Compact switchgear assemblies

HYpact
Volker JANICH
02/11/2010

GRID

Agenda
1st topic

General layout

Page 3

2nd topic

Circuit breaker

Page 6

3rd topic

Disconnector / earth switch

Page 11

4th topic

Instrument transformers, cable sealing ends

Page 18

5th topic

Indicating devices, interlocking

Page 23

6th topic

Transportation, installation, maintenance

Page 29

AGK-CSC [HYpact product] EN 06_2010- P 2

General layout
Compact switchgear assembly according to new standard IEC
62271-205: Mixed technology switchgear

3
1
4

Circuit breaker

Disconnector / Earth switch

Bushing current transformer

Drive mechanism

Central control cubicle

Steel stands

5
6
6

AGK-CSC [HYpact product] EN 06_2010- P 3

General layout

HYpact consist of three separate gas


compartments
Each houses all switching
devices for one phase
Circuit breaker
Disconnector(s)
Earth switch(es)

Bushing current transformer


Placed around the disconnector
/ earth switch
Installed on two steel stands

AGK-CSC [HYpact product] EN 06_2010- P 4

General layout

Single cast design


Avoid not always used openings
Reduced number of sealings
and gaskets
Thus low leakage

AGK-CSC [HYpact product] EN 06_2010- P 5

Circuit breaker
Double motion principle ensures low stress, thus increased
reliability
Original design for dead tank circuit breakers
Double motion breaking chamber is used with several thousend circuit
breakers for more than ten years
Reduced energy requirement leads to increased reliability
E = m v

AGK-CSC [HYpact product] EN 06_2010- P 6

Circuit breaker

Circuit breaker dive mechanism from


ALSTOMs FK3-1 range
One hundred thousend units in
service
Helical compression springs for opening
and closing
Most reliable spring design
Drive cubicle may double as central
termination box
Centralized local operation

AGK-CSC [HYpact product] EN 06_2010- P 7

Circuit breaker

Interpole connection by short rotating


linkage
Low energy dissipation
Four rotationally stressed
sealings only
One drive coupling linkage
Easy to connect

AGK-CSC [HYpact product] EN 06_2010- P 8

Circuit breaker

SF6 pipes with check valves located


above tanks
Easy decoupling of gas
compartments
Central filling point with check
valves and DN8 coupling
Allow access for topping up
gas and gas sampling
Operator-friendly
Safe access

AGK-CSC [HYpact product] EN 06_2010- P 9

Circuit breaker

Overpressure relief device at


rear end
By means of
expansion springs
Controlled blow-out
direction

AGK-CSC [HYpact product] EN 06_2010- P 10

Disconnector / Earth switch


Three position switch based on GIS technology

Connected
Disconnector
closed
Earth switch
open
AGK-CSC [HYpact product] EN 06_2010- P 11

Neutral
Disconnector
open
Earth switch
open

Earthed
Disconnector
open
Earth switch
closed

Disconnector / Earth switch


Switching positions earthing through the breaker

CB open
DS open

CB open
DS closed

CB closed
DS closed

AGK-CSC [HYpact product] EN 06_2010- P 12

CB open
DS closed

CB open
DS open
ES closed
Earthing
prepared

CB closed
ES closed
Line
earthed

Disconnector / Earth switch


Three position switch based on GIS technology

Connected
Disconnector
closed
Earth switch
open
AGK-CSC [HYpact product] EN 06_2010- P 13

Neutral
Disconnector
open
Earth switch
open

Earthed
Disconnector
open
Earth switch
closed

Disconnector / Earth switch


Three position mechanism ME1-3

AGK-CSC [HYpact product] EN 06_2010- P 14

d1

Disconnector / Earth switch


Three position mechanism ME1-3R
Padlockable point of isolation
Motorized operation to prepared
for earthing- position
Position indicators
Optional 10A - auxiliary switch for
high impedance protection
schemes (Class 1 acc. IEC 62271-1 table 6)

AGK-CSC [HYpact product] EN 06_2010- P 15

Folie 15
d1

UK-specific, hidden in the standard presentation

dnotroff; 30.07.2010

Disconnector / earth switch

Disconnector / Earth switch


linkage
Clearly separated from
other linkages

Position indicator directly


mounted on DS / ES input
shaft
Allows for direct
detection of the
switching status

AGK-CSC [HYpact product] EN 06_2010- P 16

Disconnector / Earth switch

Drive mechanisms mounted on steel


stands
No need for assembly at site
Drives already connected to central
control cubicle
Connection made by weatherproof Harting plugs
Yet, not need to connect drive
wiring at site

AGK-CSC [HYpact product] EN 06_2010- P 17

Current transformer

Epoxy cast resin design


Can be mounted on drive side
(standard), opposite side or both
sides of the circuit breaker
Belated assembly possible (slip-over
design)
Up to 5 multi-ratio cores per side
(depending on CT-specification)
Integrated cable connection box 16
terminals (6mm)
Option: Cabling in separate pre-wired
CT-terminal box

AGK-CSC [HYpact product] EN 06_2010- P 18

Current transformer

Air insulated design


Can be mounted on drive side
(standard), opposite side or both
sides of the circuit breaker
Position above or below
disconnector/earth switch module
Up to 5 multi-ratio cores per side
(depending on CT-specification)
Aluminium covered
Cabling in separate pre-wired CTterminal box

AGK-CSC [HYpact product] EN 06_2010- P 19

Voltage transformer (SF6 type)

