Code:
PrintingDate:
WATERFL2C
WEBCSS-Rev.10.1
01/08/2016
R1.0.0
Compactness.The EWWD~VZA seriesis designed toachieve thesmallest possible footprintmaking theproduct the ideal
solutiontofitthoughthetightestdoorwaysandconsequentlytheperfectproductforreplacementprojects.
Outstanding reliability. Depending on capacity, the EWWD~VZ A series features one or two independent refrigerant
circuits in order to guarantee highest possible redundancy and simplified maintenance activities. Units are equipped with
rugged compressor design with advanced and robust composite compressor gate-rotors material. Units are factory tested
beforeshipmentforanon-sitetroublefreeoperation.
Stepless capacity control. Cooling capacity is controlled by means of inverter driving the compressor motor. Units are
enjoyinginfinitely variablecapacity controlfrom 100%load downto minimumcapacity whichis variabledepending on unit
model. No any mechanical unloading system is used. This advanced capacity control method allows the unit to perfectly
matchthecooling(orheating)loadandconsequentlyprovidingextremelyaccuratewatertemperaturecontrol.
Variable Volume Ratio. Compressors are enjoying the Variable Volume Ratio (VVR) technology. This innovative system
allowsthecompressortoadaptthedischargepressureoftherefrigeranttothespecificoperatingconditions.Inthisway,itis
possible to prevent energy losses deriving from under or over compression phenomena that are typical of traditional
compressortechnologies(withfixed volumeratio).Thereduction ofenergylossesinside compressorbringstoan increased
unitefficiency.
Future readiness. The EWWD~VZ A series is designed for R134a refrigerant in order to achieve the highest possible unit
efficiency.Additionallytothis,ithasbeendesignedtobecompatiblefordropinofnextgenerationrefrigerantswithlower
GWP.Daikinisatfulldisposaltoprovidefurtherinformationaboutthisspecificsubject.
Superior control logic. The EWWD~VZ A series is enjoying MicroTech III controller that provides an easy to use control
environment. The control logic is designed to provide highest efficiency performances and continuous operation. Easy
interfacewithLonWorks,Bacnet,TCP/IPorModbuscommunicationprotocols.
Low starting current. No any current spike is experienced at start up thanks to inverter driven compressor motors. The
startingcurrentisalwayslowerthanfullloadcurrent(FLA).
Displacement power factor always > 0,95. Thanks to inverter driven compressors, the EWWD~VZ A series always
operateswithadisplacementpowerfactor>0,95allowingtoavoidpowerfactorpenaltiesanddecreasingelectricallossesin
cablesandtransformers.
2/31
AdditionalinformationrelatedtoF-GASRegulation(EU)No517/2014oftheEuropeanParliamentandoftheCouncilof16th
April2014onfluorinatedgreenhousegasesandrepealingRegulation(EC)No842/2006.
Note: Equipment contains fluorinated greenhouse gases. Actual refrigerant charge depends on the final unit construction,
detailscanbefoundontheunitnameplate.
3/31
GENERAL CHARACTERISTICS
General Characteristics
Inverter Driven Single Screw Compressor. The EWWD~VZ A series is equipped with latest Daikin design Single Screw
Compressors. This technology is enjoying highly balanced loads resulting in reduced mechanical stress for the main
components. Lifetime and reliability are in this way improved and, at the same time, vibrations and noise emissions are
reduced.ThehighvolumetricefficiencyofDaikinsinglescrewcompressorsmakesthemtheidealsolutionforvariablespeed
applications.ThankstoinvertertechnologytheEWWD~VZAscrewcompressorsareabletomatchthecoolingoutputofthe
unit to the actual load requirement. Compressors rotational speed is continuously adjusted (stepless regulation) allowing
excellentwatertemperaturecontrolandefficientcapacitymodulation.
Compressors are enjoying the Variable Volume Ratio (VVR) technology. This innovative system allows the compressor to
adapt the discharge pressure of the refrigerant to the specific operating conditions. In this way, it is possible to prevent
energy losses deriving from under or over compression phenomena that are typical of traditional compressor technologies
(withfixedvolumeratio).Thereductionofenergylossesinsidecompressorbringstoanincreasedunitefficiency.
OilseparatorisintegratedwithintheCondensershell.
Refrigerant. The EWWD~VZ A series is designed for R134a refrigerant in order to achieve the highest possible unit
efficiency.Additionallytothis,ithasbeendesignedtobecompatiblefordropinofnextgenerationrefrigerantswithlower
GWP.Daikinisatfulldisposaltoprovidefurtherinformationaboutthisspecificsubject.
Evaporator. High efficiency flooded type shell and tube heat exchanger. Evaporator tubes have been selected in order to
achievethe highestheat transfer.Optimized nucleateboiling is guaranteedby specificallydesigned cavitieson the external
tubes surface. Internal tubes surface area has helical type design. The extremely high heat transfer coefficient allows the
reductionofthetemperaturedifferencebetweenchilledwaterandrefrigerantthusresultinginhigheroverallunitefficiency.
Theevaporatorisdesignedaccordingto2014/68/EUEuropeanstandard(Constructionofpressurevessel).Thewatersideis
designed for 10 bar maximum operating pressure; vents and drain are provided. Water connections are Victaulic type as
standard, flanged connections are available as optional. As standard unit evaporator is two water passes design. Nonstandard applications may require different number of water passes (contact Factory for further information). As standard,
thermalinsulation(20mmthickness)isfittedontheexternalevaporatorsurfacearea.
Condenser.Highefficiencyshellandtubetypeheatexchanger.Condensertubeshavebeenselectedinordertoachievethe
highestheattransfer. Optimizedcondensation isachieved byfinnedtype tubeexternal surfacearea. Internaltubes surface
areahashelicaltypedesign.Theextremelyhighheattransfercoefficientallowsthereductionofthetemperaturedifference
betweencondenserwaterandrefrigerantthusresultinginhigheroverallunitefficiency.
Thecondenserisdesignedaccordingto2014/68/EUEuropeanstandard(Constructionofpressurevessel).Thewatersideis
designed for 10 bar maximum operating pressure; vents and drain are provided. Water connections are Victaulic type as
standard, flanged connections are available as optional. Unit condenser is single water pass with counter-flow design for
optimizeheattransferbetweenwaterandrefrigerant.
