Documente Academic
Documente Profesional
Documente Cultură
INTRODUCTION :
An Electrical Power Substation receives electric power from generating station via
transmission lines and delivers power via the outgoing transmission lines. Substations are
integral parts of a power system and form important links between the generating stations,
transmission systems, distribution systems and the load points. Various power substations
located in generating stations, transmission and distribution systems have similar layout and
similar electrical components. Electrical power substation basically consists of number of
incoming circuit connections and number of outgoing circuit connections connected to the bus
bars. Bus bars are conducting bars to which number of circuit connections is connected. Each
circuit has certain number of electrical components such as circuit breakers, Isolators, earth
switches, current transformers, voltage transformers etc.
In a Power Substation there are various indoor and outdoor switchgear and equipment.
Transformers are necessary in a substation for stepping up and stepping down of a.c voltage.
Besides the transformers, the several other equipment include bus bars, circuit breakers,
isolators, surge arresters, Substation Earthing System, Shunt reactors, Shunt Capacitors etc. .
Each equipment has certain functional requirement. The equipment are either indoor or outdoor
depending upon the voltage rating and local conditions.
In a large power System large number of Generating stations, Electrical Power Substations
and load centers are interconnected. This large internetwork is controlled from load dispatch
center. Digital and voice signals are transmitted over the transmission lines via the Power
substations. The substations are interlinked with the load control centers via Power Line Carrier
Systems (PLCC). Modern Power System is controlled with the help of several automatic,
semiautomatic equipment. Digital Computers and microprocessors are installed in the control
rooms of large substations, generating stations and load control centers for data collection, data
monitoring, automatic protection and control.
1.2
Supply of electric power within specified voltage limits and frequency limits
Such substations are located at suitable load centers along with the primary transmission
lines. At primary Grid Power Substations the primary transmission voltage (220kV or 400kV) is
stepped down to secondary transmission voltages (110kV). This Secondary transmission lines
are carried over to Secondary Power Substations situated at the load centers where the voltage is
further stepped down to Sub transmission Voltage or Primary Distribution Voltages (11kV or
33kV).
2
CHAPTER-II
ELEMENTS OF SUBSTATION
TRANSFORMER:
2.
3.
Design:
circuits are efficiently coupled, so that the secondary current bears an accurate relationship to the
primary current.
The most common design of CT consists of a length of wire wrapped many times around
a silicon steel ring passed over the circuit being measured. The CT's primary circuit therefore
consists of a single 'turn' of conductor, with a secondary of many tens or hundreds of turns. The
primary winding may be a permanent part of the current transformer, with a heavy copper bar to
carry current through the magnetic core. Window-type current transformers are also common,
which can have circuit cables run through the middle of an opening in the core to provide a
single-turn primary winding. When conductors passing through a CT are not centered in the
circular (or oval) opening, slight inaccuracies may occur.
Shapes and sizes can vary depending on the end user or switchgear manufacturer. Typical
examples of low voltage single ratio metering current transformers are either ring type or plastic
molded case. High-voltage current transformers are mounted on porcelain bushings to insulate
them from ground. Some CT configurations slip around the bushing of a high-voltage
transformer or circuit breaker, which automatically centers the conductor inside the CT window.
The primary circuit is largely unaffected by the insertion of the CT. The rated secondary
current is commonly standardized at 1 or 5 amperes. For example, a 4000:5 CT would provide an
output current of 5 amperes when the primary was passing 4000 amperes. The secondary
winding can be single ratio or multi ratio, with five taps being common for multi ratio CTs. The
load, or burden, of the CT should be of low resistance. If the voltage time integral area is higher
than the core's design rating, the core goes into saturation towards the end of each cycle,
distorting the waveform and affecting accuracy.
Usage:
Current transformers are used extensively for measuring current and monitoring the
operation of the power grid. Along with voltage leads, revenue-grade CTs drive the electrical
utility's watt-hour meter on virtually every building with three-phase service and single-phase
services greater than 200 amp.
12
The CT is typically described by its current ratio from primary to secondary. Often,
multiple CTs are installed as a "stack" for various uses. For example, protection devices and
revenue metering may use separate CTs to provide isolation between metering and protection
circuits, and allows current transformers with different characteristics (accuracy, overload
performance) to be used for the devices.
Safety precautions:
Care must be taken that the secondary of a current transformer is not disconnected from
its load while current is flowing in the primary, as the transformer secondary will attempt to
continue Driving current across the effectively infinite impedance. This will produce a high
voltage across the open secondary (into the range of several kilovolts in some cases), which may
cause arc. The high voltage produced will compromise operator and equipment safety and
permanently affect the accuracy of the transformer.
