PCL Number
PCL Name
PCL Colour
PCL Description
Connected Equipment
Pressure
Range
Kg/Cm2
PFD Number
Temp
PCL Material
Range C
PWHT
Yes/No
Damage Mechanism
Inspection Plan
Comments
Alert: Operation outside the IOLs given below can increase damage rate and may initiate a new Damage
Mechanism and hence can adversely affect insp. requirements and insp. interval. Also if there are other
additional IOLs specified by Process Licensor or Site Operating Practice, these shall be included. See Note 1.
P041-PCL-001
P041-PCL-002
Catalyst
C6H11 / C4H10
(100% HC)
Red Line
a) X-Cat from BL to Z-1100, D-1100 A, PCL-002, u/s of D-1552, u/s of R1102 L & UPD
b) From PCL-002/PCL-004 to R-1002A, D-1100 B, D-1101 B, PCL-002 (Z
CAT Drain), K-1102A, PCL-004 (u/s of R-1102A) & H-1121.
c) From F-1126/ D-1241 to K-1125, P1263, B-1262 & H-1262.
d) Additives from M-1651/H-1221/H-1222 to H-1203, F-1203, FD-1202, F1204, PCL-002 & SR-1263 A/B.
e) From and back to T-1261 Via E-1261 A/B (S/S).
f) From H-1201 B/ F-1205 to ATM.
a) from Unit - P010 (C6H11 & C4H10) to D-1100B, U/S of, D-1552, PCL001, R-1051, PCL-003.
b) From D-1101A/B / Z- 1052 to Z-1101/ Z-1053.
c) From PCL-001, NLD & ND to PCL-010, U/S of D-1552, D-1051 & PCL-010.
d)From Unit -P010 (C3H5, C4H6, C2H6) to R-1102 L, PCL-004,PCL-007,
PCL-010, EJ-1102A, PCL-009, PCL-011 & PCL-018.
e) Unit -P047 (PP2), PCL-004, PCL-009 & OPD to D-1153, D-1151 & PCL010.
f) From Additives, M-1651 to F-1282 Drain, PCL-004.
2310-8110-20-P041-0001
2310-8110-20-P041-0003
2310-8110-20-P041-0004
2310-8110-20-P041-0011
D-1100 A/B, D-1101 A/B, Z-1101, R-1051, D1051, Z-1052, Z-1053, D-1511, D-1501, R1056, R-1057, E-1112, R-1102 L, E-1142 (S/S),
EJ-1102 A, D-1151, H-1121, H-1122, H-1123, Z1125, D-1162, Z-1162, D-1550, D-1551, D1552, H-1202, F-1203, F-1204, Additives, F1282, B-1282, P-1263 & M-1651
2310-8110-20-P041-0001 Rev-S1
2310-8110-20-P041-0002 Rev-S1
2310-8110-20-P041-0003 Rev-S1
2310-8110-20-P041-0004 Rev-S2
2310-8110-20-P041-0005 Rev-S2
2310-8110-20-P041-0006 Rev-S3
2310-8110-20-P041-0011 Rev-S2
Rev-S1
Rev-S1
Rev-S2
Rev-S2
Atm to 70
Atm to 55
Amb to 100
Amb to 90
SS 304L
No
No
H2O - Nil,
HC-10 to 100%,
Z17 - 100%,
CAT-90%
1)
2)
3)
4)
5)
Corrosion - General
Corrosion - Localized (No Flow)
Corrosion - Localized (Heat Traced)
Erosion Corrosion (2 Phase Flow & Solid Particles)
SCC-Chlorides(External)
H2O - Nil,
HC- 100%
1)
2)
3)
4)
5)
6)
7)
8)
Corrosion - General
Corrosion - Localized (No Flow) (C/Steel)
Corrosion - Localized (No Flow) (SS 304)
Corrosion - Localized (Heat Traced)
Erosion Corrosion (Solid Particles)
Erosion Corrosion (Jacketed Piping)
Fatigue - Vibration
SCC-Chlorides(External)
1)
2)
3)
4)
Corrosion - General
Corrosion - Localized (No Flow)
Corrosion - Localized (Heat Traced)
Erosion Corrosion (Solid Particles)
Corrosion - General
Corrosion - Localized (No Flow) (C/Steel)
Corrosion - Localized (No Flow) (SS 304)
Corrosion - Localized (No Flow) (SS 304L)
Erosion Corrosion (2 Phase Flow & Solid Particles)
Erosion Corrosion (Liquid Flashing)
SCC-Chlorides(External)
PP SIMTECH COMMENTS:
1. SS 304L lines listed in "Walk the PCL" data for PCL-002 and PCL-014
moved to this PCL as the MOC and DCC are relevant to this PCL.
