Nominal cooling capacity 476-1764 kW
Nominal heating capacity 498-1872 kW
The 30XW liquid chillers are the premium solution for
industrial and commercial applications where installers,
consultants and building owners require optimal performances and maximum quality.
The 30XW liquid chillers are designed to meet current and
future requirements in terms of energy efficiency,
flexibility of use and compactness. They use the most
reliable technologies available today:
- Twin-rotor screw compressors with a variable capacity
valve
- Single refrigerant R-134a
- Touch-screen Pro-Dialog control system
- Flooded heat exchangers that are mechanically cleanable
To meet to all environmental and economic requirements,
the 30XW is available in two efficiency classes:
- Standard-efficiency 30XW units that offer an optimised
balance of technical and economical aspects, while at the
same time boasting superior energy efficiency.
- High-efficiency 30XW-P units that offer unequalled energy
efficiency to satisfy the most stringent demands of
building owners wanting to reduce operating costs to
the minimum.
The 30XW Aquaforce range is also split into two versions:
- 30XW for air conditioning and refrigeration applications
- 30XWH for heating applications
Full load and part load energy efficiency that surpasses the
industry average:
- Eurovent energy efficiency class A
- EER of up to 6.15 kW/kW (30XW-P)
- ESEER of up to 8.0 kW/kW (30XW-P)
- New twin-rotor screw compressor equipped with a highefficiency motor and a variable capacity valve that
permits exact matching of the cooling capacity to the
load.
- Flooded multi-pipe evaporator and condenser for
increased heat exchange efficiency.
- Electronic expansion device permitting operation at a
lower condensing pressure and improved utilisation of
the evaporator heat exchange surface.
- Economizer system with electronic expansion device for
increased cooling capacity (30XW-P).
Compressors
- Silencers on the discharge line.
- Silencers on the economiser return line.
- Acoustic insulation on the components that are most
subjected to radiated noise.
Compact design
- The 30XW units are designed to offer the most compact
dimensions on the market.
- With a width of approximately 1 m up to 1500 kW the
units can pass through standard door openings and only
require minimum floor space in the plant room.
Simplified electrical connections
- Main disconnect switch with high trip capacity
- Transformer to supply the integrated control circuit
(400/24 V)
Simplified hydronic connections
- Victaulic connections on the evaporator and condenser
- Practical reference marks for entering and leaving water
connections
- Possibility to reverse the heat exchanger water inlet and
outlet at the factory
- Possibilty to modify the number of heat exchanger passes
Fast commissioning
- Systematic factory operation test before shipment
- Quick-test function for step-by-step verification of the
instruments, expansion devices and compressors
Environmental care
R-134a refrigerant
- Refrigerant of the HFC group with zero ozone depletion
potential
Leak-tight refrigerant circuit
- Reduction of leaks as no capillary tubes and flare
connections are used
- Verification of pressure transducers and temperature
sensors without transferring refrigerant charge
- Discharge line shut-off valve and liquid line service
valve for simplified maintenance.
Absolute reliability
Screw compressors
- Industrial-type screw compressors with oversized
bearings and motor cooled by suction gas.
- All compressor components are easily accessible on site
minimising down-time.
- Protection increased by an electronic board.
Refrigerant circuit
- Two independent refrigerant circuits (from 1000 kW
upwards); the second one automatically takes over, if
the first one develops a fault, maintaining partial cooling
under all circumstances.
Evaporator
- Electronic paddle-free flow switch. Auto-setting according
to cooler size and fluid type.
Auto-adaptive control
- Control algorithm prevents excessive compressor
cycling (Carrier patent)
- Automatic compressor unloading in case of abnormally
high condensing pressure.
Exceptional endurance tests
- Partnerships with specialised laboratories and use of
limit simulation tools (finite element calculation) for the
design of critical components.
- Transport simulation test in the laboratory on a vibrating
table and then on an endurance circuit (based on a
military standard).
Pro-Dialog control
Load
Condenser entering
Energy
%
water temperature, C
efficiency
100
35
EER1
75
26.7
EER2
50
18.3
EER3
25
12.8
EER4
IPLV = EER1 x 1% + EER2 x 42% + EER3 x 45% + EER4 x 12%
Load
Condenser entering
Energy
Operating
%
water temperature, C
efficiency
time, %
100
30
EER1
3
75
26
EER2
33
50
22
EER3
41
25
18
EER4
23
ESEER = EER1 x 3% + EER2 x 33% + EER3 x 41% + EER4 x 23%
Operating
time, %
1
42
45
12
30XW--/30XWH
IPLV
kW/kW
ESEER kW/kW
452
6.30
552
6.40
602
6.50
652
6.93
702
6.85
802
6.86
852
6.91
1002
7.13
1052
7.48
1152
7.46
1252
7.72
30XW-P/30XWH
IPLV
kW/kW
ESEER kW/kW
512
6.78
562
6.79
712
7.00
812
7.05
862
6.98
1012
7.64
1162
7.99
1312
7.72
1462
7.59
1612
7.65
1762
7.18
1352
7.47
1452
7.35
1552
7.16
1652
7.36
1702
7.30
No.
5
51
70E
82A
84
Condenser insulation
86
Condensing temperature
limitation
Control for low condensing
temperature systems
81
84D
Use
Only for: 30XW 0512,
0562, 1012, 1152
As above
Only for:
30XW 1312, 1462
30XW 1612-1762
Permits an external electrical disconnect system 30XW 452-1762
for the unit (to be field-suppied).