Accuracy:
The accuracy of a CT is directly related to a number of factors including:
1.
Burden
2.
3.
Rating factor
4.
Load
Burden:
The load, or burden, in a CT metering circuit is the (largely resistive) impedance
presented to its secondary winding. Typical burden ratings for IEC CTs are 1.5 VA, 3 VA, 5 VA,
10 VA, 15 VA, 20 VA, 30 VA, 45 VA & 60 VA. As for ANSI/IEEE burden ratings are B-0.1, B13
0.2, B-0.5, B-1.0, B-2.0 and B-4.0. This means a CT with a burden rating of B-0.2 can tolerate
up to 0.2 of impedance in the metering circuit before its output current is no longer a fixed
ratio to the primary current. Items that contribute to the burden of a current measurement circuit
are switch-blocks, meters and intermediate conductors. The most common source of excess
burden in a current measurement circuit is the conductor between the meter and the CT. Often,
substation meters are located significant distances from the meter cabinets and the excessive
length of small gauge conductor creates a large resistance. This problem can be solved by using
CT with 1 ampere secondarys which will produce less voltage drop between a CT and its
metering devices.
14
Figure2.4:
Potential
Transformer.
Voltage transformers (VT) or potential transformers (PT) are another type of instrument
transformer, used for metering and protection in high-voltage circuits. They are designed to
present negligible load to the supply being measured and to have a precise voltage ratio to
accurately step down high voltages so that metering and protective relay equipment can be
operated at a lower potential. Typically the secondary of a voltage transformer is rated for 69 V
or 120 V at rated primary voltage, to match the input ratings of protection relays.
15
16
17
Circuit breakers are made in varying sizes, from small devices that protect an individual
household appliance up to large switchgear designed to protect high voltage circuits feeding an
entire city.
2.3.1 Operation:
Circuit breakers have common features in their operation, although details vary
substantially depending on the voltage class, current rating and type of the circuit breaker.
The circuit breaker must detect a fault condition; in low-voltage circuit breakers this is usually
done within the breaker enclosure. Circuit breakers for large currents or high voltages are usually
arranged with pilot devices to sense a fault current and to operate the trip opening mechanism.
The trip solenoid that releases the latch is usually energized by a separate battery, although some
high-voltage circuit breakers are self-contained with current transformers, protection relays, and
18
the arc. The gas inside the bubble is around 80% hydrogen, which impairs ionization. The
decomposition of oil into gas requires energy that comes from the heat generated by the arc. The
oil surrounding the bubble conducts the heat away from the arc and thus also contributes to
deionization of the arc.
Main disadvantage of the oil circuit breakers is the flammability of the oil, and the maintenance
necessary to keep the oil in good condition (i.e. changing and purifying the oil).
1.Vent valve
2 .Terminal pad
20
21
2.3.4
23
2.3.6.1 Operation:
Fast operations, suitability for repeated operation, auto reclosure, unit type multi break
constructions, simple assembly, and modest maintenance are some of the main features of air
blast circuit breakers. A compressors plant necessary to maintain high air pressure in the air
receiver. The air blast circuit breakers are especially suitable for railways and arc furnaces, where
the breaker operates repeatedly. Air blast circuit breakers are used for interconnected lines and
important lines where rapid operation is desired.
High pressure air at a pressure between 20 to 30 kg. /cm2 stored in the air reservoir. Air is
taken from the compressed air system. Three hollow insulator columns are mounted on the
reservoir with valves at their basis. The double arc extinguished chambers are mounted on the
top of the hollow insulator chambers. The current carrying parts connect the three arc extinction
chambers to each other in series and the pole to the neighboring equipment. Since there exists a
very high Voltage between the conductor and the air reservoir, the entire arc extinction chambers
assembly is mounted on insulators.
2.3.7.1 Operation:
In a vacuum circuit breaker, two electrical contacts are enclosed in a vacuum. One of the
contacts is fixed, and one of the contacts is movable. When the circuit breaker detects a
dangerous situation, the movable contact pulls away from the fixed contact, interrupting the
current. Because the contacts are in a vacuum, arcing between the contacts is suppressed,
ensuring that the circuit remains open. As long as the circuit is open, it will not be energized.
