Documente Academic
Documente Profesional
Documente Cultură
A 41 a
CONFERIN NAIONAL DE INSTALAII
INSTALAII PENTRU
NCEPUTUL MILENIULUI TREI
Volumul
Instalaii electrice i automatizri
A 41 A CONFERIN NATIONALA DE
INSTALAII ELECTRICE I AUTOMATIZRI
SIEAR - 2006
SINAIA
19 21 OCTOMBRIE 2006
CUPRINS
1. Ing. Cornel CHIOREANU C&I ELCA IMPEX - CERINTE NOI IN FATA
PROIECTARII DE INSTALATII ELECTRICE SI DE AUTOMATIZARI...... 6
2. Ing.
Marius
MILOVICI
ISPE
SITUAIA
ACTIVITII
VERIFICATORILOR DE PROIECTE I EXPERILOR TEHNICI N
INSTALAII ELECTRICE Ie N ANUL 2006................................................ 9
3. Prof. dr. ing. Ion IORDNESCU U.P.B. - COMPENSAREA PUTERII
REACTIVE
N
CONDIIILE
EXISTENEI
CONSUMATORILOR
DEFORMANI....................................................................................................... 13
4. Conf. dr. ing. Clin CIUFUDEAN, Prof. dr. ing. Alexandru LARIONESCU Universitatea tefan cel Mare Suceava - CONSIDERAII ASUPRA
SISTEMELOR AUTOMATE NEENERGOFAGE............................................. 22
5. Sl. drd. ing. Mircea ROCA UTCB - DETERMINAREA COEFICIENILOR
FOURIER PENTRU O SERIE DE SEMNALE NESINUSOIDALE
PARTICULARE..................................................................................................... 27
6. Prof. univ. dr. ing. Ion IORDANESCU U.P.B. - IMM SI CONSUMUL DE
ENERGIE ELECTRICA IN PERSPECTIVA INTRARII IN UNIUNEA
EUROPEANA......................................................................................................... 37
7. As. drd. ing. Ionu HOMEAG IGSU - INTEGRAREA SISTEMELOR DE
DETECTARE I ALARMARE A INCENDIILOR NTR-UN SISTEM DE
GESTIUNE TEHNIC.......................................................................................... 42
8. Prof. dr. ing. Constantin IONESCU UTCB - METODE DE CALCUL PENTRU
IMBUNATATIREA EFICIENTEI ENERGETICE A CLADIRILOR PRIN
UTILIZAREA SISTEMELOR DE AUTOMATIZARE INTEGRATE............ 46
9. Prof. dr. ing. Sorin LARIONESCU UTCB - PROIECTAREA SISTEMELOR
DE CONDUCERE CU AUTOMATE PROGRAMABILE................................ 49
10. Prof. dr. ing. Nicolae GOLOVANOV, Prof. dr. ing. Petru POSTOLACHE, l. dr. ing.
Radu PORUMB U.P.B, Dr. ing. VASILE RMNICEANU TIAB, Prof. dr. ing.
Cornel TOADER U.P.B. - PUTERILE I RANDAMENTELE OPTIME N
REGIM NESIMETRIC SINUSOIDAL LA TRANSFORMATOARELE CU DOU
NFURRI ........................................................................................................................... 59
11. Conf. dr. ing. Clin CIUFUDEAN, Masterand ing. Daniel GAVRIL Universitatea
tefan cel Mare - SISTEM AUTOMAT PENTRU VERIFICAREA RELEELOR
DIN INSTALAIILE
DE
CENTRALIZARE
ELECTRODINAMIC
FEROVIAR SAR-CED........................................................................................ 67
12. Cerc. t. III ing. Alina COBZARU INCERC Filiala Iai - CERCETAREA
POLURII ELECTROMAGNETICE A MEDIULUI N DOMENIUL
LOCUINELOR I INSTALAIILOR PENTRU CONSTRUCII................ 75
13. Cerc. t. III ing. Alina COBZARU INCERC Filiala Iai - INSUFICIENE
PRIVIND APRECIEREA OBIECTIV A EFICIENEI NCLZIRII
ELECTRICE PRIN RADIAIE, FR A CONSIDERA I CMPUL
ELECTROMAGNETIC EMIS............................................................................. 90
SPECIALITILOR
VERIFICATORI
DE
UNOR
NOI
10
12
13
Pc
Pc2 + Qc2
Ps
Ps2 + Qs2
(1)
Ps
Ps2
+ Qc2 QB2
14
= cos s ,comp
(2)
Fig. 1
Pc
Pc2 + Qc2
Fig. 2
Fig. 3
(3)
Fig. 4
= I 2 + I 3 + ... + I n
(4)
=2
I , rez = I + I + ... + I =
2
2
2
3
2
n
15
I
=2
(5)
(6)
I ,a = I
z ,c
z , a + z ,c
(8)
Deoarece:
.
z ,a << z ,c
(9)
componentele curenilor armonici care circul spre sistem reprezint peste 90 % din valorile
produse de consumatorii deformani.
II.2.2. SITUAIA CU BATERIE CU CONDENSATOARE
Schema electric de principiu cu baterii cu condensatoare, folosit pentru compensarea
puterii reactive, frecvent ntlnit n ntreprinderi este reprezentat n figura 7. Pentru
uurarea nelegerii fenomenului, nu se mai consider consumatorii nedeformani care, dac
exist, preiau o cot foarte redus, numai 2 % - 4 % din curenii armonici produi i injectai
de consumatorii deformani, iar influena neglijrii care este uor defavorabil, este
admisibil.
Apariia bateriei cu condensatoare n schem (fig. 7) complic n mare msur
fenomenul, devenind ea nsi vulnerabil. n primul rnd, analiznd situaia numai pentru
componenta reactiv a curentului care intr n nodul A din sistem prin linia (a), ( I 1ra ), aceasta,
nsumat cu componenta reactiv ( I 1rB ) debitat de bateria cu condensatoare pentru
compensarea puterii reactive solicitat de consumatorii deformani, circul prin linia (b) spre
aceti consumatori, respectiv:
(10)
I 1ra + I 1rB = I 1ra
16
Fig. 5
x
1
= j 1, B
jC B
Fig. 6
Fig. 7
(11)
Fig. 8
x1, s
x
x1, s 1, B
(12)
Din expresia 12 se constat c numitorul fraciei este cel care determin comportarea
bateriei pentru diferite armonici de curent. Astfel, se constat c numitorul se anuleaz pentru
un rang, rez , de rezonan, numitorul expresiei 12 devenind:
x1, s rez
x1, B
=0
rez
(13)
de unde:
rez =
x1, B
x1, s
x1, B =
1
;
C B 1
U 12
;
S1, sc
1 = 2 50
(14)
Q1, B = U 12 C B 1
S1, sc
Q1, B
(15)
n max
2
, B
(16)
=2
O alt mrime caracteristic i pentru curentul deformat prin baterie este reziduul
deformant care se determin cu expresia:
I rez , B =
nmax
2
,B
(17)
=2
I rez , B
I 1, B
100
(18)
18
1
=0
C B nrez
(21)
n care:
[]
(22)
este reactana bobinei, care reprezint necunoscuta n relaia (21), cu care se poate calcula
inductana Lb a bobinei. Pentru alegerea rangului armonicei de rezonan este necesar s se
examineze cteva elemente teoretice i tehnice, privind comportarea filtrului, n ansamblu, n
vederea atenurii i a regimului deformant, dup ce prin calcularea puterii bateriei, s-a
asigurat compensarea puterii reactive. Astfel, se menioneaz c aa cum rezult din relaia
(21), reactana rezultant a circuitului filtrului corespunztoare frecvenei rangului ( rez ), de
rezonan este zero. Deci, acesta realizeaz la barele nodului A condiiile unui scurt circuit
trifazat pentru frecvena respectiv i astfel, prin filtru va circula spre pmnt n ntregime
armonica de curent cu frecvena corespunztoare, att cea produs de consumatorii
deformani din nodul A, precum i din alte noduri exterioare, dac nu sunt reinute de filtre
pentru aceeai frecven. Deci poate apare i un aport din exterior, care va trebui considerat.
xb = Lb 2 50
19
20
Fig. 9
Fig. 10
IV. CONCLUZII
Din analiza concentrat fcut n acest material, rezult c i pentru sistemul nostru
electroenergetic etapa care se parcurge, caracterizat de ptrunderea n msur din ce n ce
mai mare a electronicii sub toate formele ei sofisticate, n instalaiile de transport, distribuie
i mai ales n masa mare a consumatorilor de energie electric, se ncheie perioada de
utilizare exclusiva i respectiv de funcionare numai a bateriilor cu condensatoare.
Apariia i intensificarea foarte rapid a fenomenului deformant al curbelor de curent i
de tensiune, au condus i conduc la afectarea siguranei n funcionare a bateriilor cu
condensatoare, care n plus contribuie i la amplificarea regimului deformant.
Aceast situaie este argumentat teoretic i tehnic n acest material n care se prezint
i se justific soluia de rezolvare prin folosirea filtrelor pasive, care rezolv simultan, cu
costuri accesibile, att problema compensrii puterii reactive la consumatori industriali ct i
atenuarea, n limite admisibile, a regimului deformant, i cu posibilitatea utilizrii bateriilor
existente, pentru realizarea noii soluii.
V. BIBLIOGRAFIE
1. Iordnescu, I., Iacobescu, Gh., .a. Reele electrice pentru alimentarea
ntreprinderilor industriale. Editura Tehnic, Bucureti, 1985.
2. Iacobescu, Gh., Iordnescu, I., .a. Reele electrice. Editura Didactic i
Pedagogic, Bucureti. 1981;
3. Iacobescu, Gh., Iordnescu, I., Tudose, M. Reele i sisteme electrice. Editura
Didactic i Pedagogic, Bucureti, 1979;
4. Golovanov, N. Utilizarea energiei electrice i mari consumatori. Litografia IPB,
Bucureti, 1983.
5. Golovanov, N., ora, I. .a. Electrotermie i electrotehnologii. (Vol.1 i 2) Editura
Tehnic, Bucureti, 1997.
21
VIN
R2
R1
AE
VREF
RL V L
R3
DZ
amplificatorul de eroare, iar DZ dioda Zener ce livreaz tensiunea de referin pentru AE.
Fig.1. Stabilizator LDO cu tranzistor regulator n conexiune colector comun
22
TR
VIN
R2
R1
AE
VREF
RL VL
R3
DZ
Pentru stabilizatoarele LDO realizate conform schemei din figura 1, tranzistoarele npn
n configuraie de repetor pe emitor necesit o tensiune de intrare destul de mare, fa de
tensiunea de intrare stabilizat, pentru a acoperi tensiunea de saturaie colector-emitor a
tranzistorului regulator.
Pentru un amplificator n conexiune emitor comun (figura 2) diferena de tensiune
intrare-ieire este mai mic, pstrndu-se un factor bun de stabilizare a tensiunii de ieire.
Acest lucru se datoreaz modului de conectare a tranzistorului regulator pnp. Stabilizatoarele
de tensiune care au o cdere redus de tensiune intrare-ieire sunt cunoscute drept
stabilizatoare LDO (Low Drop-Out). Schema bloc a unui circuit integral stabilizator LDO
este reprezentat n figura 3 [9].
Se observ n figura 3 componentele clasice ale unui circuit integrat stabilizator de
tensiune continu din generaia a doua, concomitent cu asigurarea unui mecanism intern de
protecie la supracurent ce acioneaz n colectorul tranzistorului regulator Tri nu n emitorul
su, aa cum este cazul variantelor comune, ceea ce face ca s nu existe n nici un regim de
funcionare disipare de nergie.
Fig.3. Schema bloc a unui circuit integrat stabilizator LDO
+UIN
Protecii
interne
Polarizare
Amplificator
de eroare
TR
+UOUT
R1
Referin
de tensiune
R2
GND
23
VIN
+6V
C1
0,1 F
16V
LM 2937
IN
OUT
GND
2
C2
47 F
16V C3
0,1 F
16V
3. CONTROLERE NEENERGOFAGE
Un consum redus de putere reprezint una din cerinele obligatorii ale sistemelor
automate de msur i control moderne, n special ale celor pentru aplicaiile embedded.
Multe dintre aceste sisteme sunt alimentate din surse LDO sau de la baterii, ceea ce impune
un consum redus de putere. Estimrile recente arat c pn n anul 2007, peste o treime
dintre noile microcontrolere vor lucra la 2V i vor consuma, semnificativ, mai puin putere
dect componentele actuale. Un exemplu de astfel de microcontrolere l reprezint seria
HCS08 care lucreaz la tensiuni de 1,8V la 8 MHz, respectiv 2,1V la 20 MHz i care are un
numr de moduri de operare neenergofage (low power) [6]:
- Modul Stop1, utilizat n stand-by, sau pentru aplicaii n care consumul este situat n
jurul a 2V/20 nA. n acest mod, este utilizat o ntrerupere extern de activare a
microcontrolerului, de la un pin IRQ sau pinul Reset. Cnd ntreruperea extern este primit,
microcontrolerul comut la o frecven intern de bus de 4 MHz. Activarea
microcontrolerului are loc n 50s la 3V sau 80s la 2V. Pentru aplicaii, acest mod de
operare poate reprezenta etapa de verificare, de ctre microcontroler, a sistemului pentru a
citi starea senzorilor, a elementelor de execuie etc.
- Modul Stop2, n care este meninut coninutul memoriei RAM, iar un timer wakeup se poate activa automat. Rezult c n modul Stop2, microcontrolerul se poate activa fr
o ntrerupere extern. Un oscilator de 2 kHz livreaz baza de timp pentru aceast funcie, iar
frecvena mic necesit un consum redus de putere, de aproximativ 2V / 700nA. Atunci cnd
microcontrolerul detecteaz o condiie care necesit o vitez mare de calcul, viteza
magistralei poate fi incrementat pn la 20 MHz. Aceste funcii ce pot fi executate rapid, la
20 MHz, i permit microcontrolerului s prseasc la fel de repede modul Run i s revin n
altul de consum mic.
24
25
26
Generaliti
Diversitatea perturbaiilor care apar n reeaua de alimentare face necesar gruparea lor
dup diverse criterii, cum ar fi cel al cauzelor i fenomenelor care le-au generat. Aceste
fenomene se pot mpri n dou mari categorii: fenomene aleatoare i fenomene cu caracter
permanent sau cvasipermanent.
