Service Manual
R-410A Sky-Air Indoor
www.daikin.eu
ESiEN05-04
Service Manual
R-410A Sky-Air Indoor
www.daikin.eu
ESIEN05-04
Table of Contents
1
1
Introduction
1.1
1.2
ii
iii
Part 1
System Outline
1
General Outline
1.1
1.2
1.3
1.4
1.5
1.6
1.7
1.8
1.9
1.10
1.11
1.12
1.13
1.14
1.15
1.16
1.17
1.18
1.19
1.20
1.21
13
14
16
18
110
112
114
116
118
120
122
124
126
128
130
132
134
136
138
140
142
2.1
2.2
2.3
2.4
2.5
2.6
2.7
2.8
2.9
2.10
145
146
147
148
149
150
151
152
153
154
Specifications
Table of Contents
4
5
ESIEN05-04
Functional Diagrams
3.1
3.2
3.3
3.4
4
5
5
161
162
164
166
168
170
172
174
176
178
180
182
184
186
188
190
192
195
196
197
198
199
1100
1101
1102
1103
1104
1105
1106
ii
155
156
158
159
Wiring Diagrams
4.1
4.2
4.3
4.4
4.5
4.6
4.7
4.8
4.9
4.10
4.11
4.12
4.13
4.14
4.15
4.16
4.17
Table of Contents
ESIEN05-04
PCB Layout
1
6.1
6.2
6.3
6.4
6.5
6.6
6.7
6.8
6.9
6.10
6.11
6.12
6.13
1107
1108
1109
1110
1112
1113
1114
1115
1116
1117
1118
1119
1120
3
4
5
Table of Contents
iii
ESIEN05-04
Part 2
Functional Description
1
Functional concept
1.1
1.2
1.3
1.4
1.5
1.6
1.7
1.8
1.9
1.10
1.11
1.12
1.13
1.14
1.15
1.16
1.17
1.18
3
4
23
24
25
27
28
29
210
211
213
214
215
216
217
219
220
221
222
223
iv
Table of Contents
ESIEN05-04
Part 3
Troubleshooting
1
Troubleshooting
1.1
1.2
1.3
1.4
1.5
1.6
1.7
1.8
1.9
1.10
33
34
35
320
321
322
326
327
328
330
331
332
333
335
336
338
340
342
343
Table of Contents
3
4
Error Codes
2.1
2.2
2.3
2.4
2.5
2.6
2.7
2.8
2.9
345
346
348
349
350
352
ESIEN05-04
353
354
355
356
357
358
359
360
3
4
5
vi
Table of Contents
ESIEN05-04
Part 4
Commissioning and Test Run
1
43
44
45
Field Settings
2.1
2.2
2.3
2.4
2.5
2.6
2.7
2.8
2.9
2.10
49
410
412
413
414
415
416
418
419
420
Table of Contents
424
vii
4
5
ESIEN05-04
Part 5
Disassembly and Maintenance
1
3
4
viii
Table of Contents
ESIEN05-04
Introduction
Part 0
1
Introduction
1.1
Target group
This service manual is intended for and should only be used by qualified engineers.
Purpose of this
manual
This service manual contains all the information you need to do the necessary repair and maintenance
tasks for the R-410A Sky Air Indoor Units.
Five parts
Introduction
overview
Part
See page
11
21
Part 3Troubleshooting
31
41
51
4
5
See page
1.2Combination Overview
ii
Introduction
Combination Overview
The table below contains the possible combinations between indoor units and pair split outdoor units.
Non Inverter
Inverter
950x950
cassette
standard
FCQ35B7V1
FCQ50B7V1
P
P
FCQ60B7V1
600X600
cassette
duct
standard
ceiling
suspended
FHQ60BUV1B
RXS35D(2)VMB
RXS25D(2)VMB
P
P
P
P
P
P
P
P
P
P
RSX60BVMB
RSX50BVMB
RXS35BVMB
RXS25BVMB
RKS35D(2)VMB
FHQ35BUV1B
FHQ50BUV1B
P
P
FBQ35B7V1
FBQ60B7V1
P
P
FFQ60B(7)V1B
FBQ50B7V1
FFQ35B(7)V1B
FFQ50B(7)V1B
Heat Pump
FFQ25B(7)V1B
ii
Cooling Only
RKS25BVMB
Indoor unit
RS60BVMB
RS50BVMB
Cooling Only
RKS25D(2)VMB
Outdoor unit
RKS60BVMB(9)
RKS50BVMB(9)
Introduction
RKS35BVMB
1.2
ESIEN05-04
P
P
ESIEN05-04
The table below contains the possible combinations between indoor units and multi split outdoor units.
Inverter
Outdoor unit
4MKS75BVMB
4MKS90BVMB
4MKS58DVMB
4MKS75DVMB
4MKS90DVMB
3MXS52BVMB
4MXS68BVMB
4MXS80BVMB
2MXS52DVMB
3MXS52DVMB
4MXS68DVMB
4MXS80DVMB
RMXS112D7V3B
RMXS140D7V3B
RMXS160D7V3B
FCQ35B7V1
FCQ50B7V1
600X600
cassette
950x950
cassette
standard
Indoor unit
FCQ60B7V1
FFQ25B(7)V1B
FFQ35B(7)V1B
FFQ50B(7)V1B
FFQ60B(7)V1B
duct
standard
Heat Pump
4MKS58BVMB
Cooling Only
ceiling
suspended
Introduction
FBQ35B7V1
FBQ50B7V1
FBQ60B7V1
FHQ35BUV1B
FHQ50BUV1B
FHQ60BUV1B
iii
3
4
5
Introduction
The table below contains the possible combinations between indoor units and Sky Air outdoor units.
Non Inverter
FCQ35B7V1
FCQ60B7V1
FCQ125B7V3B
P
P
600X600
standard
large
duct
P
T
FFQ60B(7)V1B
FBQ60B7V1
FDQ125B7V3B
SC30 duct
4
3
4
3
3
2
2
P
FDQ250B7V3B
iv
FDQ200B7V3B
FDEQ125B7V3B
P
P
FBQ125B7V3B
FBQ50B7V1
FDEQ100B7V3B
RZQ250B7W1B
FFQ50B(7)V1B
FDEQ71B7V3B
FCQ140DV3B
FBQ100B7V3B
RZQ200B7W1B
2
FCQ125DV3B
FBQ71B7V3B
FCQ100DV3B
FBQ35B7V1
4
3
FCQ71DV3B
FFQ35B(7)V1B
RZQ140B7W1B
RZQ125B7(8)V3B
RZQ125B7W1B
RZQ100B7(8)V3B
RZQ100B7W1B
3
P
P
RZQ71B7(8)V3B
2
FCQ71B7V3B
Heat Pump
REQ125B7W1B
RQ100B7V3B
RQ100B7W1B
RQ71B7V3B
RQ71B7W1B
RR125B7W1B
Heat Pump
FCQ50B7V1
FCQ100B7V3B
high COP
standard
950x950 cassette
RR100B7V3B
RR100B7W1B
Indoor unit
RR71B7V3B
RR71B7W1B
Cooling Only
Inverter
REQ100B7V3B
REQ100B7W1B
Outdoor unit
REQ71B7V3B
REQ71B7W1B
RQ125B7W1B
ESIEN05-04
P
P
P
P
ceiling
suspended
cassette
FUQ71BV3B
Wall
mounted
ceiling suspended
Indoor unit
FHQ35BUV1B
FHQ71BUV3B
FAQ71BV3B
FAQ100BV3B
T
FHQ50BUV1B
T
T
T
T
FHQ60BUV1B
T
T
T
T
T
T
T
T
FHQ100BUV3B
FUQ100BV3B
FHQ125BUV3B
FUQ125BV3B
P
T
P
P
P
P
P
T
P
2
3
4
4
2
3
3
P
P
RZQ250B7W1B
RZQ200B7W1B
Heat Pump
RZQ140B7W1B
Non Inverter
RZQ125B7(8)V3B
RZQ125B7W1B
RZQ100B7(8)V3B
RZQ100B7W1B
RZQ71B7(8)V3B
REQ125B7W1B
REQ100B7V3B
REQ100B7W1B
REQ71B7V3B
REQ71B7W1B
Cooling Only
RQ125B7W1B
RQ100B7V3B
RQ100B7W1B
RQ71B7V3B
RQ71B7W1B
RR125B7W1B
RR100B7V3B
RR100B7W1B
RR71B7V3B
RR71B7W1B
ESIEN05-04
Introduction
Outdoor unit
Inverter
Heat Pump
2
2
P
P
2
P
2
Introduction
ESIEN05-04
Combination matrix
Possible indoor combination
(Standard capacity for twin, triple and double twin operation)
Twin
Triple
Double Twin
Outdoor
models
RZQ71B8V3B
35-35
(KHRQ22M20TA7)
RZQ100B8V3B
RZQ100B7W1B
50-50
(KHRQ22M20TA7)
35-35-35
(KHRQ127H7)
RZQ125B8V3B
RZQ125B7W1B
60-60
(KHRQ22M20TA7)
50-50-50
(KHRQ127H7)
35-35-35-35
(3x KHRQ22M20TA7)
RZQ140B7W1B
71-71
(KHRQ22M20TA7)
50-50-50
(KHRQ127H7)
35-35-35-35
(3x KHRQ22M20TA7)
Notes:
vi
FCQ35~71
FFQ35~60
FHQ35~71
FBQ35~71
FUQ71
FAQ71
Individual indoor capacities are not given because the combinations are for simultaneous
operation (=indoor units installed in same room).
When different indoor models are used in combination, designate the remote control that is
equipped with the most functions as the main unit. In note 1 are the indoor units mentioned in order
of the possible function (most functions are on FCQ, less functions are on FAQ)
Between brackets are the required Refnet kits mentioned, that are necessary to install the
combination
ESIEN05-04
Introduction
Combination matrix
Possible indoor combination
(Standard capacity for twin, triple and double twin operation)
Twin
Triple
Double Twin
RZQ200B7W1B
100-100
(KHRQ22M20TA7)
60-60-60
71-71-71
(KHRQ250H7)
50-50-50-50
(3x KHQ22M20TA7)
RZQ250B7W1B
125-125
(KHRQ22M20TA7)
60-60-60-60
(3x KHRQ22M20TA7)
Outdoor
models
Notes:
FCQ50~125
FFQ50, 60
FHQ50~125
FBQ50~125
FUQ71~125
FAQ71, 100
FDQ125
4
5
Individual indoor capacities are not given because the combinations are for simultaneous
operation (=indoor units installed in same room).
When different indoor models are used in combination, designate the remote control that is
equipped with the most functions as the main unit. In note 1 are the indoor units mentioned in order
of the possible function (most functions are on FCQ, less functions are on FAQ)
Between brackets are the required Refnet kits mentioned, that are necessary to install the
combination
vii
Introduction
ESIEN05-04
Combination matrix
Possible indoor combination
(Standard capacity for twin and triple operation)
Twin
Triple
Outdoor
models
RQ71B7V3/W1
RR71B7V3/W1
35-35
(KHRQ22M20TA7)
RQ100B7V3/W1
RR100B7V3/W1
50-50
(KHRQ22M20TA7)
50-60
(KHRQ22M20TA7)
RQ125B7W1
RR125B7W1
60-60
(KHRQ22M20TA7)
50-71
(KHRQ22M20TA7)
Notes:
4
5
viii
35-71
(KHRQ22M20TA7)
35-35-35
(KHRQ127H7)
50-50-50
(KHRQ127H7)
FCQ35~71
FFQ35~60
FUQ71
FHQ35~71
FAQ71
FBQ35~71
Individual indoor capacities are not given because the combinations are for simultaneous
operation (=indoor units installed in same room).
When different indoor models are used in combination, designate the remote control that is
equipped with the most functions as the main unit. In note 1 are the indoor units mentioned in order
of the possible function (most functions are on FCQ, less functions are on FBQ)
Between brackets are the required Refnet kits mentioned, that are necessary to install the
combination
For unit specification of the outdoor units and the indoor units refer to the unit specifications
mentioned for pair systems.
Nominal cooling capacities are based on the following conditions: indoor air temperature: 27CDB,
19CWB, outdoor temperature 35CDB. Nominal heating capacities are based on the following
conditions: indoor air temperature: 20CDB, outdoor temperature 7CDB, 6CWB.
ESIEN05-04
1
4
Part 1
System Outline
See page
1General Outline
13
2Specifications
145
3Functional Diagrams
155
4Wiring Diagrams
161
195
6PCB Layout
1107
4
5
11
ESIEN05-04
11
12
ESIEN05-04
General Outline
Part 1
1
1
General Outline
1.1
Introduction
General outline
Components
See page
14
1.3FCQ100, 125B
16
1.4FCQ71D
18
110
112
1.7FBQ35, 50B
114
1.8FBQ60, 71B
116
1.9FBQ100, 125B
118
1.10FDQ125B
120
1.11FDQ200, 250B
122
1.12FHQ35, 50B
124
1.13FHQ60, 71B
126
1.14FHQ100B
128
1.15FHQ125B
130
1.16FUQ71B
132
1.17FUQ100, 125B
134
1.18FAQ71B
136
1.19FAQ100B
138
1.20FDEQ71, 100B
140
1.21FDEQ125B
142
4
5
13
see note 3
14
(Ceiling opening)
Branch duct
connection
Prepared hole
(Suspension position)
mo
re
or
mo
re
Branch duct
connection
Prepared hole
or
mo
re
VIEW D
or
VIEW B
Branch duct
connection
4. When the conditions exceed 30C and RH 80% in the ceiling or fresh air is
inducted into the ceiling, an additional insulation is required (polyethylene foam,
thickness 10mm or more).
3. In case of using a infrared remote control, this position will be a signal receiver.
Refer to the drawing of the infrared remote control for more details.
or less
(Ceiling opening)
5
(Suspension position)
NOTES:
1. Location of the nameplates:
- Unit body: on the bell mouth at the inside of the suction grill.
- Decoration panel: on the panel frame at the inside of the suction grill.
VIEW C
Prepared hole
Hanging bolt
VIEW A
Prepared hole
or
mo
re
Outlook and
dimensions
Adjustable
1.2
or more
Installation space
11
General Outline
ESIEN05-04
ESIEN05-04
Components
General Outline
Component
Air outlet
10
Drain hose
3
4
5
15
see note 3
16
NOTES:
1. Location of the nameplates:
- Unit body: on the bell mouth at the inside of the suction grill.
- Decoration panel: on the panel frame at the inside of the suction grill.
Branch duct
connection
Prepared hole
Branch duct
connection
Prepared hole
(Suspension position)
(Ceiling opening)
or
VIEW B
re
m
or
or e
or
mo
Branch duct
connection
Prepared hole
re
or
mo
re
VIEW D
or
mo
mo
Prepared hole
Branch duct
connection
4. When the conditions exceed 30C and RH 80% in the ceiling or fresh air is
inducted into the ceiling, an additional insulation is required (polyethylene foam,
thickness 10mm or more).
3. In case of using a infrared remote control, this position will be a signal receiver.
Refer to the drawing of the infrared remote control for more details.
(Suspension position)
Hanging bolt
VIEW A
or less
5
(Ceiling opening)
VIEW C
Prepared hole
re
Outlook and
dimensions
Adjustable
1.3
or more
Installation space
11
General Outline
ESIEN05-04
FCQ100, 125B
The illustration below shows the outlook and the dimensions of the unit (mm).
ESIEN05-04
Components
General Outline
Component
10
Drain hose
3
4
5
17
18
Adjustable (0~550)
35 or less
3. When the temperature and humidity in the ceiling exceed 30C and RH 80% or
the fresh air is inducted into the ceiling or the unit continues 24 hour operation,
an additional insulation (thickness 10mm or more of glasswool or polyethylene
form) is required.
2. In case of using infrared remote control, this position will be a signal receiver.
Refer to the drawing of infrared remote control for detail.
NOTES:
1. Location of units name plate
for indoor unit : on the bell mouth inside suction grill
for decoration panel : on the inner frame inside suction grill
Suspension bolt
Branch duct
connection
hole
Branch duct
connection
1500mm
or more
D ARROW VIEW
1500mm
or more
1500mm or more
1500mm or more
REQUIRED SPACE
C ARROW VIEW
Branch duct
connection
12-M4 hole
12-M4 hole
4-M4 hole
B ARROW VIEW
12-M4 hole
5
860~910 (Ceiling opening space) (Note 4)
680 (Suspension position)
Pipe connection
side
Drain connection
side
300
or less
Outlook and
dimensions
1500 or more
(Required space)
From
the floor side 2500 or more
1.4
11
(Note 2)
General Outline
ESIEN05-04
FCQ71D
The illustration below shows the outlook and the dimensions of the unit (mm).
ESIEN05-04
Components
General Outline
Component
Air outlet
Suction grille
3
4
5
19
110
Adjustable (0~055)
Branch duct
connection
35 or less
3. When the temperature and humidity in the ceiling exceed 30C and RH 80% or
the fresh air is inducted into the ceiling or the unit continues 24 hour operation,
an additional insulation (thickness 10mm or more of glasswool or polyethylene
form) is required.
2. In case of using infrared remote control, this position will be a signal receiver.
Refer to the drawing of infrared remote control for detail.
NOTES:
1. Location of units name plate
for indoor unit : on the bell mouth inside suction grill
for decoration panel : on the inner frame inside suction grill
Suspension bolt
12-M4 hole
12-M4 hole
4
*
more
1500mm or
1500mm or more
or more
1500mm
1500mm or more
REQUIRED SPACE
C ARROW VIEW
D ARROW VIEW
Branch duct
connection
12-M4 hole
4-M4 hole
B ARROW VIEW
Branch duct
connection
12-M4 hole
Pipe connection
side
Drain connection
side
5
860~910 (Ceiling opening space) (Note 4)
300
or less
680 (Suspension position)
Outlook and
dimensions
1500 or more
(Required space)
From
the floor side 2500 or
1.5
11
(Note 2)
General Outline
ESIEN05-04
ESIEN05-04
Components
General Outline
Component
Air-Outlet
Suction grille
3
4
5
111
112
Adjustable
3. When the temperature and humidity in the ceiling exceed 30C and RH 80% or
the fresh air is inducted into the ceiling or the unit continues 24 hour operation,
an additional insulation (thickness 10mm or more of glasswool or polyethylene
form) is required.
2. In case of using infrared remote control, this position will be a signal receiver.
Refer to the drawing of infrared remote control for detail.
NOTES:
1. Location of units name plate
for indoor unit : on the bell mouth inside suction grill
for decoration panel : on the inner frame inside suction grill
or less
or less
(Note 4).
*
or more
*
or more
Ceiling
or more
or more
B ARROW VIEW
REQUIRED SPACE
hole
Suspension bolt
A ARROW VIEW
(Note 2)
Outlook and
dimensions
(Suspension position)
or more
(Required space)
4
or more
5
1.6
11
or less
General Outline
ESIEN05-04
ESIEN05-04
Components
General Outline
Component
Suction grille
Drain hose
3
4
5
113
114
(On circumference)
VIEW C
P.C.D.
NOTES:
1. Refer to Outlook drawing for installing optional
accessories when installing optional accessories.
(Service Space)
or more
(Suspension bolt)
Outlook and
dimensions
VIEW B
1.7
VIEW A
11
(Suspension position)
General Outline
ESIEN05-04
FBQ35, 50B
The illustration below shows the outlook and the dimensions of the unit (mm).
ESIEN05-04
Components
General Outline
Component
Drain hole
Air filter
10
Nameplate
3
4
5
115
116
(On circumference)
VIEW C
P.C.D.
NOTES:
1. Refer to Outlook drawing for installing optional
accessories when installing optional accessories.
(Service Space)
Outlook and
dimensions
or more
(Suspension bolt)
3
VIEW B
1.8
VIEW A
11
(Suspension position)
General Outline
ESIEN05-04
FBQ60, 71B
The illustration below shows the outlook and the dimensions of the unit (mm).
ESIEN05-04
Components
General Outline
Component
Drain hole
Air filter
10
Nameplate
3
4
5
117
118
(On circumference)
P.C.D.
5
VIEW C
(Service Space)
or more
Suspension bolt
4
VIEW B
Outlook and
dimensions
VIEW A
1.9
NOTES:
1. Refer to Outlook drawing for installing optional
accessories when installing optional accessories.
(Suspension position)
11
(Suspension position)
General Outline
ESIEN05-04
FBQ100, 125B
The illustration below shows the outlook and the dimensions of the unit (mm).
or more
(Installation Space)
ESIEN05-04
Components
General Outline
Component
Drain hole
Air filter
10
Nameplate
3
4
5
119
General Outline
11
1.10
ESIEN05-04
FDQ125B
The illustration below shows the outlook and the dimensions of the unit (mm).
VIEW A
Outlook and
dimensions
3
4
NOTE:
SERVICE SPACE
VIEW A
120
ESIEN05-04
Components
General Outline
Component
Drain connection
Filter
3
4
5
121
General Outline
11
1.11
ESIEN05-04
FDQ200, 250B
The illustration below shows the outlook and the dimensions of the unit (mm).
VIEW A
Outlook and
dimensions
3
4
122
255
890
FDQ250B7V3B
285
830
FDQ200B7V3B
SERVICE SPACE
NOTES:
VIEW A
Model
ESIEN05-04
Components
General Outline
Component
Drain connection
Filter
3
4
5
123
124
(Required space)
Drain pipe
connection
(For left piping)
(Required space)
The front
(Hanging position)
or more
(Service Space)
NOTES:
1. Location of units Name plate: Bottom of fan
housing inside the suction grill.
Floor side
Obstacle
(Hanging position)
or more
(Service Space)
Hanging bolt
or more
Outlook and
dimensions
or more
1.12
(Required space)
11
General Outline
ESIEN05-04
FHQ35, 50B
The illustration below shows the outlook and the dimensions of the unit (mm).
ESIEN05-04
Components
General Outline
Component
Air outlet
Air filter
Suspension bracket
10
11
12
13
14
15
Position of the hole in the wall for piping straight trough the wall
16
17
18
3
4
5
125
126
Drain pipe
connection
(For left piping)
(Required space)
or more
(Required space)
Floor side
The front
or more
(Service Space)
NOTES:
1. Location of units Name plate: Bottom of fan
housing inside the suction grill.
Obstacle
(Hanging position)
Outlook and
dimensions
(Hanging position)
or more
(Service Space)
Hanging bolt
1.13
(Required space)
11
General Outline
ESIEN05-04
FHQ60, 71B
The illustration below shows the outlook and the dimensions of the unit (mm).
