Sunteți pe pagina 1din 15

Use of Desuperheater in Refrigeration

1. INTRODUCTION

The basic refrigeration system or air-conditioning system consists of removal


of heat from one source and expelling this heat to atmosphere, treating
atmosphere as heat sink. The removal of heat in general is known as cooling
effect and represented in generic term as tons of refrigeration. The expelled
heat to atmosphere can be convert into useful heat. Advancement of
Technology has developed different application to use this rejected heat.
Simultaneous requirement of heating load when cooling is generated are
most efficient form of applications where recovered heat results in obvious
savings in operating costs. This also improves cooling performance of
refrigeration cycle.

Heat Recovery Desuperheater in refrigeration cycle has obvious commercial


benefits that have been commercial exploited in recent past. A desuperheater
is supplementary heat exchanger in refrigeration condensing section and is
able to recover heat at temperatures substantially above the condensing
temperature.

AEC/MECH/2009 1
Use of Desuperheater in Refrigeration

orato 2. BASIC REFRIGERATION CYCLE:


From
Evap

Condenser
r

CT water

To Evaporator
Compressor

SLHE

TEV

Chilled Water

Fig. 1 Basic Refrigeration cycle

As shown in figure 1 the basic refrigeration cycle has four components


evaporator coils, compressor, condenser coils and throttling valve. The
evaporator coils provides us with the refrigerating effect. The compressor in
the cycle necessarily handles refrigerant in gaseous form and system design

AEC/MECH/2009 2
Use of Desuperheater in Refrigeration

necessitates avoiding use of liquid refrigerant reaching to compressor.


Superheating the gas in evaporator ensures this.

The compressor raises the pressure of the refrigerant by adiabatic


compression. By Ideal gas law the temperature of gas is also increased.
Condenser performs three fundamental operations
(a) Cooling the superheated gas to condensing temperature
(b) Condensing the gas by removing latent heat of the gas and then
(c) Sub-cooling the condensate.

Refrigerant is then passed through throttling valve where the pressure of


refrigerant is lowered to evaporating pressure. This low-pressure liquid is
passed through the evaporating coils that transform liquid back into vapour.
This evaporation of refrigerant is known as cooling effect. The cycle repeats in
continuous mode.

The major effects of refrigeration cycle are latent heat of condensing in


condenser and latent heat of evaporation in chiller. These two latent heat
quantities define performance of refrigeration. By forcing the refrigerant to
condense from a gas to a liquid, latent heat is transferred from the refrigerant
to the other medium. Conversely, by forcing the liquid refrigerant to change
into a gas inside the evaporator, heat is removed. The other forms of heat in
refrigeration cycle such as superheat in compression and sensible heat in
condensation are necessary elements for working of cycle. The suction line
heat exchanger is optional accessory which increases the performance of the
refrigeration system.

AEC/MECH/2009 3
Use of Desuperheater in Refrigeration

3 WASTE HEAT AVAILABILITY:

Heat of condensation has three phases as explained above. One may


be tempted to say that recoverable heat is same as heat removed from
refrigerated space or cold rooms. A small correction is required to above
statement that the recoverable heat also has added element of heat of
compression. This can be mathematical written as,
Heat of rejection (E1) = Heat of evaporation (E2) + Heat of compression (E3)

Since condensing latent heat is at constant temperature ranging


between 30 to 35 0C. This heat has limited applications whereas; condensing
heat above this temperature that is equivalent of energy input to compressor
has wider range of energy applications. Hence, this heat recovery has wider
importance.

Air conditioning unit generally removes heat from interior spaces


and this heat is rejected to atmosphere. It is tempted to say all heat rejected
to atmosphere is available for recovery. This is partly true. Rejected heat also
contains heat of compression in addition to cooling heat removed. However
major part of this heat is available at lower or non usable condensing
temperature. Taking this in to account it is important to assess the available /
recoverable heat in each process and generation of hot water in the system. It
is also important to note that more recovered pre-heated water than actually
required, does not mean more savings. Availability of excess hot water,
should not be claimed as savings.

