Users Manual
ACONIS-2000 PMS
Users Manual
1 / 25
Users Manual
Abbreviations
PMS
GCE
GDP
BT
Bus Tie
GE
Generator Engine
2 / 25
Users Manual
Revision History:
2004. 05. 20:
3 / 25
Users Manual
CONTENTS
1.
2.
1.2
1.3
1.4
1.5
2.2
2.3
2.4
3.
2.2.1
2.2.2
2.2.3
2.2.4
Synchronizing ......................................................................................................................15
2.2.5
2.2.6
2.2.7
2.3.2
2.3.3
2.3.4
Power...................................................................................................................................19
3.1.2
Frequency............................................................................................................................19
3.1.3
Voltage.................................................................................................................................19
3.1.4
Ampere ................................................................................................................................19
3.2
3.3
3.4
3.5
3.6
3.7
3.8
3.9
4 / 25
Users Manual
1. General Description
This manual describes PMS applications with 3 diesel generator sets. (Max 5sets)
PMS for each generator is installed inside main switchboard.
The PMS is advanced system for full automation of the power plant: including generator
control, power management, generator protection and engine safety system.
z
Each diesel generator is equipped with a local control panel with local / remote switch.
In local mode, the diesel generator is controlled at local.
In remote mode, the diesel generator is controlled by the switchboard.
z
Manual or Auto control mode is only selected by each select switch installed on the
GDP in each generator panel.
In manual mode, PMS is not controlled by push buttons.
In auto mode, the diesel generator is controlled by the PMS program and the push
buttons on the GDP can be used as well.
Each generator set is equipped with its own independent and autonomous PMS, which is
built-up in a module way. This ensures the highest degree of reliability and availability.
The PMS is built-up with two modules for each generator set:
z
5 / 25
Users Manual
PMS
Auto mode
Manual
mode
Local
mode
Load sharing
Frequency control
Description
6 / 25
Users Manual
Manual
Auto
Item
Alarm
Trip
Stand-by
Alarm
Alarm
Trip
Stand-by
Alarm
Start Fail
O(ACB)
O(ACB)
Short Circuit
O(ACB)
O(ACB)
Heavy Load
BUS abnormal recovery process is controlled in AUTO mode, even the running
generator is set as MANUAL mode.
7 / 25
Users Manual
Among upside conditions it is designed for operating the ACB close first for the idle
running GE when idle running GE and 1st standby selected GE exist at the same
time.
8 / 25
Users Manual
Operator Panel includes 8 push buttons and two 4 digit numeric display that indicates
Power, Current, (upper side 4 digit) Voltage and Frequency (lower side 4 digit).
In addition, 22 LED indicator status and alarm condition conditions and 4LED (S. Fail / P.
Fail / H.LOAD / L.LOAD) indicate Operator Panel status. Including connection serial cable
(L=2m) to GCE.
9 / 25
Users Manual
10 / 25
Users Manual
11 / 25
Users Manual
Parameter
Description
24VDC
Burden
kW (ex. 800kW)
Control Processor
Clock speed
200 MHz
512Kb
32MB
32MB
4Kb
Yes
Operating temperature
0 70 Deg. C
Environmental
Weight:
7Kg (GDP:
Protection degree
,GCE:
Digital inputs
Field bus interface
Digital outputs
12 / 25
Users Manual
Parameter
Main Bus Voltage
Generator Voltage
Generator Current
I/O Type
AC Input / 3 phase
R,S,T
AC Input / 3 phase
R,S,T
AC Input / 3 phase
R,S,T
Engine Start
Digital output
Engine Stop
Digital output
Digital input
Digital input
Digital input
Digital input
1st Standby
Digital input
Speed increase
Digital Output
Speed decrease
Digital Output
ACB Open
Digital Output
ACB Close
Digital Output
ACB Status
Digital input
Preferential Trip
Output 1 / 2
Digital Output
Digital Input
Digital Output
Description
440VAC
440VAC
5A Maximum; via Current transformers
Normally Open contact.
Output activated when engine start required
Normally Open contact.
Output activated when engine stop required
Normally Open contact
When activated, Engine is ready to start.