Quick and easy installation
30XW 1002-1762
Permits an external electrical disconnect system 30XW 452-1762
for the unit (to be field-suppied). Short-circuit
protection of the unit remains.
Quick and easy installation
30XW 452-1252
30XW 452-1252
30XW 452-1252
30XW 452-1762
30XW 452-602
30XW 1002-1162
30XW 452-1762
30XW 452-1762
30XW 452-1762
84R
92
156
200
Advantages
Covers specific applications such as ice storage
and industrial processes
Covers specific applications such as ice storage
and industrial processes
Facilitates installation in plant rooms with limited
access
Options
CCN JBus gateway
CCN BacNet gateway
CCN LON Talk gateway
Energy Management Module
EMM
Lead-lag kit
Description
Medium-temperature glycol solution production
down to -6C
Low-temperature glycol solution production down
to -12C
Unit supplied in two assembled parts. The unit is
equipped with flanges that allow disassembly of
the unit on site.
Unit without disconnect switch and no short-circuit
protection device supplied with the unit
Power connection of the unit via one main supply
connection
Unit without disconnect switch, but with shortcircuit protection device
197
30XW 1002-1762
30XW 452-1762
30XW 452-1762
30XW 452-1762
30XW 452-1762
30XW 452-1762
30XW 452-602
30XW 1002-1162
30XW 452-1762
30XW 452-1762
Easy installation
30XW 452-1762
30XW 452-1762
30XW 452-1762
Use
30XW 452-1762
30XW 452-1762
30XW 452-1762
30XW 452-1762
30XW 452-1762
30XW 452-1762
Standard-efficiency units
30XW--/30XWH
Nominal cooling capacity*
Power input
EER
Eurovent class, cooling
ESEER part-load performance
Heating capacity**
Power input
Coefficient of performance (COP)
Eurovent class, heating
Nominal cooling capacity***
Power input
EER
Heating capacity***
Coefficient of performance (COP)
Operating weight
Sound power level****
Sound pressure level at 1 m
Compressors
Circuit A
Circuit B
Refrigerant charge
Circuit A
Circuit B
Oil charge
Circuit A
Circuit B
Capacity control
Minimum capacity
Evaporator
Net water volume
Water inlet/outlet connections (Victaulic)
Drain and vent connections (NPT)
Max. water-side operating pressure
Condenser
Net water volume
Water inlet/outlet connections (Victaulic)
Drain and vent connections (NPT)
Max. water-side operating pressure
30XW-P/30XWHP
Nominal cooling capacity*
Power input
EER
Eurovent class, cooling
ESEER part-load performance
Heating capacity**
Power input
Coefficient of performance (COP)
Eurovent class, heating
Nominal cooling capacity***
Power input
EER
Heating capacity***
Coefficient of performance (COP)
Operating weight
Sound power level****
Sound pressure level at 1 m
Compressors
Circuit A
Circuit B
Refrigerant charge
Circuit A
Circuit B
Oil charge
Circuit A
Circuit B
Capacity control
Minimum capacity
Evaporator
Net water volume
Water inlet/outlet connections (Victaulic)
Drain and vent connections (NPT)
Max. water-side operating pressure
Condenser
Net water volume
Water inlet/outlet connections (Victaulic)
Drain and vent connections (NPT)
Max. water-side operating pressure
512
562
712
812
862
kW
512
581
740
789
865
kW
86
97
122
134
145
kW/kW 5.97
5.99
6.07
5.87
5.96
A
A
A
A
A
kW/kW 6.78
6.79
7.00
7.05
6.98
kW
547
621
793
854
924
kW
113
129
163
182
193
kW/kW 4.85
4.81
4.87
4.69
4.78
A
A
A
A
A
kW
463
525
672
718
780
kW
113
129
163
182
193
kW/kW 4.11
4.08
4.14
3.94
4.04
kW
566
642
820
884
956
kW/kW 5.02
4.99
5.05
4.85
4.95
kg
2981
3020
3912
3947
3965
dB(A)
99
99
99
99
99
dB(A)
82
82
81
81
81
Semi-hermetic 06T screw compressors, 50 r/s
1
1
1
1
1
R-134a
kg
130
130
180
175
170
kg
SW220
l
32
32
36
36
36
l
Pro-Dialog, electronic expansion valves (EXV)
%
15
15
15
15
15
Multi-pipe flooded type
l
106
106
154
154
154
in
6
6
8
8
8
in
3/8
3/8
3/8
3/8
3/8
kPa
1000
1000
1000
1000
1000
Multi-pipe type
l
112
112
165
165
165
in
6
6
8
8
8
in
3/8
3/8
3/8
3/8
3/8
kPa
1000
1000
1000
1000
1000
High-efficiency units
1002
1024
184
5.57
A
7.13
1070
238
4.49
A
889
239
3.72
1106
4.63
5370
102
84
1052
1068
193
5.54
A
7.48
1121
251