Vacuum reclosure will automatically reset when conditions are safe again, closing the
circuit and allowing electricity to flow through it. Recloses can usually go through several cycles
before they will need to be manually reset. Other types of vacuum circuit breakers require
resetting every time the breaker trips. Before a manual reset, the person doing the resetting needs
to check the system to determine what caused the unsafe conditions in the first place, and make
sure that they have been addressed.
Vacuum circuit breakers are very durable, and they are designed to last for an extended
period of time. These electrical safety devices can be made with a variety of materials,
depending on the need and the preference of the manufacturer. As with other devices used to
interrupt current for safety, vacuum circuit breakers are given a rating which indicates the kind
of conditions they can handle. When people install circuit breakers, they must confirm that the
breaker they are using is suitable for the conditions; a breaker which is rated too low can fail
catastrophically.
Other techniques can be used for arc suppression with medium and high voltage electrical
systems, such as filling circuit breakers with inert gases to suppress arcing. Arc suppression is a
major concern with heavy duty power systems because if an arc forms, it can override the circuit
breaker and create very dangerous and very undesirable conditions. Companies which develop
circuit breakers for these applications usually test their breaker designs extensively to confirm
that they are safe.
2.4 RELAY:
Relay is a protective device that detects the fault and initiatives the operation of the
circuit breaker to isolate the defective element from the rest of the system
25
Classification of relay:
According to construction and principle of operation:
1. Electromagnetic relays.
2. Induction relays.
3. Buchholz relay.
According to application:
1. Directional reverses current relays.
2. Directional reverse power relays.
3. Differential relay.
4. Impedance relay.
5. Reactance relay.
According to speed:
1. Instantaneous relay.
2. Definite time lag relay.
3. Inverse time lag relay
4. Inverse definite minimum time lag relay.
26
A protective relay is a device that detects the fault and initiatives the operation of the circuit
breaker to isolate the defective element from the rest of the system.
This diagram has shown one phase of 3-phase system for simplicity. The relay circuit
Connections can be divided into three parts.
1. First part is the primary wiring of a current transformer. Which is connected in series with
the line to be protected?
2.
Second part consists of secondary winding of C.T. and the relay operating coil.
3. The third part is tripping circuit which may be either ac or dc. When a short circuit occurs
of on the transmission line, the current flowing in the line increasing to an enormous
value This results in a heavy current flow through the relay coil causing the relay to
operate by closing its
27
Contacts. This in turn closes the trip circuit of the breaker, making the circuit breaker open and
isolating the faulty section from the rest of the system.
28
29
2.5 FUSE:
A fuse is a short piece of metal, inserted in the circuit which is melt when excessive
current flows through it thus break the circuit. The fuse element generally made of materials
having melting point & conductivity.
30
Important terms of fuse element: It is the current which the fuse element can normally carry with
over heating or melting. It is depends upon the temperature rise of the contacts of the fuse
holder, fuse material and the surrounding of the fuse.
b.
c.
b.
c.
32
33
Fig. 2.16- Different type of arrester that are used to protect our power system.
Earthing screen
2.
3.
8.
35
2.8 ISOLATOR:
Isolator is a disconnecting switch which operates under no load conditions, it has no
specified current breaking capacity. Isolator is not even used for breaking current. In some case
isolator are used for breaking charging current of transmission lines. Isolator is used in addition
to circuit breaker is opened first then isolator. While closing a circuit the isolator is necessary on
the supply side of circuit breakers in order to ensure isolation of the circuit breaker from live
parts of the purpose of maintenance
The operating mechanism manual plus one of the following.
Electrical motor mechanism
Pneumatic mechanism
2.9 EARTHING:
36
The Earthing practice adopted at generating stations, sub-stations and lines should be in
such a manner as to provide:
a) Safety to personnel
b) Minimum damage to equipment as a result
of flow of heavy fault currents
c) Improve reliability of power supply
2.9.1 The primary requirements are:
The impedance to ground (Resistance of the Earthing system) should be as low as possible
and should not exceed,
Large sub-stations -1 ohm
Small sub-stations -2 ohms
Power stations -0.5 ohms
Distribution transformer stations- 5 ohms
2.9.1.1 All exposed steel Earthing conductors should be protected with bituminous paint.
2.9.1.2 PLATE EARTHING:
i) EHT Substation - 1.3 M x 13 M.Ms cast iron plates 25mm thick Plates are to be buried
vertically in pits and surrounded by finely divided coke, crushed coal or char coal at least 155
mm all around the plates. Plates should not be less than 15 m apart and should be buried to
sufficient depth to ensure that they are always surrounded by moist earth.