WithinCondensershell,specificsectionisdedicatedtotheoilseparation.
-Singlescrewcompressorinverterdriven
-Refrigerantcharge
-Independentrefrigerantcircuitintotheevaporator
-Watercooledcondenser
-Electronicexpansionvalve
-Liquidlineshutoffvalve
-Sightglasswithmoistureindicator
-Highpressureswitch
-Highpressuretransducer
-Lowpressuretransducer
-Oilpressuretransducer
-Suctiontemperaturesensor
Electrical Panel.PowerandcontrolsectionsarelocatedintothemainelectricalpanelIP54designed.Themainpaneldoors
areinterlockedto themainswitch (standard)in orderguaranteesafe operationwhen doorsareopened. Thepower section
includescompressorprotectiondevicesandcompressorstarters(invertertype).
4/31
GENERAL CHARACTERISTICS
Maincontrolfeaturesare(formoreinformationrefertoUnitControlManual):
-Optimizedmanagementofcompressorssteplesscapacitycontrolthroughinverterdrive.
-Displayofevaporatorentering/leavingwatertemperatures.
-Displayofcondenserentering/leavingwatertemperatures.
-Displayofrefrigerantcondensing/evaporatingtemperaturesandpressures.
- Regulation of leaving evaporator water (cooling mode) or condenser water (heating mode). Temperature tolerance
0,1C.
-Displayofcompressorworkinghoursandnumberofcompressorstarts.
-Re-startincaseofpowerfailure(automaticormanualdependingonfailuretype).
-Softload(optimizedmanagementofthecompressorloadduringthestart-up).
-Setpointreset.
-Master/Slaveoperation(upto4chillersconnected).
Alarmssignaling(formoreinformationrefertoUnitControlManual):
-Phaseloss.
-Evaporatorwaterflowloss.
-Evaporatorwaterfreezingprotection.
-Externalalarm.
-Lowevaporatorrefrigerantpressure.
-Highrefrigerantpressure(transducer).
-Highrefrigerantpressure(switch).
-Lowpressureratio.
-Highrefrigerantdischargetemperature.
-Highoilpressuredifferential.
-Highmotortemperature.
Alarm logging: when alarm occurs, the alarm type, date, time and main unit working parameters are recorder and stored
intothecontrollermemory.Thelast25alarmsoccurredarestored.
Regulation type: Proportional-Integral-Derivative (PID) type based on the evaporator leaving water temperature set point
(coolingmode)orbasedonthecondenserleavingwatertemperaturesetpoint(heatingmode).
Connection to BMS: MicroTech III controlled is capable to communicate with BMS systems based on the most common
protocolssuchas:Modbus,LonWorks,BacNetIPandMS/TP(class4),EthernetTCP/IP.Communicationcards(optional)are
tobeselectedaccordingtotherequiredcommunicationprotocol.
5/31
GENERAL CHARACTERISTICS
Nomenclature
6/31
OPTIONS
Standard Options
Evaporator Victaulic kit (option 20 - STANDARD). Victaulicjointsandcounter-pipes.
7/31
OPTIONS
Options on request
Heat Pump Version including Pursuit Mode (option 07a ON REQUEST). Reversibility on the water side. Unit
capability to follow two different set points (cooling mode or heating mode). During cooling mode operation, unit
microprocessorisfollowingevaporatorleavingwatertemperaturesetpoint.Whenthemachineisswitchedtoheatingmode
operation, the unit microprocessor is following condenser leaving water temperature set point. Cooling or heating mode
operation can be selected by means of a dedicated switch installed on the unit electrical panel. If, communication card is
selected,coolingorheatingmodeoperationcanbemanagedbyBMS.HeatPumpVersionoptionincludes20mmcondenser
insulation(option33).
In case pursuit mode operation is enabled via Microtech III, unit controller will try to follow bot set points (cooling and
heating). When the first set point is satisfied, either the cold or the hot one, the unit will maintain that set point. Ideal
applications are when cooling and heating loads are balanced. Pursuit mode operation is not recommended in case of
unbalancedloads(e.g.80%ofnominalcoolingloadand20%ofnominalheatingload).
Brine Version (option 08 ON REQUEST). Required in case of unit operation with chilled water temperatures below
+4C. Unit will be fitted with double thermal insulation on evaporator (40 mm thickness). Brine Version option includes
compressorthermalinsulationoption(option146).Refertotheunitoperatingenvelopeformoreinformationaboutminimum
allowedevaporatorleavingwatertemperatures.
Evaporator double flanges kit (option 104 ON REQUEST). Victaulic-to-flange adapter (shipped loose and including
counter-flanges,gasketsandbolts).
Condenser double flanges kit (option 26 ON REQUEST). Victaulic-to-flange adapter (shipped loose and including
counter-flanges,gasketsandbolts).
20 mm condenser insulation (option 33 ON REQUEST). Thermalinsulationofthecondensershell(includedwithoption
07aHeatPumpVersionandwithoption111Hightemperaturekit).
Discharge line shut off valve (option 61 ON REQUEST).Installedonthedischargelineofthecompressortofacilitate
maintenanceoperations.
Suction line shut off valve (option 62 ON REQUEST). Installed on the suction line of the compressor to facilitate
maintenanceoperations.
High-pressure side manometers (option 63 ON REQUEST).
Low-pressure side manometers (option 64 ON REQUEST).
Compressor soundproof system (option 76-b ON REQUEST). High performance soundproof cabinet installed around
compressorandspecificallydesignedinordertominimizeunitsoundlevels.
High temperature kit (option 111 ON REQUEST). Requiredincaseofcondenserleavingwatertemperaturehigherthan
approximately 48C (note: this limit may change depending on evaporator water temperature and on specific unit
version/size. Refer to operating envelope and to chiller selection software for detailed information). Specifically selected
componentsareusedinordertoallowtheunittooperateatsuchconditions.Unitdimensionsandweightmaychangefrom
standard.Hightemperaturekitoptionincludes20mmcondenserinsulation(option33)andheatpumpversion(option07a).
Refrigerant leak detection (option 121 ON REQUEST). Electronic device (shipped loose) for automatic detection of
refrigerant leak. The leak detection device should be installed within the machinery room in the most appropriate location
(refertotheleakdetection deviceinstallationmanual).When leakaboveapre-set concentrationofrefrigerant(2000 ppm)
isdetected,signalis senttounitcontroller (aspecificalarmis visualizedontheunit microprocessorsdisplay).The Factory
doesnotsupplyinterconnectingcablesbetweenleakdetectiondeviceandunitcontroller.
