Water-Cooled Liquid Chillers

30XW- 30XWH
Nominal cooling capacity 476-1764 kW
Nominal heating capacity 498-1872 kW
The 30XW liquid chillers are the premium solution for
industrial and commercial applications where installers,
consultants and building owners require optimal performances and maximum quality.
The 30XW liquid chillers are designed to meet current and
future requirements in terms of energy efficiency,
flexibility of use and compactness. They use the most
reliable technologies available today:
- Twin-rotor screw compressors with a variable capacity
valve
- Single refrigerant R-134a
- Touch-screen Pro-Dialog control system
- Flooded heat exchangers that are mechanically cleanable
To meet to all environmental and economic requirements,
the 30XW is available in two efficiency classes:
- Standard-efficiency 30XW units that offer an optimised
balance of technical and economical aspects, while at the
same time boasting superior energy efficiency.
- High-efficiency 30XW-P units that offer unequalled energy
efficiency to satisfy the most stringent demands of
building owners wanting to reduce operating costs to
the minimum.
The 30XW Aquaforce range is also split into two versions:
- 30XW for air conditioning and refrigeration applications
- 30XWH for heating applications

These two versions provide the following performances:


- High heating temperature, allowing the 30XWH
Aquaforce to supply water with a condenser leaving
water temperature of +63C (option 150)
- Low temperature, allowing the 30XW Aquaforce to
operate with an evaporator leaving glycol temperature
down to -6C (option 5) or -12C (option 6).

Features and advantages


Superior operating economy

Full load and part load energy efficiency that surpasses the
industry average:
- Eurovent energy efficiency class A
- EER of up to 6.15 kW/kW (30XW-P)
- ESEER of up to 8.0 kW/kW (30XW-P)
- New twin-rotor screw compressor equipped with a highefficiency motor and a variable capacity valve that
permits exact matching of the cooling capacity to the
load.
- Flooded multi-pipe evaporator and condenser for
increased heat exchange efficiency.
- Electronic expansion device permitting operation at a
lower condensing pressure and improved utilisation of
the evaporator heat exchange surface.
- Economizer system with electronic expansion device for
increased cooling capacity (30XW-P).

Low operating sound levels

Compressors
- Silencers on the discharge line.
- Silencers on the economiser return line.
- Acoustic insulation on the components that are most
subjected to radiated noise.

Easy and fast installation

Compact design
- The 30XW units are designed to offer the most compact
dimensions on the market.
- With a width of approximately 1 m up to 1500 kW the
units can pass through standard door openings and only
require minimum floor space in the plant room.
Simplified electrical connections
- Main disconnect switch with high trip capacity
- Transformer to supply the integrated control circuit
(400/24 V)
Simplified hydronic connections
- Victaulic connections on the evaporator and condenser
- Practical reference marks for entering and leaving water
connections
- Possibility to reverse the heat exchanger water inlet and
outlet at the factory
- Possibilty to modify the number of heat exchanger passes
Fast commissioning
- Systematic factory operation test before shipment
- Quick-test function for step-by-step verification of the
instruments, expansion devices and compressors

Environmental care

R-134a refrigerant
- Refrigerant of the HFC group with zero ozone depletion
potential
Leak-tight refrigerant circuit
- Reduction of leaks as no capillary tubes and flare
connections are used
- Verification of pressure transducers and temperature
sensors without transferring refrigerant charge
- Discharge line shut-off valve and liquid line service
valve for simplified maintenance.

Absolute reliability

Screw compressors
- Industrial-type screw compressors with oversized
bearings and motor cooled by suction gas.
- All compressor components are easily accessible on site
minimising down-time.
- Protection increased by an electronic board.
Refrigerant circuit
- Two independent refrigerant circuits (from 1000 kW
upwards); the second one automatically takes over, if
the first one develops a fault, maintaining partial cooling
under all circumstances.
Evaporator
- Electronic paddle-free flow switch. Auto-setting according
to cooler size and fluid type.
Auto-adaptive control
- Control algorithm prevents excessive compressor
cycling (Carrier patent)
- Automatic compressor unloading in case of abnormally
high condensing pressure.
Exceptional endurance tests
- Partnerships with specialised laboratories and use of
limit simulation tools (finite element calculation) for the
design of critical components.
- Transport simulation test in the laboratory on a vibrating
table and then on an endurance circuit (based on a
military standard).

Pro-Dialog control

- Pro-Dialog combines intelligence with operating

simplicity. The control constantly monitors all machine


parameters and precisely manages the operation of
compressors, electronic expansion devices and of the
evaporator water pump for optimum energy efficiency.
Energy management
- Internal time schedule clock: controls chiller on/off
times and operation at a second set-point
- Set-point reset based on the return water temperature
- Master/slave control of two chillers operating in parallel
with operating time equalisation and automatic changeover in case of a unit fault.
Ease-of-use
- User interface with large touch screen (120 x 99 mm) for
intuitive access to the operating parameters. The
information is in clear text and can be displayed in local
language (please contact your distributor).

Remote management (standard)

The 30XW is equipped with an RS485 serial port that


offers multiple remote control, monitoring and diagnostic
possibilities. Carrier offers a vast choice of control products,
specially designed to control, manage and supervise the
operation of an air conditioning system. Please consult
your Carrier representative for more information.
The 30XW also communicates with other building management systems via optional communication gateways.
A connection terminal allows remote control of the 30XW
by wired cable:
- Start/stop: opening of this contact will shut down the
unit
- Dual set-point: closing of this contact activates a second
set-point (example: unoccupied mode)
- Demand limit: closing of this contact limits the maximum
chiller capacity to a predefined value
- Operation indication: this volt-free contact indicates
that the chiller is operating (cooling load) or that it is
ready to operate (no cooling load)
- Alert indication: this volt-free contact indicates the
necessity to carry out a maintenance operation or the
presence of a minor fault
- Alarm indication: this volt-free contact indicates the
presence of a major fault that has led to the shut-down
of one or several refrigerant circuits

Remote management (EMM option)

The Energy Management Module offers extended remote


control possibilities:
- Room temperature: permits set-point reset based on the
building indoor air temperature (with Carrier thermostat)
- Set point reset: ensures reset of the cooling set-point
based on a 4-20 mA or 0-10 V signal
- Demand limit: permits limitation of the maximum
chiller power or current based on a 0-10 V signal
- Demand limit 1 and 2: closing of these contacts limits
the maximum chiller power or current to two predefined
values
- User safety: this contact can be used for any customer
safety loop; opening of the contact generates a specific
alarm
- Ice storage end: when ice storage has finished, this input
permits return to the second set-point (unoccupied
mode)
- Time schedule override: closing of this contact cancels
the time schedule effects
- Out of service: this signal indicates that the chiller is
completely out of service
- Chiller capacity: this analogue output (0-10 V) gives an
immediate indication of the chiller capacity

Pro-Dialog operator interface with touch-screen

New generation 06T screw compressor

The 30XW operator interface is very user-friendly. It is a


large-format touch-screen, and the information is easily
accessible: clear text in the selected language allows
consultation of all operating parameters. Up to eight
screens can be personalised.

The new generation of the Carrier 06T screw compressors


benefits from Carriers long experience in the development
of twin-rotor screw compressors. The compressor is
equipped with bearings with oversized rollers, oil pressure
lubricated for reliable and durable operation, even at
maximum load.
A variable control valve controlled by the oil pressure
permits infinitely variable capacity.
Among the other advantages: if a fault occurs e.g. if the
condenser is fouled or at very high water temperature, the
compressor does not switch off, but continues operation
with a reduced capacity (unloaded mode).
The silencer in the discharge line considerably reduces
discharge gas pulsations for much quieter operation.
The condenser includes an oil separator that minimises
the amount of oil in circulation in the refrigerant circuit
and re-directs it to the compressor function.

Part load performances


With the rapid increase in energy costs and the care about
environmental impacts of electricity production, power
consumption of air conditioning equipment has become
an important topic. The energy efficiency of a liquid chiller
at full load is rarely representative of the actual performance
of the units, as on average a chiller works less than 5% of
the time at full load.

The heat load of a building depends on many factors, such


as the outside air temperature, the exposure to the sun
and its occupation.
Consequently it is preferable to use the average energy
efficiency, calculated at several operating points that are
representative for the unit utilisation.

IPLV (in accordance with ARI 550/590-98)

ESEER (in accordance with EUROVENT)

IPLV (integrated part load value)

ESEER (European seasonal energy efficiency ratio)

The IPLV (integrated part load value) allows evaluation


of the average energy efficiency based on four operating
conditions defined by the ARI (American Refrigeration
Institute). The IPLV is the average weighted value of the
energy efficiency ratios (EER) at different operating
conditions, weighted by the operating time.