4.47
A
928
251
3.69
1156
4.60
5408
102
84
1152
1156
200
5.78
A
7.46
1246
264
4.71
A
1049
264
3.97
1290
4.88
5705
102
84
1252
1265
211
6.00
A
7.72
1308
278
4.70
A
1101
278
3.96
1354
4.87
7066
102
83
1352
1349
232
5.81
A
7.47
1405
303
4.64
A
1177
302
3.89
1452
4.80
7267
102
83
1452
1463
255
5.73
A
7.35
1531
334
4.59
A
1281
334
3.84
1585
4.75
7305
102
83
1552
1560
274
5.70
A
7.16
1629
356
4.57
A
1362
357
3.82
1687
4.73
7337
102
83
1652
1664
279
5.96
A
7.36
1790
375
4.78
A
1515
374
4.05
1855
4.96
8681
102
83
1702
1739
290
5.99
A
7.30
1867
388
4.81
A
1577
389
4.06
1930
4.97
8699
102
83
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
85
85
85
85
105
105
120
120
115
115
110
110
105
105
195
195
195
195
32
32
32
32
32
32
36
32
36
36
36
36
36
36
36
36
36
36
10
10
10
10
10
10
10
10
10
185
6
3/8
1000
185
6
3/8
1000
214
8
3/8
1000
307
8
3/8
1000
307
8
3/8
1000
307
8
3/8
1000
307
8
3/8
1000
363
8
3/8
1000
363
8
3/8
1000
238
8
3/8
1000
238
8
3/8
1000
238
8
3/8
1000
347
8
3/8
1000
347
8
3/8
1000
347
8
3/8
1000
347
8
3/8
1000
426
8
3/8
1000
426
8
3/8
1000
1012
1047
174
6.03
A
7.64
1110
228
4.86
A
941
228
4.13
1149
5.04
6872
102
83
1162
1165
191
6.09
A
7.99
1246
253
4.92
A
1061
253
4.20
1290
5.11
6950
102
83
1312
1320
216
6.12
A
7.72
1411
287
4.92
A
1198
286
4.19
1459
5.10
9099
102
83
1462
1474
242
6.09
A
7.59
1584
322
4.92
A
1350
321
4.20
1642
5.11
9307
102
83
1612
1632
266
6.13
A
7.65
1752
361
4.85
A
1485
361
4.12
1813
5.03
10910
102
83
1762
1764
290
6.08
A
7.18
1872
396
4.73
A
1576
396
3.98
1936
4.89
10946
102
83
1
1
1
1
1
1
1
1
1
1
1
1
120
120
120
120
205
205
205
205
240
240
250
250
32
32
32
32
36
32
36
36
36
36
36
36
10
10
10
10
10
10
307
8
3/8
1000
307
8
3/8
1000
363
8
3/8
1000
363
8
3/8
1000
473
10
3/8
1000
473
10
3/8
1000
347
8
3/8
1000
347
8
3/8
1000
497
10
3/8
1000
497
10
3/8
1000
623
10
3/8
1000
623
10
3/8
1000
* Standard Eurovent conditions, cooling: evaporator entering/leaving water temperature = 12C/7C, condenser entering/leaving water temperature = 30C/35C.
** Standard Eurovent conditions, heating: condenser entering/leaving water temperature = 40C/45C, evaporator entering water temperature 10C with the same flow rate as for Eurovent
conditions in cooling mode.
*** Conditions in cooling and heating mode: evaporator entering/leaving water temperature = 10C/7C. condenser entering/leaving water temperature = 40C/45C.
**** 10-12 W in accordance with ISO 9614-1
in a free field
Weights are guidelines only. The refrigerant charge is given on the unit nameplate
Standard-efficiency units
30XW--/30XWH
Power circuit
Nominal power supply
Voltage range
Control circuit
Nominal start-up current*
Circuit A
Circuit B
Option 81
Maximum start-up current**
Circuit A
Circuit B
Option 81
Cosine phi nominal***
Cosine phi maximum****
Maximum power input
Circuit A
Circuit B
Option 81
Nominal current drawn***
Circuit A
Circuit B
Option 81
Maximum current drawn (Un)
Circuit A
Circuit B
Option 81
Maximum current drawn (Un -10%)****
Circuit A
Circuit B
Option 81
452
602
652
702
802
852
V-ph-Hz 400-3-50
V
360-440
24 V via the built-in transformer
A
A
A
414
-
414
-
414
-
587
-
587
-
587
-
587
-
414
414
558
414
414
574
414
414
574
587
414
747
587
587
780
587
587
801
587
587
819
587
587
819
587
587
819
A
A
A
414
0.86
0.89
414
0.87
0.90
414
0.87
0.90
587
0.88
0.90
587
0.89
0.91
587
0.90
0.92
587
0.90
0.92
414
414
631
0.87
0.90
414
414
656
0.87
0.90
414
414
656
0.87
0.90
587
414
829
0.88
0.90
587
587
882
0.88
0.90
587
587
904
0.89
0.91
587
587
938
0.90
0.92
587
587
938
0.90
0.92
587
587
938
0.90
0.92
kW
kW
kW
134
-
151
-
151
-
184
-
200
-
223
-
223
-
150
134
284
151
151
301
151
151
301
184
151
334
184
184
367
200
200
399
223
223
447
223
202
425
223
223
447
A
A
A
144
-
162
-
162
-
193
-
214
-
232
-
232
-
162
144
306
162
162
324
162
162
324
193
162
355
193
193
386
214
214
427
232
232
464
232
214
446
232
232
464
A
A
A
217
-
242
-
242
-
295
-
317
-
351
-
351
-
242
217
459
242
242
484
242
242
484
295
242
537
295
295
590