Knock down electrical panel (option 147 ON REQUEST). Electrical panel dismounted from the unit and shipped
separately.
Compressor thermal insulation (option 146 ON REQUEST). 20 mm thermal insulation of compressor suction side.
(Includedwithoption08Brineversion).
Cu-Ni 90-10 condenser tubes (option 50 ON REQUEST). Condenser tubes made of Cu-Ni 90-10 material and Cu-Ni
90-10 tube sheets cladding. Epoxy ceramic coating of water headers and sacrificial anodes. Unit performances may differ
from standard. Contact local Daikin office for more details. When selecting option 50, condenser double flanges kit option
(option26)mustbeselectedaswell.
Evaporator 3 passes (option 103b ON REQUEST). Three passes water side evaporator. May be required in case of
evaporatorwatertemperaturedifference higherthan8C.Unit performancesmaydifferfrom standard.Contactlocal Daikin
officeformoredetails.
Evaporator single pass (option 103 ON REQUEST). Single pass water side evaporator. May be required in case of
evaporator water temperature difference lower than 4C. Unit performances may differ from standard. Contact local Daikin
officeformoredetails.
8/31
OPTIONS
Energy meter including current limit (option 16a ON REQUEST). Electronic device installed within unit electrical
panel. Measures and display supply line individual phase voltage and current, active and reactive power input, active and
reactive energy consumption. An integrated RS485 module allows Modbus communication to BMS. It includes current limit
functionality.
Evaporator flow switch (option 58 ON REQUEST). Paddle flow switchshipped loose.Refer tounit installation manual
formoredetails.
Condenser flow switch (option 59 ON REQUEST). Paddle flow switch shipped loose. Refer to unit installation manual
formoredetails.
Compressor circuit breakers (option 95 ON REQUEST). Protection device including protection from current overload
andovercurrent.Incasethisoptionisselected,compressorfusesareremoved.
Ground fault relay (option 102 ON REQUEST). Unitshutsdownincaseofgroundfaultisdetected.
Rapid restart (option 110 ON REQUEST). Ideal solution for those critical applications that cannot afford the loose of
coolingorheating.Incaseofpowerfailureunitwillre-startasfastas15secondsfrompowerrestoration.Unitwillreachfull
loadwithin160secondsand180secondsrespectivelyforsinglecompressoranddualcompressorsunitmodels.Refertounit
controlmanualformoreinformationaboutthisoption.
Automatic transfer switch free standing (option 149 ON REQUEST). Free standing panel separate from the unit
allowing to connect two separate power supply lines (e.g. main supply line and secondary line from backup generator). In
caseoffailureofmainpowersupplyline,theautomatictransferswitchdevicewillautomaticallyswitchtothesecondaryline
ifpowerisdetected.
Inverter EN61800-3 Class C2 compliant (option 150 ON REQUEST). Additional RFI filters on the unit power supply
line.Reduces electromagnetic interferences.Increases the inverterimmunity level accordingto residential environment and
allowsitscompliancywithemissionslevelrequiredinC2category.
Rubber pads (option 152 ON REQUEST). Rubber pad mounts to be installed under the unit base frame during
installation.
Container kit (option 71 ON REQUEST).
Transport kit (option 112 ON REQUEST).
9/31
TECHNICAL SPECIFICATIONS
EWWD~VZ-SS
MODEL
COOLING PERFORMANCE
Capacity-Cooling
Capacitycontrol-Type
Capacitycontrol-Minimumcapacity
Unitpowerinput-Cooling
EER
ESEER
IPLV
kW
610
Stepless
20
110
5.51
7.25
9.08
704
Stepless
20
132
5.31
7.30
9.27
757
Stepless
20
142
5.31
7.40
9.20
894
Stepless
20
162
5.52
7.27
9.22
1,039
Stepless
20
196
5.28
7.52
9.40
IW
GPSS
IW
GPSS
IW
GPSS
IW
GPSS
IW
GPSS
mm
mm
mm
2120
1180
3460
2120
1180
3460
2120
1180
3460
2290
1240
3690
2480
1340
3830
kg
kg
2892
2977
2928
3033
2941
3053
3451
3611
4237
4488
FloodedS&T
Water
0
88
12
7
29.3
80.0
CC
FloodedS&T
Water
0
88
12
7
33.8
106
CC
FloodedS&T
Water
0
96
12
7
36.3
89.0
CC
FloodedS&T
Water
0
134
12
7
42.9
98.0
CC
FloodedS&T
Water
0
156
12
7
49.9
104
CC
S&T
Water
0
81
30
35
34.5
54.0
S&T
Water
0
102
30
35
40.2
41.0
S&T
Water
0
102
30
35
43.1
46.0
S&T
Water
0
126
30
35
50.7
44.0
S&T
Water
0
217
30
35
59.4
33.0
%
kW
CASING
Colour*
Material*
DIMENSIONS
Height
Width
Length
WEIGHT
UnitWeight
OperatingWeight
HEAT EXCHANGER - EVAPORATOR
Type*
Fluid
FoulingFactor
WaterVolume
Watertemperaturein
Watertemperatureout
Waterflowrate
Waterpressuredrop
Insulationmaterial*
l
C
C
l/s
kPa
l
C
C
l/s
kPa
COMPRESSOR
Type
Oilcharge
Quantity
l
No.
Inverter
Inverter
Inverter
Inverter
Inverter
DrivenSingle DrivenSingle DrivenSingle DrivenSingle DrivenSingle
Screw
Screw
Screw
Screw
Screw
36.0
36.0
36.0
50.0
50.0
1
1
1
1
1
SOUND LEVEL**
SoundPower-Cooling
SoundPressurelevel@1mdistanceCooling
dB(A)
101
105
105
105
108
dB(A)
82
86
86
86
89
kg
No.