Load
Condenser entering
Energy
%
water temperature, C
efficiency
100
35
EER1
75
26.7
EER2
50
18.3
EER3
25
12.8
EER4
IPLV = EER1 x 1% + EER2 x 42% + EER3 x 45% + EER4 x 12%

Part load performances

The ESEER (European seasonal energy efficiency ratio)


permits evaluation of the average energy efficiency at part
load, based on four operating conditions defined by
Eurovent. The ESEER is the average value of energy
efficiency ratios (EER) at different operating conditions,
weighted by the operating time.

Load
Condenser entering
Energy
Operating
%
water temperature, C
efficiency
time, %
100
30
EER1
3
75
26
EER2
33
50
22
EER3
41
25
18
EER4
23
ESEER = EER1 x 3% + EER2 x 33% + EER3 x 41% + EER4 x 23%

Operating
time, %
1
42
45
12

30XW--/30XWH
IPLV
kW/kW
ESEER kW/kW

452
6.30

552
6.40

602
6.50

652
6.93

702
6.85

802
6.86

852
6.91

1002
7.13

1052
7.48

1152
7.46

1252
7.72

30XW-P/30XWH
IPLV
kW/kW
ESEER kW/kW

512
6.78

562
6.79

712
7.00

812
7.05

862
6.98

1012
7.64

1162
7.99

1312
7.72

1462
7.59

1612
7.65

1762
7.18

1352
7.47

1452
7.35

1552
7.16

1652
7.36

1702
7.30

Main options and accessories


Options
Medium-temperature brine
solution
Low-temperature brine solution

No.
5

Unit supplied in two assembled


parts

51

No disconnect switch/no shortcircuit protection


Single power connection point

70E

No disconnect switch/but with


short-circuit protection

82A

Evaporator pump electrical


power/control circuit
Dual evaporator pump electrical
power/control circuit
Condenser pump electrical
power/control circuit
Service valve set

84

Condenser insulation

86

Evaporator with one pass


Condenser with one pass
21 bar evaporator
21 bar condenser
Reversed evaporator water
connections
Reversed condenser water
connections
JBus gateway
BacNet gateway
LON gateway
High condensing temperature

Condensing temperature
limitation
Control for low condensing
temperature systems

81

84D

Use
Only for: 30XW 0512,
0562, 1012, 1152
As above

Only for:
30XW 1312, 1462
30XW 1612-1762
Permits an external electrical disconnect system 30XW 452-1762
for the unit (to be field-suppied).
Quick and easy installation
30XW 1002-1762
Permits an external electrical disconnect system 30XW 452-1762
for the unit (to be field-suppied). Short-circuit
protection of the unit remains.
Quick and easy installation
30XW 452-1252
30XW 452-1252

Quick and easy installation

30XW 452-1252

Simplified service and maintenance

30XW 452-1762

100C Evaporator with one pass on the water-side.


Evaporator inlet and outlet on opposite sides.
102C Condenser with one pass on the water-side.
Condenser inlet and outlet on opposite sides.
104
Reinforced evaporator for extension of the
maximum water-side service pressure to 21 bar
104A Reinforced condenser for extension of the
maximum water-side service pressure to 21 bar
107
Evaporator with reversed water inlet/outlet

Allows configuration with special installation


criteria (hot parts insulated).
Quick and easy installation. Reduced evaporator
pressure losses.
Quick and easy installation. Reduced condenser
pressure losses.
Covers applications with a high water column
(high buildings)
Covers applications with a high water column
(high buildings)
Simplification of the water piping

30XW 452-602
30XW 1002-1162
30XW 452-1762

107A Condenser with reversed water inlet/outlet

Simplification of the water piping

30XW 452-1762

148B Two-directional communications board, complies


with JBus protocol
148C Two-directional communications board, complies
with BacNet protocol
148D Two-directional communications board, complies
with LON protocol
150
Increased condenser leaving water temperature
up to 63C. To ensure control of the condenser
leaving water temperature, this option must be
fitted for 30XWH units (but not for 30XW units).
150B Limitation of the maximum condenser leaving
water temperature to 45C. Modification on the
unit name plate to reflect the reduced power input
and current values.
152
Output signal (0-10 V) to control the condenser
water inlet valve.

Easy connection by communication bus to a


building management system
Easy connection by communication bus to a
building management system
Easy connection by communication bus to a
building management system
Allows applications with high condensing
temperature (for heat reclaim or dry cooler
applications)

30XW 452-1762

84R
92

156

Code compliance for Australia

200

Water connection kit for welded


connections
Water connection kit for flanged
connections

Unit equipped with an electrical power/control


circuit for single evaporator pumps
Unit equipped with an electrical power/control
circuit for dual evaporator pumps
Unit equipped with an electrical power/control
circuit for single condenser pumps
Valve set consisting of liquid line valve (evaporator inlet), economiser return line valve and compressor suction line valve to isolate the various
refrigerant circuit components.
Thermal condenser insulation

Advantages
Covers specific applications such as ice storage
and industrial processes
Covers specific applications such as ice storage
and industrial processes
Facilitates installation in plant rooms with limited
access

Quick and easy installation

Energy Management Module


EMM
Code compliance for
Switzerland

Options
CCN JBus gateway
CCN BacNet gateway
CCN LON Talk gateway
Energy Management Module
EMM
Lead-lag kit

Description
Medium-temperature glycol solution production
down to -6C
Low-temperature glycol solution production down
to -12C
Unit supplied in two assembled parts. The unit is
equipped with flanges that allow disassembly of
the unit on site.
Unit without disconnect switch and no short-circuit
protection device supplied with the unit
Power connection of the unit via one main supply
connection
Unit without disconnect switch, but with shortcircuit protection device

197

30XW 1002-1762
30XW 452-1762
30XW 452-1762
30XW 452-1762

30XW 452-1762
30XW 452-1762
30XW 452-602
30XW 1002-1162

Avoids oversizing of the protection elements and 30XW 452-1762


the power cables.

Used for applications with cold water at the


condenser inlet (well water). In this case the
valve controls the water entering temperature to
maintain an acceptable condensing pressure.
Remote control module. Additional contacts for an Easy connection by wired connection to a
extension of the unit control functions.
building management system
Additional tests on the water heat exchangers.
Conformance with Swiss regulations
Supply of PED documents, dimensional drawings
and test certificates.
Heat exchanger approved in accordance with the Conformance with Australian regulations
Australian code.
Description
Advantages
See option 148B
See option 148B
See option 148C
See option 148C
See option 148D
See option 148D
See option 156
Easy connection by wired connection to a
building management system
Supplementary water outlet temperature sensor
Optimised operation of two chillers connected in
kit, field-installed, allows master/slave operation of parallel with operating time balancing.
two chillers connected in parallel.
Victaulic piping connections with welded joints.
Easy installation

30XW 452-1762

Victaulic piping connections with flanged joints.

30XW 452-1762

Easy installation

30XW 452-1762
30XW 452-1762
30XW 452-1762
Use
30XW 452-1762
30XW 452-1762
30XW 452-1762
30XW 452-1762
30XW 452-1762
30XW 452-1762

Physical data, standard units

Standard-efficiency units

30XW--/30XWH
Nominal cooling capacity*
Power input
EER
Eurovent class, cooling
ESEER part-load performance
Heating capacity**
Power input
Coefficient of performance (COP)
Eurovent class, heating
Nominal cooling capacity***
Power input
EER
Heating capacity***
Coefficient of performance (COP)
Operating weight
Sound power level****
Sound pressure level at 1 m
Compressors
Circuit A
Circuit B
Refrigerant charge
Circuit A
Circuit B
Oil charge
Circuit A
Circuit B
Capacity control
Minimum capacity
Evaporator
Net water volume
Water inlet/outlet connections (Victaulic)
Drain and vent connections (NPT)
Max. water-side operating pressure
Condenser
Net water volume
Water inlet/outlet connections (Victaulic)
Drain and vent connections (NPT)
Max. water-side operating pressure

452 552 602 652 702 802 852


kW
476 536 541 681 735 796 844
kW
85
98
98
120 131 144 148
kW/kW 5.58 5.47 5.52 5.68 5.61 5.53 5.69
A
A
A
A
A
A
A
kW/kW 6.30 6.40 6.50 6.93 6.85 6.86 6.91
kW
498 568 596 707 770 820 892
kW
110 127 130 158 173 184 195
kW/kW 4.51 4.46 4.57 4.46 4.46 4.45 4.58
A
A
A
A
A
A
A
kW
415 471 500 586 638 678 742
kW
110 128 130 159 173 185 193
kW/kW 3.76 3.69 3.84 3.69 3.68 3.67 3.84
kW
516 588 619 730 795 846 917
kW/kW 4.67 4.60 4.75 4.60 4.59 4.58 4.75
kg
2575 2613 2644 3247 3266 3282 3492
dB(A)
99
99
99
99
99
99
99
dB(A)
82
82
82
82
82
82
82
Semi-hermetic 06T screw compressors, 50 r/s
1
1
1
1
1
1
1
R-134a
kg
82
82
82
145 140 135 140
kg
SW220
l
32
32
32
36
36
36
36
l
Pro-Dialog, electronic expansion valves (EXV)
%
15
15
15
15
15
15
15
Multi-pipe flooded type
l
72
72
72
109 109 109 98
in
5
5
5
6
6
6
6
in
3/8
3/8
3/8
3/8
3/8
3/8
3/8
kPa
1000 1000 1000 1000 1000 1000 1000
Multi-pipe type
l
80
80
80
80
80
80
141
in
5
5
5
6
6
6
8
in
3/8
3/8
3/8
3/8
3/8
3/8
3/8
kPa
1000 1000 1000 1000 1000 1000 1000