ESIEN05-04
Components
General Outline
Component
Air outlet
Air filter
Suspension bracket
10
11
12
13
14
15
Position of the hole in the wall for piping straight trough the wall
16
17
18
3
4
5
127
128
(Required space)
or more
Floor side
Drain pipe
connection
(For left piping)
(Required space)
The front
4
Brand name plate
(Note 2)
or more
(Service Space)
NOTES:
1. Location of units Name plate: Bottom of fan
housing inside the suction grill.
Obstacle
(Hanging position)
Outlook and
dimensions
(Hanging position)
or more
(Service Space)
Hanging bolt
1.14
(Required space)
11
General Outline
ESIEN05-04
FHQ100B
The illustration below shows the outlook and the dimensions of the unit (mm).
ESIEN05-04
Components
General Outline
Component
Air outlet
Air filter
Suspension bracket
10
11
12
13
14
15
Position of the hole in the wall for piping straight trough the wall
16
17
18
3
4
5
129
130
(Required space)
or more
Floor side
Drain pipe
connection
(For left piping)
(Hanging position)
or more
(Required space)
The front
Brand name plate
(Note 2)
or more
(Service Space)
NOTES:
1. Location of units Name plate: Bottom of fan
housing inside the suction grill.
Obstacle
(Hanging position)
or more
(Service Space)
Hanging bolt
Outlook and
dimensions
1.15
(Required space)
11
General Outline
ESIEN05-04
FHQ125B
The illustration below shows the outlook and the dimensions of the unit (mm).
ESIEN05-04
Components
General Outline
Component
Air outlet
Air filter
Suspension bracket
10
11
12
13
14
15
Position of the hole in the wall for piping straight trough the wall
16
17
18
3
4
5
131
132
or more
or more
or more
Suspension bolt
or more
or more
(Required space)
2.In case of using infrared remote control, this is the position for the
signal receiver. Refer to the drawing of infrared remote control for
detail.
NOTES:
1. Location of units name plate: on bell mouth.
3
Required space
Outlook and
dimensions
Drain
connection
location for rear
piping
1.16
Suspension position
11
Drain
connection
location for
upwards piping
General Outline
ESIEN05-04
FUQ71B
The illustration below shows the outlook and the dimensions of the unit (mm).
ESIEN05-04
Components
General Outline
Component
Air outlet
10
3
4
5
133
134
or more
or more
or more
Suspension bolt
or more
or more
(Required space)
2.In case of using infrared remote control, this is the position for the
signal receiver. Refer to the drawing of infrared remote control for
detail.
NOTES:
1. Location of units name plate: on bell mouth.
3
Required space
Outlook and
dimensions
Drain
connection
location for rear
piping
1.17
Suspension position
11
Drain
connection
location for
upwards piping
General Outline
ESIEN05-04
FUQ100, 125B
The illustration below shows the outlook and the dimensions of the unit (mm).
ESIEN05-04
Components
General Outline
Component
Air outlet
10
3
4
5
135
136
hole
Mounting Location
5
Approx.
Approx.
Approx.
50 OR MORE
(Required space)
2500 OR MORE
For installation in
50 or more
(Required space) high spaces
hole
(Piping and
Wiring intake)
Piping
direction
Outside line
Piping
direction
50 or more
(Required space)
Dimensions for
full open front
panel.
120 or less
Outlook and
dimensions
NOTES
1. Location of units Name
Plate: Right side surface of
casing
Approx.
1.18
30 or more
(Required space)
11
Piping direction
General Outline
ESIEN05-04
FAQ71B
The illustration below shows the outlook and the dimensions of the unit (mm).
ESIEN05-04
Components
General Outline
Component
Front panel
Front grille
Air outlet
Gas pipe
Liquid pipe
Drain hose
Grounding terminal
3
4
5
137
or more
138
Detail A
(Mounting hole for installation plate)
Mounting Location
Approx.
Approx.
Approx.
Ceiling surface
4
Brand name plate
(Note 2)
50 or more
(Required space)
hole
(Piping and
Wiring intake)
or more
(Service space
for air filter)
NOTES:
1. Location general rated name plate
Right side plate outside surface
3
or more
Outlook and
dimensions
(Required space)
11
1.19
(Required space)
Piping direction
General Outline
ESIEN05-04
FAQ100B
The illustration below shows the outlook and the dimensions of the unit (mm).
ESIEN05-04
Components
General Outline
Component
Front grille
Air filter
Discharge outlet
Earth terminal
3
4
5
139
140
NOTES:
300 or more
(Service space)
Suspension Bolt
Outlook and
dimensions
VIEW A
VIEW B
1.20
300 or more
(Installation space)
11
960 (Suspension
General Outline
ESIEN05-04
FDEQ71, 100B
The illustration below shows the outlook and the dimensions of the unit (mm).
ESIEN05-04
Components
General Outline
Component
Air filter
Nameplate
3
4
5
141
142
2. For maintenance of the air filter, it is necessary to provide a
service access panel according to the installation method.
(Refer to the Filter installation method drawing).
NOTES:
VIEW B
(Service space)
5
B
Suspension Bolt
Outlook and
dimensions
VIEW A
1.21
300 or more
(Installation space)
11
General Outline
ESIEN05-04
FDEQ125B
The illustration below shows the outlook and the dimensions of the unit (mm).
ESIEN05-04
Components
General Outline
Component
Air filter
Nameplate
3
4
5
143
General Outline
ESIEN05-04
11
3
4
5
144
ESIEN05-04
Specifications
Part 1
1
2
Specifications
2.1
Introduction
Indoor units
Technical specifications
Electrical specifications
See page
2.2FCQ B
146
2.3FCQ D
147
2.4FFQ B
148
2.5FBQ B
149
2.6FDQ B
150
2.7FHQ B
151
2.8FUQ B
152
2.9FAQ B
153
2.10FDEQ B
154
4
5
145
Specifications
11
2.2
ESIEN05-04
FCQ B
Technical
specifications
Specification
Heat exchanger
FCQ35B7V1
FCQ50B7V1
FCQ60B7V1
Face area
0.497 m
HIXA diam. 7
HiXSS diam. 7
Rhombus
14 m/min
15 m/min
18 m/min
18 m/min
28 m/min
10 m/min
11 m/min
14 m/min
14 m/min
21 m/min
24 m/min
14 m/min
15 m/min
18 m/min
18 m/min
28 m/min
31 m/min
10 m/min
11 m/min
14 m/min
14 m/min
21 m/min
24 m/min
1 x QTS46B14M
1 x 19NFB6079
Fan speed
31 m/min
1 x QTS46A17M
1 x 19NFB6078
2 steps (direct drive)
Fan type
Refrigerant
FCQ125B7V3B
2 x 12 x 1.5 mm
Fin type
FCQ100B7V3B
0.331 m
Tube type
Fan
FCQ71B7V3B
2 x 8 x 1.5 mm
Turbo fan
Type
R410A
Temperature control
Weight
Electrical
specifications
Computerized control
Unit
27.0 kg
Specification
Unit
23 kg
FCQ35B7V1
FCQ50B7V1
FCQ60B7V1
Phase
FCQ71B7V3B
Voltage
230V
Frequency
50 Hz
Power consumption
FCQ100B7V3B
FCQ125B7V3B
1~
140 W
161 W
146
0.6 A
1.0 A
1 x 45 W
1 x 90 W
ESIEN05-04
2.3
Specifications
FCQ D
Technical
specifications
1
The table below contains the technical specifications.
Specification
Heat exchanger
FCQ71DV3B
Rows x stages x fin pitch
Face area
FCQ100DV3B
2 x 10 x 1.2 mm
FCQ140DV3B
2 x 12 x 1.2 mm
0.454 m
0.544 m
Tube type
Hi-XSS
Fin type
Fan
FCQ125DV3B
19 m/min
14 m/min
30 m/min
21 m/min
24 m/min
25 m/min
1 x QTS46F15M
1 x QTS46E17M
1x
EHDS50B30DK
(inverter)
1x
EHDS10B120DK
(inverter)
Fan speed
Fan type
Refrigerant
Turbo fan
Type
R410A
Air filter
Electrical
specifications
Microcomputer control
Unit
24 kg
28 kg
FCQ71DV3B
Phase
FCQ100DV3B
FCQ125DV3B
FCQ140DV3B
1~
Voltage
230V
Frequency
50 Hz
Temperature control
Weight
0.30 A
0.70 A
1 x 30 W
1 x 120 W
147
Specifications
11
2.4
ESIEN05-04
FFQ B
Technical
specifications
FFQ25B7V1B
FFQ35B7V1B
0.269 m
Tube type
HiXSS diam. 7
Multi louver fin
9.0 m/min
10.0 m/min
12.0 m/min
15.0 m/min
6.5 m/min
6.5 m/min
8.0 m/min
10.0 m/min
9.0 m/min
10.0 m/min
15.0 m/min
6.5 m/min
6.5 m/min
10.0 m/min
1 x QTS32C15M
1 x D16P52A23
Fan speed
2 steps
Fan type
Refrigerant
Turbo fan
Type
R410A
Air filter
Electrical
specifications
Microcomputer control
Unit
17.5 kg
FFQ25B7V1B
FFQ35B7V1B
Fan motor
FFQ50B7V1B
Phase
1~
Voltage
230V
Frequency
FFQ60B7V1B
50 Hz
Power consumption
73 W
84 W
97 W
120 W
0.37 A
0.40 A
0.49 A
0.61 A
148
Temperature control
Weight
FFQ60B7V1B
2x10x1.5 mm
Face area
Fin type
Fan
FFQ50B7V1B
0.60 A
0.70 A
1 x 55 W
ESIEN05-04
2.5
Specifications
FBQ B
Technical
specifications
1
The table below contains the technical specifications.
Specification
Heat exchanger
FBQ35B7V1
FBQ50B7V1
FBQ60B7V1
0.132 m
Tube type
0.338 m
Hi-XSS diam. 7
Rhombus
11.5 m/min
14.0 m/min
19.0 m/min
19.0 m/min
27.0 m/min
35.0 m/min
9.0 m/min
10.0 m/min
14.0 m/min
14.0 m/min
20.0 m/min
24.0 m/min
11.5 m/min
14.0 m/min
19.0 m/min
19.0 m/min
27.0 m/min
35.0 m/min
9.0 m/min
10.0 m/min
14.0 m/min
14.0 m/min
20.0 m/min
24.0 m/min
1 x QD18G3BM
1 x CA-0513D
Fan speed
1 x CA-0514D
2 x QD18G2BM
3 x QD18G2BM
1 x CA-0515SEK
1 x A37P135G20
Type
R410A
_
Fan motor thermal fuse 152
Air filter
Temperature control
Computerized control
Unit
30 kg
31 kg
FBQ35B7V1
FBQ50B7V1
41 kg
51 kg
52 kg
FBQ71B7V3B
FBQ100B7V3B
FBQ125B7V3B
FBQ60B7V1
Phase
1~
Voltage
230 V
Frequency
50Hz
Power consumption
Specification
Unit
+/-2
Electrical
specifications
0.5 A
0.7 A
1 x 65 W
1 x 85 W
Fan type
Weight
FBQ125B7V3B
Refrigerant
FBQ100B7V3B
0.221 m
HI-XA diam. 7
Fin type
Fan
FBQ71B7V3B
3 x 14 x 1.75 mm
0.9 A
1 x 125 W
1.0 A
1 x 125 W
1 x 135 W
1 x 225 W
149
Specifications
11
2.6
ESIEN05-04
FDQ B
Technical
specifications
FDQ125B7V3B
Rows x stages x fin pitch
3 x 14 x 1.75 mm
0.634 m
Tube type
Hi-XSS diam. 7
Hi-XSS (8)
Rhombus
43.0 m/min
69 m/min
89 m/min
43.0 m/min
69 m/min
89 m/min
1x
DPA216-178NB
1x
DPC241-241NB
1 step (direct drive)
Fan type
Sirocco
Type
R410A
Air filter
Temperature control
Weight
Non-symmetric fin
Fan speed
Refrigerant
3 x 24 x 2.00 mm
0.338 m
FDQ250B7V3B
Face area
Fin type
Fan
FDQ200B7V3B
59.0 kg
93 Kg
4
Electrical
specifications
5
Fan motor
150
FDQ125B7V3B
FDQ200B7V3B
FDQ250B7V3B
Phase
1~
1~
1~
Voltage
230 V
230 V
230 V
Frequency
50Hz
50Hz
50Hz
Power consumption
4.2 A
6.8 A
7.6 A
1 x 500 W
1 x 650 W
1 x 1000 W
ESIEN05-04
2.7
Specifications
FHQ B
Technical
specifications
1
The table below contains the technical specifications.
Specification
Heat exchanger
FHQ35BUV1B
FHQ50BUV1B
FHQ60BUV1B
2 x 12 x 1.75 mm
3 x 12 x 1.75 mm
2 x 12 x 1.75 mm
Face area
0.182 m
FHQ125BUV1B
0.293 m
0.341 m
30.0 m/min
N-Hix
Fin type
Multi louver
13.0 m/min
17.0 m/min
17.0 m/min
24.0 m/min
10.0 m/min
13.0 m/min
14.0 m/min
20.0 m/min
25.0 m/min
13.0 m/min
16.0 m/min
17.0 m/min
24.0 m/min
30.0 m/min
10.0 m/min
13.0 m/min
14.0 m/min
20.0 m/min
25.0 m/min
2 x QD12K1AH
1 x QD12K1BH
3 x QD12K1AH
1 x QD12K1BH
Refrigerant
FHQ100BUV1B
3 x 12 x 1.75 mm
0.233 m
Tube type
Fan
FHQ71BUV1B
3 x QD12K2AH
1 x QD12K2BH
D09P62A20
D10P130H23
Fan speed
2 steps
Fan type
Sirocco
Type
R410A
Removable/washable
Temperature control
Microcomputer control
Weight
Unit
Electrical
specifications
24 kg
25 kg
27 kg
FHQ35BUV1B
FHQ50BUV1B
35 kg
FHQ60BUV1B
FHQ71BUV1B
Phase
1~
Voltage
230 V
Frequency
FHQ100BUV1B
FHQ125BUV1B
135 W
144 W
50Hz
Power consumption
Fan motor
32 kg
Specification
Unit
111 W
0.45 A
115 W
0.52 A
117 W
0.6 A
0.7 A
1 x 62 W
1 x 130 W
151
Specifications
11
2.8
ESIEN05-04
FUQ B
Technical
specifications
FUQ71BUV1B
Rows x stages x fin pitch
Face area
3 x 6 x 1.5 mm
0.353 m
N-Hix
Fin type
Multi louver
19.0 m/min
29.0 m/min
32.0 m/min
14.0 m/min
21.0 m/min
23.0 m/min
19.0 m/min
29.0 m/min
32.0 m/min
14.0 m/min
21.0 m/min
23.0 m/min
1 x QTS48A10M
1 x D16P45R23
Fan speed
R410A
Fan motor thermal protector:
Air filter
Electrical
specifications
Microcomputer control
Unit
25 kg
31 kg
FUQ71BUV1B
Phase
1~
220-240 V
Power consumption
FUQ125BUV1B
50 Hz
180 W
FUQ100BUV1B
Voltage
Frequency
152
Temperature control
Weight
1 x D17P90J23
Turbo fan
Type
1 x QTS50B15M
2 steps
Fan type
Refrigerant
FUQ125BUV1B
3 x 8 x 1.5 mm
0.265 m
Tube type
Fan
FUQ100BUV1B
289 W
_
0.6 A
1.0 A
1 x 45 W
1 x 90 W
ESIEN05-04
2.9
Specifications
FAQ B
Technical
specifications
1
The table below contains the technical specifications.
Specification
Heat exchanger
FAQ71BUV1B
FAQ100BUV1B
2 x 16 x 1.4 mm
2 x 12 x 1.4 mm
Face area
0.289 m
0.332 m
Tube type
Hi-XA
Fin type
Fan
N-Hix
Multi louver
19.0 m/min
23.0 m/min
15.0 m/min
19.0 m/min
19.0 m/min
23.0 m/min
15.0 m/min
19.0 m/min
1 x QCL9886M
1 x QCL1163MA +
1 x QCL1163MB
1x
(ARW30R8P43DA)
1 x D09P49A23
Fan speed
2 steps
Fan type
Refrigerant
Microcomputer control
Unit
13 kg
26 kg
FAQ71BUV1B
1~
Voltage
220-240 V
Power consumption
50 Hz
68 W
101 W
_
FAQ100BUV1B
Phase
Frequency
Temperature control
Electrical
specifications
R410A
Fan motor thermal OFF: 130 +/- 5 C
protector: ON: 83 +/- 20 C
Air filter
Weight
Type
0.4 A
1 x 43 W
1 x 49 W
153
Specifications
11
2.10
ESIEN05-04
FDEQ B
Technical
specifications
FDEQ71B7V3B
Rows x stages x fin pitch
FDEQ100B7V3B
3 x 14 x 1.75 mm
Face area
0.226 m
Tube type
Rhombus
16.0 m/min
24.0 m/min
30.0 m/min
12.0 m/min
17.0 m/min
20.0 m/min
19.0 m/min
28.0 m/min
35.0 m/min
14.0 m/min
20.0 m/min
24.0 m/min
MLA6027
MLA6028
Fan type
Sirocco
R410A
Fan motor thermal fuse: 152 +/-2 C
Air filter
Temperature control
Weight
Electrical
specifications
Computerized control
Unit
38.1 kg
48.6 kg
FDEQ71B7V3B
1~
Voltage
230 V
Power consumption
195 W
415 W
FDEQ125B7V3B
50 Hz
150 W
FDEQ100B7V3B
Phase
Frequency
154
A37P225E23
Type
2 x QD18G2AM
1 x QD18G2BM
2 x QD18G3BM
Fan speed
Refrigerant
0.344 m
Hi-XSS diam. 7
Fin type
Fan
FDEQ125B7V3B
_
1 x 130 W
1 x 155 W
1 x 225 W
ESIEN05-04
Functional Diagrams
Part 1
1
3
Functional Diagrams
3.1
Introduction
Functional
diagrams
Functional diagrams
See page
3.2Indoor Piping
156
158
3.4Piping Components
159
4
5
155
Functional Diagrams
11
3.2
ESIEN05-04
Indoor Piping
2
R3T (*)
4
R1T
Heating
Cooling
R2T
Liquid piping
1a
Gas piping
4
1a
Indoor unit
(*) Remark
156
FCQ35~60B
FFQ25~60B
FBQ35~60B
FHQ35~60B
ESIEN05-04
Piping components
(*) Remark
Functional Diagrams
The table below contains the different components of the functional diagrams.
No.
Component
Function / remark
1a
Flare connection
Heat exchanger
The heat exchanger is of the multi louvre fin type. Hi-X -tubes and coated waffle louvre fins are
used.
Filter
The filter is used to collect impurities, which may enter the system during installation and is also
used to avoid blockage of the capillaries and other fine mechanical parts of the unit.
Fan
Depending on indoor unit type, an axial or centrifugal fan is used. See chapter on specifications
for the exact type.
Thermistor
Sensor R3T on indoor coil of FCQ35~60B, FFQ35~60B, FBQ35~60B & FHQ35~60BU is not used
when connected to sky-air outdoor units (RR, RQ, RZQ).
4
5
157
Functional Diagrams
11
3.3
ESIEN05-04
Indoor units
FCQ35B
9.5 mm
6.4 mm
FCQ50, 60B
12.7 mm
6.4 mm
15.9 mm
9.5 mm
15.9 mm
9.5 mm
FFQ25, 35B
9.5 mm
6.4 mm
FFQ50, 60B
12.7 mm
6.4 mm
FBQ35B
9.5 mm
6.4 mm
FBQ50, 60B
12.7 mm
6.4 mm
15.9 mm
9.5 mm
FDQ125B
15.9 mm
9.5 mm
FDQ200B
28.6 mm
12.7 mm
FDQ250B
28.6 mm
15.9 mm
FHQ35B
9.5 mm
6.4 mm
FHQ50, 60B
12.7 mm
6.4 mm
15.9 mm
9.5 mm
15.9 mm
9.5 mm
FAQ71, 100B
15.9 mm
9.5 mm
15.9 mm
9.5 mm
Model
3
4
5
158
ESIEN05-04
Part 1
1
3.4
Piping Components
Components
The table below contains the different components of the functional diagrams.
No.
Component
Function / remark
1a
Flare connection
Heat exchanger
The heat exchanger is of the multi louvre fin type. Hi-X -tubes and coated waffle louvre fins are
used.
Filter
The filter is used to collect impurities, which may enter the system during installation and is also
used to avoid blockage of the capillaries and other fine mechanical parts of the unit.
Fan
Thermistor
3
4
5
159
ESIEN05-04
11
3
4
5
160
ESIEN05-04
Wiring Diagrams
Part 1
1
4
Wiring Diagrams
4.1
Introduction
Indoor units:
Wiring diagram
See page
162
164
166
168
170
4.7FBQ71B
172
4.8FBQ100, 125B
174
176
178
180
182
4.13FAQ71B
184
4.14FAQ100B
186
4.15FDEQ71B
188
4.16FDEQ100B
190
4.17FDEQ125B
192
4
5
161
Wiring Diagrams
11
4.2
ESIEN05-04
Wiring diagram
indoor
Wired remote
control
outdoor
Norm.emerg.
Note 3
Receiver / Display unit
remote control
(Slave)
(Master)
Outdoor
unit
: Field wiring
: Connector
: Wire lamp
: Protective earth (screw)
: Terminal
adapter for
wiring
Colors:
BLK : Black
RED : Red
WHT : White
YLW : Yellow
Switch box
Notes:
1. Use copper conductors only.
2. When using the central remote control, see manual for connection to
the unit.
3. X24A is connected when the infrared remote control kit is used.
4. The remote control model varies according to the combination
system. See technical data and catalogs before connecting.
162
ESIEN05-04
Wiring Diagrams
33H
Float switch
A1P
SS1
C1R
Capacitor (M2F)
F1U
HAP
A2P, A3P
M1A
BS
ON/OFF button
M2F
H1P
M3P
H2P
Q1F
H3P
R1T
Thermistor (Air)
H4P
R2T
Thermistor (Liquid)
SS1
R3T
Thermistor (Coil)
SS2
RyP
SS1
T1R
Transformer (220V~240V/22 V)
RyC, RyF
X1M
X2M
PC
X60A, X61A
RC
X33A
TC
X35A
X40A
3
Magnetic relay
4
5
163
Wiring Diagrams
11
4.3
ESIEN05-04
Wiring diagram
indoor
Wired remote
control
outdoor
Norm.emerg.