Normally Open contact
When closed, the engine has shut down.
Normally Open contact.
When closed, Engine is in remote (MSB)
operation.
Normally Open contact
When closed the ACB has tripped due to
overload or short circuit
Normally Open contact
Digital input from Standby Selection switch;
when closed the generator is selected 1st
Standby.
Normally Open contact.
Output activated when increase of engine
speed required
Normally Open contact.
Output activated when decrease of engine
speed required
Normally Open contact.
Output activated when open circuit breaker
required
Normally Open contact.
Output activated when close circuit breaker
required
Normally Open contact.
When closed the ACB is closed when open
than the ACB is open.
Normally Open contact.
Output activated when Non Preferential
consumer 1 / 2 should be switched off.
Normally Open contact.
When closed the BT is closed and when open
the Bus Tie is open.
Normally Closed contact.
Output activated when open PMS alarm
required.
Remarks
Digital input / output can be changed according to project.
13 / 25
Users Manual
2. PMS Functions
Each generator is equipped with its own and autonomous PMS generator control and
power management system.
PMS system executes automatic control functions and can be operated from the GDP.
The following section assumes that the diesel generators are set to remote (MSB) mode.
PMS can be operated in automatic mode and manual mode. The automatic or manual
mode can be selected from the MSB.
When PMS in manual mode, the Manual indicating LED on GDP will be illuminated.
When PMS in Auto mode, the Auto indicating LED on GDP will be illuminated.
When pressing the Start push button, the following functions are executed:
Synchronization and close ACB to main Bus Bar.
During the start sequence the START push button will be illuminated ENGINE
STARTING LED on the GDP. And RUN LED is flashing
When the diesel engine is running, ENGINE STARTING LED is off and RUN LED
is on (steady).
The status of the ACB is displayed on the GDP by lighting the LED ACB CLOSED or
ACB OPEN
When synchronization is fail, this is indicated on the GDP by lighting the LED ACB
NON CLOSE / SYNC. FAIL
2.2.2
When pressing the STOP push button in Automatic mode, the following functions are
executed:
Check if the other running generators can take over the load; when this is not possible
(over 80%), the stop sequence will be aborted. The operator will notify this because the
ENGINE STOPPING LED will not be illuminated.
Power Management System
Shipyard : HMD
Hull No : H8005-10
Class : LRS
Rev. No : R3
14 / 25
Users Manual
When a preset value of load in percentage is reached and available for a preset time, a
start request is generated to the 1st standby generator. The 1st Standby generator can be
selected via a selection switch in the switchboard. When a generator is selected 1st
Standby or 2nd Standby this is indicated by lighting a LED on the GDP.
The preset values and times are listed in the parameter-list and changeable by means of
adapting the parameters via the set-up on the GDP.
2.2.4
Synchronizing
PMS checks that the voltage and frequency deviation between generator and net is
acceptable, and finally gives the breaker a close signal when phase is equal on generator
and net. If synchronizing is exceeds 60 second, a synchronizing fail alarm will be given.
The diesel engine will stop and, if there is an automatic start situation, another diesel will
be started.
2.2.5
Based on input data (net frequency, generator load), PMS controls the speed on the
auxiliary engines, which is proportionally generator frequency. By giving increase and
decrease pulses to the governor motor, PMS keeps a steady net frequency and will also,
when more than one generator are connected to the net, perform load between the
generators.
Parameters can be set for fine-tuning this function.
2.2.6
When a heavy consumer request is detected by the system, the system is checks if the
available power is sufficient for the consumer to start up. If the available power is
insufficient, a start request is issued to the 1st standby generator. As soon as this
generator is on line and load shared (within a pre-set percentage), the consumer start is
granted.
15 / 25
Users Manual
Black out is a situation defined as no voltage and no frequency is measured on the BUS
BAR section and all generator circuit breakers are open.
All outgoing breakers on the blackout BUS BAR section will be opened by the A PMS
system.
When Blackout is detected, the PMS will start to 1st standby generator and a close
breaker signal. When BUS abnormal than 1st Standby generator starts, and after running,
if bus status is still abnormal, working ACB trips and than 1st Standby ACB closed. After
standby generator is running, if bus abnormal is recovery, after standby generator is idle
running for 30sec, standby generator is stopping.