30XW-P/30XWHP
Nominal cooling capacity*
Power input
EER
Eurovent class, cooling
ESEER part-load performance
Heating capacity**
Power input
Coefficient of performance (COP)
Eurovent class, heating
Nominal cooling capacity***
Power input
EER
Heating capacity***
Coefficient of performance (COP)
Operating weight
Sound power level****
Sound pressure level at 1 m
Compressors
Circuit A
Circuit B
Refrigerant charge
Circuit A
Circuit B
Oil charge
Circuit A
Circuit B
Capacity control
Minimum capacity
Evaporator
Net water volume
Water inlet/outlet connections (Victaulic)
Drain and vent connections (NPT)
Max. water-side operating pressure
Condenser
Net water volume
Water inlet/outlet connections (Victaulic)
Drain and vent connections (NPT)
Max. water-side operating pressure

512
562
712
812
862
kW
512
581
740
789
865
kW
86
97
122
134
145
kW/kW 5.97
5.99
6.07
5.87
5.96
A
A
A
A
A
kW/kW 6.78
6.79
7.00
7.05
6.98
kW
547
621
793
854
924
kW
113
129
163
182
193
kW/kW 4.85
4.81
4.87
4.69
4.78
A
A
A
A
A
kW
463
525
672
718
780
kW
113
129
163
182
193
kW/kW 4.11
4.08
4.14
3.94
4.04
kW
566
642
820
884
956
kW/kW 5.02
4.99
5.05
4.85
4.95
kg
2981
3020
3912
3947
3965
dB(A)
99
99
99
99
99
dB(A)
82
82
81
81
81
Semi-hermetic 06T screw compressors, 50 r/s
1
1
1
1
1
R-134a
kg
130
130
180
175
170
kg
SW220
l
32
32
36
36
36
l
Pro-Dialog, electronic expansion valves (EXV)
%
15
15
15
15
15
Multi-pipe flooded type
l
106
106
154
154
154
in
6
6
8
8
8
in
3/8
3/8
3/8
3/8
3/8
kPa
1000
1000
1000
1000
1000
Multi-pipe type
l
112
112
165
165
165
in
6
6
8
8
8
in
3/8
3/8
3/8
3/8
3/8
kPa
1000
1000
1000
1000
1000

High-efficiency units

1002
1024
184
5.57
A
7.13
1070
238
4.49
A
889
239
3.72
1106
4.63
5370
102
84

1052
1068
193
5.54
A
7.48
1121
251
4.47
A
928
251
3.69
1156
4.60
5408
102
84

1152
1156
200
5.78
A
7.46
1246
264
4.71
A
1049
264
3.97
1290
4.88
5705
102
84

1252
1265
211
6.00
A
7.72
1308
278
4.70
A
1101
278
3.96
1354
4.87
7066
102
83

1352
1349
232
5.81
A
7.47
1405
303
4.64
A
1177
302
3.89
1452
4.80
7267
102
83

1452
1463
255
5.73
A
7.35
1531
334
4.59
A
1281
334
3.84
1585
4.75
7305
102
83

1552
1560
274
5.70
A
7.16
1629
356
4.57
A
1362
357
3.82
1687
4.73
7337
102
83

1652
1664
279
5.96
A
7.36
1790
375
4.78
A
1515
374
4.05
1855
4.96
8681
102
83

1702
1739
290
5.99
A
7.30
1867
388
4.81
A
1577
389
4.06
1930
4.97
8699
102
83

1
1

1
1

1
1

1
1

1
1

1
1

1
1

1
1

1
1

85
85

85
85

105
105

120
120

115
115

110
110

105
105

195
195

195
195

32
32

32
32

32
32

36
32

36
36

36
36

36
36

36
36

36
36

10

10

10

10

10

10

10

10

10

185
6
3/8
1000

185
6
3/8
1000

214
8
3/8
1000

307
8
3/8
1000

307
8
3/8
1000

307
8
3/8
1000

307
8
3/8
1000

363
8
3/8
1000

363
8
3/8
1000

238
8
3/8
1000

238
8
3/8
1000

238
8
3/8
1000

347
8
3/8
1000

347
8
3/8
1000

347
8
3/8
1000

347
8
3/8
1000

426
8
3/8
1000

426
8
3/8
1000

1012
1047
174
6.03
A
7.64
1110
228
4.86
A
941
228
4.13
1149
5.04
6872
102
83

1162
1165
191
6.09
A
7.99
1246
253
4.92
A
1061
253
4.20
1290
5.11
6950
102
83

1312
1320
216
6.12
A
7.72
1411
287
4.92
A
1198
286
4.19
1459
5.10
9099
102
83

1462
1474
242
6.09
A
7.59
1584
322
4.92
A
1350
321
4.20
1642
5.11
9307
102
83

1612
1632
266
6.13
A
7.65
1752
361
4.85
A
1485
361
4.12
1813
5.03
10910
102
83

1762
1764
290
6.08
A
7.18
1872
396
4.73
A
1576
396
3.98
1936
4.89
10946
102
83

1
1

1
1

1
1

1
1

1
1

1
1

120
120

120
120

205
205

205
205

240
240

250
250

32
32

32
32

36
32

36
36

36
36

36
36

10

10

10

10

10

10

307
8
3/8
1000

307
8
3/8
1000

363
8
3/8
1000

363
8
3/8
1000

473
10
3/8
1000

473
10
3/8
1000

347
8
3/8
1000

347
8
3/8
1000

497
10
3/8
1000

497
10
3/8
1000

623
10
3/8
1000

623
10
3/8
1000

* Standard Eurovent conditions, cooling: evaporator entering/leaving water temperature = 12C/7C, condenser entering/leaving water temperature = 30C/35C.
** Standard Eurovent conditions, heating: condenser entering/leaving water temperature = 40C/45C, evaporator entering water temperature 10C with the same flow rate as for Eurovent
conditions in cooling mode.
*** Conditions in cooling and heating mode: evaporator entering/leaving water temperature = 10C/7C. condenser entering/leaving water temperature = 40C/45C.
**** 10-12 W in accordance with ISO 9614-1
in a free field
Weights are guidelines only. The refrigerant charge is given on the unit nameplate

Electrical data, standard units

Standard-efficiency units

30XW--/30XWH
Power circuit
Nominal power supply
Voltage range
Control circuit
Nominal start-up current*
Circuit A
Circuit B
Option 81
Maximum start-up current**
Circuit A
Circuit B
Option 81
Cosine phi nominal***
Cosine phi maximum****
Maximum power input
Circuit A
Circuit B
Option 81
Nominal current drawn***
Circuit A
Circuit B
Option 81
Maximum current drawn (Un)
Circuit A
Circuit B
Option 81
Maximum current drawn (Un -10%)****
Circuit A
Circuit B
Option 81

452

602

652

702

802

852

1002 1052 1152 1252 1352 1452 1552 1652 1702

V-ph-Hz 400-3-50
V
360-440
24 V via the built-in transformer
A
A
A

414
-

414
-

414
-

587
-

587
-

587
-

587
-

414
414
558

414
414
574

414
414
574

587
414
747

587
587
780

587
587
801

587
587
819

587
587
819

587
587
819

A
A
A

414
0.86
0.89

414
0.87
0.90

414
0.87
0.90

587
0.88
0.90

587
0.89
0.91

587
0.90
0.92

587
0.90
0.92

414
414
631
0.87
0.90

414
414
656
0.87
0.90

414
414
656
0.87
0.90

587
414
829
0.88
0.90

587
587
882
0.88
0.90

587
587
904
0.89
0.91

587
587
938
0.90
0.92

587
587
938
0.90
0.92

587
587
938
0.90
0.92

kW
kW
kW

134
-

151
-

151
-

184
-

200
-

223
-

223
-

150
134
284

151
151
301

151
151
301

184
151
334

184
184
367

200
200
399

223
223
447

223
202
425

223
223
447

A
A
A

144
-

162
-

162
-

193
-

214
-

232
-

232
-

162
144
306

162
162
324

162
162
324

193
162
355

193
193
386

214
214
427

232
232
464

232
214
446

232
232
464

A
A
A

217
-

242
-

242
-

295
-

317
-

351
-

351
-

242
217
459

242
242
484

242
242
484

295
242
537

295
295
590

317
317
634

351
351
702

351
317
668

351
351
702

A
A
A

230
-

260
-

260
-

304
-

340
-

358
-

358
-

260
230
490

260
260
520

260
260
520

304
260
564

304
304
608

340
340
680

358
358
716

358
340
698

358
358
716

High-efficiency units

30XW-P/30XWHP
Power circuit
Nominal power supply
Voltage range
Control circuit
Nominal start-up current*
Circuit A
Circuit B
Option 81
Maximum start-up current**
Circuit A
Circuit B
Option 81
Cosine phi nominal***
Cosine phi maximum****
Maximum power input
Circuit A
Circuit B
Option 81
Nominal current drawn***
Circuit A
Circuit B
Option 81
Maximum current drawn (Un)
Circuit A
Circuit B
Option 81
Maximum current drawn (Un -10%)****
Circuit A
Circuit B
Option 81