2.9.1.3 PIPE EARTHING:
a) EHT substations Cast iron pipes 125 mm in diameter 2.75 m long and not less than 9.5 mm thick
pipes 50.8mm in dia. and 3.05m long. Pipes are to be placed vertically at intervals of not less
than 12.2 m in large stations surrounded by finely broken coke crushed coal and charcoal at least
150 mm around the pipe on the extra depth. a) Peripheral or main earth mat- 100 x 16 m MS
flat
b) Internal earth mat-
c) Branch connections-
Joints are to be kept down to the minimum number. All joints and connections in earth
grid are to be brazed, riveted, sweated, bolted or welded. For rust protection the welds should be
treated with barium chromate. Welded surfaces should be painted with red lead and aluminum
paint in turn and afterwards coated with bitumen. Joints in the Earthing conductor between the
switch gear units and the cable sheaths, which may require to subsequently broken should be
bolted and the joint faces tinned. All joints in steel Earthing system should be made by welding
except the points for separating the Earthing mat for testing purposes which should be bolted.
These points should be accessible and frequently supervised.
2.9.1.4 In all sub-stations there shall be provision for earthing the following:
a) The neutral point of earth separate system should have an independent earth, which in turn
should be interconnected with the station grounding mat
b) Equipment frame work and other non-current carrying parts (two connections)
c) All extraneous metallic frame work not associated with equipment (two connections)
d) Lightning arrestors should have independent earths which should in turn be connected to the
station grounding grid.
e) Overhead lightning screen shall also be connected to the main ground mat.
2.9.1.5 The earth conductor of the mat could be buried under earth to economical depth of burial
of the mat 0.5 meters.
inductive element used to tune the device and a transformer used to isolate and further step-down
the voltage.
39
The device has at least four terminals, a high-voltage terminal for connection to the high
voltage signal, a ground terminal and at least one set of secondary terminals for connection to the
instrumentation or protective relay. CVTs are typically single-phase devices used for measuring
voltages in excess of one hundred KV where the use of voltage transformers would be
uneconomical. In practice the first capacitor, C1, is often replaced by a stack of capacitors
connected in series. This results in a large voltage drop across the stack of capacitors, that
replaced the first capacitor and a comparatively small voltage drop across the second capacitor,
C2, and hence the secondary terminals.
CVT type
: CVEB/245/1050
Weight
: 665 kg
: 250 VA
Output maximum
: 750 VA at 50O C
Rated voltage
: A-N, 220/3
: A-N, 245/3
Page|28
Insulation level
: 460/1050 KV
40
Rated frequency
: 50Hz
: A1-N, 20/3 KV
Voltage factor
HF capacitance
Primary capacitance C1
Secondary capacitance C2
: 48400 pF +10%-5%
Voltage ratio
: 220000/3/ 110/3/110-
Voltage
Burden
110/3
: 110/3
: 150 100
Class
: 0.5
110-110/3
3P
41
Line trap also is known as Wave trap. What it does is trapping the high frequency
communication signals sent on the line from the remote substation and diverting them to the
telecom/tele protection panel in the substation control room through coupling capacitor.
This is relevant in Power Line Carrier Communication (PLCC) systems for communication
among various substations without dependence on the telecom company network. The signals are
primarily tele protection signals and in addition, voice and data communication signals. The Line
trap offers high impedance to the high frequency communication signals thus obstructs the flow
of these signals in to the substation bus bars. If these are not present in the substation, then signal
loss is more and communication will be ineffective/probably impossible.
42
43
2.13.BUSBAR:
The bus is a line in which the incoming feeders come into and
get into the instruments for further step up or step down. The
first bus is used for putting the incoming feeders in la single
line. There may be double line in the bus so that if any fault
occurs in the one the other can still have the current and the
supply will not stop. The two lines in the bus are separated by
a little distance by a conductor having a connector between
them. This is so that one can work at a time and the other
works only if the first is having any fault.
1. Reduce losses due to reactive load current; Reduce KVA demand, decrease customer energy
consumption, Improve voltage profile, and increase revenue.
2. Indirectly capacitor control also results in longer equipment lifetimes because of reduced
equipment stresses.
