DESIGNATION

NO.
FROM

TO

MSB to MCC
1
2
3
4
5
6
7

MSB
MSB
MSB
MSB
MSB
MSB
MSB

Power
Power
Power
Power
Power
Power
Power

House
House
House
House
House
House
House

MCC-1
MCC-2
MCC-3
MCC-4
MCC-5
MCC-6
M Boiler

Cable Number

Load
type

Installation
type

TO
Oil Unloading Pump
Oil Dispatch Pump
Boiler WTP
Sheel Receiving
Kernel Receiving
Kernel Shiping
Boiler MCP

P-MCC-1
P-MCC-2
P-MCC-3
P-MCC-4
P-MCC-5
P-MCC-6
P-M Boiler

F
F
F
F
F
F
F

UG
UG
UG
UG
UG
UG
UG

LF

kW

(pu)

45
105
11
8.1
26
36
74

0.75
0.78
0.8
0.82
0.85
0.8
0.75

Absord
Load
kW
33.75
81.9
8.8
6.642
22.1
28.8
55.5

P.F
cos

0.85
0.85
0.85
0.85
0.85
0.85
0.85

Eff.

Ib

volt

1.00
1.00
1.00
1.00
1.00
1.00
1.00

380
380
380
380
380
380
380

60.3
146.4
15.7
11.9
39.5
51.5
99.2

MF

1.15
1.15
1.15
1.15
1.15
1.15
1.15

Design
Current

Cable Length
Length

Total
Length

mtr

mtr

69.4
168.4
18.1
13.7
45.4
59.2
114.1

80
80
110
50
50
120
120

80
80
110
50
50
120
120

CABLE DATA
S

VAR

sqmm
4C x 35
4C x 95
4C x 10
4C x 6
4C x 10
4C x 35
4C x 70

8
11
5
4
5
8
10

1
1
1
1
1
1
1

No.

CCC

Rac (70 C)

X (70 C)

of Core

/ km

/ km

4
4
4
4
4
4
4

157
257
79
59
79
157
215

0.627
0.232
2.19
3.685
2.19
0.627
0.321

0.077
0.075
0.084
0.090
0.084
0.077
0.075

CF

0.76
0.76
0.76
0.76
0.76
0.76
0.76

Voltage Drop

Lmax S.State

Allowable Vd

Vd

mtr

S.State %

S.State %

119.3
195.3
60.0
44.8
60.0
119.3
163.4

127
127
146
116
58
149
142

2
2
2
2
2
2
2

1.26
1.26
1.50
0.86
1.72
1.62
1.69

Selected cable

1 x (4C x 35)
1 x (4C x 95)
1 x (4C x 10)
1 x (4C x 6)
1 x (4C x 10)
1 x (4C x 35)
1 x (4C x 70)

Remarks

Rev.

NYY; 0.6/1 kV ; 1 Core


Cu/PVC insulated/PVC Sheathed - IEC 60502-1
Cross
Section
mm2

No.

1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20

Cu/PVC/PVC (0.6/1 kV)


Cu/PVC/PVC (0.6/1 kV)
Cu/PVC/PVC (0.6/1 kV)
Cu/PVC/PVC (0.6/1 kV)
Cu/PVC/PVC (0.6/1 kV)
Cu/PVC/PVC (0.6/1 kV)
Cu/PVC/PVC (0.6/1 kV)
Cu/PVC/PVC (0.6/1 kV)
Cu/PVC/PVC (0.6/1 kV)
Cu/PVC/PVC (0.6/1 kV)
Cu/PVC/PVC (0.6/1 kV)
Cu/PVC/PVC (0.6/1 kV)
Cu/PVC/PVC (0.6/1 kV)
Cu/PVC/PVC (0.6/1 kV)
Cu/PVC/PVC (0.6/1 kV)
Cu/PVC/PVC (0.6/1 kV)
Cu/PVC/PVC (0.6/1 kV)
Cu/PVC/PVC (0.6/1 kV)
Cu/PVC/PVC (0.6/1 kV)
Cu/PVC/PVC (0.6/1 kV)

1C x 1.5
1C x 2.5
1C x 4
1C x 6
1C x 10
1C x 16
1C x 25
1C x 35
1C x 50
1C x 70
1C x 95
1C x 120
1C x 150
1C x 185
1C x 240
1C x 300
1C x 400
1C x 500
1C x 630
1C x 800

NYY; 0.6/1 kV ; 2 Core


Cu/PVC insulated/PVC Sheathed - IEC 60502-1
Cross
Section
mm2

No.

