Sunteți pe pagina 1din 61

EE 101

Electrical Sciences

Department of Electronics & Electrical Engineering


Indian Institute of Technology Guwahati

EE 101
AC Circuits and Systems
AC Circuits - Sinusoidal Analysis
G. B. Shrestha
Visiting Professor

Department of Electronics & Electrical Engineering


New Faculty Block - Room 13,
Ph. x3475, Email: gbshrestha@iitg.ernet.in

Indian Institute of Technology Guwahati

Sinusoidal Functions
A sinusoidal wave form is generated by the vertical component of a vector rotating

counterclockwise with uniform angular velocity as shown in Fig. 1

v V p sin(t ) V p sin(2 ft )

(1)

Fig. 4:

where,

v
Vp

is instantaneous voltage, and


is the peak or the maximum value (amplitude)

One cycle:

Period (T):
Frequency (f):
Angular speed ():

is a complete revolution
time required for one revolution
Number of cycles per second (f = 1/T)
2f

(s)
Hz
rad/s

Such rotating vectors are termed Phasors. It may be noted that the horizontal component of

the rotating vector will give the cosine wave.


Indian Institute of Technology Guwahati

Sinusoidal Functions
In Fig. 2, there are two sinusoids, denoting two voltages and the

corresponding phasors.
It is possible that the

sinusoids pass through zero


at different times, but it is
necessary for the two
sinusoids to have the
same frequency to be
included in the same diagram.
If,

Fig. 5:

v1 V p1 sin(t ) V p1 sin(2 ft )

(2)

v2 Vp 2 sin(t ) V p 2 sin(2 ft )

(3)

Then, is said to be the phase difference between v1 and v2.and


the phasor that passes through zero at t=0 is called the reference.

In Figure 2, v1 is the reference and v2 is said to lead v1 by .


Indian Institute of Technology Guwahati

Average Value of Sinusoids


A general definition of the average value of any function f(t) over the specified

interval between t1 and t2 is expressed as


1 t2
Fav
(4)
t1 f (t )dt
t2 t1
The average value of a cyclic function is
1 2
1 2
Fav
f
(

t
)
d
(

t
)

f ( )d (5)
2 0
2 0
Hence the average value of a sinusoidal voltage is:
2
vav 0 V p sin(t )d (t ) 0
(6)
The average value of a sinusoid over one complete cycle is equal to zero.
A finite and more meaningful average value can be found for the sinusoid for
the positive or negative half cycle. The half cycle average value for the
waveform shown in Fig.1 is given by
1
2
vav 0 V p sin(t )d (t ) V p 0.636V p (7)

The average value of either the positive or negative half of a sine function can
be found by multiplying the amplitude of the wave by 0.636.
Indian Institute of Technology Guwahati

Effective (RMS) Value of Sinusoids


Although the criterion of the average value of current works well in describing

the energy transferring capacity for direct sources, it is less meaningful for
symmetrical periodic functions.
A more suitable definition of the average value for a symmetric periodic

functions is effective current. It is expressed as


1 T 2
I eff I rms
(8)
0 i (t )dt
T
If the function I(t) in eq. 8 is sinusoidal then the effective value is obtained as
1 T 2
1 T 2 2
I eff
i
(
t
)
dt

(9)
0
0 I m sin t
T
T
1
Using the trigonometric identity sin 2 t (1 cos(2t ))
2

The effective value, called the rms (root mean squared) value, is obtained as

I eff

I m2 T
Im

(1

cos(2

t
))

2T 0
2

(10)

Indian Institute of Technology Guwahati

Instantaneous Power
Let v(t) and i(t) be the instantaneous voltage and instantaneous current

across a network given by


v(t ) Vm sin(t )
(11)
i (t ) I m sin(t q )
(12)
The expression for instantaneous power is given by
p(t ) v(t )i(t ) Vm I m sin(t )sin(t q )
(13)
Using, sin( t q ) sin( t ) cosq cos t sin q ,
1
1
sin 2 t (1 cos 2t ), and sin( t ) cos t sin( 2t )
2
2

p (t )

Vm I m sin 2 (t ) cos q sin(t ) cos(t )sin q

Vm I m
V I
cos q m m cos(2t q )
2
2

(14)

It can be seen that for a given value of angle q the instantaneous power

consists of two components; a constant part and a time varying part.


The time varying part has a frequency which is twice that of the voltage
and current sinusoids.
Indian Institute of Technology Guwahati

Instantaneous Power
Vm I m
2

Vm I m
cos(q )
2

Fig. 6:

The shaded part of the power in Fig.6 refers to those time intervals when the
power is negative. The negative power in effect means that the circuit is
returning power to the source during these intervals.
It should be noted from Form Fig.6 that the time varying component
oscillates about the constant power axis, which gives the average power.

