OperatingInstructionsforMonitoringFeatures
(Drawing102196A)

Figure1
POWER ON FANS ON

ALARM

TRIP

OPERATING STA TUS

MAXIMUM
TEMP.
MEMORY

READ

RESET

LEFT
PHASE

CENTER
PHASE

RIGHT
PHASE

TABLE1:STEPMODE
OPERATION CONTROL

DISPLAY CONTROL

AUTO

MANUAL
ON

TE M PERATURE C

INSTRUMENT
AUTOMATICALLY
DISPLAYS PHASE WITH
HIGHEST TEMPERATURE.
PRESS PHASE BUTTONS
TOREAD CURRENT
PHASE TEMPERATURES.
PRESS ANDHOLD
"READ" BUTTONTHEN
PRESS LEFT, CENTEROR
RIGHT PHASE BUTTON
TO READMAXIMUM
TEMPERATURE MEMORIES
OF OTHERPHASES.
PRESS ANDHOLD
LEFT, CENTERANDRIGHT
PHASE BUTTONS
TO READ
MATHEMATICAL AVERAGE
OF THREE INPUTS.

10
PRESS AND HOLD
TO OPERATE SYSTEM TEST

FAN
MOD E
CONT ROL
PRESS
TO
SILENCE

LOCAL
ALARM

11
PRESS AND RELEASE
TOADVANCE TEST MODE

SYS TEM TEST CONTROL S


TES TMODE SE QUENCE
1.
2.
3.
4.

INSTRUMENT AMBIENT
FANS ON
ALARM ON
TRIP ON

5.
6.
7.
8.

4 THSET-POINT ON - OPTION
5 THSET-POINT ON - OPTION
5 THSET-POINT OFF - OPTION
4 THSET-POINT OFF - OPTION

9. TRIP OFF
10. ALARM OFF
11. FANOFF

1.INSTRUMENTAMBIENT
2.FANSON
3.ALARMON
4.TRIPON
5.4THSETPOINTON
OPTIONAL
6.5THSETPOINTON
OPTIONAL
7.5THSETPOINTOFF
OPTIONAL
8.4THSETPOINTOFF
OPTIONAL
9.TRIPOFF
10.ALARMOFF
11.FANOFF

1.Firsttime(asshipped)startupstatus
1.Fanmodeisautomatic.
2.Fanexerciserisoff.
2.Future"startup's"usecustomer'schoiceofprogrammedoperations.
1.ReferenceDrawing102196B.
2.Accesscodeisrequiredforallprogrammablefeatures.
3.DEFAULTCODEIS6777621.

3.Resetorrestartsoftware(ifinstrumentdoesnotrespondtocommands)
1.Pressandholdbuttons1,6,&9in169simultaneously.
2.Alllightsexceptfor"POWERON"willturnoff.
3.Releasethethreebuttons.
4.Instrumentsoftwarewillresettonormalstartupmode.
5.CheckinstrumentfuseifPowerOnstatuslightis"OFF".

4.Displaymaximumtemperaturememory.
1.Pressbutton1.
2.Displaywillindicatehighesttemperatureinmemory.
3.PhaseLED'swillindicatewhichphasetemperatureisdisplayed.

5.Displaymaximumtemperaturememory(MTM)ofotherphases
1.Pressandholdbutton1.Thenpress
2.Button3todisplayMTMofleftphaseor
3.Button4todisplayMTMofcenterphaseor
4.Button5todisplayMTMofrightphase.
5.Buttons4and5todisplayMTMofoptional4thinput.
6.Releasebutton1.

6.Erasemaximumtemperaturememories.
1.Pressbutton2toresetallMTM'stozero.
2.Maximumtemperaturememoriesinclude
1.Allthreephasesand
2.Optionalfourthtemperaturesensor.

7.Displaycurrentoperatingtemperatures
1.Pressbutton3or4or5todisplaycurrentphasetemperatures.
2.Pressbuttons4&5todisplayoptional4thinputtemperature.
3.Pressandholdbuttons3,4,&5todisplaymathematicalaverageofthe
threephasetemperatures.
ReferenceDrawings102196A,B,C

8.Operationcontrols
1.Fanmode
1.Startupisalwaysinautomaticmode.
2.Pressbutton7formanualonmode.
3.Pressbutton6forautomaticmode.
2.Alarmcontrol
1.Pressbutton9tosilencelocalalarm.
2.Remotealarmrelayremains"on"untilalarmconditionclears.