3. Experience shows that switched feeder capacitors produce some of the fastest returns on
equipment investment Sources of Energy Loss. Energy losses in transmission lines and
transformers are of two kinds: resistive and reactive. The former are caused by resistive
component of the load and cannot be avoided. The latter, coming from reactive component of the
load, can be avoided. Reactive losses come from circuit In the case of concentrated industrial
loads, there should be a bank, sized to almost equal the reactive load current, located as close to
each load as possible
45
CHAPTER-III
TYPES OF CONTROL
VAR control is the natural means to control capacitors because the latter adds a fixed
amount of leading VARs to the line regard less of other conditions, and loss reduction depends
46
only on reactive current. Since reactive current at any point along a feeder is affected by
downstream capacitor banks, this kind of control is susceptible to interaction with downstream
banks. Consequently, in multiple capacitor feeders, the furthest downstream banks should go online first and off-line last. VAR controls require current sensors.
Current control is not as efficient as VAR control because it responds to total line current,
and assumptions must be made about the load power factor. Current controls require current
sensors. Voltage control is used to regulate voltage profiles; however it may actually increase
losses and cause instability from highly leading currents.
Voltage control requires no current sensors.
Power factor control is not the best way to control capacitor banks because power factor
by itself is not a measure of reactive current. Current sensors are needed.
Combination control using various above methods is usually the best choice. If enough
current, and/or other sensors are available, a centrally managed computerized capacitor control
system taking into account the variety of available input parameters can be most effective,
though expensive to implement
3.1 CAPACITORS:
i)
ii)
In the event of failure of one capacitor unit (say in R-phase) it is observed that
balancing is done by removing one capacitor each from Y and B-phases.
iii)
48
Requires VTs on all circuits because there is no definite voltage reference point. These VTs
may be required in all cases for synchronizing live line or voltage indication
2.
Breaker failure: During fault on one circuit causes loss of additional circuit because of breaker
failure.
3. Remarks:Most widely used for very large power stations having large no. of incoming and
outgoing lines and high power transfer.
3.2.2 Bus bar Isolator: These can be used for the protection of the instruments in the substation
by isolating the buses at the required instant.
3.3 INSULATORS:Ball and socket type disc insulators are assembled to the 132 KV, 220 KV
and 400 KV suspension and tension hardware, certain important design aspects and other details
are indicated below: in next page:
Sl.
Description
No.
1. Type of insulators
2. Dimensions of insulators of
suspensions string
3. Dimensions of insulators for
tension string
4. Number of insulator disc per single
132 KV lines
220 KV lines
400 KV lines
Ball and
Ball and
Ball and
socket type
socket type
socket type
disc insulator
255mm x
disc insulator
280mm x
disc insulator
280mm x
145mm
145mm
280mm x
280mm x
145mm
145mm
9 nos.
13 nos.
suspension string
5. Number of insulator disc per
2 x 9 nos.
2 x 13 nos.
10 nos.
14 nos.
2 x 10 nos.
2 x 14 nos.
49
145mm
280mm x
170mm
23 nos.
2 x 23 nos.
24 nos.
2 x 24 nos.
7000 Kgs.
7000 Kgs.
11,500 Kgs.
11,500 Kgs.
11,500 Kgs.
16,500 Kgs.
280 mm
280 mm
315 mm
280 mm
280 mm
330 mm
110 KV
110 KV
120 KV
70 KV (dry)
70 KV (dry)
70 KV
40 KV (wet)
40 KV (wet)
(dry)
40 KV
110 KV
110 KV
(wet)
140 KV
(Suspension
(Suspension
(Suspension
strings)
strings)
strings)
140 KV
140 KV
140 KV
(Tension
(Tension
Strings)
Strings)
(Tension
16 mm
16 mm
Strings)
20 mm
20 mm
20 mm
20 mm
50 Micro
50 Micro
Volts at
Volts at
1 MHz
50
1 MHz
50 Micro
Volts at 1
MHz
18.
320 KV
(RMS)
CHAPTER IV
PROTECTION OF EQUIPMENTS
4.1 PROTECTION OF TRANSFORMER:
There are different kinds of transformers such as two winding or three winding electrical
power transformers, auto transformer, regulating transformers, Earthing transformers, rectifier
transformers etc. Different transformers demand different schemes of transformer protection
51
depending upon their importance, winding connections, Earthing methods and mode of operation
etc. It is common practice to provide Buchholz relay protection to all 0.5 MVA and above
transformers. While for all small size distribution transformers, only high voltage fuses are used
as main protective device. For all larger rated and important distribution transformers, over
current protection along with restricted earth fault protection is applied. Differential protection
should be provided in the transformers rated above 5 MVA.