With primary disconnector for


high voltage tests

Without primary disconnector

AGK-CSC [HYpact product] EN 06_2010- P 20

Voltage transformer
Flexible design with multi-connection housing
SF6 to air interface

SF6 to cable interface

AGK-CSC [HYpact product] EN 06_2010- P 21

Cable sealing ends


Dry type and fluid type connectors available

Pluggable current contact

Stress-cone in silicone rubber

Insulator in cast resin

Inlet with inner spring assembly

Clip mounting

Screen connection

Cable clamp

XLPE cable

2
3
4

5
6
7
8

AGK-CSC [HYpact product] EN 06_2010- P 22

Cable sealing ends


Flexibility due to adaptable housing
Two different housings
470mm for dry type
connections
760mm for fluid type
connections
Female contacts of various suppliers
can be mounted

AGK-CSC [HYpact product] EN 06_2010- P 23

Indicating devices / Interlocking

SF6 density monitor


Temperature compensated
reading on colour dial
Electrical two-step alarm
warning
Lockout

Combined mimic diagram


Circuit breaker on / off
Disconnector open / close
Earthing switch open / close

AGK-CSC [HYpact product] EN 06_2010- P 24

Indicating devices / Interlocking

spring condition indicator


Symbol charged
Symbol discharged

Mechanical circuit breaker operation


counter

AGK-CSC [HYpact product] EN 06_2010- P 25

d2

Indicating devices / Interlocking

UK-specific SF6 density monitor


MPa/bar scale
Temperature compensated
reading on colour dial
Electrical two-step alarm
warning
Lockout

UK-specific circuit breaker position


indicator
Coloured ON / OFF signs

AGK-CSC [HYpact product] EN 06_2010- P 26

Folie 26
d2

dnotroff30.07.2010
UK-specific, hidden in the standard presentation

dnotroff; 30.07.2010

d3

Indicating devices / Interlocking

UK-specific position indicator for


disconnector and earth switch
Disconnector ON / OFF
Earth switch ON / OFF

AGK-CSC [HYpact product] EN 06_2010- P 27

Folie 27
d3

dnotroff30.07.2010
UK-specific, hidden in the standard presentation

dnotroff; 30.07.2010

d4

Indicating devices / Interlocking

UK-specific spring condition


indicator
Spring charged
Spring discharged

Mechanical circuit breaker operation


counter

AGK-CSC [HYpact product] EN 06_2010- P 28

Folie 28
d4

dnotroff30.07.2010
UK-specific, hidden in the standard presentation

dnotroff; 30.07.2010

Indicating devices / Interlocking

Push buttons for local operation of circuit breaker and


disconnector / earth switch
padlockable Local / (Off) / Remote selector switch (option)
Position indicators (option)
Green / red illumination (LEDs)
Mechanical Semafor indicators

AGK-CSC [HYpact product] EN 06_2010- P 29

Indicating devices / Interlocking

Intrinsic interlock between disconnector and Earth switch


Electrical interlocking between circuit breaker and disconnector /
earthing switch
disconnector / earthing switch must not open or close when the
circuit breaker is closed
disconnector / earthing switch can only operate when the circuit
breaker is open
Cicuit breaker must not open or closed when the disconnector /
earthing switch is operating
Circuit breaker shall automatically close when the earth switchs
function is completed

AGK-CSC [HYpact product] EN 06_2010- P 30

Transportation, installation, maintenance


Two packing units only

Sea transport

AGK-CSC [HYpact product] EN 06_2010- P 31

Road transport

Transportation, installation, maintenance


Two packing units only
Support
Steel stands
Drive mechanisms
Mounted on steel stands

Central control cubicle (if


applicable)

Mounted on steel stands

Three phase switchgear unit


Completely assembled and
factory-tested
SF6 piping completely mounted
Interphase linkages installed and
adjusted
CT connection box, pre-wired

AGK-CSC [HYpact product] EN 06_2010- P 32

Transportation, installation, maintenance


HYpact is designed for fast and easy site erection
To do at site
Coupling of drive rods
Mounting of current transformer
connection box
SF6 density monitor wire
connection
Top up gas to service pressure
Commissioning test
No special tool required

AGK-CSC [HYpact product] EN 06_2010- P 33

Transportation, installation, maintenance


HYpact maintenance cycle based on GIS-, not on AISdisconnector cycle
Due to compactness, HYpacts circuit breaker cannot be isolated with disconnectors
Conventional AIS disconnectors also cannot be safely isolated without switching off HV
lines or busbars
Maintenance of conventional AIS disconnectors and earthing switched required after
several years, after every short circuit

With HYpact, conventional AIS disconnectors and earthing switches become obsolete,
thus no frequent DS/ES maintenance required anymore
HYpact disconnectors and earthing switches are based on GIS technology
Long maintenance cycles as of GIS reached

AGK-CSC [HYpact product] EN 06_2010- P 34

Transportation, installation, maintenance


Inspection
Visual inspection on occasional base during station tours, latest after 6
years
Corrosion
SF6 gas pressure
Ventilation ports and heating system

Maintenance
Every 12 years

Gas quality
Cable joints and connecting linkages
Function of electric control circuits
Operation time
Contact resistance

Reconditionning (normal service conditions)


After 2.500-3000 operations at rated normal current or
After a total current, i.e. 15 x rated breaking current

AGK-CSC [HYpact product] EN 06_2010- P 35

www.alstom.com

Circuit breaker

Presentation title - 01/01/2010 - P 37

Disconnector / Earth switch