R134a
100
1
R134a
110
1
R134a
110
1
R134a
170
1
R134a
180
1
mm
mm
141.3
168.3
141.3
168.3
141.3
168.3
168.3
219.1
219.1
219.1
REFRIGERANT CIRCUIT
Refrigeranttype
Refrigerantcharge
N.ofcircuits
PIPING CONNECTIONS
Evaporatorwaterinlet/outlet
Condenserwaterinlet/outlet
All the perfrormances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0C;
condenser 30.0/35.0C, unit at full load operation; operating fluid: Water; fouling factor = 0. (*) IW: Ivory White; GPSS: Galvanized and
Painted Steel Sheet; S&T: Single Pass Shell & Tube; CC:Closed Cell; (**) The values are according to ISO 3744 and are referred to: evaporator
12/7 C, condenser 30/35 C, full load operation.
10/31
TECHNICAL SPECIFICATIONS
EWWD~VZ-XS
MODEL
COOLING PERFORMANCE
Capacity-Cooling
Capacitycontrol-Type
Capacitycontrol-Minimumcapacity
Unitpowerinput-Cooling
EER
ESEER
IPLV
kW
449
Stepless
20
81.1
5.53
7.51
9.42
501
Stepless
20
89.6
5.58
7.92
9.59
613
Stepless
20
108
5.64
8.10
9.52
713
Stepless
20
128
5.54
8.20
9.66
793
Stepless
20
146
5.43
8.22
9.64
901
Stepless
20
158
5.67
7.92
9.48
IW
GPSS
IW
GPSS
IW
GPSS
IW
GPSS
IW
GPSS
IW
GPSS
mm
mm
mm
2090
1180
3460
2120
1180
3460
2120
1180
3690
2230
1220
3690
2290
1240
3690
2480
1340
3830
kg
kg
2968
3098
2911
3006
3102
3274
3470
3648
3451
3611
4257
4518
FloodedS&T
Water
0
70
12
7
21.6
89.0
CC
FloodedS&T
Water
0
88
12
7
24.0
63.0
CC
FloodedS&T
Water
0
136
12
7
29.4
59.0
CC
FloodedS&T
Water
0
134
12
7
34.2
63.0
CC
FloodedS&T
Water
0
134
12
7
38.0
55.0
CC
FloodedS&T
Water
0
168
12
7
43.2
67.0
CC
S&T
Water
0
81
30
35
25.4
31.0
S&T
Water
0
92
30
35
28.3
28.0
S&T
Water
0
126
30
35
34.7
22.0
S&T
Water
0
145
30
35
40.4
20.0
S&T
Water
0
126
30
35
45.2
24.0
S&T
Water
0
217
30
35
50.9
25.0
%
kW
CASING
Colour*
Material*
DIMENSIONS
Height
Width
Length
WEIGHT
UnitWeight
OperatingWeight
HEAT EXCHANGER - EVAPORATOR
Type*
Fluid
FoulingFactor
WaterVolume
Watertemperaturein
Watertemperatureout
Waterflowrate
Waterpressuredrop
Insulationmaterial*
l
C
C
l/s
kPa
l
C
C
l/s
kPa
COMPRESSOR
Type
Oilcharge
Quantity
l
No.
Inverter
Inverter
Inverter
Inverter
Inverter
Inverter
DrivenSingle DrivenSingle DrivenSingle DrivenSingle DrivenSingle DrivenSingle
Screw
Screw
Screw
Screw
Screw
Screw
32.0
32.0
36.0
36.0
50.0
50.0
1
1
1
1
1
1
SOUND LEVEL**
SoundPower-Cooling
SoundPressurelevel@1mdistanceCooling
dB(A)
97
99
101
105
105
105
dB(A)
78
80
82
86
86
86
kg
No.
R134a
95
1
R134a
95
1
R134a
100
1
R134a
110
1
R134a
170
1
R134a
170
1
mm
mm
141.3
168.3
141.3
168.3
141.3
219.1
168.3
219.1
168.3
219.1
219.1
219.1
REFRIGERANT CIRCUIT
Refrigeranttype
Refrigerantcharge
N.ofcircuits
PIPING CONNECTIONS
Evaporatorwaterinlet/outlet
Condenserwaterinlet/outlet
All the perfrormances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0C;
condenser 30.0/35.0C, unit at full load operation; operating fluid: Water; fouling factor = 0. (*) IW: Ivory White; GPSS: Galvanized and
Painted Steel Sheet; S&T: Single Pass Shell & Tube; CC:Closed Cell; (**) The values are according to ISO 3744 and are referred to: evaporator
12/7 C, condenser 30/35 C, full load operation.
11/31
TECHNICAL SPECIFICATIONS
EWWD~VZ-XS
MODEL
EWWDC11V
ZXSA1
COOLING PERFORMANCE
Capacity-Cooling
Capacitycontrol-Type
Capacitycontrol-Minimumcapacity
Unitpowerinput-Cooling
EER
ESEER
IPLV
kW
%
kW
1,053
Stepless
20
192
5.46
8.17
9.58
CASING
Colour*
Material*
IW
GPSS
DIMENSIONS
Height
Width
Length
mm
mm
mm
2480
1340
3830
kg
kg
4552
4860
WEIGHT
UnitWeight
OperatingWeight
HEAT EXCHANGER - EVAPORATOR
Type*
Fluid
FoulingFactor
WaterVolume
Watertemperaturein
Watertemperatureout
Waterflowrate
Waterpressuredrop
Insulationmaterial*
l
C
C
l/s
kPa
FloodedS&T
Water
0
199
12
7
50.4
58.0
CC
l
C
C
l/s
kPa
S&T
Water
0
241
30
35
59.9
25.0
l
No.
Inverter
DrivenSingle
Screw
50.0
1
dB(A)
108
dB(A)
89
kg
No.
R134a
180
1
mm
mm
219.1
219.1
COMPRESSOR
Type
Oilcharge
Quantity
SOUND LEVEL**
SoundPower-Cooling
SoundPressurelevel@1mdistanceCooling
REFRIGERANT CIRCUIT
Refrigeranttype
Refrigerantcharge
N.ofcircuits
PIPING CONNECTIONS
Evaporatorwaterinlet/outlet
Condenserwaterinlet/outlet
All the perfrormances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0C;
condenser 30.0/35.0C, unit at full load operation; operating fluid: Water; fouling factor = 0. (*) IW: Ivory White; GPSS: Galvanized and
Painted Steel Sheet; S&T: Single Pass Shell & Tube; CC:Closed Cell; (**) The values are according to ISO 3744 and are referred to: evaporator
12/7 C, condenser 30/35 C, full load operation.