Depending upon the normal service condition, nature of transformer faults, degree of
sustained over load, scheme of tap changing, and many other factors, the suitable transformer
protection schemes are chosen.
relay will operate the associated CB to trip. In this case, CB-2 will trip. If CB-2 also fails to trip,
then next circuit breaker i.e. CB-1 will trip to isolate major portion of the line.
54
55
4.2.5 Over Current Protection of Parallel Feeders:For maintaining stability of the system it is
required to feed a load from source by two or more than two feeders in parallel. If fault occurs in
any of the feeders, only that faulty feeder should be isolated from the system in order to maintain
continuity of supply from source to load. This requirement makes the protection of parallel
feeders little bit more complex than simple nondirection over current protection of line as in the
case of radial feeders. The protection of parallel feeder requires to use directional relays and to
grade the time setting of relay for selective tripping.
Fig:4.3 Over Current Protection of Parallel Feeders
There are two feeders connected in parallel from source to load. Both of the feeders have
non-directional over current relay at source end. These relays should be inverse time relay. Also
both of the feeders have directional relay or reverse power relay at their load end. The reverse
power relays used here should be instantaneous type. That means these relays should be operated
as soon as flow of power in the feeder is reversed. The normal direction of power from source to
load. Now, suppose a fault occurs at point F, say the fault current is If. This fault will get two
parallel paths from source, one through circuit breaker an only and other via CB-B, feeder-2,
CB-Q, load bus and CB-P. This is clearly shown in figure below, where IA and IB are current of
fault shared by feeder-1 and feeder-2 respectively.
56
57
Due this circulating current, the coil of both relays will close the trip circuit of associate circuit
breaker. Hence, the faulty line will be isolated from both ends.
protection cannot discriminate the faulty section of the bus bar. Now days, electrical power
system deals with huge amount of power. Hence any interruption in total bus system causes big
loss to the company. So it becomes essential to isolate only faulty section of bus bar during bus
fault.
Another drawback of second zone distance protection scheme is that, sometime the
clearing time is not short enough to ensure the system stability. To overcome the above
mentioned difficulties, differential bus bar protection scheme with an operating time less than 0.1
sec., is commonly applied to many SHT bus systems.
4.3.1 Differential bus bar Protection:
4.3.1.1 Current Differential Protection:
The scheme of bus bar protection, involves, Kirchhoffs current law, which states that,
total current entering an electrical node is exactly equal to total current leaving the node. Hence,
total current entering into a bus section is equal to total current leaving the bus section.
The principle of differential bus bar protection is very simple. Here, secondaries of CTs
are connected parallel. That means, S1 terminals of all CTs connected together and forms a bus
wire. Similarly S2 terminals of all CTs connected together to form another bus wire. A tripping
Relay is connected across these two bus wires. Here, in the figure above we assume that at
normal condition feed, A, B, C, D, E and F carries current IA, IB, IC, ID, IE and IF. Now, according
to Kirchhoffs current law,
59
So, it is clear that under normal condition there is no current flows through the bus bar
protection tripping relay. This relay is generally referred as Relay 87. Now, say fault is occurred
at any of the feeders, outside the protected zone. In that case, the faulty current will pass through
primary of the CT of that feeder. This fault current is contributed by all other feeders connected
to the bus. So, contributed part of fault current flows through the corresponding CT of respective
Feeder. Hence at that faulty condition, if we apply KCL at node K, we will still get, iR = 0.That
means, at external faulty condition, there is no current flows through relay 87. Now consider a
situation when fault is occurred on the bus itself.
60
At this condition, also the faulty current is contributed by all feeders connected to the bus.
Hence, at this condition, sum of all contributed fault current is equal to total faulty current. Now,
at faulty path there is no CT. (in external fault, both fault current and contributed current to the
fault by different feeder get CT in their path of flowing). The sum of all secondary currents is no
longer zero. It is equal to secondary equivalent of faulty current. Now, if we apply KCL at the
nodes, we will get a non-zero value of iR
So at this condition current starts flowing through 87 relay and it makes trip the circuit
breaker corresponding to all the feeders connected to this section of the bus bar. As all the
incoming and outgoing feeders, connected to this section of bus are tripped, the bus becomes
dead. This differential bus bar protection scheme is also referred as current differential protection
of bus bar.
sectionalized in than one sections to increase stability of the system. It is done because, fault in
one section of bus should not disturb other section of the system. Hence during bus fault, total
bus would be interrupted.
