Ohms
Ohms
Ohms
Ohms
Ohms
Ohms
Ohm
Ohm
Ohm
Degree
Ohm
Ohm
Ohm
Degree
KM
Ohm
Ohm
Ohm
Ohm
Ohm
Ohm
Degree
MVA
2
400
KV
63.49
Ohm
31.75
Ohm
2000
1
400
Amp
Amp
Kilo Volt
CT & PT Details
CT Primary
CT Secondary
PT Primary
For 2x700MW Rajpura Thermal Power Plant
400kV Line Protection.
Rev:0
PT Secondary
110
CT/PT Ratio
0.55
GROUND FACTOR
Grounding Factor kg = (Z0/Z1)/(3*Z1)
Magnitude of grounding factor Kg =(SQRT((X0-XL)*(X0-XL))+((R00.811
RL)*(R0-RL)))/ (3*(SQRT(RL*RL)+(XL*XL)))
Angle of Grounding factor Kg = (arc Tan((X0-XL/(R0-RL)))-(arc
-12.292
Tan(XL/RL))*180*7/22
KZ1,KZ2,KZ3..PS1
0.811
Angle Kg
-12.292
ZONE SETTINGS
DIST Z1
80%
DIST Z2
(100 of Protected line +
25%
DIST Z3
(100 of Protected line +
100%
DIST Z4
10%
ZONE SETTING CALCULATIONS
VALUES
ZONE 1
80% of Protected line
(recommended)
18.872
VALUES
ZONE 2
100% of protected line + 50% of Adjacent line
28.087
27.955
100% of protected line + 25% of Transformer
On comparing the above values, the recommended value is the smallest of all values
VALUES
ZONE 3
100% of protected line + 100 % of longest line
32.584
100% of protected line + 50% of Transformer
32.320
On comparing the above values, the recommended value is the smallest of all values
ZONE 4
10% of Zone 1 Impedence
1.887
RESISTIVE REACH SETTING:
Primary full load current, CTR considered as Full load
2000
Y
L
N
O
E
C
EN
OR
R
E
EF
Volt
Degree
Degree
of protected line
of parallel ICT Impedance
of parallel ICT Impedance
of zone 1 impedence
Ohm
Ohm
Ohm
Ohm
Ohm
Ohm
Amp
76.982
Ohm
42.340
25.404
25.404
25.404
33.872
33.872
33.872
Ohm
Ohm
Ohm
Ohm
Ohm
Ohm
Ohm
0.00
0.30
0.75
1.00
Sec
Sec
SEC
SEC
20
5.081
20
5.081
% of R3
Ohm
% of R3
Ohm
The three unblocking current thresholds namely, IN>, I2> and Imax should be set above the maximum expected residual
current unbalance, the maximum negative sequence unbalance and the maximum expected power swing current.
IN> 40%
I2> 30 %
Value of Imax line = 3 Inom
NOTE: PSB Block Zone 2, Zone 3 & Zone 4
PSB Allowed to trip Zone 1
Unblocking timer:
To be set to 2s typically to un block in case of a prolonged power swing.
DISTANCE SCHEMES SETTING
Program Mode
Standard Scheme
Standard Mode
PUR Permissive under reach scheme
Disabled
Z1Ext Fail
Trip mode
1 pole Z1 , CR Received
SWITCH ON TO FAULT
Switch on to fault logic is pre-set in MiCOM P444
I>3 Current Set
3.00A
I>3 Time delay
3sec
I>4 Status
Disabled
Operation on pick up of level detector method and activation of all zones is recommended.This time delay is not having role
in SOTF/TOR logic. Since not possible to block time delay, keep a higher setting as 3 Sec.
Y
L
N
OR
N
E
R
E
F
E
O
E
C
Yes
3A
1.2 sec
IDMT
M/s. Alstom T&D India Limited,
19/1, GST Road,
Pallavaram,
Chennai - 600043.
IN>1 Directional
IN>1 VTS Block
IN>1 Current set
IN>1 Time Delay
IN>1 Time VTS
IN>2 status
BROKEN CONDUCTOR PROTECTION
I2/I1 ratio
Time Set
VT SUPERVISION
VTS Time Delay
VTS I2> & I0> Inhibit
Detect 3P
Threshold 3P U<
Delta I>
OVER VOLTAGE PROTECTION:
V>
V>1 Function
V>1 Voltage Set
V>1 Time Delay
V>2 Status
V>2 Voltage Set
V>2 Time Delay
UNDER VOLTAGE PROTECTION:
V< Mode
V< Operation
V<1 Function
V<1 Voltage Set (80% of Nominal Voltage)
V<1 Time Delay
V<1 Pole Dead Inh
V<2 Status
V<2 Voltage Set (70% of Nominal Voltage)
V<2 Time Delay
Stub Bus Protection (50STB)
Relay Type
CT Primary in Amps
CT Secondary in Amps
Settings:
Stub Bus
Pickup for Stub Bus in secondary
OR
Directional Forward
Non Directional
0.2 A
1.2 sec
1.2 sec
Disabled
0.20.
60 Sec.
5.000 s (alarm indication time )
50 mA
Enabled
10 Volts
100 mA
Y
L
N
O
E
C
N
E
R
E
F
E
Frequency Protection:
Relay type used
P141
Under Frequency Protection
F<1 Status
Enabled
F<1 Setting in Hz
48.5
F<1 Time delay in sec
2
F<2 Status
Enabled
F<2 Setting in Hz
48
F<2 Time delay in sec
0.5
Over Frequency Protection
F>1 Status
Enabled
F>1 Setting in Hz
51.0
F>1 Time delay in sec
1.5
F>2 Status
Enabled
F>2 Setting in Hz
50.5
F>2 Time delay in sec
0.5
DF/DT Protection
df/dt>1 Status
Enabled
df/dt>1 Setting in Hz
0.250
df/dt>1 Time in sec
0.200
df/dt>1 Dir'n
Both
df/dt>2 Status
Enabled
df/dt>2 Setting in Hz
0.300
df/dt>2 Time in sec
0.200
df/dt>2 Dir'n
Both
Note: These settings of Frequency & DF/DT Protection are recommended based on general practice. These settings shall be
adjusted if required as per the site conditions.
These settings are applicable only if the protections are enabled in P442.