For example fuel fired (Diesel or Furnace oil) boilers are used to
generate hot water for domestic use, cleaning, or for process need. At the
same time refrigeration is used for process cooling, cold storage and
pasteurisation or ice making. Entire heat rejected by refrigeration is rejected
to atmosphere through air-cooled or water-cooled condensers. Many times

AEC/MECH/2009 4
Use of Desuperheater in Refrigeration

this process of heat rejection and fresh heat generation is done across the
wall in the same plant and seldom noticed for complimenting each other.
While this energy is of low grade variety, it still represents waste energy.
Combining these two, waste heat and fresh heat generation makes clever
sense of energy conservation.

4 .THE CONCEPT:

Desuperheater

Hot
Water
Evapo
From

Condenser
rator

Compressor

SLHE

TEV

Figure 2 Evaporator

Refrigeration cycle with the Desuperheater


As seen in the figure, Desuperheater is piped in series between the
compressor gas discharge and the condenser. It is a special purpose heat

AEC/MECH/2009 5
Use of Desuperheater in Refrigeration

exchanger, designed to transfer hot gas energy to domestic hot water use.
Every air conditioning system has available heat energy, which can be
recovered. This heat is comprised of two components; “superheat” and
“condensing” heat energy. The “superheat” typically accounts for 15% of the
total system heat of rejection, whereas the “condensing” energy accounts for
about 85%. The Desuperheater uses hot refrigerant gas “superheat” energy
to heat domestic hot water to 60 deg C.

Many desuperheater sections combine both the cooling of the


superheated refrigerants and the part of saturated condensing requirement. A
typical selection will have a desuperheater that accomplishes approximately
one-third of the total heat rejection requirement.

Now we feel why can’t a single condenser system provide us with


same heat recovery and at same time be simple in construction?
Yes it can be used with some limitations that can be listed as follows
1. There is inability to economically provide water temperatures above 54
deg C.
2. Cooling tower winterization is required
3. In a system that circulates water from open cooling tower circuit to the
heating equipment, corrosion and particulate control are concerns.
4. In a system with heat exchanger to separate the open cooling tower
circuit from heating equipment the temperature of recovered heat is
reduced by 1-3deg C.

Let us see what advantages Desuperheater provides

5. ADVANTAGES TO THE REFRIGERATION CYCLE:


1. Improved System Operation

AEC/MECH/2009 6
Use of Desuperheater in Refrigeration

Because heat recovery is equivalent to adding 15% more


condenser capacity, it lowers the compressor head pressure. This helps
prolong the life of the air conditioning compressor and promotes improved
system operation.

2. Slight increase in capacity


The heat recovery decreases the gas passing through the throttling
valve thus there is small increase in amount of liquid refrigerant, thus there is
slight increase in refrigerating capacity.

3. Reduced refrigeration Costs


Desuperheater reduces the operating costs of the air
conditioning/refrigerating system by 3% to 5%. This means additional energy
efficiency for the overall system when the Heat Recovery is in use.

4. Reduction in power cost


Reduced operating hours of cooling tower fan and thereby reduced
power cost.

5. Lower maintenance cost


Improved condenser cooling and reduced condenser clogging
results in lower maintenance cost of the refrigeration is used

6. Reduction in cost of fuel


Desuperheater provides hot water for other needs such as cleaning,
pasteurisation etc. equivalent, thermal heat being lower for overall heating
cycle; it saves fuel required for hot water heating.