Let us draw and discuss about protection of bus bar with two sections. Here, bus section
A or zone A is bounded by CT1, CT2 and CT3 where CT1 and CT2 are feeder CTs and CT3 is bus
CT. Similarly bus section B or zone B is bounded by CT4, CT5 and CT6 where CT4 is bus CT,
CT5 and CT6 are feeder CT. Therefore, zone A and B are overlapped to ensure that, there is no
zone left behind this bus bar protection scheme. ASI terminals of CT1, 2 and 3 are connected
together to form secondary bus ASI BSI terminals of CT4, 5 and 6 are connected together to form
secondary bus BSI. S2 terminals of all CTs are connected together to form a common bus S2.
energized whereas during internal fault in zone B, the respective relay 87B will be energized. As
soon as relay coil of 87A or 87B is energized respective no. contact 87A-1 or 87B-1 is closed.
Hence, the tripping relay 96 will trip the breakers connected to the faulty zone. To indicate
whether zone A or B bus bar protection operated, relay 30 is used. For example, if relay 87A is
operated, corresponding No contact 87A-2 is closed which energized relay 30A. Then the No
contact 30A-1 of relay 30A is closed to energized alarm relay 74.
Supervision relay 95 of respective zone is also energized during internal fault, but it has a
time delay of 3 second. So, it reset as soon as the fault is cleared and therefore does not pick up
zone bus wire shorting relay 95x which in turn shorts out the bus wires. An alarm contact is also
given to this auxiliary 95x relay to indicate which CT is open circuited. No volt relay 80 is
provided in both trip and non-trip section of the D. C. circuit of differential bus bar protection
system to indicate any discontinuity of D. C. supply.
4.3.4 Voltage Differential Protection of bus bar:
The current differential scheme is sensitive only when the CTs do not get saturated and
maintain same current ratio, phase angle error under maximum faulty condition. This is usually
not 80, particularly, in the case of an external fault on one of the feeders. The CT on the faulty
feeder may be saturated by total current and consequently it will have very large errors. Due to
this large error, the summation of secondary current of all CTs in a particular zone may not be
zero. So there may be a high chance of tripping of all circuit breakers associated with this
protection zone even in the case of an external large fault. To prevent this mul. Operation of
current differential bus bar protection, the 87 relays are provided with high pick up current and
enough time delay. The greatest troublesome cause of current transformer saturation is the
transient dc component of the short circuit current. This difficulties can be overcome by using air
core CTs. This current transformer is also called linear coupler. As the core of the CT does not
use iron the secondary characteristic of these CTs, is straight line. In voltage differential bus bar
protection the CTs of all incoming and outgoing feeders are connected in series instead of
64
economical point of view. We should compare the initial investment in the capacitor and the cost
of the protection applying on it. There are mainly 3 types of protection arrangement are applied
to a capacitor bank.
1. Element Fuse.
2. Unit. Fuse.
3. Bank Protection.
Element Fuses:
Manufacturers of capacitor unit commonly provide inbuilt fuse in each element of the
unit. In this case, if any fault occurs in any element itself, it is automatically disconnected from
rest of the unit. In this case, the unit still serves its purpose, but with smaller output. In smaller
rated capacitor bank only these inbuilt protection scheme is applied to avoid the expenditure of
other special protective equipments.
Unit Fuse:
The unit fuse protection is generally provided to limit the duration of arc inside a faulty
capacitor unit. As the arc duration is limited, there is less chance of major mechanical
deformation and huge production of gas in the faulty unit, and hence the neighborhood units of
the bank are saved. If each unit of a <="" p="" style="margin: 0px; padding: 0px; font-family:
Verdana, Geneva, sans-serif; color: rgb(80, 80, 80); font-size: 18px; font-style: normal; fontvariant-ligatures: normal; font-variant-caps: normal; font-weight: normal; letter-spacing: normal;
line-height: 27px; orphans: 2; text-align: start; text-indent: 0px; text-transform: none; whitespace: pre-wrap; widows: 2; word-spacing: 0px; -web kit-text-stroke-width: 0px;">
Bank Protection:
Although in general fuse protection is provided with each of the capacitor units, but when
a capacitor unit is under fault and the associated fuse element is blown out, the voltage stress
increases to the other capacitor units connected in series in same row. Generally, each capacitor
unit is designed for withstanding 110% of its normal rated voltage. If any other capacitor unit
further becomes out of service, in the same row where previously one unit is damaged, the
voltage stress upon other healthy units of that row will increase further and easily crosses the
limit of maximum allowable, voltage of these units. Hence it is always desirable to
66
replacedamaged capacitor unit from the bank as soon as possible to avoid excess voltage stress
on the other healthy units. Hence, there must be some indicating arrangement to identify the
exact faulty unit. As soon as the faulty unit is identified in a bank, the bank should be removed
from the service for replacing the faulty unit. There are several methods of sensing unbalance
voltage caused by failure of capacitor unit. The figure below is showing the most common
arrangement of capacitor bank protection. Here, the capacitor bank is connected in star
formation. Primary of a potential transformer is connected across each phase. The secondary of
all three potential transformers are connected in series to form an open delta and a voltage
sensitive relay is connected across this open delta. In exact balanced condition there must not be
any voltage appears across the voltage sensitive relay because summation of balanced 3 phase
voltages is zero. But when there would be any voltage unbalancing due to failure of capacitor
unit, the resultant voltage will appear across the relay and the relay will be actuated for providing
an alarm and trip signals.