P041-PCL-001
P041-PCL-002
PP SIMTECH COMMENTS:
1. Based on the upstream / downstream piping MoC given in the PFD,
certain sections marked as SS 304 in the PFD, has been considered as
CS during the PCL categorization process.
2. C/Steel & SS 304 lines listed in "Walk the PCL" data for PCL-001 and
PCL-003 moved to this PCL as the MOC and DCC are relevant to this
PCL.
P041-PCL-003
C3H6
2310-8110-20-P041-0001 Rev-S1
2310-8110-20-P041-0006 Rev-S3
0.02 to 71.5
Amb to 40
P041-PCL-004
CAT
Brown Line
a) From P-1041 A/B, PCL-002 to PCL-010 (U/S of R-1102L & D/S of Z-1102
L) & R-1102A.
b) From Unit -P-042, D-1652 A/B, S-1221 & Additives to D-1241, PCL-002,
H-1221, H-1222, PCL-019, Pellet, H-1301, H-1302 A/B/C/D/E.
c) From S-1371 to S-1372.
d) From various PCL's and equipment to Atm and Drain.
Z-1102 L, R-1102 L, H-1201 A/B, D-1240, D1241, F-1203, D-1652 A/B, S-1221, H-1221, H1222, SR-1262 A/B, H-1262, F-1286, H-1340,
H-1350 A/B/C, F-1351, H-1300, H-1331, H1301, Additives, H-1302 A/B/C/D/E & S-1312
2310-8110-20-P041-0001 Rev-S1
2310-8110-20-P041-0002 Rev-S1
2310-8110-20-P041-0003 Rev-S1
2310-8110-20-P041-0011 Rev-S2
2310-8110-20-P041-0012 Rev-S2
2310-8110-20-P041-0013 Rev-S2
- 0.1 to 70.3
Amb to 70
P041-PCL-005
Hydrogen
Pink Line
Hydrogen from Unit - P010 to PCL - 010 ( U/S of R-1102 L & R-1102 A)
2310-8110-20-P041-0002 Rev-S1
2310-8110-20-P041-0003 Rev-S1
20.7 to 70
Amb to 40
P041-PCL-006
Orange Line
H-1122, H-1123, H-1201 A/B, F-1201 A/B, F1202, H-1202, FD-1202, CR-1203, H-1203, X1201, E-1201 S/S, E-1202 S/S, E-1125 S/S, E1126 S/S, F-1125 & F-1200.
2310-8110-20-P041-0004 Rev-S2
2310-8110-20-P041-0011 Rev-S2
Atm to 2.2
P041-PCL-007
Purple Line
2310-8110-20-P041-0002 Rev-S1
2310-8110-20-P041-0003 Rev-S1
1 to 100
PP SIMTECH COMMENTS:
1. SS 316L lines listed in "Walk the PCL" data for PCL-002 moved to
this PCL as the MOC and DCC are relevant to this PCL.