317
317
634
351
351
702
351
317
668
351
351
702
A
A
A
230
-
260
-
260
-
304
-
340
-
358
-
358
-
260
230
490
260
260
520
260
260
520
304
260
564
304
304
608
340
340
680
358
358
716
358
340
698
358
358
716
High-efficiency units
30XW-P/30XWHP
Power circuit
Nominal power supply
Voltage range
Control circuit
Nominal start-up current*
Circuit A
Circuit B
Option 81
Maximum start-up current**
Circuit A
Circuit B
Option 81
Cosine phi nominal***
Cosine phi maximum****
Maximum power input
Circuit A
Circuit B
Option 81
Nominal current drawn***
Circuit A
Circuit B
Option 81
Maximum current drawn (Un)
Circuit A
Circuit B
Option 81
Maximum current drawn (Un -10%)****
Circuit A
Circuit B
Option 81
552
512
562
712
812
862
1012
1162
1312
1462
1612
1762
V-ph-Hz 400-3-50
V
360-440
24 V via the built-in transformer
A
A
A
414
-
414
-
587
-
587
-
587
-
414
414
556
414
414
574
587
414
747
587
587
780
587
587
801
587
587
819
A
A
A
414
0.86
0.89
414
0.87
0.90
587
0.88
0.90
587
0.89
0.91
587
0.90
0.92
414
414
631
0.86
0.89
414
414
656
0.87
0.90
587
414
829
0.88
0.90
587
587
882
0.88
0.90
587
587
904
0.89
0.91
587
587
938
0.90
0.92
kW
kW
kW
134
-
151
-
184
-
200
-
223
-
134
134
267
151
151
301
184
151
334
184
184
367
200
200
399
223
223
447
A
A
A
144
-
162
-
193
-
214
-
232
-
144
144
288
162
162
324
193
162
355
193
193
386
214
214
427
232
232
464
A
A
A
217
-
242
-
295
-
317
-
351
-
217
217
434
242
242
484
295
242
537
295
295
590
317
317
634
351
351
702
A
A
A
230
-
260
-
304
-
340
-
358
-
230
230
460
260
260
520
304
260
564
304
304
608
340
340
680
358
358
716
* Instantaneous start-up current (maximum operating current of the smallest compressor(s) + locked rotor current or reduced start-up current of the largest compressor). Values obtained at
standard Eurovent unit operating conditions: evaporator entering/leaving water temperature = 12C/7C, condenser entering/leaving water temperature = 30C/35C.
** Instantaneous start-up current (maximum operating current of the smallest compressor(s) + locked rotor current or reduced start-up current of the largest compressor). Values obtained at
operation with maximum unit power input.
*** Values obtained at standard Eurovent unit operating conditions: evaporator entering/leaving water temperature = 12C/7C, condenser entering/leaving water temperature = 30C/35C
**** Values obtained at operation with maximum unit power input.
Values obtained at operation with maximum unit power input. Values given on the unit name plate.
kW
kW
kW/kW
kW
kW
kW/kW
kW
kW
kW/kW
kW
kW/kW
kg
dB(A)
dB(A)
kg
kg
l
l
%
l
in
in
kPa
l
in
in
kPa
kW
kW
kW/kW
kW
kW
kW/kW
kW
kW
kW/kW
kW
kW/kW
kg
dB(A)
dB(A)
kg
kg
l
l
%
l
in
in
kPa
l
in
in
kPa
512
562
712
812
862
520
580
96
105
5.43
5.51
A
A
562
625
113
124
4.99
5.04
A
A
419
466
150
165
2.80
2.83
555
617
3.71
3.74
2981
3020
99
99
82
82
Semi-hermetic 06T screw compressors, 50 r/s
1
1
R-134a
130
130
SW220
32
32
Pro-Dialog, electronic expansion valves (EXV)
30
30
Multi-pipe flooded type
106
106
6
6
3/8
3/8
1000
1000
Multi-pipe type
112
112
6
6
3/8
3/8
1000
1000
-
1052
1037
205
5.06
A
1085
238
4.56
A
739
304
2.43
1015
3.34
5408
102
84
1152
1129
216
5.21
A
1229
255
4.82
A
908
339
2.68
1216
3.59
5705
102
84
1252
-
1352
-
1452
-
1552
-
1652
-
1702
-
1
1
1
1
85
85
105
105
32
32
32
32
20
20
185
6
3/8
1000
214
8
3/8
1000
238
8
3/8
1000
238
8
3/8
1000
1012
1017
195
5.21
A
1107
230
4.82
A
817
306
2.67
1096
3.58
6872
102
83
1162
1142
215
5.32
A
1241
253
4.91
A
916
338
2.71
1224
3.62
6950
102
83
1312
-
1462
-
1612
-
1762
-
1
1
1
1
120
120
120
120
32
32
32
32
20
20
307
8
3/8
1000
307
8
3/8
1000
347
8
3/8
1000
347
8
3/8
1000
* Standard Eurovent conditions, cooling: evaporator entering/leaving water temperature = 12C/7C, condenser entering/leaving water temperature = 30C/35C.
** Standard Eurovent conditions, heating: condenser entering/leaving water temperature = 40C/45C, evaporator entering water temperature 10C with the same flow rate as for Eurovent
conditions in cooling mode.
