Mantenimiento de transformadores
Ing. Guillermo Rodriguez
g.rodriguez.r@ieee.org
SanSalvadorAbril13al15/2016
Referencias
IEEE C57.93-2007 IEEE Guide for Installation and Maintenance of Liquid-Immersed Power Transformers
Power Transformer Maintenance and Application Guide, EPRI, Palo Alto, CA: 2002. 1002913.
IEEE Std C57.104-1991, IEEE Guide for the Interpretation of Gases Generated in Oil-Immersed
Transformers.
IEEE Std C57.106-2002, IEEE Guide for Acceptance and Maintenance of Insulating Oil in Equipment.
IEEE Std 62-1995, IEEE Guide for Diagnostic Field Testing of Electric Power Apparatus
ASTM D923-2015 Standard Practices for Sampling Electrical Insulating Liquids
ASTM D1816-2004, Standard Test Method for Dielectric Breakdown Voltage of Insulating Oils of Petroleum
Origin Using VDE Electrodes.2
ABB- 1ZCL000002EG-EN rev. 1 User's Manual Operation and Maintenance for Power Transformers
Cooper Power Industries - S210-15-10 - Substation Transformer Installation, Operation, and Maintenance
Instructions and Parts Replacement Information
Ernesto Gallo ACIEM, Curso de transformadores 2008- Diagnstico y mantenimiento de Transformadores
inmersos en Aceite Mineral Aislante (En FRIO y ENERGIZADO)
Mantenimiento
Definicin:
Es asegurar el funcionamiento continuo de todo activo.
Objetivo:
Asegurar la competitividad de la empresa por medio de:
Garantizar la disponibilidad y confiabilidad planeadas de la funcin.
Satisfacer todos los requisitos del sistema de calidad de la
empresa.
Cumplir normas de seguridad y medio ambiente.
Maximizar el beneficio global.
Tipos de Mantenimiento
Predictivo
Preventivo
Detectivo
Correctivo
Mejorativo
Generalidades
Eltransformadornotienepartesrodantesporlotantorequieremenor
cuidadocomparadoconotrosequiposelctricos.
Elgradodemantenimientoeinspeccinnecesariosparasuoperacin
dependede:
sucapacidad,
delaimportanciadentrodelsistemaelctrico,
dellugardeinstalacindentrodelsistema,
delascondicionesclimatolgicas,
delambiente
y,engeneral,delascondicionesdeoperacin.
Inspeccin visual
No destapar, la humedad es el principal enemigo del transformador
Limpieza de aisladores
Transformadores CSP chequear la luz de sealizacin
Chequear la carga (se puede hacer con un programa TLM)
Inspeccin visual
No destapar, la humedad es el principal enemigo del transformador
Limpieza de aisladores
Registrar la informacin sobre nivel de aceite, temperatura del aceite,
presin de vaco
Chequear que los elementos como codos, etc se encuentren en buen
estado
Chequear la conexin a tierra y ver el estado de la base de concreto
Chequear la carga (se puede hacer con un programa TLM)
Inspeccin visual
Para transformadores la inspeccin visual debe hacerse por lo menos 4
veces al ao.
En sitios donde las condiciones anormales prevalecen tales como polvo
excesivo, gases corrosivos etc, los bushings deben ser regularmente
inspeccionados y limpiados.
Los radiadores deben mantenerse limpios y libres de cualquier
obstruccin que interfiera con el flujo del aire de ventilacin. Tambin hay
que revisar los radiadores por problemas de corrosin. .
En los tableros de control exterior se deben mantener limpias todas las
rejillas de ventilacin.
Inspeccin visual
El cableado de los accesorios debe mantenerse, debe ser chequeado
detalladamente por lo menos una vez al ao y reemplazarlo si esta
daado, las alarmas deben ser chequeadas tambin.
La conexin a tierra debe ser chequeada anualmente para medir la
cointinuidad entre el tanque y la tierra.
En unidades selladas, el medidor de presin vaco debe ser chequeada
diariamente la primera semana, despus cada 3 meses por el primer ao
y despus anualmente. Es evidencia de una fuga en el sistema o un
medidor daado si el medidor lee cero bajo diferentes condiciones de
carga
Inspeccin visual
Para transformadores crticos el nivel de aceite debe ser chequeado
diariamente por la primera semana, despus cada tres meses y despus
cada ao. Tambin se debe chequear el nivel de aceite de los aisladores
con la misma frecuencia, si el transformador tiene estos aisladores.