Indian Institute of Technology Guwahati

Instantaneous Power

As the angle q is made smaller and smaller, i.e. as the current I is brought

nearly in phase to the voltage v, the negative area gets smaller and smaller.
As q =0, the current and voltage are in phase, there is no negative area

associated with p(t) curve and all the power in consumed between the circuit
branch terminals. This circuit is purely resistive.
When q is increased, the negative area increases and less power is consumed

by the circuit and more returned to the source.


At the extreme value of q,

Vm I m
2

i.e. q=/2, the p(t) curve is


such that the negative area

Vm I m
cos(q )
2

is equal to the positive area.

In this case no power is


consumed between the
circuit terminals.

Fig. 6:

Indian Institute of Technology Guwahati

Average Power
The useful quantity in terms of the capability of the circuit to do work is the

average power.
The average power is given by
TV I
1 T Vm I m

Pav
cos q dt m m cos(2t q )dt
0
T 0 2
2

(15)

The second term in eq.15 involves the integration of a sine function over a

time interval of two period, hence its value is equal to zero.


The first term is independent of time t, the average power is obtained as
V I
Pav m m cos q
(16)
2
More commonly, the average power is written as:
Pav

Vm I m
cos q Veff I eff cos q
2 2

Indian Institute of Technology Guwahati

(17)

10

Power Factor
While the product of V and I (VI) gives power in dc circuits It should be

noted that this product (VI) does not give the average power when
sinusoidal voltages and currents are involved. In ac circuits, the product
(VI) is called the apparent power or Volt Amperes.
In ac circuits, Pav Vm I m cosq Vm I m cos q VI cos q
2

2 2

(18)

The product of V and I, or the apparent power must be multiplied by the

factor (cosq) to obtain the average power.


This important factor
P
Average Power
cosq av
VI
Volt Amps or Apparent Power

(19)

is called the power factor.


so that, Average Power = Apparent Power power factor.

Indian Institute of Technology Guwahati

(20)

11

Phasor Representation
Consider two sinusoids, denoting two voltages corresponding to two
v1 V p1 sin(t )

phasors as shown.

v1 Im (V p1e jt )
V1 = (V p10)
v2 V p 2 sin(t )

Algebraic treatment

v2 Im (V p 2e j (t ) )
V2 (V p 2 )

of sinusoids are made simpler by phasor

representation, eg,
v1 v2

(V p10 V p 2 )
(V p1 cos0 V p 2 cos j (V p1 sin 0 V p 2 sin ))
(Vt t ) Vt sin(t t )

where

(21)

Vt (V p1 cos0 V p 2 cos ) 2 (V p1 sin 0 V p 2 sin ) 2 , and,

t tan

(V p1 sin 0 V p 2 sin )
(V p1 cos0 V p 2 cos )

Indian Institute of Technology Guwahati

(22)
12

Phasor Addition - Example

v1 Vm sin( t )

V1 (Vm0)

v2 Vm sin( t 90)

V2 Vm90

Direction
of
rotation

Vm
V2

V3 2Vm45
V1

Vm

Figure 8b

Figure 8a

V3 V1 V2 Vm0 Vm90 2Vm45

v3 2Vm sin( t 45)

Commonly, the phasors use rms values for magnitude in frequency domain
(rather than the peak values) which are more convenient in circuit analysis.
Lower case letters like v or i are used to indicate instantaneous values
Normal letters like V or V or V are used to indicate vectors or phasors
Italic letters like V or I are used to indicate magnitudes of vectors and phasors.
Indian Institute of Technology Guwahati

13

Representation of Circuit Parameters in Frequency Domain


ie, I I q
If a current i I m sin(t q )
is made to flow through a resistor R, the voltage across R is:
vR i R RI m sin( t q ) VR RI q
Therefore, ZR = R
(23)
ie, I I q
If a current i I m sin(t q )
is made to flow through an inductor L,
di
the voltage across L is: vL L LI m cos(t q ) LI m sin(t q 90)

dt
VL LI (90 q ) j LI

Therefore, ZL = jL

(24)

If a voltage v Vm sin(t q )

ie,

V V q

is applied across a capacitor C,


dv
the current through C is: iC C CVm cos(t q ) CVm sin(t q 90)

Therefore,

ZC

dt
IC CV (90 q ) jCV

1
1
j
jC
C

(25)

Indian Institute of Technology Guwahati

14

RL Circuit Steady State Analysis (Revisit)


Consider the RL circuit

Let the input voltage be:


v Vm sin( t )

V V0 ref .

i(t)

v(t)