1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16

Cu/PVC/PVC (0.6/1 kV)


Cu/PVC/PVC (0.6/1 kV)
Cu/PVC/PVC (0.6/1 kV)
Cu/PVC/PVC (0.6/1 kV)
Cu/PVC/PVC (0.6/1 kV)
Cu/PVC/PVC (0.6/1 kV)
Cu/PVC/PVC (0.6/1 kV)
Cu/PVC/PVC (0.6/1 kV)
Cu/PVC/PVC (0.6/1 kV)
Cu/PVC/PVC (0.6/1 kV)
Cu/PVC/PVC (0.6/1 kV)
Cu/PVC/PVC (0.6/1 kV)
Cu/PVC/PVC (0.6/1 kV)
Cu/PVC/PVC (0.6/1 kV)
Cu/PVC/PVC (0.6/1 kV)
Cu/PVC/PVC (0.6/1 kV)

NYY; 0.6/1 kV ; 3 Core


Cu/PVC insulated/PVC Sheathed - IEC 60502-1

2C x 1.5
2C x 2.5
2C x 4
2C x 6
2C x 10
2C x 16
2C x 25
2C x 35
2C x 50
2C x 70
2C x 95
2C x 120
2C x 150
2C x 185
2C x 240
2C x 300

Cross
Section
mm2

No.

1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16

Cu/PVC/PVC (0.6/1 kV)


Cu/PVC/PVC (0.6/1 kV)
Cu/PVC/PVC (0.6/1 kV)
Cu/PVC/PVC (0.6/1 kV)
Cu/PVC/PVC (0.6/1 kV)
Cu/PVC/PVC (0.6/1 kV)
Cu/PVC/PVC (0.6/1 kV)
Cu/PVC/PVC (0.6/1 kV)
Cu/PVC/PVC (0.6/1 kV)
Cu/PVC/PVC (0.6/1 kV)
Cu/PVC/PVC (0.6/1 kV)
Cu/PVC/PVC (0.6/1 kV)
Cu/PVC/PVC (0.6/1 kV)
Cu/PVC/PVC (0.6/1 kV)
Cu/PVC/PVC (0.6/1 kV)
Cu/PVC/PVC (0.6/1 kV)

3C x 1.5
3C x 2.5
3C x 4
3C x 6
3C x 10
3C x 16
3C x 25
3C x 35
3C x 50
3C x 70
3C x 95
3C x 120
3C x 150
3C x 185
3C x 240
3C x 300

NYY; 0.6/1 kV ; 4 Core


Cu/PVC insulated/PVC Sheathed - IEC 60502-1
Cross
Section
mm2

No.

1
2
3
4
5
6
7
8
9
10
11
12

Cu/PVC/PVC (0.6/1 kV)


Cu/PVC/PVC (0.6/1 kV)
Cu/PVC/PVC (0.6/1 kV)
Cu/PVC/PVC (0.6/1 kV)
Cu/PVC/PVC (0.6/1 kV)
Cu/PVC/PVC (0.6/1 kV)
Cu/PVC/PVC (0.6/1 kV)
Cu/PVC/PVC (0.6/1 kV)
Cu/PVC/PVC (0.6/1 kV)
Cu/PVC/PVC (0.6/1 kV)
Cu/PVC/PVC (0.6/1 kV)
Cu/PVC/PVC (0.6/1 kV)

4C x 1.5
4C x 2.5
4C x 4
4C x 6
4C x 10
4C x 16
4C x 25
4C x 35
4C x 50
4C x 70
4C x 95
4C x 120

13
14
15
16

Cu/PVC/PVC (0.6/1 kV)


Cu/PVC/PVC (0.6/1 kV)
Cu/PVC/PVC (0.6/1 kV)
Cu/PVC/PVC (0.6/1 kV)