552

512

562

712

812

862

1012

1162

1312

1462

1612

1762

V-ph-Hz 400-3-50
V
360-440
24 V via the built-in transformer
A
A
A

414
-

414
-

587
-

587
-

587
-

414
414
556

414
414
574

587
414
747

587
587
780

587
587
801

587
587
819

A
A
A

414
0.86
0.89

414
0.87
0.90

587
0.88
0.90

587
0.89
0.91

587
0.90
0.92

414
414
631
0.86
0.89

414
414
656
0.87
0.90

587
414
829
0.88
0.90

587
587
882
0.88
0.90

587
587
904
0.89
0.91

587
587
938
0.90
0.92

kW
kW
kW

134
-

151
-

184
-

200
-

223
-

134
134
267

151
151
301

184
151
334

184
184
367

200
200
399

223
223
447

A
A
A

144
-

162
-

193
-

214
-

232
-

144
144
288

162
162
324

193
162
355

193
193
386

214
214
427

232
232
464

A
A
A

217
-

242
-

295
-

317
-

351
-

217
217
434

242
242
484

295
242
537

295
295
590

317
317
634

351
351
702

A
A
A

230
-

260
-

304
-

340
-

358
-

230
230
460

260
260
520

304
260
564

304
304
608

340
340
680

358
358
716

* Instantaneous start-up current (maximum operating current of the smallest compressor(s) + locked rotor current or reduced start-up current of the largest compressor). Values obtained at
standard Eurovent unit operating conditions: evaporator entering/leaving water temperature = 12C/7C, condenser entering/leaving water temperature = 30C/35C.
** Instantaneous start-up current (maximum operating current of the smallest compressor(s) + locked rotor current or reduced start-up current of the largest compressor). Values obtained at
operation with maximum unit power input.
*** Values obtained at standard Eurovent unit operating conditions: evaporator entering/leaving water temperature = 12C/7C, condenser entering/leaving water temperature = 30C/35C
**** Values obtained at operation with maximum unit power input.
Values obtained at operation with maximum unit power input. Values given on the unit name plate.

Physical data, units for high condensing temperatures

Standard-efficiency units (option 150)


30XW--/30XWH
Nominal cooling capacity*
Power input
EER
Eurovent class, cooling
Heating capacity**
Power input
Coefficient of performance (COP)
Eurovent class, heating
Nominal cooling capacity***
Power input
EER
Heating capacity***
Coefficient of performance (COP)
Operating weight
Sound power level****
Sound pressure level at 1 m
Compressors
Circuit A
Circuit B
Refrigerant charge
Circuit A
Circuit B
Oil charge
Circuit A
Circuit B
Capacity control
Minimum capacity
Evaporator
Net water volume
Water inlet/outlet connections (Victaulic)
Drain and vent connections (NPT)
Max. water-side operating pressure
Condenser
Net water volume
Water inlet/outlet connections (Victaulic)
Drain and vent connections (NPT)
Max. water-side operating pressure

kW
kW
kW/kW
kW
kW
kW/kW
kW
kW
kW/kW
kW
kW/kW
kg
dB(A)
dB(A)

kg
kg
l
l
%
l
in
in
kPa
l
in
in
kPa

High-efficiency units (option 150)


30XW-P/30XWHP
Nominal cooling capacity*
Power input
EER
Eurovent class, cooling
Heating capacity**
Power input
Coefficient of performance (COP)
Eurovent class, heating
Nominal cooling capacity***
Power input
EER
Heating capacity***
Coefficient of performance (COP)
Operating weight
Sound power level****
Sound pressure level at 1 m
Compressors
Circuit A
Circuit B
Refrigerant charge
Circuit A
Circuit B
Oil charge
Circuit A
Circuit B
Capacity control
Minimum capacity
Evaporator
Net water volume
Water inlet/outlet connections (Victaulic)
Drain and vent connections (NPT)
Max. water-side operating pressure
Condenser
Net water volume
Water inlet/outlet connections (Victaulic)
Drain and vent connections (NPT)
Max. water-side operating pressure

kW
kW
kW/kW
kW
kW
kW/kW
kW
kW
kW/kW
kW
kW/kW
kg
dB(A)
dB(A)

kg
kg
l
l
%
l
in
in
kPa
l
in
in
kPa

452 552 602 652 702 802 852 1002


462 518 526 977
91
102 104 193
5.06 5.06 5.07 5.05
A
A
A
A
485 542 581 1027
105 119 123 224
4.60 4.56 4.72 4.59
A
A
A
A
331 369 431 699
135 152 164 287
2.46 2.43 2.64 2.44
454 508 580 960
3.37 3.34 3.55 3.35
2575 2613 2644 5370
99
99
99
102
82
82
82
84
Semi-hermetic 06T screw compressors, 50 r/s
1
1
1
1
1
R-134a
82
82
82
85
85
SW220
32
32
32
32
32
Pro-Dialog, electronic expansion valves (EXV)
30
30
30
20
Multi-pipe flooded type
72
72
72
185
5
5
5
6
3/8 3/8 3/8 3/8
1000 1000 1000 1000
Multi-pipe type
80
80
80
238
5
5
5
8
3/8 3/8 3/8 3/8
1000 1000 1000 1000

512
562
712
812
862
520
580
96
105
5.43
5.51
A
A
562
625
113
124
4.99
5.04
A
A
419
466
150
165
2.80
2.83
555
617
3.71
3.74
2981
3020
99
99
82
82
Semi-hermetic 06T screw compressors, 50 r/s
1
1
R-134a
130
130
SW220
32
32
Pro-Dialog, electronic expansion valves (EXV)
30
30
Multi-pipe flooded type
106
106
6
6
3/8
3/8
1000
1000
Multi-pipe type
112
112
6
6
3/8
3/8
1000
1000
-

1052
1037
205
5.06
A
1085
238
4.56
A
739
304
2.43
1015
3.34
5408
102
84

1152
1129
216
5.21
A
1229
255
4.82
A
908
339
2.68
1216
3.59
5705
102
84

1252
-

1352
-

1452
-

1552
-

1652
-

1702
-

1
1

1
1

85
85

105
105

32
32

32
32

20

20

185
6
3/8
1000

214
8
3/8
1000

238
8
3/8
1000

238
8
3/8
1000

1012
1017
195
5.21
A
1107
230
4.82
A
817
306
2.67
1096
3.58
6872
102
83

1162
1142
215
5.32
A
1241
253
4.91
A
916
338
2.71
1224
3.62
6950
102
83

1312
-

1462
-

1612
-

1762
-

1
1

1
1

120
120

120
120

32
32

32
32

20

20

307
8
3/8
1000

307
8
3/8
1000

347
8
3/8
1000

347
8
3/8
1000

* Standard Eurovent conditions, cooling: evaporator entering/leaving water temperature = 12C/7C, condenser entering/leaving water temperature = 30C/35C.
** Standard Eurovent conditions, heating: condenser entering/leaving water temperature = 40C/45C, evaporator entering water temperature 10C with the same flow rate as for Eurovent
conditions in cooling mode.
*** Conditions in cooling and heating mode: evaporator entering/leaving water temperature = 10C/7C. condenser entering/leaving water temperature = 50C/60C.
**** 10-12 W in accordance with ISO 9614-1
in a free field
Weights are guidelines only. The refrigerant charge is given on the unit nameplate.