V Vm / 2
Impedance of the circuit is formed as:
Z
jX
Z R L Zq
q
L
R
where, Z R 2 (L) 2 and, q tan 1
Impedance Diagram
R
This is commonly depicted in the impedance triangle as shown.
V V 0 V

q I q ,
Z Z q Z
VR IR IR q ,

Then, I

and

VL IX I q j L I L90 q

V
jIX

-q
I

IR
The relationships between various quantities are shown Vector Diagram
in a phasor/vector diagram.
The current can be written as: i I m sin(t q ), I m 2 (V / Z )
Indian Institute of Technology Guwahati

15

Example 1
Question:
A voltage v(t)=220 sin(t) Volts is applied to a series combination of a
resistance of 15 W, an inductive reactance 10 W and a capacitive
reactance of 5 W.
R
C
L
i. Find the current in the circuit
ii. Sketch the phasor diagram
i(t)
v(t)
Solution
The applied voltage is : V(t) = 220 sin (t)
The phasor representation of the voltage is:

220
0 155.560
2

Indian Institute of Technology Guwahati

16

Solution
The impedance of the circuit is

Z 15 j10 j5 15 j5 15.8118.43
The current in the circuit is

V
155.560

9
.
84

18
.
43
Z 15.8118.43

The instantaneous current in the circuit is

i(t ) 2 9.84 sin(t 18.43 pi 180) 13.92 sin(t 0.32)


The voltage across the resistor is

Indian Institute of Technology Guwahati

17

Solution - The Phasor Diagram


The voltage across the inductor is

VL 1090 I 1090 9.84 18.43 98.471.57

The voltage across the capacitor


VC 5 90 I 5 90 9.84 18.43 49.2 108.43

The resultant voltage is


V VR VL VC 155.560

Im

Direction of
rotation

VL

The current is

I 9.84 18.43

V (reference)
Re

q18.43o
VC

Indian Institute of Technology Guwahati

VL-VC
VR

18

Multiplication and Division of Complex Quantities


In dealing with the sinusoidal steady state response of electric circuits the

need frequently arises to multiply and divide complex numbers.


As an illustration consider the phasors I Ie jq and

Z Ze j . The

product of these two phasors is


IZ Ie jq Ze j IZe j (q ) IZ q

(26)

Hence, the product of two complex numbers is found by taking the product

of their magnitudes and the sum of their angles.


To illustrate the division of the complex numbers consider the phasors
V Ve jq and Z Ze j

The division of these two phasors is given by


V Ve jq V j (q ) V
I j e
q
(27)
Z Ze
Z
Z
The division of one complex number by another involves the division of
their magnitudes and difference in their phase angles.
Indian Institute of Technology Guwahati

19

Power and Roots of Complex Quantities


The nth power of the complex quantity Z Ze j is obtained as
n
j n
Z Ze
Z n e jn Z nn
(28)

The nth power of a complex number is a complex number whose magnitude

is the nth power ot the magnitude of the original complex number and
whose angle is n times as large as that of the original complex number.
To find the root of a complex number the exponent n is made a proper

fraction in eq. 40. The angle of the original complex number is increased
by 2k in order to determine all the roots that satisfy eq. 28.
Accordingly, the fourth power of Z Ze j is
1
1
1
k
Z 4 Ze j ( 2 k ) 4 Z 4
4 2

(29)

Then the four distinct roots are,


1
Z4

1
Z 4 4 ,

1
Z 4 4 2

1
Z 4 4 ,

1
Z 4 4 34

for k=1, 2, 3, and 4 respectively.


Indian Institute of Technology Guwahati

20

Complex Power
Consider the ac load shown in Fig. The voltage and current in the network

are:

v Vm sin(t )

(30)

i I m sin(t q )

(31)

The phasors in terms of rms values can be written as:


+
V
I
V m 0 V0, and
I m q I q
2
2
The complex power S absorbed by the ac load is defined as:

S V I* V 0 ( I q )* VI q
VI cos q jVI sin q S cos q jS sin q P jQ
The complex power may also be written as:
In terms of load impedance and V as:
*
V2
V VV *
S V I* V
2
Z*
Z*
Z
In terms of circuit parameters and I as:

(32)

(33)

S V I* IZ I* I 2Z I 2 (R jX ) I 2 R jI 2 X P jQ
Indian Institute of Technology Guwahati

Load
Z

(34)
21

Power Triangle
S
q

The complex power


S V I* V0 ( I q )* VIq
VI cos q jVI sin q S cos q jS sin q P jQ

jQ
P

Power Triangle

is commonly represented in the power triangle as shown.


where, S

= VI, is the apparent power,

= VI cos q is the real power

= VI sin q is the reactive power , and

cos q

= P/S is the power factor

It may be noted that the angle q in the power triangle, in the current, and
the power triangle is the same, except for the sign, when the voltage is
the reference.