Note 3
Receiver / Display unit
remote control
: Field wiring
: Connector
: Wire lamp
: Protective earth (screw)
: Terminal
(Slave)
(Master)
Outdoor
unit
Remote
ON/OFF
Forced OFF
adapter for
wiring
Colors:
BLK : Black
RED : Red
WHT : White
YLW : Yellow
Switch box
Notes:
1. Use copper conductors only.
2. When using the central remote control, see manual for connection to
the unit.
3. X24A is connected when the infrared remote control kit is used.
4. The remote control model varies according to the combination
system. See technical data and catalogs before connecting.
164
ESIEN05-04
Wiring Diagrams
S1L
Float switch
A1P
A2P, A3P
C1R
Capacitor (M2F)
BS
ON/OFF button
HAP
H1P
M1A
H2P
M2F
H3P
M3P
H4P
Q1F
SS1
R1T
Thermistor (Air)
SS2
R2T
Thermistor (Liquid)
RyP
SS1
RyC, RyF
T1R
Transformer (220V~240V/22 V)
X1M
X2M
X60A, X61A
PC
X33A
RC
X35A
TC
X40A
Magnetic relay
3
4
165
Wiring Diagrams
11
4.4
ESIEN05-04
Wiring diagram
to Outdoor
Unit
Norm.Emg.
Note 5
Note 5
Note 2
Central
remote
control
Wired remote
control
to Outdoor Unit
In case of simultaneous
operation system
Indoor unit
Indoor unit
(Slave)
(Master)
remote control
Switch box
(Indoor Unit)
Notes
1.
: Terminal
: Connector
: Field wiring
2. In case using central remote control, connect it to the unit in accordance with the
attached installation manual.
3. remote control model varies according to the combination system, confirm
engineering materials and catalogs, etc. before connecting.
4. Confirm the method of setting the selector switch (SS1, SS2) by installation
manual and engineering data, etc.
5. Ground the shield of the remote control cord to the indoor unit (in case of using
shield wire).
6. Symbols show as follows:
RED : Red
BLK : Black
WHT : White
YLW : Yellow
GRN : Green
ORG : Orange
BRN : Brown
PNK : Pink
GRY : Gray
BLU : Blue
166
ESIEN05-04
Wiring Diagrams
A1P
A2P
A4P
A3P
A5P
HAP
BS1
KPR
H1P
M1F
H2P
M1P
H3P
M1S
H4P
R1T
Thermistor (Air)
SS1
R2T
Thermistor (Coil)
SS2
S1L
Float switch
SS1
X1M
Terminal strip
R1T
Thermistor (Air)
X2M
Terminal strip
SS1
Z1C
Noise filter
Z2C
Noise filter
PC
Power circuit
X33A
RC
X35A
TC
3
4
5
167
Wiring Diagrams
11
4.5
ESIEN05-04
Wiring diagram
to Outdoor Unit
to Outdoor Unit
remote control
Note 3
Note 5
Wired remote
control
Note 3
Receiver / Display unit
Notes
1.
: Terminal
: Connector
: Field wiring
2. In case using central remote control, connect it to the unit in accordance with the
attached installation manual.
3. X24A is connected when the infrared remote control kit is being used.
4. remote control model varies according to the combination system, confirm
engineering materials and catalogs, etc. before connecting.
5. Ground the shield of the remote control cord to the indoor unit (in case of using
shield wire).
6. Symbols show as follows:
BLK : Black
WHT : White
YLW : Yellow
PRP : Purple
GRY : Gray
BLU : Blue
168
Control box
ESIEN05-04
Wiring Diagrams
A1P
C1
Capacitor (M1F)
R1T
Thermistor (Air)
F1U
SS1
HAP
KPR
M1F
A3P
M1P
A4P
M1S
BS1
Q1M
H1P
R1T
Thermistor (Air)
H2P
R2T
Thermistor (Coil~1)
H3P
R3T
Thermistor (Coil~2)
H4P
S1L
Float switch
SS1
T1R
Transformer (220~240V/22 V)
SS2
V1TR
X1M
Terminal strip
X2M
Terminal strip
X33A
RC
X35A
TC
X40A
X60A, X61A
4
5
169
Wiring Diagrams
11
4.6
ESIEN05-04
Wiring diagram
35,50,60,CLASS
outdoor
indoor
Wired remote
control
Details of Wired
remote control
(Optional accessory)
Compressor
Operation
Fan
Operation
Terminals for
Operation Indicator
Notes:
1. When using the central remote control, see manual for connection to
the unit.
2. The remote control model varies according to the combination
system. See technical materials and catalogues, etc. before
connecting.
170
: Field wiring
: Terminal
: Connector
: Wire lamp
: Protective earth (screw)
Colors:
BLK : Black
BLU : Blue
GRY : Gray
ORG : Orange
RED : Red
WHT : White
ESIEN05-04
Wiring Diagrams
33H
Float switch
A1P
BS1
C1R
Capacitor (Fan)
BS2
F1U
BS3, BS8
F1T
BS4, BS9
ON/OFF button
HAP
BS6
M1F
Motor (Fan)
BS7
M1P
BS11
R1T
Thermistor (Air)
BS12
R2T
Thermistor (Liquid)
BS14
R3T
Thermistor (Coil)
H1P
RyF1-4
LCD
RyP
SS1
SS1
T1R
X1M
Terminal strip
X60A, X61A
X2M
Terminal strip
RC
X33A
TC
X35A
X40A
Magnetic relay
171
Wiring Diagrams
11
4.7
ESIEN05-04
FBQ71B
Wiring diagram
71 CLASS
outdoor
indoor
Wired remote
control
3
4
Fan
Operation
Details of Wired
remote control
(Optional accessory)
Remote
ON/OFF
Forced OFF
Compressor
Operation
Terminals for
Operation Indicator
172
: Field wiring
: Terminal
: Connector
: Wire lamp
: Protective earth (screw)
Colors:
BLK : Black
BLU : Blue
GRY : Gray
ORG : Orange
RED : Red
WHT : White
ESIEN05-04
Wiring Diagrams
S1L
Float switch
A1P
BS1
C1R
Capacitor (Fan)
BS2
F1T
BS3, BS8
HAP
BS4, BS9
M1F
Motor (Fan)
BS6
M1P
BS7
R1T
Thermistor (Air)
BS11
R2T
Thermistor (Coil)
BS12
RyF1-4
BS14
RyP
H1P
SS1
LCD
T1R
SS1
X1M
Terminal strip
X2M
Terminal strip
RC
X60A, X61A
TC
Magnetic relay
ON/OFF button
X33A
X35A
X40A
4
5
173
Wiring Diagrams
11
4.8
ESIEN05-04
FBQ100, 125B
Wiring diagram
100,125 CLASS
outdoor
indoor
Wired remote
control
Fan
Operation
4
Details of Wired
remote control
(Optional accessory)
Remote
ON/OFF
Forced OFF
Compressor
Operation
Terminals for
Operation Indicator
174
: Field wiring
: Terminal
: Connector
: Wire lamp
: Protective earth (screw)
Colors:
BLK : Black
BLU : Blue
GRY : Gray
ORG : Orange
RED : Red
WHT : White
BRN : Brown
ESIEN05-04
Wiring Diagrams
S1L
Float switch
A1P
BS1
C1R
Capacitor (Fan)
BS2
F1T
BS3, BS8
HAP
BS4, BS9
M1F
Motor (Fan)
BS6
M1P
BS7
R1T
Thermistor (Air)
BS11
R2T
Thermistor (Coil)
BS12
RyF1-4
BS14
RyP
H1P
SS1
LCD
T1R
SS1
X1M
Terminal strip
X2M
Terminal strip
RC
X60A, X61A
TC
Magnetic relay
ON/OFF button
X33A
X35A
X40A
4
5
175
Wiring Diagrams
11
4.9
ESIEN05-04
Wiring diagram
125 CLASS
outdoor
Wired remote
control
indoor
3
4
Details of Wired
remote control
Switch box
Remote
ON/OFF
Forced OFF
Compressor
Operation
Fan
Operation
Terminals for
Operation Indicator
176
Notes:
: Connector
Colors:
BLK : Black
BLU : Blue
RED : Red
WHT : White
YLW : Yellow
ESIEN05-04
Wiring Diagrams
A1P
BS4
A3P
BS9
C1R
Capacitor (Fan)
BS6
F1T
BS7
HAP
BS12
K1F
BS14
M1F
Motor (Fan)
H1P
R1T
Thermistor (Air)
LCD
R2T
Thermistor (Coil)
SS1
RyF1
SS1
T1R
Transformer (230V/21.8V)
RyC, RyF
X1M
Terminal strip
RC
TC
X60A, X61A
X33A
Magnetic relay
BS1
ON/OFF button
X35A
BS2
X40A
BS3, BS8
3
4
5
177
Wiring Diagrams
11
4.10
ESIEN05-04
Wiring diagram
to Outdoor Unit
remote control
to Outdoor
Unit
Note 4
Note 6
Note 4
Receiver / Display unit
Note 6
Control box
Notes
1.
: Terminal
: Connector
2.
: Field wiring
3. In case using central remote control, connect it to the unit in accordance with the
attached installation manual.
4. X24A is connected when the infrared remote control kit is being used.
5. remote control model varies according to the combination system, confirm
engineering materials and catalogs, etc. before connecting.
6. In case installing the drain pump (M1P), remove the jumper connector of X15A
and execute the additional wiring for float switch and drain pump.
7. Symbols show as follows:
RED : Red
BLK : Black
WHT : White
YLW : Yellow
PRP : Purple
GRY : Gray
BLU : Blue
178
ESIEN05-04
Wiring Diagrams
A1P
C1
Capacitor (M1F)
R1T
Thermistor (Air)
F1U
SS1
HAP
KAR
KPR
A3P
M1F
A4P
M1S
BS1
Q1M
H1P
R1T
Thermistor (Air)
H2P
R2T
Thermistor (Coil~1)
H3P
R3T
Thermistor (Coil~2)
H4P
S1Q
SS1
T1R
Transformer (220~240V/22 V)
SS2
V1TR
X1M
Terminal block
X2M
Terminal block
X15A
RC
X25A
TC
X33A
X35A
X40A
X60A, X61A
4
5
179
Wiring Diagrams
11
4.11
ESIEN05-04
Wiring diagram
to Outdoor Unit
remote control
to Outdoor
Unit
Note 4
4
Note 6
Note 4
Receiver / Display unit
Note 6
Notes
Control
box
1.
: Terminal
: Connector
2.
: Field wiring
3. In case using central remote control, connect it to the unit in accordance with the
attached installation manual.
4. X24A is connected when the infrared remote control kit is being used.
5. remote control model varies according to the combination system, confirm
engineering materials and catalogs, etc. before connecting.
6. In case installing the drain pump (M1P), remove the jumper connector of X15A
and execute the additional wiring for float switch and drain pump.
7. Symbols show as follows:
RED : Red
BLK : Black
WHT : White
YLW : Yellow
PRP : Purple
GRY : Gray
BLU : Blue
180
ESIEN05-04
Wiring Diagrams
A1P
C1
Capacitor (M1F)
A2P
HAP
A3P
KAR
BS1
KPR
H1P
M1F
H2P
M1S
H3P
Q1M
H4P
R1T
Thermistor (Air)
SS1
R2T
Thermistor (Coil)
SS2
S1Q
T1R
Transformer (220~240V/22 V)
V1TR
X15A
X1M
Terminal block
X25A
X2M
Terminal block
X33A
RC
X35A
TC
X40A
X60A, X61A
Thermistor (Air)
SS1
4
5
181
Wiring Diagrams
11
4.12
ESIEN05-04
Wiring diagram
Indoor unit
(Slave)
remote control
to Outdoor
Unit
Wired remote
control
Note 4
Norm.Emg.
4
Note 4
Receiver / Display unit
Notes
1.
2.
: Terminal
: Connector
: Field wiring
3. In case using central remote control, connect it to the unit in accordance with the
attached installation manual.
4. X24A is connected when the infrared remote control kit is being used.
5. remote control model varies according to the combination system, confirm
engineering materials and catalogs, etc. before connecting.
6. Symbols show as follows:
RED : Red
BLK : Black
WHT : White
YLW : Yellow
GRN : Green
BLU : Blue
Control box
7. Confirm the method of setting the selector switch (SS1, SS2) by installation
manual and engineering materials, etc.
182
ESIEN05-04
Wiring Diagrams
A1P
C1
Capacitor (M1F)
R1T
Thermistor (Air)
HAP
SS1
KAR
KPR
M1F
A2P
M1P
A3P
M1S
BS1
Q1M
H1P
R1T
Thermistor (Air)
H2P
R2T
Thermistor (Coil)
H3P
S1L
Float switch
H4P
S1Q
SS1
SS1
SS2
T1R
Transformer (220~240V/22 V)
V1TR
X1M
Terminal block
X35A
X2M
Terminal block
X60A, X61A
RC
TC
4
5
183
Wiring Diagrams
11
4.13
ESIEN05-04
FAQ71B
Wiring diagram
to Outdoor
Unit
Note 4
Note 4
In case of simultaneous
operation system
Indoor unit
Indoor unit
(Master)
(Slave)
Note 2
Transmission wiring
Central remote control
to Outdoor Unit
Norm.Emg.
remote control
Notes
1.
Front
Side
: Terminal
: Connector
: Field wiring
Control box
2. In case using central remote control, connect it to the unit in accordance with the
attached installation manual.
3. remote control model varies according to the combination system, confirm
engineering materials and catalogs, etc. before connecting.
4. X24A is connected when the infrared remote control kit is being used.
5.
Shows short circuit connector.
6. Symbols show as follows:
RED : Red
WHT : White
GRN : Green
BLK : Black
ORG : Orange
BRN : Brown
BLU : Blue
YLW : Yellow
PNK : Pink
7. Confirm the method of setting the selector switch (SS1, SS2) of wired remote
control and infrared remote control by installation manual and engineering data,
etc.
184
ESIEN05-04
Wiring Diagrams
A1P
HAP
A2P
M1F
A3P
M1S
BS1
R1T
Thermistor (Air)
H1P
R2T
Thermistor (Coil)
H2P
SS1
H3P
X1M
Terminal block
H4P
X2M
Terminal block
SS1
PS
Power supply
SS2
RC
TC
Thermistor (Air)
SS1
X35A
3
4
5
185
Wiring Diagrams
11
4.14
ESIEN05-04
FAQ100B
Wiring diagram
to Outdoor Unit
Indoor unit
(Master)
remote control
Wired remote
control
to Outdoor
Unit
Note 4
Norm.
Emg.
4
5
Control box
Notes
1.
: Terminal
: Connector
2.
: Field wiring
3. In case using central remote control, connect it to the unit in accordance with the
attached installation manual.
4. X24A is connected when the infrared remote control kit is being used.
5. remote control model varies according to the combination system, confirm
engineering materials and catalogs, etc. before connecting.
6. Symbols show as follows:
RED : Red
BLK : Black
WHT : White
YLW : Yellow
ORG : Orange
GRY : Gray
PRP : Purple
BLU : Blue
7. Confirm the method of setting the selector switch (SS1, SS2) by installation
manual and engineering data, etc.
8. X15A, X25A are connected when the drain up kit is being used. Connect it to the
kit in accordance with the attached installation manual.
186
ESIEN05-04
Wiring Diagrams
A1P
A2P
A3P
C1
Capacitor (M1F)
A4P
HAP
BS1
KAR
H1P
KPR
H2P
M1F
H3P
M1S
H4P
Q1M
SS1
R1T
Thermistor (Air)
SS2
R2T
Thermistor (Coil)
S1Q
SS1
X15A
V1TR
X25A
X1M
Terminal block
X35A
X2M
Terminal block
X60A, X61A
RC
TC
Thermistor (Air)
SS1
4
5
187
Wiring Diagrams
11
4.15
ESIEN05-04
FDEQ71B
Wiring diagram
71 CLASS
outdoor
indoor
Wired remote
control
3
4
Details of Wired
remote control
(Optional Accessory)
Compressor
Operation
Fan
Operation
Terminals for
Operation Indicator
Remote
ON/OFF
Forced OFF
: Field wiring
: Terminal
: Connector
: Wire Clamp
: Protective earth (screw)
Colors:
BLK : Black
BLU : Blue
GRY : Grey
ORG : Orange
RED : Red
WHT : White
Notes:
1. When using the central remote control, see manual for connection to the unit.
2. The remote control model varies according to the combination system.
See technical materials and catalogues, etc. before connecting.
188
ESIEN05-04
Wiring Diagrams
A1P
C1R
Capacitor (Fan)
BS1
F1T
BS2
HAP
BS3, BS8
M1F
Motor (Fan)
BS4, BS9
R1T
Thermistor (Air)
BS6
R2T
Thermistor (Coil)
BS7
RyF1-4
BS11
RyP
BS12
SS1
BS14
T1R
H1P
X1M
Terminal strip
LCD
X2M
Terminal strip
SS1
RC
TC
Magnetic relay
X33A
X35A
X40A
ON/OFF button
4
5
189
Wiring Diagrams
11
4.16
ESIEN05-04
FDEQ100B
Wiring diagram
100 CLASS
outdoor
indoor
Wired remote
control
Fan
Operation
4
Details of Wired
remote control
(Optional Accessory)
Compressor
Operation
Terminals for
Operation Indicator
Remote
ON/OFF
Forced OFF
: Field wiring
: Terminal
: Connector
: Wire Clamp
: Protective earth (screw)
Colors:
BLK : Black
BLU : Blue
GRY : Grey
ORG : Orange
RED : Red
WHT : White
BRN : Brown
Notes:
1. When using the central remote control, see manual for connection to the unit.
2. The remote control model varies according to the combination system.
See technical materials and catalogues, etc. before connecting.
190
ESIEN05-04
Wiring Diagrams
A1P
C1R
Capacitor (Fan)
BS1
F1T
BS2
HAP
BS3, BS8
M1F
Motor (Fan)
BS4, BS9
R1T
Thermistor (Air)
BS6
R2T
Thermistor (Coil)
BS7
RyF1-4
BS11
RyP
BS12
SS1
BS14
T1R
H1P
X1M
Terminal strip
LCD
X2M
Terminal strip
SS1
RC
TC
Magnetic relay
X33A
X35A
X40A
ON/OFF button
4
5
191
Wiring Diagrams
11
4.17
ESIEN05-04
FDEQ125B
Wiring diagram
125 CLASS
outdoor
indoor
Wired remote
control
3
4
Details of Wired
remote control
(Optional Accessory)
Compressor
Operation
Fan
Operation
Terminals for
Operation Indicator
Remote
ON/OFF
Forced OFF
: Field wiring
: Terminal
: Connector
: Wire Clamp
: Protective earth (screw)
Colors:
BLK : Black
BLU : Blue
GRY : Grey
ORG : Orange
RED : Red
WHT : White
BRN : Brown
Notes:
1. When using the central remote control, see manual for connection to the unit.
2. The remote control model varies according to the combination system.
See technical materials and catalogues, etc. before connecting.