12/31
TECHNICAL SPECIFICATIONS
EWWD~VZ-PS
MODEL
COOLING PERFORMANCE
Capacity-Cooling
Capacitycontrol-Type
Capacitycontrol-Minimumcapacity
Unitpowerinput-Cooling
EER
ESEER
IPLV
kW
505
Stepless
20
87.5
5.77
8.15
9.61
718
Stepless
20
126
5.66
8.48
9.68
908
Stepless
20
156
5.81
8.25
9.57
IW
GPSS
IW
GPSS
IW
GPSS
mm
mm
mm
2090
1180
3690
2430
1330
3690
2480
1340
3830
kg
kg
3247
3375
4082
4349
4346
4660
FloodedS&T
Water
0
96
12
7
24.2
55.0
CC
FloodedS&T
Water
0
168
12
7
34.4
42.0
CC
FloodedS&T
Water
0
199
12
7
43.5
44.0
CC
S&T
Water
0
126
30
35
28.5
15.0
S&T
Water
0
217
30
35
40.6
17.0
S&T
Water
0
241
30
35
51.2
19.0
%
kW
CASING
Colour*
Material*
DIMENSIONS
Height
Width
Length
WEIGHT
UnitWeight
OperatingWeight
HEAT EXCHANGER - EVAPORATOR
Type*
Fluid
FoulingFactor
WaterVolume
Watertemperaturein
Watertemperatureout
Waterflowrate
Waterpressuredrop
Insulationmaterial*
l
C
C
l/s
kPa
l
C
C
l/s
kPa
COMPRESSOR
Type
Oilcharge
Quantity
l
No.
Inverter
Inverter
Inverter
DrivenSingle DrivenSingle DrivenSingle
Screw
Screw
Screw
36.0
40.0
50.0
1
1
1
SOUND LEVEL**
SoundPower-Cooling
SoundPressurelevel@1mdistanceCooling
dB(A)
99
105
105
dB(A)
80
86
86
kg
No.
R134a
100
1
R134a
150
1
R134a
180
1
mm
mm
141.3
219.1
219.1
219.1
219.1
219.1
REFRIGERANT CIRCUIT
Refrigeranttype
Refrigerantcharge
N.ofcircuits
PIPING CONNECTIONS
Evaporatorwaterinlet/outlet
Condenserwaterinlet/outlet
All the perfrormances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0C;
condenser 30.0/35.0C, unit at full load operation; operating fluid: Water; fouling factor = 0. (*) IW: Ivory White; GPSS: Galvanized and
Painted Steel Sheet; S&T: Single Pass Shell & Tube; CC:Closed Cell; (**) The values are according to ISO 3744 and are referred to: evaporator
12/7 C, condenser 30/35 C, full load operation.
13/31
ELECTRICAL SPECIFICATIONS
EWWD~VZ-SS
MODEL
POWER SUPPLY
Phases
Frequency
Voltage
VoltagetoleranceMinimum
VoltagetoleranceMaximum
No.
Hz
V
%
%
3
50
400
-10%
10%
3
50
400
-10%
10%
3
50
400
-10%
10%
3
50
400
-10%
10%
3
50
400
-10%
10%
A
A
A
A
179
171
256
282
214
202
306
336
245
220
350
385
295
249
421
463
344
300
491
540
No.
V
%
%
A
3
400
-10%
10%
256
VFD
3
400
-10%
10%
306
VFD
3
400
-10%
10%
350
VFD
3
400
-10%
10%
421
VFD
3
400
-10%
10%
491
VFD
UNIT
Maximumstartingcurrent
Nominalrunningcurrentcooling
Maximumrunningcurrent
Maximumcurrentforwiressizing
COMPRESSORS
Phases
Voltage
VoltagetoleranceMinimum
VoltagetoleranceMaximum
Maximumrunningcurrent
Startingmethod
Allowed voltage tolerance 10%. Voltage unbalance between phases must be within 3%. Maximum starting current: starting current of biggest
compressor plus current of the other compressor at 75% of maximum load. In case of inverter driven units, no inrush current at start up is experienced.
Nominal running current in cooling is referred to the following conditions: evaporator 12/7C; condenser 30/35C. Maximum running current is based on
max compressor absorbed current in its envelope. Maximum current for wires sizing is based on minimum allowed voltage. Maximum current for wires
sizing: compressors full load ampere x 1,1. The data are referred to the standard unit without options. All data are subject to change without notice.
Please refer to unit nameplate data.
14/31
ELECTRICAL SPECIFICATIONS
EWWD~VZ-XS
MODEL
POWER SUPPLY
Phases
Frequency
Voltage
VoltagetoleranceMinimum
VoltagetoleranceMaximum
No.
Hz
V
%
%
3
50
400
-10%
10%
3
50
400
-10%
10%
3
50
400
-10%
10%
3
50
400
-10%
10%
3
50
400
-10%
10%
3
50
400
-10%
10%
A
A
A
A
155
126
222
244
173
140
247
272
179
171
256
282
214
201
306
336
256
229
366
403
295
249
421
463
No.
V
%
%
A
3
400
-10%
10%
222
VFD
3
400
-10%
10%
247
VFD
3
400
-10%
10%
256
VFD
3
400
-10%
10%
306
VFD
3
400
-10%
10%
366
VFD
3
400
-10%
10%
421
VFD
UNIT
Maximumstartingcurrent
Nominalrunningcurrentcooling
Maximumrunningcurrent
Maximumcurrentforwiressizing
COMPRESSORS
Phases
Voltage
VoltagetoleranceMinimum
VoltagetoleranceMaximum
Maximumrunningcurrent
Startingmethod
MODEL
EWWDC11V
ZXSA1
POWER SUPPLY
Phases
Frequency
Voltage
VoltagetoleranceMinimum
VoltagetoleranceMaximum
No.
Hz
V
%
%
3
50
400
-10%
10%
A
A
A
A
344
299
491
540
No.
V
%
%
A
3
400
-10%
10%
491
VFD
UNIT
Maximumstartingcurrent
Nominalrunningcurrentcooling
Maximumrunningcurrent
Maximumcurrentforwiressizing
COMPRESSORS
Phases
Voltage
VoltagetoleranceMinimum
VoltagetoleranceMaximum
Maximumrunningcurrent
Startingmethod
Allowed voltage tolerance 10%. Voltage unbalance between phases must be within 3%. Maximum starting current: starting current of biggest
compressor plus current of the other compressor at 75% of maximum load. In case of inverter driven units, no inrush current at start up is experienced.