Within the above 30sec, bus abnormal is occurred again, working ACB trips and than
standby ACB closes.
16 / 25
2.3
Users Manual
Function of PMS
2.3.1
A reverse power trip takes place in case the measured reverse power has exceeded the
pre-configured limit for a certain time. The preset values and times are listed in the
parameter-list and changeable by means of adapting the parameters via the set-up on the
GDP.
The reverse power trip will be indicated on the GDP by lighting the LED REVERSE
POWER TRIP
2.3.2
An over current / short circuit trip takes place in case the measured current has exceeded
the pre-configured limit for a certain time. The preset values and times are listed in the
parameter-list and changeable by means of adapting the parameters via the set-up on the
GDP.
The over current trip will be indicated on the GDP by lighting the LED OVER
CURRENT /SHOPRT CIR.TRIP
2.3.3
An alarm takes place in case the measured values have exceeded the pre-configured limit
for a certain time. The preset values and times are listed in the parameter-list and
changeable by means of adapting the parameters via the set-up on the GDP.
The alarms will be indicated on the GDP by blinking the LED, BUSBAR VOLTAGE
LOW / BUSBAR VOLTAGE HIGH / BUSBAR FREQUENCY HIGH or
BUSBAR FREQUNECY LOW
2.3.4
Each PMS has two non-essential groups which can be tripped in case of:
Group 1: generator load at certain load for certain time (e.g. 100% for 5 seconds).
Group 2: generator load at certain load for certain time (e.g. 100% for 10 seconds).
The preferential tripping will be indicated on the GDP by lighting the LED Preferential
Trip 1 and 2
The load and time can be set via parameters.
Restoration of the tripped consumers is not controlled by the PMS system.
17 / 25
2.4
Users Manual
18 / 25
Users Manual
Power
Frequency
Voltage
Ampere
z ALARM
19 / 25
3.3
Users Manual
3.4
20 / 25
3.5
Users Manual
21 / 25
3.6
Users Manual
22 / 25
3.7
Users Manual
23 / 25
3.8
Users Manual
24 / 25
3.9
Users Manual
25 / 25
Parameter List
ACONIS-2000 PMS
Parameter List
ACONIS2000 PMS
Shipyard : HMD
Hull No : H8005-10
Class : LRS
Rev. No : R2_1
1/9
Parameter List
Category
P. No
Description
Unit
DG1
DG2
DG3
P001
450
450
450
P002
Hz
60
60
60
P003
kW
750
750
750
P004
1323
1323
1323
P005
sec
15
15
15
P006
Num
P007
sec
60
60
60
P008
CB Open at Load
10
10
10
P009
sec
180
180
180
P010
sec
10
10
10
P011
Synchronize Time
sec
60
60
60
P012
Delta Frequency
Hz
0.2
0.2
0.2
P013
Delta Voltage
22.5
22.5
22.5
P014
CB Make Time
msec
100
100
100
P015
msec
600
600
600
P016
Hz
0.2
0.2
0.2
P017
Hz
P018
kW
25
25
25
P019
50
50
50
P020
Cycle Time
sec
P021
sec
0.5
0.5
0.5
P022
sec
1.5
1.5
1.5
P023
90
90
90
P024
sec
15
15
15
P025
190
190
190
P026
sec
-1
-1
-1
Remarks
Generator
setting
Start Control
setting
Stop Control
setting
Synchronize
Control setting
Auto Governor
Control setting
Heavy Load
demand Auto