192
ESIEN05-04
Wiring Diagrams
A1P
C1R
Capacitor (Fan)
BS1
F1T
BS2
HAP
BS3, BS8
M1F
Motor (Fan)
BS4, BS9
R1T
Thermistor (Air)
BS6
R2T
Thermistor (Coil)
BS7
RyF1-4
BS11
RyP
BS12
SS1
BS14
T1R
H1P
X1M
Terminal strip
LCD
X2M
Terminal strip
SS1
RC
TC
Magnetic relay
X33A
X35A
X40A
ON/OFF button
4
5
193
Wiring Diagrams
ESIEN05-04
11
3
4
5
194
ESIEN05-04
Part 1
1
5
5.1
Introduction
Indoor units
PCB layout
See page
196
5.3FCQ100, 125B
197
198
199
1100
1101
1102
1103
5.10FAQ71B
1104
5.11FAQ100B
1105
1106
4
5
195
11
5.2
ESIEN05-04
PCB
C1R
3
4
X1M
196
X2M
Item
Description
PCB
T1R
Transformer
C1R
X1M
X2M
ESIEN05-04
5.3
FCQ100, 125B
X1M
PCB
C1R
Item
Description
PCB
T1R
Transformer
C1R
X1M
X2M
T1R
197
11
5.4
ESIEN05-04
PCB1
3
PCB2
PCB3 X1M
X2M
4
5
198
Item
Description
PCB1
PCB2
PCB3
X1M
X2M
ESIEN05-04
5.5
T1R
4
X1M
PCB
X2M
Item
Description
PCB
T1R
Transformer
C1R
X1M
X2M
199
11
5.6
ESIEN05-04
C1R
4
T1R
X1M
X2M
1100
Item
Description
PCB
T1R
Transformer
C1R
X1M
X2M
ESIEN05-04
5.7
C1R
3
4
T1R
X1M
X2M
Item
Description
PCB
T1R
Transformer
C1R
X1M
X2M
1101
11
5.8
ESIEN05-04
PCB
4
5
1102
Item
Description
PCB
T1R
Transformer
C1R
X1M
X2M
X1M
T1R
X2M
ESIEN05-04
5.9
T1R
3
4
X2M
X1M
C1R
Item
Description
PCB
T1R
Transformer
C1R
X1M
X2M
1103
11
5.10
ESIEN05-04
FAQ71B
The illustration below shows the switch box layout:
X2M
PCB
4
5
X1M
1104
Item
Description
PCB
X1M
X2M
ESIEN05-04
5.11
FAQ100B
1
The illustration below shows the switch box layout:
PCB
X1M
X2M
Item
Description
PCB
X1M
X2M
4
5
1105
11
5.12
ESIEN05-04
X2M
T1M
3
4
PCB
1106
Item
Description
PCB
T1R
Transformer
X1M
X2M
ESIEN05-04
PCB Layout
Part 1
1
6
PCB Layout
6.1
Introduction
Indoor units
See page
1108
1109
1110
1112
1113
1114
1115
1116
1117
1118
6.12FAQ71B
1119
6.13FAQ100B
1120
4
5
1107
PCB Layout
11
6.2
ESIEN05-04
PCB
X10A
X33A
X19A
X60A X61A
X5A
X35A
X24A
3
X15A
X25A
X18A
X36A
X40A
X17A
4
Connectors
1108
Connected to
Description
X5A
X1M
X10A
T1R
X11A
T1R
X15A
33H
Float switch
X17A
R3T
Coil thermistor
X18A
R2T
X19A
R1T
Air thermistor
X20A
M2F
X24A
X2A on A3P
X25A
M3P
X27A
X2M
X33A
X1A on KRP1B
X35A
X1A on KRP4
X36A
M1A
X40A
X60A
X1A on DTA112
X61A
X2A on DTA112
ESIEN05-04
6.3
PCB Layout
PCB
X33A X19A
X10A
X60A X61A
X5A
X35A
X20A
X24A
X15A
X18A
X25A
Connectors
X36A
X40A
Connected to
Description
X5A
X1M
X10A
T1R
X11A
T1R
X15A
S1L
Float switch
X18A
R2T
X19A
R1T
Air thermistor
X20A
M2F
X24A
X2A on A3P
X25A
M3P
X27A
X2M
X33A
X1A on KRP1B
X35A
X1A on KRP4
X36A
M1A
X40A
X60A
X1A on DTA112
X61A
X2A on DTA112
1109
PCB Layout
11
6.4
ESIEN05-04
X54A
X27A
X25A
X55A
X20A
4
Connectors
1110
Connected to
Description
X20A
M1F
X25A
M1P
X27A
X2M
X54A
X55A
X56A
ESIEN05-04
PCB Layout
X57A
X16A
X30A
X24A
X18A
X35A
X15A
3
X58A
Connectors
X6A X33A
Connected to
Description
X6A
Not used
X15A
S1L
Float switch
X16A
A3P
Humidity sensor
X18A
R2T
Coil thermistor
X24A
X2A on A4P
X30A
X1M
X33A
X1A on KRP1B
X35A
X1A on KRP4
X36A
M1S
X40A
Not used
X57A
X58A
1111
PCB Layout
11
6.5
ESIEN05-04
PCB
X11A
X10A
X33A
X60A X61A
X19A
X20A
X5A
X35A
X24A
3
X15A
X25A
X18A
X36A X40A
X17A
4
Connectors
1112
Connected to
Description
X5A
X1M
X10A
T1R
X11A
T1R
X15A
S1L
Float switch
X17A
R3T
X18A
R2T
X19A
R1T
Air thermistor
X20A
M1F
X24A
X2A on A3P
X25A
M1P
X27A
X2M
X33A
X1A on KRP1B
X35A
X1A on KRP4
X36A
M1S
X40A
X60A
X1A on DTA112
X61A
X2A on DTA112
ESIEN05-04
6.6
PCB Layout
PCB
X33A
X11A
X25A
X27A
X15A
X18A
X19A
X21A
X17A
X10A
X35A
Connectors
X5A
X40A
Connected to
Description
X5A
X1M
X10A
T1R
X11A
T1R
X15A
33H
Float switch
X17A
R3T
Coil thermistor
X18A
R2T
X19A
R1T
Air thermistor
X21A
M1F
X25A
M1P
X27A
X2M
X33A
X1A on KRP1B
X35A
X1A on KRP4
X40A
X60A
X1A on DTA112
X61A
X2A on DTA112
1113
PCB Layout
11
6.7
ESIEN05-04
PCB
X33A
X11A
X25A
X27A
X15A
X18A
X21A
X19A
X10A
X35A
Connectors
1114
X40A
X5A
Connected to
Description
X5A
X1M
X10A
T1R
X11A
T1R
X15A
S1L
Float switch
X18A
R2T
X19A
R1T
Air thermistor
X21A
M1F
X25A
M1P
X27A
X2M
X33A
X1A on KRP1B
X35A
X1A on KRP4
X40A
X60A
X1A on DTA112
X61A
X2A on DTA112
ESIEN05-04
6.8
PCB Layout
PCB
X33A
X11A
X27A
X60A
X31A
X18A
X19A
X21A
X10A
X35A
Connectors
X40A
X5A
Connected to
Description
X5A
X1M
X10A
T1R
X11A
T1R
X18A
R2T
X19A
R1T
Air thermistor
X21A
K1F
X27A
X2M
X31A
A3P
PCB
X33A
X1A on KRP1B
X35A
X1A on KRP4
X40A
X60A
X1A on DTA112
X61A
X2A on DTA112
1115
PCB Layout
11
6.9
ESIEN05-04
PCB
X33A
X11A X27A
X14A
X15A
X40A
X20A
X23A
X29A
X18A
X25A
X19A
X17A
X35A
Connectors
1116
X10A X5A
X24A
X26A
Connected to
Description
X5A
X1M
X10A
T1R
X11A
T1R
X14A
S1Q
X15A
X17A
R3T
X18A
R2T
X19A
R1T
Air thermistor
X20A
M1F
X24A
X2A on A3P
X25A
X26A
M1F
X27A
X2M
X29A
M1S
X33A
X1A on KRP1B
X35A
X1A on KRP4
X40A
X60A
X1A on DTA112
X61A
X2A on DTA112
ESIEN05-04
6.10
PCB Layout
PCB
X33A
X11A X27A
X14A
X15A
X40A
X20A
X29A
X18A
X35A
Connectors
X25A
X19A
X10A X5A
X24A
X26A
Connected to
Description
X5A
X1M
X10A
T1R
X11A
T1R
X14A
S1Q
X15A
X18A
R2T
X19A
R1T
Air thermistor
X20A
M1F
X24A
X2A on A2P
X25A
X26A
M1F
X27A
X2M
X29A
M1S
X33A
X1A on KRP1B
X35A
X1A on KRP4
X40A
X60A
X1A on DTA112
X61A
X2A on DTA112
1117
PCB Layout
11
6.11
ESIEN05-04
PCB
X11A
X27A
X14A
X15A
X20A
X29A
X18A
X25A
X19A
X35A
Connectors
1118
X10A X5A
X24A
Connected to
Description
X5A
X1M
X10A
T1R
X11A
T1R
X14A
S1Q
X15A
S1L
Float switch
X18A
R2T
X19A
R1T
Air thermistor
X20A
M1F
X24A
X2A on A3P
X25A
M1P
X27A
X2M
X29A
M1S
X35A
X1A on KRP4
X60A
X1A on DTA112
X61A
X2A on DTA112
ESIEN05-04
6.12
PCB Layout
FAQ71B
PCB
1
The illustration below shows the PCB connectors.
X27A
X20A
3
X30A
X36A
5
X18A
X19A
Connectors
Connected to
X15A
X35A
X15A
X24A
Description
Connector float switch
X18A
R2T
X19A
R1T
Air thermistor
X20A
M1F
X24A
X2A on A2P
X27A
X2M
X30A
X1M
X35A
X1A on KRP4
X36A
M1S
1119
PCB Layout
11
6.13
ESIEN05-04
FAQ100B
PCB
X27A
X11A
X19A
X98A
X20A
X24A X35A
X25A X29A
X5A X10A
Connectors
X18A
Connected to
Description
X5A
X1M
X10A
X2A on A2P
X11A
X1A on A2P
X14A
S1Q
X15A
1120
X26A
X14A X15A
X18A
R2T
X19A
R1T
Air thermistor
X20A
M1F
X24A
X2A on A3P
X25A
M1P
X26A
M1F
X27A
X2M
X29A
M1S
X35A
X1A on KRP4
X60A
X1A on DTA112
X61A
X2A on DTA112
X98A
C1
ESIEN05-04
4
Part 2
Functional Description
This part contains information on the functions used to control the system. Understanding these
functions is vital when diagnosing a malfunction that is related to the functional control.
Overview
2
3
Chapter
See page
1Functional concept
23
4
5
21
ESIEN05-04
1
2
3
22
ESIEN05-04
Functional concept
Part 2
1
1
Functional concept
2
1.1
Introduction
Overview
This chapter will explain more details about the various functions that are programmed for the
Sky - Air R410A indoor units.
See page
1.2Functions of Thermistors
24
25
27
28
1.6Restart Standby
29
1.7Automatic Restart
210
211
213
214
1.11PMV Control
215
1.12Thermostat Control
216
217
219
220
221
222
223
4
5
23
Functional concept
1.2
ESIEN05-04
Functions of Thermistors
Locating the
thermistors
R3T
2
R1T
3
R2T
4
5
Remark
Functions of the
thermistors
Thermistor
1
Location
Indoor air
return
Wiring
symbol
Mode
Function
R1T
Cooling
Thermostat control
PMV control
Thermostat control
PMV control
Freeze-up control
Peak cut-off
Peak cut-off
Heating
Indoor
heat
exchanger
R2T
Cooling
Heating
24
Indoor
heat
exchanger
R3T
Heating
ESIEN05-04
1.3
Functional concept
Purpose
The table below describes the purpose of the forced operating mode.
If...
Starting conditions
Then...
R/C is defective
Forced operating mode can be used to go to cooling or heating. In forced operating mode, the compressor is forced to
operate until the defective indoor or outdoor PCB is back
online.
You can operate the system manually by changing the emergency switch on the indoor and outdoor
PCB from "normal" to "emergency". When the system is operating in "emergency" it can not control
the room temperature.
2
3
Both the indoor and outdoor unit must be set to "emergency" while the power is off.
Ending conditions
Emergency
operation
You can end the emergency operation by changing the "emergency" switch back to "normal" while the
power is OFF.
Below table explains what will happen when the switch is set to "emergency":
Switches ON the
Indoor unit
Indoor fan(s)
Drain pump
Compressor
Outdoor fan(s)
Outdoor unit
How to set
Emergency
Operation
4
5
Action
Normal
Emergency
25
Functional concept
ESIEN05-04
Step
Action
Set the emergency switch on the outdoor PCB to the forced mode you prefer (Cooling or
Heating).
2
3
4
5
Active components
Additional info
26
Component
Forced cooling
Forced heating
Forced defrosting
Compressor
ON
ON
ON
4-way valve
OFF
ON
OFF
H fan speed
H fan speed
OFF
H fan speed
H fan speed
H fan speed
Drain pump
ON
OFF
ON
During emergency operation, do not attempt to operate the equipment from the remote control. The
remote control shows "88" while the emergency operation is active on the indoor unit
If a safety device is activated during emergency, all actuators are turned OFF
In cooling, the unit runs for 20 min and then stops for 10 min in order to avoid freeze-up of the
indoor coil.
Emergency operation can not be carried out when the PCB board itself is defective.
Be sure to set the emergency switch on both the outdoor and indoor unit.
The unit will not regulate the temperature during emergency operation.
Change the position of the emergency switch only when the power is turned off.
ESIEN05-04
1.4
Functional concept
Purpose
The purpose of the outdoor unit identification function is to enable the indoor unit to automatically
determine which operating mode has to be set in function of the type of connected outdoor unit (c/o or
h/p).
Operating modes
Operating modes
h/p
Fan
Cooling
Dry keep
Heating
Fan
Cooling
Dry keep
c/o
2
3
4
Used input
Connection on
indoor PCB
Connection on
outdoor PCB
Indoor PCB
TC & RC
Outdoor PCB
TC & RC
27
Functional concept
1
2
1.5
ESIEN05-04
Outline
When a malfunction on one of the below thermistors occurs, operation will continue while displaying
the applicable alarm on the remote-controller. Fin thermistor malfunction is only displayed when
pressing the "Inspection" button on the remote-controller.
Sensors
Fin thermistor
3
Remark
Simulated operation will not be conducted in case the low pressure sensor or suction thermistor is
malfunctioning.
4
5
28
ESIEN05-04
1.6
Outline
Functional concept
Restart Standby
To prevent the compressor from frequently turning ON and OFF and allow pressure equalization,
forced thermostat OFF will be conducted for 3 minutes after compressor stopping (compressor guard
timer).
Graph
Thermostat OFF
Compressor
Restart standby
complete
ON
OFF
Moves to Stop or
Starting control after
completion of Restart
standby.
ON
OFF
Residual
operation
For 3 minutes
29
Functional concept
1.7
ESIEN05-04
Automatic Restart
Purpose
The purpose of the auto-restart function is to automatically resume the same operating mode as when
the unit was operating when the power supply is restored after a power failure.
Do not use the "Automatic Restart" function to daily start/stop the unit.
Precautions when
turning OFF power
When you have to turn OFF the power supply in order to carry out maintenance, make sure to turn
the remote control's ON/OFF switch OFF firstly.
If you turn OFF the power supply while the remote control's ON/OFF switch is still ON, the
"automatic restart function" automatically starts the indoor fan immediately and the outdoor unit fan
starts automatically 3 minutes after the power supply is turned back ON.
Do not start/stop the unit by disconnecting the power supply.Stop the unit by stop commando from
the remote control or optional controller before disconnecting the power supply. Be sure that the
compressor and the outdoor fans are stopped before disconnecting the power supply so the
"Refrigerant Recovery function" has been finished correctly.
When restarting the unit after the power was disconnected for a longer period leave the unit OFF
with the power supply connected for about half an hour.
4
5
210
ESIEN05-04
1.8
Functional concept
Applicable
Method
Unlike with VRV units, the remote control sensor is standard disabled for sky-air units. The use of the
remote control sensor can be enabled by changing field setting 10(20)-2-02 to 10(20)-2-01.
Conditions
Cooling
The table below contains the condition in which the remote control thermostat is not used:
Condition
The set temperature / air suction temperature combination is out of range. (See
below graph)
The diagram below shows the operation range of the set temperature / air suction temperature
combination in cooling operation:
35
34
TH1 = Ts
32
TH1 = Ts
30
28
TH1 = Ts
TH1 = Ts
26
A
24
22
20
12
14
16
18
20
22
24
26
28
30
32
34
Differential
Example: Assuming the preset temperature above is 24C, and the suction temperature has
changed from 18C to 30C (A --> F):
(This example also assumes there are several other air conditioners, the VRV system is off, and that
temperature changes even when the thermostat sensor is off.)
Body thermostat sensor is used for temperatures from 18C to 23C (A --> C).
remote control thermostat sensor is used for temperatures from 23C to 27C (C --> E).
Body thermostat sensor is used for temperatures from 27C to 30C (E --> F).
211
Functional concept
ESIEN05-04
And assuming suction temperature has changed from 30C to 18C (F --> A):
Body thermostat sensor is used for temperatures from 30C to 25C (F --> D).
remote control thermostat sensor is used for temperatures from 25C to 21C (D --> B).
Body thermostat sensor is used for temperatures from 21C to 18C (B --> A).
1
Heating
The diagram below shows the operation range of the set temperature / air suction temperature
combination in heating operation:
32
30
28
TH1 = Ts
26
A
24
22
TH1 = Ts + 1 <
= 31 C
20
TH1 = Ts + 12 <
= 33 C
18
TH1 = Ts + 10 <
= 31 C
16
15
12
14
16
18
20
22
24
26
28
30
32
34
Differential
Example: Assuming the preset temperature above is 24C, and the suction temperature has
changed from 18C to 28C (A --> F):
(This example also assumes there are several other air conditioners, the VRV system is off, and that
temperature changes even when the thermostat sensor is off.)
Body thermostat sensor is used for temperatures from 18C to 25C (A --> C).
remote control thermostat sensor is used for temperatures from 25C to 28C (C --> E).
And assuming suction temperature has changed from 28C to 18C (D --> A):
remote control thermostat sensor is used for temperatures from 28C to 23C (D --> B).
Body thermostat sensor is used for temperatures from 23C to 18C (B --> A).
212
ESIEN05-04
1.9
Functional concept
Outline
The unit will perform the forced thermostat off function in following conditions:
Condition 1
(cooling)
Prevent the indoor unit heat exchanger from freezing in cooling operation when one of the below
conditions is applicable:
Condition 2
(heating)
Indoor unit heat exchanger temperature < -5C for 1 minute continuously.
Indoor unit heat exchanger temperature < -1C for 40 minutes accumulated.
2
3
Reference
4
5
213
Functional concept
1
2
1.10
ESIEN05-04
Purpose
In order to avoid formation of ice on the indoor unit heat exchanger in cooling and dry mode, the
system automatically starts up a freeze prevention cycle when a number of specific conditions are
fulfilled.
Freeze Prevention
start conditions
OR
&
3
Freeze Prevention
stop conditions
Parameters
FAQ
FHQ
-1C
-3C
-5C
214
ESIEN05-04
1.11
Functional concept
PMV Control
Applicable units
Outline
When the automatic mode is selected on the remote-controller, the unit will automatically activate the
PMV control.
The PMV index is a calculated average comfort level.
Function
In practice, the set point will be moved with 1 or 2 degrees whenever the conditions change. This will
result in a combination of power saving and increased comfort level.
PMV control can be disabled by changing the field settings:
From: 11(21)-4-01 to: 11(21)-4-02
4
5
215
Functional concept
1
2
1.12
ESIEN05-04
Thermostat Control
Purpose
Based on the information received from the air return sensor, the thermostat control will decide the
required operation status of the system.
Thermostat control
Cooling mode:
Set point
Thermostat ON
0.5 K
+1 K
Thermostat OFF
Heating mode:
Set point
Thermostat ON
+0.5 K
Thermostat OFF
1 K
2 K
Automatic heating
Preventing
thermostat OFF
conditions
Automatic cooling
+2 K
The thermostat control prevents the thermostat from turning OFF in the following conditions:
Q
Defrosting, or
Within the first 6 hours after power ON, initial operation for the first 10 minutes (See note)
Note: To protect the compressor, make sure to turn on the power supply 6 hours before starting
operation.
216
ESIEN05-04
1.13
Functional concept
Purpose
Starting conditions
The drain pump control starts the drain pump motor when one of the following conditions is fulfilled:
Normal control
In normal control, the drain pump is turned ON at compressor starting and turned OFF 5 minutes after
the compressor has stopped (residual operation).
5 min
ON
Drain pump
OFF
4
ON
Compressor
OFF
Float switch
activation during
thermostat OFF
When an abnormal drain level is detected in the drain pan, the float switch opens:
1
The drain pump starts to operate for minimum 10 minutes (even if abnormality is solved within the
10 minutes).
If the float switch closes again within 80 seconds, cooling operation can restart within the 10
minutes recovery period.
Water level
abnormality
Float switch
Normal
ON
Compressor
Drain pump
OFF
ON
OFF
5 min
5s
5 min
Abnormal
Error processing
Normal
1 min 20
217
Functional concept
Float switch
activation during
thermostat ON
ESIEN05-04
The drain pump continues to operate for minimum 10 minutes (even if abnormality is solved within
the 10 minutes).
If the float switch closes again within 80 seconds, cooling operation can restart within the 10
minutes recovery period.
Water level
abnormality
Float switch
Normal
ON
Compressor
OFF
ON
Drain pump
OFF
5 min
5s
5 min
Abnormal
Error processing
Normal
Used inputs
Input
X15A
218
ESIEN05-04
1.14
Functional concept
Purpose
Avoid condensation on the swing flap when the most downward position of the swing flap (position 4)
is selected on the remote control.
Applicable units
Method
The condensation avoidance control will function in the following operating modes:
Method
Cooling (automatic)
Dry keep.
2
3
To avoid condensation on the swing flap, the condensation avoidance control is activated:
Stage
Description
The fan operates in cooling mode with the blade in downward position (set on the remote
control).
4
2
After 1 h operation in horizontal position, the blade moves back to its downward position
for 30 min.
219
Functional concept
1
2
1.15
ESIEN05-04
Purpose
Avoid draft for the customer by delaying transfer of the flap to the Po0 (horizontal) position for a certain
amount of time when defrosting and in heating thermostat OFF.
Heating thermostat
OFF
The time chart below illustrates the draft avoidance control 1 in heating thermostat OFF.
When the flap starts to move, there can be
a draft. The fan speed decreases to LL
speed but it takes some time because of
its inertia.
Setting
Fan
LL
Setting
Flap
Po0
Po0
20 s
ON
Thermostat
OFF
Flap moves from
setting position to Po0
4
Defrosting
The time chart below illustrates the draft avoidance control 1 in defrosting.
Fan
Flap
Setting
Off
Setting
Po0
Po0
20 s
Defrosting
Used inputs
220
Yes
No
Connection on
indoor PCB
Connection on
outdoor PCB
33S
X26A
R2T
ESIEN05-04
1.16
Functional concept
Purpose
The purpose of the draft avoidance control 2 is to avoid draft when the flap is moving.
Starting conditions
Time chart
If the fan speed is set to "H", the fan turns at low speed for a certain amount of time.
Fan
L
OFF/LL
Flap
Setting
T = 24 s
FCQ: T = 5s
Po0
T
Used input
Connection on
indoor PCB
Connection on
outdoor PCB
33S
X26A
221
Functional concept
1.17
Cooling operation
Function
2
3
4
ESIEN05-04
In
Thermostat ON
in Dry Keep
Mode
Swing operation
Thermostat
OFF in Dry
Keep Mode
Swing operation
Thermostat
OFF in Cooling
Mode
Swing operation
Stop (Error)
Swing operation
Fan
Swing operation
OFF(*)
Flap (FAQ)
Remote control
indication
Swing
Swing
Swing
Set position
Set position
Set position
Horizontal
Horizontal
Swing
Set position
Set position
Set position
Horizontal
Horizontal
Swing
Set position
Set position
Set position
Horizontal
Downward
---
Set position
Downward
Horizontal
Horizontal
Swing
Set position
Set position
Set position
Heating operation
Function
In
Fan
OFF
Flap (FAQ)
Horizontal
Remote control
indication
Swing operation
Swing
Set position
Defrost
Swing operation
Swing
Set position
Thermostat
OFF
Swing operation
LL
Set position
Swing operation
Swing
Set position
Stop (error)
Swing operation
OFF
222
Swing operation
Airflow direction setting
Swing
---
Fully closed
LL
Horizontal
Swing
Set position
ESIEN05-04
1.18
Functional concept
Outline
Before compressor
stop
During compressor start and stop control, the indoor fan will receive instruction from the outdoor unit
in order to protect the compressor from receiving liquid and to assure a smooth compressor start up:
Q
After thermostat off or remote-controller signal off has been sent from the outdoor unit to the indoor
unit, the compressor will keep on running for a period of time in order to execute the "residual pump
down operation". During this pump down operation, the indoor fan will keep on operating.
Purpose:
Q
Cooling: Minimize the remaining refrigerant amount in indoor unit heat exchanger
Heating: Lower the high pressure by avoiding high temperature build up around the indoor unit heat
exchanger.
Thermostat OFF
LL
Thermostat OFF
LL
LL
Indoor drying
Thermostat OFF
LL
LL
During compressor
stop
Indoor fan tap
Indoor cooling / Automatic
cooling
Thermostat OFF
Thermostat OFF
remote control OFF
OFF
Indoor drying
Thermostat OFF
OFF
OFF
OFF
LL
Before compressor
startup
Indoor fan tap
Indoor cooling / Automatic cooling
OFF
Indoor drying
223
Functional concept
At compressor
startup
ESIEN05-04
In cooling: The indoor fan is operated at low speed until the low-pressure value reaches 6 bar.