Indian Institute of Technology Guwahati

22

3-Phase Systems

Dr. Govinda Bol Shrestha


Visiting Professor
Department of Electronics and Electrical Engineering

Indian Institute of Technology Guwahati

23

3-phase Systems- Introduction


A brief history.
Almost all electric power generation and transmission in the world
today is in the form of 3-phase
Most of the large industrial loads are also 3-phase
Small loads (such as residential loads) are 1-phase, but this is simply a
tap-off from a 3-phase system
A 3-phase system is an integration of three 1-phase systems
A 3-phase system consists of 3-phase generators, 3-phase transmission
lines and 3-phase loads
A 3-phase power system is preferred over a 1-phase power system for
the following reasons:
3-phase generators,

motors and transformers are simpler, cheaper

and more efficient


3-phase transmission lines deliver more power for a given cost or

for a given weight of conductor


Voltage regulation of a 3-phase system is inherently better
Indian Institute of Technology Guwahati

24

Generation of 3-phase Voltages and Currents


A 3-phase generator consists of three 1-phase generators
All three voltages are equal in magnitude but differing in phase angle from
others by 1200
Quantities of three phases (of a 3-phase system) are represented by using
subscripts a, b and c. They are called phase-a, phase-b and phase-c

Expression of Three Phase Voltages


Time domain

va (t ) 2V sin(t ) V
vb (t ) 2V sin(t 120) V
vc (t ) 2V sin(t 120) V

Phasor

Va V0 V

Vb V 120 V

Vc V120 V

Indian Institute of Technology Guwahati

25

Nature of 3-phase Voltages


Phasor diagram

Va

Va(t)

Vb(t)

Vc(t)

Vc
1200

Vb

1200

Va
1200

Vc

Vb

Three 1-ph generators

Voltage waveforms

Indian Institute of Technology Guwahati

26

Ia

Nature of 3-phase Currents


Each of these three generators can be
connected to one of the three identical
loads by a pair of wires.

Ib

The load impedance is considered as:


Z Zq W
Such a system is basically three 1-phase
circuits which happen to differ in phase
angle by 120

Z Zq

Va

Z Zq

Vb
Ic

Currents in the above circuits are:


Vc
Z Zq
Va V0 V
Ia
q I q
Z Zq Z
V V 120 V
Ib b
120 q I 120 q
Z
Zq
Z
V V 120 V
Ib c
120 q I120 q
Z
Zq
Z
All currents have the same magnitude (V/Z) but a phase shift of 120 from others
Indian Institute of Technology Guwahati

27

Integration of Three Generators


The above three 1-phase systems require six wires (two for each system)
In fact, three of the six wires are not necessary for the generators to supply
power to the loads
Consider that the three negative ends of the generators are joined together.

Similarly, the three lower ends of the loads are also joined together
Three return wires can now be replaced by a single wire called neutral wire.
Current can still return from the loads to the generators as shown in the
following figure
Ia

Such a system is called

3-phase, 4-wire system.


It consists of three
Va
phase wires and
a neutral wire

Ib
Ic

Vb

Vc
In

Generator
Indian Institute of Technology Guwahati

Load
28

4-wire and 3-wire Systems


Current in the neutral wire can
be written as (using KCL)

Ib

I(q 120) 0

Va

I n I a Ib Ic
I q I(q 120)

Ia

In

Vb

Vc

n
Z

Ic

As long as the three loads are


identical, the current in the

With a neutral line

neutral line is always zero


Ia

Thus, the neutral line can be


eliminated (as shown in the
following figure) and power can
still be transferred from the

generators to the loads


Such a system is called 3-phase,
3-wire system

Ib

Va

Vb

Vc

Ic

Without a neutral line


Indian Institute of Technology Guwahati

29

Balanced 3-phase Systems


A 3-phase source is called balanced if it consists of three voltages of equal
magnitude with phase shifts of exactly 1200 from others

Example:

Va V V

Vb V( 120) V

Vc V( 120) V

A 3-phase source is called unbalanced if the voltage magnitudes are not equal
and/or the phase shifts are not exactly 1200
A 3-phase load is called balanced if all three impedances are identical.
Identical means all impedances have the same magnitude and same angle
A 3-phase transmission system is called balanced if the impedances of all
three lines are identical
A 3-phase system is called balanced if the sources, transmission systems and
loads are balanced
In this subject, we will mainly concentrate on balanced 3-phase systems

Indian Institute of Technology Guwahati

30

Phase Sequence
There are two possibilities for the phase
sequence.