*** Conditions in cooling and heating mode: evaporator entering/leaving water temperature = 10C/7C. condenser entering/leaving water temperature = 50C/60C.
**** 10-12 W in accordance with ISO 9614-1
in a free field
Weights are guidelines only. The refrigerant charge is given on the unit nameplate.
452
602
652
702
802
852
V-ph-Hz 400-3-50
V
360-440
24 V via the built-in transformer
A
A
A
587
-
587
-
587
-
587
587
757
587
587
757
587
587
757
A
A
A
587
0.88
0.91
587
0.88
0.92
587
0.88
0.92
587
587
887
0.88
0.92
587
587
887
0.88
0.92
587
587
887
0.88
0.92
kW
kW
kW
173
-
191
-
191
-
190
174
364
191
191
382
191
191
382
A
A
A
162
-
171
-
171
-
171
162
333
171
171
342
171
171
342
A
A
A
275
-
300
-
300
-
300
275
575
300
300
600
300
300
600
A
A
A
300
-
330
-
330
-
330
300
630
330
330
660
330
330
660
552
512
562
712
812
862
1012
1162
1312
1462
1612
1762
V-ph-Hz 400-3-50
V
360-440
24 V via the built-in transformer
A
A
A
587
-
587
-
587
587
749
587
587
757
A
A
A
587
0.88
0.91
587
0.88
0.92
587
587
862
0.87
0.91
587
587
887
0.88
0.92
kW
kW
kW
173
-
191
-
173
173
346
191
191
382
A
A
A
162
-
171
-
162
162
324
171
171
342
A
A
A
275
-
300
-
275
275
550
300
300
600
A
A
A
300
-
330
-
300
300
600
330
330
660
* Instantaneous start-up current (maximum operating current of the smallest compressor(s) + locked rotor current or reduced start-up current of the largest compressor). Values based on standard
Eurovent unit operating conditions: evaporator entering/leaving water temp. = 12C/7C, condenser entering/leaving water temp. = 30C/35C.
** Instantaneous start-up current (maximum operating current of the smallest compressor(s) + locked rotor current or reduced start-up current of the largest compressor). Values obtained at
operation with maximum unit power input.
*** Values based on standard Eurovent unit operating conditions: evaporator entering/leaving water temp. = 12C/7C, condenser entering/leaving water temp. = 30C/35C.
**** Values obtained at operation with maximum unit power input.
Values obtained at operation with maximum unit power input. Values given on the unit name plate.
kW
kW
kW/kW
kW
kW/kW
kW
kW
kW/kW
kW
kW/kW
-1152
705
193
3.66
880
4.57
760
196
3.87
938
4.78
Option 5
* Values based on 25% ethylene glycol, evaporator entering/leaving water temperatures of -2C/-6C and condenser entering/leaving water temperatures of 30C/35C.
** Values based on 24% propylene glycol, evaporator entering/leaving water temperatures of +1C/-3C and condenser entering/leaving water temperatures of 30C/35C.
Note: Evaporator with 2 pass configuration with water inlet and outlet on the same side.
-1152
502
178
2.81
664
3.73
558
182
3.06
724
3.97
Option 6
* Values based on 35% ethylene glycol, evaporator entering/leaving water temperatures of -8C/-12C and condenser entering/leaving water temperatures of 30C/35C.
** Values based on 30% propylene glycol, evaporator entering/leaving water temperatures of -4C/-8C and condenser entering/leaving water temperatures of 30C/35C.
Note: Evaporator with 3 pass configuration with water inlet and outlet on opposite sides.
* Not provided for units equipped with options 70E and 82A
** Not provided for units equipped with option 70E
*** The required protection level for this class is IP21BW (according to reference document
IEC 60529). All 30XW units are protected to IP23C and fulfil this protection condition.
Dimensions/clearances
30XW--/30XWH- 452-852
30XW-P/30XWHP 512-862
Evaporator
Condenser
Dimensions in mm
A
B
C
D
E
F
Standard-efficiency units 30XW--/30XWH452
1693 810 936 2742 141.3 141.3
552
1693 810 936 2742 141.3 141.3
602
1693 810 936 2742 141.3 141.3
652
1848 968 1044 3059 168.3 168.3
702
1848 968 1044 3059 168.3 168.3
802
1848 968 1044 3059 168.3 168.3
852
1898 828 1044 2780 219.1 168.3
High-efficiency units 30XW-P/30XWHP
512
1743 968 936 3059 168.3 168.3
562
1743 968 936 3059 168.3 168.3
712
1950 1083 1065 3290 219.1 219.1
812
1950 1083 1070 3290 219.1 219.1
862
1950 1083 1070 3290 219.1 219.1
G
2600
2600
2600
2900
2900
2900
2600
2900
2900
3100
3100
3100
Legend:
1
2
10
Dimensions/clearances
30XW--/30XWH- 1002-1552
30XW-P/30XWHP 1012-1162
Evaporator
Condenser
Dimensions in mm
A
B
C
D
E
F
Standard-efficiency units 30XW--/30XWH1002 1870 950 1036 4025 219.1 168.3
1052 1870 950 1036 4025 219.1 168.3
1152 1926 950 1036 4025 219.1 219.1
1252 2051 1512 1162 4730 219.1 219.1
1352 2051 1512 1162 4730 219.1 219.1
1452 2051 1512 1162 4730 219.1 219.1
1552 2051 1512 1162 4730 219.1 219.1
High-efficiency units 30XW-P / 30XHP
1012 1997 1512 1039 4795 219.1 219.1
1162 1997 1512 1039 4795 219.1 219.1
G
3800
3800
3800
4500
4500
4500
4500
4500
4500
Legend:
1
2
11
Dimensions/clearances
30XW--/30XWH- 1652-1702
30XW-P/30XWHP 1312-1762
Dimensions in mm
A
B
C
D
E
F
Standard-efficiency units 30XW--/30XWH1652 1541 1568 1902 4790 219.1 219.1
1702 1541 1568 1902 4790 219.1 219.1
High-efficiency units 30XW-P/30XHP
1312 1541 1581 1935 4812 273.0 219.1
1462 1541 1581 1935 4812 273.0 219.1
1612 1594 1591 2129 4832 273.0 273.0
1762 1594 1591 2129 4832 273.0 273.0
G
4500
4500
4500
4500
4600
4600
Evaporator
Legend:
1
2
Condenser
12
Minimum
Maximum
-
3.3C*
2.8 K
35.0C
20.0C
11.1 K
13.0C**
19.0C**
2.8 K
50.0C***
11.1 K
* For low-temperature applications, where the leaving water temperature is below 3.3C, a
frost protection solution must be used. Please refer to option 5 and option 6.