Fenomenele aleatoare sunt acele evenimente cu caracter accidental; cum ar fi pot
trsnetul i defectele care iau natere fie n elementele reelei (linii, cabluri, transformatoare,
etc.), fie n instalaiile de la consumator.
Fenomene permanente sau cvasipermanente apar pe perioade bine determinate i sunt
generate de diferite echipamente instalate la utilizatorii de energie electric. Aceste aparate
preiau curenii nesimetrici pe cele trei faze, absorb cureni a cror amplitudine variaz de o
manier important sau a cror forma este mult diferita de cea sinusoidal.
Perturbaiile continue (altele dect supratensiunile sau subtensiunile de lung durat) se
manifest ca distorsiuni armonice. Sursele unor astfel de distorsiuni includ aparatura de
comand n frecven variabil a turaiei motoarelor asincrone, redresoarele n punte,
cuptoarele cu arc electric, aparatele de sudare, sursele nentreruptibile de alimentare cu
energie electric (UPS), sursele de alimentare n comutaie ale echipamentelor de calcul,
balasturile electronice ale lmpilor fluorescente, etc. Consumatorii care dein un numr mare
de echipamente de tipul celor menionate mai nainte sunt cei mai predispui la apariia
problemelor cauzate de distorsiuni armonice. Sursa acestui tip de probleme poate fi, deci, att
n interiorul unitii consumatoare, ct i n exteriorul ei.
n zilele noastre, toate receptoarele electrice, cu excepia, poate, doar a lmpilor cu
incandescen i a aparatelor de nclzit echipate cu rezistene, produc armonici. Armonicile
sunt definite ca fiind tensiuni sau cureni ale cror frecvene sunt un multiplu ntreg al
frecvenei fundamentale. Pentru sistemele de alimentare a cror frecven de lucru este de 50
Hz, frecvenele armonicilor sunt 100 Hz, 150 Hz, 200 Hz, etc.
Uzual, armonicile sunt definite prin ordinul lor, care reprezint multiplul fundamentalei
la care aceasta se raporteaz. De exemplu, armonica a crei frecven este de 150 Hz este
cunoscut ca fiind armonica a 3-a. n acest caz, unei perioade a fundamentalei, i corespund
trei perioade ale armonicii. Dac multiplul ntreg al frecvenei fundamentale este impar,
armonicile se numesc de ordin impar, n timp ce dac multiplul ntreg al frecvenei
fundamentale este par, armonicile se numesc de ordin par.
Marea majoritate a echipamentelor moderne produce armonici. Practic, orice aparat
care conine un modul ce convertete energia electric alternativ n energie electric continu
i invers, este considerat ca fiind un aparat care produce armonici. Cele mai rspndite
echipamente de acest fel sunt calculatoarele electronice, sursele de alimentare
nentreruptibile, receptoarele de televiziune, etc.
Cea mai important consecin a apariiei armonicilor o constituie distorsionarea formei
de und sinusoidale a tensiunii de alimentare.
n general, problemele cauzate de apariia armonicilor pot fi grupate n dou mari
categorii:
27
28
(4-1)
k =1
anumite condiii, cum sunt, de exemplu, condiiile Dirichlet, i anume funcia (semnalul) s
fie mrginit, neted (monoton) pe poriuni i cu un numr finit de discontinuiti de prima
spe), atunci seria Fourier fn (t ) este convergent, iar suma ei coincide cu semnalul y (t )
pentru orice t R , adic:
B
k N
(4-
k =1
2)
n orice punct de continuitate t a semnalului y (t ) , respectiv:
x ( t0 + 0 ) + x ( t 0 0 )
lim fn ( t0 ) =
,
(4n
2
3)
n orice punct t0 de discontinuitate de spea I a semnalului y (t ) .
Dac se fac notaiile:
A
(4C k = Ak2 + Bk2 i k = arctg k ,
Bk
4)
n care Ck i k sunt amplitudinea i, respectiv, faza iniial a armonicii de ordinul k, atunci se
deduce c semnalul periodic y (t ) poate fi echivalat prin relaia:
y (t ) = C0 + C k sin (k t + k )
(4-
k =1
5)
care reprezint forma canonic (compact) a seriei Fourier.
Forma n complex a seriei Fourier se obine din forma complex a funciilor
trigonometrice sin (k t ) i, respectiv, cos (k t ) :
1 j k t
1
sin (k t ) =
e
e j k t
cos (k t ) = (e j k t + e j k t )
2j
2
1
1 j k t
y (t ) = C0 + Ak e j k t + e j k t + Bk
e
e j k t =
2
2j
k =1
k =1
A
A B
B
= C0 + k + k e j k t + k k e j k t =
2j
2j
k =1 2
k =1 2
A j Bk j k t
A + j Bk j k t
= C0 + k
+ k
e
e
2
2
k =1
k =1
29
1
A j Bk j k t 1 Ak + j Bk j k t
(4-6)
+
y (t ) = C0 + k
= Ck e j k t k Z
e
e
2
2
k =
k =
k =
T
1
j k
Ck = Ck ( j k ) e
= y (t )e j k t dt
n care
(4T0
7)
Funcia Ck este o funcie de variabil complex, care are modulul dependent de
frecven (denumit i amplitudine spectral) i argumentul dependent, de asemenea, de
frecven.
Reprezentarea n funcie de frecven a modulului Ck = Ck (k ) conduce la definirea
spectrului de frecven al amplitudinilor (spectrul discret) iar reprezentarea argumentului
k = k (k ) , conduce la spectrul de frecven al fazelor iniiale.
Expresiile (4-1) i (4-5) arat faptul c spectrul unui semnal periodic are un caracter
discret, deoarece este constituit dintr-o sum de componente de frecvene distincte (0, , 2,
3,etc.).
Componenta armonic corespunztoare lui n = 1 se numete fundamental (armonic
de baz), avnd frecventa f =
30
~
~
~
sin k t dt = 0
cos k t dt = 0
8)
T
sin k t sin t dt =
0
1
2
(4-
9)
pentru n
pentru n =
(4-
T
0 pentru n
1
(
)
(
)
cos
k
t
cos
t
dt
[
]
cos
k
t
cos
k
t
dt
=
+
+
=
T pentru n = (4-10)
0
2 0
2
T
T
1
(40 sin k t cos t dt = 2 0 [sin (k ) t + sin (k + ) t ]dt = 0
11)
cu care, din relaia (4-1), se obine:
T
T
1
1
(
)
y
t
sin
k
t
dt
A
T
y (t ) cos k t dt = BnT
=
(4n
0
2
2
0
12)
din care rezult valorile coeficienilor C0, Ak i Bk,:
T
T
T
1
2
2
C0 = y (t ) dt
Ak = y (t ) cos k t dt Bk = y (t ) sin k t dt (4-13)
T 0
T 0
T 0
Coeficienii din relaiile (4-13) pot fi exprimai i sub form polar (figura 1.2), rezultnd:
T
31
Ak cos k t + Bk sin k t
Ak
cos k t +
= Ak2 + Bk2
Ak2 + Bk2
Ak2 + Bk2
sin k t =
Ak2 + Bk2
Bk
Fig. 1.2
Ak cos k t + Bk sin k t =
(4-
14)
n care sin k =
Ak
cos k =
Bk
Ak2 + Bk2
Ak2 + Bk2
Aplicnd
relaiei
(4-8)
identitatea
sin ( + ) = sin cos + cos sin , rezult:
Ak cos k t + Bk sin k t =
15)
n care tg k =
trigonometric
cunoscut
(4-
sin k
A
= k
cos k Bk
Tipul de simetrie
Definiie
32
k =1
k =1
= C0 Ak cos k t Bk sin k t
k =1
k =1
k =1
k =1
= C0 + Ak cos k t Bk sin k t
k =1
k =1
2 C0 + [Ak cos k ( t )] = 0
k =1
C0 = 0 ;
k =1
[A
k =1
cos k ( t )] = 0
y (t ) = Bk sin k t
k =1
Acelai rezultat se obine i prin impunerea condiiei de imparitate n relaiile (4-4), (45) i (4-7):
T
T
1
2
C0 = y (t ) dt = 0 i Ak = y (t ) cos k t dt = 0 ,
T 0
T 0
iar forma canonic (4-5) a dezvoltrii n serie Fourier devine:
4 2
2
(4-16)
y (t ) = Bk sin k t cu Bk = y (t ) sin k t dt = y (t ) sin k t dt
T 0
T 0
k =1
A
0
deoarece Ck = Ak2 + Bk2 = Bk2 = Bk , k = arctg k = arctg
= arctg 0 = 0
Bk
Bk
n figura 1.3 sunt prezentate cteva forme de und care prezint proprietatea de
imparitate.
k =1
k =1
k =1
k =1
k =1
k =1
k =1
k =1
k =1
k =1
[B
k =1
Bk = 0
k =1
y (t ) = C0 + [Ak cos k t ]
k =1
Acelai rezultat se obine i prin impunerea condiiei de paritate n relaiile (4-4), (4-5)
i (4-7):
T
2
Bk = y (t ) sin k t dt = 0 , Ck = Ak2 + Bk2 = Ak2 = Ak
T 0
Ak
A
sin k t + = cos k t
= arctg k = arctg =
2
Bk
0
2
k = arctg
2
4 2
y (t ) = C0 + Ak cos k t cu Ak = y (t ) cos k t dt = y (t ) cos k t dt
T 0
T 0
k =1
17)
n figura 1.4 sunt prezentate cteva forme de und care prezint simetrie impar.
(4-
Dac funcia y (t ) ndeplinete condiia y (t ) = y t , atunci ea este alternativ
2
simetric sau se mai spune c prezint simetrie de semiund. n aceste condiii, pornind de la
relaia (4-2), se obine:
k =1
k =1
k =1
k =1
k =1
k =1
k =1
k =1
k =1
k =1
k =1
k =1
k =1
de unde rezult c C0 =
1
y (t ) dt = 0 , iar amplitudinile de ordin par A2k (A2, A4, A6, ...) i
T 0
B2k (B2, B4, B6, ) sunt nule. n aceasta situaie, funcia y (t ) conine numai armonici impare.
Prin descompunerea ei n armonici, rezult numai armonicile de ordin impar n sinus:
B
y (t ) = Ck sin k t , (k = 1, 3, 5, .)
(4-
k =1
18)
T
2
4
n care: Ak = y (t ) cos k t dt =
T 0
T
T
y (t ) cos k t dt , (k = 1, 3, 5, .) i
0
2
4 2
(
)
y
t
sin
k
t
dt
=
y (t ) sin k t dt , (k = 1, 3, 5, .)
T 0
T 0
n figura 1.5 sunt prezentate cteva forme de und care prezint proprietatea de simetrie
de semiund.
Ak =
35
C0 = 0
C0 = A
Ak = 0
Bk = 0
k
Semnal triunghiular
Semnal constant
8A
Ak = (n )2
0
Bk = 0 k
C0 =
C0 = 0
A1 = A
Ak = 0
k 1
Bk = 0
k
Semnal
sinusoidal
redresat
C0 = 0
k
B1 = A
k 1
Semnal sinusoidal
Semnal sinusoidal
redresat bialternan
C0 = 0
Ak = 0
2A
k impar
Ak = 1 n 2
0
k par
A
k =1
Bk =
2
Bk = 0
k 1
C0 =
Bk = 0
2A
k impar
0
4A
Ak =
k par
1 n 2
Bk = 0
k
A
2
Ak = 0 k
C0 =
4A
Bk = n
0
k par
Semnal cosinusoidal
Ak = 0
k impar
k impar
Bk =
k par
Semnal ptratic
A
k
C0 = 0
AF
C0 =
T
2A
k F
Ak =
sin
k
T
Bk = 0 k
Ak = 0
32 A
Bk = (k )3
0
k imp
k par
Semnal parabolic
Semnal dreptunghiular
Fig. 1.6. Valorile coeficienilor Fourier pentru cteva tipuri particulare de semnale periodice
Bibliografie
[1] Iordache M., Conecini I.: Calitatea energiei electrice, Editura Tehnic, 1997
[2] Iordache M, Chiu I., Costina S.: Controlul calitii energiei electrice, Editura AGIR, 2000
[3] Darie S.: Aspecte privind calitatea energiei electrice http://bavaria.utcluj.ro/~picas/edsa7.pdf
36
37
39
41
43
Toat informaia este recepionat i prelucrat de postul central de comand care este
un calculator PC i reprezint nivelul ierarhic superior n aceast configuraie. Semnalele
provenite de pe magistrala de comunicaie cu sistemele vitale au prioritate fa de celelalte.
La apariia unui eveniment (incendiu), informaia despre natura i locul apariiei acestuia se
afieaz automat pe ecranul calculatorului. Concomitent cu aceasta se afieaz indicaii
despre modul n care trebuie s acioneze operatorul conform procedurilor de intervenie
stabilite i implementate ntr-un program software adecvat.
La apariia unui semnal de incendiu, automat se transmite alarma local de incendiu
prin activarea sistemelor de cutare a personalului de intervenie i a dispoziiilor de alarm
intern. n cazul n care nu are loc o intervenie uman, dup expirarea unei anumite
temporizri, se declaneaz alarma general. Aceasta include alarma extern (acustic i
optic) pentru avertizarea i mobilizarea personalului din obiectiv i totodat anunarea
serviciilor de pompieri.
Concomitent cu alarma extern, sistemul activeaz comenzile specifice n caz de
incendiu (nchiderea uilor rezistente foc, deschiderea gurilor de evacuare a fumului,
ntreruperea alimentrii cu energie electric) i declanarea instalaiilor de stingere a
incendiului.
44
45
47
48
extensie.
Fig. 1
Intr-un sistem de domotic, Fig. 2, pot exista la nivelul de management i nivelul de
automatizare calculatoare care nu ndeplinesc condiia de funcionare n timp real, de exemplu
diversele servere (web, baze de date, ftp, etc), gateway sau staii clieni. Sistemul lor de
programare este diferit de cel pentru AP.