Vc

1200

(a) Phase sequence a-b-c

1200

In this case, a leads b, b leads c and c


leads a (in the sequence of a-b-c)
Va V0 V

Va

1200
Vb

Vb V 120 V
Vc V120 V

(b) Phase sequence a-c-b


In this case, leads , leads and leads
(in the sequence of a-c-b)
Va V0 V
Vc V 120 V

Vb

1200
1200

Va

1200
Vc

Vb V120 V
Indian Institute of Technology Guwahati

31

Connections of 3-phase Generators and Loads


A 3-phase generator or load may be connected in two ways
1. Star or Y (Wye) connection
In star or Y-connection, one end of each source (or load) is connected to a
common point called neutral point. In a balanced system, the voltage at the
neutral point is zero and sometimes it is connected to the ground
a

a
b

Va
n

Z
Z

Vb

Vc

Z
c

Y-Connected generator

Indian Institute of Technology Guwahati

Y-Connected load

32

Connections of 3-phase Generators and Loads


2. Mesh or (Delta) connection

In mesh or -connection, three sources (or loads) are connected in (or


closed form) as shown below. There is no neutral point in -connection
a

Va

Vc

b
b
Vb

-Connected generator

Z
c

-Connected load

Any number of Y and connected generators and loads may be mixed up in a


power system
Indian Institute of Technology Guwahati

33

General Representation of 3-phase Generators and Loads


3-phase
generator
( or Y)

a
b
c

a
b
c

3-phase
load
( or Y)

3-phase, 3-wire system


3-phase
generator
Y-conn.

a
b
c
n

a
b
c
n

3-phase
load
Y-conn.

3-phase, 4-wire system


In -connection, there is no neutral point and thus it is always 3-phase, 3-wire.
However, a Y-connected system can be 3-phase, 3-wire or 3-phase, 4-wire

Indian Institute of Technology Guwahati

34

Phase and Line Quantities


In both Y- and -connection
Voltage of each source or across each load impedance (inside the dotted

box) is called phase voltage


Current of each source or through each load impedance (inside the

dotted box) is called phase current


Voltage between any two lines (outside the dotted box) is called line

voltage. Exclude the neutral wire (if any)


Current through any line (outside the dotted box) is called line current.

Exclude the neutral wire (if any)


IA

Ia

IB

Va

Vab

Vb

Vbc

Vc
Ic

Vca

IB

Vb

c
Indian Institute of Technology Guwahati

Vab

Va

Ic

IC

Ia

Vc

Ib

IA

Ib

Vca

I C Vbc

35

Phase and Line Quantities


I
A

Ia

IB

Va

Vab

Vb

Vbc

Vc
Ic

Vca

IB

Vb

Vab

Va

Ic

IC

Ia

Vc

Ib

IA

Ib

Vca

I C Vbc

In the Above Diagrams


Va, Vb, and Vc are phase voltages and Vab, Vbc, and Vca are line voltages
Ia, Ib, and Ic are phase currents and IA, IB, and IC are line currents
Phase quantities are inside the dotted box (which may not be accessible) and line
quantities are outside the dotted box (which are always available)
By Inspection
For Y-connection
Line current = phase current
Line voltage phase voltage
For -connection
Line voltage = phase voltage
Line current phase current
Indian Institute of Technology Guwahati

36

Relationship between VL and Vp of Y-connection


Let the phase voltages be (for phase sequence a-b-c) be:

Va V0,

Vb V 120,

Vc V120

Then, the line voltages are:

Vab Va Vb V0 V 120 3V30


Vbc Vb Vc V 120 V120 3V 90
Vca Vc Va V120 V0 3V150
The above voltages are shown in the following phasor diagrams
Vc

Vca

Vb

Vab

Vc

Vca
Va

Va

Vbc

Va

Vc

Vb

Vab
Vbc

Vb

Magnitude of line voltage = 3magnitude of phase voltage, and the line

voltages are shifted by 30 from the phase voltages.


Indian Institute of Technology Guwahati

37

Relationship between IL and Ip of -connection


Let the phase currents (for phase sequence a-b-c) be:

I a I0,

Ib I 120,

I c I120

Then, the line currents (using KCL) are:


I A I a I c I0 I120 3I 30
I B Ib I a I 120 I0 3I 150

IC I c Ib I120 I 120 3I90


The above currents are shown in the following phasor diagrams
IC
Ic
IA
Ib

Ic

IC

Ia

IB

Ia

Ia

Ib

Ic

IA

Ib

IB

Magnitude of line current = 3magnitude of phase current, and the line


currents are shifted by 30 from the phase currents.
Indian Institute of Technology Guwahati

38

Analysis of a Balanced 3-phase Y-Y System


Consider a 3-phase Y-connected generator
supplying power to a 3-phase Y-connected load
as shown in the figure.
Let,Va V V V
, b V( 120) V ,

Vc V( 120) V

, and

Z Zq

Add a fictitious neutral line between the


generator neutral point and the load neutral
point as shown in the following. Note that

addition of the neutral line has no effect


because it does not carry any current (under
balanced condition).
Thus, the 3-phase circuit can be analyzed as
three single-phase circuits, each consisting of
one phase and the neutral line as shown.