Electrical data, units for high condensing temperatures

Standard-efficiency units (option 150)


30XW--/30XWH
Power circuit
Nominal power supply
Voltage range
Control circuit
Nominal start-up current*
Circuit A
Circuit B
Option 81
Maximum start-up current**
Circuit A
Circuit B
Option 81
Cosine phi nominal***
Cosine phi maximum****
Maximum power input
Circuit A
Circuit B
Option 81
Nominal current drawn***
Circuit A
Circuit B
Option 81
Maximum current drawn (Un)
Circuit A
Circuit B
Option 81
Maximum current drawn (Un -10%)****
Circuit A
Circuit B
Option 81

452

602

652

702

802

852

1002 1052 1152 1252 1352 1452 1552 1652 1702

V-ph-Hz 400-3-50
V
360-440
24 V via the built-in transformer
A
A
A

587
-

587
-

587
-

587
587
757

587
587
757

587
587
757

A
A
A

587
0.88
0.91

587
0.88
0.92

587
0.88
0.92

587
587
887
0.88
0.92

587
587
887
0.88
0.92

587
587
887
0.88
0.92

kW
kW
kW

173
-

191
-

191
-

190
174
364

191
191
382

191
191
382

A
A
A

162
-

171
-

171
-

171
162
333

171
171
342

171
171
342

A
A
A

275
-

300
-

300
-

300
275
575

300
300
600

300
300
600

A
A
A

300
-

330
-

330
-

330
300
630

330
330
660

330
330
660

High-efficiency units (option 150)


30XW-P/30XWHP
Power circuit
Nominal power supply
Voltage range
Control circuit
Nominal start-up current*
Circuit A
Circuit B
Option 81
Maximum start-up current**
Circuit A
Circuit B
Option 81
Cosine phi nominal***
Cosine phi maximum****
Maximum power input
Circuit A
Circuit B
Option 81
Nominal current drawn***
Circuit A
Circuit B
Option 81
Maximum current drawn (Un)
Circuit A
Circuit B
Option 81
Maximum current drawn (Un -10%)****
Circuit A
Circuit B
Option 81

552

512

562

712

812

862

1012

1162

1312

1462

1612

1762

V-ph-Hz 400-3-50
V
360-440
24 V via the built-in transformer
A
A
A

587
-

587
-

587
587
749

587
587
757

A
A
A

587
0.88
0.91

587
0.88
0.92

587
587
862
0.87
0.91

587
587
887
0.88
0.92

kW
kW
kW

173
-

191
-

173
173
346

191
191
382

A
A
A

162
-

171
-

162
162
324

171
171
342

A
A
A

275
-

300
-

275
275
550

300
300
600

A
A
A

300
-

330
-

300
300
600

330
330
660

* Instantaneous start-up current (maximum operating current of the smallest compressor(s) + locked rotor current or reduced start-up current of the largest compressor). Values based on standard
Eurovent unit operating conditions: evaporator entering/leaving water temp. = 12C/7C, condenser entering/leaving water temp. = 30C/35C.
** Instantaneous start-up current (maximum operating current of the smallest compressor(s) + locked rotor current or reduced start-up current of the largest compressor). Values obtained at
operation with maximum unit power input.
*** Values based on standard Eurovent unit operating conditions: evaporator entering/leaving water temp. = 12C/7C, condenser entering/leaving water temp. = 30C/35C.
**** Values obtained at operation with maximum unit power input.
Values obtained at operation with maximum unit power input. Values given on the unit name plate.

Physical data, low-temperature units

Standard and high-efficiency 30XW-/30XWH units (options 5 and 6)


Reference number
Nominal cooling capacity*
Power input
EER
Heating capacity
Coefficient of performance (COP)
Nominal cooling capacity**
Power input
EER
Heating capacity
Coefficient of performance (COP)

kW
kW
kW/kW
kW
kW/kW
kW
kW
kW/kW
kW
kW/kW

Option 5 (medium temperature)


P0512
P0562
P1012
298
332
626
85
93
173
3.49
3.56
3.62
376
417
784
4.40
4.47
4.53
316
354
668
87
95
176
3.65
3.72
3.80
395
440
827
4.56
4.63
4.71

-1152
705
193
3.66
880
4.57
760
196
3.87
938
4.78

Option 6 (low temperature)


P0512
P0562
P1012
222
245
452
80
87
163
2.76
2.81
2.78
295
325
601
3.67
3.72
3.69
245
271
505
82
89
167
3.00
3.04
3.03
320
352
657
3.91
3.95
3.94

Option 5
* Values based on 25% ethylene glycol, evaporator entering/leaving water temperatures of -2C/-6C and condenser entering/leaving water temperatures of 30C/35C.
** Values based on 24% propylene glycol, evaporator entering/leaving water temperatures of +1C/-3C and condenser entering/leaving water temperatures of 30C/35C.
Note: Evaporator with 2 pass configuration with water inlet and outlet on the same side.

-1152
502
178
2.81
664
3.73
558
182
3.06
724
3.97

Option 6
* Values based on 35% ethylene glycol, evaporator entering/leaving water temperatures of -8C/-12C and condenser entering/leaving water temperatures of 30C/35C.
** Values based on 30% propylene glycol, evaporator entering/leaving water temperatures of -4C/-8C and condenser entering/leaving water temperatures of 30C/35C.
Note: Evaporator with 3 pass configuration with water inlet and outlet on opposite sides.

Electrical data, low-temperature units

Standard and high-efficiency 30XW-/30XWH units (options 5 and 6)


Options 5 and 6
Reference number
P0512 P0562 P1012 -1152
Power circuit
Nominal power supply
V-ph-Hz 400-3-50
Voltage range
V
360-440
Control circuit
24 V via the built-in transformer
Nominal start-up current*
Circuits A/B
A
587/587/587/587 587/587
Option 81
A
749
757
Maximum start-up current**
Circuits A/B
A
587/587/587/587 587/587
Option 81
A
862
887
Cosine phi nominal***
0.88
0.88
0.87
0.88
Cosine phi maximum****
0.91
0.92
0.91
0.92
Maximum power input
Circuits A/B
kW
173/191/173/173 191/191
Option 81
kW
346
382
Nominal current drawn***
Circuits A/B
A
162/171/162/162 171/171
Option 81
A
324
342
Maximum current drawn (Un)
Circuits A/B
A
275/300/275/275 300/300
Option 81
A
550
600
Maximum current drawn (Un -10%)
Circuits A/B
A
300/330/300/300 330/330
Option 81
A
600
660

* Instantaneous start-up current (maximum operating current of the smallest compressor(s)


+ locked rotor current or reduced start-up current of the largest compressor). Values
obtained at standard Eurovent unit operating conditions: evaporator entering/leaving water
temperature = 12C/7C, condenser entering/leaving water temperature = 30C/35C.
** Instantaneous start-up current (maximum operating current of the smallest compressor(s) +
locked rotor current or reduced start-up current of the largest compressor). Values obtained
at operation with maximum unit power input.
*** Values obtained at standard Eurovent unit operating conditions: evaporator entering/leaving
water temperature = 12C/7C, condenser entering/leaving water temperature = 30C/35C.
Maximum values obtained at operation with maximum unit power input.
**** Values obtained at operation with maximum unit power input.
Values obtained at operation with maximum unit power input. Values given on the unit name
plate.

Notes, electrical data and operating conditions 30XW


As standard
30XW 452 to 862 units have a single power connection point located immediately
upstream of the main disconnect switch.
30XW 1002 to 1762 units have two connection points located immediately upstream of the
main disconnect switches.
The control box includes the following standard features:
- One main disconnect switch per circuit*
- Starter and motor protection devices for each compressor
- Anti-short cycle protection devices**
- Control devices
Field connections:
All connections to the system and the electrical installations must be in full accordance
with all applicable codes.
The Carrier 30XW units are designed and built to ensure conformance with local codes.
The recommendations of European standard EN 60204-1 (corresponds to IEC 60204-1)
(machine safety - electrical machine components - part 1: general regulations) are
specifically taken into account, when designing the electrical equipment.
The absence of power supply disconnect switch(es) and short-cycle protection devices in
options 82A and 70E is an important factor that has to be taken into consideration at the
installation site.
Units equipped with one of these two options are supplied with a declaration of
incorporation, as required by the machinery directive.
Notes:
Generally the recommendations of IEC 60364 are accepted as compliance with the
requirements of the installation directives. Conformance with EN 60204-1 is the best
means of ensuring compliance with the Machines Directive and 1.5.1.
Annex B of EN 60204 1 describes the electrical characteristics used for the operation of
the machines.

1. The operating environment for the 30XW units is specified below:


Environment*** Environment as classified in EN 60721 (corresponds to IEC 60721):
- indoor installation
- ambient temperature range: minimum temperature +5C to +42C, class AA4
- altitude: lower than or equal to 2000 m
- presence of water: class AD2 (possibility of water droplets)
- presence of hard solids, class 4S2 (no significant dust present)
- presence of corrosive and polluting substances, class 4C2 (negligible)
2. Power supply frequency variation: 2 Hz.
3. The neutral (N) line must not be connected directly to the unit (if necessary use a
transformer).
4. Overcurrent protection of the power supply conductors is not provided with the unit.
5. The factory installed disconnect switch(es)/circuit breaker(s) is (are) of a type suitable for
power interruption in accordance with EN 60947-3 (corresponds to IEC 60947-3).
6. The units are designed for connection to TN networks (IEC 60364). For IT networks
the earth connection must not be at the network earth. Provide a local earth, consult
competent local organisations to complete the electrical installation.