Dei n Fig. 2 nu apar, aproximativ 20% dintre calculatoarele folosite n conducerea
automat n timp real nu sunt de tip AP, principala deosebire constnd n caracteristicile
software care permit o programare mai elastic. ntr-adevr, schema de funcionare pentru AP
const n scanarea intrrilor, executarea algoritmului de conducere, actualizarea ieirilor i
realizarea operaiilor de ntreinere. Proiectarea n aceast situaie este concentrat asupra
algoritmului de conducere deoarece ciclurile de intrare, ieire i ntreinere sunt ascunse.
Celelalte tipuri de calculatoare folosite n conducerea automat, numite PAC (Programmable
Automation Controller) ofer un acces mai profund la resursele hardware ale sistemului.
i din Fig. 2 se observ rolul important al intrrilor/ieirilor i comunicrii prin
magistrala (bus) de automatizare i magistralele de cmp. Automatele programabile pot juca
diferite roluri ntr-un sistem de domotic: interconectare direct I/E, Interconectare I/E prin
intermediul magistralei de cmp sau gateway ntre magistrale.
49
Fig. 2
Proiectarea unui sistem de conducere cu AP are cel puin urmtoarele etape:
1. Identificarea procesului.
2. Stabilirea algoritmului de conducere i a performanelor necesare.
3. Programarea AP
4. Configurarea AP
Orice discuie privind proiectarea sistemelor de conducere cu automate programabile nu
poate fi fcut n afara standardelor IEC 61131 i IEC 61499. Standardul IEC 61131 are
urmtoarele seciuni:
IEC 61131-1 Generaliti
IEC 61131-2 Testare
IEC 61131-3 Programare i tipuri de date
IEC 61131-4 Ghidul utilizatorului
IEC 61131-5 Comunicaii
IEC 61131-7 Conducerea Fuzyy
Evoluia standardelor referitoare la AP este prezentat n tabelul urmtor:
Anul
1977
1983
1993
1994
1995
Standarde nationale
DIN 40 719-6 (scheme bloc)
GRAFCET (Frana)
DIN 19239 PLC programming
Allen Bradley: limbaje de programare
pentru AP
DIN EN 661131 Part 3
DIN EN 661131 Parts 1 and 2
Standardul international
IEC 848
IEC 61131-3
IEC 61131-4
IEC 61499 Conducere
distribuita
2005
O importan deosebit are standardul IEC 61131-3 care prevede urmtoarele modele
pentru programarea AP:
1. LD (Ladder Diagram) schem desfurat cu contacte i relee
50
Fig. 3
Pentru programarea sistemelor de conducere distribuite cu AP s-a elaborat standardul
IEC 61499. n Fig. 4 se prezint o schem tehnologic simpl pentru un sistem de conducere
distribuit format dintr-un PC, un AP, un regulator PID i un robinet de reglare, toate
interacionnd prin intermediul unei magistrale (bus). Un program sub form de FBD
conform IEC 61499 pentru acest sistem de conducere distribuit apare n Fig. 5. ntre blocurile
funcionale exist o legtur la nivelul fluxului de evenimente i la nivelul fluxului de date.
Fiecare bloc poate s aib diferite intrri i ieiri cum ar fi referina SP i ieirea AUT pentru
regulatorul PID. Blocul RESTART furnizeaz eveniment pentru execuia periodic a
celorlalte blocuri funcionale.
n cadrul foarte general furnizat de aceste standarde vreau s prezint o modalitate de
proiectare a sistemelor cu AP pe care am elaborat-o. Bineneles c metoda are multe limitri
dar este mai simpl i, lucru important, destul de algoritmizat, permind i inginerilor mai
puin experimentai proiectarea unor sisteme de conducere cu performane bune.
n primul rnd, modelul pentru sistemul de conducere este o reea Petri conform i nu un
grafcet cum prevede IEC 61131-3. Grafcetul este mai general i mai elastic pentru construcia
de modele dect reeaua Petri /11/. n schimb modelul Petri este mai uor de analizat i tradus
sub forma unui model matematic care s stea la baza elaborrii programului pentru AP.
Stabilirea relaiilor logice o fac cu ajutorul unor automate elementare cu prioritate la pornire,
spre deosebire de soluia recomandat n /8/ care folosete automate elementare cu prioritate
la oprire. Soluia mea este mai aproape de spiritul grafcetului i evit erori care pot apare la
elaborarea unor modele care conin paralelisme de tip conveyor. Metoda de proiectare va fi
prezentat n continuare pe baza exemplului automatului care pornete un motor electric i
dup o rotaie l oprete n poziia iniial, Fig. 6.
Primul pas n proiectarea unui sistem automat const n alegerea soluiei de conducere
automat. n cazul de fa se dorete o soluie simpl, care s nu controleze continuu poziia
axului motorului. Motorul trebuie s porneasc la acionarea butonului de pornire p i s se
opreasc la acionarea contactului a care indic terminarea unei rotaii. Algoritmul de
51
Fig. 4
Staiile de comand trebuiesc proiectate i construite din punct de vedere hardware
(mecanic, electric i electronic) i software. n aceast lucrare se va pune accentul, n special,
pe proiectarea sistemului de conducere.
n continuare se va prezenta n special proiectarea automatului, elementului de execuie,
a sistemului de semnalizare i comutare n diferite regimuri de lucru.
52
Fig. 5
Analiza structural. S considerm c exist o reea Petri echivalent grafcetului.
Structura sa este identic, iar din punct de vedere grafic ptratele (etapele) se nlocuiesc cu
cercuri (poziii). n etapa iniial A se pun o singur marc. Deoarece fiecare din cele trei
tranziii are un singur arc de intrare i un singur arc de ieire Reeaua Petri este de tip main
de stare. Graful asociat reelei Petri este conex deoarece din orice nod 1 se poate ajunge n
oricare alt nod, mai mult este tare conex deoarece aceast performan se realizeaz prin
intermediul unor arce orientate.
Reductor
Cama
24V
M
Palpator
k2
Resort
p
24V
ZK
1
Fig. 6
Teorema lui Commoner /15/ spune c dac graful este tare conex atunci reeaua este
viabil. Dac marcajul iniial are o singur marc, cum este cazul aici, atunci reeaua este
viabil i sigur. Analiznd structura reelei se observ imediat c nu exist conflicte
structurale, deci reeaua Petri este conform i echivalent cu grafcetul. Toate concluziile pe
care te obinem lucrnd cu reeaua Petri sunt valabile i pentru grafcet.
Analiza comportamental. Tranziia (1), validat iniial, se declaneaz cnd se apas
butonul de pornire i p=1. Devine activ etapa B i motorul pornete. La terminarea unei
rotaii contactul traductorului este acionat de palpator i a=1. Tranziia (2) se declaneaz i
1
Nodurile grafului sunt poziiile. Laturile grafului sunt arcele orientate care leag nodurile
atunci cnd se ignor tranziiile.
53
xt xt xt
0 1 2
A
H=1, M=0
(1)
H=0, M=1
0 1 0 H=0, M=1
(2)
Memorare a
b=a
(3)
(1)
(2)
1 0 0 H=1, M=0
0 0 1 Memorare a
b=a
(3)
a)
b)
Fig. 7
Metoda de programare Grafcet. Caietul de sarcini Grafcet din Fig. 7a) poate fi
implementat direct la unele automate programabile folosind o interfa grafic. Metoda este
foarte util n cazul automatelor complexe.
Metoda listei de instruciuni. Se folosete reeaua Petri conform care descrie
funcionarea automatului. Pentru exemplul considerat aceasta este prezentat n Fig. 7 b).
Metoda de proiectare are urmtoarele etape:
Etapa 1. Codificarea locaiilor cu ajutorul codului distribuit (1 din n). Rezultatul apare
n Fig. 7b). Se observ c fiecrei locaii i corespunde un singur bit egal cu unu. Metoda de
proiectare se bazeaz pe observaia c acest bit poate fi implementat cu ajutorul unui automat
elementar cu prioritate la pornire. Condiia de setare coincide cu condiia de activare a locaiei
iar condiia de resetare coincide cu condiia de dezactivare a locaiei.
Etapa 2. Calculul condiiilor de setare i resetare a biilor corespunztori fiecrei etape.
Setarea coincide cu activarea locaiei care are loc dac toate locaiile precedente sunt active i
evenimentele care interpreteaz tranziiile de la aceste locaii au aprut, adic au valoarea
logic unu. Resetarea are loc dac locaia respectiv este activ i evenimentele care
declaneaz tranziiile posterioare tranziiei au aprut. Exemplul studiat este mai simplu
pentru c fiecare locaie are cte o singur tranziie precedent i o singur tranziie
posterioar
54
n = 0 s0 = x2 a r0 = x0 p
(1)
n = 1 s1 = x0 p r1 = x1a
(2)
n = 2 s2 = x1a r2 = x2 a
(3)
Etapa 3. Determinarea relaiilor logice pentru locaiile active iniial cu ajutorul
urmtoarei formule care provine din expresia automatului elementar cu prioritate la pornire:
xnt + = snt + rnt xnt + i
(4)
(5)
(6)
Pentru automatul din Fig. 7 b) locaiile B i C nu sunt active iniial i aplicnd formula
precedent pentru condiiile (3) i (3) se obine:
x1t + = ( x0t p t + ax1t )i
(7)
x 2t + = ( x1t + x 2t )a t i
(8)
Exist tentaia ca n cazul unor relaii logice simple, cum este cazul exemplului prezentat, s
se deduc direct relaia logic fr ajutorul diagramei Karnaugh. Este o metod greit pentru
c permite ignorarea anumitor situaii care sunt puse ns n eviden de ctre diagrama
Karnaugh. n exemplul prezentat acesta este cazul cu situaia n care toate variabilele de stare
sunt egale cu zero, situaie care nu apare n reeaua Petri. Diagrama Karnaugh ne-a silit s
precizm valorile de ieire n acest caz. Am hotrt, de exemplu, c n acest caz lampa de
semnalizare H nu este aprins.
55
x t xt
xt 0 1
2
y t = xt + xt
1 2
m
00
01
11
10
Fig. 8
y t = xt
h
0
x t xt
0 1
t
x
2
00
01
11
10
Fig. 9
Din aceiai reea Petri rezult c lampa H semnalizeaz numai n locaia A i deci numai
atunci variabila de ieire corespunztoare yh are valoarea 1. Relaia logic corespunztoare
determinat cu ajutorul diagramei Karnaugh este prezentat n Fig. 9.
Etapa 6. Elaborarea tabelului de configurare. Se stabilete o coresponden ntre
variabilele relaiilor logice i denumirile elementelor componente ale automatului
programabil: intrri, ieiri, memorii (relee), timere (relee de timp), etc. Pentru exemplul
considerat acestea apar n Tab 1 i Tab 2.
p
I0.1
M0.1
a
I0.2
M0.2
ym
Q0.1
M0.14
yh
Q0.0
M0.15
x1t
M0.4
Q0.4
x2t
M0.5
Q0.5
x0t+
M0.6
x1t+
M0.7
56
x2t+
M0.8
tampon1
M0.9
tampon2
M0.10
Instruciunea
LI0.0
001
002
003
004
005
006
007
=M0.0
LI0.1
=M0.1
LI0.2
M0.2
LM0.5
ANM0.2
008
009
010
011
012
013
Comentariu
Achiziia
intrrilor
Adresa
029
Instruciunea
LM0.2
030
031
032
033
034
035
036
AM0.5
=M0.10
LM0.9
OM0.10
ANM0.0
=M0.8
LM0.6
=M0.9
LNM0.1
AM0.3
=M0.10
LM0.9
OM0.10
037
038
039
040
041
042
=M0.3
LM0.7
=M0.4
LM0.8
=M0.5
LM0.4
014
015
016
017
018
OM0.0
=M0.6
LM0.3
AM0.11
=M0.9
043
044
045
046
047
OM0.5
=M0.14
LM0.3
=M0.15
LM0.14
019
020
021
022
LNM0.2
AM0.4
=M0.10
LM0.9
048
049
050
051
=Q0.1
LM0.15
=Q0.0
LM0.3
023
024
025
026
027
028
OM0.10
ANM0.0
=M0.7
LM0.4
AM0.2
=M0.9
052
053
054
055
056
=Q0.3
LM0.4
=Q0.4
LM0.5
=Q0.5
Calcul x0t+
Calcul x1t+
Calcul x2t+
57
Comentariu
Actualizare
stri
t+
xn
--> xnt
Calcul ieiri
ynt
Furnizare
ieiri ynt
Semnalizare
stri
58
59
raportul de transformare:
u
U nk'
1 p k pk'
U nk
100
(1)
n care: Unk este tensiunea nominal de linie la m.t pe transformatorul Tk; Unk - tensiunea
nominal de linie la j.t pe transformatorul Tk; pk - priza pe care funcioneaz transformatorul
Tk; upk - variaia de tensiune pe o priza la transformatorul Tk.
3. Curba de sarcin a consumatorului
n ipoteza c sistemul de achiziie a datelor este compus dintr-o interfa ce poate
prelucra de la j.t: tensiunea U, curentul I, puterea activ P sau energia activ Wa la intervale
de timp t, puterea reactiv Q sau energia activ Wr la aceleai intervale de timp t, atunci cu
acestea se pot compune curbe de sarcin, att pentru fiecare faz ct i pe ansamblul
sistemului trifazat.
Indicatorii curbelor de sarcina cei mai utilizai sunt:
- puterea aparent medie Smed:
Smed =
-
Wa2 + Wr2
tf
(2)
coeficientul de umplere ku :
60
Smed
SM
(3)
1 a
ku
(4)
unde: SM este puterea aparent maxim, a coeficientul de regresie cuprins n domeniul [0,15
0,30], iar tf - timpul de funcionare al consumatorului C.
4. Pierderi de putere i energie electric n transformatorul Tk
Pornind de la relaiile de definiie ale acestor mrimi asociate transformatoarelor
monofazate, pentru un transformator trifazat n construcie simetric, acestea devin:
Pierderile de putere activ Pk
Pk = P0k
V2 + V2 + V2
A
B
U2
n
+ Psck
U2
n
2
S
nk
(I 2 + I 2 + I 2 )
A
(5)
Wak
VA2 + V 2 + V 2
U2
2 2
2 2
2 2
B
C
n
= P0k
t f + Psck
(I k + I k + I k )
A A
B B
C C
2
2
U
S
nk
n
(6)
n care: VA, VB, VC sunt tensiunile medii de funcionare pe faze ale transformatorului Tk; IA,
IB, IC - curenii medii de funcionare ai transformatorului Tk; kA , kB , kC - coeficienii de
form ai curbelor de sarcin.
