Purpose
2.
Kind of Inspections
3.
References
4.
Test Equipments
5.
Work Sequence
6.
Annexes
01.April.2010
First issued
Issue
Changes
Prepared by:
Checked by:
Approved by:
Organizational unit:
Technical Dept.
Technical Dept.
Director
Name:
Fahmi Assegaf
Luwi Wibowo
Hidayatullah
Date:
01.April.2010
01.April.2010
01.April.2010
Signature
sgd.
sgd.
sgd.
Distribution list:
Technical Division
1/6
Issue: 01-April-2010
Technical Division
Page:
2/6
Issue: 01-April-2010
Page:
3/6
Purpose
The purpose of an electrical asessment (preventive maintenance (EPM) and testing program)
should be to recognize deterioration and provide means for correcting them. With an EPM
and testing program, potential hazards that can cause failure of equipment or interruption of
electrical service can be discovered and corrected. Also, the EPM and testing program
program will minimize the hazards to life and equipment that can result from failure of
equipments.
2.
Kind of Inspection
2.01 Visual
2.02 Insulation Test
2.03 Resistant Measurement
2.04 Power Frequency Withstand Test
2.05 Partial Discharge Test (optional)
2.06 Impulse Test (optional)
3.
References
3.1 IEC-60044 Current and Voltage Transformers.
3.2 IEC-60060 High Voltage Test Techniques.
3.3 IEC-60076 Power Transformer
3.4 IEC-60129 Alternating Current Disconnector and Earthing Switches.
3.5 IEC-60270 HV test techniques_ Partial Discharge measurement.
3.6 IEC-62271 High-Voltage Switchgear and Controlgear.
4.
Test Equipments
4.1 Megger.
4.2 High-Potential Unit.
4.3 MPD600 (optional).
4.4 Impulse Test Unit (optional).
4.5 Ohm-meter.
Technical Division
Issue: 01-April-2010
Page:
4/6
5. Work Sequence
5.01. Insulation Resistance Test
Carefully check for cracked insulators or bushings and Current Transformer (if any) first.
Check all internal connections for tightness, and then Vacuum any dirt or debris from the
inside of the enclosure.
Short the CT secondary wiring at CT terminal. This test is conducted with voltages from 500
to 2500 V and provides information on the condition of NGR insulation. A clean, dry insulation
system has very low leakage as compared to a wet and contaminated insulation system.
This test does not check the high-voltage strength of the insulation system, but does provide
information whether the insulation system has high leakage resistance or not. This test is
commonly made before the high-voltage test to identify insulation contamination or faults.
After measurement is possible also.
Issue: 01-April-2010
Page:
5/6
resistance of the element is more than 15% off from the nameplate value, the resistors
should be replaced. Any open resistors should be replaced.
COMPLETE NAMEPLATE DATA WILL BE NECESSARY TO OBTAIN REPLACEMENT
PARTS.
Technical Division
Issue: 01-April-2010
Page:
6. Annexes
a) Megger
Technical Division
b) Hipot
c) MPD600
6/6