Transformadores con equipo auxiliar para enfriamiento tales como
ventiladores y bombas deben tener las siguiente pruebas:
Opere los ventiladores (chequear si la direccin de rotacin es la
correcta y chequear por aspas rotas en los ventiladores)
Opere las bombas (chequear indicador de flujo de lquido para el flujo
correcto y la direccin de el, y tambin chequear para ruido excesivo ).
Si el transformador tiene cambiador bajo carga algunos fabricantes de
cambiadores especifican la primera inspeccin basados o en el perodo
de tiempo especificado por ellos o en el nmero de operaciones.
Rigidez dielctrica
Tensin superficial (interfacial)
Cantidad de agua.
ndice de neutralizacin
Prdida dielctrica a 25C
Color
Gravedad especifica
Rigidez dielctrica
Es la medida de la resistencia que el aceite aislante
presenta al impacto elctrico.
Esta prueba es la indicada para comprobar la presencia
de agentes contaminantes como el agua, impurezas, fibras
celulsicas hmedas, partculas metlicas o conductoras
en el aceite, pudiendo existir concentraciones significativas
cuando se presenta bajo tensin.
Aceite Nuevo : ASTM D 1816 48 kV mnimo
Aceite Usado : ASTM D 1816 32 kV mnimo
Contenido de Agua
Color
El aceite aislante debe tener un color claro y ser
pticamente claro de tal manera que permita la
inspeccin visual dentro del tanque del equipo. Cualquier
cambio de color en el tiempo es una indicacin del
deterioro o contaminacin del aceite ..
Aceite sobrecalentado
Proporcinrelativa(%)
Aceitesobrecalentado
Gas
Figura 3 IEEE C57.104-2008
Descomposicin de la celulosa
Proporcinrelativa(%)
Celulosasobrecalentada
Gas
Figura 3 IEEE C57.104-2008
Descargas parciales
DescargaParcialenelaceite
Proporcinrelativa(%)
Arcos en el aceite
Proporcinrelativa(%)
Arcosenelaceite
Gas
Figura 3 IEEE C57.104-2008
Status
H2
CH4
C2H2
C2H4
C2H6
CO
CO2
TDCG
Condicin 1
100
120
35
50
65
350
2,500
720
Condicin 2
101 - 700
121 - 400
36 - 50
51 - 100
66 - 100
351 - 570
2,500 - 4,000
721 - 1,920
Condicin 3
701 - 1,800
401 - 1,000
51 - 80
101 - 200
101 - 1,150
571 - 1,400
4,001 - 10,000
1,921 - 4,630
Condicin 4
> 1,800
> 1,000
> 80
> 200
> 150
> 1,400
> 10,000
> 4,630
Tabla 1
Condicion 1
< 10
10 - 30
> 30
Condicin 4
< 10
10 - 30
> 30
< 10
10 - 30
> 30
< 10
10 - 30
> 30
Intervalo de
nuestreo
Acciones a tomar
Anualmente o
semestralmente
para trafos de
alta tensin
Continue operacin normal
Trimestralmente
Mensualmente
Diariamente
R1: CH4
C2H4
H2
R5 : C2H4
C2H6
0,1 - 3,0
0,1 - 1,0
> 3,0
< 0,1
1,0 - 3,0
< 0,1
> 1,0
1,0 - 3,0
< 0,1
> 1,0
> 3,0
Tabla 2
Oxigeno
Agua
Temperatura
Compuestos
polares
ACEITE
REGENERACION
Proceso Reversible
TERMOVACIO
Acidos
Lodos
CamaradeVaco
Tablerode
control
Filtros
Bomba
devacio
SECADO DE TRANSFORMADORES
La mayor parte del aislamiento slido de un transformador est
constituido de materiales de naturaleza celulsica (papel, cartn,
madera) que tiene una elevada rigidez dielctrica si estn secos.
Cuando en un aceite los ensayos realizados presentan valores
aceptables y slo el grado de humedad es elevado, se puede retirar esta
humedad an teniendo el transformador energizado. Para efectuarlo se
usa el secado por termovacio.
Cuando el aceite presenta un contenido de agua elevado(por encima
de los valores de orientacin recomendados), ocurre la impregnacin
en los materiales celulsicos del transformador, siendo necesario un
completo secado del transformador.