Considernd tensiunile i curenii fr component homopolar, ipoteza valabil n
sistemele de distribuie fr conductor de nul, se pot defini coeficienii de nesimetrie invers
afereni tensiunii i curentului ( kU , k I ) cu relaia:
2
k- = 1 3 6 U ,
U
1 + 3 6 U
2
k- = 1 3 6 I
I
1 + 3 6 I
(7)
(VA2 + VB2 + V )
2 2
C
I 4A + I 4B + I C4
(I2A + I 2B + I )
2 2
C
= U
pentru tensiuni
(8)
= I
pentru curenti
61
Pk = P0k 1 + k
U
2 +
2 I + U
n
U + P 1 + k
U sck I S
nk
n
2
(9)
unde coeficienii k U si k I sunt definii cu relaia (7) innd seama de relaia (8).
Marimile Vd si Id sunt componentele normate de succesiune pozitiv (direct) ale
tensiunii i curentului, fiind definite cu relaiile:
U2
d
V2 + V2 + V2
A
1+ 3 6
);
I2
d
I2 + I2 + I2
A
1+ 3 6
(10)
2
f
I 2A k 2A + I 2B k 2B + I C2 k C2
(11)
I 2A + I 2B + I C2
Wak
VA2 + V 2 + V 2
U2
2
2
2
2
B
C
n
= P0k
+ Psck
k f (I + I + I ) t
A
B
C f
2
2
U
S
n
nk
(12)
Wak
= P
0k
1 + k
U
2
2
U + + P
sck
S
nk
2
2
1 + k k 2 I + t (13)
I f f
(14)
U =
Ud
,
Un
sk =
Sd
Snk
(15)
Pk = P0k 1 + k
U
Wak
2
2
2 + P 1 + k 2
sck
U
I sk
= P 1 + k
0k U
2
2
2 + P 1 + k k 2 2 t
sck
U
I f sk f
62
(16)
Fig.2. Graficul pierderilor de putere Pk (a) i a pierderilor de energie activ Wak (b) n
regim simetric () i n regim nesimetric (------)
5. Concluzii
Din analiza graficelor din fig.2 rezult cteva observaii care permit evidenierea unor
msuri pentru ridicarea eficienei exploatrii posturilor de transformare. Dintre aceste msuri
sunt relevante urmatoarele:
- alegerea parametrilor transformatoarelor (Pok si Psck) astfel nct s fie satisfacut
asigurarea nevoilor consumatorilor cu minim de pierderi (putere si energie) ;
- asigurarea regimului de ncrcare simetric ( k U = 0 ) i echilibrat ( k I = 0 ) care permit,
la acelai tranzit de energie electric, pierderi de putere i energie minime;
- msuri tarifare tentante pentru o mai bun aplatisare a curbelor de sarcin care, n
regim simetric (i nesimetric), conduce la pierderi de putere i energie mai mici.
Toate aceste elemente sunt cunoscute i concretizate n toate normativele n vigoare
care trebuie completate cu studii pentru curbe de tip sarcin ce vor putea permite elaborarea
unor noi reglementri n domeniul tarifelor de energie electric care s conving
consumatorul de necesitatea ridicrii eficienei distribuiei i utilizrii energiei electrice.
6. Studiu de caz
Folosind modelul prezentat mai sus, s-a realizat o aplicaie numeric pentru
determinarea pierderilor de putere respectiv de energie pentru 2 posturi de transformare ale
caror caracteristici sunt prezentate n tabelul 1.
63
Unp [kV]
Uns [kV]
usc [%]
i0 [%]
Psc [kW]
P0 [kW]
PT 250
kVA
20
0,4
6
1,8
6,5
1,35
PT 160
kVA
240,99
242,63
240,87
142,37
173,35
80,32
UA [V]
UB [V]
UC [V]
IA [A]
IB [A]
IC [A]
PT 250
kVA
236,74
234,9
231,2
111,93
118,39
124,71
Pnesimetric Psimetric
100
Psimetric
2,11
0,03
102,0
Expon. (SoptW)
94,0
Expon. (SoptP)
92,0
60,00
+ 6,4178
R = 0,8417
k-U
Power (W)
1000
630
250
160
Sn [kVA]
100,00
80,00
60,00
R2 = 0,8475
40,00
20,00
R2 = 0,8417
0,816
0,655
0,555
0,474
0,000
0,00
0,816
0,655
0,555
0,474
0,403
0,333
0,262
0,179
0,000
0,00
Power (P)
R = 0,9741
0,403
SoptP =
20,00
0,13k -U
2
R2 = 0,8456
40,00
W = 93,901Sn
SoptW optW
80,00
P
0,0251
90,0
Sopt - opt
120,00
100,00
R2 = 0,9733
96,0
Sn [kVA]
1000
630
250
160
100
40
98,0
R2 = 0,9888
16
SoptW
0,0168
P = 95,877Sn
100
SoprP = 6,1738e0,3341Sn
100,0
0,333
R = 0,9888
SoptP
40
0,262
SoptW = 10,233e0,3341Sn
0,179
900,00
800,00
700,00
600,00
500,00
400,00
300,00
200,00
100,00
0,00
opt[%]
16
Sopt[kVA]
k-U
64
Sopt - opt
120,00
SoptW optW
100,00
100,00
-
R2 = 0,8475
SoptW = 0,2155x + 10,637
60,00
40,00
R2 = 0,8417
R2 = 0,8417
20,00
20,00
k-I
0,333
0,262
0,179
0,000
0,00
0,816
0,655
0,555
0,474
0,403
0,333
0,262
0,179
0,000
0,00
0,816
40,00
80,00
-
0,655
R2 = 0,8456
0,555
60,00
0,474
0,403
80,00
k-I
Fig 4. Variaia puterilor i randamentului optimi funcie de coeficientul de ncrcare pentru regim
nesimetric de cureni
7. Interpretarea rezultatelor
65
66
67
68
69
70
71
Intrare
microcontroler
Frecvena de oscilaie
Rezistena de contact
Frecvena de oscilaie
()
(Hz)
()
(Hz)
0,01
2281
0,91
2311
0,02
2281
0,94
2324
0,03
2281
1,03
2330
0,04
2281
1,22
2332
0,11
2281
1,24
2332
0,12
2281
1,27
2333
0,13
2281
1,24
2333
0,20
2297
1,30
2333
0,21
2297
1,32
2333
0,23
2297
1,37
2333
0,26
2298
1,98
2394
0,27
2298
2,31
2434
0,35
2299
2,34
2441
0,55
2304
2,45
2458
0,51
2301
2,81
2493
0,68
2306
2,97
2501
0,71
2311
5,32
2987
0,72
2311
21,56
4201
0,82
2311
98
5200
72
73
74
Partea I
Evaluarea riscului expunerii populaiei la cmpuri EMG.
Atitudini privind gradul de implicare i cunoatere tiinific
a efectelor nocive posibile ale cmpurilor electromagnetice
n etapa 2000-2006 fa de 1990-2000 n domeniul locuinelor
i instalaiilor pentru construcii.
I. 1 Poluarea electromagnetic criteriu de analiz
a gradului de expunere a populaiei n spaiul locuit.
n sprijinul clarificrii zonei de interes pentru specialitii din aplicaiile electrotehnice pentru
construcii de locuine i social-culturale privind evaluarea gradului de poluare electromagnetic a
mediului construit, am pornit analiza din lucrarea de fa de la:
1. ce se considera semnificativ n plan internaional n perioada 1990 pn n 2000 n abordarea
problemelor de poluare electromagnetic a mediului;
2. ce a adus nou perioada din 2000 pn n 2006, fa de etapa de mai sus;
3. ce se consider n plan naional ca prioritar i atitudinea Romniei n acest domeniu.
75
Convenional, joasa frecven se consider atunci cnd spectrul de frecven al perturbaiei este,
n cea mai mare parte, sub 9KHz. Gradul de perturbare este un indicator al clasei corespunztoare unui
nivel de severitate al perturbaiei. Gradele de perturbare sunt clasificate de la A (controlat), 1, 2,,6 i
X (sever).
Din perspectiva domeniului instalaiilor pentru construcii i a consumatorului de energie
electric, ne intereseaz o analiz privind progresele n evaluarea riscului expunerii populaiei la
cmpuri EMG, obinute n plan naional i internaional, n perioada 2000-2005, n raport cu 19952000 cu introducerea noiunii de poluare electromagnetic ca i criteriu de analiz a gradului de
expunere a materiei vii, respectiv a publicului n spaiul locuit.
n cadrul programului naional Orizont 2000, INCERC Filiala Iai a avut n derulare o tem de
cercetare [11] intitulat Studiul influenei cmpurilor electromagnetice ce apar n cldirile civile,
asupra condiiilor de exploatare, care pe parcursul 1996-1998, a adus aportul:
- unui prim studiu documentar n domeniul construciilor de locuine (la nivelul anilor 19951998), privind stadiul cercetrilor impactului confortului electromagnetic asupra oamenilor i
habitaiei cu enunarea principalilor parametri care ar influena acest tip de confort n locuire.
Semnalarea faptului c nu exista practic la acea data noiunea de un criteriu de
- o analiz succint a posibilitilor tehnice la acea dat pentru cercetarea lor experimental n
situ i n laborator i cteva exemple prin studii de caz din alte ri, a unor situaii critice de amplasare
a cldirii din perspectiva influentelor EMG.
o sintez privind abordarea conceptului de confort electromagnetic n state ale lumii (SUA, UK,
Suedia, Canada) i a unor strategii de cercetare experimental, cu problemele specifice pe care le
ridic supravegherea cmpurilor electromagnetice n interiorul i n apropierea locuinelor. Aparatura
de control i date experientale.
Parcurgerea acestei teme de cercetare a relevat atunci, urmtoarea situaie de fapt, nc valabil i
astzi:
ntr-un domeniu de grani, n care interferena cmpului magnetic i electric natural cu cel
artificial este aproape permanent, n condiiile unei cereri intensive de electricitate pe zone foarte
ntinse i unele foarte aglomerate, statele mai sus menionate au semnalat apariia de probleme majore
de politic a producerii, transportului, distribuiei i receptrii la consumatorul de energie electric,
conjugate cu norme de igien electromagnetic n spaiul de lucru i de locuit.
n consecin au aprut din perioada 1990-1999 recomandri i abordri privind evaluarea i
managementul factorilor de risc n prevenirea efectelor expunerii la cpuri EMG asupra sntii
populaiei. Colaborarea cu cetenii, a devenit un scop utilitar, n semnalarea i stabilirea punctelor
de ncrcare ce depesc limite admisibile, mai ales pentru zonele n care proiectarea nu s-a fcut
considernd i acest criteriu de cmp. n august 1993 aprea primul caz n Europa prin care o familie
din Bolton ddea n judecat compania local de electricitate NORWEB, pentru moartea tragic a
fiului lor de leucemie [1].
76
77
10,95
10,55 m
47,8 m
obinerea unui diagnostic medical, dar expunerea ar trebui s fie suficient de scurt pentru a
menine sczut probabilitatea statistic a cancerelor i sarcoamelor (efecte stochastice), sau a induce
efecte deterministe (ex. nroirea pielii sau cataracte) [4]. Coridor de siguran
7,85 m
11,35 m
14,85 m
78
fields publicat de WHO Regional Office for Europe n 1999, Local authorities, health and
environment briefing pamphlet series; 32, prezent i n 2006 pe site-ul oficial al OMS),
urmtoarele atitudini, exprimate ntr-un limbaj simplu, i pentru public. OMS recunoate oficial c
[7]:
a. privind originea cmpurilor electrice "conectarea unui cablu ntr-o born exterioar
(ex. priz, branament, etc.) creeaz cmpuri electrice n aer care nconjoar aparatul conectat. Cu
ct este mai nalt tensiunea cu att este mai intens cmpul produs. Att timp ct tensiunea electric
poate exista chiar i atunci cnd nu circul nici un curent, aparatul nu trebuie s fie deschis (on) ca s
existe un cmp electric n ncpere care s-l nconjoare."
b - privind cmpurile magnetice produse de curentul alternativ "cmpurile magnetice
sunt create numai cnd curentul electric circul..
Deci cmpurile magnetice i electrice exist mpreun n mediul ncperii. Cu ct este curentul mai
mare, cu att mai puternic este cmpul magnetic. Tensiunile nalte sunt folosite pentru transportul i
distribuirea electricitii, pe cnd n locuine sunt utilizate tensiuni relativ joase. Tensiunile utilizate de
echipamentul din staiile de distribuie variaz puin de la o zi la alta, curenii printr-o linie de
transmisie variaz cu consumul de putere electric."
79
80
140
120
100
80
60
40
20
0
1
200
150
100
50
0
1
Pentru a ncheia acest subiect cu o concluzie mai puin sceptic dect cea a OMS i mai realist
privind susceptibilitatea existenei EHS, n condiii de expunere electromagnetic insuficient sau
incorect supravegheate, menionm n continuare afeciunile enunate prin raportul RALF (diagrama
3), care cuprind n capul listei pe cele dermatologice, urmate de sensibilitatea la lumin/probleme
oculare i oboseal (col.2, 3), probleme legate de inim i de tensiunea arterial (4), dureri de cap,
1
Este cunoscut faptul c mercurul (coninut i n amalgamul dentar) amplific puterea de absorbie n esuturi a
undelor radio i microundelor.
81
11 13 15 17 19 21 23 25
au aprut firme private n strintate, mai puin la noi n ar, care asigur servicii de
supraveghere calificat n urmrirea cmpurilor de radiaie EMG, n zone semnalate ca potenial
periculoase [2], [6];
au aprut n conlucrarea cu ceteanul, chestionare de tip informare - educare i cele pentru
remedierea n amplasamentul cldirii sau n interior a deficienelor de poziionare sau execuie a
instalaiilor electrice sau a echipamentelor care ncarc peste limite admise spaiul unde sunt utilizate.
Detalii n continuare n partea a II - a lucrrii.
