Sunteți pe pagina 1din 15

Pruebas De Operatividad De Reles de Proteccion del Proyecto Misti 6.

0 KV

REPORTE DE PRUEBA OMICRON


CELDA = CA2
Proteccin de Bahia 10.5 kV
RELE AREVA / P141
Compaia:

OEM ELECTRIC SAC.

Nombre de Usuario:

JENSEN GARCIA R.

Dia de Prueba:

04 de Agosto, 2016

Estado de Prueba:
Modulos de Prueba:
12
Modulos de Prueba Correctos:
9
Modulos de Pruebas con Error:
0
_____________________________________________________________________________

Test Object - Device Settings


Substation/Bay:
Substation:
Bay:

SE 5 MANANTIALES
CELDA = CA4

Substation address:
Bay address:

RELE DE SOBRECORRIENTE
P141
102877T
CT = 600/5

Manufacturer:
Device address:

AREVA
P141316A6M0410J

60.00 Hz
100.0 V
5.000 A

Number of phases:
V primary:
I primary:

3
10.50 kV
600.0 A

1.732

IN / I nom:

200.0 m

200.0 V

I max:

60.00 A

Deglitch time:

0.000 s

Device:
Name/description:
Device type:
Serial/model number:
Additional info 1:
Additional info 2:

Nominal Values:
f nom:
V nom (secondary):
I nom (secondary):

Residual Voltage/Current Factors:


VLN / VN:

Limits:
V max:

Debounce/Deglitch Filters:
Debounce time:

3.000 ms

Overload Detection:
Suppression time:

50.00 ms

1 de 15

Pruebas De Operatividad De Reles de Proteccion del Proyecto Misti 6.0 KV

Test Object - Other RIO Functions


CB Configuration
Description

Name

Value

CB trip time
CB close time
Times for 52a, 52b in percent of CB time

CB trip time
CB close time
52a, 52b % of CB

50.00 ms
100.00 ms
20.00 %

Test Object - Differential Parameters


Protected Object:
Protected Object:
Vector Group:

Transformer
YY0

Winding/Leg Name:

Primary

Secondary

58.00 kV
25.00 MVA
Yes
No

22.90 kV
25.00 MVA
Yes
No

Primary

Secondary

300.00 A
1.00 A
tow. Prot. Obj.
12000.00 A
5.00 A
n/a

600.00 A
5.00 A
tow. Prot. Obj.
12000.00 A
5.00 A
n/a

Voltage:
Power:
Starpoint Grounding:
Delta-connected CT:

CT:
Winding/Leg Name:
CT Current Prim:
CT Current Sec:
CT Grounding:
Gnd CT Prim Current:
Gnd CT Sec Current:
Gnd CT Grounding:

Protection device:
Reference Winding:
Ibias Calculation:
Zero Seq. Elimination:
Reference Current:
Ground CT Used:

Secondary
( |Ip| + |Is| ) / K1 (K1 = 1.00)
IL-I0
PO nominal current
No

Idiff>:
Idiff>>:

0.30 In
10.00 In

Itol rel:
Itol abs:

4.00 %
0.10 In

tdiff>:
tdiff>>:

0.03 s
0.03 s

ttol rel:
ttol abs:

3.00 %
0.01 s

VT connection:
CT starpoint connection:

At protected object
To protected object

Test Object - Overcurrent Parameters


General - Values:
TimeTolAbs:
TimeTolRel:
CurrentTolAbs:
CurrentTolRel:
Directional:

0.04 s
5.00 %
0.00 Iref
0.00 %
No

Elements - Phase:
Active

Name

Tripping characteristic

I Pick-up

Time

Reset Ratio

Direction

Yes

I>

IEC Very Inverse

0.44 Iref

1.00

0.95

Non Directional

2 de 15

Pruebas De Operatividad De Reles de Proteccion del Proyecto Misti 6.0 KV

Elements - Residual:
Active

Name

Tripping characteristic

I Pick-up

Time

Reset Ratio

Direction

Yes

Io>

IEC Definite Time

0.08 Iref

0.30 s

0.95

Non Directional

Elements - Negative Sequence:


Active

Name

Tripping characteristic

I Pick-up

Time

Reset Ratio

Direction

Yes

I2>

IEC Definite Time

0.20 Iref

3.00 s

0.95

Non Directional

Test Object - Distance Settings


System parameters:
Line length:
PT connection:
Impedance correction
1A/I nom:
Impedances in primary
values:

40.00
at line
no

Line angle:
CT starpoint:

270.00
Dir. line

Tol. T abs. -:
Tol. Z abs.:

100.0 ms
100.0 m

kL angle:

0.000000

no

Tolerances:
Tol. T rel.:
Tol. T abs. +:
Tol. Z rel.:

5.000 %
100.0 ms
5.000 %

Grounding factor:
kL mag.:
Separate arc
resistance:

1.000000
no

Zone Settings:
Label

Type

Fault loop Trip time

Tol.T rel

Tol.T abs+ Tol.T abs- Tol.Z rel.

Tol.Z abs

Z1 All
Z2 All

Tripping
Tripping

All
All

5.000 %
5.000 %

100.0 ms
100.0 ms

100.0 m
100.0 m

80.00 ms
500.0 ms

100.0 ms
100.0 ms

X/
-5
-10
-15
-20
-25
-30
-35
-40

-25

-20

-15

-10

-5

10

15

20

3 de 15

R/

5.000 %
5.000 %

Pruebas De Operatividad De Reles de Proteccion del Proyecto Misti 6.0 KV

Hardware Configuration
Test Equipment
Type

Serial Number

CMC356

BD480B

Hardware Check
Performed At

Result

04/08/2016 06:14:43
p.m.

Passed

Details

Group:A) Inyeccion inicial

1) Inyeccion Corriente y Tension


1.1) [Iny] Corriente V3P & I3p_No Trip
Test Module
Name:
Test Start:
User Name:
Company:

OMICRON QuickCMC
04-ago-2016 18:21:01

Version:
Test End:
Manager:

3.01
04-ago-2016 18:22:07

Test Results
Title: No Trip
Fault Calculator:
Table Inputmode

Parameters (All values are secondary)

Direct

I L1
I L2
I L3

1.000 A
1.000 A
1.000 A

0.00
-120.00
120.00

60.000 Hz
60.000 Hz
60.000 Hz

Generator Settings
I L1
I L2
I L3

1.000A
1.000A
1.000A

0.00
-120.00
120.00

I L3

+90

I L1
0

180

I L2
1.0 A

-90

Binary Inputs
TRIP

Overload

Summary
1 tests passed, 0 tests failed, 0 tests not assessed
Test passed

100.00% passed

1.2) [Iny] Corriente V3P & I3p_Trip


4 de 15

Pruebas De Operatividad De Reles de Proteccion del Proyecto Misti 6.0 KV

Test Module
Name:
Test Start:
User Name:
Company:

OMICRON QuickCMC
04-ago-2016 18:22:14

Version:
Test End:
Manager:

3.01
04-ago-2016 18:22:35

Test Results
Title:
Fault Calculator:
Table Inputmode

Parameters (All values are secondary)

Direct

I L1
I L2
I L3

10.00 A
10.00 A
10.00 A

-20.00
-140.00
100.00

60.000 Hz
60.000 Hz
60.000 Hz

Generator Settings
I L1
I L2
I L3

10.000A
10.000A
10.000A

-20.00
-140.00
100.00

+90
I L3

180

0
I L1

I L2
10.0 A

-90

Binary Inputs
TRIP

Overload

0->1
3.821s

1->0
n/a

Summary
1 tests passed, 0 tests failed, 0 tests not assessed
Test passed

100.00% passed

Group end:A) Inyeccion inicial

Group:B) Sobrecorriente de fases

2) [50/51] Tiempo de operacion

5 de 15

Pruebas De Operatividad De Reles de Proteccion del Proyecto Misti 6.0 KV

2.1) [50/51] Trip Time_L1L2:


Test Object - Overcurrent Parameters
General - Values:
TimeTolAbs:
TimeTolRel:
CurrentTolAbs:
CurrentTolRel:
Directional:

0.04 s
5.00 %
0.00 Iref
0.00 %
No

VT connection:
CT starpoint connection:

At protected object
To protected object

Elements - Phase:
Active

Name

Tripping characteristic

I Pick-up

Time

Reset Ratio

Direction

Yes

I>

IEC Very Inverse

0.44 Iref

1.00

0.95

Non Directional

Elements - Residual:
Active

Name

Tripping characteristic

I Pick-up

Time

Reset Ratio

Direction

Yes

Io>

IEC Definite Time

0.08 Iref

0.30 s

0.95

Non Directional

Elements - Negative Sequence:


Active

Name

Tripping characteristic

I Pick-up

Time

Reset Ratio

Direction

Yes

I2>

IEC Definite Time

0.20 Iref

3.00 s

0.95

Non Directional

Test Module
Name:
Test Start:
User Name:
Company:

OMICRON Overcurrent
04-ago-2016 18:27:46

Version:
Test End:
Manager:

3.01
04-ago-2016 18:29:28

Test Settings:
Binary Inputs:
Trigger Logic:

And

Name

Trigger State

TRIP

Shot Test Results:


Type

Relative To

Factor

Magnitude

Angle

tnom

tact

Overload

Result

L1-L2
L1-L2
L1-L2
L1-L2
L1-L2
L1-L2
L1-L2
L1-L2
L1-L2
L1-L2

(---)
(---)
(---)
(---)
(---)
(---)
(---)
(---)
(---)
(---)

n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a

8.00 A
11.00 A
14.00 A
17.00 A
20.00 A
23.00 A
26.00 A
29.00 A
32.00 A
35.00 A

n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a

5.121 s
3.375 s
2.517 s
2.007 s
1.669 s
1.428 s
1.248 s
1.108 s
996.6 ms
905.5 ms

5.135 s
3.384 s
2.528 s
2.023 s
1.677 s
1.444 s
1.265 s
1.123 s
1.013 s
919.2 ms

No
No
No
No
No
No
No
No
No
No

Passed
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Passed

Charts for Fault Types:


Type
L1-L2

Angle
n/a

6 de 15

Pruebas De Operatividad De Reles de Proteccion del Proyecto Misti 6.0 KV


10000.0
1000.0
t/s

100.0
10.0
1.0
3

10

20

30

I/A

State:
10 out of 10 points tested.
10 points passed.
0 points failed.
General Assessment: Test passed!

2.2) [50/51] Trip Time_L2L3:


Test Object - Overcurrent Parameters
General - Values:
TimeTolAbs:
TimeTolRel:
CurrentTolAbs:
CurrentTolRel:
Directional:

0.04 s
5.00 %
0.00 Iref
0.00 %
No

VT connection:
CT starpoint connection:

At protected object
To protected object

Elements - Phase:
Active

Name

Tripping characteristic

I Pick-up

Time

Reset Ratio

Direction

Yes

I>

IEC Very Inverse

0.44 Iref

1.00

0.95

Non Directional

Elements - Residual:
Active

Name

Tripping characteristic

I Pick-up

Time

Reset Ratio

Direction

Yes

Io>

IEC Definite Time

0.08 Iref

0.30 s

0.95

Non Directional

Elements - Negative Sequence:


Active

Name

Tripping characteristic

I Pick-up

Time

Reset Ratio

Direction

Yes

I2>

IEC Definite Time

0.20 Iref

3.00 s

0.95

Non Directional

Test Module
Name:
Test Start:
User Name:
Company:

OMICRON Overcurrent
04-ago-2016 18:26:25

Version:
Test End:
Manager:

Test Settings:
Binary Inputs:
Trigger Logic:

And

Name

Trigger State

TRIP

7 de 15

3.01
04-ago-2016 18:27:35

40

Pruebas De Operatividad De Reles de Proteccion del Proyecto Misti 6.0 KV

Shot Test Results:


Type

Relative To

Factor

Magnitude

Angle

tnom

tact

Overload

Result

L2-L3
L2-L3
L2-L3
L2-L3
L2-L3
L2-L3
L2-L3
L2-L3
L2-L3
L2-L3

(---)
(---)
(---)
(---)
(---)
(---)
(---)
(---)
(---)
(---)

n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a

8.00 A
11.00 A
14.00 A
17.00 A
20.00 A
23.00 A
26.00 A
29.00 A
32.00 A
35.00 A

n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a

5.121 s
3.375 s
2.517 s
2.007 s
1.669 s
1.428 s
1.248 s
1.108 s
996.6 ms
905.5 ms

5.125 s
3.381 s
2.536 s
2.019 s
1.680 s
1.443 s
1.259 s
1.122 s
1.014 s
922.1 ms

No
No
No
No
No
No
No
No
No
No

Passed
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Passed

Charts for Fault Types:


Angle

Type
L2-L3

n/a

10000.0
1000.0
t/s

100.0
10.0
1.0
3

10

20

30

I/A

State:
10 out of 10 points tested.
10 points passed.
0 points failed.
General Assessment: Test passed!

2.3) [50/51] Trip Time_L3L1:


Test Object - Overcurrent Parameters
General - Values:
TimeTolAbs:
TimeTolRel:
CurrentTolAbs:
CurrentTolRel:
Directional:

0.04 s
5.00 %
0.00 Iref
0.00 %
No

VT connection:
CT starpoint connection:

At protected object
To protected object

Elements - Phase:
Active

Name

Tripping characteristic

I Pick-up

Time

Reset Ratio

Direction

Yes

I>

IEC Very Inverse

0.44 Iref

1.00

0.95

Non Directional

Elements - Residual:
Active

Name

Tripping characteristic

I Pick-up

Time

Reset Ratio

Direction

Yes

Io>

IEC Definite Time

0.08 Iref

0.30 s

0.95

Non Directional

8 de 15

40

Pruebas De Operatividad De Reles de Proteccion del Proyecto Misti 6.0 KV

Elements - Negative Sequence:


Active

Name

Tripping characteristic

I Pick-up

Time

Reset Ratio

Direction

Yes

I2>

IEC Definite Time

0.20 Iref

3.00 s

0.95

Non Directional

Test Module
Name:
Test Start:
User Name:
Company:

OMICRON Overcurrent
04-ago-2016 18:23:54

Version:
Test End:
Manager:

3.01
04-ago-2016 18:26:07

Test Settings:
Binary Inputs:
Trigger Logic:

And

Name

Trigger State

TRIP

Shot Test Results:


Type

Relative To

Factor

Magnitude

Angle

tnom

tact

Overload

Result

L3-L1
L3-L1
L3-L1
L3-L1
L3-L1
L3-L1
L3-L1
L3-L1
L3-L1
L3-L1

(---)
(---)
(---)
(---)
(---)
(---)
(---)
(---)
(---)
(---)

n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a

8.00 A
11.00 A
14.00 A
17.00 A
20.00 A
23.00 A
26.00 A
29.00 A
32.00 A
35.00 A

n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a

5.121 s
3.375 s
2.517 s
2.007 s
1.669 s
1.428 s
1.248 s
1.108 s
996.6 ms
905.5 ms

5.127 s
3.386 s
2.532 s
2.018 s
1.679 s
1.443 s
1.258 s
1.122 s
1.011 s
918.0 ms

No
No
No
No
No
No
No
No
No
No

Passed
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Passed

Charts for Fault Types:


Angle

Type
L3-L1

n/a

10000.0

t/s

1000.0
100.0
10.0
1.0
3

10
I/A

State:
10 out of 10 points tested.
10 points passed.
0 points failed.
General Assessment: Test passed!