P041-PCL-003
P041-PCL-004
No
H2O - Nil,
HC- 100%
No
H2O - Nil,
H2 - 0.005%,
HC-87.2 to 100%,
Z12- 8 to 19%,
CAT-Traces,
PP - 12%
1)
2)
3)
4)
5)
6)
7)
C/S
No
H2 - 100%,
H2O - Nil
1) Corrosion - General
2) Corrosion - Localized (No Flow)
P041-PCL-005
40 to 100
SS 304L
No
1)
2)
3)
4)
P041-PCL-006
Amb to 50
C/S
No
CO - 100%
1) Corrosion - General
2) Corrosion - Localized (No Flow)
P041-PCL-007
Corrosion - General
Corrosion - Localized (No Flow)
Corrosion - Localized (Heat Traced)
Fatigue - Vibration.
SCC-Chlorides(External)
P041-PCL-008
SS 316L
Corrosion - General
Corrosion - Localized (No Flow)
Erosion Corrosion (2 Phase Flow & Solid Particles)
SCC-Chlorides(External)
PP SIMTECH COMMENTS:
1. SS 316L lines listed in "Walk the PCL" data for PCL-010 moved to
this PCL which is also mentioned in the given "Walk ther PCL" data for
PCL-008 and also the MOC and DCC are relevant to this PCL.
P041-PCL-008
H-1121
2310-8110-20-P041-0004 Rev-S2
0.2
75
SS 316L
No
H2O - Nil,
H2 - 0.2%,
HC - Rem
1)
2)
3)
4)
5)
P041-PCL-009
2310-8110-20-P041-0003 Rev-S1
2310-8110-20-P041-0004 Rev-S2
0.2 to 21
77 to 85
SS 316L
No
H2O - Nil,
HC- 100%
1)
2)
3)
4)
Corrosion - General
Corrosion - Localized (No Flow)
Erosion Corrosion (Solid Particles)
SCC-Chlorides(External)
P041-PCL-009
P041-PCL-010
R-1102 A, R-1102 L, S-1102 A, E-1102A T/S, Da) From PCL-002/ PCL-005 to R-1102L
1103 A, E-1103A T/S, D-1151, D-1152, H-1121,
b) From PCL_008 (D/S of H-1121 to H-1121, PCL-002, OSBL-HOFCC & Unit- E-1161 S/S, Z-1161, D-1161, D-1162, F-1161
P-010 (TK-9550).
A/B, E-1166 S/S, F-1161 A/B, D-1166, F-1162
c) From various PCL's and equipment to Flare.
A/B, Z-1163, E-1167, D-1152, E-1152, F-1552
A/B.
2310-8110-20-P041-0002 Rev-S1
2310-8110-20-P041-0003 Rev-S1
2310-8110-20-P041-0004 Rev-S2
2310-8110-20-P041-0005 Rev-S2
2310-8110-20-P041-0006 Rev-S3
0.2 to 55
30 to 120
C/S
No
H2O - Nil,
H2 - 0.03 to 0.16%,
HC - Rem to 100%
1)
2)
3)
4)
5)
6)
Corrosion - General
Corrosion - Localized (No Flow)
Corrosion - Localized (Heat Traced)
Erosion Corrosion (2 Phase Flow & Solid Particles)
Erosion Corrosion (Liquid Flashing)
Fatigue - Vibration
P041-PCL-010
P041-PCL-011
2310-8110-20-P041-0003 Rev-S1
2310-8110-20-P041-0004 Rev-S2
0.2
77 to 85
SS 316L
No
H2O - Nil,
H2 - 0.17 to 0.3%,
HC - Rem%,
Z17 - 0.003%,
Z18 - 0.0003%,
CAT - 0.02%,
PP - 86.7 to 89.3%
1)
2)
3)
4)
Corrosion - General
Corrosion - Localized (No Flow)
Fatigue - Vibration
SCC-Chlorides(External)
P041-PCL-011
P041-PCL-012
D-1153
2310-8110-20-P041-0003 Rev-S1
0.5
70
C/S
No
P041-PCL-012
P041-PCL-013
2310-8110-20-P041-0004 Rev-S2
Atm to 3.5
Amb to 110
SS 304L
No
H2O - 0.62%,
N2 - 99.37%
1)
2)
3)
4)
P041-PCL-013
P041-PCL-014
N/A
Atm to 3
Amb to 50
C/S
No
H2O - Nil,
HC - 79.1%,