Concluzii:
1. Expunerea la cmpuri electromagnetice nu este un fenomen nou. ns perioada anilor 2000
2006, n raport cu semnalrile sporadice din anii 1980-1989 i n contrast cu sesizarea protestatar i
contestat a anilor 1990-1999, a consolidat i statuat oficial cercetarea acestui fenomen, n vederea
reducerii sau ameliorrii lui, n aproape toate statele dezvoltate tehnologic i prin cele mai importante
organisme europene sau mondiale implicate n monitorizarea strii publice de sntate i supraveghere
a mediului, fie administrativ /epidemiologic, fie normativ / tiinific.
2. n evaluarea problemelor de sensibilitate electromagnetic, exist nc, pn n prezent, o
problem de receptare subiectiv dar i de raportare a valorilor percepute a cmpului electric i
magnetic la o valoare de referin unic care s poat exprima n ce msur cuantumul de cmp
82
83
Partea II
Confortul electromagnetic de locuire de la realitate
la ignorare. Analiza cadrului legal pentru dezvoltarea
serviciilor de supraveghere EMG la consumator n domeniul
instalaiilor electrice i automatizrilor pentru construcii.
Part II The Living Electromagnetic Comfort Between Reality And Ignorance.
The Legal Framework Analysis For The EMFields Survey Services Development
To Consumers In the Electrical Installations And Automations Domain for Buildings.
Abstract
Based on the conclusions of the part I of the paper, the part II of the paper approaches:
1. What would be needed to be known as being the living electromagnetic comfort and what would mean
to develop the basis of the electromagnetic hygiene in the living spaces in Romania;
2. The official and legal framework in Romania for EMFields Survey Services Development to seriously
consider the risk management factors concerning the occupational and residential exposure of people to EM
fields;
3. The work area for the building specialists, to provide the communication and proceedings interface to the
wide public as electrical comfort services consumer and resident of the built spaces.
Personal monitoring can provide information to help the public make educated choices about prudent
avoidance;
4. Romania to be helped and still actively supported to be integrated into the general attitude of the EC
countries to have more present organisms with international participation in this domain;
84
expunerii legate de emisiile de cmpuri EMG din diverse surse, care spre exemplu "s-au mai
mult dect dublat pentru cei mai muli dintre canadieni n ultimii 5 ani [4]", n special datorit
creterii foarte mari a posesorilor de telefoane mobile.
Apreciem n acest sens efortul vizibil constructiv al Asociaiei pentru Compatibilitate
Electromagnetic din Romnia, ACER, pentru informarea profesional actualizat de calitate i
seriozitatea abordrii problematicii CEM i expunerii populaiei, cu implicarea n diseminarea
aspectelor practice ale acestui domeniu de cercetare printre specialiti.
85
Fig.1 a.
Fig.1 b.
Fig.1 c.
II.2.11. Nu folosii toat noaptea pturi electrice care se aeaz deasupra aternutului (over
blankets) n timp ce suntei n pat. Ele sunt proiectate s fie utilizate toat noaptea, dar folosesc cureni
ridicai (A) pentru a funciona cu tensiune sczut. Ca urmare genereaz nivele destul de ridicate de
cmpuri EMG n corpul oricui este aezat sub ele.
II.2.12. Spre deosebire de acestea pturile i pernele electrice ce se aeaz sub aternut (under
blankets) nu sunt proiectate s poat fi utilizate cnd consumatorii sunt aezai pe ele. Oricum
asigurai-v ca nu v-ai aezat pe una din ele sau i mai sigur deconectai-le nainte de culcare. Dac
totui nu dorii s le deconectai, asigurai-v c, instalaia electric a casei este n bun funcionare,
iar cablul maro al pturii este conectat la circuitul de mpmntare prin fia de conectare. Aceste
86
87
88
89
1. Introducere
Lucrarea de fa a fost inspirat de situaii frecvent ntlnite n practic cum sunt:
a. din motive individuale de rspuns termic al corpului, dei este asigurat n ncperi necesarul
de cldur (min. + 18 22 oC), fie la locul de munc, fie acas, persoane aparinnd ambelor sexe, de
vrste diferite, stau extrem de aproape de aparatele electrice de nclzit ]n special de cele portabile
(care pot fi radiatoare electrice cu ulei, radiatoare electrice cu rezistene i convecie de aer, aeroterme,
plci radiante de perete, etc). Gestul se repet zilnic, pe parcursul mai multor ore de funcionare a
aparatului i pentru perioade lungi de timp din anotimpul friguros sau toamn / primvar.
La ntrebarea "de ce stau att de aproape de aparatele de nclzit", rspunsul aproape fr
deosebire, vine sub forma "nu m mai dezghe, nu m mai nclzesc sau nu m pot dezlipi de cldura
lor " !
b. din aceleai motive individuale de rspuns termic al corpului, asociate cu cele de rspuns
electromagnetic la mediu, cei care utilizeaz perne sau pturi electrice pentru nclzit n aternut sau
puse deasupra pturii, au tendina care le devine obicei, s in aparatul de nclzit n funciune i dup
ce de fapt i-au ridicat temperatura corpului suficient sau patul s-a nclzit, sub motivul c "nu vor s
se rceasc aternutul sau corpul"!
c. ntrebarea din punct de vedere tehnic, dac utilizatorii acestor aparate de nclzit electric tiu
minimal ce alctuire are aparatul i ce efect poate avea asupra organismului lor o folosire ndelungat
neasociat cu un discernmnt n cunotin de cauz. Este ceea ce n termenii "evitrii prudente" din
principiile de prevenire a expunerilor necontrolate la emisii electromagnetice, se exprim n
recomandrile din campaniile de reducere a cmpurilor EMG prin "instruirea personal n
monitorizarea utilizrii poate furniza informaii care s ajute publicul s aib opiuni "educate" (n
englez "educated options"), adic n limba romn s utilizeze un aparat n cunotin de cauz.
n sensul celor de mai sus, lucrarea propune cteva observaii tehnice privind ce ar mai fi de
adugat n acest sens:
a. despre erorile n utilizarea aparatelor electrice de nclzit privind nelegerea principiul de
funcionare la utilizator i a prilor lor constructive emisive de cmp electromagnetic ntr-un
anumit cuantum care poate fi duntor dac se ignor modul corect de folosire;
90
91
92
PE 1
PE 2
PE 2
9
4
3
10
1
U = 220 V
11
Fig. 2.1.4 - 11 puncte de msur pentru PE 2;
22 puncte de msur pentru PE 1 i PE 2 alturate;
Valorile msurate ale intensitii cmpului magnetic B (mGauss) sunt cuprinse n domeniul
0,98 2,2 mG, cu valori maxime e 3,5 -6 mG n centrul lor (poz. 4), constant i la 10 i la 20 cm n
jurul pernei electrice, att msurat direct pe aparat, ct i acoperit cu 3 - 15 cm grosime de material
93
E (V/m)
I
II
III
IV
V
0 5,9
6,0
6,1 8,9
9,0 13,9
> 14
Normal
Prag de risc
Periculos
Foarte periculos
Extrem de periculos
B (nT)
1nT = 10
-9
B (mG)
T
0 64
65
66 99
100 249
> 250
1mG = 10 - 3 G = 1-7 T
0 0,64
0,65
0,66 - 0,99
1 - 2,49
2,5
94
95
6
4
2
Fig. 2.2.2
Legend:
panouri electrice Calunteg Confort, montate pe un perete interior;
1 dormitor, 2 dormitor, 3 baie, 4 dormitor, 5 hol, 6 teras
96
Fig. 2.2.4 - Plac mare n raport cu dimensiunile utilizatorului, n timpul fixrii pe perete
97
98
99
101
102
103
104
Fig.1 b.
Fig. 1a, b lamp fluorescent de veghe, 220 V, 3W, conectat la reea prin circuitul de
priz.
a11. Nu folosii toat noaptea pturi electrice care se aeaz deasupra aternutului (over
blankets) n timp ce suntei n pat. Ele sunt proiectate s fie utilizate toat noaptea, dar
folosesc cureni ridicai (A) pentru a funciona cu tensiune sczut. Ca urmare genereaz
nivele destul de ridicate de cmpuri EMG n corpul oricui este aezat sub ele.
a12. Spre deosebire de acestea pturile i pernele electrice ce se aeaz sub aternut
(under blankets) nu sunt proiectate s poat fi utilizate cnd consumatorii sunt aezai pe ele.
105
106
107
108
109
Nivel pardoseal
L =18 cm
Poz.6
H = 126 cm
Pos 5
Pos 4
60 cm
Poz.4
Pos 3
Poz.2
20 cm de la
poz. 1 i
85 cm de la
pardoseal
Poz.1
20
Fotoliu
25
30
20 cm
10
35
Poz.1
65 cm
de la
pardoseal
65 cm
Poz.2
40 cm
Poz.3
65 cm
Poz.5
126 cm
66 cm
Pos 6
111
1 cm
Poz 1
10 cm
20 cm
x - distana (cm)
Poz 17
Poz 9
30 cm
50 cm
80 cm
1m
y - distana (cm)
Zona S1 montaj
balast i elemente
de circuit
Zona S2 montaj
balast i elemente
de circuit
9 10 11
80
11
22
4 3,5
>>
>>
>>
200*
200*
200*
la 10
>120* >120* 100
cm
la 20
20-25 20-25 20
cm
la 30
5 -7** 4 -7
4 -6
cm
la 50
2
2
2
cm
la 80
0,4
0,4 0,4
cm
la 1 m
0,4
0,4
0,4
2,5 2
6,5 6,5
1-2
2,5 2,5
1- 2
2,5
12
13
14
11
105
2,5 -5 8,5-14
3,5
6,5
3,5
50
15
16
17
>>
>>
>>
200*
200*
200*
>120* >120*
13-15 25-40
100
35-50 25-35
4,5
10
15
0,3
0,3
1,4
0,4
0,2
0,3
0,3
0,3
Not: Valorile maxime ale intensitii cmpului magnetic B, n valoare efectiv sunt cele msurate n
zonele S1 i S2 din dreptul poziiei balasturilor i a circuitului de alimentare.
* - valori limitate de posibilitile de msur ale scalei aparatului.
** - domeniul de variaie al B n aceleai puncte de msur este influenat de starea vremii i variaii ale
tensiuni de la reea.
Tabel nr. 1.2.2 Valori msurate ale intensitii cmpului electric E ( V/m )
Poz.
ms
la 1-3
cm
1000
>1000
>> 1000
la
10 cm
la
20 cm
la
30 cm
la
50 cm
la
80 cm
la
1m
>>
100 160
90 100
70-80
85
350
25
30
10
15-20
40
20
50
10
11
12
13
250 250
900 . >1000
15
160
70
15 - 25
15 - 25
16
17
>> 1000
>1000
>1000
350.350 250
160
50
14
>> 1000
>> 1000
255
50
15 - 25
900 . >1000
350
150
70
15 - 25
145 110
85 70
70
40
30
25
20
10
10 12
Not: Valorile msurate ale E sunt mai mari pe timp de ploaie sau foarte umed i nnorat i mai
mici cu cca. 10-15% pe timp uscat i foarte cald, temperaturi de 30-34 o C.
Fig. 5a, b - Repartiia distribuiei distribuiei intensitii cmpului electric E ( V/m ) i intensitii
cmpului magnetic B (mGauss) pe lungimea corpului de iluminat (17 poziii de msur - pe axa x) i
7 poziii pa axa y, de la 1100 cm, (conf. schem fig. 3)
113
5a
E (V /m)
2500
2000
1500
1
53
7
9
11
13
15
17
1000
la 100 cm
la 50 cm
la 20 cm
E la 1 cm
500
17 poziii
msur
5b
B (mGauss)
250
200
150
1
53
7
9
11
13
15
17
100
la 100 cm
la 50 cm
la 20 cm
la 1 cm
50
17 poziii
msur
114
115
116
117
SITUATIA AUTORIZARII
INGINERILOR DE INSTALATII ELECTRICE
Prof. dr. ing. Constantin IONESCU SIEAR
e-mail: siear@siear.ro
A. Situaia actual
Regulament pentru autorizarea electricienilor care proiecteaz, execut, verific i
exploateaz instalaii electrice din sistemul electroenergetic. - Revizia 2 Cod ANRE:
55.1.207.0.01.22/12/05 aprobat prin ORDINUL nr.55 din 22.12.2005 este unicul regulament
care reglementeaz atestarea electricienilor i aceasta numai pentru sistemul electroenergetic.
In Capitolul II Scop la Art.3 se precizeaz c Regulamentul stabilete condiiile de
autorizare pentru electricienii care proiecteaz i execut instalaii electrice racordate la
Sistemul Electroenergetic Naional
In Capitolul VII Verificarea proiectelor i lucrrilor de instalaii electrice racordate
la SEN se arat la Art.10. Verificarea proiectelor de instalaii electrice racordate la
Sistemul Electroenergetic Naional se face de ctre specialiti atestai de Ministerul
Economiei i Comerului ca Verificator de proiecte iar la Art.11 Verificarea instalaiilor
electrice racordate la Sistemul Electroenergetic Naional se va face de ctre specialiti atestai
de Ministerul Economiei i Comerului ca Responsabil tehnic cu execuia
In Capitolul VIII Autorizarea electricienilor care desfoar activiti de proiectare i
execuie a instalaiilor electrice la Art.12 (1) Atestarea electricienilor care desfoar
activiti de proiectare/executare a instalaiilor electrice racordate la SEN, se realizeaz de
ctre Autoritatea competent, n conformitate cu prevederile Regulamentului
La Art.13 (1), (2) se arat c autorizrile sunt de:
tip A pentru proiectarea instalaiilor electrice
tip.B - pentru executarea instalaiilor electrice
Pentru fiecare tip de autorizaie tip A i B sunt prevzute cte patru grupe de
competene: gradul I, gradul II, gradul III i gradul IV.
La Art.14 sunt date tipurile i gradele.
In Capitolul IX sunt date condiiile de autorizare pentru proiectare i executare de
instalaii electrice
B. Comentarii
1. Proiectantii de sisteme energetice sunt absolventi ai facultatilor de Energetica
Un regulament elaborat chiar de ANRE nu poate limita competentele absolventului de
facultate . Regulamentul poate stabili conditiile de autorizare a executantilor de lucrari din
SEN de la muncitor, maistru pana la inginer (sef echipa, sef lot,), dat fiind importanta si
pericolul unor astfel de lucrari pentru societate.