El sistema de secado completo consiste en retirar el equipo de
operacin, secar el liquido aislante a travs del sistema termovacio y
secar la parte activa en un horno, proceder a encubar la parte activa del
transformador y llenado con el aceite ya tratado.
Termografia
En el mbito industrial la aplicacin de la termografa en el rea de
mantenimiento es una de las ms difundidas.
La Termografa Infraroja en el rea de mantenimiento presenta ventajas
comparativas inigualables, Quiz sea el ensayo mas divulgado y
exitoso de los ltimos aos.
Se complementa eficientemente con los otros ensayos del
mantenimiento
El anlisis de lubricantes, el anlisis de vibraciones, el ultrasonido, etc.
Lodo en el
Tanque de expansin
Flujo de aceite en el
transformador
Piezas a Inspeccionar
Termmetros
Accesorios con contactos de alarma y/o disparo
Ventiladores de refrigeracin
4
5
6
7
8
Conservador
Resistencia de aislamiento de los devanados
Medicin de Tangente Delta
Aceite
Componentes del interior
Bitcora mantenimiento
Anotelaslecturasdelosmedidoresqueestninstalados,cuandolas
lecturasseanmuydiferentesdelasobtenidasencondiciones
normales,esnecesariorealizarunacuidadosaverificacin.
Ademsdeloanterior,sedebeprestaratencinalosfenmenos
anormalestalescomoruido,cambiodecolorodeolores,quepuedan
detectarseatravsdelossentidos.
Programa de mantenimiento
TemperaturadelTransformador
Latemperaturadeltransformadorestadirectamenterelacionadacon
laduracindelosmaterialesdeaislamiento,porloqueesnecesario
prestarleatencin.
Indicador
de temperatura de
Los devanados
Indicador de
Temperatura del aceite
Programa de mantenimiento
InspeccindelVolumendeaceite
Elvolumendelaceitetienesiemprequeserverificadodesdeel
puntodevistadelaislamientoydelarefrigeracin.
Cuandoelniveldeaceitefluctenotoriamenteenrelacinconla
temperatura,sedebedetectarlacausaparaunoportunoarreglo.
Indicador de Nivel
Programa de mantenimiento
Ruido
Lassiguientessonlascausasposiblesderuidoanormal:
o Resonanciadelacajaydelosradiadoresdebidoacambiosanormales
enlafrecuencia.
o Defectoenelmecanismodeajustedelncleo.
o Aflojamientodelaspiezasdeanclaje.
o Ruidoanormalpordescargaesttica,debidoapartesmetalicas
carentesdetierraoalaimperfeccindelapuestaatierra.
Programa de mantenimiento
Aflojamientodelaspiezasdefijacinydelasvlvulas
Cuandoencuentrelosterminalesdetierraflojos,desenergiceel
transformadoryapritelosenseguida.
Lostornillosdeloscimientosqueestnsujetosagrandescargas,debenser
apretadosfirmementeparaevitareldesplazamientodeltransformador.
FugasdeAceite
Lasfugasdeaceitepuedensercausadasporeldeteriorodealgn
empaqueopormalposicionamiento,verifiquecuidadosamentelas
vlvulasylosempaques.
PRUEBA DE TRANSFORMADORES EN
CAMPO
PRUEBADERESISTENCIADEAISLAMIENTOENTRANSFORMADORES
Laresistenciadeaislamientosedefinecomoelvalordelaresistenciaenmegaohms,
queofreceunaislamientoalaplicarleunvoltajedecorrientedirectaduranteun
tiempodadoymedidoapartirdelaaplicacindelmismo.Seusacomoreferencia
detiempode1a10min
Resistencia mnima de aislamiento en aceite a 20C
Voltaje entre
Voltaje entre
fases kV
Megohms
fases kV
Megohms
1.2
32
92
2480
2.5
68
115
3100
5
135
138
3720
8.66
230
161
4350
15
410
196
5300
25
670
230
6200
34.5
930
287
7750
46
1240
345
9300
69
1860
PRUEBA DE TRANSFORMADORES EN
CAMPO
Monitoreodetransformadores
ANALIZADOR DE GASES
Monitoreodetransformadores
ANALIZADOR DE GASES Y
DETECTOR DE HUMEDAD
Monitoreodetransformadores
BUSHINGS
Monitoreodetransformadores
MONITORES DE TEMPERATURA
TEC
Transformer Electronic
Control