Z17 - 0.2%,
CAT - 5.2%,
PP - 16.5%
1) Corrosion - General
2) Corrosion - Localized (No Flow)
3) Erosion Corrosion (Solid Particles)
P041-PCL-014
2310-8110-20-P041-0006 Rev-S3
1) Corrosion - General
2) Corrosion - Localized (No Flow)
Corrosion - General
Corrosion - Localized (No Flow)
Corrosion - Localized (Heat Traced)
SCC-Chlorides(External)
P041-PCL-015
BaOH
Z-1552
2310-8110-20-P041-0006 Rev-S3
0.5 to 3.5
Amb to 50
C/S
No
H2O - Nil,
HC- 100%
1) Corrosion - General
2) Corrosion - Localized (No Flow)
P041-PCL-015
P041-PCL-016
BaOH + H2O
2310-8110-20-P041-0006 Rev-S3
0.5 to 3.5
Amb to 50
C/S
No
H2O
HC- 100%
1) Corrosion - General
2) Corrosion - Localized (No Flow)
P041-PCL-016
P041-PCL-017
Moisture
F-1300
2310-8110-20-P041-0012 Rev-S2
0.02
46
SS
No
H2O
1) Corrosion - General
P041-PCL-017
IDENTIFIED DAMAGE MECHANISMS, INSPECTION PLAN and IOLs REVIEWED and APPROVED by PRC
Page 1 of 2
PETRORABIGH UNIT P041 (POLYPROPYLENE PP-1): PCLs SUMMARY WITH DMs-INSPECTION PLAN-IOLs
PCL Number
PCL Name
PCL Colour
PCL Description
Connected Equipment
PFD Number
Pressure
Range
Kg/Cm2
Temp
PCL Material
Range C
PWHT
Yes/No
Damage Mechanism
Inspection Plan
Comments
Alert: Operation outside the IOLs given below can increase damage rate and may initiate a new Damage
Mechanism and hence can adversely affect insp. requirements and insp. interval. Also if there are other
additional IOLs specified by Process Licensor or Site Operating Practice, these shall be included. See Note 1.
P041-PCL-018
P041-PCL-019
Air
P041-PCL-020
P041-PCL-021
Cooling Water
PP SIMTECH COMMENTS:
1. SS 304L lines listed in "Walk the PCL" data for PCL-010 moved to
this PCL as the MOC and DCC are relevant to this PCL.
P041-PCL-018
2310-8110-20-P041-0004 Rev-S2
0.2
80
SS 304L
No
2310-8110-20-P041-0012 Rev-S2
0.05 to 2
Amb to 210
SS 304
No
Air
1) Corrosion - General
2) Corrosion - Localized (No Flow)
3) SCC-Chlorides (External)
None
P041-PCL-019
From H-1301, H-1302 A/B/C/D/E & PCL- 019 TO S-1312, S1371, U/S of S1372 & U/S of H-1222
2310-8110-20-P041-0012 Rev-S2
2310-8110-20-P041-0013 Rev-S2
0.1 to 2.5
60
SS 304
No
H2O - Nil,
Air - TBS,
HC - Rem to 100%
1) Corrosion - General
2) Erosion Corrosion (2 Phase Flow & Solid Particles)
3) SCC-Chlorides (External)
P041-PCL-020
2310-8110-20-P041-0011 Rev-S2
Atm to 4
36 to 46
SS 304
No
Cooling Water
1) Corrosion - General
P041-PCL-021
2310-8110-20-P041-0002 Rev-S1
2310-8110-20-P041-0003 Rev-S1
2310-8110-20-P041-0004 Rev-S2
2310-8110-20-P041-0005 Rev-S2
2310-8110-20-P041-0006 Rev-S3
2310-8110-20-P041-0011 Rev-S2
2310-8110-20-P041-0012 Rev-S2
2.5 to 4
36 to 46
C/S
No
Cooling Water
1) Corrosion - General
2) Corrosion - Localized (No Flow)
P041-PCL-022
2310-8110-20-P041-0001 Rev-S1
2310-8110-20-P041-0002 Rev-S1