In heating: Hot startup controlWhen performing a startup, or after the defrosting cycle has been
completed, the indoor fan will be controlled as to prevent cold air draft and secure the starting
performance (quick pressure build-up).
2
Heating operation is turend on with remote control.
Condition A is met.
Condition B is met.
Condition C is met.
5
Indoor unit fan: Set fan speed
224
Condition A
Condition B
Condition C
---
---
---
---
---
---
---
---
---
ESIEN05-04
4
Part 3
Troubleshooting
33
See page
1Troubleshooting
33
2Error Codes
331
33
353
4
5
Part 3 Troubleshooting
31
ESIEN05-04
33
32
Part 3 Troubleshooting
ESIEN05-04
Troubleshooting
Part 3
1
1
Troubleshooting
1.1
Introduction
When a problem occurs, you have to check all possible malfunctions. This chapter gives a general idea
of where to look for malfunctions.
Not all repair procedures are described. Some procedures are considered common practice.
Overview
Part 3 Troubleshooting
33
See page
34
35
320
321
322
326
327
328
330
4
5
33
Troubleshooting
1.2
ESIEN05-04
Wait until
power failure
is over.
YES
Units equipped with liquid
crystal remote controllers only
YES
YES
Doesn't run at all
Is there a
power
failure?
NO
33
YES
Runs
Doesn't run
YES
Units equipped with liquid
crystal remote controllers only
Is the remote
controller's operation
lamp blinking?
NO
Cooling
Heating
Nomal
NO
YES
Runs
Operation is
normal.
NO
Troubleshooting by remote
controller malfunction
code.
Nomal
Is the remote
controller's operation
lamp blinking?
YES
Temperature
differential is 8~18C
NO
(Temperature differential
=suction temperature - discharge temperature)
Operation is
normal.
Is there something causing the
indoor heat load to be large, such
as an open window or door?
YES
Temperature
differential is 14~30C
(Temperature differential
=discharge temperature - suction temperature)
NO
OK.We'll be right over.
34
Part 3 Troubleshooting
ESIEN05-04
1.3
Troubleshooting
Overview
Equipment Condition
Remedy
See page 3-6
See page 3-8
See page 3-10
7
8
9
10
11
12
13
14
15
1
2
3
4
16
17
18
19
20
21
22
Part 3 Troubleshooting
35
33
4
5
Troubleshooting
1.3.1
ESIEN05-04
Applicable Model
Error Detection
Method
Error Generating
Condition
33
Possible Causes
4
5
36
Malfunction of compressor
Part 3 Troubleshooting
ESIEN05-04
Troubleshooting
Troubleshooting
Is power
switch OFF or fuse for
power switch
blown?
NO
YES
YES
NO
Is
operation switch pressed
repeatedly?
NO
Is
thermostat changed and
reset again?
NO
YES
Is
operation lamp on
LCD remote controller
flashing?
YES
NO
YES
Wireless
remote controller
YES
Is operation lamp on indoor
unit signal receiving
section flashing?
33
NO
Possibly faulty electric
component
(S2575)
Caution
Part 3 Troubleshooting
Be sure to turn off power switch before connect or disconnect connector, or parts damage may be
occurred.
37
Troubleshooting
1.3.2
ESIEN05-04
Applicable Model
Method of
Malfunction
Detection
Malfunction
Decision
Conditions
33
Possible Causes
Faulty thermistor
Faulty compressor
38
Part 3 Troubleshooting
ESIEN05-04
Troubleshooting
Troubleshooting
Indoor unit fan runs at set airflow rate.
(In cooling operation)
When air thermistor ambient temperature is higher than set temperature
(In heating operation)
When air thermistor ambient temperature is lower than set temperature
Is the power
switch OFF or the fuse for
power switch
blown?
YES
NO
Is the heating
switch turned on at outdoor
temperature >30C
Normal.
(Thermostat OFF by
outdoor temperature)
YES
33
NO
c
Is rated voltage
applied at
the compressor
terminals?
YES
Replace the
compressor.
NO
d
Is rated voltage
output from the magnetic
switch or power
transistor?
YES
NO
e
Is rated voltage output
from the PC board?
YES
NO
Air sensor
Indoor unit
PC board
Input
to PC
board
Output
from
PC
board
Input
to PC
board
Magnetic
switch
e
Output from
relay or
microcomputer
COMP
d
Output from
magnetic
switch or SW
circuit of
power
transistor
c
Output from
magnetic
switch or
U,V,W of
power
transistor
(S2576)
Caution
Part 3 Troubleshooting
Be sure to turn off power switch before connect or disconnect connector, or parts damage may be
occurred.
39
Troubleshooting
1.3.3
ESIEN05-04
Applicable Model
Error Detection
Method
Error Generating
Condition
33
Possible Cause
4
5
310
Part 3 Troubleshooting
ESIEN05-04
Troubleshooting
Troubleshooting
Is
wired
the operation
Is the type of
lamp of remote controller
remote controller wired or
flashing?
wireless?
Wireless
YES
Is the
operation lamp
YES
of indoor unit photo-sensing
section flashing?
[ Heating: Indoor unit ] NO
Cooling: Outdoor unit
NO
Does the fan rotate?
YES
Is the filter soiled?
YES
33
Cleaning
NO
Is there any item
disturbing airflow?
YES
NO
Is the heat
exchanger soiled?
NO
Possible causes as follows:
Refrigerant overcharge
Mixing of air in refrigerant
system
Faulty pressure switch
YES
Caution
Part 3 Troubleshooting
Be sure to turn off power switch before connect or disconnect connector, or parts damage may be
occurred.
311
Troubleshooting
1.3.6
ESIEN05-04
Applicable Model
Error Detection
Method
Error Generating
Condition
33
Possible Cause
4
5
312
Part 3 Troubleshooting
ESIEN05-04
Troubleshooting
Troubleshooting
YES
Is the unit
in defrost mode?
NO
Measure the temperature of
suction air and supply air.
Temperature difference =
Suction air temp. Supply air
temp.
Temperature
difference for heating
should be between 14
and 30C.
NO
YES
Does the
heat load increase after
installation of the
unit?
NO
Incorrect selection of model
Affection of sunlight
Affection of excessive fresh
air into room
Is the operation
YES Gas shortage possibly
current less than specified
generates trouble.
level?
YES
No abnormality
33
Additional unit installation
should be considered
After vacuum drying, charge
correct amount of refrigerant.
NO
Does indoor
unit air flow
rate down?
NO
Is the level
of high pressure lower
than normal level?
NO
Insufficient compression of
compressor
Insufficient circulation of
refrigerant
Faulty expansion valve
Caution
Part 3 Troubleshooting
Refrigerant overcharge
Soiled heat exchanger
YES Short circuit of discharge air
Disturbing item in air flow
Malfunction of fan motor of
outdoor unit
(Refer error code E7, H7)
Be sure to turn off power switch before connect or disconnect connector, or parts damage may be
occurred.
313
Troubleshooting
1.3.7
ESIEN05-04
Applicable Model
Error Detection
Method
Error Generating
Condition
33
4
Possible Cause
Troubleshooting
Is the room
temperature higher than
set value in cooling
operation?
YES
NO
Is white fog coming
out from the unit?
NO
Normal
YES
Is the heat
exchanger of indoor
unit soiled?
It may be necessary to
remove the source of humid
condition.
YES
Cleaning of heat exchanger
is necessary.
NO
Is the site
dusty or with dense
oil mist?
NO
Is the
airflow rate too small?
NO
Did the trouble generate on
switching to heating mode
after complete of defrosting
during heating?
Normal
(Fog is generated due to
defrosting operation)
(S1996)
Caution
314
Be sure to turn off power switch before connect or disconnect connector, or parts damage may be
occurred.
Part 3 Troubleshooting
ESIEN05-04
1.3.8
Troubleshooting
Applicable Model
Error Detection
Method
Error Generating
Condition
Possible Cause
33
Troubleshooting
Does
the noise generate
with vibration of whole
ceilings and
walls?
NO
Does
the noise generate
with vibration of unit
mounting section?
NO
YES
NO
Does the
pipe contact with
casing?
Continuous
slight noise of "shoo..."
during cooling or
defrosting
NO
Sound of
"shoo..." generates
just after operation start or
stop, or defrosting
start or stop.
YES
Does the
fan contact with other
parts?
YES
NO
Correction of installation
Reinforcement for ceilings or
walls
YES
NO
Is
the noise
YES
flushing sound from
pressure reducing valve
or capillary
tube?
NO
YES
YES
NO
Sound of
"shoo..." generates
during cooling or after
operation
stop.
NO
Creak during
heatingand after operation
stop
NO
YES
YES
Normal. Creak generates by
shrinkage of resin parts due to
temperature change.
Normal.
Caution
Part 3 Troubleshooting
Be sure to turn off power switch before connect or disconnect connector, or parts damage may be
occurred.
315
4
5
Troubleshooting
1.3.9
ESIEN05-04
Applicable Model
Error Detection
Method
Error Generating
Condition
33
Possible Cause
Carpet
Animal's hair
Troubleshooting
Does
the trouble
generate at the time
YES
of operation start again after
extended period of
operation?
NO
YES
Caution
316
Be sure to turn off power switch before connect or disconnect connector, or parts damage may be
occurred.
Part 3 Troubleshooting
ESIEN05-04
Troubleshooting
Error Detection
Method
Error Generating
Condition
Possible Cause
33
Troubleshooting
Trouble
generates just after power
supply ON
YES
NO
Is the
position of (SS 1) on
indoor unit PCB at
"Emergency"?
YES
Turn the switch to "Normal", and
reset power supply.
NO
Caution
Part 3 Troubleshooting
Be sure to turn off power switch before connect or disconnect connector, or parts damage may be
occurred.
317
Troubleshooting
33
ESIEN05-04
Method of
Malfunction
Detection
Malfunction
Decision
Conditions
When ON/OFF of the micro switch for positioning cannot be reversed even through the swing flap
motor for a specified amount of time (about 30 seconds).
Remark
Some functions can force the swing flap into a fixed position, altough swing mode is selected on the
remote control. This is not an unit error, but a control function to prevent draft to the customer.
Before starting the troubleshooting, make sure the swing flap is not forced into such a fixed position.
(e.g. Hot start, defrost operation, thermostat OFF in heating operation or freeze prevention in cooling
operation. For details see "Fan and Flap Operations" on page 2-22 )
4
Possible Causes
318
Part 3 Troubleshooting
ESIEN05-04
Troubleshooting
Troubleshooting
Are
the connectors
correctly connected to
X29A and X14A on
the PC board?
NO
YES
Is
the limit
switchs transfer
connector correctly
connected?
NO
Connect correctly.
Connect correctly.
YES
Turn the power supply off once
and back on, and check
whether the swing flap motor
swings when the power supply
is turned back on.
33
NO
Turn the power supply off once
and back on, and measure the
output voltage of connector
X29A when the power supply is
turned back on.
Is continuity/no
continuity reversed?
YES
NO
220 - 240 VAC?
YES
NO
(S2577)
Caution
Part 3 Troubleshooting
Be sure to turn off power switch before connect or disconnect connector, or parts damage may be
occurred.
319
Troubleshooting
1.4
ESIEN05-04
The inspection/test
button
The following modes can be selected by using the [Inspection/Test Operation] button on the
remote control.
Others
33
Local
setting
mode
Service
mode
Forced fan ON
Normal
mode
Press Inspection/Test Operation button once.
Or after 30 minutes.
After 10 seconds
Following codes can be checked.
Malfunction codes
Inspection
mode
Test
operation
mode
320
Part 3 Troubleshooting
ESIEN05-04
1.5
Troubleshooting
Explanation
If operation stops due to malfunction, the remote controls operation LED blinks, and malfunction code
is displayed. (Even if stop operation is carried out, malfunction contents are displayed when inspection
mode is entered.) The malfunction code enables you to tell what kind of malfunction caused operation
to stop. See page 3-26 for malfunction code and malfunction contents.
Operation lamp
33
4
5
Inspection / test button
Inspection display
Part 3 Troubleshooting
321
Troubleshooting
1.6
ESIEN05-04
Introduction
Contrary to the wired remote control, the infrared remote control does not display the error code.
Instead, the operation LED on the light reception section flashes.
Checking
Action
Press the INSPECTION/TEST button to select inspection. The equipment enters the
inspection mode. 0 flashes in the UNIT No. display.
33
0
4
INSPECTION/TEST
322
Part 3 Troubleshooting
ESIEN05-04
Troubleshooting
Step
Action
Press the UP or DOWN button and change the UNIT No. until the receiver of the remote
control starts to beep.
UP
DOWN
33
4
If you hear...
Then...
3 short beeps
1 short beep
1 continuous beep
3
There is no abnormality.
Press the MODE selector button.The left 0 (upper digit) indication of the error code
flashes.
MODE
Part 3 Troubleshooting
323
Troubleshooting
ESIEN05-04
Step
Action
Press the UP or DOWN button to change the error code upper digit until the receiver of
the remote control starts to beep.
DOWN
UP
DOWN
33
UP
4
5
5
If you hear...
Then...
2 short beeps
1 short beep
No digits match.
1 continuous beep
Press the MODE selector button.The right 0 (lower digit) indication of the error code
flashes.
MODE
324
Part 3 Troubleshooting
ESIEN05-04
Troubleshooting
Step
Action
Press the UP or DOWN button and change the error code lower digit until the receiver of
the remote control generates a continuous beep.
DOWN
UP
DOWN
33
UP
Press the MODE button to return to normal status. If you do not press any button for at
least 1 min, the remote control returns automatically to normal status.
5
MODE
Part 3 Troubleshooting
325
Troubleshooting
1.7
ESIEN05-04
Malfunction Code
A1
A3
A6
AF
AJ
Contents/Processing
Remarks
Failure of PC board assy for indoor unit
Malfunction of drain water level system
Indoor unit fan motor overload / overcurrent / lock (Note 1)
Abnormal drain water level
Activation of float switch during compressor off.
Failure of capacity setting
Either capacity data is set incorrectly, or capacity
has not been set for the data IC
Malfunction of heat exchanger temperature
sensor system
Malfunction of gas piping temperature sensor
system
Malfunction of suction air temperature sensor
system
Malfunction of humidity sensor system
FCQ-D only.
Malfunction of remote control air temperature
Failure of remote control air thermistor.
sensor system
Unit can be operated by indoor unit thermistor.
Failure of transmission (between indoor and
Transmission between indoor and outdoor unit is
outdoor unit)
not being correctly carried out. (Note 1, Note 2)
Failure of transmission (between indoor unit and Transmission between indoor and remote control
remote control)
is not being correctly carried out.
Failure of transmission (between main and
Transmission between main and sub remote
sub remote control
control is not being correctly carried out.
Failure of fieldsetting
System fieldsetting error pair, twin, triple, double
twin or wrong capacity class.
Address error of central remote control
C4
C5
C9
33
CC
CJ
U4/UF
U5
U8
UA
UC
5
Notes:
326
In the case of the shaded error codes, inspection is not displayed. The system operates, but be
sure to inspect and repair it.
There is a possibility of open phase power supply, check power supply also.
Part 3 Troubleshooting
ESIEN05-04
1.8
Troubleshooting
Foreword
Troubleshooting can be carried out by service monitor LED (green). (Blinks when normal)
w : LED on
x : LED off
c : LED blinks
Microcomputer
Normal Monitor
Transmission
Normal Monitor
HAP (LED-A)
HBP (LED-B)
c
c
c
w
x
w
x
Notes:
Part 3 Troubleshooting
Contents/Processing
Indoor unit normal Outdoor unit trouble shooting
Incorrect transmission wiring between indoor and outdoor unit
If outdoor units LED-A is off, proceed outdoor units
trouble shooting. If outdoor units LED-A blinks, failure of
wiring or indoor or outdoor unit P.C board assy. (Note 4)
Failure of indoor unit PC board assy (Note 5)
33
When the INSPECTION/TEST button of remote control is pushed, INSPECTION display blinks
entering INSPECTION mode.
In the INSPECTION mode, when the ON/OFF button is pushed and held for 5 seconds or more,
the aforementioned malfunctioning history display is off. In this case, after the malfunction code
blinks 2 times, the code display turns to 00 (=Normal) and the unit No. turns to 0. The
INSPECTION mode automatically switches to the normal mode (set temperature display).
If LED-B is off, the transmission wiring between indoor and outdoor unit may be incorrect or
disconnected. Before performing the previously described troubleshooting, check the transmission
wiring.
Troubleshoot by turning off the power supply for a minimum of 5 seconds, turning it back on, and
then rechecking the LED display.
327
4
5
Troubleshooting
1.9
ESIEN05-04
Explanation for
Symbols
w : LED on
x : LED off
1.9.1
Indoor Malfunctions
33
Indoor
Indoor Unit
Unit Mal- LED Display
functions
Note 2
H1P
remote
control
Display
H2P
Other
than PC
Board
4
5
328
Location of Malfunction
Contents of Malfunction
PC Board
Outdoor
Unit
Indoor
Unit
remote
control
Details of
Malfunction
(Reference
Page)
c
c
c
w
x
c
c
w
x
*Note 1
A1
A3
AF
c
c
c
c
A6
AJ
C4
C5
C9
CC
CJ
333
335
336
338
340
340
340
343
342
Part 3 Troubleshooting
ESIEN05-04
1.9.2
Troubleshooting
System Malfunctions
Outdoor Unit
Malfunction
remote
control
Display
Location of Malfunction
Other
than PC
Board
Contents of Malfunction
Details of
Malfunction
(Reference
Page)
34
PC Board
Outdoor
Unit
Indoor
Unit
remote
control
U4
or UF
U5
U8
UA
UC
36
37
33
38
310
4
5
Part 3 Troubleshooting
329
Troubleshooting
1.10
ESIEN05-04
Thermal protector
33
4
Abnormal
Reset (automatic)
>130C +/-5C
<83C +/-20C
N.A.
FCQ100, 125B
>140C +/-5C
<45C +/-15C
N.A.
N.A.
N.A.
N.A.
>130C +/-5C
<83C +/-20C
N.A.
N.A.
N.A.
>152 +/-2C
N.A.
N.A.
>160 C
>130C +/-5C
<83C +/-20C
N.A.
>130C +/-5C
<83C +/-20C
N.A.
FAQ71, 100B
>130C +/-5C
<83C +/-20C
N.A.
N.A.
N.A.
>152 +/-2C
330
Part 3 Troubleshooting
ESIEN05-04
Error Codes
Part 3
1
2
Error Codes
2.1
Introduction
In the first stage of the troubleshooting sequence, it is important to correctly interpret the error code on
the remote control display. The error code helps you to find the cause of the problem.
Shutdown
For some errors, the system only shuts down when the error occurs several times. This means that
you have to wait until the system shuts down to be able to see the flashing LED on the front panel and
the error code on the remote control.
Overview
Part 3 Troubleshooting
33
4
Topic
See page
332
333
335
336
338
340
342
343
331
Error Codes
2.2
ESIEN05-04
Error code
A1
LED indications
HAP (green)
HBP (green)
Normal
Malfunctioning
33
Error generation
4
5
The error is generated when the data from the EEPROM is not received correctly.
EEPROM (Electrically Erasable Programmable Read Only Memory): A memory chip that holds its
content without power. It can be erased, either within the computer or externally and usually requires
more voltage for erasure than the common +5 volts used in logic circuits. It functions like non-volatile
RAM, but writing to EEPROM is slower than writing to RAM.
Causes
Troubleshooting
Switch the power off
and on again to restart.
Normal reset?
No
Replace
indoor PCB.
Yes
The malfunction may be caused by an
external factor, rather than damaged parts.
Locate the cause and correct the situation.
Caution
332
Be sure to turn off power switch before connect or disconnect connector, or parts damage may be
occurred.
Part 3 Troubleshooting
ESIEN05-04
2.3
Error Codes
Error code
A3
LED indications
HAP (green)
HBP (green)
Normal
Malfunctioning
Error generation
The error is generated when the water level reaches its upper limit and when the float switch turns
OFF.
Causes
3
4
5
Part 3 Troubleshooting
333
Error Codes
ESIEN05-04
Troubleshooting
Begin
Is
the unit a
cassette or built-in
type?
Is
the
optional drain
raising mechanism
connected?
No
No
Is
the
short-circuit
connector connected to X15A
on the indoor unit
PCB?
Yes
Connect the
Short-circuit
connector.
No
Yes
Yes
33
Yes
Is
a drain
pump connected to
the indoor unit PCB?
No
Is
there
continuity?
Connect the
drain pump.
Replace the
Short-circuit
connector
No
Yes
Replace the
indoor unit PCB.
Yes
Does
the drain pump
work after restarting
operation?
Set to
"emergency" and
check the voltage
of X25A.
No
Yes
Is the
drain water
level abnormally
high?
No
Is
the float
switch connected to
X15A?
No
Connect
float switch
22
0-240
VAC?
Yes
Yes
Yes
There is a malfunction
of the drain system.
Replace the
drain pump.
Does "A3"
appear on the remote
controller display?
No
No
Replace indoor
unit PCB.
Replace float
switch.
Yes
Replace indoor
unit PCB.
Remark
If "A3" is detected by a PC board which is not mounted with X15A, the PC board is defective.
Caution
Be sure to turn off power switch before connect or disconnect connector, or parts damage may be
occurred.
334
Part 3 Troubleshooting
ESIEN05-04
2.4
Error Codes
Error code
AF
LED indications
HAP (green)
HBP (green)
Normal
Malfunctioning
Error generation
The error is generated when the float switch changes from ON to OFF while the compressor is OFF.
Causes
3
4
Troubleshooting
Are float
switch and drain
pipe normal?
NO
YES
Is
water
drainage system
normal?
Is
drain-up
kit installed?
YES
NO
NO
YES
Is
drain pump
normal?
NO
YES
Is
amount
of circulated drain
water excessive after
pump stops
operation?
NO
YES
Does drain
water flow in reverse
during nonoperation?
YES
Caution
Part 3 Troubleshooting
NO
Be sure to turn off power switch before connect or disconnect connector, or parts damage may be
occurred.
335
Error Codes
2.5
ESIEN05-04
Error code
A6
LED indications
33
HAP (green)
HBP (green)
Normal
Malfunctioning
Error generation
The error is generated when the fan rotations are not detected while the output voltage to the fan is at
its maximum.