9.SYSTEMTEST(generaldescription)
(forstartuptestorchecksetpointsandrelays)
1.ReferenceTable1fortestmodesequence
2.Pressandholdbutton10then
(NOTE:Usermustholdbutton10untildesiredstepsinTABLE1are
complete.)
3.Pressandreleasebutton11toadvanceTESTMODEonestep.

10.SYSTEMTESTsequentialactionsoftestmodeare:
1.InstrumentambienttemperatureisdisplayedandallotherLED'sturn
on.
2.Fansonsetpointtemperatureisdisplayed.
1.FansonLEDisturnedon.
2.Fansrelaysareturnedon.
3.Alarmonsetpointtemperatureisdisplayed.
1.AlarmonLEDisturnedon.
2.Alarmrelayisturnedon.
3.Localalarmisturnedon.
4.Localalarmcanbesilencedifdesired.
4.Triponsetpointtemperatureisdisplayed.
1.TriponLEDisturnedon.
2.Triprelaywillnotturnon.
3.Triprelayturnsononlywithinputsignal.
5.Fourthsetpointontemperatureisdisplayed.
(Displaywillindicate180ifsetpointisnotactivated.)
1.100'sdecimalpointisturnedon.
2.Fourthsetpointrelayisturnedon.
6.Fifthsetpointontemperatureisdisplayed.
(Displaywillindicate180ifsetpointisnotactivated.)
1.10'sdecimalpointisturnedon.
2.Fifthsetpointrelayisturnedon.
7.Fifthsetpointofftemperatureisdisplayed.
(Displaywillindicate166ifsetpointisnotactivated.)
1.10'sdecimalpointwillblink.
2.Fifthsetpointrelaywillturnoff.
8.Fourthsetpointofftemperatureisdisplayed.
(Displaywillindicate175ifsetpointisnotactivated.)
1.100'sdecimalpointwillblink.
2.Fourthsetpointrelaywillturnoff.
9.Tripoffsetpointtemperatureisdisplayedand
triponLEDwillblink.
10.Alarmoffsetpointtemperatureisdisplayed.
1.AlarmonLEDwillblink.
2.Alarmrelaywillturnoffor
3.Localalarmwillturnoffifnotpreviouslysilenced.
11.Fansoffsetpointtemperatureisdisplayed.
1.FansonLEDwillblink.
2.Fanrelayswillturnoff.

access_code_00.docx
01172011

CimcoElectronics,Inc.
P.O.Box1338
McMurray,PA15317
Phone:7249418001
Fax:7249418002

www.cimcoelectronics.com
cimco@cimcoelectronics.com

4.TurnFANEXERCISERon
1.RepeatACCESSCODEproceduresifbutton10hasbeenreleased.
2.Pressandreleasebutton9then
3.Pressandreleasebutton1.
4.Releasebutton10toturnfanexerciseron.
5.ClockstartsinAUTOONrunningmode.

6.FANSOFFMODEstatusduringfanexerciser"ontime";
1.ClockcontinuestorunduringFANSOFFmode.
Figure1
POWER ON FANS ON
ALARM
TRIP
2.FanpoweristurnedoffduringFANSOFFmode
OPERATING STA TUS

TABLE1:STEPMODE
OPERATION CONTROL
5.SelectFANEXERCISER"ontime"
DISPLAY CONTROL
1.INSTRUMENTAMBIENT
1.ENTERACCESSCODE
MAXIMUM
2.FANSON
AUTO
TEMP.
1
2
6
MEMORY
2.Select"ontime"withoneofthefollowingchoices.
3.ALARMON
READ
RESET
TE M PERATURE C
1.Pressandreleasebutton3fortwohoursor
4.TRIPON
MANUAL
LEFT
2.Pressandreleasebutton4foronehouror
3
7
ON
PHASE
5.4THSETPOINTON
INSTRUMENT
AUTOMATICALLY
3.Pressandreleasebutton5foroneminuteor
DISPLAYS PHASE WITH
OPTIONAL
HIGHEST TEMPERATURE.
FAN
PRESS PHASE BUTTONS
4.Pressandreleasebutton6toaddoneminuteor
CENTER
TOREAD CURRENT
MOD E
6.5THSETPOINTON
4
PHASE
PHASE TEMPERATURES.
CONT ROL
5.Pressandreleasebutton7tosubtractoneminute.
OPTIONAL
PRESS ANDHOLD
3.Releasebutton10andthe"ontime"isselected.
"READ" BUTTONTHEN
PRESS
PRESS LEFT, CENTEROR
7.5THSETPOINTOFF
LOCAL
RIGHT
TO
RIGHT PHASE BUTTON
9 ALARM
5
PHASE