Indian Institute of Technology Guwahati

39

Analysis of YY system: Single Phase Equivalent Circuit


All three phases are identical except for a phase shift of 120 in the voltages.
Therefore, the results of all the phases will be the same, except for the proper
phase shift of 120.
For example, for phase a, I a V0 V q
Zq Z

And complex power of phase a is:


Sa V I a * Va I a q

Then, it can be easily seen that:


Ib

V
q 120,
Z

Ic

V
q 120
Z

And, Sb Sc Sa V I a * Va I a q
The complex power of all three phases: S3 ph 3V ph I phq
Thus one phase of the 3-phase Y-Y system adequately describes all three phases,

and it is called the Single Phase Equivalent Circuit of the 3-phase system.

Indian Institute of Technology Guwahati

40

3-Phase Conventions
In practice, the three phase supply comes from a large

number of 3-phase sources, many could be in Star


configuration and many in Delta.

a
b
VL volt
3-phase
source

Therefore 3-phase sources are commonly shown and


specified as depicted in the figure.

n
c

The source may be represented as a Star or a Delta as needed.


a

a
b
VL volt
3-phase
source

Va VL / 30

Vca VL120

b
Vb VL / 3 120

n
c

Vc VL / 3120

Vab VL0

OR

Indian Institute of Technology Guwahati

b
Vbc VL 120

41

3-Phase Conventions
Unless specified otherwise, the following convention is understood in 3phase systems:

Voltage of a 3-phase system is always specified as line voltage (only


magnitude or rms value)

Current of a 3-phase system is always specified as line current (only


magnitude or rms value)

Power (P, Q or S) of a 3-phase system is always specified as total power

However, the impedance of a 3-phase system can always specified as


phase impedance.

Indian Institute of Technology Guwahati

42

Example
A 415 V, 3-phase source supplies power to a balanced 3-phase Y-connected
load having an impedance of (16+j12) W per phase. Determine the current
and complex power absorbed by the load.
Solution

Since the load is in Y, it would be proper


to represent the source in Y also.
Here VL = 415 V
V
415
239.6 V/phase
Vp L
3

b
VL
3-phase
source

Va 239.60

11.98 36.87 A
Z (16 j12)
And, Sa Va I a* 239.60 11.9836.87
2870.436.87 (2296.3 j1722.2) VA

S p 2870.436.87

Ia

Ia

Ip = 11.98 A

n
c

Consider Va as the reference


Va 239.60 V

Finally,

Va

IL = Ip = 11.98 A, and

VA

ST 3S p VA

Indian Institute of Technology Guwahati

43

Example
A 415 V, 3-phase source supplies power to a balanced 3-phase -connected

load having an impedance of (16+j12) W per phase. Determine the current and
complex power absorbed by the load.
Solution
a
Vca
Z
Z
V
Since the load is in , it is possible
ab
VL
Vbc
to represent the source in also,
3-phase
b
and directly find the phase currents.
source
Z
c

Here VL = 415 V
V p VL 415

V /phase

Consider Vab as the reference


V
Vab 4150 V I ab ab
Z

Vca

Vab
Vbc

b
c

However, if you like to find the line current Ia,

I ab

Then, it should be noted that


I a I ab I ac I ab I ca

Indian Institute of Technology Guwahati

Vab

44

Example
A 415 V, 3-phase source supplies power to a balanced 3-phase -connected
load having an impedance of (16+j12) W per phase. Determine the current

and complex power absorbed by the load.


Consider that the line connecting the source to the load has an impedance
of j0.5 W per phase
j0.5 W

Solution

Vca

In the presence of tr. line


impedance, the Configuration
is not easy to analyze.

Vab
Vbc

j0.5 W
Z

c
j0.5 W

So, conversion to Y-Y system is preferable.


The general approach is to adopt the Y-Y configuration converting all s to
Y whenever required.

Indian Institute of Technology Guwahati

45

Delta Star Conversion for Balanced Systems


The equivalence between star and delta connected networks were shown to
be:
Z2 Z3
ZZ
Z Z
Z 23 Z 2 Z 3
Z1

Z1

Z31 Z 3 Z1

Z12 Z13
,
Z12 Z13 Z 23

Z2

Z2

Z12 Z1 Z 2

Z 21Z 23
,
Z12 Z13 Z 23

1
2

3 1

Z3

1 2

Z3

Z 31Z 32
Z12 Z13 Z 23

ZY

ZY

ZY

If the networks are balanced, it can be easily observed that,

Z 3ZY

and,

ZY

Indian Institute of Technology Guwahati

Z
3
46

Analysis of a Balanced 3-phase System


The general approach to solve balanced 3-phase systems is outlined below:
Convert
3-ph system to
Y-Y
configuration