6. AMOUNT OF THE HEAT CONVERSION:

AEC/MECH/2009 7
Use of Desuperheater in Refrigeration

We have already seen the available heat but all the heat available is
not completely recovered. The amount heat recovered depends upon the heat
exchanger effectiveness. The heat exchanger generally has their
effectiveness between 60-80%.
Once the amount of heat that may be transferred to the water is
determined, it is then appropriate to view this energy recovery in terms of the
energy savings that may be achieved. One ton of heat removal is equivalent
to 12600 kJ/hr. Every liter of water requires 8.75kJ/hr of heat addition to raise
its temperature 1 deg C. Thus we can have hot water per hour free for every
ton. Free is relative since the equipment has some costs attached. Assuming
the alternative was to heat the water electrically (or burning fuel), the heat
recovery unit would provide savings on electricity (or on burning fuel). To get
overall savings, simply multiply hourly savings by the hours/day of operation.
Then consider the number of days/year that cooling is required.
Several other considerations are important:
• Since installation of a heat recovery unit requires the addition of other
components in the refrigerant lines, your warranty or service
agreement may be affected.
• Heat recovery units recover heat only when the chiller is operating.
Therefore, savings will be reduced if the chiller operating hours are
reduced.
• Long runs of refrigerant or water lines can add to the cost, as well as
resulting in additional heat loss in the system.
• If the unit produces hot water faster than it can be used, the excess
capacity may be wasted, thereby reducing potential savings.
• All heat recovery units should be provided with bypass valves that
allow the unit to be isolated from the system in case of leaks or
required maintenance.
• Heating water to temperatures higher than recommended results in
lower output in gallons per hour.

AEC/MECH/2009 8
Use of Desuperheater in Refrigeration

• Heat recovery systems can be adopted for all air conditioning units
from as small as 2 tons up to the largest chillers available

7. ECONOMICS CONSIDERATIONS:
The economics of this heat recovery is attractive. It is important to
ensure recovered hot water displaces prime energy (fuel or electricity) used
by facility. The economics can be adversely affected due to poor operating
hours of compressor. The system evaluation and total integration with facility
hot water system is essential step to ensure favorable economics of project.
Though there are other advantages of heat recovery system, over
empathizing of these benefits can create serious situation. While system is
conceptualized use of hot water should be properly estimated so that
recovered heat is not wasted. Providing metering of hot water flow and
recording the operating temperature will help to monitor and compare post
implementation performance of system. Generally 1litre fuel oil and 1kWh of
electricity delivers 270 & 28 liters of hot water respectively hot water at
55deg C. Thus with large requirement of hot water and refrigeration running
on one side, Desuperheater provides substantial savings in fuel.

AEC/MECH/2009 9
Use of Desuperheater in Refrigeration

8.USE OF CONVERTED HEAT:


The heat recovered can be used effectively wherever both heating
and refrigerating effects are required. Typical applications include restaurants,
hotels, apartments, hospitals, office buildings and industrial processes...
anywhere hot water is needed

The amount of waste heat available in a plant varies widely from


sector to sector in the food industry owing to the different processes and
energy requirements involved. There are also substantial differences in waste
heat from plant to plant within each sector due to such factors as product
concentration, continuous or batch operation, plant size and location. The
actual amount of potentially useful waste heat can only be revealed by a
comprehensive audit of the plant's energy consumption. However, in each
sector there are general opportunities and applications for waste heat
recovery. These are briefly discussed below for various sectors of the food
industry.

8.1.Dairy processing:
Dairy processing plants usually use energy efficiently. Heat
transmitted to milk products during pasteurization is normally rejected to
incoming cold milk in the regenerator. A large percentage of waste energy is
in the heat rejected by the refrigeration condensers. It can be used in
generating hot water for use in cleanup, in preheating boiler feed water, or in
heating culture tanks for some unit operations. Wastewater and exhaust from
spray dryers are other major sources of waste heat. Contaminants in the
wastewater may restrict its use for heat recovery, but dryer exhaust can be
recovered and used to preheat supply air for the dryer.

AEC/MECH/2009 10
Use of Desuperheater in Refrigeration

8.2.Poultry processing:
In poultry processing, large quantities of energy are required for scalding,
cooling and freezing. The scalders and chillers have continuous overflow, and
thus large amounts of energy are lost. However, recovery of heat (or cooling
capacity) from scalders (or from chillers) is feasible, and the energy can be
returned to the scalders (or chillers). Heat can also be recovered from
refrigeration system condensers and used to preheat boiler makeup water or
washwater.