2. Verificatorii de proiecte atestati de Ministerul Economiei si Comertului, prin propriul
statut, sunt verificatori de proiecte tehnologice. Instalatiile electrice aferente unor
echipamente, instalatii tehnologice de sine statatoare etc. Instalatiile electrice racordate la
SEN sau la alte surse proprii sunt verificate de verificatori atestati de MTCT conform Legii
nr.10 din 1995 privind calitatea lucrarilor din constructii in conditiile Regulamentului de
verificare aprobat prin HG nr.925 din 1995. In nici un caz , proiectele de instalatii electrice
118
Propuneri
119
120
121
123
124
Conf. dr. ing. Clin CIUFUDEAN - Universitatea tefan cel Mare Suceava
e-mail: calin@eed.usv.ro
1. Introducere
Sistemul interactiv pentru pentru semaforizarea ecologic a interseciilor este un sistem
automat destinat conducerii traficului rutier, capabil s controleze o intersecie semaforizat i
s se adapteze n funcie de trafic pentru a acorda prioritate mainilor aflate pe sensul pe
care se acumuleaz o cantitate mai mare de noxe provenite de la motoarele cu combustie.
Acest sistem a fost realizat n cadrul Universitii tefan cel Mare din Suceava, respectiv n
laboratorul de Sisteme Automate Discrete al Facultii de Inginerie Electric i tiina
Calculatoarelor.
2. Suportul hardware al sistemului interactiv de semaforizare ecologic
Obiectivele trasate de acest proiect presupun realizarea unui mecanism de ecologizare a
interseciior rutiere. Ideea de la care s-a plecat a fost aceea a detectrii noxelor din intersecie
cu ajutorul unor senzori de gaze i n funcie de rezultatele transmise de aceti senzori s se
determine sensul de circulaie pe care se afl autovehicule care produc mai multe noxe i
ncercarea meninerii acestora un timp ct mai scurt n intersecie prin micorarea timpului de
afiare a culorii roii la semafor. Printre noxele aflate n componena gazelor de eapament
amintim dioxidul de sulf, plumbul, hidrocarburile, compusi organici, metanul, etc. Aceste
substane duneaz sntii i implementarea acestui sistem ar trebui s fie realizat n
interseciile din vecintatea unor coli, spitale, rezervaii, etc.
Senzorii utilizai n realizarea proiectului sunt senzori de CO2. Datele furnizate de
senzor sunt transmise ctre unitatea de control a interseciei wireless cu ajutorul unui modul
de emisie-recepie, eliminnd astfel inconvenientul folosirii cablurilor i oferind libertate n
alegerea locului de amplasare a senzorului. Modulul de emisie-recepie este un kit de
dezvoltare oferit de Microchip (Kitul de dezvoltare rfPIC Development Kit 1). Modelul rfPIC
Development Kit 1 ofer inginerilor de proiectare o modalitate uoar de evaluare a
conexiunilor fr cablu de detectare i control unidirecionale, de mic putere, ntr-un
domeniu mic, pentru aplicaii incorporate de control pe baza microcontrolerului rfPIC12F675
Flash, a transmitorului UHF RF i a receptorului rfRXD0420. Este alctuit din module
transmitoare i receptoare care suport o modulaie a amplitudinii de manipulare a
transferului - Amplitude Shift Keying (ASK) - la 315 i 433 MHz.
2.1
ntr-o definiie succint senzorul este un sistem destinat determinarii unor proprieti,
cuprinznd att traductorul, care transform marimea de intrare n semnal electric util, ct i
circuite pentru adaptarea i conversia semnalelor, i eventual pentru prelucrarea i evaluarea
informaiilor. Exist foarte multe clasificri ale senzorilor i traductoarelor: cu sau fr
125
126
2)
(3)
(4)
Unde:
P(co2) presiunea parial a CO2
Ec valoare constant
R constant de gaz
T temperature (K)
F constanta lui Faraday
Monitoriznd fora elctromotoare care se genereaz ntre cei doi electrozi, se poate msura
concentraia de CO2.
2.2 Microcontrolerul rfPIC 12F675
Este un microprocesor cu arhitectur RISC ce ofer performane ridicate. Setul de
instruciuni este format din 35 instruciuni. Toate instruciunile sunt executate ntr-un singur
ciclu de ceas (200 ns), nafara ramificaiilor care sunt executate n doi cicli.
Viteze de operare:
- oscilator intern (4 MHz) de mare precizie ( 1%), calibrat din fabric;
- 20 MHz pentru oscilator cu cuar sau intrare de ceas;
- 4 MHz pentru oscilator extern RC sau oscilator cu cuar;
- 200 ns pentru un ciclu instruciune.
Microprocesorul dispune de capaciate de ntreruperi, are o stiv hardware cu 8 nivele,
diferite modaliti de adresare a memoriei: adresare direct, adresare indirect i adresare
relativ. Caracteristicile perifericelor:
- memorie:
- 1024 x 14 cuvinte memorie de program de tip FLASH;
- 64 x 8 octei memorie de date (SRAM);
- 128 x 8 octei memorie de date tip EEPROM;
- memoria FLASH suport 100000 scrieri;
- EEPROM-ul suport 1000000 scrieri.
- 6 pini de intrare/ieire cu control individual de direcie;
- Comparator analogic cu 16 nivele de referin interne;
- Convertor analog/digital cu rezoluie de 10 bii i cu 4 canale de intrare programabile;
- Timer0: temporizator/numrtor pe 8 bii;
- Timer1: temporizator/numrtor pe 16 bii;
- 5 s timp de wake-up din modul SLEEP carcteristic unei tensiuni VDD = 3V.
Transmitorul UHF cu modulare ASK/FSK prezint urmtoarele caracteristici:
- vitez de date pentru modularea ASK: 0 40 Kbps;
- vitez de date pentru modularea FSK: 0 40 Kbps;
- putere de ieire: ntre +10 dBm i -12 dBm n 4 trepte;
- putere consumat pentru transmisie ajustabil;
- diferite frecvene de transmisie.
Microcontrolerul rfPIC12F675 este capabil s transmit date modulate n amplitudine
(ASK = Amplitude Shift Keying) sau modulate n frecven (FSK = Frequency Shift Keying).
127
128
Dup cum se oberv din figur sistemul este compus din mai multe module:
Modulul denumit Senzor Sx este compus din senzorul efectiv i dintr-un circuit
instrumental;
Modulul TX reprezint modulul de transmisie i are ca element principal
microcontrolerul rfPIC 12F675 i realizeaz conversia semnalului din analogic n digital i
transmiterea acestuia n ether;
Modulul RX reprezint modulul de recepie i are ca element principal
microcontrolerul rfRFD0420;
Un modul de adaptare pentru comunicaie serial pentru interconectarea cu PC;
Unitatea de comand i control, realizat n jurul microcontrolerului PIC 16F648A,
care este dispozitivul care comand funcionarea semaforului.
Module de alimentare.
3.1. Principiul de funcionare
Senzorii amplasai n intersecie n prezena dioxidului de carbon, provenit din gazele
de eapare a autovehiculelor, vor furniza la intrarea circuitului de condiionare un curent care
depinde de concentraia de CO2 detectat. Circuitul de condiionare este de fapt un
amplificator instrumental ce conine 3 amplificatoare operaionale. Acesta preia semnalul de
129
130
131
132
ACTUALITATE SI PERSPECTIVA
IN SISTEMELE DE MANAGEMENT ALE CLDIRILOR
Prof. dr.ing Constantin Ionescu UTCB
Drd.ing. Stefan Alecsandru SIEAR
Ca urmare a aciunii de economisire a energiei n cldiri, n prezenta lucrare se arat
c o contribuie important n acest demers este constituit de introducerea sistemelor de
management a cladirilor-Building Management System (BMS). Este artat stadiul actual i
unele preocupri de viitor.
Energy saving has become a major challenge over the last decade. The ultimate
solution for this issue, for large and medium buildings, is using an integrated control and
monitoring automation system known as Building Management System BMS. This paper
presents the state of the art and future trends in building automation.
1. Generaliti
In ultimii douzeci de ani funcionarea cldirilor bazat pe tehnologia informaiei, din
mai multe puncte de vedere (utiliti, administrativ, financiar), a avut o evoluie
spectaculoas.
Astzi o cldire modern este dotat cu infrastructur electronic care i permite s se
adapteze i s raspund n mod permanent la schimbarea condiiilor avnd ca rezultat
utilizarea eficient a resurselor energetice, mbuntirea condiiilor de confort i creterea
gradului de securitate a celor ce o ocup.
Infrastructura electronic (creierul) cldirii care conduce i monitorizeaz funcionarea
echipamentelor i instalaiilor aferente este cunoscut n literatura de specialitate cu numele de
Sistem de Management al Cladirii (SMC) sau Building Management System (BMS).
Conceptul de BMS aferent unei cldirii cuprinde totalitatea aparatelor, echipamentelor,
sistemelor locale de automatizare a instalatiilor (hidraulice, nclzire, ventilare-climatizare,
iluminat, ascensoare, prevenirea i stingerea incendiilor, control acces, supraveghere,
antiefracie etc.) si reelelor de comunicaie care asigur supravegherea si controlul
functionarii instalatiilor din cladire. BMS implementeaz programe de utilizare eficient a
energiei, n condiii de siguranta la incendiu, securitate, mediu si reduce cheltuielile de
mentenan
Cladirea bazata pe tehnologie si a carei functionare este asigurata de un sistem
automatizat integrat ce asigura managementul fluxurilor informationale si energetice dintr-o
cladire (BMS) este cunoscuta in literatura cu numele de cladire inteligenta (Smart Building ,
Intelligent Building). Pentru a determina nivelul de inteligen la oameni a fost inventat testul
IQ. Sunt preocupri de a stabili nivelul de inteligen i la cldiri.
Datorit limitrilor din punct de vedere hardware si software ale instalaiilor din
cldirile vechi, realizarea unei astfel de infrastructuri este dificil.
BMS este un sistem de automatizare modern cu o arhitectur ierarhizat i distribuit pe
dou sau trei niveluri. Elementele principale sunt computerul central (PC Workstation post
central de comand) i controlerele necesare automatizrii diverselor tipuri de echipamente i
instalaii. Transmiterea informaiilor ntre acestea i computer i invers se face n timp real
prin intermediul unei reele de comunicaii. Controlerele sunt dispozitive electronice , dotate
cu microprocesor, i care au implementai algoritmi moderni de funcionare (PID, EPID,etc.).
PID inseamna Enhanced PID adica PID imbunatatit.
Imbunatatirea provine de la faptul ca controlerul PID este prevazut cu algoritm de tip
fuzzy.
133
134
135
136
137
- 138 -
ON
OFF
Doar
Ventilare
Rcire
Inclzire
23
26
21
24
Temperatura aerului interior
Fig.3 Zero Energy Band
- 139 -
- 140 -
- 141 -
- 142 -
- 143 -
L1
e5
e6
e1
e2
L3
L4
e4
e3
L5
(1)
(2)
Prima relaie se refer la locaiile active iniial (L4 n Fig. 1) iar a doua relaie este
valabil pentru locaiile inactive iniial. Variabilele logice au urmtoarea semnificaie:
i : condiia de iniializare a automatului,
sn : condiia de setare a bitului n,
144
10000
01000
L1
e5
e6
00100
e1
L2
e2
00010
L4
L3
e7
e4
e3
00001
L5
(3)
r4 = x3t x4t e3
(4)
x4t = x1t e1 + x2t e2 + ( x3t x4t e3 )x4t + i = x1t e1 + x2t e2 + ( x3t + e3 ) x4t + i
145
(5)
(6)
Se observ c pentru automate tip maina de stare condiia de resetare nu mai necesit
validarea pentru declanarea tranziiei posterioare. Aceast simplificare a metodei este
important atunci cnd implementarea automatului se face cu automate programabile care
folosesc automate elementare tip RS cu prioritate la pornire. Se prezint n continuare un
exemplu de implementare pentru un automat cu APL pentru anclanarea automat a rezervei
tehnologice.
Schema tehnologic cu echipamentul de automatizare pentru o instalaie format dintrun rezervor i dou pompe este prezentat n Fig. 3. Scopul automatizrii l constituie
pstrarea nivelului la o valoare cuprins ntre un minim i maxim chiar i n condiiile
avarierii uneia dintre cele dou pompe. Pentru aceasta se folosete traductorul de nivel 1,
automatul programabil 2 i elementul de execuie 3. Se specific intrrile i ieirile din
automatul programabil, care au urmtoarea semnificaie:
I1 intrarea 1 format din contactul normal deschis al unui buton n impuls pentru
selectarea pompei P1 pentru regimul de lucru i al pompei P2 pentru regimul de rezerv
tehnologic.
I2 intrarea 2 format din contactul normal deschis al unui buton n impuls pentru
selectarea pompei P2 pentru regimul de lucru i al pompei P1 pentru regimul de rezerv
tehnologic.
I3, I4 intrrile 3 i 4 formate din contactele normal nchise ale traductoarelor de avarie
ale pompelor P1, respectiv P2. La apariia avariei contactele se deschid. n felul acesta se
asigur funcionarea n regim de fail safe.
I5 intrarea 5, un contact normal nchis n impuls, pentru iniializarea automatului.
I6 intrarea 5, format dintr-un contact normal deschis, n impuls, pentru oprirea
pompelor.
I7 intrarea 7, format dintr-un contact normal deschis, n impuls cu cheie, pentru
confirmarea avariei.
Q1, Q2 ieirile 1 i 2, formate din contacte normal deschise, pentru acionarea i
semnalizarea acionrii pompelor P1 i P2.
Q3, Q4 ieirile 3 i 4, formate din contacte normal deschise, pentru semnalizarea prin
plpire a avariei pompelor P1 i P2. Dup acionarea butonului de oprire de la intrarea I6
plpirea nceteaz, dar lmpile semnalizeaz n continuare avaria pn la confirmarea ei cu
ajutorul butonului I7.
Q5, Q6 ieirile 5 i 6, formate din contacte normal deschise, pentru semnalizarea
selectrii pompei P1, respectiv P2, pentru funcionarea n regim de lucru.