NOTE: If particular aspects of an actual installation do not conform to the


conditions described above, or if there are other conditions which should be
considered, always contact your local Carrier representative.

* Not provided for units equipped with options 70E and 82A
** Not provided for units equipped with option 70E
*** The required protection level for this class is IP21BW (according to reference document
IEC 60529). All 30XW units are protected to IP23C and fulfil this protection condition.

Dimensions/clearances

30XW--/30XWH- 452-852
30XW-P/30XWHP 512-862

Evaporator

Condenser

Dimensions in mm
A
B
C
D
E
F
Standard-efficiency units 30XW--/30XWH452
1693 810 936 2742 141.3 141.3
552
1693 810 936 2742 141.3 141.3
602
1693 810 936 2742 141.3 141.3
652
1848 968 1044 3059 168.3 168.3
702
1848 968 1044 3059 168.3 168.3
802
1848 968 1044 3059 168.3 168.3
852
1898 828 1044 2780 219.1 168.3
High-efficiency units 30XW-P/30XWHP
512
1743 968 936 3059 168.3 168.3
562
1743 968 936 3059 168.3 168.3
712
1950 1083 1065 3290 219.1 219.1
812
1950 1083 1070 3290 219.1 219.1
862
1950 1083 1070 3290 219.1 219.1

G
2600
2600
2600
2900
2900
2900
2600
2900
2900
3100
3100
3100

Legend:

1
2

All dimensions are in mm.

Required clearance for maintenance


Recommended clearance for tube removal
Water inlet
Water outlet
Power supply connection

NOTE: Drawings are not contractually binding.


Before designing an installation, consult the certified
dimensional drawings, available on request.

10

Dimensions/clearances

30XW--/30XWH- 1002-1552
30XW-P/30XWHP 1012-1162

Evaporator

Condenser
Dimensions in mm
A
B
C
D
E
F
Standard-efficiency units 30XW--/30XWH1002 1870 950 1036 4025 219.1 168.3
1052 1870 950 1036 4025 219.1 168.3
1152 1926 950 1036 4025 219.1 219.1
1252 2051 1512 1162 4730 219.1 219.1
1352 2051 1512 1162 4730 219.1 219.1
1452 2051 1512 1162 4730 219.1 219.1
1552 2051 1512 1162 4730 219.1 219.1
High-efficiency units 30XW-P / 30XHP
1012 1997 1512 1039 4795 219.1 219.1
1162 1997 1512 1039 4795 219.1 219.1

G
3800
3800
3800
4500
4500
4500
4500
4500
4500

Legend:

1
2

All dimensions are in mm.

Required clearance for maintenance


Recommended clearance for tube removal
Water inlet
Water outlet
Power supply connection

NOTE: Drawings are not contractually binding.


Before designing an installation, consult the certified
dimensional drawings, available on request.

11

Dimensions/clearances

30XW--/30XWH- 1652-1702
30XW-P/30XWHP 1312-1762

Dimensions in mm
A
B
C
D
E
F
Standard-efficiency units 30XW--/30XWH1652 1541 1568 1902 4790 219.1 219.1
1702 1541 1568 1902 4790 219.1 219.1
High-efficiency units 30XW-P/30XHP
1312 1541 1581 1935 4812 273.0 219.1
1462 1541 1581 1935 4812 273.0 219.1
1612 1594 1591 2129 4832 273.0 273.0
1762 1594 1591 2129 4832 273.0 273.0

G
4500
4500
4500
4500
4600
4600

Evaporator
Legend:

All dimensions are in mm.

1
2

Required clearance for maintenance


Recommended clearance for tube removal
Water inlet
Water outlet
Power supply connection

Condenser

12

NOTE: Drawings are not contractually binding.


Before designing an installation, consult the certified
dimensional drawings, available on request.

Standard 30XW-- and 30XW-P units


Evaporator
Entering temperature at start-up
Leaving temperature during operation
Entering/leaving temperature difference at full load
Condenser
Entering temperature at start-up
Leaving temperature during operation
Entering/leaving temperature difference at full load

Minimum

Maximum

-
3.3C*
2.8 K

35.0C
20.0C
11.1 K

13.0C**
19.0C**
2.8 K

50.0C***
11.1 K

* For low-temperature applications, where the leaving water temperature is below 3.3C, a
frost protection solution must be used. Please refer to option 5 and option 6.
** For lower condenser temperatures, a water flow control valve must be used at the condenser
(two or three-way valve). Please refer to option 152 to ensure the correct condensing
temperature.
*** Please refer to option 150 for applications with a high condenser leaving temperature (up to
63C).

Standard units

From approx. 45% to full load


Part load limit approx. 35%

Condenser leaving water temperature, C

Operating limits and operating ranges

Minimum load limit approx. 15%

Minimum

Maximum

-
3.3C*
2.8 K

35.0C
15.0C
11.1 K

13.0C**
23.0C**
2.8 K

63.0C
11.1 K

50
45
40
35
30
25
20
15

Option 150

0
5
10
15
20
Evaporator leaving water temperature, C

70

* For low-temperature applications, where the leaving water temperature is below 3.3C, a
frost protection solution must be used. Please refer to option 5 and option 6.
** For lower condenser temperatures, a water flow control valve must be used at the condenser
(two or three-way valve). Please refer to option 152 to ensure the correct condensing
temperature.
From approx. 60% to full load
Part load limit approx. 50%

Condenser leaving water temperature, C

Units with option 150


30XW--/30XWH-/30XW-P/30XWHP
Evaporator
Entering temperature at start-up
Leaving temperature during operation
Entering/leaving temperature difference at full load
Condenser
Entering temperature at start-up
Leaving temperature during operation
Entering/leaving temperature difference at full load

55

65
60
55
50
45
40
35
30
25
20

10

15

20

Evaporator leaving water temperature, C

Minimum load limit approx. 30%

PG 5
EG 6
PG 6

Minimum

Maximum

35.0C

-6C
-3C
-12C
-8C
2.8 K

15.0C
15.0C
15.0C
15.0C
11.1 K***

Condenser
Entering temperature at start-up
13.0C**
Leaving temperature during operation
19.0/23.0C**

Entering/leaving temperature difference at full load 2.8 K

55.0/
63.0C****
11.1 K

* The operating range with evaporator leaving temperatures above 3C is permitted, but the
performances are not optimised.
** For lower condenser temperatures, a water flow control valve must be installed at the
condenser (two-way or three-way). Please refer to option 152 to ensure the correct
condensing temperature.
*** Please refer to chapter 10.5 of the installation manual for the minimum recommended
evaporator glycol flow rate.
**** Depends on the conditions at the evaporator and the load conditions.

Options 5 and 6
70

Condenser leaving water temperature, C

EG 5

Units with options 5 and 6


30XW--/30XWH-/30XW-P/30XWHP
Evaporator
Entering temperature at start-up
Leaving temperature during operation*
Option 5 with ethylene glycol
Option 5 with propylene glycol
Option 6 with ethylene glycol
Option 6 with propylene glycol
Entering/leaving temperature difference at full load

65
60
55
50
45
40
35

EG 6

30

PG 6
EG 5

25

PG 5

20
15

-15

-10

-5
0
5
10
15
Evaporator leaving glycol temperature, C

20

Operating range permitted, but performances are not optimised


Full load with option 5/6 and ethylene or propylene glycol

Part load limit approx. 80%

Part load limit approx. 50%

Part load limit approx. 30%

Note: Ambient temperatures: During storage and transport of the 30XW units (including by
container) the minimum and maximum permissible temperatures are -20C and 72C (and 65C
for option 200).