Draw the
1-ph equivalent
circuit

Solve the
1-ph equivalent
circuit

Get the
3-ph results

Convert the system to Y-Y configuration converting all s to Y whenever


required.
Obtain the phase quantities to construct the 1-phase equivalent circuit
The balanced 3-phase system can be analyzed from its single-phase
equivalent circuit
At the end, results of the 3-phase system can be obtained from the results
of the 1-phase equivalent circuit using the standard relationships

Indian Institute of Technology Guwahati

47

Example
The general approach to solve balanced 3-phase systems is outlined below
using the system shown.:
Ztr
a

VL
3-phase
source

Z2
Ztr
Ztr

Z1

Z1

Z1

Z2

Z2

Represent the source in Y, and get the reference phase voltage.


The transmission line impedances are already in Y configuration
The load impedance Z1 is already in Y configuration.
Convert the load impedance Z2 to Y configuration (Z2Y = Z2/3)

Given: VL=433 V, Ztr= j0.1 W, Z1=1.4+j4.6 W, and Z2=4.2+j13.8 W


Find the current output of the source,
The phase currents in load 1, and load 2
And, find whatever you want, say pf and power output of source, etc.
Ans: 100 A, 100 A, 57.7 A, etc.
Indian Institute of Technology Guwahati

48

Power Measurement
For sinusoidal voltage and current, the average power is:

P = VIcos W
where V and I are the rms values of voltage and current,
respectively, and is the angle between voltage and current
Thus, a wattmeter needs the information of voltage magnitude, current
magnitude and the angle between the voltage and current
I
A wattmeter can be considered as an integration
CC
of a voltmeter and an ammeter with special calibration
It should have two measuring coils
VC
Voltage coil (VC) to measure voltage
V
Current coil (CC) to measure current
VC and CC of a wattmeter must be connected with correct polarities
Connect the terminal of the CC towards the source
Connect the terminal of the VC to the line containing the current coil
Indian Institute of Technology Guwahati

49

Example
In the following circuit, determine the reading of the voltmeter, ammeter
0.5W
j1.5W
and wattmeter.
A
Here 25 W resistor and j30 W
CC
25W
inductor are in parallel.
VC
240V
Equivalent impedance
V
j30W
of the parallel combination
is:
Z eq R // jX L

25 j 30
(14.75 j12.3) W
25 j 30

Total impedance isZT (0.5 j1.5) (14.75 j12.3) 20.5642.14 W

2400
11.67 42.14 A
ZT 20.5642.14
Voltage across the equivalent impedance is V I Z eq 224.13 2.3 V
Therefore, Voltmeter reading = 224.13 V
Ammeter reading = 11.67 A
Wattmeter reading = 224.1311.67cos(-2.30+42.140)= 2008.4 W
The current in the circuit is I V

Indian Institute of Technology Guwahati

50

Power Measurement in 3-phase Systems


Total power in a 3- system is the sum of three phase powers (for both

balanced and unbalanced systems)


PT = (Pa + Pb + Pc) W = (VaIacosa + VbIbcosb + VcIccosc) W
Three-wattmeter Method - One possible way of measuring the total

power in a 3- system is by using three wattmeters (one for each


phase), connected as shown in the following figure.
Total power is the sum of three wattmeter readings and is valid for both

balanced and
unbalanced
conditions

a
Wa

CC
VC

b
Va

CC

Vb
Vc

Wb

VC

n
Z

VC
CC

Wc

Indian Institute of Technology Guwahati

51

Balanced System
Pa = Pb = Pc and thus the total power is 3phase power
For such a case, power of only one of the phases measured by using a

single wattmeter may be sufficient.


To get the total power, multiply the wattmeter reading by 3 (because
the system is balanced)
This is called one-wattmeter method
Limitations
Three-wattmeter (or one-wattmeter) method uses phase voltages and
currents to measure the phase powers. However, the phase voltages and
phase currents are not always accessible
A better way of measuring the 3-phase power is by using the line
quantities (line voltages and line currents) instead of phase quantities
Line quantities are always available at the source or load terminals
Indian Institute of Technology Guwahati

52

Blondels Theorem

The minimum number of (single-phase) wattmeters needed to

measure the total power of a poly-phase system is one less than the
number of wires in the system
For a 3-, 3-wire system: 2 wattmeters are needed
For a 3-, 4-wire system: 3 wattmeters are needed