4C x 150
4C x 185
4C x 240
4C x 300

DC
Resistance
at 20oC
(ohm/km)

AC
Resistance
at 70oC
(ohm/km)

Inductance
Flat Formation

Reactance
at 50 Hz

Rated Current
at 30o C

in air
(mH/km)

(ohm/km)

Flat formation
(Ampere)

12.100
7.410
4.610
3.080
1.830
1.150
0.727
0.524
0.387
0.268
0.193
0.153
0.124
0.099
0.075
0.060

14.478
8.866
5.516
3.685
2.190
1.376
0.870
0.627
0.464
0.321
0.232
0.184
0.150
0.121
0.093
0.075

0.505
0.470
0.450
0.426
0.396
0.374
0.358
0.345
0.336
0.326
0.321
0.315
0.313
0.310
0.307
0.305
0.302
0.299
0.293
0.289

0.159
0.148
0.141
0.134
0.124
0.117
0.112
0.108
0.106
0.102
0.101
0.099
0.098
0.097
0.096
0.096
0.095
0.094
0.092
0.091

21
28
38
48
65
87
117
144
177
225
278
325
373
433
518
598
695
806
930
1052

Reactance
at 50 Hz

Rated Current

DC
Resistance
at 20oC
(ohm/km)

AC
Resistance
at 90oC
(ohm/km)

Reactance
at 50 Hz
(mH/km)

(ohm/km)

(Ampere)

12.100
7.410
4.610
3.080
1.830
1.150
0.727
0.524
0.387
0.268
0.193
0.153
0.124
0.099
0.075
0.060

14.478
8.866
5.516
3.685
2.190
1.376
0.870
0.627
0.464
0.321
0.232
0.184
0.150
0.121
0.093
0.075

0.328
0.304
0.303
0.288
0.269
0.255
0.255
0.246
0.247
0.238
0.238
0.233
0.233
0.233
0.232
0.231

0.103
0.095
0.095
0.090
0.084
0.080
0.080
0.077
0.078
0.075
0.075
0.073
0.073
0.073
0.073
0.073

23
30
40
51
70
93
123
151
182
230
280
325
371
424
501
572

at 30o C

in air

Reactance
at 50 Hz

Rated Current

DC
Resistance
at 20oC
(ohm/km)

AC
Resistance
at 70oC
(ohm/km)

Reactance
at 50 Hz
(mH/km)

(ohm/km)

(Ampere)

12.100
7.410
4.610
3.080
1.830
1.150
0.727
0.524
0.387
0.268
0.193
0.153
0.124
0.099
0.075
0.060

14.478
8.866
5.516
3.685
2.190
1.376
0.870
0.627
0.464
0.321
0.232
0.184
0.150
0.121
0.093
0.075

0.328
0.304
0.303
0.288
0.269
0.255
0.255
0.246
0.247
0.238
0.238
0.233
0.233
0.233
0.232
0.231

0.103
0.095
0.095
0.090
0.084
0.080
0.080
0.077
0.078
0.075
0.075
0.073
0.073
0.073
0.073
0.073

19
26
34
44
60
79
105
129
162
203
250
289
330
381
451
517

DC
Resistance
at 20oC
(ohm/km)

AC
Resistance
at 70oC
(ohm/km)

Reactance
at 50 Hz

Reactance
at 50 Hz

Rated Current

(mH/km)

(ohm/km)

(Ampere)

12.100
7.410
4.610
3.080
1.830
1.150
0.727
0.524
0.387
0.268
0.193
0.153

14.478
8.866
5.516
3.685
2.190
1.376
0.870
0.627
0.464
0.321
0.232
0.184

0.328
0.304
0.303
0.288
0.269
0.255
0.255
0.246
0.247
0.238
0.238
0.233

0.103
0.095
0.095
0.090
0.084
0.080
0.080
0.077
0.078
0.075
0.075
0.073

22
29
39
50
68
90
121
149
173
215
266
308

at 30o C

in air

at 30o C

in air

0.124
0.099
0.075
0.060

0.150
0.121
0.093
0.075

0.233
0.233
0.232
0.231

0.073
0.073
0.073
0.073

357
405
482
552

10

Rated Current
at 30o C

Overall

in ground

Diameter

Flat formation
(Ampere)
27
35
45
57
76
97
125
150
178
218
260
296
331
374
432
486
549
618
692
762