Nominal running current in cooling is referred to the following conditions: evaporator 12/7C; condenser 30/35C. Maximum running current is based on
max compressor absorbed current in its envelope. Maximum current for wires sizing is based on minimum allowed voltage. Maximum current for wires
sizing: compressors full load ampere x 1,1. The data are referred to the standard unit without options. All data are subject to change without notice.
Please refer to unit nameplate data.
15/31
ELECTRICAL SPECIFICATIONS
EWWD~VZ-PS
MODEL
POWER SUPPLY
Phases
Frequency
Voltage
VoltagetoleranceMinimum
VoltagetoleranceMaximum
No.
Hz
V
%
%
3
50
400
-10%
10%
3
50
400
-10%
10%
3
50
400
-10%
10%
A
A
A
A
173
138
247
272
214
200
306
336
295
247
421
463
No.
V
%
%
A
3
400
-10%
10%
247
VFD
3
400
-10%
10%
306
VFD
3
400
-10%
10%
421
VFD
UNIT
Maximumstartingcurrent
Nominalrunningcurrentcooling
Maximumrunningcurrent
Maximumcurrentforwiressizing
COMPRESSORS
Phases
Voltage
VoltagetoleranceMinimum
VoltagetoleranceMaximum
Maximumrunningcurrent
Startingmethod
Allowed voltage tolerance 10%. Voltage unbalance between phases must be within 3%. Maximum starting current: starting current of biggest
compressor plus current of the other compressor at 75% of maximum load. In case of inverter driven units, no inrush current at start up is experienced.
Nominal running current in cooling is referred to the following conditions: evaporator 12/7C; condenser 30/35C. Maximum running current is based on
max compressor absorbed current in its envelope. Maximum current for wires sizing is based on minimum allowed voltage. Maximum current for wires
sizing: compressors full load ampere x 1,1. The data are referred to the standard unit without options. All data are subject to change without notice.
Please refer to unit nameplate data.
16/31
SOUND LEVELS
EWWD~VZ-SS
Sound pressure level at 1 m from the unit (rif. 2 x 10-5 Pa)
MODEL
63Hz
125Hz
250Hz
500Hz
1000Hz
2000Hz
4000Hz
8000Hz
db(A)
Power db
(A)
600
700
760
890
C10
65.7
69.7
69.7
69.7
72.7
67.5
71.5
71.5
71.5
74.5
74.5
78.5
78.5
78.5
81.5
82.2
86.2
86.2
86.2
89.2
75.8
79.8
79.8
79.8
82.8
73.8
77.8
77.8
77.8
80.8
65.7
69.7
69.7
69.7
72.7
58.3
62.3
62.3
62.3
65.3
82
86
86
86
89
101
105
105
105
108
The values are according to ISO 3744 and are referred to: evaporator 12/7 C, condenser 30/35 C, full load operation.
17/31
SOUND LEVELS
EWWD~VZ-XS
Sound pressure level at 1 m from the unit (rif. 2 x 10-5 Pa)
MODEL
63Hz
125Hz
250Hz
500Hz
1000Hz
2000Hz
4000Hz
8000Hz
db(A)
Power db
(A)
450
58.4
66.2
76.0
73.2
73.9
72.0
62.9
53.7
78
97
500
610
60.4
65.7
68.2
67.5
78.0
74.5
75.2
82.2
75.9
75.8
74.0
73.8
64.9
65.7
55.7
58.3
80
82
99
101
710
800
69.7
69.7
71.5
71.5
78.5
78.5
86.2
86.2
79.8
79.8
77.8
77.8
69.7
69.7
62.3
62.3
86
86
105
105
900
C11
69.7
72.7
71.5
74.5
78.5
81.5
86.2
89.2
79.8
82.8
77.8
80.8
69.7
72.7
62.3
65.3
86
89
105
108
The values are according to ISO 3744 and are referred to: evaporator 12/7 C, condenser 30/35 C, full load operation.
18/31
SOUND LEVELS
EWWD~VZ-PS
Sound pressure level at 1 m from the unit (rif. 2 x 10-5 Pa)
MODEL
63Hz
125Hz
250Hz
500Hz
1000Hz
2000Hz
4000Hz
8000Hz
db(A)
Power db
(A)
505
60.4
68.2
78.0
75.2
75.9
74.0
64.9
55.7
80
99
715
69.7
71.5
78.5
86.2
79.8
77.8
69.7
62.3
86
105
910
69.7
71.5
78.5
86.2
79.8
77.8
69.7
62.3
86
105
The values are according to ISO 3744 and are referred to: evaporator 12/7 C, condenser 30/35 C, full load operation.
19/31
OPERATING LIMITS
Operating Limits
Legend:
ELWT:EvaporatorLeavingWaterTemperature(C)
CLWT:CondenserLeavingWaterTemperature(C)
Ref. 1:StandardUnit.
Ref. 2:StandardUnitplusBrineVersion(option08-onrequest).
Ref. 3:StandardUnitplusHightemperaturekit(option111-onrequest).
Ref. 4:StandardUnitplusHightemperaturekit(option111-onrequest)plusBrineVersion(option08-onrequest).
Notes:
- The above graph refers to the unit operating at full load. Unit may be able to operate outside the above envelope with
compressorsunloading.Pleasecontactfactoryforfurtherdetails.
- For operation with EWLT below 4C, the unit must operate with glycol mixture. The glycol percentage must be provided
accordingtotheminimumELWTneeded.
-Theabovegraphicrepresentsaguidelineabouttheoperatinglimitsoftherange.PleaserefertothelatestChillerSelection
Software(CSS)forrealoperatinglimitsworkingconditionsforeachsize.
-Inareas2,3and4chillermaynotunloadtotheminimumcapacity.Pleaserefertochillerselectionsoftware.
20/31
OPERATING LIMITS
Operating
Limits
Legend:
ELWT:EvaporatorLeavingWaterTemperature(C)
CLWT:CondenserLeavingWaterTemperature(C)
Ref. 1:StandardUnit.
Ref. 2:StandardUnitplusBrineVersion(option08-onrequest).
Ref. 3:StandardUnitplusHightemperaturekit(option111-onrequest).