Indian Institute of Technology Guwahati

53

Two-wattmeter Method
It is very commonly used to measure the total power of a 3-, 3-wire

system
The reading of an individual wattmeter may not have any meaning but

the sum of two readings is always the total power of a 3- system (if the
wattmeters are connected properly)
The method is valid for both balanced and unbalanced systems as well

as for both and Y systems

W1

a
CC

One possible way of connecting

two wattmeters to measure


the total power is shown below

3-
3-wire
source

VC

b
CC

W2

3-
3-wire
load

VC

Indian Institute of Technology Guwahati

54

Two-wattmeter Method
Let P1 and P2 be the readings of the

wattmeters W1 and W2, respectively


According to the connection,
the readings
of the wattmeters are
T
P1 1 vac (t )ia (t )dt W,
T 0T
P2 1 vbc (t )ib (t )dt W
T0

W1

a
CC

3-
3-wire
source

VC

b
CC

W2

3-
3-wire
load

VC

It can be shown that, (P1 + P2) is the total power of the 3-phase system
T
1T
1T
P1 P2 vac (t )ia (t )dt vbc (t )ib (t )dt 1 (va vc )ia dt 1 (vb vc )ib dt
T0
T0
T0
T
T
1
T
[va ia vbib vc (ia ib )]dt 1 [v i v i v i ]dt [(i + i ) = -i ]
a a
b b
c c
a
b
c
T0
T0
( Pa Pb Pc )
That is, (P1 + P2) ( Pa Pb Pc ) = total 3-phase power
Indian Institute of Technology Guwahati

55

Two-wattmeter Method
The above derivations requires no assumption on
Phase sequence (a-b-c or a-c-b)
Waveforms of the voltage and current (sinusoidal or non-sinusoidal)
The nature of the load (balanced or unbalanced)
Example:

3-
source

b
A balanced 3-phase, 400 V, Y-connected
load has a phase impedance of
W2
c
(10+j8) W/phase. Two wattmeters are
used to measure the total power of the
load and their connections are as shown in the figure.

W1
CC
VC

3-
Y-con.
load

CC
VC

Determine the reading of each wattmeter if the phase sequence is a-b-c.

Indian Institute of Technology Guwahati

56

and

Solution
VL = 400 V, Vp = 230.9 V
Consider Va as reference Va 230.90 V
Vab 40030 V

Vbc 400 90 V
Vca 400150 V Vac 400 30 V
Current of phase a (as well as line a) is
V
I a a 230.90 18.03 38.66 A,
Z L (10 j8)

W1
CC

3-
source b

VC
CC

W2

3-
Y-con.
load

VC

I c 18.0381.34 A
Therefore, Ib 18.03 158.66 A,
and,
Wattmeter readings are
P1 Vac I a cos q V , I 400 18.03 cos(30 38.66 ) 7.13 kW

P2 Vbc I b cos q V

ac

bc , I b

Total power
Also

400 18.03 cos(90 158.66 ) 2.62 kW

PT = (P1 + P2)
PT = 3Ia2RL

= (7.13 + 2.62)
= 318.03210

Indian Institute of Technology Guwahati

= 9.75 kW
= 9.75 kW (checked)
57

Balanced 3 Phase System


Total reactive power QT as well as power factor (cos) can also be

determined from the two wattmeter readings


Consider Va as reference and is lagging power factor angle
Under this case (for phase sequence a-b-c), all voltages and currents
for Y-connected system are
Va Vp 0 ,

Vb Vp 120 ,

I a I L ,

Ib I L 120 , I c I L 120

Vab VL 30 ,

Vba VL 150

Vc Vp 120

Vbc VL 90 , Vcb VL 90

Vca VL 150 ,

Vac VL 30

Indian Institute of Technology Guwahati

58

Balanced 3 Phase System


the wattmeter readings can be written as

P1 Vac I a cos q V

ac , I a

P2 Vbc Ib cos q V

bc , Ib

VL I L cos(30 )

VL I L cos(30 )

VL I L cos(90 120 ) VL I L cos(30 )

Note that: cos(30 ) cos30 cos sin 30 sin

3
2

cos 12 sin

cos(30 ) cos30 cos sin 30 sin

3
2

cos 12 sin

Then: ( P1 P2 ) VL I L [cos(30 ) cos(30 )]

VL I L [ 3 cos ] 3VL I L cos

( P1 P2 ) VL I L [cos(30 ) cos(30 )] VL I L sin

3( P1 P2 ) 3VL I L sin
Therefore,

Total real power


Total reactive power

= P1+P2,
= 3( P1 P2 )

Indian Institute of Technology Guwahati

and,

59

Other possible connections of the two-wattmeter method


a

The general procedure is to

connect two wattmetters in


any two of the three lines and
the third line should be common
for the voltage coil of both
wattmeters.

3-
3-wire
source

VC

W1

CC

3-
3-wire
load

VC
CC

W2
W2

a
CC
VC

3-
3-wire
source

3-
3-wire
load

VC
CC

Indian Institute of Technology Guwahati

W1
60

Thanks !

Indian Institute of Technology Guwahati

61

S-ar putea să vă placă și