Algoritmul de funcionare al automatului este descris de reeaua Petri din Fig. 4. Dup
pornirea APL locaia L10 este activ. Acionarea butonului de iniializare i5 activeaz locaia
L11. Din aceast stare se poate selecta regimul de lucru al pompelor Q1 i Q2 care poate fi de
lucru sau de rezerv. Reeaua este simetric i din aceast cauz n continuare se va analiza
doar situaia n care se alege pompa Q1 de lucru i se activeaz locaia L12, situaie
semnalizat de lampa Q5. Nivelul din rezervor poate lua trei valori.. Dac este mai mic dect
min1=2,9 atunci a1=1, se activeaz L13 n care pornete pompa Q1. Nivelul va crete i
atunci cnd va depi Max=3 evenimentul a3=1 i pompa Q1=0 se oprete deoarece se
activeaz din nou L12. Acesta este ciclul repetitiv principal de funcionare. Dac apare o
146
P2
P1
LZ
3
Q1 .. Q6
I3,i4
I1,i2,i5,i6,i7
LKA
2
ia
LET
V2
In cadrul unei avarii funcionale echipamentul nu este scos din funciune ci lucreaz cu performane
reduse.
147
i5
L11
i6
i6
i6
i6
i1 i2
Q1 = 1
Q2 = 1
L14
i6
i2 i1
i6
Q1 = 1
Q6 = 1
Q5 = 1
L12
L15
Q2 = 1
L17
a3
a3
a2 d 4
Q1 = 1
L13
i3 + i4
a3
a3
a1
c16 a2
Q2 = 1
L16
c13 a2
i3
a2 d 5
a1
i4
Q3 1
i3 + i4
Q4 1
Q2 = 1
Q3 1
L18
L20
i6
L21
i4
Q3 = 1
i6
L22
Q1 = 1
L19
i3
Q3 = 1
Q4 = 1
Q4 1
i6
i7
L23
Q4 = 1
Fig. 4 Caietul de sarcini sub form de reea Petri pentru anclanarea automat a
rezervei tehnologice
148
Codul
Aut. elementar
L10
00000000000000000000000
L11
10000000000000000000000
M11
L12
01000000000000000000000
M12
L13
00100000000000000000000
M13
......
.........
........
L21
00000000000000000000100
M21
L22
00000000000000000000010
M22
L23
00000000000000000000001
M23
149
150
151
152
153
UPS-urile
pasive
(passive-standby) au fost
denumite anterior UPSuri off line. Denumirea
acestei topologii provine
din faptul c sursa de
tensiune st "de veghe" i
alimenteaz consumatorul
din
bateria
de
acumulatoare
prin
intermediul invertorului
numai n situaia cderii
tensiunii reelei. Aceste
tipuri de UPS-uri au ca
avantaje costul redus i
zgomotul redus n modul
de funcionare on line.
Principalele dezavantaje
154
155
Fig.4 - Formele de und ale tensiunii i curentului, valorile puterilor activ, reactiv i aparent,
ale factorului de putere i spectrul armonic determinate pentru un UPS (1400 VA) fr sarcin
(n regim de ncrcare a acumulatorilor)
Fig. 5 - Formele de und ale tensiunii i curentului, valorile puterilor activ, reactiv i
aparent, ale factorului de putere i spectrul armonic determinate pentru un UPS 30 kVA
(produs MGE UPS SYSTEMS) care deservete o parte din echipamentele informatice de la
BRD Turnul din Piaa Victoriei
156
157
Specificaii:
5 intrri digitale (0= mas, 1= deschis). Sunt prevzute butoane de test pe plac
2 intrri analogice cu opiune de amplificare i atenuare.
Test de alimentare cu +5 V cu indicator cu led
8 ieiri digitale cu colector n gol (max. 50 V/100 mA). Test de funcionare cu leduri.
158
159
160
Interfaa grafic
Cnd conexiunea s-a realizat cu succes sub butonul Connect va aprea mesajul Card
x connected.
Acum se pot simula intrrile digitale cu ajutorul butoanelor 1-5.
Csuele corespunztoare intrrilor vor rmne bifate pn la eliberarea butoanelor
apsate.
Se pot comanda ieirile digitale prin bifarea uneia sau mai multor csue din zona
Outputs. Cu ajutorul butonului Set All Digital sunt comandate toate ieirile digitale iar cu
butonul Clear All Digital sunt inactivate toate ieirile digitale. Pentru testarea automat a
ieirilor digitale se apas butonul Output test.
Ieirile analogice se pot comanda cu butoanele Set All Analog i Clear All Analog
sau prin acionarea cursoarelor grafice DA1 i DA2.
Contoarele 1 i 2 sunt pe 16 bii i sunt comandate de intrrile digitale 1 i 2. Se poate
testa funcionarea lor prin apsarea butoanelor Inp1 i Inp2 de pe plac. Valoarea din csuele
Counter1 i Counter2 este incrementat cu 1 de fiecare dat cnd un buton este apsat.
Intervalul de citire poate fi selectat cu ajutorul setrilor din zonele Debounce Time (0-2-101000 ms).
Se pot simula intrrile analogice prin acionarea rezistenelor semireglabile ATT1 i
ATT2.
Cursoarele grafice AD1 i AD2 indic pe ecran valoarea tensiunilor de intrare. Valoarea
digital (ntre 0 i 255) se poate citi n partea de jos a cursoarelor grafice.
161
Schema cablajului
Schema electronic
162
163
165
Pagina de autentificare
Pentru a putea accesa interfaa de control trebuie introduse corect utilizatorul i parola
n pagina de autentificare. n funcie de nivelul de acces interfaa de control va avea mai
multe sau mai puine opiuni.
Pentru conectarea logic cu modulul trebuie apsat butonul Open Device. Pe interfaa
de control sunt afiate toate intrrile i ieirile digitale i analogice. n partea de jos se pot citi
valorile intrrilor digitale i analogice iar remprosptarea ecranului (recitirea valorilor) se
face la 2 secunde sau la apsarea butonului Receive. n partea de sus a ecranului se introduc
valorile dorite pentru ieirile digitale i analogice i se comand transmiterea lor cu ajutorul
butonului Send.
Interfaa de control
166
167
168
169
170
MULTUMIM DK EXPO!
LA REVEDERE IEAS 2006!
171
172
173
174
Fig. 1.
Linia derivat este o conexiune cu originea pe bucl (fig. 2). O linie nu poate fi
derivat din alt linie.
175
Fig. 2.
Zonele fizice supravegheate dintr-o cldire vor constitui domenii de detecie. ncperile,
podelele duble i tavanele false vor fi asociate unor domenii proprii de detecie (fig. 3).
Fig. 3.
Seciunea de incendiu este o parte a cldirii separat de restul construciei prin
mijloace specifice de protecie contra incendiilor (fig. 4); n cazul apariiei unui incendiu, ea
se va nchide pentru a mpiedica rspndirea focului n seciunile de incendiu vecine.
Fig. 4.
Grupa de detecie se definete ca fiind asocierea unora sau mai multor detectoare care
dispune de afiarea individual a mesajelor de alarm i a deranjamentelor (fig. 5). ntr-o
grup de detecie vor fi asociate maxim 32 detectoare automate sau 10 detectoare neautomate
(butoane) conform [5,6].
176
Fig. 5.
Izolatoarele, cunoscute i sub denumirea de separatoare, sunt amplasate n soclurile
detectoarelor sau n interiorul butoanelor. Ele sunt utilizate pentru separarea conexiunii n
cazul apariiei unui scurtcircuit pe magistral (bus, bucl).
Componentele conectate pe magistral aflate n grupe de detecie diferite trebuie
separate prin izolatoare (fig. 6).
Fig. 6.
Conform normelor, apariia unui deranjament va trebui s conduc la scoaterea din
funciune a maxim 32 de detectoare automate; aceasta nseamn c la maxim al 32-lea
detector automat conectat ntr-o bucl, trebuie prevzut un izolator. O alt consecin este
faptul c ntr-o grup de detecie pot fi montate maxim 32 detectoare automate.
De asemenea, apariia unui deranjament va trebui s conduc la scoaterea din funciune
a maxim 10 detectoare neautomate (butoane); aceasta nseamn c la maxim al 10-lea buton
conectat ntr-o bucl, trebuie prevzut un izolator. O alt consecin este faptul c ntr-o grup
de detecie pot fi montate maxim 10 butoane.
Segmentul reprezint o parte a buclei limitat de dou izolatoare (fig. 7). Un scurtcircuit
va determina cderea tuturor participanilor aflai pe segmentul respectiv.
177
Fig. 7.
Deranjamentele care pot apare ntru-un sistem automat de detectare i de alarmare la
incendii sunt cauzate de ntreruperi ale buclei (fig. 8), scurtcircuite pe bucl (fig. 9) sau de
extragerea (scoaterea) din bucl a detectoarelor (fig. 10).
Fig. 8.
Fig. 9.
178
Fig. 10.
Fig. 11.
Grupele de acionri sunt ieiri programabile ale sistemului automat aparinnd
centralei de semnalizare sau elementelor montate pe bucl (fig. 11).
Sectoarele de detecie sunt entiti ale buclei sistemului automat de detectare i de
alarmare la incendii (fig. 12). Conform [5,6] pot fi programate maxim 32 de sectoare de
detecie i 32 de sectoare de acionri. Unui sector i pot fi asociate maxim 15 grupe de
detecie, respectiv 15 grupe de acionri.
179
Fig. 12.
Un eveniment produs ntr-un sector de detecie poate determina o reacie ntrziat de
alarmare ntr-un sector de acionri. Aceast acionare poate fi activat intermitent pe durata
unui interval de timp programabil ntre 1...600 secunde, urmnd apoi o activare permanent.
Participanii pe o bucl a sistemului automat de detectare i de alarmare la incendii sunt
constituii din toate echipamentele care pot fi conectate pe bucl: detectoare automate de
incendiu, butoane manuale de alarm i transpondere. Fiecare participant are alocat o adres
unic.
Transponderele pot ndeplini mai multe funcii:
- mrirea numrului de ieiri de acionare ale centralei de semnalizare cu ajutorul unui
anumit numr de relee; se poate monta chiar n central sau n periferie pe bucl.
- ofer ieiri pentru comanda unor LED-uri care, spre exemplu, intr n componena
tablourilor sinoptice amplasate pe etajele cldirii;
- face posibil includerea suplimentar n bucl a unui numr de detectoare automate i
neautomate neadresabile, conectate la intrrile transponderului.
Norme i reglementri
Dispunerea traseelor de plecare i de sosire ale conexiunii unei bucle nu trebuie s se
fac n acelai cablu (fig. 13). Este permis amplasarea mai multor cabluri distincte n acelai
canal de cabluri. De asemenea, este permis trecerea prin acelai cablu (cu mai multe perechi)
a mai multor trasee de plecare pe bucle distincte. Similar, este permis trecerea prin acelai
cablu (cu mai multe perechi) a mai multor trasee de sosire din bucle distincte.
180
Fig. 13.
n cazul apariiei unui deranjament trebuie s fie scos din funciune maxim un domeniu
de detecie, respectiv n cazul conectrii unui transponder grupele conectate la
transponder vor trebui s acopere un singur domeniu de detecie.
Exemplu de proiectare
Planul unei cldiri cu un singur nivel, care conine i amplasarea elementelor
componente ale sistemului automat de detectare i de alarmare la incendii, este prezentat n
figura 14.
Soluia de cablare a sistemului automat, conform celor prezentate mai nainte, se
prezint n figura 15.
181
Fig. 14.
182
*
*
*
*
Fig. 15.
183
BIBLIOGRAFIE
[1] Popescu, D. Automatizri n construcii. Editura MATRIX ROM, Bucureti,
2006.
[2] Ionescu C., Larionescu S., Caluianu S., Popescu D. Automatizarea instalaiilor.
Comenzi automate. Ediia a doua revzut i adugit, 335 pagini, ISBN 973-685-460-4.
Editura MATRIX ROM, Bucureti, 2004.
[3] Popescu D. Contribuii la conducerea ierarhizat a instalaiilor din cldiri. Teza
de doctorat, U.T.C.B., 1998.
[4] Popescu D., Ionescu C. Supravegherea i alarmarea la incendii component a
sistemelor automate din cldiri. Lucrrile Sesiunii de comunicri tiinifice a Facultii de
Pompieri SIGPROT 2001, pag. 101-108, ISSN 1222-1325, Editura Ministerului de
Interne, 2001.
[5] *** - Documentaie tehnic ESSER, 2005. Novar Austria GmbH.
[6] *** - www.novar.at
184
E. Extinderi
Domeniul
A1 Instalaii electrice pentru cldiri civile i industriale
A2 Instalaii de automatizri
A3 Sisteme de alarmare pentru incendiu
A4 Instalaii pentru controlul proceselor industriale
A5 Reele subterane de cabluri pentru distribuia energiei
electrice, iluminat public i controlul traficului (inclusiv
conectri electrice)
A6 Linii aeriene de distribuie a energiei electrice, iluminat
public i controlul traficului (inclusiv conectri electrice)
B1 Instalaii industriale
B2 Linii aeriene de energie electric (inclusiv conectri
electrice)
B3 Reele subterane de cabluri pentru distribuia energiei
electrice (inclusiv conectri electrice)
B4 Instalaii pentru iluminat public
C1 Instalaii industriale
D1 Sisteme de comunicaii pentru cldiri civile i industriale
D2 Reele de calculatoare i instalaii pentru echipamente
periferice
D3 Instalaii pentru infrastructura comunicaiilor
D4 Linii aeriene pentru comunicaii
D5 Linii aeriene pentru comunicaii
E1 Instalaii pentru zone cu risc
E2 Contractri generale
Se poate face constatarea c acesta coincide n cea mai mare parte cu cel cuprins n
regulamentul pentru atestarea calificrii elaborat i aplicat pn n prezent de SIEAR.
n anexa C5 a normei SR CLC/TS 50349/2006 sunt descrise orientativ principalele
activiti i lucrri de instalaii electrice pentru toate domeniile de mai sus: A1A6;
B1.B4; C1; D1 D5 i E1, E2.
Este important de precizat c o societate (firm, antreprenor) poate solicita certificatul
de calificare nu numai pentru execuie ci i pentru proiectarea, sau numai pentru proiectare
sau execuie.
Pentru societile (firmele) ce nu au experiena cerut pentru un domeniu de calificare
ca debutant n acel domeniu.