Starting
ACONIS2000 PMS
Shipyard : HMD
Hull No : H8005-10
Class : LRS
Rev. No : R2_1
Fixed 1 Item
60~600 sec
5%
Not used
2/9
Category
Heavy Load
demand Auto
Starting
Light Load
demand Auto
Stopping
Load Demand
Preferential Trip
Group
P. No
Description
Parameter List
Unit
DG1
DG2
DG3
P027
95
95
95
P028
sec
10
10
10
P029
195
195
195
P030
sec
-1
-1
-1
P031
100
100
100
P032
sec
P033
200
200
200
P034
sec
-1
-1
-1
P035
70
70
70
P036
sec
180
180
180
P037
100
100
100
P038
sec
P039
100
100
100
P040
sec
10
10
10
P041
Hz
58.5
58.5
58.5
P042
sec
P043
100
100
100
P044
sec
10
10
10
P045
100
100
100
P046
sec
15
15
15
P047
Hz
58.5
58.5
58.5
P048
sec
P049
427.5
427.5
427.5
P050
sec
P051
472.5
472.5
472.5
P052
sec
Remarks
Not used
Not used
60 ~ 600sec
95%
Bus Abnormal
ACONIS2000 PMS
Shipyard : HMD
Hull No : H8005-10
Class : LRS
Rev. No : R2_1
105%
3/9
Category
P. No
Description
Parameter List
Unit
DG1
DG2
DG3
Remarks
95%
P053
Hz
57
57
57
P054
sec
P055
Hz
63
63
63
P056
sec
P057
315
315
315
P058
sec
P059
585
585
585
P060
sec
P061
Hz
54
54
54
P062
sec
10
10
10
P063
Hz
66
66
66
P064
sec
P065
150
150
150
P066
sec
30
30
30
P067
-10
-10
-10
P068
sec
P069
P070
330
99
90
P071
P072
P073
P074
99
99
150
P075
P076
P077
P078
90
50
50
P079
P080
Bus Abnormal
DG Protection
Setting
(ACB Trip)
Aux #1. DO
Control setting
Aux #2. DO
Control setting
Aux #3. DO
Control setting
ACONIS2000 PMS
Shipyard : HMD
Hull No : H8005-10
Class : LRS
Rev. No : R2_1
105%
70%
130%
90%
110%
see AXO
Table
see AXO
Table
see AXO
Table
4/9
Category
P. No
Aux #1. DI
P081
Aux #2. DI
Aux #3. DI
Description
Parameter List
Unit
DG1
DG2
DG3
P082
P083
Remarks
See AXI
Table
Hardware
setting
Internal Control
setting
Heavy
Consumer
Block Setup
Synchronize
Setup
System
Configuration
P. No
Description
Unit
DG1
DG2
DG3
P084
30
30
30
P085
sec
P086
85
85
85
P090
400
400
400
P091
70
70
70
P092
10
10
10
P093
10
10
10
P094
sec
P095
Deg
P096
Deg
P100
Number of GCE
Num
P101
Num
Remarks
Fixed items
Meter
Calibration
Factor
Extern System
Communication
Setup
ACONIS2000 PMS
Shipyard : HMD
Hull No : H8005-10
Class : LRS
Rev. No : R2_1
P102
Num
1000
1000
1000
P103
Num
1000
1000
1000
P104
Num
1000
1000
1000
P105
Num
1000
1000
1000
P108
Num
P109
XIC Reserved
Num
10
10
10
(x 1000)
Time Value
x 100ms
5/9
Parameter List
Category
P. No
Custom
Function
Parameters
P111
P112
Description
Unit
DG1
DG2
DG3
0/1
0/1
Unit
DG1
DG2
DG3
Remarks
Reserved Parameters
Category
System
Reserved
Parameters
ACONIS2000 PMS
Shipyard : HMD
Hull No : H8005-10
Class : LRS
Rev. No : R2_1
P. No
Description
P120
Num
715
715
715
P121
Num
2300
2300
2300
P122
Num
P123
Num
8005
8005
8005
Remarks
Hull No
6/9
Parameter List
AXO Table
Description
Function Code
Aux. DO
Function
Disable
Heavy
Consumer
Block
PMS Status
Output
Code = 00
Code = 01
Code = 02
Parameter Value
Parameter #1
Not Use
Parameter #2
Not Use
Parameter #3
Not Use
Parameter #1
