STRUCTURAL DESIGN
U DRAIN 1000 mm x 2000 mm
Date
125
0
U Drain
H=
1000 mm
B=
2000 mm
Tw=
125 mm
Tb=
150 mm
Drain Height
Drain Width
Thickness of Wall
Thickness of Base
1000
soil
150
water
2.653
11.28
surcharge
Defined Variables
HACJ
KKND
2.95
2000
Soil
s=
sub
c=
=
c=
BC =
Calculation
19.0 kN/m
Soil Density
9 kN/m
0.0 kN/m
33.0
22.0
125 N/mm2
2
Concrete
fcu=
25 N/mm
24 kN/m
=
con
Cohession of soil
Internal Friction Angle of soil
Friction Angle of soil-concrete
Bearing capasity of soil
Loads acting at critical load combination -Drain is Empty & outside Water Level at FGL
Ka
=
[1-sin ( ]/[1+sin ( ]
=
0.29 active pressure coefficie
Fsb
K
x
x
(H)/1000
=
=
2.65 Active soil pressure at b
a
sub
Fwb
x
(H)/1000
=
=
11.28 Active water pressure a
w
Fsurb =
Ka x sur x (H)/1000
=
2.95 Active surcharge pressu
Strength of concrete
Density of concrete
SF
Structure
Cover to wall
Cover to Base
Surcharge Pressure sur
Allowable crack width
Water table
Density of water
Thickness of cover slab
Longitudinal R/F -wall
Vertical R/F -wall
shorter span R/F-bottom
longer span R/F-bottom
40 mm
40 mm
10 N/mm2
0.3 mm
same as FGL
9.81
kN/m3
75 mm
10 mm
10 mm
12 mm
10 mm
Check for
Wd
=
Wc
=
Wwi =
Ww/Wd
Soil Bearing Capacity
[(2xTw+B)xTb+(2xH)xTw]x24/E6
75x(B+2xTw)
(H)x(B)x9.81/E6
Lsur
sur x (B+2xTw)/E3
=
Total SLS Load for Soil Pressure
Soil Pressure
=
=
=
=
=
=
14.1
Designed by
Checked by
STRUCTURAL DESIGN
U DRAIN 1000 mm x 2000 mm
HACJ
KKND
Date
Structural Analysis
The structural analysis is done by SAP2000. The bending moments, Shear forces are attched in the report. Results and calculations are as follows.
Bending Moments -wall
ULS Envilop-
Vertical direction
Horizontal direction
10 @
200 mm c/c
Horizontal direction
Effective depth
Ultimate bending moment
K=M/bd2fcu
Z= [.5+(0.25-K/.9)^0.5]d
Hence,
Z=
0.95
Required Steel Area As=M/0.87fyZ
Provide T
10 @
=
=
d=
80
Mu= 13
K= 0.081
Z=
0.90
Z= 72
As= 451.3375
AsProv= 392.6991
d=
Mu=
200 mm c/c
13 kNm
3 kNm
K=
Z=
Z=
As=
AsProv=
70
5
0.041
0.95
66.5
187.876
392.6991
mm
kNm
<
0.156
d
mm
mm/m
mm/m
mm
kNm
<
0.156
d
mm
mm/m
mm/m
=
=
Horizontal direction
Effective depth
d=
70
Maximum Shear force
V=
10
shear stress
v= 0.143
100As/bd
= 0.561
vc=
shear capacity
1.02
Hence, no shear reinforcement required
24
10
mm
kN/m
N/mm2
N/mm2
mm
kN/m
N/mm2
N/mm2
Designed by
Checked by
STRUCTURAL DESIGN
U DRAIN 1000 mm x 2000 mm
HACJ
KKND
Date
Structural Analysis
The structural analysis is done by SAP2000. The bending moments, Shear forces are attched in the report. Results and calculations are as follows.
Bending Moments -Base
ULS Envilop-
shorter direction
longer direction
10 @
200 mm c/c
longer direction
Effective depth
Ultimate bending moment
K=M/bd2fcu
Provide T
10 @
K=
Z=
200 mm c/c
0.048
0.94
mm
kNm
<
d
0.156
Z= 98.1
mm
As= 331.092 mm/m
AsProv= 392.6991 mm/m
K=
Z=
d
13 kNm
2.5 kNm
d= 104
Mu= 13
d=
Mu=
Z= [.5+(0.25-K/.9)^0.5]d
Hence,
Z=
0.95
Required Steel Area As=M/0.87fyZ
=
=
93
5
mm
kNm
0.023
0.97
<
d
Z= 88.4
mm
As= 141.412 mm/m
AsProv= 392.6991 mm/m
d=
V=
24
11
104
24
shear stress
100As/bd
v= 0.231
= 0.378
v
=
shear capacity
0.81
c
Hence, no shear reinforcement required
longer direction
Effective depth
Maximum Shear force
0.156
=
=
shear stress
100As/bd
d=
V=
93
11
v= 0.118
= 0.422
v
=
shear capacity
0.864
c
Hence, no shear reinforcement required
mm
kN/m
N/mm2
N/mm2
mm
kN/m
N/mm2
N/mm2
STRUCTURAL DESIGN
DESIGN
CALCULATIONS U DRAIN 1000 mm x 2000 mm
Load assignment for Sap2000
Water Pressure
Designed by
Checked by
HACJ
KKND
Date
2.95
Wall -Horizontal M
STRUCTURAL DESIGN
DESIGN
CALCULATIONS U DRAIN 1000 mm x 2000 mm
Designed by
Checked by
HACJ
KKND
Date
Wall -Horizontal M
kN/m
kN/m
kN/m
N/mm2
N/mm2
>
>
kN/m
N/mm2
N/mm2
DESIGN
CALCULATIONS
kN/m
kN/m
kN/m
N/mm2
N/mm2
>
>
kN/m
N/mm2
N/mm2
DESIGN
CALCULATIONS
Lateral surcharge pressure
DESIGN
CALCULATIONS