Dup doi ani debutantul este reevaluat pentru calificare. Dac acesta nu aduce
dovezi concludente pentru a evidenia depirea stadiului de debutant i pierde calificarea i
devine necalificat. Prin excepie calitatea de debutant poate fi prelungit cu un an.
Certificatul de calificare este valabil timp de trei ani. Cu ase luni nainte de expirarea
termenului, organismul care a fcut calificare aduce la cunotina societii calificate
necesitatea renoirii procedurii de evaluare. n urma revizuirii calificrii organismul de
calificare trebuie s decid:
a) s menin calificarea;
b) s extind sau s restricioneze domeniile calificrii, dup caz;
186
Norma SR CLC/TS 50349.2006, descris succint mai sus, va putea fi aplicat dup ce
va fi stabilit o autoritate naional pentru certificarea organismelor de calificare.
SIEAR-ul va sista temporar activitatea de certificare profesional a ntreprinderilor,
urmrind a face demersurile necesare pentru obinerea calitii de organism de calificare.
187
188
189
190
191
19
04
192
193
194
C.I. Budeanu,contribuii
deosebite la definirea
regimului deformant
Academician Profesor
Remus Rdule
195
196
Anexa
Lista presedintilor CEI
2005
Mr. R. Tani
Italy
2002
Dr. S. Takayanagi
Japan
1999
Mr. M. R. Fnfschilling
Switzerland
1996
Mr. B. H. Falk
1993
Dr. H. Gissel
Germany
1990
Mr. R. E. Brett
Australia
1986
Mr. G. R. C. McDowell
United Kingdom
1983
Mr. A. Djou
France
1980
Mr. W. A. McAdams
1977
Japan
1974
1973
Dr. G. L. Palandri
Italy
1970
Mr. S. E. Goodall
United Kingdom
1967
Mr. P. Ailleret
France
1964
Romania
1961
Prof. G. de Zoeten
Netherlands
1958
Dr. I. Herlitz
Sweden
1955
Dr. P. Dunsheath
United Kingdom
1952
Dr. H. Osborne
1949
Dr. M. Schiesser
Switzerland
1946
Mr. E. Uytborck
Belgium
1938
Prof. L. Lombardi
Italy
1935
Mr. J. Burke
1930
Sweden
1927
Netherlands
1923
Mr. G. Semenza
Italy
1919
Dr. C. O. Mailloux
1913
Mr. M. Leblanc
France
1911
Germany
1908
1906
United Kingdom
197
1906
1908
1911
1913
1919
1923
1927
1930
Dr. C. O. Mailloux
United States of
America
1935
1938
1946
1949
198
1955
1958
1961
Dr. P. Dunsheath
United Kingdom
Dr. I. Herlitz
Sweden
Prof. G. de Zoeten
Netherlands
1964
1967
1970
1973
Mr. P. Ailleret
France
Mr. S. E. Goodall
United Kingdom
Dr. G. L. Palandri
Italy
1974
1977
1980
1983
Mr. W. A. McAdams
United States of
America
Mr. A. Djou
France
199
1986
1990
1993
1996
Mr. G. R. C. McDowell
United Kingdom
Dr. H. Gissel
Germany
Mr. B. H. Falk
United States of
America
1999
2002
2005
Mr. M. R. Fnfschilling
Switzerland
Dr. S. Takayanagi
Japan
Mr. R. Tani
Italy
200
201
202
203
204
205
206
207
200 euro
50 lei
20 lei
10 lei
208
COMITET
TEHNIC
CEI
Statutul Romaniei
Comitet tehnic
ASRO n oglind
Terminology
Rotating machinery
Information structures, documentation and
graphical symbols
Participant
Observator
Participant
173
1
SC 3C
SC 3D
TC 4
TC 5
TC 7
TC 8
TC 9
TC 10
TC 11
TC 13
Participant
Participant
Observator
Observator
Participant
Observator
Participant
Observator
Participant
Participant
TC 14
TC 15
Power transformers
Standards on specifications for electrical
insulating materials (Provisional)
Participant
Participant
TC 16
Observator
TC 17
SC 17A
SC 17B
SC 17C
Participant
Observator
Participant
Observator
SC 17D
Participant
Participant
SC 18A
TC 20
TC 21
SC 21A
Participant
Participant
Participant
Participant
TC 22
SC 22E
SC 22F
Observator
Participant
Observator
SC 22G
Participant
TC 23
SC 23A
SC 23B
SC 23C
Electrical accessories
Cable management systems
Plugs, socket-outlets and switches
World-wide plug and socket-outlet systems
Participant
Participant
Participant
Participant
TC 1
TC 2
TC 3
15
16
17
18
19
20
21
TC 18
22
23
24
25
26
27
28
29
30
31
32
33
34
Denumirea CT CEI
209
2
2
2
133
134
224
167
4
264
165
164
3
5
7
8
8
9
8
9
142
142
159
161
161
36
36
36
36
11
11
11
11
Participant
SC 23F
SC 23G
SC 23H
SC 23J
TC 25
TC 26
TC 27
TC 28
TC 29
TC 31
SC 31G
SC 31H
Connecting devices
Appliance couplers
Industrial, plugs and socket-outlets
Switches for appliances
Quantities and units, and their letter symbols
Electric welding
Industrial electroheating equipment
Insulation co-ordination
Electroacoustics
Participant
Participant
Participant
Participant
Participant
Participant
Observator
Observator
Participant
Participant
Participant
Participant
SC 31J
Participant
137
50
TC 32
SC 32A
Fuses
High-voltage fuses
Participant
Observator
12
12
51
SC 32B
Low-voltage fuses
Participant
12
52
SC 32C
Miniature fuses
Participant
12
53
TC 33
Power capacitors
Participant
37
54
TC 34
Participant
131
55
SC 34A
Lamps
Participant
131
56
SC 34B
Observator
131
57
SC 34C
Participant
131
58
SC 34D
Luminaires
Participant
131
59
TC 35
Observator
141
60
TC 36
Insulators
Participant
15
61
SC 36A
Insulated bushings
Participant
15
SC 36B
Participant
15
64
SC 36C
TC 37
Participant
Observator
15
311
65
SC 37A
Observator
311
SC 37B
Participant
311
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
62
63
66
Intrinsically-safe apparatus
Apparatus for use in the presence of
combustible dust
11
11
11
11
11
173
129
31
162
26
137
137
137
67
TC 38
Instrument transformers
Participant
68
TC 39
Electronic tubes
Participant
17
TC 40
Observator
135
Participant
70
TC 42
71
TC 44
Participant
23
72
TC 45
Nuclear instrumentation
Participant
16
73
SC 45A
Participant
16
74
SC 45B
Participant
16
Participant
160
Coaxial cables
Participant
160
69
TC 46
75
76
SC 46A
210
Observator
160
79
SC 46F
TC 47
Participant
Participant
145
17
80
SC 47A
Integrated circuits
Participant
17
SC 47D
Participant
17
Observator
145
77
78
81
TC 48
82
83
SC 48B
Connectors
Participant
145
84
SC 48D
Observator
145
TC 49
Observator
18
Observator
Participant
20
87
TC 51
TC 55
21
88
TC 56
Dependability
Participant
144
TC 57
Observator
140
90
TC 59
Observator
238
91
SC 59A
Electric dishwashers
Participant
238
92
SC 59C
Heating appliances
Participant
238
93
SC 59D
Participant
238
94
SC 59F
Observator
238
SC 59K
Participant
238
SC 59L
Participant
238
Observator
239
85
86
89
95
96
TC 61
97
98
SC 61B
Observator
239
99
SC 61C
Observator
239
SC 61D
Observator
239
SC 61E
Observator
239
Observator
255
Observator
239
Observator
239
Participant
22
SC 62A
Participant
22
SC 62B
Participant
22
SC 62C
Participant
22
SC 62D
Electromedical equipment
Participant
22
TC 64
Observator
136
111
TC 65
Participant
23
112
SC 65A
System aspects
Participant
23
113
SC 65B
Devices
Participant
23
100
101
102
103
SC 61F
SC 61H
SC 61J
104
105
TC 62
106
107
108
109
110
211
SC 65C
Digital communications
Participant
23
115
SC 65D
Analyzing equipment
Participant
23
TC 66
Participant
24
TC 68
Observator
25
TC 69
Observator
333
Participant
29
116
117
119
TC 70
120
TC 72
Observator
130
121
TC 73
Short-circuit currents
Observator
158
122
TC 76
Participant
38
123
TC 77
Electromagnetic compatibility
Participant
30
124
SC 77A
Participant
30
125
SC 77B
Participant
30
126
SC 77C
Participant
30
127
TC 78
Live working
Observator
176
128
TC 79
Observator
27
TC 80
Participant
143
130
TC 81
Lightning protection
Observator
346
131
TC 82
Participant
35
TC 85
Participant
166
133
TC 86
Fibre optics
Participant
138
134
SC 86A
Observator
138
SC 86B
Participant
138
136
SC 86C
Participant
138
137
TC 87
Ultrasonics
Participant
26
138
TC 88
Wind turbines
Observator
174
139
TC 89
Observator
33
140
TC 90
Superconductivity
Participant
34
141
TC 91
Participant
193
142
TC 94
Observator
128
143
TC 95
Participant
128
TC 96
Participant
312
TC 100
Participant
193
TC 101
Electrostatics
Participant
175
TC 103
Participant
Observator
19
118
129
132
135
144
145
146
147
TC 104
148
TC 108
Participant
368
TC 109
Participant
162
149
150
212
TC 110
Participant
17
TC 112
Participant
CISPR
Participant
30
Participant
30
Participant
30
Participant
30
Participant
30
Participant
30
152
153
154
CISPR/SC
A
CISPR/SC
B
155
CISPR/SC
D
156
157
158
CISPR/SC
F
CISPR/SC
I
213
74
111
47
215
216
217
PREZENTARE DE FIRME
218
Servicii de certificare
certificarea sistemelor de management al calitii ISO 9001:2000
4276 organizaii certificate pn la 31.08.2006
219
certificare de produs prin SRAC CERTSERV, organism acreditat pentru certificarea de produs
(certificatul nr. 019C) i desemnat pentru evaluarea conformitii produselor pentru
construcii (HG 622/2004-Directiva 89/106/EEC)
Instruire
Peste 6.500 de participani la cursurile organizate prin SRAC SERVICII GRUP SA.
Cursuri de instruire n domeniul sistemelor de management al calitii, mediu, siguranei
alimentului, sntii si securitii ocupaionale, securitii informaiilor etc., precum i cursuri de
formare auditori.
Publicaii
Reviste de specialitate: Calitatea acces la succes (lunar), Asigurarea Calitii (trimestrial)
Cri de specialitate: Manualul Calitii Juran, Istoria Calitii. Un eseu concentrat, Sisteme de
management al calitii n ntreprinderile mici si mijlocii, etc.
220
PRATCO
Proiectare, Asisten Tehnic, Consultan
Echipamente pentru instalaii HVAC, electrice i de automatizare
Misiunea: satisfacerea n cel mai nalt grad a clienilor prin oferirea unor produse i servicii
de nalt calitate, identificarea i implemen-tarea soluiilor tehnico-economice optime pentru
nevoile acestora n domeniul HVAC, al automatizrilor i acionrilor electrice, a distribuiei
energiei.
Istoria: Firm cu capital integral privat, fondat n 1990 i dedicat furnizrii serviciilor i
produselor de calitate pentru industria electroteh-nic i de automatizare, PRATCO a ctigat
un important segment de pia ca urmare a serviciilor de calitate pe care s-a angajat s le ofere
clienilor. PRATCO a fost i nc este implicat n activitatea de cercetare pe care o consider
garania reuitei n viitor.
Calitatea: Angajat s furnizeze servicii i produse de calitate, PRATCO a nceput
demersurile pentru obinerea certificrii Sistemului de Management al Calitii n
conformitate cu standardul ISO 9001.
Produsele: Echipamentele fabricate sau asamblate de PRATCO au un design robust fiind
construite pentru a avea o durat de via ct mai mare. Tablourile electrice i de automatizare
pentru instalaii termice, pentru automatizarea instalaiilor de aer condiionat, clim,
ventilaie, tablourile de distribuie precum i dimensiunea listei de referine demonstreaz
rezistena i durabilitatea produselor noastre.
Dac nu ai ncercat un produs PRATCO, v invitm s o facei. Mcar o dat. De obicei
este suficient pentru ca oamenii s neleag avantajele utilizrii produselor i serviciilor de
cea mai bun calitate.
Acordnd o atenie deosebit calitii produselor oferite, PRATCO a devenit un nume
binecunoscut pe piaa materialelor i echipamentelor electrice. Oferind SOLUII, nu numai
aparate i echipamente, promovnd produse cu un grad nalt de tehnicitate, PRATCO s-a
strduit s impun pe piaa romneasc soluii noi i produse moderne. PRATCO este un loc
unde clientul poate gsi suportul tehnic necesar n alegerea soluiei optime pentru aplicaia pe
care acesta trebuie s o dezvolte.
Serviciile: PRATCO este un furnizor cu o gam complet de echipamente electrice de joas
tensiune, materiale pentru instalaii i tablouri electrice, aparate i echipamente pentru
instalaiile de nclzire, ventilaie, clim, aer condiionat, instalaii de automatizare i control,
echipamente pentru instalaii termice - arztoare, cazane, boilere, pompe, vane, acionri,
senzori, fittinguri, schimbtoare de cldur cu plci, aparate de aer condiionat, centrale
termice murale etc.
PRATCO s-a dezvoltat rapid prin creterea gamei i a numrului de produse oferite. De la
nceput, pe lng serviciile de vnzare i marketing pentru produsele comercializate,
PRATCO a oferit clienilor si i suport ingineresc, proiecte complexe de instalaii, tablouri
electrice i de automatizare, asigurnd proiectarea instalaiilor, furnizarea echipamentelor,
asistena tehnic la montaj, punere n funciune, service n garanie i post-garanie.
PRATCO i-a creat un renume prin competena i seriozitatea cu care a realizat sisteme de
gestiune tehnic computerizat a termoficrii urbane i a building managementului.
Considernd c timpul de rspuns este un factor important n derularea unei afaceri,
PRATCO i-a propus, nc de la nceput:
221
222
223
225
229
230
231
232