13

Evaporator pressure drop curves


Units with one evaporator pass (option 100C):
30XW--/30XWH-/30XW-P/30XWHP

120

36

110

33

100

30

90

27

80

24

Pressure drop, kPa

Pressure drop, kPa

Units with two evaporator passes (standard):


30XW--/30XWH-/30XW-P/30XWHP

70
60
50
40

21
18
15
12

30

20

10

10

20

30

40

50

60

70

Water flow rate, l/s

80

90

100 110 120

Legend
1 452, 552, 602
2 512, 562, 652, 702, 802
3 712, 812, 862
4 852
5 1002, 1052
6 1012, 1162, 1252, 1352, 1452, 1552
7 1152
8 1312, 1462, 1652, 1702
9 1612, 1762

10

20

30

40

50

60

70

Water flow rate, l/s

80

90

100 110 120

Legend
1 452, 552, 602
2 512, 562, 652, 702, 802
3 712, 812, 862
4 852
5 1002, 1052
6 1012, 1162, 1252, 1352, 1452, 1552
7 1152
8 1312, 1462, 1652, 1702
9 1612, 1762

Condenser pressure drop curves


120

36

110

33

100

30

90

27

80

24

70
60
50
40

21
18
15
12

30

20

10

10

20

30

40

Legend
1 452, 552, 602
2 512, 562, 652, 702, 802
3 712, 812, 862
4 852
5 1002, 1052
6 1152
7 1012, 1162, 1252, 1352, 1452, 1552
8 1312, 1462
9 1652, 1702
0 1612, 1762

14

Units with one condenser pass (option 102C):


30XW--/30XWH-/30XW-P/30XWHP

Pressure drop, kPa

Pressure drop, kPa

Units with two condenser passes (standard):


30XW--/30XWH-/30XW-P/30XWHP

50

60

70

Water flow rate, l/s

80

90

100 110 120

10

20

30

40

50

60

70

Water flow rate, l/s

Legend
1 1002, 1052
2 1152
3 1012, 1162, 1252, 1352, 1452, 1552
4 1312, 1462
5 1652, 1702
6 1612, 1762

80

90

100 110 120

Cooling and heating capacities, standard units


Evaporator leaving water temperature = 5C

Condenser leaving water temperature. C


30XW 30
35
Qc
Qh
Unit Cool Cool Qc
Qh
kW kW kW l/s
kPa kW kW
Standard-efficiency units 30XW--/30XWH452 462 530 75
22.0 36
441 518
552 517 596 86
24.6 45
497 586
602 523 601 86
24.9 46
505 595
652 657 754 107 31.3 43
632 741
702 717 822 116 34.1 51
682 801
802 768 883 126 36.6 57
738 868
852 813 931 130 38.7 58
798 935
1002 992 1140 163 47.2 70
947 1114
1052 1042 1197 170 49.6 76
992 1167
1152 1104 1263 174 52.6 63
1084 1266
1252 1233 1403 187 58.7 65
1175 1367
1352 1326 1510 203 63.1 75
1253 1465
1452 1437 1640 223 68.4 88
1359 1592
1552 1533 1751 239 73.0 99
1447 1696
1652 1608 1829 244 76.5 56
1557 1812
1702 1679 1910 254 80.0 61
1627 1892
High-efficiency units 30XW-P/30XWHP
512 487 555 75
23.2 25
477 555
562 553 630 85
26.3 32
542 631
712 708 805 106 33.7 30
690 801
812 758 866 118 36.1 34
736 860
862 826 941 127 39.3 39
803 936
1012 970 1107 150 46.2 41
975 1133
1162 1122 1274 167 53.4 55
1088 1263
1312 1260 1431 187 60.0 34
1232 1429
1462 1417 1608 210 67.5 44
1377 1598
1612 1573 1786 235 74.9 52
1528 1771
1762 1682 1915 256 80.1 59
1644 1909