Causes
Malfunctioning contact
336
Part 3 Troubleshooting
ESIEN05-04
Error Codes
Troubleshooting
Check the
connections of X20A
and X26A.
Are X20A
and X26A properly
connected?
No
Connect X20A
and X26A
correctly.
Yes
Unplug X26A
and switch the
power supply on.
4
Check the voltage
between pins 1
and 3 of X26A.
5
Is there about 12
VDC?
No
Replace indoor
unit PCB.
Yes
Caution
Part 3 Troubleshooting
Be sure to turn off power switch before connect or disconnect connector, or parts damage may be
occurred.
337
Error Codes
2.6
ESIEN05-04
Error code
AJ
LED indications
33
Error generation
4
5
HAP (green)
HBP (green)
Normal
Malfunctioning
Description
The capacity that is set, does not exist for that unit.
Causes
Capacity setting
adapter
The capacity is set in the PCBs memory IC. A capacity setting adapter that matches the capacity of
the unit is required in the following case:
In case the indoor PCB installed at the factory is for some reason changed at the installation site, the
capacity will not be contained in the replacement PCB. To set the correct capacity for the PCB you
have to connect a capacity setting adapter with the correct capacity setting to the PCB. The capacity
setting for the PCB will become the capacity setting of the adapter because the capacity setting
adapter has priority.
338
Part 3 Troubleshooting
ESIEN05-04
Error Codes
Troubleshooting
Check if the capacity setting
adapter is plugged into X23A of the
indoor PCB.
Is
the
capacity setting
adapter plugged into
X23A of the indoor
unit PCB?
No
Yes
Is "AJ"
displayed on the remote
controller?
No
Yes
Replace indoor
unit PCB.
Caution
Part 3 Troubleshooting
Be sure to turn off power switch before connect or disconnect connector, or parts damage may be
occurred.
339
Error Codes
2.7
Error code
33
4
5
ESIEN05-04
LED indications
Description
C4
C5
C9
Error generation
Causes
Checking
thermistors
340
HAP (green)
HBP (green)
Normal
Malfunctioning
Malfunctioning thermistor
Malfunctioning PCB
Part 3 Troubleshooting
ESIEN05-04
Error Codes
Troubleshooting
Check the connector
connection.
Is
it
connected
properly?
No
Correct the
connection.
Yes
Is
it normal?
No
Replace the
thermistor.
Yes
Check the contact between
thermistor and PCB.
Is
the
contact OK?
Yes
Replace outdoor
unit PCB.
Caution
Part 3 Troubleshooting
5
No
Correct contact
Be sure to turn off power switch before connect or disconnect connector, or parts damage may be
occurred.
341
Error Codes
2.8
ESIEN05-04
Error code
CJ
LED indications
33
Error generation
HAP (green)
HBP (green)
Normal
Malfunctioning
The error is generated when the remote control thermistor becomes disconnected or shorted while the
unit is running.
Even if the remote control thermistor is malfunctioning, the system can operate with the system
thermistor.
Causes
Malfunctioning thermistor
Broken wire.
Troubleshooting
Is
"CJ"
displayed on the
remote
controller?
NO
Caution
342
YES
Be sure to turn off power switch before connect or disconnect connector, or parts damage may be
occurred.
Part 3 Troubleshooting
ESIEN05-04
2.9
Error Codes
Remote
controller
display
CC
Applicable
models
FCQ-D
Method of
malfunction
detection
Malfunction
decision
conditions
Supposed
causes
Faulty sensor
Disconnection
3
4
Troubleshooting
Turn the power supply
off once and back on.
Is the code
"CC" displayed on the
remote controller?
5
Yes
No
Problem could be caused by external
factor (noise, etc.) other than malfunction.
Caution
Part 3 Troubleshooting
Be sure to turn off power switch before connect or disconnect connector, or parts damage may be
occurred.
343
Error Codes
ESIEN05-04
33
4
5
344
Part 3 Troubleshooting
ESIEN05-04
4
Part 4
Commissioning and Test
Run
3
What is in this part?
See page
411
3Field Settings
417
431
44
5
41
ESIEN05-04
3
4
5
42
ESIEN05-04
Part 4
1
1
1.1
Introduction
Overview
Part 3 Troubleshooting
In the first stage of the troubleshooting sequence, it is important to correctly interpret the error code on
the remote control display. The error code helps you to find the cause of the problem.
33
See page
34
36
37
38
310
4
5
43
1.2
ESIEN05-04
Error code
U4 or UF
Error generation
The error is generated when the microprocessor detects that the transmission between the indoor and
the outdoor unit is not normal over a certain amount of time.
Causes
33
Troubleshooting 1
Diagnosis of incorrect or broken/disconnected wiring. If the LEDs on the indoor unit PC board are off,
it indicates that the transmission wiring between indoor and outdoor units may be incorrect or
broken/disconnected.
4
Is HAP flashing?
Check of
indoor unit
microcomputer
normal
HAP
NO (ON or OFF)
YES
NO
Failure of indoor unit PCB or
malfunction of power supply
system.
Is H1P flashing?
YES
Resets normally.
Could be outside cause (noise...).
NO
Is HAP flashing?
Check of
indoor unit
transmission
malfunction
HBP
YES
Failure of indoor unit PCB.
Is H2P on?
YES
NO (OFF)
NO
Does
outdoor unit
microcomputer
normal H1P
flash?
YES
To outdoor unit
(next page)
Caution
44
YES
Is
indoor-outdoor
transmission wire
connected
correctly?
NO
Wire correctly.
Be sure to turn off power switch before connect or disconnect connector, or parts damage may be
occurred.
Part 3 Troubleshooting
ESIEN05-04
Troubleshooting 2
Continued from
previous page
Is HAP flashing?
Check of
outdoor unit
microcomputer
normal HAP
NO (ON or OFF)
YES
Is HAP flashing?
YES
Resets normally.
Could be outside cause (noise...).
33
NO
Is HAP on?
YES
NO (OFF)
Turn off the power
supply, disconnect the NO.2
indoor-outdoor transmission
wire, and turn power supply
back on.
5
Is HAP flashing?
NO
"U4" displays
constantly?
NO
Caution
Part 3 Troubleshooting
YES
YES
Resets normally.
Could be outside cause (noise...).
Be sure to turn off power switch before connect or disconnect connector, or parts damage may be
occurred.
45
1.3
ESIEN05-04
Error code
U5
Error generation
The error is generated when the microprocessor detects that the transmission between the indoor unit
and the remote control is not normal over a certain amount of time.
Causes
33
Connection of two master remote controls (when using two remote controls).
Troubleshooting
Control by 2 remote
controllers
YES
SS1 of both
remote controllers is
set to MAIN.
YES
NO
All indoor
unit PCB
microcomputer
normal monitors
flashing
NO
YES
Using
multicore
transmission wiring
between indoor unit
and remote
controller
NO
Caution
46
Resets
normally when
power supply is turned
off temporarily.
YES
YES
NO
Change to
double-core
independent cable.
Failure of remote
controller PCB or
replacement of
defective indoor
unit PCB.
Be sure to turn off power switch before connect or disconnect connector, or parts damage may be
occurred.
Part 3 Troubleshooting
ESIEN05-04
1.4
Error code
U8
Error generation
The error is generated when, in case of controlling with two remote controls, the microprocessor
detects that the transmission between the indoor unit and the remote controls (MAIN and SUB) is not
normal over a certain amount of time.
Causes
Transmission error between MAIN remote control and SUB remote control
33
Troubleshooting
Controlling with
2-remote controller
NO
YES
SS-1 switch
on remote controller
PCB is turned
to MAIN
NO
YES
5
Both SS-1
switches on remote
controllers are turned
to SUB
NO
YES
Turn the SS-1switch of one
remote controller to MAIN.
Turn OFF the power supply,
and restart operation.
Caution
Part 3 Troubleshooting
Be sure to turn off power switch before connect or disconnect connector, or parts damage may be
occurred.
47
1.5
ESIEN05-04
Error code
UA
Error generation
The error is generated when incorrect field settings have been set for pair/twin/triple/double twin.
Causes
33
4
5
48
Part 3 Troubleshooting
ESIEN05-04
Troubleshooting
Is the remote
control connected to
more than
one indoor
unit?
YES
Connect the remote controller correctly.
NO
Is the
outdoor unit used for
Twin system?
NO
Check setting "No. of Connected Twin
System Indoor Units" of indoor unit.
YES
Is the setting
of Pair/Twin/Triple set
correctly?
NO
33
Set correctly.
YES
Are the
microcomputer normal
monitors (HAP) of all
indoor unit PCB
flashing?
NO
Is the
indoor-indoor and
indoor-outdoor jumper
correctly
connected?
NO
Connect correctly.
YES
YES
Is the power
supply PCB correctly
connected?
Are the
transmission normal
montiors (HBP) of all
indoor unit PCB
flashing?
NO
Connect correctly.
NO
YES
Is there
220-240 VAC
between No.1 and No.3 of
X2M (indoor Unit)?
YES
Turn the power off once, then
back on, and restart operation.
NO
Replace the transformer.
YES
Wiring could be incorrect, recheck.
NO
Operating normally?
Is the
indoor-indoor and
indoor-outdoor jumper
correctly
connected?
NO
Connect correctly.
YES
YES
Caution
Part 3 Troubleshooting
Be sure to turn off power switch before connect or disconnect connector, or parts damage may be
occurred.
49
1.6
remote control
Display
33
ESIEN05-04
UC
Applicable Models
Method of
Malfunction
Detection
Indoor unit microcomputer detects and judges the centralized address signal according to the
transmission between indoor units.
Malfunction
Decision
Conditions
When the microcomputer judges that the centralized address signal is duplicated
Supposed Causes
4
Troubleshooting
Are devices
relating to centralized
control connected to the
indoor
unit?
YES
NO
Replace the indoor unit PC board.
Caution
410
Be sure to turn off power switch before connect or disconnect connector, or parts damage may be
occurred.
Part 3 Troubleshooting
ESIEN05-04
Part 4
1
2
2.1
Introduction
Overview
Setting the address for the receiver of the infrared remote control
3
4
See page
412
413
411
2.2
ESIEN05-04
Action
Make sure the voltage at the primary side of the safety breaker is:
Q
3
4
5
412
230 V 10%
Check that the temperature setting of the remote control is at the lowest level in cooling mode or
use test mode.
Cautions or warnings
Are all air inlets and outlets of the indoor and outdoor
units unobstructed?
Poor cooling.
Poor heating.
Water leakage.
Water leakage.
Poor cooling.
Poor heating.
Stop.
Incorrect operation.
Damage of cables.
No operation.
ESIEN05-04
2.3
Introduction
To set the infrared remote control, you have to set the address for:
Q
The address for the receiver of the infrared remote control is factory set to 1. To change this setting,
proceed as follows:
Step
Action
Sealing pad
2
S
SS
Small opening
SS
4
Receiver
Set the wireless address switch (SS2) according to the table below. You can find the wireless address switch attached on the PCB of the receiver and it is visible through the small
opening on the back of the receiver.
No. 1
No. 2
No. 3
Unit No.
1 2 3
1 2 3
1 2 3
SS2
If you use a wired and a infrared remote control for one indoor unit, proceed as follows:
1. Set the wired remote control to MAIN: On the remote control.
2. Set the infrared remote control to SUB: On the receiver with the MAIN/SUB switch
(SS1).
MAIN/SUB
SUB
MAIN
SS1
Seal off the opening of the address switch and the MAIN/SUB switch with the attached
sealing pad.
Sealing pad
S
SS
Small opening
SS
Receiver
413
ESIEN05-04
The address for the infrared remote control is factory set to 1. To change this setting, proceed as
follows:
Step
Action
Hold down the FILTER RESET button and the TEST button for at least 4 s, to go to field
set mode. The display indicates the field set mode.
3
4
FILTER RESET
TEST
5
2
Press the FAN button to select a multiple setting (A/b), see Multiple settings A/b further
in this section. Each time you press the button, the display switches between A and b.
FAN
414
ESIEN05-04
Step
Action
Press the UP and DOWN buttons to set the address. Set the same address as the
receiver (1, 2 or 3). The receiver does not work with addresses 4, 5 and 6.
UP
DOWN
3
4
4
RESERVE
415
ESIEN05-04
Step
Action
Press the TEST button to quit the field set mode and return to the normal display.
ON / OFF
TEMP
TIME
C
UP
DOWN
FAN
RESERVE CANCEL
TIMER
MODE
SWING
/TEST
TEST
4
5
Multiple settings
A/b
When an outside control (central remote control...) controls an indoor unit, sometimes the indoor unit
does not respond to ON/OFF and temperature settings commands from this controller.
remote control
416
Indoor unit
Setting
A: Standard
b: Multi System
No other control
ESIEN05-04
Field Settings
Part 4
1
3
Field Settings
3.1
Introduction
Overview
See page
3.2How to Change the Field Settings with the Wired remote control
418
3.3How to Change the Field Settings with the infrared remote control
420
421
422
423
424
426
427
428
4
5
417
Field Settings
3.2
ESIEN05-04
How to Change the Field Settings with the Wired remote control
Installation
conditions
The field settings have to be changed with the remote control according to the installation conditions.
Wired remote
control
23 7
10
11
12
14
22
17
25
16
13
15 18
19
20
29
21
24
33
26
35
27
36
37
28
Components
418
30
31
32
34
The table below contains the components of the wired remote control.
No. Component
No. Component
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
ON/OFF button
Operation lamp
Operation mode icon
Ventilation mode icon
Ventilation icon
Air cleaning icon
Leave home icon
External control icon
Change-over under centralised control icon
Day of the week indicator
Clock display
Maximum set temperature
Minimum set temperature
Schedule timer icon
Action icons
Off icon
Inspection required
Set temperature display
Setting
ESIEN05-04
Setting
Field Settings
Mode No.
Action
Hold down the INSPECTION/TEST button for at least 4 s during normal mode to enter
the Field setting mode.
Press the TEMPERATURE CONTROL button until the desired Mode No. appears.
If the indoor unit is under group control, all settings for all the indoor units are set at the
same time. Use the codes 10 to 15 to apply this group control and proceed to the next
step.
If you want to set the indoor units of one group individually or if you want to read out
the last settings, use the codes 20 to 25 which are displayed in brackets. Press the
TIMER SELECTION button to select the Indoor unit No. for which you want to adjust
the field settings.
Press the upper part of the PROGRAMMING TIME button to select the First code No..
Press the lower part of the PROGRAMMING TIME button to select the
Second code No.
3
4
5
419
Field Settings
3.3
ESIEN05-04
How to Change the Field Settings with the infrared remote control
Optional
accessories
If optional accessories are mounted on the indoor unit, the indoor unit setting may have to be changed.
Refer to OH98-2 or the installation manual (optional handbook) for each optional accessory.
infrared remote
control
UP button
Mode No.
Field setting mode
DOWN button
RESERVE button
First code No.
MODE button
INSPECTION/TEST button
5
Setting
Mode No.
420
Step
Action
Hold down the INSPECTION/TEST button for at least 4 s during normal mode to enter
the Field setting mode.
ESIEN05-04
3.4
Field Settings
Field settings
Mode
No.
10 or 20
The table below contains the possible field settings of all indoor units.
First
code No.
02
03
04
Filter counter
Light
contamination
heavy
contamination
Filter type
Long
Super long
External
Oil mist
TH1 = rem.
controller
TH1 = air
return
Filter display
Filter indic.
No filter indic.
Pair
Twin
Triple
Double twin
Group setting
Indiv. setting
LL-speed
OFF
Thermostat
ON
Option
Operation
Malfunction
EKRORO
Forced OFF
ON/OFF operation
LL-speed
Set speed
Continuously
OFF
Automatic restart
Disabled
Enabled
Normal
High
Extra high
2.7 m
>2.73.0 m
>3.03.5 m
4-way flow
3-way flow
2-way flow
Enabled
Disabled
Draft prevention
Standard
Standard
Option 1
Option 2
Normal
High
Low
14 or 24
0s
5s
10 s
15 s
1b
Level 2
Level 3
(Only in
case of
BRC1D52)
Not
permitted
Permitted
Use
Not use
11 or 21
12 or 22
13 or 23
3
4
5
421
Field Settings
3.5
ESIEN05-04
Factory settings
Mode No.
The table below contains the factory settings of all indoor units
First code
No.
10 or 20
3
11 or 21
12 or 22
13 or 23
14 or 24
422
FFQ
FBQ
FAQ
FDQ,
FEDQ
FUQ
FHQ
01
01
01
01
01
01
01
01
01
01
02
01
02
02
02
02
02
02
01
01
01
01
01
01
01
01
01
01
01
01
01
01
01
01
01
01
01
01
01
01
01
01
01
01
01
01
01
01
01
01
01
01
01
01
01
01
02
02
02
02
02
02
02
01
01
01
01
01
01
02
02
01
01
01
01
01
01
01
01
01
01
01
01
ESIEN05-04
3.6
Field Settings
Incorrectly setting
If you set the controller incorrectly, a connection mistake malfunction UA will appear on the remote
control display.
See Malfunctioning Field Setting Switch (UA) on page 38.
Mode No. 13 or 23
First code No. 0
Ceiling-suspended type
01
02
03
Not used
FAQ
Second code No.
Wall-mounted type
01
Normal
02
High
03
Extra high
4
5
4-way outlet
3-way outlet
2-way outlet
FCQ35-71
01
< 2.7 m
< 3.0 m
< 3.5 m
02
< 3.0 m
< 3.3 m
< 3.8 m
03
< 3.5 m
< 3.5 m
01
< 3.2 m
< 3.6 m
< 4.2 m
02
< 3.6 m
< 4.0 m
< 4.2 m
03
< 4.2 m
< 4.2 m
01
< 2.7 m
< 3.0 m
< 3.5 m
02
< 3.0 m
< 3.5 m
< 3.8 m
03
< 3.5 m
< 3.8 m
FCQ100-125-140
FUQ
423
Field Settings
3.7
ESIEN05-04
Mode No. 10 or 20
First code No. 0
When the filter counter indication time is set to ON, set the second code No., according to the table
below
Unit
Mode No.
Contamination
01
02
light
heavy
FCQ
2500 hrs
1250 hrs
FFQ
2500 hrs
1250 hrs
FHQ
2500 hrs
1250 hrs
2500 hrs
1250 hrs
FAQ
200 hrs
100 hrs
FBQ
2500 hrs
1250 hrs
FDQ, FDEQ
2500 hrs
1250 hrs
FUQ
10 or 20
When the cool/heat thermostat is OFF, you can stop the indoor unit fan by switching the setting to
Fan OFF. This setting is used as a countermeasure against odour, for example for barber shops and
restaurants.
You can switch the fan speed to the set fan speed when the heating thermostat is OFF. This setting is
called Set Fan Speed . Default the fan speed is set LL to prevent cold draft.
Note: That a combination of modes 11 (21) and 12 (22) is required to enable following settings:
Mode No. - First code No.
12 (22) - 3
01
02
03
01
Head: LL Speed
12 (21) - 2
Second
code No.
424
02
ESIEN05-04
Field Settings
1
ON
THERMO
OFF
ON
INDOOR
FAN
OFF
6 min
6 min
1 min
1 min
Set the air flow direction of the indoor units as given in the table below. This setting is needed when
the optional air outlet blocking pad has been installed. The Second code No is factory set to 01.
Mode No
13 or 23
First code No
Second code No
Setting
01
02
03
425
Field Settings
3.8
ESIEN05-04
Situation
The MAIN/SUB setting is necessary when one indoor unit is controlled by two remote controls. When
you use two remote controls (control panel and separate remote control), set one to MAIN and the
other to SUB. You can do this by setting the switch on the remote controls PCB.
Setting
The remote controls are factory set to MAIN, so you only have to change one remote control from
MAIN to SUB. To change a remote control from MAIN to SUB, proceed as follows:
Step
Action
Insert a flathead screwdriver into the recess between the upper and lower part of the
remote control, as shown in the illustration below. Gently pry off the upper part of the controller, working from the two possible positions.
5
M
S
M
S
426
ESIEN05-04
3.9
Field Settings
When?
If you want to carry out centralized control with a central remote control and a unified ON/OFF
controller, you have to set the group No. for each group with the remote control.
Wired remote
control
UNIT No.
Unit N
First Code N
Second Code N
GROUP
SETTING
1
7
5
6
Setting
Action
Switch ON the power supply of the central remote control, the unified ON/OFF controller
and the indoor unit(s).
Hold down the INSPECTION/TEST button for at least 4 s during normal mode to enter
the Field setting mode.
Set the Group No. for each group by pressing the PROGRAMMING TIME button.
The Group No. rises in the order of 100, 101, ..., 115, 200, ..., 215, 300,
etc.
The unified ON/OFF controller however displays only the range of group numbers
selected by the switch for setting each address.
Individually
address setting
If the address must be set individually for each unit, set the Mode No. to 30. For example, for power
consumption counting.
427
Field Settings
3.10
ESIEN05-04
Introduction
Inspection level
Monitoring level
The inspection level is the highest level of the three field setting levels. You can change the views in
the inspection level by pressing the INSPECTION/TEST button.
The flow chart below explains the different windows of the inspection level.
Normal display
Last occurred
malfunction
Push
INSPECTION/TEST
button
System
Test
428
ESIEN05-04
Possible system
settings
Field Settings
The table below contains the possible system settings, which are displayed on the remote control if
the TEST button is pushed twice shortly.
Size
Type
Software
Settings
Display
Settings
Display
35
35
FCQ
FJ
45
45
FHQ
HJ
60
63
FAQ
AJ
71
71
FFQ
GJ
100
100
FBQ
JJ
125
125
FUQ
3J
200
200
FDQ, FDEQ
UJ
250
250
To enter the monitoring level and to change the maintenance mode settings, proceed as follows:
Step
Action
Hold down the INSPECTION/TEST button for at least 4 s to enter the field setting mode.
Hold down the INSPECTION/TEST button for at least 4 s to enter the maintenance
mode.
Press the TEMPERATURE CONTROL buttons as many times as needed to select the
mode No. you want.
Press the TIMER SELECTION button as many times as needed to select the unit No. you
want.
Carry out the settings for modes 44 and 45. See Maintenance Mode Settings further in
this section.
Press the CONFIRMATION button to confirm the settings of modes 44 and 45.
4
5
429
Field Settings
Maintenance Mode
Settings
Mode No.
Function
40
History error
codes
The history No. can be changed with the programming time button.