Parameter #2
Parameter #3
Not Use
Parameter #1
Parameter #2
Parameter #3
Remark
15 : Stop Failure
01 : CB Open
02 : GE Run
17 : GE Shut Down
03 : CB Closed
04 : Alarm
05 : Manual
06 : Automatic
21 : Preferential Trip 1
22 : Preferential Trip 2
st
nd
09 : 2 Stand by
10 : GE Starting
11 : GE Stopping
12 : Synchronizing
13 : Stand by GE Start
14 : Start Failure
08 : 1 Stand by
ACB Trip
INFO
Code = 03
Parameter #1
Unused
Parameter #2
Parameter #3
ACB ABNORMAL / ENGINE SHUT DOWN / OCR / SHORT CIRCUIT / REVERSE POWER TRIP
ACONIS2000 PMS
Shipyard : HMD
Hull No : H8005-10
Class : LRS
Rev. No : R2_1
7/9
Description
Total Available
Power [%]
Condition
Total Available
Power [kw]
Condition
Total Used
Power [%]
Condition
Total Used
Power [kw]
Condition
Single DG
Available
Power [%]
Condition
Single DG
Available
Power [kw]
Condition
Single DG
Used Power
[%] Condition
Single DG
Used Power
[kw] Condition
ACONIS2000 PMS
Shipyard : HMD
Hull No : H8005-10
Class : LRS
Rev. No : R2_1
Function Code
Code = 21
Code = 22
Code = 23
Code = 24
Code = 25
Code = 26
Code = 27
Code = 28
Parameter List
Parameter Value
Parameter #1
Parameter #2
0 = <, 1 = >
Parameter #3
Parameter #1
Parameter #2
0 = <, 1 = >
Parameter #3
Parameter #1
Parameter #2
0 = <, 1 = >
Parameter #3
Parameter #1
Parameter #2
0 = <, 1 = >
Parameter #3
Parameter #1
Parameter #2
0 = <, 1 = >
Parameter #3
Parameter #1
Parameter #2
0 = <, 1 = >
Parameter #3
Off Delay
Parameter #1
Parameter #2
0 = <, 1 = >
Parameter #3
Parameter #1
Parameter #2
0 = <, 1 = >
Parameter #3
Remark
8/9
Description
Multiple 1&2
DG Used
Power [%]
Condition
Multiple 1&2
DG Used
Power [kw]
Condition
Function Code
Code = 29
Code = 30
Parameter List
Parameter Value
Remark
Parameter #1
Parameter #2
0 = <, 1 = >
Parameter #3
Parameter #1
Parameter #2
0 = <, 1 = >
Parameter #3
AXI Table
Function Code
Description
Code = 00
Code = 01
Code = 02
Code = 03
ACONIS2000 PMS
Shipyard : HMD
Hull No : H8005-10
Class : LRS
Rev. No : R2_1
Parameter Value
Remark
Option
9/9
Flow Chart
ACONIS-2000 PMS
Flow Chart
1 / 19
Flow Chart
Flow Chart
1.1 Flow Chart Symbol
FLOWCHART SYMBOLS
DESCRIPTION
SYMBOL
PROCESS
USED TO INDICATE ANY FORM OF INTERNAL PROCESSING MANIPULATION OTHER THAN DECISIONS.
AN IDENTIFYING LEGEND APPEARS IN THE BOX.
PREDEFINED PROCESS
CAUSE
USED TO INDICATE THE PREDEFINED COMMAND GROUP SUCH LIKE SUB-ROUTINE IN ANOTHER
PROGRAM OR ORDERED PROCESS STEPS CONSIST OF SOME OPERATIONS.
USE TO INDICATE INITIATING CONDITIONS. AN IDENTIFYING LEGEND AND A SET VALUE OF
VALUES APPEAR IN THE LEFTHAND AND RIGHTHAND COLUMNS OF THE BOX. RESEECTIVELY.
DECISION
PREPARATION
MANUAL OPERATION
TERMINAL
MANUAL INPUT
ANNOTATION
USED FOR ADDITION OF DESCRIPTIVE COMMENTS OF EXPLANATORY NOTES.
ANDOPERATION
INPUT
OUTPUT
OR OPERATION
INPUT
OUTPUT
USED TO INDICATE AND OPERATIONS; THE OUTPUT IS PRESENT IF ALL INPUTS ARE
PRESENT, OTHERWISE THERE IS NO OUTPUT.