40
Unit Cool Cool Qc
kW l/s
kPa kW

Qh
kW

45
Unit Cool Cool Qc
kW l/s
kPa kW

Qh
kW

50
Unit Cool Cool Qc
kW l/s
kPa kW

Qh
kW

Unit Cool Cool


kW l/s
kPa

85
98
99
120
131
143
150
184
192
200
211
232
256
274
280
291

21.0
23.7
24.1
30.1
32.5
35.2
38.0
45.1
47.2
51.6
55.9
59.7
64.7
68.9
74.1
77.5

33
42
43
40
46
53
56
64
70
61
60
67
79
89
53
58

412
467
487
590
636
685
752
891
936
1028
1103
1178
1279
1359
1488
1555

500
569
590
716
774
833
909
1083
1137
1238
1324
1420
1545
1643
1784
1861

97
112
114
138
151
162
172
210
221
231
242
266
292
312
326
337

19.6
22.2
23.2
28.1
30.3
32.6
35.8
42.4
44.6
48.9
52.5
56.1
60.9
64.7
70.8
74.0

29
37
40
36
41
47
51
57
63
56
53
60
70
79
48
53

386
439
467
545
594
632
697
828
866
985
1028
1101
1196
1266
1422
1480

486
555
586
689
751
800
875
1044
1094
1225
1281
1376
1499
1590
1763
1833

110
127
130
158
173
184
196
238
251
264
278
303
334
356
375
388

18.4
20.9
22.3
26.0
28.3
30.1
33.2
39.4
41.2
46.9
48.9
52.4
56.9
60.3
67.7
70.5

26
33
37
31
36
40
44
50
55
52
46
53
62
69
44
48

359
407
447
504
548
576
654
766
788
939
955
1020
1109
1172
1352
1405

473
539
582
668
728
768
858
1013
1047
1219
1243
1334
1455
1540
1743
1808

125
145
149
180
197
211
224
271
284
308
317
345
380
405
429
444

17.1
19.4
21.3
24.0
26.1
27.4
31.1
36.5
37.5
44.7
45.5
48.6
52.8
55.8
64.4
66.9

22
29
34
27
31
34
40
44
46
47
40
45
53
59
40
43

86
97
123
136
146
174
192
217
243
267
291

22.7
25.8
32.8
35.1
38.2
46.4
51.8
58.7
65.6
72.7
78.3

24
30
28
32
37
42
51
33
41
49
57

456
516
661
705
767
926
1040
1171
1323
1458
1566

546
618
789
849
920
1107
1242
1399
1578
1743
1876

99
112
141
158
168
200
221
250
280
313
341

21.7
24.6
31.5
33.6
36.5
44.1
49.5
55.8
63.0
69.4
74.6

22
28
26
30
34
38
47
30
38
45
52

435
492
630
674
731
882
995
1124
1266
1395
1478

537
610
778
839
907
1090
1225
1385
1559
1724
1838

113
129
163
182
193
229
254
287
322
362
396

20.7
23.4
30.0
32.1
34.8
42.0
47.4
53.5
60.3
66.4
70.4

20
26
24
27
32
34
43
27
35
41
46

415
470
598
642
694
843
950
1073
1209
1329
1401

533
604
769
832
894
1080
1214
1373
1546
1706
1816

129
148
188
209
221
261
290
330
370
415
456

19.8
22.4
28.5
30.6
33.0
40.1
45.2
51.1
57.6
63.3
66.7

19
23
22
25
29
31
40
25
32
38
42

40
Unit Cool Cool Qc
kW l/s
kPa kW

Qh
kW

45
Unit Cool Cool Qc
kW l/s
kPa kW

Qh
kW

50
Unit Cool Cool Qc
kW l/s
kPa kW

Qh
kW

Unit Cool Cool


kW l/s
kPa

85
98
98
120
131
144
148
184
193
200
211
232
255
274
279
290

22.7
25.6
25.8
32.5
35.1
37.9
40.2
48.8
50.9
55.1
60.3
64.3
69.7
74.4
79.3
82.9

38
48
49
46
52
60
61
73
79
68
68
77
90
101
60
65

444
499
519
635
684
737
797
960
1007
1096
1189
1269
1377
1465
1589
1660

532
602
623
760
822
885
951
1152
1209
1306
1409
1510
1643
1749
1885
1967

97
112
114
138
152
163
169
210
222
230
242
265
292
313
325
337

21.2
23.8
24.8
30.3
32.6
35.1
38.0
45.8
48.0
52.3
56.7
60.5
65.7
69.8
75.8
79.2

33
42
45
40
46
53
55
65
71
62
60
68
80
90
54
59

416
472
498
587
639
680
741
890
928
1050
1109
1187
1289
1366
1519
1581

517
588
617
732
797
848
917
1108
1157
1291
1362
1462
1592
1691
1860
1935

110
128
130
159
173
185
193
239
251
264
278
302
333
357
374
389

19.8
22.5
23.8
28.0
30.5
32.4
35.3
42.4
44.3
50.1
52.9
56.6
61.4
65.1
72.4
75.4

29
37
41
35
41
45
49
57
61
57
53
60
70
79
50
54

387
439
476
544
592
498
621
826
843
1001
1031
1102
1197
1265
1444
1501

501
571
612
708
771
641
814
1074
1102
1282
1319
1415
1543
1634
1834
1905

125
145
149
181
198
157
212
272
284
308
316
344
380
405
429
444

18.5
20.9
22.7
25.9
28.2
23.8
29.6
39.4
40.2
47.7
49.2
52.5
57.1
60.3
68.8
71.5

26
33
38
30
35
26
39
50
51
53
46
52
61
68
45
48

86
97
122
134
145
174
191
216
242
266
290

24.4
27.7
35.3
37.6
41.2
49.9
55.5
62.9
70.3
77.8
84.1

27
34
32
36
42
47
58
37
47
55
64

488
551
706
752
820
991
1111
1252
1414
1556
1674

577
653
835
895
972
1172
1312
1478
1668
1840
1984

98
112
141
157
168
199
220
249
279
312
341

23.3
26.3
33.7
35.9
39.1
47.2
53.0
59.7
67.4
74.2
79.8

25
31
29
33
38
42
53
34
43
50
58

464
526
674
718
780
943
1062
1201
1352
1489
1580

567
643
821
884
956
1150
1292
1461
1644
1817
1940

113
129
163
182
193
228
253
286
321
361
396

22.1
25.1
32.1
34.2
37.2
44.9
50.6
57.2
64.5
71.0
75.3

23
28
27
30
35
39
49
31
39
46
52

443
502
641
685
741
900
1014
1147
1291
1419
1499

560
636
811
875
943
1137
1277
1446
1627
1795
1914

129
147
187
209
221
260
289
328
369
414
456

21.1
23.9
30.6
32.6
35.4
42.9
48.3
54.7
61.6
67.6
71.4

21
26
25
28
32
35
44
28
36
42
47

Evaporator leaving water temperature = 7C

Condenser leaving water temperature, C


30XW 30
35
Qc
Qh
Unit Cool Cool Qc
Qh
kW kW
kW l/s
kPa kW kW
Standard-efficiency units 30XW--/30XWH452 495 564
75
23.6 41
476 554
552 549 628
86
26.2 50
536 625
602 559 636
86
26.6 51
541 631
652 705 803
107 33.6 48
681 790
702 767 872
116 36.5 56
735 854
802 813 928
127 38.7 63
796 927
852 849 965
127 40.5 62
844 979
1002 1069 1217 163 51.0 79
1024 1192
1052 1122 1277 171 53.5 86
1068 1244
1152 1166 1324 173 55.6 69
1156 1338
1252 1327 1498 187 63.3 74
1265 1457
1352 1426 1610 203 68.0 85
1349 1560
1452 1547 1750 223 73.8 100 1463 1695
1552 1649 1867 239 78.6 113 1560 1808
1652 1719 1940 243 81.9 64
1664 1918
1702 1795 2026 253 85.6 70
1739 2003
High-efficiency units 30XW-P/30XWHP
512 521 588
74
24.8 28
512 590
562 592 669
84
28.2 35
581 669
712 760 856
106 36.2 33
740 851
812 811 918
118 38.7 38
789 912
862 882 997
126 42.0 44
865 997
1012 1021 1158 150 48.7 45
1047 1205
1162 1201 1352 166 57.3 61
1165 1339
1312 1349 1518 186 64.3 39
1320 1516
1462 1511 1701 209 72.0 49
1474 1694
1612 1682 1895 234 80.2 58
1632 1874
1762 1800 2031 255 85.8 66
1764 2028

Legend:
Qc kW Cooling capacity
Qh kW Heating capacity
Unit kW Unit power input (compressors, control)
Cool l/s Evaporator water flow rate
Cool kPa Evaporator pressure drop
Application data:
Standard units, refrigerant R-134a
Evaporator water temperature rise: 5 K
Evaporator fluid: chilled water
Fouling factor: 0.18 x 10-4 (m2 K)/W
Performances in accordance with EN 14511

15

Cooling and heating capacities, standard units

Evaporator leaving water temperature = 10C

Condenser leaving water temperature. C


30XW 30
35
Qc
Qh Unit Cool Cool Qc
Qh Unit
kW kW kW l/s
kPa kW kW kW
Standard-efficiency units 30XW--/30XWH452 533 602 76
25.5 46
521 600 86
552 580 659 87
27.7 55
578 668 99
602 604 681 85
28.8 59
595 684 98
652 763 861 108 36.4 55
745 855 121
702 816 921 116 38.9 62
797 918 133
802 848 964 127 40.5 67
849 982 146
852 872 988 127 41.6 64
864 998 148
1002 1186 1335 164 56.7 93
1134 1302 185
1052 1242 1398 171 59.3 101 1185 1361 194
1152 1239 1393 169 59.2 76
1236 1416 198
1252 1478 1648 187 70.6 90
1401 1595 213
1352 1586 1770 203 75.7 103 1502 1712 232
1452 1723 1925 223 82.3 121 1631 1863 255
1552 1836 2054 240 87.7 137 1737 1986 274
1652 1856 2076 242 88.6 73
1824 2079 280
1702 1941 2171 253 92.7 80
1905 2170 292
High-efficiency units 30XW-P/30XWHP
512 573 640 74
27.3 33
559 636 85
562 651 727 84
31.1 41
634 722 97
712 837 933 106 39.9 39
809 920 122
812 888 995 117 42.4 44
864 987 135
862 966 1081 127 46.1 51
945 1077 145
1012 1061 1197 150 50.6 48
1112 1269 172
1162 1311 1461 164 62.6 72
1281 1454 190
1312 1442 1610 185 68.9 44
1445 1638 213
1462 1622 1810 207 77.4 56
1617 1834 239
1612 1845 2057 233 88.1 69
1786 2030 269
1762 1952 2184 255 93.2 76
1925 2192 294

40
Cool Cool Qc
l/s
kPa kW

Qh
kW

45
Unit Cool Cool Qc
kW l/s
kPa kW

Qh
kW

50
Unit Cool Cool Qc
kW l/s
kPa kW

Qh
kW

Unit Cool Cool


kW l/s
kPa

24.9
27.6
28.4
35.6
38.1
40.5
41.3
54.1
56.6
59.0
66.9
71.7
77.9
82.9
87.1
91.0

44
54
57
53
60
67
63
86
93
75
81
93
109
123
71
77

494
539
570
705
760
804
838
1061
1114
1206
1321
1414
1536
1634
1750
1825

583
641
673
832
899
955
990
1254
1316
1415
1543
1656
1801
1919
2045
2132

98
113
113
139
153
165
168
212
223
230
244
265
292
313
324
338

23.6
25.7
27.2
33.7
36.3
38.4
40.0
50.7
53.2
57.6
63.1
67.5
73.3
78.0
83.5
87.1

40
47
53
48
55
61
59
76
83
72
73
83
97
109
65
71

464
519
547
654
711
752
812
989
1019
1154
1238
1325
1438
1528
1672
1742

565
636
665
799
870
923
989
1208
1248
1395
1491
1600
1741
1853
2013
2096

111
128
130
159
174
188
193
240
252
264
278
302
334
357
374
389

22.2
24.8
26.1
31.2
34.0
35.9
38.8
47.2
48.7
55.1
59.1
63.3
68.6
73.0
79.9
83.2

36
44
49
42
48
54
56
67
71
67
64
73
85
96
59
64

433
484
522
607
660
693
783
923
931
1100
1154
1232
1337
1416
1590
1653

547
616
658
772
841
888
988
1171
1190
1381
1441
1545
1683
1786
1981
2059

125
146
149
181
198
214
225
272
285
309
316
344
380
406
429
446

20.7
23.1
25.0
29.0
31.5
33.1
37.4
44.1
44.5
52.5
55.1
58.8
63.8
67.6
75.9
78.9

31
39
45
36
42
46
53
60
60
61
56
64
74
83
54
58

26.7
30.3
38.6
41.3
45.1
53.1
61.2
69.0
77.2
85.3
91.9

31
39
37
42
49
52
68
44
55
64
74

534
605
775
824
899
1090
1225
1382
1556
1712
1842

623
706
903
968
1052
1270
1424
1606
1807
1995
2152

98
112
141
158
168
198
218
246
276
311
342

25.5
28.9
37.0
39.4
42.9
52.0
58.5
66.0
74.3
81.8
87.9

29
36
34
38
45
50
63
40
51
60
68

511
579
742
789
860
1038
1171
1325
1491
1637
1742

613
695
889
955
1036
1245
1399
1583
1780
1964
2102

112
128
162
182
193
227
251
283
318
359
396

24.4
27.6
35.4
37.7
41.1
49.6
55.9
63.3
71.2
78.2
83.2

27
33
32
35
41
46
58
37
47
55
62

488
557
707
752
817
992
1117
1265
1423
1560
1653

605
691
877
943
1019
1228
1379
1561
1757
1936
2069

128
147
186
209
221
259
288
325
367
413
457

23.3
26.6
33.8
35.9
39.0
47.4
53.3
60.4
68.0
74.5
78.9

24
31
29
32
38
42
53
34
43
50
56

Legend:
Qc kW Cooling capacity
Qh kW Heating capacity
Unit kW Unit power input (compressors, control)
Cool l/s Evaporator water flow rate
Cool kPa Evaporator pressure drop
Application data:
Standard units, refrigerant R-134a
Evaporator water temperature rise: 5 K
Evaporator fluid: chilled water
Fouling factor: 0.18 x 10-4 (m2 K)/W
Performances in accordance with EN 14511

Carrier is participating in the Eurovent Certification Programme for liquid chilling


packages. Certified data of certified models are as listed in the Eurovent Directory
of Certified Products or on the Internet site www.eurovent-certification.com.
This programme covers air-cooled chillers up to 600 kW and water-cooled
chillers up to 1500 kW.

Order No.13457-20, 10.2009. Supersedes order No. 13457-20, 01.2009


Manufacturer reserves the right to change any product specifications without notice.
The cover photo is solely for illustration purposes and not contractually binding.

Manufactured by: Carrier SCS, Montluel, France.