TO READMAXIMUM
SILENCE
TEMPERATURE MEMORIES
OPTIONAL
OF OTHERPHASES.
6.TurnFANEXERCISERoff
8.4THSETPOINTOFF
PRESS ANDHOLD
1.ENTERACCESSCODE
10
11
LEFT, CENTERANDRIGHT
OPTIONAL
PHASE BUTTONS
TO READ
2.Pressandholdbutton10then
PRESS AND HOLD
PRESS AND RELEASE
MATHEMATICAL AVERAGE
9.TRIPOFF
OF THREE INPUTS.
TO OPERATE SYSTEM TEST
TOADVANCE TEST MODE
3.Pressandreleasebutton9then
10.ALARMOFF
SYS TEM TEST CONTROL S
4.Pressandreleasebutton2.
TES TMODE SE QUENCE
11.FANOFF
1. INSTRUMENT AMBIENT 5. 4 THSET-POINT ON - OPTION
9. TRIP OFF
5.Releasebutton10toturnfanexerciseroff.
6. 5 THSET-POINT ON - OPTION
10. ALARM OFF
2. FANS ON
3. ALARM ON
7. 5 THSET-POINT OFF - OPTION
11. FANOFF

4. TRIP ON
8. 4 THSET-POINT OFF - OPTION

7.ACCESSCODEISTURNEDOFFwhenbutton10isreleased.
1.ACCESSCODEisrequiredforallprogrammablefeatures.

1.Transformermanufacturermaintainscontrolof"CODE".
8.SeeDrawing102196CforRELAYONelapsedtimemonitoring
Cimcosuppliesstandardcode.DEFAULTCODEIS6777621.
instructions.
Customermayselectcode.

2.Instructionsforeachprogrammablefeature

aredescribedinItems2,3,4,5,or6onthispage.

Table2
3.Accesswillbeturnedonwiththefollowingsteps.

1.OperatingstatusLED'sindicatedwhichsetpointisavailableforchange.
1.Pressandholdbutton10untilprogrammableselections

1.For"on"setpointsLED'sdonotblink.
arecompleted.

2.For"deadband"LED'sblink.
2.Entersevendigitaccesscode.

3.Fourthsetpoint(optional)isassociatedwith100'sdecimalpoint.
3.A"beep'willindicateacceptanceof"code".

4.Fifthsetpoint(optional)isassociatedwith10'sdecimalpoint.
4.Continuetoholdbutton10untilchangesarecomplete.

2.Fansonsetpointchangesinfivedegreeincrements.
1.Steps2,3,4,5,and6canbeexecutedassingleactionsor

3.Allsetpointanddeadbandsexceptfansonchangeinonedegree
2.Steps2,3,4,5,and6softwareselectionscanbecompleted

increments.
withoneACCESSCODEinput.

4.Deadbandlimitsarefixedtohelppreventmistakes.
5.RepeatACCESSCODEproceduresifbutton10isrelease

1.Fanrelaydeadbandmaximumis50C.
beforeallsoftwareselectionsarecompleted.

2.Fanrelaydeadbandminimumis10C.

3.Allotherdeadbandmaximumsare10C.
2.Change"ONSETPOINTS"(referencetable1&2)

4.Allotherdeadbandminimumsare3C.
1.Pressandreleasebutton11toselectsetpointrequiringchange.

5.Fanexerciser
2.Pressbutton6oncetoincrease"TEMPERATUREON"oneincrement.

1.Minimumontimeisoneminute.
3.Pressbutton7oncetodecrease"TEMPERATUREON"one

2.Maximumontimeistwohours.
increment.

3.Offtimeisoneweekonly.

6.Fourthsetpointrelayisoptional.
3.Change"DEADBAND"(referencetables1&2)

7.Fifthsetpointrelayisoptional.
1.DEADBANDisdefinedasthedifferencebetween

8.Fourthinputsensorsareoptional.
setpointonandsetpointoff.

9.Setpointmonitoring"on"timesarein100'sofhours.
2.Pressandreleasebutton11toselectdeadbandrequirechange.

3.Pressbutton6oncetoincrease"DEADBAND"oneincrement.

4.Pressbutton7oncetodecrease"DEADBAND"oneincrement.