USED TO INDICATE OR OPERATIONS; THE OUTPUT IS PRESENT IF ONE OR MORE INPUTS ARE
PRESENT.
FLOW LINE
USED TO CONNECT EACH BOX AND SYMBOL IN A FLOWCHART.
CONNECTOR
*
ALARM
INDICATOR LAMP
(*)
2 / 19
Flow Chart
COS-P
(M/S)
(M/S)
MODE SELECT
AUTO
STANDBY
READY TO
START
READY
CONT. POSI
REMOTE
LOCAL
START POSS
DISPLAY
RL
YL
YL
REMOTE CONT
AVAILABLE
COS-P
(MSB)
OFF
STANDBY
SELECT
COS-A
(MSB)
AUTO STANDBY
SELECT
(LOWEST NO.)
SET
AUTO START
AVAILABLE
ENG START
COND. NOR
CONT. POSI
LOCAL
COS-L
(M/S)
(M/S)
LOCAL CONT
AVAILABLE
3 / 19
Flow Chart
1.3 Manual start and ACB closure onto the Dead BUS
REF TO PAGE: 3
REF TO PAGE: 3
LOCAL CONT
AVAILABLE
REMOTE CONT
AVAILABLE
STARTING
RUN
ENG
STOPPED
READY
DISPLAY
YL
GL
YL
STANDBY SELECT
OFF
COS-A
(MSB)
ENG CONTROL
START
ECS(M/S)
ENG CONTROL
START
ECS(MSB)
ENG START
COMMAND
(MSB)
OVERDUE
15sec
(Para:005)
ENG
STARTED
(M/S)
VOLTAGE
ESTABLISHED
(PMS)
TO BE CHECKED
VGENVRAT
BY VM
(MSB)
ACB CONTROL
CLOSE
BCS(MSB)
ACB CLOSE
COMMAND
(MSB)
ACB CLOSED
(MSB)
POWER
SUPPLY
4 / 19
Flow Chart
REF TO PAGE: 3
LOCAL CONT
AVAILABLE
REMOTE CONT
AVALILABLE
ENG CONTROL
START
ECS(M/S)
ENG CONTROL
START
ECS(MSB)
RUN
REF TO PAGE: 3
STARTING
ENG
STOPPED
READY
DISPLAY
YL
GL
YL
ENG START
COMMAND
(MSB)
ENG
STARTED
(M/S)
GOV CONTROL
RAISE/LOWER
GCS(MSB)
MANU
MODE SELECT
COS-P
(MSB)
SYNCHRO
SET
SYS
(MSB)
VOLTAGE
ESTABLISHED
(PMS)
TO BE
CHECKED
VGENVRAT
BY VM
(MSB)
AUTO
AUTO LOAD
SHARING COMMAND
(PMS)
AUTO LOAD
SHARING
(PMS)
POWER
SUPPLY
F
OVERDUE
15sec
(Para:005)
GOV CONTROL
RAISE/LOWER
GCS(MSB)
SYNCHRONIZED
ACB CONTROL
CLOSE
BCS(MSB)
(MSB)
ACB CLOSE
COMMAND
(MSB)
ACB CLOSED
(MSB)
5 / 19
Flow Chart
RUN
STOPPING
POWER
SUPPLY
READY
DISPLAY
YL
YL
YL
GOV CONTROL
RAISE/LOWER
GCS(MSB)
LOAD SHIFT
(MSB)
ACB CONTROL
OPEN
BCS(MSB)
LOAD SHIFT
FINISH
(MSB)
TO BE CHECKED
BY KwM (MSB)
ABOUT 10% (Para:008)
ACB OPEN
COMMAND
(MSB)
ENG CONTROL
STOP
ECS(MSB)
ENG CONTROL
STOP
ECS(MSB)
ACB OPENED
REMAININAG GEN
POWER SUPPLY
ENG STOP
COMMAND
(MSB)
ENG STOPPED
6 / 19
Flow Chart
1.6 Automatic start and ACB closure onto the Dead BUS (Black Out)
STARTING
RUN
STOPPING
START FAIL
NON CLOSE
SYCN FAIL
ALARM
ENG STOPPED
REF TO PAGE: 3