6.1
6.6
7.6
8.1
9.1
10.10
11.9
13.0
15.0
16.9
19.1
21.0
23.0
25.5
29.0
32.0
35.5
39.5
44.0
48.5

Rated Current
at 30o C

Overall

in ground

Diameter

(Ampere)

(mm)

27
36
47
59
80
104
134
162
191
236
281
321
361
406
470
528

12.50
13.40
15.40
16.50
18.40
20.50
24.00
26.00
29.50
33.00
37.50
41.00
45.00
50.00
56.00
62.00

Rated Current
at 30o C

Overall

in ground

Diameter

(Ampere)

(mm)

23
31
40
50
68
88
114
137
168
206
247
281
315
356
412
464

13.00
14.00
16.10
17.30
19.40
22.00
25.00
27.50
30.00
34.00
38.50
41.50
46.00
50.50
57.00
62.50

Rated Current
at 30o C

Overall

in ground

Diameter

(Ampere)

(mm)

27
35
46
57
77
99
128
154
173
212
255
289

13.80
15.00
17.30
18.70
21.50
23.50
27.50
30.00
35.50
39.00
44.50
48.50

327
366
425
479

54.50
59.00
66.00
72.50

Cable Gland Selection Data


Entry Thread Size
Metric
NPT
M16
"
M20
"/"
M25
1"/"
M32
1"/1"
M40
1"/1"
M50
2"-1"
M63
2"/2"
M75
3"/2"
M90
3"
M100
4"

* Refer Unibell

Min

Outer Shath
Max

8
12
16.5
23
32
43
55
67
86

14.7
23
26.2
34
45
56.5
68.5
80
100

11.35
18
21
29
39
50
62
74
93

Entry Thread Size


Metric
M16
M20
M25
M32
M40
M50
M63
M75
M90
M100

Entry Thread Size


NPT
"
"/"
1"/"
1"/1"
1"/1"
2"-1"
2"/2"
3"/2"
3"
4"

A. Underground Cable
A1. Rating Factor for Variation of ground temperature
Ground Temperature (C)

10

15

20

Rating

XLPE

1.15

1.12

1.08

Rating

PVC

1.22

1.17

1.12

0.7

1.5

A2. Rating Factor for Thermal Resistivity of soil


Thermal Resistivity of soil
Km/Watt)

Rating

XLPE

1.12

0.88

Rating

PVC

1.14

0.85

A3. Rating Factor for Variation of depth of laying in ground


Deep of Laying (m)

0.5

0.7

Rating

XLPE

1.02

0.98

Rating

PVC

1.01

0.99

A4. Rating Factor for Grouping of three-single core cables in three-phase system

Formation

Number of group
Rating
XLPE cables
Rating
PVC cables

Formation

1
1
1

2
0.87
0.87

3
0.77
0.77

Formation

Number of group
Rating
XLPE cables
Rating
PVC cables

1
1
1

2
0.85
0.85

3
0.75
0.75

1
1
1

2
0.89
0.90

3
0.82
0.82

Formation

Number of group
Rating
XLPE cables
Rating
PVC cables

A5. Rating Factor for Grouping multi core cables in three-phase system

Formation

Number of group
Rating
XLPE cables
Rating
PVC cables

1
1
1

For Low Voltage Cable

2
0.85
0.86

3
0.75
0.76

0.76

25

30

35

40

45

50

1.03

0.96

0.91

0.86

0.82

1.06

0.94

0.87

0.79

0.71

6
0.68
0.68

8
0.65
0.65

10
0.63
0.63

2.5
0.79
0.72

1.2

1.6

0.97

0.95

0.98

0.97

s in three-phase system

4
0.73
0.74

5
0.7
0.7

4
0.7
0.7

5
0.66
0.66

6
0.63
0.63

8
0.59
0.59

10
0.56
0.56

4
0.78
0.79

5
0.75
0.76

6
0.73
0.74

8
0.7
0.71

10
0.68
0.69

5
0.66
0.67

6
0.63
0.64

8
0.59
0.60

10
0.56
0.57

-phase system

4
0.7
0.71

B. Air Installation
B1.

Rating Factor for Variation in Air temperature


Air Temperature (C)

B2.