** For lower condenser temperatures, a water flow control valve must be used at the condenser
(two or three-way valve). Please refer to option 152 to ensure the correct condensing
temperature.
*** Please refer to option 150 for applications with a high condenser leaving temperature (up to
63C).
Standard units
Minimum
Maximum
-
3.3C*
2.8 K
35.0C
15.0C
11.1 K
13.0C**
23.0C**
2.8 K
63.0C
11.1 K
50
45
40
35
30
25
20
15
Option 150
0
5
10
15
20
Evaporator leaving water temperature, C
70
* For low-temperature applications, where the leaving water temperature is below 3.3C, a
frost protection solution must be used. Please refer to option 5 and option 6.
** For lower condenser temperatures, a water flow control valve must be used at the condenser
(two or three-way valve). Please refer to option 152 to ensure the correct condensing
temperature.
From approx. 60% to full load
Part load limit approx. 50%
55
65
60
55
50
45
40
35
30
25
20
10
15
20
PG 5
EG 6
PG 6
Minimum
Maximum
35.0C
-6C
-3C
-12C
-8C
2.8 K
15.0C
15.0C
15.0C
15.0C
11.1 K***
Condenser
Entering temperature at start-up
13.0C**
Leaving temperature during operation
19.0/23.0C**
Entering/leaving temperature difference at full load 2.8 K
55.0/
63.0C****
11.1 K
* The operating range with evaporator leaving temperatures above 3C is permitted, but the
performances are not optimised.
** For lower condenser temperatures, a water flow control valve must be installed at the
condenser (two-way or three-way). Please refer to option 152 to ensure the correct
condensing temperature.
*** Please refer to chapter 10.5 of the installation manual for the minimum recommended
evaporator glycol flow rate.
**** Depends on the conditions at the evaporator and the load conditions.
Options 5 and 6
70
EG 5
65
60
55
50
45
40
35
EG 6
30
PG 6
EG 5
25
PG 5
20
15
-15
-10
-5
0
5
10
15
Evaporator leaving glycol temperature, C
20
Note: Ambient temperatures: During storage and transport of the 30XW units (including by
container) the minimum and maximum permissible temperatures are -20C and 72C (and 65C
for option 200).
13
120
36
110
33
100
30
90
27
80
24
70
60
50
40
21
18
15
12
30
20
10
10
20
30
40
50
60
70
80
90
Legend
1 452, 552, 602
2 512, 562, 652, 702, 802
3 712, 812, 862
4 852
5 1002, 1052
6 1012, 1162, 1252, 1352, 1452, 1552
7 1152
8 1312, 1462, 1652, 1702
9 1612, 1762
10
20
30
40
50
60
70
80
90
Legend
1 452, 552, 602
2 512, 562, 652, 702, 802
3 712, 812, 862
4 852
5 1002, 1052
6 1012, 1162, 1252, 1352, 1452, 1552
7 1152
8 1312, 1462, 1652, 1702
9 1612, 1762
36
110
33
100
30
90
27
80
24
70
60
50
40
21
18
15
12
30
20
10
10
20
30
40
Legend
1 452, 552, 602
2 512, 562, 652, 702, 802
3 712, 812, 862
4 852
5 1002, 1052
6 1152
7 1012, 1162, 1252, 1352, 1452, 1552
8 1312, 1462
9 1652, 1702
0 1612, 1762
14
50
60
70
80
90
10
20
30
40
50
60
70
Legend
1 1002, 1052
2 1152
3 1012, 1162, 1252, 1352, 1452, 1552
4 1312, 1462
5 1652, 1702
6 1612, 1762
80
90
40
Unit Cool Cool Qc
kW l/s
kPa kW
Qh
kW
45
Unit Cool Cool Qc
kW l/s
kPa kW
Qh
kW
50
Unit Cool Cool Qc
kW l/s
kPa kW
Qh
kW
85
98
99
120
131
143
150
184
192
200
211
232
256
274
280
291
21.0
23.7
24.1
30.1
32.5
35.2
38.0
45.1
47.2
51.6
55.9
59.7
64.7
68.9
74.1
77.5
33
42
43
40
46
53
56
64
70
61
60
67
79
89
53
58
412
467
487
590
636
685
752
891
936
1028
1103
1178
1279
1359
1488
1555
500
569
590
716
774
833
909
1083