OperatingInstructionsforProgrammableFeatures
(Drawing102196B)
ReferenceTable1andTable2onthisdrawing
Referencedrawing102196A

ReferenceDrawings102196A,B,C

access_code_00.docx
01172011

CimcoElectronics,Inc.
P.O.Box1338
McMurray,PA15317
Phone:7249418001
Fax:7249418002

www.cimcoelectronics.com
cimco@cimcoelectronics.com

OperatingInstructionsforMonitoringTemperatureTrends
(Drawing102196C)
ReferenceDrawings102196A&102196B

Figure1
POWER ON FANS ON

ALARM

TRIP

OPERATING STA TUS

MAXIMUM
TEMP.
MEMORY

READ

RESET

LEFT
PHASE

CENTER
PHASE

RIGHT
PHASE

TABLE1:STEPMODE
OPERATION CONTROL

DISPLAY CONTROL

AUTO

MANUAL
ON

1.INSTRUMENTAMBIENT
2.FANSON
3.ALARMON
4.TRIPON
5.4THSETPOINTON
OPTIONAL
6.5THSETPOINTON
OPTIONAL
7.5THSETPOINTOFF
OPTIONAL
8.4THSETPOINTOFF
OPTIONAL
9.TRIPOFF
10.ALARMOFF
11.FANOFF

TE M PERATURE C

INSTRUMENT
AUTOMATICALLY
DISPLAYS PHASE WITH
HIGHEST TEMPERATURE.
PRESS PHASE BUTTONS
TOREAD CURRENT
PHASE TEMPERATURES.
PRESS ANDHOLD
"READ" BUTTONTHEN
PRESS LEFT, CENTEROR
RIGHT PHASE BUTTON
TO READMAXIMUM
TEMPERATURE MEMORIES
OF OTHER PHASES.
PRESS ANDHOLD
LEFT, CENTERANDRIGHT
PHASE BUTTONS
TO READ
MATHEMATICAL AVERAGE
OF THREE INPUTS.

10
PRESS AND HOLD
TO OPERATE SYSTEM TEST

FAN
MOD E
CONT ROL
PRESS
TO
SILENCE

LOCAL
ALARM

11
PRESS AND RELEASE
TOADVANCE TEST MODE

SYS TEM TEST CONTROL S


TES TMODE SE QUENCE
1.
2.
3.
4.

INSTRUMENT AMBIENT
FANS ON
ALARM ON
TRIP ON

5.
6.
7.
8.

4 THSET-POINT ON - OPTION
5 THSET-POINT ON - OPTION
5 THSET-POINT OFF - OPTION
4 THSET-POINT OFF - OPTION

9. TRIP OFF
10. ALARM OFF
11. FANOFF

SPECIALNOTES FORTEMPERATURETRENDDATA

1.Schedulefanmotormaintenance.
2.Monitorfansontime.
3.Monitoralarmontime.
4.Monitortripontime.
5.Dataforcalculatingconsumedlifeoftransformer
insulation.
6.Timeisdisplayedin100'sofhours.
1.Accuracyisplus0andminus1hour.
2.Maximumreadingis25,500hours.
3.Automaticresettozeroafter25,500hours.

1.ACCESSCODEisrequiredforallprogrammablefeatures.
1.Transformermanufacturermaintainscontrolof"CODE".
DEFAULTCODEIS6777621.
2.Accesswillbeturnedonwiththefollowingsteps.
1.Pressandholdbutton10untildesiredoperations
arecompleted.Enteraccesscodeagainifrequired.
2.Entersevendigitaccesscode.
3.A"beep"willindicateacceptanceof"code".
4.Followinstructionsinitems2,3,or4onthispage.
3.Continuetoholdbutton10untilallchangesarecompleted.
1.StartStep2andcontinuethroughSteps3and4or
2.PerformStep1orStep2orStep3

2.Monitorfansonelapsedtime
1.Toread
1.Pressandreleasebutton3.
2.Displaywillindicateelapsedtimeinhundredsofhours.
3.Pressandreleasebutton3thencontinuetoStep3.1.2.
2.Toeraseorresettimetozero
1.Pressandholdbutton10then
2.Pressandreleasebutton4then
3.Pressandreleasebutton2.
4.Displaywillindicatethreezeroes.

4.Monitortriponelapsedtime
1.Toread
1.Pressandreleasebutton5.
2.Displaywillindicateelapsedtimeinhundredsofhours.
2.Toeraseorresettimetozero
1.Pressandreleasebutton5then
2.Pressandreleasebutton2.
3.Displaywillindicatethreezeroes.

5.ACCESSCODEISTURNEDOFFwhenbutton10isreleased.

ReferenceDrawings102196A,B,C