10

15

20

Rating

XLPE

1.15

1.12

1.08

Rating

PVC

1.22

1.17

1.12

Rating Factor for group in Air for Single-core cables in three-phase systems
Installed in one plane
Clearance = cable diameter
Arrangement of
Cables

Number of
cable trays or
cable racks

Distance from wall 2 cm


Number of group

On the Floor

On cable trays

0.92

0.89

0.88

1
2
3
6

0.92
0.87
0.84
0.82

0.89
0.84
0.82
0.8

0.88
0.83
0.81
0.79

On cable racks

1
2
3
6

0.92
0.87
0.84
0.82

0.89
0.84
0.82
0.8

0.88
0.83
0.81
0.79

On support or on
the wall

B3.

Rating Factor for group in Air for Multi-core cables in three-phase systems
Clearance = cable diameter
Arrangement of
Cables

On the Floor

Number of
cable trays or Distance from wall 2 cm
cable racks
Number of group
1
2
3

0.95

0.9

0.88

On the Floor

On cable trays

On cable racks

On the support or
on the wall

0.95

0.9

0.88

1
2
3
6

0.95
0.90
0.88
0.86

0.90
0.85
0.83
0.83

0.88
0.83
0.81
0.79

1
2
3
6

1.00
1.00
1.00
1.00

0.98
0.95
0.94
0.93

0.96
0.93
0.92
0.90

0.93

0.9

For Low Voltage Cable

0.810

25

30

35

40

45

50

1.04

0.96

0.91

0.87

0.82

1.06

0.94

0.87

0.79

0.71

in three-phase systems
Installed in bunches
Clearance = cable diameter
Distance from wall 2 cm
Number of group
1

0.95

0.9

0.95
0.9
0.88
0.86

0.90
0.85
0.83
0.81

1.00
1.00
1.00
1.00

n three-phase systems

meter

2 cm

ber of group
6

0.85

0.84

0.98
0.95
0.94
0.93

0.85

0.84

0.85
0.81
0.79
0.77

0.84
0.80
0.78
0.76

0.93
0.90
0.89
0.87

0.92
0.89
0.88
0.86

0.87

0.86

bunches

cable diameter

rom wall 2 cm

ber of group
3

0.88

0.88
0.83
0.81
0.79

0.96
0.93
0.92
0.90

Arrangement of
Cables

On the Floor

Number of Side by side without clearance and touching wall


cable trays
or cable
racks
Number of group
1
2
3

0.90

0.84

0.8

On the Floor

On cable trays

On cable trays

On the Floor

0.90

0.84

0.8

1
2
3
6

0.95
0.95
0.95
0.95

0.84
0.8
0.78
0.76

0.8
0.76
0.74
0.72

1
2
3
6

0.95
0.95
0.95
0.95

0.84
0.8
0.78
0.76

0.8
0.76
0.74
0.72

0.95

0.78

0.73

learance and touching wall

ber of group
6

0.75

0.73

0.75

0.73

0.75
0.71
0.7
0.68

0.73
0.69
0.68
0.66

0.75
0.71
0.7
0.68

0.73
0.69
0.68
0.66

0.68

0.66

CORRECTION FACTOR TABLE

Temperature Derating Factor for (30 C)


Above ground
Installation

Group Derating Factor


Derating factor
Temperature Derating Factor for (30 C)
Thermal Resistivity of soil 1 Km/Watt

Under ground
Installation

Rating Factor for Variation of Depth laying in the ground


(0.7 M)
Cable laying group derating factor (Multicore 3 Group)

Derating factor

1 1.5
2 2.5
34
46
5 10
6 16
7 25
8 35
9 50
10 70
11 95
12 120
13 150
14 185
15 240
16 300
17 400

18 500
19 630
20 800

LV cable
1
0.81

0.810
1
1

0.76

0.760

Basic Calculation