READY
DISPLAY
YL
GL
YL
YL
RL
RL
RL
REMOTE CONT
AVAILABLE
MODE
SELECT
AUTO
COS-P
(MSB)
YES
IDLING DG
EXIST
NO
ENG START
COMMAND
(PMS)
OVERDUE
15sec
(Para:005)
VOLT BUILD
UP 95%
NO
(Para:084,085)
YES
WAITING TIME FOR
STABLE VOLT
(3sec)
VOLTAGE
ESTABLISHED
(PMS)
YES
NO
START FAIL
ACB CLOSE
ACOMMAND
OVERDUE
3sec
(PMS)
ACB
CLOSED
NO
ACB NON CLOSE
YES
POWER SUPPLY
7 / 19
Flow Chart
STARTING
RUN
STOPPING
START FAIL
WL
YL
GL
YL
YL
RL
NON CLOSE
SYNC FAIL
ALARM
READY
VOLTAGE
ESTABLISHED
AUTO CONT
DISPLAY
RL
RL
REF TO PAGE: 3
REMOTE CONT
AVAILABLE
AUTO START
COMMAND
(PMS)
MODE
SELECT
AUTO
COS-P
(MSB)
ENG START
COMMAND
(PMS)
VOLT BUILD
UP 95%
OVERDUE
15sec
(Para:005)
NO
(Para:084,085)
YES
WAITING TIME FOR
STABLE VOLT
(3sec)
VOLTAGE
ESTABLISHED
(PMS)
YES
NO
START FAIL
AUTO SYNCHRO
COMMAND
(PMS)
OVERDUE
60sec (P:011)
ACB
CLOSED
NO
ACB NON CLOSE
& SYNC FAIL
YES
AUTO LOAD
SHARING COMMAND
(PMS)
AUTO LOAD
SHARING
(PMS)
POWER SUPPLY
8 / 19
Flow Chart
9 / 19
Flow Chart
10 / 19
Flow Chart
10sec
15sec
11 / 19
Flow Chart
1.11 Auto and Dead BUS due to Black Out (ACB Trip, Reverse Power, Over Current)
REF TO PAGE: 11
REF TO PAGE: 3
ACB TRIP
(BLACK OUT)
AUTO START
AVAILABLE
YES
STARTING
RUN
STOPPING
START FAIL
ALARM
POWER SUPPLY
STANDBY
READY
DISPLAY
YL
YL
GL
YL
YL
RL
RL
IDLING DG
EXIST
NO
ENG START
COMMAND
(PMS)
VOLT BUILD
NO
UP 95%
(Para:084,085)
OVERDUE
15sec
(Para:005)
YES
VOLTAGE
ESTAVLISHED
(PMS)
NO
START FAIL
YES
ACB CLOSE
COMMAND
OVERDUE
3sec
(PMS)
NO
ACB CLOSED
NO
ACB NON CLOSE
YES
NO
OTHER
STANDBY
POWER SUPPLY
YES
INTERRUPTION
NOTE:
STANDBY GENERATORS ACB CLOSED
WITH IN 30sec AFTER BLACK OUT
12 / 19
Flow Chart
1.12 Auto start and ACB closure onto the Dead BUS via Black Out (due to BUS Abnormal)
STOPPING
/ FAIL
ALARM
AUTO START
AVAILABLE
START FAIL
REF TO PAGE: 3
BUS
ABNORMAL
RUN
REF TO PAGE: 10
STARTING
POWER SUPPLY
STANDBY
READY
DISPLAY
YL
YL
GL
YL
RL
RL
RL
ENG START
COMMAND
F
(PMS)
VOLT BUILD
NO
UP 95%
(Para:084,085)
YES
OVERDUE
15sec
(Para:005)
NO
NORMAL
BUS CHECK
IDLE RUNNING
(>30sec)
ABNORMAL
OVERDUE
60sec (Para:009)
NO
START FAIL
(PMS)
(PMS)
STOPPED
NO
STOPPING FAIL
YES
ENG STOPPED
ACB OPENED
OVERDUE
1sec
NO
YES
