Control Valve Respect


When was the last time you heard someone say they were going to ?calibrate? a control valve?

Home
About Us

To most people the term ?field instrumentation calibration? applies to analyzers, switches, and
transmitters. The reality is, field instrumentation also includes final control devices, such as variablefrequency drives and control valves.

Maintenance solution
eMaintenance
eLearning
Services
eMRO
Site Specific
Links to other Sites
Reports
Suggestions/Feedback

It?s unfortunate when final control devices are ignored because the cause of process variability
frequently has little or nothing to do with controller tuning, operator actions, or raw material influences,
and everything to do with how well these devices perform.
Getting respect
Recently revised standards are designed to establish control valve evaluation and acceptance testing
criteria, available from the Instrumentation, Systems, and Automation Society (ISA, Research Triangle
Park, N.C.). The standards do not define acceptable control valve performance nor do they restrict
selecting a control valve for any application.
The standards do provide detailed instructions that establish a uniform means of testing and analyzing
control valve cradle-to-grave performance. For example, ANSI/ISA-75.25.01-2000, ?Test Procedure for
Control Valve Response Measurement from Step Inputs,? defines how to test, measure, and report
control valve response characteristics for three test types-bench, laboratory, and in-process.
z

Bench tests are conducted with the control valve out of the line or out of service. Because there is
no flow through the valve body, results can be significantly different than results produced by
laboratory and/or in-process tests for the same valve. Despite the simplicity of bench testing,
useful information can be obtained.

Laboratory tests are performed with media flowing through the valve but under highly controlled
conditions (i.e., flow is fully turbulent and not choked). Because of the controlled testing
environment, control valve laboratory performance results may not be achievable under actual inprocess conditions.

In-process tests provide valve response results in actual, or close-to-actual conditions. The
limiting factor to obtaining meaningful in-process test results is usually the availability of suitable
measurement devices and/or process factors that may limit the range of tests that can be
conducted.

Test procedures
Regardless of the test type used, ANSI/ISA 75.25.01 defines three procedures designed to obtain the
maximum quality and quantity of valve performance information-baseline, small step, and response time.
Baseline testing is considered optional, but when used it evaluates measurement noise, presence of
valve limit cycling, and establishes baseline response time. Baseline testing is very useful in establishing
a control valve?s initial installation performance ?signature.?
Small-step testing is performed to determine a valve?s deadband and resolution. Testing begins after
setting the input signal to a nominal value and waiting a specified time. The test continues with a series
of small up and down step changes with defined wait periods between each step change.
Response time step testing provides a comparison of response time to step size as well as approximate
values for dead band and resolution. Despite their rugged appearance, control valves are every bit as
much a precision instrument as an analyzer or transmitter. Show them a little respect and