2310-8110-20-P041-0006 Rev-S3
0.1 to 5.4
2 to 60
C/S
No
1) Corrosion - General
2) Corrosion - Localized (No Flow)
3) CUI
P041-PCL-023
2310-8110-20-P041-0001 Rev-S1
2310-8110-20-P041-0003 Rev-S1
2310-8110-20-P041-0004 Rev-S2
2310-8110-20-P041-0005 Rev-S2
2310-8110-20-P041-0006 Rev-S3
2310-8110-20-P041-0011 Rev-S2
1) Corrosion - General
2) Corrosion - Localized (No Flow)
3) CUI
P041-PCL-025
P041-PCL-026
P041-PCL-022
Cooling Water
Yellow Line
P041-PCL-023
Chilled water
Steam
Corrosion - General
Corrosion - Localized (No Flow)
Fatigue - Vibration
SCC-Chlorides (External)
Cooling water Supply to R-1102 L, E-1102A S/S, E-1103A S/S, E-1121 T/S,
E-1122 T/S, PCL-006 Jacketing line, E-1161 T/S, E-1162, E-1166 T/S, D1550 (Jacketing), D-1551 (Jacketing), RU-1070, D-1552 (Jacketing), E1552, E-1125 T/S, E-1126 T/S, E-1201 T/S, E-1202 T/S, E-1261 A/B (T/S), E1301 T/S, E-1302 T/S, E-1303 T/S, E-1304 T/S, E-1340 T/S & E-1350 T/S
and back
P041-PCL-024
1)
2)
3)
4)
H2O - Nil,
H2 - 0.2%,
HC - Rem
Steam line to E-1051, E-1142 T/S, D-1103 A, E-1167, E-1124 T/S, D-1240
(Jacketing), D-1241 (Jacketing), PCL-022 U/S of E-1102 A & D-1551
4.5 to 7
160 to 200
C/S
No
Steam
PP SIMTECH COMMENTS:
1. Revised Walk the PCL Data vide Mail dated 15/03/2016 and TRANSINX_INSP-148 is considered.
PP SIMTECH COMMENTS:
1. Revised Walk the PCL Data vide Mail dated 15/03/2016 and
TRANS-INX_INSP-148 is used.
P041-PCL-024
PP SIMTECH COMMENTS:
1. SS 304L lines listed in "Walk the PCL" data for PCL-027 moved to
this PCL as the MOC and DCC are relevant to this PCL.
P041-PCL-025
Steam Condensate
2310-8110-20-P041-0003 Rev-S1
2310-8110-20-P041-0011 Rev-S2
0.1
103
SS 304L
No
1) Corrosion - General
2) Corrosion - Localized (No Flow)
3) SCC-Chlorides (External)
P041-PCL-026
Nitrogen
2310-8110-20-P041-0001 Rev-S1
2310-8110-20-P041-0004 Rev-S2
2310-8110-20-P041-0006 Rev-S3
2310-8110-20-P041-0011 Rev-S2
0.1 to 3.5
Amb
C/S
No
Nitrogen -100%
1) Corrosion - General
2) Corrosion - Localized (No Flow)
None
2310-8110-20-P041-0001 Rev-S1
2310-8110-20-P041-0003 Rev-S1
2310-8110-20-P041-0004 Rev-S2
2310-8110-20-P041-0005 Rev-S2
2310-8110-20-P041-0011 Rev-S2
1 to 2
114 to 133
C/S
No
1) Corrosion - General
2) Corrosion - Localized (No Flow)
P041-PCL-027
2310-8110-20-P041-0011 Rev-S2
200
SS 304
No
Steam
1) Corrosion - General
2) SCC-Chlorides (External)
P041-PCL-028
2310-8110-20-P041-0011 Rev-S2
2 to 5.5
Amb
SS 304L
No
DM Water -100 %
1) Corrosion - General
2) Corrosion - Localized (No Flow)
P041-PCL-029
PP SIMTECH COMMENTS:
1. Revised Walk the PCL Data vide Mail dated 15/03/2016 and TRANSINX_INSP-148 is used.
2. C/Steel lines listed in "Walk the PCL" data for PCL-025 moved to this
PCL as the MOC and DCC are relevant to this PCL.
