KENCANA SQUARE

FIRESTOPPING
SECTION FP-361
Page 1

1.0

GENERAL

1.1

DESCRIPTION
.1

1.2

1.3

1.4

2.0
2.1

Work of this Section shall conform to the requirements of the Contract


Documents.

WORK INCLUDED
.1

Firestop Compounds.

.2

Damming Material.

SUBMITTALS
.1

Submit shop drawings, product data, and manufacturer's installation instructions


for all materials and prefabricated devices, providing descriptions sufficient for
identification at the job site.

.2

Submit shop drawings showing proposed material, reinforcements anchorage,


fastenings, and method of installation. Construction details shall accurately reflect
actual job conditions.

.3

Submit Material Safety Data Sheets with product delivered to job site.

.4

Submit complete details of each type of penetration to be used indicating the


proper local authority or Uniform Laboratory (U.L.) approved firestop system or
equal.

QUALITY ASSURANCE
.1

Firestop system installation shall conform to requirements of qualified designs or


manufacturer approved modifications, as supported by engineering reports.

.2

Install firestop materials, and systems as required by these Contract Documents


and accepted for use by Director General of Fire Services (D.G.F.S.) or Bomba.

.3

Submit manufacturer's product data, letter of certification, or certified laboratory


test report that the material or combination of materials (firestop system) meets
the requirements specified in accordance with the applicable referenced
standards.

.4

The firestop compound shall not contain any solvents or inorganic fibers. The
penetration seal material must be unaffected by moisture and must maintain the
integrity of the floor or wall assembly for its rated time period when tested in
accordance with Bomba requirement.

PRODUCTS
FIRESTOPS
.1

Firestop compounds shall be provided for caulk, pour, trowel or pump application.
Material must be capable of sealing openings around single or multiple ducts,
cables, wire or conduits against fire, smoke and toxic gases, and maintaining
rating with a thickness no greater than the structure.

KENCANA SQUARE
FIRESTOPPING
SECTION FP-361
Page 2

2.2

.2

The firestop compound shall not contain any solvents or inorganic fibres. The
penetration seal material must he unaffected by moisture and must maintain the
integrity of the floor or wall assembly for its rated time period when tested in
accordance with Bomba requirement

.3

Firestop system shall consist of a material, or combination of materials, to retain


the integrity of fire-rated construction by maintaining an effective barrier against
the spread of flame, smoke or gases through penetrations in fire-rated barriers. It
shall be used in specific locations as follows:.1

Penetration for the passage of duct, cable tray, conduit, and electrical
busways and raceways through fire-rated vertical barriers (walls and
partitions), horizontal barriers (floor slabs and floor/ceiling assemblies),
and vertical services shafts.

.2

locations shown specifically on the drawings or where specified in other


sections of these specification.

DAMMING MATERIAL
Damming material,
recommendations.

2.3

shall

provided

where

required

as

per

manufacturers

MATERIALS
.1

Firestopping materials/systems shall be flexible to allow for normal movement of


building structure and penetrating item(s) without affecting the adhesion or
integrity of the system.

.2

Firestopping materials shall not require hazardous waste disposal of used


containers/packages.

.3

Firestoppong materials shall not free of solvents which will experience shrinkage
while curing.

3.0

EXECUTION

3.1

DELIVERY AND STORAGE

3.2

be

.1

Deliver materials to site in original unopened containers or packages bearing the


manufacturers name, brand designation, product description and classification
marking.

.2

Coordinate delivery of materials with scheduled installation date to allow minimum


storage time at job site.

.3

Store materials under over and protect from weather and damage in compliance
with manufacturers requirements.

.4

Comply with recommended procedures, precautions or remedies described in


Material Safety Data Sheets as applicable.

EXAMINATION
.1

Examine areas and conditions under which work is to be performed and notify the
Contractor in writing of conditions detrimental to proper and timely completion of
the work.

KENCANA SQUARE
FIRESTOPPING
SECTION FP-361
Page 3

.2

3.3

3.4

3.5

Verify that openings are properly sized and in suitable condition to receive the
work of this section.

PREPARATION
.1

Clean substrate of dirt, dust, grease, oil, loose materials, rust or other matter that
may affect the proper fitting or adhesion of the firestopping materials.

.2

clean metal and glass surfaces with a non-alcohol solvent.

INSTALLATION
.1

Install firestop material as indicated in accordance with design requirements and


manufacturers instructions.

.2

Seal all holes or voids made by penetrations to ensure an air, smoke and watertight seal.

.3

Firestopping may be required under related sections of the project specifications.


Identify all locations requiring firestopping and coordinate the work of this section
with work performed under other sections of the project to provide a uniform
system of firestopping.

.4

Schedule installation of firestopping after completion of penetrating item


installation but prior to covering or concealing of openings.

.5

Do not proceed with installation of firestop materials when temperatures exceed


the manufacturers recommended limitations for installation.

.6

Firestop system do not re-establish the structural integrity of load bearing


partitions. Contractor shall consult Employers Representative prior to penetrating
any load bearing assembly.

.7

Firestop systems are not intended to support live loads or traffic. Contractor shall
consult Employers Representative if he has reason to believe these limitations
may be violated.

PIPES
.1

Install a pipe sleeve with an inside diameter large enough to include the specified
diameter of cable.

.2

Install firestop material at each end of sleeve to form JBM approved system.

.3

Insulate pipe on each side of wall and caulk all around insulation at joint of wall
and insulation.

END OF SECTION FP-361