Ref. 4:StandardUnitplusHightemperaturekit(option111-onrequest)plusBrineVersion(option08-onrequest).
Notes:
- The above graph refers to the unit operating at full load. Unit may be able to operate outside the above envelope with
compressorsunloading.Pleasecontactfactoryforfurtherdetails.
- For operation with EWLT below 4C, the unit must operate with glycol mixture. The glycol percentage must be provided
accordingtotheminimumELWTneeded.
-Theabovegraphicrepresentsaguidelineabouttheoperatinglimitsoftherange.PleaserefertothelatestChillerSelection
Software(CSS)forrealoperatinglimitsworkingconditionsforeachsize.
-Inareas2,3and4chillermaynotunloadtotheminimumcapacity.Pleaserefertochillerselectionsoftware.
21/31
OPERATING LIMITS
Water heat exchangers - maximum/maximum water t
Theminimumandmaximumallowedtatfullloadconditionsarerespectively4Cand8C.Contactfactoryincaseloweror
highertarerequired.
Limitsforoperation:
-Maximumambienttemperature:42C
-Minimumambienttemperature:5C
-Maximumrelativehumidity:95%notcondensing
Limitsforstorage:
-Maximumambienttemperature50C
-Minimumambienttemperature:-20C
-Maximumrelativehumidity:95%notcondensing
Storagebelowtheminimumtemperaturemaycausedamagetocomponents.
Storageabovethemaximumtemperaturecausesopeningofsafetyvalves.
Storageincondensingatmospheremaydamageelectroniccomponents.
Water treatment
Before putting the unit into operation, clean the water circuit. Dirt, scales, corrosion debris and other materials can
accumulate inside the heat exchanger and reduce its heat exchanging capacity. Pressure drops can increase as well, thus
reducing water flow. Proper water treatment therefore reduces the risk of corrosion, erosion, scaling, etc.. The most
appropriate water treatment must be determined locally, according to the type of system and water characteristics. The
manufacturerisnotresponsiblefordamagetoormalfunctioningofequipmentcausedbyimproperlytreatedwater.
22/31
OPERATING LIMITS
23/31
DIMENSIONAL DRAWING
LEGEND
1.ELECTRICALPANEL
2.POWERSUPPLYCABLEENTRY
3.EVAPORATORWATERINLET
4.EVAPORATORWATEROUTLET
5.CONDENSERWATERINLET
6.CONDENSERWATEROUTLET
Unitdimensionsbelowareinmm
MODEL
EWWD600VZSSA1
EWWD700VZSSA1
EWWD760VZSSA1
EWWD890VZSSA1
EWWDC10VZSSA1
1179
1179
1179
1219
1303
3634
3634
3634
3510
3822
2122
2122
2122
2292
2487
830
830
830
999
1013
431
431
431
431
485
965
965
965
981
1101
270
270
270
340
292
232
232
232
135
326
185
185
185
205
150
168.3
168.3
168.3
219.1
219.1
139.7
139.7
139.7
168.3
219.1
3170
3170
3170
3170
3170
490
490
490
550
670
24/31
DIMENSIONAL DRAWING
LEGEND
1.ELECTRICALPANEL
2.POWERSUPPLYCABLEENTRY
3.EVAPORATORWATERINLET
4.EVAPORATORWATEROUTLET
5.CONDENSERWATERINLET
6.CONDENSERWATEROUTLET
Unitdimensionsbelowareinmm
MODEL
EWWD450VZXSA1
EWWD500VZXSA1
EWWD610VZXSA1
EWWD710VZXSA1
EWWD800VZXSA1
EWWD900VZXSA1
EWWDC11VZXSA1
1179
1179
1179
1219
1877
1303
1303
3634
3634
3490
3510
3510
3822
3822
2093
2093
2122
2234
2234
2487
2487
828
828
830
762
762
1013
1013
431
431
431
431
431
485
485
965
965
965
981
981
1101
1101
270
270
270
340
340
292
292
232
232
135
135
135
326
326
185
185
185
205
205
150
150
168.3
168.3
219.1
219.1
219.1
219.1
219.1
139.7
139.7
139.7
168.3
168.3
219.1
219.1
3170
3170
3170
3170
3170
3170
3170
490
490
550
550
550
670
670
25/31
DIMENSIONAL DRAWING
LEGEND
1.ELECTRICALPANEL
2.POWERSUPPLYCABLEENTRY
3.EVAPORATORWATERINLET
4.EVAPORATORWATEROUTLET
5.CONDENSERWATERINLET
6.CONDENSERWATEROUTLET
Unitdimensionsbelowareinmm
MODEL
EWWD505VZPSA1
EWWD715VZPSA1
1179
1276
3490
3822
2093
2429
757
822
431
485
965
1101
270
292
135
326
185
150
219.1
219.1
139.7
219.1
3170
3170
550
670
EWWD910VZPSA1
1303
3822
2487
1013
485
1101
1101
326
150
219.1
219.1
3170
670
26/31
INSTALLATION NOTES
Installation Notes
Warning Installationandmaintenanceoftheunitmustbeperformedonlybyqualifiedpersonnelwhohaveknowledgewith
localcodesandregulations,andexperiencewiththistypeofequipment.Mustbeavoidedtheunitinstallationinplacesthat
couldbeconsidereddangerousforallthemaintenanceoperations.
Handling Avoid bumping and/or jolting during loading/unloading unit from the truck and moving it. Secure the unit inside
thetrucktopreventitfrommovingand causingdamages.Donotallowanypart oftheunittofallduringtransportation or
loading/unloading.
Use extreme caution when handling the unit to prevent damage to the control or the refrigerant piping. The unit mustbe
lifted by attaching cables or chains at the lifting holes in each corner. For more information please refer to the unit
InstallationManual.
Location Unitisdesignedforindoorinstallationonly.Theunitmustbemountedonaleveledbaseofconcreteorsteel.The
unitmustbeinstalledonarobustandperfectlyleveledfoundation;itmightbenecessarytouseweightdistributionbeams.
Rubber mounts/pads as well as vibration isolators in all water piping connected to the chiller are recommended to avoid
transmissionofvibrationandnoise.
Space requirements Every side of the machine must be accessible for all post installation maintanance activities. The
minimumspacerequiredisshownonthefollowingdrawing:
Acoustic protection When noise level must meet special requirements, it is necessary to pay the maximum attention to
ensuretheperfectinsulationoftheunitfromthesupportbasebyapplyingappropriateanti-vibrationdevicesontheunit,on
thewaterpipesandontheelectricalconnections.