1137
1238
1324
1420
1545
1643
1784
1861
97
112
114
138
151
162
172
210
221
231
242
266
292
312
326
337
19.6
22.2
23.2
28.1
30.3
32.6
35.8
42.4
44.6
48.9
52.5
56.1
60.9
64.7
70.8
74.0
29
37
40
36
41
47
51
57
63
56
53
60
70
79
48
53
386
439
467
545
594
632
697
828
866
985
1028
1101
1196
1266
1422
1480
486
555
586
689
751
800
875
1044
1094
1225
1281
1376
1499
1590
1763
1833
110
127
130
158
173
184
196
238
251
264
278
303
334
356
375
388
18.4
20.9
22.3
26.0
28.3
30.1
33.2
39.4
41.2
46.9
48.9
52.4
56.9
60.3
67.7
70.5
26
33
37
31
36
40
44
50
55
52
46
53
62
69
44
48
359
407
447
504
548
576
654
766
788
939
955
1020
1109
1172
1352
1405
473
539
582
668
728
768
858
1013
1047
1219
1243
1334
1455
1540
1743
1808
125
145
149
180
197
211
224
271
284
308
317
345
380
405
429
444
17.1
19.4
21.3
24.0
26.1
27.4
31.1
36.5
37.5
44.7
45.5
48.6
52.8
55.8
64.4
66.9
22
29
34
27
31
34
40
44
46
47
40
45
53
59
40
43
86
97
123
136
146
174
192
217
243
267
291
22.7
25.8
32.8
35.1
38.2
46.4
51.8
58.7
65.6
72.7
78.3
24
30
28
32
37
42
51
33
41
49
57
456
516
661
705
767
926
1040
1171
1323
1458
1566
546
618
789
849
920
1107
1242
1399
1578
1743
1876
99
112
141
158
168
200
221
250
280
313
341
21.7
24.6
31.5
33.6
36.5
44.1
49.5
55.8
63.0
69.4
74.6
22
28
26
30
34
38
47
30
38
45
52
435
492
630
674
731
882
995
1124
1266
1395
1478
537
610
778
839
907
1090
1225
1385
1559
1724
1838
113
129
163
182
193
229
254
287
322
362
396
20.7
23.4
30.0
32.1
34.8
42.0
47.4
53.5
60.3
66.4
70.4
20
26
24
27
32
34
43
27
35
41
46
415
470
598
642
694
843
950
1073
1209
1329
1401
533
604
769
832
894
1080
1214
1373
1546
1706
1816
129
148
188
209
221
261
290
330
370
415
456
19.8
22.4
28.5
30.6
33.0
40.1
45.2
51.1
57.6
63.3
66.7
19
23
22
25
29
31
40
25
32
38
42
40
Unit Cool Cool Qc
kW l/s
kPa kW
Qh
kW
45
Unit Cool Cool Qc
kW l/s
kPa kW
Qh
kW
50
Unit Cool Cool Qc
kW l/s
kPa kW
Qh
kW
85
98
98
120
131
144
148
184
193
200
211
232
255
274
279
290
22.7
25.6
25.8
32.5
35.1
37.9
40.2
48.8
50.9
55.1
60.3
64.3
69.7
74.4
79.3
82.9
38
48
49
46
52
60
61
73
79
68
68
77
90
101
60
65
444
499
519
635
684
737
797
960
1007
1096
1189
1269
1377
1465
1589
1660
532
602
623
760
822
885
951
1152
1209
1306
1409
1510
1643
1749
1885
1967
97
112
114
138
152
163
169
210
222
230
242
265
292
313
325
337
21.2
23.8
24.8
30.3
32.6
35.1
38.0
45.8
48.0
52.3
56.7
60.5
65.7
69.8
75.8
79.2
33
42
45
40
46
53
55
65
71
62
60
68
80
90
54
59
416
472
498
587
639
680
741
890
928
1050
1109
1187
1289
1366
1519
1581
517
588
617
732
797
848
917
1108
1157
1291
1362
1462
1592
1691
1860
1935
110
128
130
159
173
185
193
239
251
264
278
302
333
357
374
389
19.8
22.5
23.8
28.0
30.5
32.4
35.3
42.4
44.3
50.1
52.9
56.6
61.4
65.1
72.4
75.4
29
37
41
35
41
45
49
57
61
57
53
60
70
79
50
54
387
439
476
544
592
498
621
826
843
1001
1031
1102
1197
1265
1444
1501
501
571
612
708
771
641
814
1074
1102
1282
1319
1415
1543
1634
1834
1905
125
145
149
181
198
157
212
272
284
308
316
344
380
405
429
444
18.5
20.9
22.7
25.9
28.2
23.8
29.6
39.4
40.2
47.7
49.2
52.5
57.1
60.3
68.8
71.5
26
33
38
30
35
26
39
50
51
53
46
52
61
68
45
48
86
97
122
134
145
174
191
216
242
266
290
24.4
27.7
35.3
37.6
41.2
49.9
55.5
62.9
70.3
77.8
84.1
27
34
32
36
42
47
58
37
47
55
64
488
551
706
752
820
991
1111
1252
1414
1556
1674
577
653
835
895
972
1172
1312
1478
1668
1840
1984
98
112
141
157
168
199
220
249
279
312
341
23.3
26.3
33.7