P041-PCL-027
Condensate
P041-PCL-028
Steam
P041-PCL-029
Demineralized Water
P041-PCL-030
Instrument Air
2310-8110-20-P041-0011 Rev-S2
Amb
SS 304
No
Air (Utility)
1) Corrosion - General
2) Corrosion - Localized (No Flow)
None
P041-PCL-030
P041-PCL-031
Nitrogen
2310-8110-20-P041-0011 Rev-S2
0.7 to 3.5
Amb
SS 304L
No
Nitrogen
1) Corrosion - General
2) Corrosion - Localized (No Flow)
None
P041-PCL-031
2310-8110-20-P041-0011 Rev-S2
Amb
SS 304
No
Utility Water
1) Corrosion - General
P041-PCL-032
P041-PCL-032
P041-PCLUnidentified
None
2310-8110-20-P041-0004 Rev-S2
1) Fatigue - Vibation
2) Corrosion Shielding / Under Deposit (External)
PP SIMTECH COMMENTS:
1. Revised Walk the PCL Data vide Mail dated 15/03/2016 and TRANSINX_INSP-148 is used.
2. C/Steel lines listed in "Walk the PCL" data for PCL-031 moved to this
PCL as the MOC and DCC are relevant to this PCL.
P041-PCL-Unidentified
PP SIMTECH COMMENTS:
1. SS 304L lines listed in "Walk the PCL" data for PCL-026 moved to
this PCL as the MOC and DCC are relevant to this PCL.
PP SIMTECH COMMENTS :
PRC has provided Walk the PCL data for the lines which are unidentified
in the marked P & IDs. PP SIMTECH has reviewed the line numbers
listed in this Walk the PCL data and shifted to the respective PCLs.
However there are few more lines which could not be identified with
the existing PCLs. For such lines, the additional inspection plan
(except general corrosion) is given in this PCL which is numbered as
F041-PCL- Unidentified. PRC/Inovx to review the lines listed in this PCL
inspection Plan and shift the same to relevant PCLs based on the MoC
and DCCs present.
IOLs: Note 1
PRC Actions for Setting IOLs By Process/Operation Engineers
1. Measure and Establish Operating Temperatures.
2. If the presence of listed Damage Causing Chemicals (DCCs) or their composition is uncertain or presence of certain other DCC is suspected, instigate chemical sampling to confirm actual DCCs present and their composition.
3. Measure and establish actual Min. and Max. pH to set IOL
4. Establish Conductivity, pH to set IOL.(Specific PCL-029)
5. Establish Conductivity, pH and TDS (Total Dissolved Solids) to set IOL.(Specific PCL-025, PCL-027 and PCL-032)
6. Establish Conductivity, pH, TDS (Total Dissolved Solids) and Treatment Chemicals concentration to set IOL. (Specific PCL-021, PCL-022 and PCL-023)
7. Analyse and confirm moisture is 'Nil', unless moisture/H2O is poison to the process.(Specific to PCL- 001 to PCL-005, PCL-007 to PCL-011, PCL-014 to PCL-015, PCL-018, PCL-020)
8. If there are other additional IOLs specified by Process Licensor or Site Operating Practice, these shall be included.
IOLs: Note 2
a) It should be noted that Pressure, Temperature & Process Fluid Stream Compositions provided by PRC (as shown above for each PCL) is the known Range under Normal Operation
b) Agreed IOLs shall be set and monitored by Operations / Process Department and the impact of any excursions shall be jointly reviewed by Process/Operations/Inspection Dept, ideally on a quarterly basis.
IDENTIFIED DAMAGE MECHANISMS, INSPECTION PLAN and IOLs REVIEWED and APPROVED by PRC