2.4) [50/51] Trip Time_L1L2L3:

9 de 15

20

30

40

Pruebas De Operatividad De Reles de Proteccion del Proyecto Misti 6.0 KV

Test Object - Overcurrent Parameters


General - Values:
TimeTolAbs:
TimeTolRel:
CurrentTolAbs:
CurrentTolRel:
Directional:

0.04 s
5.00 %
0.00 Iref
0.00 %
No

VT connection:
CT starpoint connection:

At protected object
To protected object

Elements - Phase:
Active

Name

Tripping characteristic

I Pick-up

Time

Reset Ratio

Direction

Yes

I>

IEC Very Inverse

0.44 Iref

1.00

0.95

Non Directional

Elements - Residual:
Active

Name

Tripping characteristic

I Pick-up

Time

Reset Ratio

Direction

Yes

Io>

IEC Definite Time

0.08 Iref

0.30 s

0.95

Non Directional

Elements - Negative Sequence:


Active

Name

Tripping characteristic

I Pick-up

Time

Reset Ratio

Direction

Yes

I2>

IEC Definite Time

0.20 Iref

3.00 s

0.95

Non Directional

Test Module
Name:
Test Start:
User Name:
Company:

OMICRON Overcurrent
04-ago-2016 18:23:00

Version:
Test End:
Manager:

3.01
04-ago-2016 18:23:41

Test Settings:
Binary Inputs:
Trigger Logic:

And

Name

Trigger State

TRIP

Shot Test Results:


Type

Relative To

Factor

Magnitude

Angle

tnom

tact

Overload

Result

L1-L2-L3
L1-L2-L3
L1-L2-L3
L1-L2-L3
L1-L2-L3
L1-L2-L3
L1-L2-L3
L1-L2-L3
L1-L2-L3
L1-L2-L3

(---)
(---)
(---)
(---)
(---)
(---)
(---)
(---)
(---)
(---)

n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a

8.00 A
11.00 A
14.00 A
17.00 A
20.00 A
23.00 A
26.00 A
29.00 A
32.00 A
35.00 A

n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a

5.121 s
3.375 s
2.517 s
2.007 s
1.669 s
1.428 s
1.248 s
1.108 s
996.6 ms
905.5 ms

5.131 s
3.389 s
2.526 s
2.016 s
1.679 s
1.443 s
1.259 s
1.119 s
1.015 s
920.1 ms

No
No
No
No
No
No
No
No
No
No

Passed
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Passed

Charts for Fault Types:


Type
L1-L2-L3

Angle
n/a

10 de 15

Pruebas De Operatividad De Reles de Proteccion del Proyecto Misti 6.0 KV


10000.0
1000.0
t/s

100.0
10.0
1.0
3

10

20

30

I/A

State:
10 out of 10 points tested.
10 points passed.
0 points failed.
General Assessment: Test passed!
Group end:B) Sobrecorriente de fases
Group:C) Sobrecorriente de tierra

3) [50N/51N] Tiempo de operacion

3.1) [50N/51N] Trip Time_L1E:


Test Object - Overcurrent Parameters
General - Values:
TimeTolAbs:
TimeTolRel:
CurrentTolAbs:
CurrentTolRel:
Directional:

0.04 s
5.00 %
0.00 Iref
0.00 %
No

VT connection:
CT starpoint connection:

At protected object
To protected object

Elements - Phase:
Active

Name

Tripping characteristic

I Pick-up

Time

Reset Ratio

Direction

Yes

I>

IEC Very Inverse

0.44 Iref

1.00

0.95

Non Directional

11 de 15

40

Pruebas De Operatividad De Reles de Proteccion del Proyecto Misti 6.0 KV

Elements - Residual:
Active

Name

Tripping characteristic

I Pick-up

Time

Reset Ratio

Direction

Yes

Io>

IEC Definite Time

0.08 Iref

0.30 s

0.95

Non Directional

Elements - Negative Sequence:


Active

Name

Tripping characteristic

I Pick-up

Time

Reset Ratio

Direction

Yes

I2>

IEC Definite Time

0.20 Iref

3.00 s

0.95

Non Directional

Test Module
Name:
Test Start:
User Name:
Company:

OMICRON Overcurrent
04-ago-2016 18:30:21

Version:
Test End:
Manager:

3.01
04-ago-2016 18:30:42

Test Settings:
Binary Inputs:
Trigger Logic:

And

Name

Trigger State

TRIP

Shot Test Results:


Type

Relative To

Factor

Magnitude

Angle

tnom

tact

Overload

Result

L1-E
L1-E
L1-E
L1-E
L1-E
L1-E
L1-E
L1-E
L1-E
L1-E

(---)
(---)
(---)
(---)
(---)
(---)
(---)
(---)
(---)
(---)

n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a

0.50 A
1.50 A
2.50 A
3.50 A
4.50 A
5.50 A
6.50 A
7.50 A
8.50 A
9.50 A

n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a

300.0 ms
300.0 ms
300.0 ms
300.0 ms
300.0 ms
300.0 ms
300.0 ms
300.0 ms
300.0 ms
300.0 ms

326.8 ms
320.7 ms
322.1 ms
323.7 ms
324.5 ms
322.6 ms
317.1 ms
324.5 ms
318.4 ms
320.1 ms

No
No
No
No
No
No
No
No
No
No

Passed
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Passed

Charts for Fault Types:


Type
L1-E

Angle
n/a

t/s

0.60
0.50
0.40
0.30
0.20

0.5

0.7

1.0

2.0

3.0
I/A

12 de 15

5.0

7.0

10.0

20.0

Pruebas De Operatividad De Reles de Proteccion del Proyecto Misti 6.0 KV

State:
10 out of 10 points tested.
10 points passed.
0 points failed.
General Assessment: Test passed!

3.2) [50N/51N] Trip Time_L2E:


Test Object - Overcurrent Parameters
General - Values:
TimeTolAbs:
TimeTolRel:
CurrentTolAbs:
CurrentTolRel:
Directional:

0.04 s
5.00 %
0.00 Iref
0.00 %
No

VT connection:
CT starpoint connection:

At protected object
To protected object

Elements - Phase:
Active

Name

Tripping characteristic

I Pick-up

Time

Reset Ratio

Direction

Yes

I>

IEC Very Inverse

0.44 Iref

1.00

0.95

Non Directional

Elements - Residual:
Active

Name

Tripping characteristic

I Pick-up

Time

Reset Ratio

Direction

Yes

Io>

IEC Definite Time

0.08 Iref

0.30 s

0.95

Non Directional

Elements - Negative Sequence:


Active

Name

Tripping characteristic

I Pick-up

Time

Reset Ratio

Direction

Yes

I2>

IEC Definite Time

0.20 Iref

3.00 s

0.95

Non Directional

Test Module
Name:
Test Start:
User Name:
Company:

OMICRON Overcurrent
04-ago-2016 18:30:57

Version:
Test End:
Manager:

3.01
04-ago-2016 18:31:18

Test Settings:
Binary Inputs:
Trigger Logic:

And

Name

Trigger State

TRIP

Shot Test Results:


Type

Relative To

Factor

Magnitude

Angle

tnom

tact

Overload

Result

L2-E
L2-E
L2-E
L2-E
L2-E
L2-E
L2-E
L2-E
L2-E
L2-E

(---)
(---)
(---)
(---)
(---)
(---)
(---)
(---)
(---)
(---)

n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a

0.50 A
1.50 A
2.50 A
3.50 A
4.50 A
5.50 A
6.50 A
7.50 A
8.50 A
9.50 A

n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a

300.0 ms
300.0 ms
300.0 ms
300.0 ms
300.0 ms
300.0 ms
300.0 ms
300.0 ms
300.0 ms
300.0 ms

335.9 ms
325.8 ms
325.8 ms
318.6 ms
322.3 ms
319.1 ms
321.9 ms
319.7 ms
320.3 ms
318.0 ms

No
No
No
No
No
No
No
No
No
No

Passed
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Passed

13 de 15

Pruebas De Operatividad De Reles de Proteccion del Proyecto Misti 6.0 KV

Charts for Fault Types:


Angle

Type
L2-E

n/a

0.60
0.50
0.40
t/s

0.30
0.20

0.5

0.7

1.0

2.0

3.0

5.0

7.0

10.0

I/A

State:
10 out of 10 points tested.
10 points passed.
0 points failed.
General Assessment: Test passed!

3.3) [50N/51N] Trip Time_L3E:


Test Object - Overcurrent Parameters
General - Values:
TimeTolAbs:
TimeTolRel:
CurrentTolAbs:
CurrentTolRel:
Directional:

0.04 s
5.00 %
0.00 Iref
0.00 %
No

VT connection:
CT starpoint connection:

At protected object
To protected object

Elements - Phase:
Active

Name

Tripping characteristic

I Pick-up

Time

Reset Ratio

Direction

Yes

I>

IEC Very Inverse

0.44 Iref

1.00

0.95

Non Directional

Elements - Residual:
Active

Name

Tripping characteristic

I Pick-up

Time

Reset Ratio

Direction

Yes

Io>

IEC Definite Time

0.08 Iref

0.30 s

0.95

Non Directional

Elements - Negative Sequence:


Active

Name

Tripping characteristic

I Pick-up

Time

Reset Ratio

Direction

Yes

I2>

IEC Definite Time

0.20 Iref

3.00 s

0.95

Non Directional

Test Module
Name:
Test Start:
User Name:
Company:

OMICRON Overcurrent
04-ago-2016 18:31:30

Version:
Test End:
Manager:

14 de 15

3.01
04-ago-2016 18:32:22

20.0

Pruebas De Operatividad De Reles de Proteccion del Proyecto Misti 6.0 KV

Test Settings:
Binary Inputs:
Trigger Logic:

And

Name

Trigger State

TRIP

Shot Test Results:


Type

Relative To

Factor

Magnitude

Angle

tnom

tact

Overload

Result

L3-E
L3-E
L3-E
L3-E
L3-E
L3-E
L3-E
L3-E
L3-E
L3-E

(---)
(---)
(---)
(---)
(---)
(---)
(---)
(---)
(---)
(---)

n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a

0.50 A
1.50 A
2.50 A
3.50 A
4.50 A
5.50 A
6.50 A
7.50 A
8.50 A
9.50 A

n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a

300.0 ms
300.0 ms
300.0 ms
300.0 ms
300.0 ms
300.0 ms
300.0 ms
300.0 ms
300.0 ms
300.0 ms

325.8 ms
323.6 ms
325.9 ms
324.4 ms
317.3 ms
320.8 ms
323.7 ms
322.6 ms
322.6 ms
324.3 ms

No
No
No
No
No
No
No
No
No
No

Passed
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Passed

Charts for Fault Types:


Type
L3-E

Angle
n/a

t/s

0.60
0.50
0.40
0.30
0.20

0.5

0.7

1.0

2.0

3.0
I/A

State:
10 out of 10 points tested.
10 points passed.
0 points failed.
General Assessment: Test passed!
Group end:C) Sobrecorriente de tierra

15 de 15

5.0

7.0

10.0

20.0

S-ar putea să vă placă și