35.9
39.1
47.2
53.0
59.7
67.4
74.2
79.8
25
31
29
33
38
42
53
34
43
50
58
464
526
674
718
780
943
1062
1201
1352
1489
1580
567
643
821
884
956
1150
1292
1461
1644
1817
1940
113
129
163
182
193
228
253
286
321
361
396
22.1
25.1
32.1
34.2
37.2
44.9
50.6
57.2
64.5
71.0
75.3
23
28
27
30
35
39
49
31
39
46
52
443
502
641
685
741
900
1014
1147
1291
1419
1499
560
636
811
875
943
1137
1277
1446
1627
1795
1914
129
147
187
209
221
260
289
328
369
414
456
21.1
23.9
30.6
32.6
35.4
42.9
48.3
54.7
61.6
67.6
71.4
21
26
25
28
32
35
44
28
36
42
47
Legend:
Qc kW Cooling capacity
Qh kW Heating capacity
Unit kW Unit power input (compressors, control)
Cool l/s Evaporator water flow rate
Cool kPa Evaporator pressure drop
Application data:
Standard units, refrigerant R-134a
Evaporator water temperature rise: 5 K
Evaporator fluid: chilled water
Fouling factor: 0.18 x 10-4 (m2 K)/W
Performances in accordance with EN 14511
15
40
Cool Cool Qc
l/s
kPa kW
Qh
kW
45
Unit Cool Cool Qc
kW l/s
kPa kW
Qh
kW
50
Unit Cool Cool Qc
kW l/s
kPa kW
Qh
kW
24.9
27.6
28.4
35.6
38.1
40.5
41.3
54.1
56.6
59.0
66.9
71.7
77.9
82.9
87.1
91.0
44
54
57
53
60
67
63
86
93
75
81
93
109
123
71
77
494
539
570
705
760
804
838
1061
1114
1206
1321
1414
1536
1634
1750
1825
583
641
673
832
899
955
990
1254
1316
1415
1543
1656
1801
1919
2045
2132
98
113
113
139
153
165
168
212
223
230
244
265
292
313
324
338
23.6
25.7
27.2
33.7
36.3
38.4
40.0
50.7
53.2
57.6
63.1
67.5
73.3
78.0
83.5
87.1
40
47
53
48
55
61
59
76
83
72
73
83
97
109
65
71
464
519
547
654
711
752
812
989
1019
1154
1238
1325
1438
1528
1672
1742
565
636
665
799
870
923
989
1208
1248
1395
1491
1600
1741
1853
2013
2096
111
128
130
159
174
188
193
240
252
264
278
302
334
357
374
389
22.2
24.8
26.1
31.2
34.0
35.9
38.8
47.2
48.7
55.1
59.1
63.3
68.6
73.0
79.9
83.2
36
44
49
42
48
54
56
67
71
67
64
73
85
96
59
64
433
484
522
607
660
693
783
923
931
1100
1154
1232
1337
1416
1590
1653
547
616
658
772
841
888
988
1171
1190
1381
1441
1545
1683
1786
1981
2059
125
146
149
181
198
214
225
272
285
309
316
344
380
406
429
446
20.7
23.1
25.0
29.0
31.5
33.1
37.4
44.1
44.5
52.5
55.1
58.8
63.8
67.6
75.9
78.9
31
39
45
36
42
46
53
60
60
61
56
64
74
83
54
58
26.7
30.3
38.6
41.3
45.1
53.1
61.2
69.0
77.2
85.3
91.9
31
39
37
42
49
52
68
44
55
64
74
534
605
775
824
899
1090
1225
1382
1556
1712
1842
623
706
903
968
1052
1270
1424
1606
1807
1995
2152
98
112
141
158
168
198
218
246
276
311
342
25.5
28.9
37.0
39.4
42.9
52.0
58.5
66.0
74.3
81.8
87.9
29
36
34
38
45
50
63
40
51
60
68
511
579
742
789
860
1038
1171
1325
1491
1637
1742
613
695
889
955
1036
1245
1399
1583
1780
1964
2102
112
128
162
182
193
227
251
283
318
359
396
24.4
27.6
35.4
37.7
41.1
49.6
55.9
63.3
71.2
78.2
83.2
27
33
32
35
41
46
58
37
47
55
62
488
557
707
752
817
992
1117
1265
1423
1560
1653
605
691
877
943
1019
1228
1379
1561
1757
1936
2069
128
147
186
209
221
259
288
325
367
413
457
23.3
26.6
33.8
35.9
39.0
47.4
53.3
60.4
68.0
74.5
78.9
24
31
29
32
38
42
53
34
43
50
56
Legend:
Qc kW Cooling capacity
Qh kW Heating capacity
Unit kW Unit power input (compressors, control)
Cool l/s Evaporator water flow rate
Cool kPa Evaporator pressure drop
Application data:
Standard units, refrigerant R-134a
Evaporator water temperature rise: 5 K
Evaporator fluid: chilled water
Fouling factor: 0.18 x 10-4 (m2 K)/W
Performances in accordance with EN 14511