The voltage sensitive relay can be so adjusted that up to a certain voltage unbalancing
only alarm contacts would be closed and for certain higher voltage level the trip contacts along
with alarm contacts would be closed. The potential transformer connected across the capacitors
of each phase also serves for discharging of the bank after being switched off. In another scheme,
the capacitors in each phase are divided into two equal parts connected in series. Discharge coil
is connected across each of the parts as shown in the figure. In between the secondary of
discharge coil and the sensitive voltage unbalance the relay an auxiliary transformer is connected
which serves to regulate the voltage difference between secondary voltages of discharge coil
under normal conditions.
68
Fig:4.13 Bank
Protection.
Here, the
capacitor bank
of each phase is divided into two equal parts connected in parallel and the star points of both
parts are interconnected through a current transformer. The secondary of the current transformer
are connected across a current sensitive relay. In case any misbalancing occurs between the two
parts of the bank, there would be an unbalance current flowing through the current transformer
and hence the current sensitive relay will actuate. In this scheme for discharging the bank after
switching off, discharge coil may be connected across the capacitors in each phase.
69
70
In another scheme of protection of capacitor bank, the star point of a three phase
capacitor bank is connected to the ground through a current transformer and a current sensitive
relay is connected across the secondary of the current transformer. As soon as there is any
unbalancing between the phases of capacitor bank, there must be a current flowing to the ground
through the current transformer and hence the current sensitive relay will be actuated to trip the
circuit breaker associated with the capacitor bank.
71
CHAPTER-V
132/33KV TSTRANSCO NARSAMPET
The present-day electrical power system is A.C. i.e. electric power is generated,
transmitted and distributed in the form of alternating current. The electric power is produced at
the power stations which are located at favorable places, generally quite away from the
consumers. It is delivered to the consumers through a large network of transmission and
distribution. At many places in the line of the power system, it may be desirable and necessary to
change some characteristic (e.g. voltage, A.C. to D.C., frequency, P.f. etc.) of electric supply.
This is accomplished by suitable apparatus called sub-station. For example, generation voltage
(11KV or 66KV) at the power station is stepped up to high voltage (say 400KV or 220KV) for
transmission of electric power. The assembly of apparatus (e.g. transformer etc.) used for this
purpose is the sub-station. Similarly, near the consumers localities, the voltage may have to be
stepped down to utilization level. This job is again accomplished by a suitable apparatus called
substation.
72
5.3 SINGLE
LINE
DIAGRAM OF
SUBSTATION:
SUBSTATION AT NARSAMPET:
73
The substation in narsampet, Warangal (dist.), Telangana was completed by the year 2000,
under APTRANSCO; it is one of the largest substations in the state of Telangana.
This substation has the carrying capacity of 300MW at different voltage levels of 132 and can
step down to 33KV, using two input lines through the incoming feeders.
Make-INDOTEC
Make-VIJAYA
ELECTRIALS
5.4.3 DC SYSTEM :
5.4.3.1 Battery Bank:
74
5.4.3.3 Chargers:
1 No. 80AH, 220V DUBAS Make charger along with 1 set (110 cells) of amararaja make
maintenance free VRLA battery bank is available for DC supply. Main input AC supply is fed
from ACDB. Following checks are to be made in each shift
i)
ii)
iii)
iv)
v)
vi)
5.4.3.4 DC Systems:
1)
2)
3)
4)
5)
6)
75
i)
ii)
iii)
iv)
76
CHAPTER-VI
CONCLUSION
77
78
79
80