STANDBY GEN ACB
CLOSE COMMAND
OVERDUE
3sec
OTHER
STADNBY
NO
NO
(PMS)
ACB CLOSED
NO
ACB NON CLOSE
YES
YES
INTERRUPTION
POWER SUPPLY
13 / 19
Flow Chart
1.13 Auto start and synchronization due to ACB trip (BUS Alive) or Preferential Trip
RUN
STOPPING
START FAIL
SYNC FAIL
ALARM
REF TO PAGE: 3
STARTING
POWER SUPPLY
STANDBY
READY
DISPLAY
YL
YL
GL
YL
YL
RL
RL
RL
AUTO START
AVAILABLE
REF TO PAGE: 11
REF TO PAGE: 11
ACB TRIP
(BUS ALIVE)
PREF TRIP
IDLING DG
EXIST
YES
NO
ENG START
COMMAND
F
(PMS)
VOLT BUILD
UP 95%
OVERDUE
15sec
(Para:005)
NO
(Para:084,085)
YES
WAITING TIME FOR
STABLE VOLT
(3sec)
NO
VOLTAGE
ESTABLISHED
(PMS)
NO
START FAIL
YES
AUTO SYNC
COMMAND
OVERDUE
60sec (Para:011)
(PMS)
NO
ACB CLOSED
NO
SYNCHRO FAIL
& NON CLOSE
YES
AUTO LOAD
SHARING COMMAND
NO
OTHER
STANDBY
(PMS)
INTERRUPTION
YES
(PMS)
AUTO LOAD
SHARING
(PMS)
POWER SUPPLY
14 / 19
Flow Chart
STARTING
RUN
STOPPING
START FAIL
SYNC FAIL
ALARM
POWER SUPPLY
REF TO PAGE: 3
STANDBY
READY
DISPLAY
YL
YL
GL
YL
YL
RL
RL
RL
AUTO START
AVAILABLE
HEAVY
LOAD
90%
15sec
(Para:023)
(Para:024)
(PMS)
ENG START
COMMAND
(PMS)
VOLT BUILD
UP 95%
OVERDUE
15sec
(Para:005)
NO
(Para:084,085)
YES
WAITING TIME FOR
STABLE VOLT
(3sec)
NO
VOLTAGE
ESTABLISHED
(PMS)
YES
NO
START FAIL
AUTO SYNC
COMMAND
OVERDUE
60sec (Para:011)
(PMS)
NO
ACB CLOSED
NO
SYNCHRO FAIL
& NON CLOSE
YES
AUTO LOAD
SHARING COMMAND
NO
OTHER
STANDBY
(PMS)
INTERRUPTION
YES
(PMS)
AUTO LOAD
SHARING
(PMS)
POWER SUPPLY
15 / 19
Flow Chart
READY
STOP FAIL
ALARM
POWER SUPPLY
STOPPING
DISPLAY
YL
YL
RL
RL
UNDER
REMAINING
GEN RATED
KW x 0.7
MODE
SELECT
AUTO
COS-P
(MSB)
BOW
NOT RUN
LIGHT
LOAD
70%
180sec
(Para:035)
(Para:036)
AUTO LOAD
SHIFT COMMAND
OVERDUE
60sec
(Para:007)
(PMS)
NO
REMAINING
GEN SUPPLY
POWER 70%
LOAD SHIFT
FINISH
(PMS)
YES
ACB OPEN
COMMAND
LOAD SHIFT
CANCEL
(RETURN TO
PARALLEL RUNNING)
(PMS)
5sec
ACB OPENED
NO
(PMS)
OVERDUE
180sec
(Para:009)
YES
IDLE RUNNNIG
ENG STOP
COMMAND
OVERDUE
10sec
(Para:010)
(PMS)
STOPPED
NO
YES
STOPPED
16 / 19
Flow Chart
17 / 19
Flow Chart
18 / 19
Flow Chart
ACONIS-PMS FAIL
POWER SUPPLY
CPU
IS FAULT ?
YES
NO
MAIN POWER
IS FAIL
YES
NO
S. FAIL LED
IS OFF
S. FAIL LED
IS ON
19 / 19