 10 15

Ipn

measure secondary

protection secondary

2nd protection secondary

3rd protection sec.

Rated primary

Cl. 0,5 Fs=10


VA

Cl. 5P Fl=10
VA

Cl. 5P Fl=10
VA

Cl. 5P Fl=15
VA

current [A]

SR

DR

7,5 10 15 20 30 50 5 7,5 10 15 20 30 50 5

5 7,5 5 10 10 15 20 30 50 5

5 7,5 10 15

750
800
1000
1200
1250
400-800
500-1000
600-1200

For others characteristics please contact us.


pag. 16/20

REFERENCED CURRENT TRANSFORMERS


Type ARM3/N2 F
Panel type DM1-A, DM1-D, DM1-W, DM2, GBC-A, GBC-B
Dimensions

Drawing n H 103005

Characteristics

Standard reference IEC 60044-1


Rated highest voltage : 24 kV
Rated continous thermal current 1,2 x In
Frequency 50 and 60 Hz
Double primary ratio through primary coupling.

CTs type ARM3/N2F


Reference
number

Ratio

Short-time current
I th
t

1st secondary

2nd secondary

(A/A)

(kA)

(s)

51303122F0

40-20 / 5-1

12,5

0,8

7,5VA 0,5s Fs<10

1VA 10P30

51303123F0

100-50 / 5-1

12,5

0,8

7,5VA 0,5s Fs<10

1VA 10P30

51303124F0

200-100 / 5-1

12,5

7,5VA 0,5s Fs<10

1VA 10P30

51303125F0

400-200 / 5-1

12,5

7,5VA 0,5s Fs<10

1VA 10P30

3731090

10-20 / 5-5

7,5 VA cl. 0,5 Fs<10

5 VA 5P10

3731092

15-30 / 5-5

7,5 VA cl. 0,5 Fs<10

5 VA 5P10

3731094

20-40 / 5-5

12,5

0,8

7,5 VA cl. 0,5 Fs<10

5 VA 5P10

3731096

25-50 / 5-5

12,5

7,5 VA cl. 0,5 Fs<10

5 VA 5P10

3731097

25-50 / 5-5

12,5

0,8

7,5 VA cl. 0,5 Fs<10

5 VA 5P10

3731098

50-100 / 5-5

21

7,5 VA cl. 0,5 Fs<10

5 VA 5P15

3731099

50-100 / 5-5

14,5

30 VA cl. 0,5 Fs<10

5 VA 5P15 - 7,5 VA 5P10

3731100

75-150 / 5-5

25

7,5 VA cl. 0,5 Fs<10

5 VA 5P15

3731101

75-150 / 5-5

16

30 VA cl. 0,5 Fs<10

5 VA 5P15 - 7,5 VA 5P10

3731102

100-200 / 5-5

25
20

1
2

7,5 VA cl. 0,5 Fs<10

5 VA 5P15

3731103

100-200 / 5-5

16

30 VA cl. 0,5 Fs<10

7,5 VA 5P15 - 15 VA 5P10

3731104

200-400 / 5-5

25
20

1
2

7,5 VA cl. 0,5 Fs<10

5 VA 5P15

3731105

200-400 / 5-5

25

30 VA cl. 0,5 Fs<10

7,5 VA 5P15 - 15 VA 5P10

3731708

300-600 / 5-5

25
20

1
2

7,5 VA cl. 0,5 Fs<10

5 VA 5P15

3730426

300-600 / 5-5

25

30 VA cl. 0,5 Fs<10

7,5 VA 5P15 - 15 VA 5P10

For others characteristics see next page.


pag. 18/20

CONFIGURED CURRENT TRANSFORMER


Type ARM3/N1 F - ARM3/N2 F
Single and Double Primary Ratio
Panels type DM1-A, DM1-D, DM1-W, DM2, GBC-A, GBC-B

Dimensions

Drawing n H 103005

Characteristics

Standard reference IEC 60044-1


Rated highest voltage : 7,2 - 12 - 17,5 - 24 KV
Rated continous thermal current 1,2 x In
Frequency 50 or 60 Hz
Rated secondary current standard 5 or 1 A
Double primary ratio through primary coupling.

Value K=Ith/Ipn must de fixed in comparison with the smaller rated primary current ratio .

Table of options:
N of secondaries for CT

STANDARD TYPE

ARM3/N1 F

ARM3/N2 F
1st measure secondary

Cl 0,5 Fs=10
VA
alternatively

"K"

5 7,5 10 15 20 20 30 30 30 30 30

Ipn

measure secondary

protection secondary

2nd protection secondary

K=Ith/Ipn

Rated primary

Ith max

current [A]

Cl 0,5 Fs=10
VA

Cl 5P Fl=10
VA

Cl 5P Fl=10
VA

25 kA for 1s

SR

DR

100

10 to 800

10-20 to 400-800

150

10 to 300

10-20 to 300-600

200

10 to 300

10-20 to 300-600

250

10 to 200

10-20 to 200-400

300

10 to 150

10-20 to 150-300

400

10 to 100

10-20 to 100-200

500

10 to 50

10-20 to 100-200

7,5 10 15 20 30 50 5 7,5 10 15 20 30 50 5 5 5 7,5 5 10 10 15 20 30 50

For others characteristics please contact us.


pag. 19/20