8.3.Fruit and vegetable processing (freezing and canning):


Although the percentage of waste heat does not differ greatly between
freezing and canning plants, the sources of the waste streams do. In freezing
plants, the major source is the refrigeration system condensers. Heat is
available from the hot refrigerant and should be easily recoverable. A second
source is wastewater, however, waste heat from it is of low quality and solid
particles in the wastewater might cause fouling problems in heat exchangers,
Individual hot waste streams may offer some recovery potential if they are
intercepted prior to mixing with the main waste flow.
In canning plants, the major waste heat sources are retort vents and
wastewater. Heat from retort vents can be recovered, but no backpressure
should be applied to these vents, since free flow of steam is essential during
venting to ensure that adequate thermal processing of cans will be
accomplished.
Waste heat can be used at numerous points in the plant. Water heating for
can washing, blancher makeup water, and plant cleanup and boiler feedwater
are potential applications.

AEC/MECH/2009 11
Use of Desuperheater in Refrigeration

9. CASE STUDIES :
Let us now evaluate how much savings are we seeing at
Case study 1:
Hotel requires overall cooling of building and hot water for domestic use. Hot
water is required in room service as well as kitchen is supplied from hot water
that is maintained between 45 to 50 0C. Hotel has 50TR of refrigeration. The
desuperheater produces hot water and it is piped in existing hot water system.
Thus the required hot water is provided by desuperheater and electricity
/diesel firing makes up the short fall.
The assumed 15%heat recovery for 50ton we get 1575kJ/min
16 hrs operation per day provides 1.5 GJ /day.
Fuel heat gives 2751kJ/kg. (for HSD fuel)
(Assuming Density 0.84, efficiency .84)
Effective heat 1940 kJ/lit
Savings /day/TR /16 hr Operation of refrigeration system = 0.77 lit

Case study 2:
Heat energy is removed from milk during cooling. The heat energy can be
'dumped' from an air-cooled condenser, or all/or part of it can be transferred
to water using a water-cooled condensing mechanism or milk precooler.
Water-cooled condensers and milk precoolers will reduce compressor
running- time. However, the greater energy savings usually come from
displacing water heating energy costs.
On most, dairy farms the milk heat available can preheat more water than the
required for nominal wash-up and sanitizing.

Milk Cooling
To maintain milk quality, milk must be cooled from about 39° C (cow body
temperature) to 3° C for safe storage. Milk is normally cooled by a
refrigeration unit removing heat from milk (source) to air or water (sink).

AEC/MECH/2009 12
Use of Desuperheater in Refrigeration

27℃
Evaporator Air

Hot water
As discussed hot water is required for sanitization and pasteurization. The
temperature of this water is around 70 0C.
Consider a refrigeration capacity of dairy as 30TR(2100kJ/min)
Assuming 15%heat recovery from it gives us 945kJ/min
20 hrs operation per day provides 1.13 GJ /day.
Fuel heat gives 2488kJ/kg. (for furnace oil)
(Assuming Density 0.94, efficiency .80)
Effective heat 1870 kJ/lit
Desuperheater
Savings /day/TR /16 hr Operation of
refrigeration system = 0.60 lit Hot water
65℃

Temperature controlled bath

Valve 24℃

Water pass

Refrigerant pass Existing air-conditioning system


Compressor

35℃
Condenser Air

AEC/MECH/2009 13
Use of Desuperheater in Refrigeration

10. CONCLUSION:
Heat recovery from refrigeration is effective and provides reliable source of
heat to fulfill major demand of hot water. System can preheat water up to
600C without affecting refrigeration cycle. Simultaneous generation of chilled
water and usable hot water results in
1. Increased output of heating system
2. Reduced fuel consumption and
3. Enhanced overall system efficiency.

Figure3. Circuit chart of experimental


equipment

AEC/MECH/2009 14
Use of Desuperheater in Refrigeration

11.REFERENCE :
1. HEAT CHILLER RECOVERY published by ASHRAE in 1999
2. A COURSE OF REFRIGERATION AND AIR-CONDITIONING by
S.C. Arora and S. Domkundwar
3. Best Energy Systems Inc. acrobat file BRAMPTON case study
4. www.agr.gc.ca
5. Internet.oit.edu
6. Fact sheet EES-26 published by UNIVERSITY OF FLORIDA

AEC/MECH/2009 15

S-ar putea să vă placă și