SETTING
0: Newest
Malfunction
history
ESIEN05-04
2: Oldest
3
41
43
Thermistor
data display
Forced fan ON
Thermistor:
0. Remote control thermistor
1. Suction thermistor
2. Heat exchanger thermistor.
Turns the fan ON for each unit individually.
Thermistor
Temperature
Unit No.
SETTING
Unit No.
SETTING
44
Individual
setting
Settings are made using the air flow direction adjust and fan speed adjust buttons.
Confirmation by the confirmation button is
required.
Fan
speed
CODE
45
Unit No.
change
Set the unit No. after changing with the programming time buttons.
Confirmation by the confirmation button is
required.
SETTING
Field set No
No after change
Unit No.
CODE
430
1: Low
3: High
SETTING
ESIEN05-04
Part 4
1
4
Introduction
Overview
See page
432
4
5
431
4.1
ESIEN05-04
The operation value guide lines when operating under standard conditions (at Rated frequency) by
pushing the test run button on the remote control are as given in the table below.
Low
Pressure
(Mpa)
Discharge
Pipe
Temperature
(C)
Suction
Temperature
(C)
Indoor Unit
Side:
Differential
Between
Suction Temperature and
Discharge
Temperature
(C)
26 bar ~
34 bar
25 bar ~
32.6 bar
6 bar ~
10 bar
5.3 bar ~
9.5 bar
60~100
2~10
8~18
Outdoor Unit
Side:
Differential
Between
Suction Temperature and
Discharge
Temperature
(C)
7~12
60~100
6~2
14~30
2~6
3
Cooling
Heating
4
5
432
ESIEN05-04
Standard
Conditions
Indoor Unit Conditions
27C DB/19C WB
20C DB
Cooling Operation
Heating Operation
During or after maintenance, when the power supply is turned back on, operation restarts
automatically by the auto restart function. Please exercise the proper caution.
When perfoming maintenance, you should at least perform the following inspections:
Indoor unit
3
Transmission wiring between
indoor and outdoor units
To dedicated
breaker
Refrigerant piping
Drain piping
Outdoor unit
Earth
433
Correlation of
Air-Conditioners
Operation Status
and Pressure /
Running Current
When Cooling
Air-Conditioner Status
Air Filter Fouling
Short Circuit of Indoor Unit
Inlet/Outlet Air
Outdoor Unit Fin Fouling
Short Circuit of Outdoor Unit
Inlet/Outlet Air
Air Mixed in Refrigerant
Water Mixed in Refrigerant
Dirt Mixed in Refrigerant
Lack of Refrigerant (Gas)
Unsatisfactory Compression
ESIEN05-04
Low Pressure
High Pressure
Running Current
Lower
Lower
Lower
Lower
Lower
Lower
Higher
Higher
Higher
Higher
Higher
Higher
Higher
1 Lower
2 Lower
Lower
3 Higher
Higher
Lower
Lower
Lower
Lower
Higher
Lower
Lower
Lower
Lower
Low Pressure
High Pressure
Running Current
Higher
Higher
Higher
Higher
Higher
Higher
Lower
Lower
Lower
Lower
Lower
Lower
Higher
1 Lower
2 Lower
Lower
3 Higher
Higher
Lower
Lower
Lower
Lower
Higher
Lower
Lower
Lower
Lower
When Heating
Air-Conditioner Status
Air Filter Fouling
Short Circuit of Indoor Unit
Inlet/Outlet Air
Outdoor Unit Fin Fouling
Short Circuit of Outdoor Unit
Inlet/Outlet Air
Air Mixed in Refrigerant
Water Mixed in Refrigerant
Dirt Mixed in Refrigerant
Lack of Refrigerant (Gas)
Unsatisfactory Compression
Notes:
434
1. Water in the refrigerant freezes inside the capillary tube or expansion valve, and is basically
the same phenomenon as pump down.
2. Dirt in the refrigerant clogs filters inside the piping, and is basically the same phenomenon as
pump down.
3. Pressure differential between high and low pressure becomes low.
ESIEN05-04
4
Part 5
Disassembly and
Maintenance
3
What is in this part?
See page
53
4
55
51
ESIEN05-04
52
ESIEN05-04
Part 5
1
1
1.1
Introduction
Dissassembly
procedures
Exploded views
Components
Disassembly procedures
See page
54
1.3FCQ100, 125B
56
58
1.5FBQ35, 50B
510
1.6FBQ60, 71B
512
1.7FBQ100, 125B
514
516
1.9FDEQ71, 100B
518
1.10FDEQ125B
520
55
See page
522
542
579
594
1.15FAQ71B
5111
1.16FAQ100B
5122
53
1.2
ESIEN05-04
Exploded view
55
54
ESIEN05-04
Components
Component
No.
Component
B1
E23
Drain pump
B1.1
E24
Float switch
B1.1
E25
Fan motor
B1.2
F1
Casing assy
B1.3
F6
B1.4
Flare nut
F8
B1.5
Flare nut
F8.1
Drain plug
B1.6
F9
C1
F10
C2
Lock washer
F11
C3
F12
E1
F13
E2
F14
E4
Bell mouth
F15
Vibration isolator
E5
F16
E6
F17
Vibration isolator
E7
PCB assy
F18
E7.1
F19
E8
Thermistor (Air)
F20
E9
Capacitor
F21
Rubber bush
E10
Terminal
F22
E11
Terminal block
G1
Drain hose
E12
G2
Hose band
E14
Wire harness
H1
E15
Wire harness
H2
E16
Wire harness
K1
E19
Earth wire
K2
Hose band
E20
Earth screw
K3
E21
Thermistor (liquid)
K4
E22
K5
Sealing material
55
55
1.3
ESIEN05-04
FCQ100, 125B
Exploded view
55
56
ESIEN05-04
Components
Component
No.
Component
B1
E25
Fan motor
B1.1
F1
Casing assy
B1.2
F6
B1.3
F8
B1.4
Flare nut
F8.1
Drain plug
B1.5
Flare nut
F9
C1
F10
C2
Lock washer
F11
C3
F12
E1
F13
E2
F14
E4
Bell mouth
F15
Vibration isolator
E5
F16
E6
F17
Vibration isolator
E7.1
PCB assy
F18
E7.1.1
Thermistor (Air)
F19
E9
Capacitor
F21
Rubber bush
E10
Terminal
F22
E11
Terminal block
G1
Drain hose
E12
G2
Hose band
E14
Wire harness
H1
E15
Wire harness
H2
E16
Wire harness
K1
E19
Earth wire
K2
Hose band
E20
Earth screw
K3
E21
Thermistor (liquid)
K4
E23
Drain pump
K5
Sealing material
E24
Float switch
55
57
1.4
ESIEN05-04
Exploded view
55
58
ESIEN05-04
Components
Component
No.
Component
B1
E21
Lock metal
B1-1
Header assy
E22
B1-1-1
E23
Vibro-isolating bolt
E24
Vibration isolator
E25
E25-1
Drain pump
B1-2
E25-2
B1-2-1
Distributor
E25-3
Mounting bolt
B1-2-2
E25-4
B3
Flare nut
E26
B4
Flare nut
E26-1
C1
E26-2
C2
F1
C3
Insulation nut
F2
E1
F3
E2
F4
E3
F5
E4
Power transformer
F6
E5
F7
E5-1
F7-1
Grounding wire
E6
F7-2
Grounding screw
E7
F7-3
E8
Terminal block
F8
E9
Terminal block
F9
E10
F10
E10-1
Fuse holder
F11
E10-2
Fuse
F12
E11
F12-1
Drain plug
E12
F13
E13
F14
Bushing
E14
G1
E15
Thermistor assy
K1
E15-1
Thermistor
K2
Hose band
E16
Grounding screw
K3
E17
Grounding wire
K4
E18
Grounding wire
K6
E19
Wire clip
K7
sealing material
E20
Wire clip
B1-1-1
55
59
FBQ35, 50B
Fan assy
Accessories
Switch box
Exploded view
1.5
ESIEN05-04
55
510
ESIEN05-04
Components
Component
No.
Component
29
Plain washer
30
31
Fan assy
Interchangeable plate
31.1
31.2
31.3
31.4
Rotor assy
31.4.1
31.5
Fan motor
10
31.6
11
31.7
12
32
13
32.1
14
32.2
15
32.3
16
32.4
17
32.5
18
Hanger bracket
32.6
PCB assy
19
32.7
Air thermistor
19.1
32.8
20
32.9
20.1
32.10
20.2
32.11
20.3
32.12
Wire harness
20.4
Flare nut
32.13
Wire harness
20.5
Flare nut
32.14
21
32.15
22
33
Thermistor (liquid)
23
34
Thermistor (coil)
24
35
25
Drain pump
36
Metal clamp
26
Float switch
37
Drain hose
27
38
28
Vibration absorber
39
55
511
FBQ60, 71B
The illustration below shows the exploded view.
Fan assy
Accessories
Switch box
Exploded view
1.6
ESIEN05-04
55
512
ESIEN05-04
Components
Component
No.
Component
29
Plain washer
30
31
Fan assy
Interchangeable plate
31.1
31.2
31.3
31.4
Rotor assy
31.4.1
31.5
Fan motor
10
31.6
11
31.7
12
32
13
32.1
14
32.2
15
32.3
16
32.4
17
32.5
18
Hanger bracket
32.6
PCB assy
19
32.7
Air thermistor
19.1
32.8
20
32.9
20.1
32.10
20.2
32.11
20.3
32.12
Wire harness
20.4
Flare nut
32.13
Wire harness
20.5
Flare nut
32.14
21
32.15
22
33
Thermistor (liquid)
23
34
24
35
25
Drain pump
36
Metal clamp
26
Float switch
37
Drain hose
27
38
28
Vibration absorber
39
55
513
FBQ100, 125B
Fan assy
Accessories
Switch box
Exploded view
1.7
ESIEN05-04
55
514
ESIEN05-04
Components
Component
No.
Component
31
Fan assy
31.1
31.2
Interchangeable plate
31.3
31.4
Rotor assy
31.5
Fan motor
31.6
31.7
31.8
Rotor assy
10
31.8.1
11
31.9
Shaft assy
12
31.10
Coupling
13
31.11
14
31.12
Bearing board
15
31.13
16
32
17
32.1
18
Hanger bracket
32.2
19
32.3
19.1
32.4
20
32.5
20.1
32.6
PCB assy
20.2
32.7
Air thermistor
20.3
32.8
20.4
Flare nut
32.9
20.5
Flare nut
32.10
21
32.11
22
32.12
Wire harness
23
32.13
Wire harness
24
32.14
25
Drain pump
33
Thermistor (liquid)
26
Float switch
35
27
36
Metal clamp
28
Vibration absorber
37
Drain hose
29
Plain washer
38
30
39
55
515
1.8
ESIEN05-04
Switch box
Exploded view
55
516
ESIEN05-04
Components
Component
No.
Component
6.22
Thermistor
6.23
6.24
PCB assy
6.25
6.26
Earth wire
6.27
6.1
6.28
6.3
6.29
6.4
Magnetic contacor
Hook
6.6
Filter cover
6.7
6.8
10
6.9
Wire harness
11
6.10
Wire harness
12
6.14
Wire harness
13
6.15
Wire harness
14
6.16
Wire harness
15
Airfilter
6.17
Wire harness
16
6.18
PCB assy
17
Clamp
6.19
18
Clamp
6.20
Terminal strip
19
Thermistor fixing
6.21
Thermistor
55
517
1.9
ESIEN05-04
FDEQ71, 100B
Exploded view
55
518
ESIEN05-04
Components
Component
No.
Component
10
11
Bottom assy
Air filter
12
Fan assy
13
Hook
4.1
14
4.2
15
Pipe sealing
4.3
16
4.4.1
Rotor assy
16.1
4.5
16.2
4.6
16.3
Resin case
4.7
16.4
PCB assy
4.8
Capacitor 5 microf
16.5
Transformer
4.9
Cable holder
16.6
Terminal board
4.15
16.7
Terminal strip
16.8
16.9
16.10
7.1
16.11
7.2
16.12
Thermistor (air)
7.3
16.13
Thermistor (liquid)
7.4
17
7.5
18
19
20
55
519
1.10
ESIEN05-04
FDEQ125B
Exploded view
55
520
ESIEN05-04
Components
Component
No.
Component
7.5
Air filter
Fan assy
10
4.1
11
Bottom assy
4.2
12
4.3
13
Hook
4.4.1
Rotor assy
14
4.4.2
Rotor assy
15
Pipe sealing
4.4.2
Rotor assy
16
4.5
16.1
4.6
16.2
4.7
16.3
Resin case
4.8
Capacitor 5 microf
16.4
PCB assy
4.9
Cable holder
16.5
Transformer
4.10
Bearing board
16.6
Terminal board
4.11
16.7
Terminal strip
4.12
16.8
4.13
Shaft assy
16.9
4.14
Cuppling
16.10
4.15
16.11
16.12
Thermistor (air)
16.13
Thermistor (liquid)
17
7.1
18
7.2
19
7.3
20
7.4
55
521
1.11
Overview
ESIEN05-04
See page
523
524
526
528
529
531
Removal of PC Board
533
535
536
538
541
55
522
ESIEN05-04
Be sure to wait 10 minutes or more after turning off all power supplies before disassembling work.
Procedure:
Step
1
Procedure
Points
dOpen te 45
55
Suction grille
523
ESIEN05-04
Be sure to wait 10 minutes or more after turning off all power supplies before disassembling work.
Procedure:
Step
1
Procedure
Points
55
Air filter
Tab
Tab
524
ESIEN05-04
Step
2
Procedure
Points
55
525
ESIEN05-04
Be sure to wait 10 minutes or more after turning off all power supplies before disassembling work.
Procedure:
Step
1
Procedure
Points
Hook
Mounting
fixture
55
Decoration cover in the corner
Retaining screw
526
Connector for
swing motor
ESIEN05-04
Step
5
Procedure
Remove the 2 mounting
fixtures on the outside
(Section A), then remove
the 2 mounting fixtures
on the inside (Section B).
Points
Decoration panel
String
Mounting fixture
Mounting fixture
Mounting fixture
3
6
55
527
ESIEN05-04
Be sure to wait 10 minutes or more after turning off all power supplies before disassembling work.
Procedure:
Step
1
Procedure
Points
3
Seal material
55
Reassembling
Q
Seal
material
Swing motor
Horizontal blade
528
ESIEN05-04
Be sure to wait 10 minutes or more after turning off all power supplies before disassembling work.
Procedure:
Procedure
Step
Points
55
Swing motor
529
ESIEN05-04
Procedure
Step
Q
1.
Points
Protect the connector section
with using the aluminum tape.
Motor-side gear
Swing motor
3
Panel-side gear
Motor-side gear
Panel-side gear
55
530
ESIEN05-04
Be sure to wait 10 minutes or more after turning off all power supplies before disassembling work.
Procedure:
Procedure
Step
Points
55
Disconnect each
connector
(7 connectors in total)
connected to the inside
of the switch box.
Q
Transfer connector x
3 pieces
Direct connector x 4
pieces
remote control
Moisture sensor
remote control
Heat exchanger
For power
Drain pump
temperature
supply
thermistor
connection
Float switch
Swing motor
Moisture sensor
Swing motor
531
Procedure
Step
5
6
ESIEN05-04
Disconnect the
connector for fan motor.
Q
For FCQ100~
140D: Relay
connector
Points
Fan motor
Grounding wire
55
Control PC board
532
ESIEN05-04
Be sure to wait 10 minutes or more after turning off all power supplies before disassembling work.
Procedure:
Procedure
Step
Q
Points
Disconnect the 2
connectors between the
power supply and
control PC boards, then
draw the control PC
board out in the
direction shown by the
arrow.
55
Tabs
533
Procedure
Step
ESIEN05-04
Points
Tabs
55
534
ESIEN05-04
Be sure to wait 10 minutes or more after turning off all power supplies before disassembling work.
Procedure:
Procedure
Step
Q
Points
Disconnect the
connector for humidity
sensor.
Disengage the 3 tabs to
remove the humidity
sensor.
Humidity sensor
55
Tabs
Connector
Tab
535
ESIEN05-04
Be sure to wait 10 minutes or more after turning off all power supplies before disassembling work.
Procedure:
Procedure
Step
Q
Points
55
Remote
controller
cable
536
ESIEN05-04
Procedure
Step
2
1
Points
3
Fan rotor retainer
Resin nut
3
1
55
Vibro-isolating
rubber
Nut with collar
537
ESIEN05-04
Be sure to wait 10 minutes or more after turning off all power supplies before disassembling work.
Procedure:
Step
1
1
2
Procedure
Points
55
538
ESIEN05-04
Procedure
Step
Points
Q
Clamp material
55
Drain pump
539
Step
[Installation procedure of
drain pump or float switch]
1
Install a spare drain
pump or float switch on
the mounting plate, then
firmly secure the lead
wires using the provided
clamp materials (3
pieces).
2
Connect the lead wires of
the drain pump or float
switch in the original
state, firmly secure the
aforementioned clamp
materials (screw type
fixing) to the drain pan
with the use of mounting
screws.
ESIEN05-04
Procedure
Points
Drain pump
Mounting screw
(For float switch)
Float
switch
Provided clamp
material
(for bundling)
Float switch
lead wire
Drain pump
lead wire
Mounting plate
Provided clamp material
(for bundling)
(Fix to the hole in the
mounting plate)
Mounting
screw
Clamp material
(for fixing screw)
55
Drain
Pan
540
ESIEN05-04
Be sure to wait 10 minutes or more after turning off all power supplies before disassembling work.
Procedure:
Step
Q
1
2
Procedure
Points
Clamp
material
55
Heat exchanger
temperature thermistor
Insulation
material
541
1.12
Overview
ESIEN05-04
See page
543
544
546
549
551
553
555
558
559
561
564
566
Replacement of PC Board
572
576
55
542
ESIEN05-04
Warning
Be sure to wait 10 minutes or more after turning off all power supplies before disassembling work.
Procedure:
Step
1
Procedure
Points
(S2630)
55
(S2631)
543
ESIEN05-04
Be sure to wait 10 minutes or more after turning off all power supplies before disassembling work.
Procedure:
Step
1
Procedure
Points
(S2632)
55
2
(S2633)
544
ESIEN05-04
Step
2
Procedure
Points
(S2634)
(S2635)
55
545
ESIEN05-04
Be sure to wait 10 minutes or more after turning off all power supplies before disassembling work.
Procedure:
Step
1
Procedure
Points
(S2636)
(S2637)
55
Provisional hanger
(S2638)
546
ESIEN05-04
Step
3
Procedure
The decoration panel is
attached with 4 mounting
screws.
Points
3
(S2639)
55
547
Step
5
ESIEN05-04
Procedure
Points
3
(S2640)
55
(S2641)
548
ESIEN05-04
Be sure to wait 10 minutes or more after turning off all power supplies before disassembling work.
Procedure:
Step
1
Procedure
Points
Anti-sweat material
(S2642)
Sealing material
of discharge port
(S2643)
Padding
Sealing material
of discharge port
Anti-sweat material
(S2644)
549
55
Step
3
ESIEN05-04
Procedure
Remove the two screws
for each bearing of
horizontal vane (16
screws in total).
Points
Fixing screws
Fixing
screws
3
(S2645)
55
(S2646)
550
ESIEN05-04
Be sure to wait 10 minutes or more after turning off all power supplies before disassembling work.
Procedure:
Step
1
Procedure
Removing the decoration
panel
Points
Fixing screw
Wiring groove
(S2647)
55
(S2648)
551
Step
Q
Procedure
Points
ESIEN05-04
Motor-side gear
Panel-side gear
(S2649)
55
552
ESIEN05-04
Be sure to wait 10 minutes or more after turning off all power supplies before disassembling work.
Procedure:
Step
Procedure
Points
Fixing screw
(M412)
3
Fixing
screw
(M512)
Capacitor
for fan
(S2650)
Disconnect the
connection wires for
outdoor units and earth
wire. At this time, cut the
tie wrap fixing the
connection wires.
Tie wrap
Fixing
screw
(M412)
Disconnect wire of
remote control also. At
this time, cut the tie wrap
Wires for remote controller
fixing the wire of remote
control.
X17A
P1 P2 F1 F2
X18A
X25A
X15A
X20A
Tie wrap
Outdoor unit
connection
wire terminal
Outdoor unit
connection wire
and earth wire
(S2651)
553
55
Step
3
55
Procedure
Remove five pieces of
lead wires from PCB on
the switch box and lead
wire connected to the
capacitor for fan motor.
(Refer to the list shown in
the right.)
ESIEN05-04
Points
Five pieces lead wires shown below (connect to the PCB) and
(S2763)
554
ESIEN05-04
Be sure to wait 10 minutes or more after turning off all power supplies before disassembling work.
Procedure:
Step
Procedure
Points
A convex protrusion is
provided at the position of bell
mouth fixing screw to prevent
misjudgment with switch box
fixing position.
(S2653)
(S2654)
Caution
When tighten or loosen the fan
rotor fixing resin nut,
hold the base of the fan.
see detail below.
Rotation
stopper
Resin nut
(S2655)
555
55
Step
4
ESIEN05-04
Procedure
Points
Hub
Fig. 1 Fan fixing method
Shroud
Fig. 2 Do not apply excessive torque
to the area shown in slash
(S2764)
2
1
55
(S2656)
556
ESIEN05-04
Step
3
Procedure
Points
3
(S2657)
55
557
ESIEN05-04
Be sure to wait 10 minutes or more after turning off all power supplies before disassembling work.
Procedure:
Step
Procedure
Points
Drain socket
55
(S2658)
(S2659)
558
ESIEN05-04
Be sure to wait 10 minutes or more after turning off all power supplies before disassembling work.
Procedure:
Step
1
Procedure
Points
Screw
Screw
Screw
(S2660)
55
(S2661)
559
Step
3
ESIEN05-04
Procedure
Points
Screw
(S2662)
(S2663)
(S2664)
55
560
ESIEN05-04
Be sure to wait 10 minutes or more after turning off all power supplies before disassembling work.
Procedure:
Step
1
Procedure
Points
3
Screw c
Wiring groove
(S2665)
55
561
Step
2
ESIEN05-04
Procedure
Points
White line
3
(S2666)
(S2667)
55
(S2668)
562
ESIEN05-04
Step
4
Procedure
Points
3
(S2661)
55
When install the drain
pan, put the lead wires
of float switch and drain
pump in wiring groove
and pass the lead wires
above on the black
sealing material on the
drain pan.
(Otherwise, due
dripping may occur due
to leakage of cool air.)
