Sunteți pe pagina 1din 8

Trip Circuit Supervision | Electrical4u

Trip Circuit Supervision

Page 1 of 8

MENU

Previous

Next

There are different contacts connected in series along a trip circuit of a electrical circuit
breaker. There must be some situation when the circuit breaker should not trip even a
faulty current passes through its power contacts. Such situations are low gas pressure
in SF6 circuit breaker, low air pressure in pneumatic operated circuit breaker etc. In

this situation the trip coil of the CB must not be energized to trip the CB. So there
must be NO contacts associated with gas pressure and air pressure relays, connected
in series with breaker trip coil. Another scheme of trip coil is that it should not be re
energized once the circuit breaker is open. That is done by providing one NO contact of
breaker auxiliary switch in series with trip coil. In addition to that the trip circuit of a
CB has to pass through considerable numbers of intermediate terminal contacts in
relay, control panel and circuit breaker kiosk. So if any of the intermediate contacts is
detached, the circuit breaker fails to trip. Not only that, if dc supply to the trip circuit
fails, the CB will not trip.

http://www.electrical4u.com/trip-circuit-supervision/

19/11/2016

Trip Circuit Supervision | Electrical4u

Page 2 of 8

To overcome this abnormal situation, trip circuit supervision becomes very


necessary. The figure below shows the simplest form of trip circuit healthy scheme.
Here one series combination of one lamp, one push bottom and one resistor is
connected across the protective relay contact as shown. In healthy situation all the
contacts except protective relay contact are in close position. Now if push bottom (PB)
is pressed, the trip circuit supervision network is completed and lamp glows
indicating that the breaker is ready for tripping.

http://www.electrical4u.com/trip-circuit-supervision/

19/11/2016

Trip Circuit Supervision | Electrical4u

Page 3 of 8

The above scheme is for supervision while circuit breaker is closed. This scheme is
called post close supervision.

There is another supervision scheme which is called pre and post close supervision.
This trip circuit supervision scheme is also quite simple. The only difference is that
here in this scheme, one NC contact of same auxiliary switch is connected across the
auxiliary NO contact of the trip circuit. The auxiliary NO contact is closed when CB is
closed and auxiliary NC contact is closed when CB is open and vice versa. Hence, as
shown in the figure below when the circuit breaker is closed the trip circuit supervision
network is completed via auxiliary NO contact but when the circuit breaker is open the

same supervision network is completed via NC contact. The resistor is used series with
the lamp for preventing unwanted tripping of circuit breaker due to internal short
circuit caused by failure of the lamp.

http://www.electrical4u.com/trip-circuit-supervision/

19/11/2016

Trip Circuit Supervision | Electrical4u

Page 4 of 8

So far whatever we have discussed it is only for local controlled installation but for a
distance control installation, relay system is necessary. The figure below shows the trip
circuit supervision scheme wherever a remote signal is required.

When trip circuit is healthy and circuit breaker is closed, relay A is energized which
closes the NO contact A1 and hence relay C is energized. Energized relay C keeps NC

contact in open position. Now if the circuit breaker is open, relay B is energized which
closes No contact B1 hence relay C is energized. As C is energized, it keeps the NC

contact C1 in open position. While CB is closed, if there is any discontinuity in the trip

http://www.electrical4u.com/trip-circuit-supervision/

19/11/2016

Trip Circuit Supervision | Electrical4u

Page 5 of 8

circuit relay A is de-energized which opens contact A1 and consequently relay C is deenergized and which make the NC contact C1 in close position and hence alarm circuit

is actuated. Trip circuit supervision is experienced by relay B with the circuit


breaker is open in a similar manner as relay A with the circuit breaker is closed. Relays
A and C are time-delayed by copper slugs to prevent spurious alarms during tripping
or closing operations. The resistors are mounted separately from the relays and their
values are chosen such that if any one component is inadvertently short-circuited, a
tripping operation will not take place.
The alarm circuit supply should be separated from main trip supply so that the alarm
can be actuated even the trip supply is fail.

Over Current Relay Working


Principle Types

Pick Up Current | Current


Setting | Plug Settin...

Differential Protection of
Transformer | Differ...

Miniature Circu
MCB

Protection System in Power


System

Types and Operation of SF6


Circuit Breaker

Buchholz Relay in transformer


| Buchholz Relay ...

Electrical Bus S
Electrical Subs

Previous

Closely Related Articles

Next

Protection System in Power System

Differential Protection of Generator or Alternator

http://www.electrical4u.com/trip-circuit-supervision/

19/11/2016

Trip Circuit Supervision | Electrical4u

Page 6 of 8

Annunciation System Alarm Annunciator

Rotor Earth Fault Protection of Alternator or Generator

Loss of Field or Excitation Protection of Alternator or Generator


Overvoltage Protection

Motor Protection Circuit Breaker or MPCB

Stator Earth Fault Protection of Alternator

Inter Turn Fault Protection of Stator Winding of Generator


Small and Large Motor Protection Scheme
Motor Thermal Overload Protection

Electrical Fault Calculation | Positive Negative Zero Sequence Impedance


External and Internal Faults in Transformer

Backup Protection of Transformer | Over Current and Earth Fault


Transformer Protection and Transformer Fault
Generator Protection

Protection of Lines or Feeder

Busbar Protection | Busbar Differential Protection Scheme


Protection of Capacitor Bank
More Related Articles

Types of Electrical Protection Relays or Protective Relays


Motor Protection Relay for High Voltage Induction Motor
Feeder Protection Relays

Pick Up Current | Current Setting | Plug Setting Multiplier and Time Setting Multiplier
of Relay
Electromagnetic Relay Working | Types of Electromagnetic Relays
Induction Cup Relay Working Principle Construction and Types
Over Current Relay Working Principle Types

http://www.electrical4u.com/trip-circuit-supervision/

19/11/2016

Trip Circuit Supervision | Electrical4u

Page 7 of 8

Differential Relay

Thermal Relay Working Principle Construction of Thermal Overload Relay


Distance Relay or Impedance Relay Working Principle Types
Instantaneous Relay

Inverse Time Relay | Definite Time Lag Relay


Backup Relay
New Articles

Nuclear Reactor

Gas Turbine Power Plant


Cost of Electrical Energy
Load Flow and Y Bus

Thermal Conductivity of Metals


Free Electron Theory of Metals

Please provide your valuable comments


Name : -

Enter your name here


Enter your email here

Enter your location here


Enter your content here

Email : Location : Your content : -

http://www.electrical4u.com/trip-circuit-supervision/

19/11/2016

Trip Circuit Supervision | Electrical4u

Page 8 of 8

Enter the above code here

2011-2016 electrical4u.The content is copyrighted to electrical4u and may not


be reproduced on other websites.

http://www.electrical4u.com/trip-circuit-supervision/

19/11/2016

S-ar putea să vă placă și