Screw
Screw
Lead wires
Wiring groove
(S2669)
563
ESIEN05-04
Be sure to wait 10 minutes or more after turning off all power supplies before disassembling work.
Procedure:
Step
1
Procedure
Points
Disconnect the
grounding terminal from
the header.
3
(S2670)
Thermistor
ass'y
Clamp
Clamps
55
3
(S2671)
Heat exchanger
partition plate
(S2672)
564
ESIEN05-04
Step
5
Procedure
Take out the two tie
wraps fixing the anti
sweat tube of header and
thermistor.
Points
Q
(S2673)
Replace thermistor as an
ass'y. (Two thermistors are
bound with special heat
resistance tube.)
55
(S2674)
565
ESIEN05-04
Be sure to wait 10 minutes or more after turning off all power supplies before disassembling work.
Procedure:
Step
1
Procedure
Points
Heat exchanger
fixing plate
55
(S2675)
Pipe fixing
plate
(S2676)
566
ESIEN05-04
Step
4
Procedure
Points
3
(S2677)
55
(S2678)
(S2680)
Claw section
(S2679)
567
Step
Procedure
ESIEN05-04
Points
Heat exchanger
mounting plate
(S2681)
55
Anti sweat tube
(S2682)
(S2673)
568
ESIEN05-04
Step
6
Procedure
Put the heat exchanger
partition plate inside and
fix them with two screws.
Points
Heat exchanger
partition plate
(S2672)
Clamp
Clamps
55
Thermistor ass'y
(S2683)
(S2684)
569
Step
9
10
ESIEN05-04
Procedure
Points
Wiring groove
Fan motor lead wire
Wiring groove
(S2685)
55
(S2686)
11
A convex protrusion is
provided at the position of bell
mouth fixing screw to prevent
misjudgment with switch box
fixing position.
(S2654)
(S2653)
570
ESIEN05-04
Step
12
Procedure
Points
(S2652)
55
571
ESIEN05-04
Be sure to wait 10 minutes or more after turning off all power supplies before disassembling work.
Procedure:
Step
1
1
Procedure
Points
To the swing
flap motor
55
X17A
P1 P2 F1 F2
X36A
X18A
X5A
Claw
Lead wire of Tie wrap
remote controller
X25A
Connector for
fan motor
X15A
X10A
X11A
X20A
X27A
X19A
Low-voltage cable
of transformer
Cut this tie wrap
High-voltage
cable of
transformer
Claw
Outdoor unit
connection
wire terminal
Outdoor unit
connection wire
and earth wire
(S2687)
Claw
(S2688)
572
ESIEN05-04
Step
2
Procedure
Points
:X36A
:X11A
:X10A
:X27A
:X5A
X10A
X5A
X36A
P1 P2F1 F2
X11A
X27A
(S2689)
55
Be careful that the lead wire does not lay off the groove.
To drain pump
To
float switch
dLead wire of
capacitor for
fan motor
gHeat exchanger
thermistor connectors
X17A, X18A
Wire clamp
hTie wrap
To heat
exchanger
thermistor
fConnector X15A
for float switch
573
ESIEN05-04
Step
3
Procedure
Re-connect the outdoor
unit connection wire, the
earth wire and wire of
remote control as they
were, and fix them
securely with tie wrap.
Points
Q
Power
transformer
PC
board
Terminal of outdoor unit
connection wire
Outdoor unit connection
wire and earth wire
Tie wrap
(S2691)
55
(S2692)
574
(S2693)
ESIEN05-04
Step
Procedure
Points
(S2637)
(S2636)
55
575
ESIEN05-04
Be sure to wait 10 minutes or more after turning off all power supplies before disassembling work.
Procedure:
Step
1
Procedure
Points
3
X24
(S2694)
55
(S2695)
X1
Tie wrap
X2
(S2696)
576
ESIEN05-04
Step
4
Procedure
Removing the decoration
panel
Points
Refer to "Removal of
Decoration Panel"
Pull out the lead wire of
receiver section from
wiring groove.
Q
(S2697)
3
Decoration panel
(S2698)
55
(S2699)
(S2700)
Hooking piece
(S2701)
577
Step
ESIEN05-04
Procedure
Points
X1
Tie wrap
X2
(S2696)
123
(S2694)
SS2
55
MS
SS1
(S2702)
Hooking piece
X24
(S2703)
578
ESIEN05-04
1.13
Overview
See page
580
582
585
586
589
591
593
55
579
ESIEN05-04
Be sure to wait 10 minutes or more after turning off all power supplies before disassembling work.
Procedure:
Step
Procedure
Points
55
580
ESIEN05-04
Step
3
Procedure
Points
55
581
ESIEN05-04
Be sure to wait 10 minutes or more after turning off all power supplies before disassembling work.
Procedure:.
Step
Procedure
Points
55
582
ESIEN05-04
Step
3
Procedure
Points
3
4
Disconnect the
connector mounted on
the PC board.
55
583
Step
6
ESIEN05-04
Procedure
Points
55
584
ESIEN05-04
Be sure to wait 10 minutes or more after turning off all power supplies before disassembling work.
Procedure:
Step
1
Procedure
Points
55
Reassembling precautions
1
The shaft at the right end
of the horizontal blade is
cut in D shape. Fit this
D-shaped end to the
D-profiled bearing.
Reattach the horizontal
blade at the right side
first.
585
ESIEN05-04
Be sure to wait 10 minutes or more after turning off all power supplies before disassembling work.
Procedure:
Step
1
Procedure
Points
55
586
ESIEN05-04
Step
2
Procedure
Points
55
587
Step
4
ESIEN05-04
Procedure
Points
Aconnectors
Connector (1) handles high
voltage (220-240 V), so be
sure to turn of the power
supply before disconnecting.
3
7
55
588
ESIEN05-04
Be sure to wait 10 minutes or more after turning off all power supplies before disassembling work.
Procedure:
Step
Q
Procedure
Points
55
589
Step
2
Procedure
ESIEN05-04
Points
55
590
ESIEN05-04
Be sure to wait 10 minutes or more after turning off all power supplies before disassembling work.
Procedure:
Step
1
Procedure
Points
55
591
ESIEN05-04
55
592
ESIEN05-04
Be sure to wait 10 minutes or more after turning off all power supplies before disassembling work.
Procedure:
Step
1
Procedure
Points
Disconnect the
connector from the swing
motor connector.
55
593
1.14
Overview
ESIEN05-04
See page
595
596
Removal of Fan
598
5100
5102
5105
5107
5109
55
594
ESIEN05-04
Be sure to wait 10 minutes or more after turning off all power supplies before disassembling work.
Procedure:
Step
1
Procedure
Points
3
2
55
595
ESIEN05-04
Be sure to wait 10 minutes or more after turning off all power supplies before disassembling work.
Procedure:
Step
Procedure
Unhook two
drop-prevention strings
while supporting suction
grille with hand.
Points
55
596
ESIEN05-04
Step
3
Procedure
Points
55
597
ESIEN05-04
Be sure to wait 10 minutes or more after turning off all power supplies before disassembling work.
Procedure:
Step
Procedure
Points
Edge of rib
55
Stick filament
tape
Edge of
clamp
(S1271)
598
ESIEN05-04
Step
4
Procedure
Points
3
5
55
6
599
ESIEN05-04
Be sure to wait 10 minutes or more after turning off all power supplies before disassembling work.
Procedure:
Step
1
Procedure
Points
Caution:
Fan motor can be removed
without removing the lead wire
retaining plate.
However, when washing the heat
exchanger, this plate should be
removed and protect the lead
wires.
55
5100
FUQ71BUV1B:
Three screws
FUQ100/125BUV1B:
Four screws
ESIEN05-04
Step
3
Procedure
Points
55
5101
ESIEN05-04
Be sure to wait 10 minutes or more after turning off all power supplies before disassembling work.
Procedure:
Procedure
Step
Q
Points
55
1
5102
ESIEN05-04
Procedure
Step
Points
3
4
Caution:
This work should be done by two
personnel.
If drain water remain in the pan, it
may drop and stain on the floor.
Make sure to check if no drain
water remain in the pan, or cover
the floor with vinyl sheet before
disassembling work.
5103
55
Procedure
Step
ESIEN05-04
Points
55
5104
ESIEN05-04
Be sure to wait 10 minutes or more after turning off all power supplies before disassembling work.
Procedure:
Step
1
Procedure
Drain pump is located at
piping side.
Cut clamp material of
hose, and disconnect
hose from pump.
Points
Caution:
When reconnect drain hose with
the pump, secure hose at joint
using clamping material such as
Tielap. (Clamping material should
be normally included in the stock
items.)
55
5105
Step
4
ESIEN05-04
Procedure
Points
55
5106
ESIEN05-04
Be sure to wait 10 minutes or more after turning off all power supplies before disassembling work.
Procedure:
Step
Q
Procedure
Points
55
5107
Step
4
ESIEN05-04
Procedure
Points
55
5108
ESIEN05-04
Be sure to wait 10 minutes or more after turning off all power supplies before disassembling work.
Procedure:
Step
1
Procedure
Points
To remove horizontal
blade, press down tabs
located at both end of
blade and pull them
forward.
55
5109
Step
2
ESIEN05-04
Procedure
Points
Remove horizontal
blade.
55
5110
ESIEN05-04
1.15
Overview
FAQ71B
1
This part contains the following topics:
Topic
See page
5112
5112
5115
5117
5118
5119
5120
5121
55
5111
ESIEN05-04
Be sure to wait 10 minutes or more after turning off all power supplies before disassembling work.
Procedure:
Step
Procedure
Points
55
5112
ESIEN05-04
Step
3
Procedure
Points
55
5113
ESIEN05-04
Be sure to wait 10 minutes or more after turning off all power supplies before disassembling work.
Procedure:
Step
Q
Procedure
Points
55
5114
ESIEN05-04
Be sure to wait 10 minutes or more after turning off all power supplies before disassembling work.
Procedure:
Step
1
Procedure
Points
Horizontal blade
55
Holder
5115
Step
2
ESIEN05-04
Procedure
Points
Holder plate
Protrusion
3
Holder plate
Hook
55
Vertical blade
5116
ESIEN05-04
Be sure to wait 10 minutes or more after turning off all power supplies before disassembling work.
Procedure:
Step
Q
Procedure
Points
55
5117
ESIEN05-04
Be sure to wait 10 minutes or more after turning off all power supplies before disassembling work.
Procedure:
Step
Q
Procedure
Points
Caution:
If gas leaks, repair the leakage
section, collect refrigerant inside
the unit completely, then,
recharge refrigerant after
performing vacuum dehydration.
Caution:
Don't mix air or the like other than
the specified refrigerant into a
refrigeration circle.
(Mixing of air or other gas causes
abnormal high pressure in the
refrigerating cycle and results in
pipe rupture or personal injuries.)
55
Caution:
When removing or reinstalling the
heat exchanger, be sure to wear
gloves or wrap the heat
exchanger with cloth or the like.
(Otherwise, the fins may injure
your hand.)
5118
ESIEN05-04
Be sure to wait 10 minutes or more after turning off all power supplies before disassembling work.
Procedure:
Step
Procedure
Points
55
5119
ESIEN05-04
Be sure to wait 10 minutes or more after turning off all power supplies before disassembling work.
Procedure:
Step
Q
Procedure
Points
55
3
5120
ESIEN05-04
Be sure to wait 10 minutes or more after turning off all power supplies before disassembling work.
Procedure:
Step
Q
Procedure
Points
Q
3
2
55
3
5121
1.16
Overview
ESIEN05-04
FAQ100B
This part contains the following topics:
Topic
See page
5123
5124
5125
Removal of PC Board
5126
5127
5129
5130
5132
5133
55
5122
ESIEN05-04
Be sure to wait 10 minutes or more after turning off all power supplies before disassembling work.
Procedure:
Step
Procedure
Points
3
1
55
5123
ESIEN05-04
1.16.2 Removal of Slide Panel, Operation Display Cover, and Front Grille
Warning
Be sure to wait 10 minutes or more after turning off all power supplies before disassembling work.
Procedure:
Step
Procedure
Points
The wiring diagram is applied to
the right side panel, and
troubleshooting list is applied to
the left side panel.
55
5124
ESIEN05-04
Be sure to wait 10 minutes or more after turning off all power supplies before disassembling work.
Procedure:
Step
Q
Procedure
Points
The left and right side panels
have to be taken off in order to
remove the front grille.
Remove the
(1) thermistor,
(2) heater connector
and
(3) rubber clip
connected to the PC
board.
Remove the 2 screws
fastening the electrical
parts box to the units.
55
5125
ESIEN05-04
Be sure to wait 10 minutes or more after turning off all power supplies before disassembling work.
Procedure:
Procedure
Step
Points
55
5126
ESIEN05-04
Be sure to wait 10 minutes or more after turning off all power supplies before disassembling work.
Procedure:
Step
Q
Procedure
Points
55
5127
Step
3
ESIEN05-04
Procedure
Remove the swing motor
from the swing Louvre
unit.
Points
You can replace the swing motor
without removing the swing
Louvre unit.
55
5128
ESIEN05-04
Be sure to wait 10 minutes or more after turning off all power supplies before disassembling work.
Procedure:
Step
Q
Procedure
Points
Use 2.5 mm hexagon nut driver.
55
5129
ESIEN05-04
Be sure to wait 10 minutes or more after turning off all power supplies before disassembling work.
Procedure:
Procedure
Step
Points
The bottom panel is fastened to
the unit installation plate by 3
screws.
55
2
5130
ESIEN05-04
Procedure
Step
Points
Center of air discharge section
also screw fastened.
3
4
55
5131
ESIEN05-04
Be sure to wait 10 minutes or more after turning off all power supplies before disassembling work.
Procedure:
Step
Q
Procedure
Points
Top plate
(S1325)
55
5132
ESIEN05-04
Be sure to wait 10 minutes or more after turning off all power supplies before disassembling work.
Procedure:
Step
Q
Procedure
Points
You can also remove the auxiliary
electric heater without removing
the heat exchanger.
55
Reference:
If you have enough space to pull
the fan rotor out from the left side,
you can remove it without
dismounting the heat exchanger.
5133
ESIEN05-04
55
5134
ESIEN05-04
Index
1
Symbols
"88" . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 317
A
A1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 332
A3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 333
A6 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 336
AF . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 335
Air Filter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 544, 580, 595, 5112, 5123
AJ . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 338
Automatic restart . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 210
B
Bottom Panel. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 591
C
C4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 340
C5 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 340
C9 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 340
CC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 343
Ceiling height. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 415
Centralized Address Setting Error. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 352
Centralized group No. Setting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 419
Changing
Field settings, wired remote control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 411
Field settings, infrared remote control. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 412
Maintenance mode settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 421
Checking
Clogged points . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 360
Fan motor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 361
PCBs Hall IC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 354
Power supply wave form . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 355
Test run checks. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 44
Thermistors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 356
CJ . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 342
Combination overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k iii
Components
Exploded views, indoor units. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 53
Functional diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 155
PCB layout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 1107
Switch box layout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 195
Wired remote control. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 410
infrared remote control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 412
Wiring diagrams, indoor units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 161
Index
ESIEN05-04
1
Control
Condensation avoidance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 219, 220,
Draft avoidance control 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k
Draft avoidance control 2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k
Drain pump . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k
Indoor unit fan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k
PMV. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k
Thermostat . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k
Correlation of Air-Conditioners Operation Status and Pressure / Running Current . . . . . . . . . . . . . . . k
221
220
221
217
223
215
216
426
D
Decoration Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 526, 546
Diameters, pipe connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 155
Dimensions
Indoor units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 13
Draft avoidance control 2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 221
Drain Pan. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 558, 591, 5102, 5130
Drain Pump . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 559, 561, 5105
3
4
E
EEPROM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 332
Electrical specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 145
Emergency operation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 25
Error codes
Indoor units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 331
System malfunctions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 345
Evaluation
Abnormal high pressure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 358
Abnormal low pressure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 359
Exploded views
Indoor units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 53
F
Factory settings
Indoor units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 414
Fan and flap operations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 222
Fan Bearing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 589
Fan Motor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 555, 586, 5100, 5119, 5129
Fan Rotor. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 555, 586, 5119, 5133
FAQ100B
Removal of Air Filter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 5123
Removal of Drain Pan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 5130
Removal of Electrical Parts Box . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 5125
Removal of Swing Louvre Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 5127
FAQ100BUV1B
Removal of Fan Motor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 5129
Removal of Fan Rotor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 5133
Removal of Heat Exchanger . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 5132
Removal of PC Board . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 5126
Removal of Slide Panel, Operation Display Cover, and Front Grille . . . . . . . . . . . . . . . . . . . . . k 5124
FAQ71B
Drain Hose Piping to the Left. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 5121
Removal of Air Filter and Front Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 5112
Removal of Air Swing Motor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 5120
Removal of Fan Motor and Fan Rotor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 5119
Removal of Heat Exchanger . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 5118
Removal of the horizontal blade and vertical blade. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 5115
FAQ71BUV1B
Removal of Electrical Box . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5117
Removal of Front Grille . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5114
ii
Index
ESIEN05-04
1
FCQ71~140D
Removal of Air Filter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 524
Removal of Decoration Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 526
Removal of Drain Pan, Drain Pump, Float Switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 538
Removal of Fan Motor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 536
Removal of Heat Exchanger Temperature Thermistor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 541
Removal of Horizontal Blade. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 528
Removal of Humidity Sensor and Air Temperature Thermistor . . . . . . . . . . . . . . . . . . . . . . . . . . . 535
Removal of PC Board . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 533
Removal of Suction Grille . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 523
Removal of Swing Motor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 529
Removal of Switch Box . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 531
FFQ35~60B
Installation of drain pump . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 561
Removal of air filter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 544
Removal of decoration panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 546
Removal of drain pan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 558
Removal of drain pump . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 559
Removal of fan rotor and fan motor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 555
Removal of horizontal vane. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 549
Removal of suction grille . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 543
Removal of swing motor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 551
Removal of switch box . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 553
Replacement of heat exchanger thermistor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 564
Replacement of heat exchanger . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 566
Replacement of PC board. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 572
Replacement of receiver of infrared remote control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 576
FHQ35~125B
Removal of air filter and suction grille . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 580
Removal of bottom panel and drain pan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 591
Removal of electrical parts and pcb boards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 582
Removal of fan bearing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 589
Removal of fan rotor and fan motor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 586
Removal of horizontal blade . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 585
Removal of swing motor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 593
Field settings
Levels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 420
Overview indoor units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 413
Filter counter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 416
Forced operating mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 25
Forced thermostat OFF . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 213
Freeze prevention function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 214
Functional diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 155
FUQ71~125B
Removal of Air Filter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 595
Removal of Drain Pan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 5102
Removal of Fan. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 598
Removal of Swing Motor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 5107
FUQ71~125BU
Removal of Air Flow Control Blade . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 5109
Removal of Drain Pump . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 5105
Removal of Fan Motor. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 5100
Removal of Suction Grille . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 596
3
4
5
H
Heat Exchanger. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 566
Horizontal Blade . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 585
Horizontal Vane. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 549
I
Identification function. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 27
Index
iii
ESIEN05-04
1
L
Locating
Exploded views, indoor units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
Functional diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 155
PCB layout. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1107
Switch box layout. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 195
Thermistors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Wired remote control components. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 410
infrared remote control components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 412
Wiring diagrams, indoor units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 161
M
Malfunction Code and LED Display Table
Indoor Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
System. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Malfunction of
Capacity setting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Drain system . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Drain water level systemt . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Field setting switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Indoor PCB . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
remote control air thermistor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
remote control air thermistor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Transmission between indoor and outdoor unit. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Transmission between indoor unit and remote control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Transmission between MAIN and SUB remote control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Motor lock
Indoor unit fan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4
5
k 328
k 329
k
k
k
k
k
k
k
k
k
k
338
335
333
350
332
342
343
346
348
349
k 336
O
Operation data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 424
Outlook
Indoor units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
P
PCBs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1107
Printed Circuit Board (PCB)
Indoor Unit PCB (FFQ-B) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 572
Indoor Unit PCB (FHQ-B) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 582
R
Receiver Section . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 576
remote control
Multiple setting. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
Setting address for receiver of infrared remote control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
Setting address for infrared remote control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
Thermostat, using conditions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 211
remote control Display Malfunction Code and Contents . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 326
Removal of Drain Pan, Drain Pump, Float Switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 538
Removal of Heat Exchanger Temperature Thermistor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 541
Removal of PC Board . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 533
Resistance conversion table . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 357
iv
Index
ESIEN05-04
1
S
Safety devices
Indoor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 330
Self-Diagnosis by Wired remote control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 321
Setting
Address for receiver of infrared remote control. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
Address for infrared remote control. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
Ceiling height . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 415
Centralized group No. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 419
Field settings, wired remote control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 411
Field settings, infrared remote control. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 412
Filter counter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 416
MAIN/SUB when using two remote controls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 418
Settings
Changing maintenance mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 421
Factory overview indoor units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 414
Feld overview indoor units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 413
Maintenance mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 422
Possible system settings. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 421
Simulated operation function. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 145
Standard Conditions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 425
Suction Grille . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 523, 543, 580, 596
Swing Motor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 551, 593, 5107, 5120
Switch box
Layout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 195
Removal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 553
3
4
5
T
Technical specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 145
Test run
Checks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 44
Thermistor
Indoor Heat Exchanger . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 564
Thermistors
Checking . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 356
Functions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 24
Locating. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 24
Troubleshooting Based on Equipment Condition
Cooling/Heating Operation Starts but Stops Immediately. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 310
Equipment Discharges Dust.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 316
Equipment Discharges White Mist . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 314
Equipment does not Operate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 36
Equipment Operates but does not Provide Heating.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 312
Equipment Produces Loud Noise or Shakes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 315
Indoor Fan Operates, but Compressor does not. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 38
remote control LCD Displays "88". . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 317
Swing Flap does not Operate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 318
Troubleshooting by LED Indication on the Indoor Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 327
Troubleshooting by remote control Display / LED Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 328
U
U4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
U5 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
U8 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
UA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
UC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
UF . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Index
k
k
k
k
k
k
346
348
349
350
352
346
ESIEN05-04
1
W
Wiring diagrams
Indoor units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . k 161
3
4
5
vi
Index
ESiEN05-04 02/2007
Prepared in Belgium by Lannoo
Copyright Daikin
Naamloze Vennootschap
Zandvoordestraat 300
B-8400 Ostend, Belgium
www.daikin.eu
BTW: BE 0412 120 336
RPR Oostende
q.<R.7bst