Storage Theenvironmentconditionshavetobeinthefollowinglimits:
-Maximumambienttemperature50C
-Minimumambienttemperature:-20C
-Maximumrelativehumidity:95%notcondensing
Storagebelowtheminimumtemperaturemaycausedamagetocomponents.Storageabovethemaximumtemperature
causesopeningofsafetyvalves.Storageincondensingatmospheremaydamageelectroniccomponents
27/31
TECHNICAL SPECIFICATIONS
Technical Specifications
General ThechillerwillbedesignedandmanufacturedinaccordancewiththefollowingEuropeandirectives:
-Constructionofpressurevessel2014/68/EU
-MachineryDirective2006/42/EC
-LowVoltage2014/35/EU
-ElectromagneticCompatibility2014/30/EU
-Electrical&SafetycodesEN60204-1/EN61439-1/EN61439-2
-Manufacturing&QualityStandardsUNIENISO9001:2008
-EnvironmentalManagementSystemUNIENISO14001:2004
-Health&SafetyManagementSystemBSOHSAS18001:2007
To avoid any losses, the unit will be tested at full load in the factory (at the nominal working conditions and water
temperatures). The chiller will be delivered to the job site completely assembled and charged with refrigerant and oil. The
installationofthechillermustcomplywiththemanufacturersinstructionsforriggingandhandlingequipment.
Theunitwillbeabletostartupandoperate(asstandard)atfullloadwith:
-evaporatorleavingfluidtemperaturebetween...............Cand...............C
-condenserleavingfluidtemperaturebetween...............Cand...............C
Refrigerant OnlyHFC134acanbeused.
Performance Chillershallsupplythefollowingperformances:
-Numberofchiller(s):unit(s)
-Coolingcapacityforsinglechiller:kW
-Powerinputforsinglechillerincoolingmode:kW
-Evaporatorheatexchangerenteringwatertemperatureincoolingmode:C
-Evaporatorheatexchangerleavingwatertemperatureincoolingmode:C
-Evaporatorheatexchangerwaterflow:l/s
-Condenserheatexchangerenteringwatertemperatureincoolingmode:C
-Condenserheatexchangerleavingwatertemperatureincoolingmode:C
-Condenserheatexchangerwaterflow:l/s
Operatingvoltage range should be400V 10%, 3ph, 50Hz(or 380V 10%, 3ph,60Hz), voltage unbalance maximum 3%,
withoutneutralconductorandshallonlyhaveonepowerconnectionpoint.
Unit description Sound level and vibrations Sound pressure level at 1 meter distance in free field, semispherical
conditions, shall not exceed dB(A). The sound pressure levels must be rated in accordance to ISO 3744. Vibration on
thebaseframeshouldnotexceed2mm/s.
Dimensions Unitdimensionsshallnotexceedfollowingindications:
Unitlength...............mm
Unitwidth...............mm
Unitheight...............mm
Compressors Theunitshallbeequippedwith:
-Semi-hermetic,single-screwtypewithonemainhelicalrotorandtwogaterotors.Thegaterotorswillbeconstructedofa
carbonimpregnatedengineeredcompositematerial.Thegaterotorsupportswillbeconstructedofcastiron.
-Compressors rotational speedshall be continuously adjustedby means of inverter(stepless regulation) allowing accurate
watertemperaturecontrolandefficientcapacitymodulation.
- Compressor shall be able to adapt the discharge pressure of the refrigerant to any operating conditions by means of
variablevolumeratiosystem.
- Refrigerant system differential pressure shall provide oil injection on all moving compressor parts to correctly lubricate
them.Electricaloilpumplubricatingsystemisnotacceptable.
28/31
TECHNICAL SPECIFICATIONS
-The compressors oil cooling must be realized, whennecessary, by refrigerant liquid injection. External oil cooling system
willnotbeaccepted.
-Theoilseparatorshallbeintegratedwithinthecondenserandshallnotrequireoilpump
-Thecompressorshallbedirectdriventype,withoutgeartransmissionbetweenthescrewandtheelectricalmotor.
- Compressor shall be equipped with two thermal protections realized by means of thermistors for high temperature
protection: one temperature sensor to protect electrical motor and another sensor to protect unit and lubricating oil from
highdischargegastemperature.
-Noanyoil-crankcaseheaterwillbeacceptedontheunit.
-Compressorshallbefullyfieldserviceable.
Evaporator The units shall be equipped with a flooded shell & tube evaporator with water flowing inside the tubes and
refrigerantboiling outside. Thetubes are enhanced formaximum heat transferand rolled into steeltube sheet and sealed.
Thetubesareindividuallyreplaceable.
-Theexternalshellshallbeinsulatedwithflexible,closedcellpolyurethaneinsulationmaterial(20-mmthick).
-ThewaterconnectionsshallbeVICTAULICtypeconnectionsasstandardtoensurequickmechanicaldisconnectionbetween
theunitandthehydronicnetwork.
-TheevaporatorwillbemanufacturedinaccordancetoPEDstandard(2014/68/EU).
-Thewatersideshallbedesignedfor10barofmaximumoperatingpressure;ventsanddrainshallbeprovided.
Condenser The unit shall be equipped with single-passcounter-flow shell & tube heat exchanger with water flowing inside
thetubesandrefrigerantcondensingoutside.
Thelowersideofthecondensershallbeprovidedwithsubcoolingsectionforimprovedunitperformances.Thetubesshallbe
enhancedformaximumheattransferandrolledintosteeltubesheetandsealed.Thetubesshallbeindividuallyreplaceable.
-ThewaterconnectionsshallbeVICTAULICtypeconnectionsasstandardtoensurequickmechanicaldisconnectionbetween
theunitandthehydronicnetwork.
-ThecondenserwillbemanufacturedinaccordancetoPEDstandard(2014/68/EU).
-Thewatersideshallbedesignedfor10barofmaximumoperatingpressure;ventsanddrainshallbeprovided.
-Theoilseparatingsectionshallbeintegratedwithinthecondenser.
Refrigerant circuit The unit shall have one or two independent refrigerant circuits and one variable frequency driver per
compressor(Inverter).
The circuit shall include as standard: electronic expansion device piloted by units microprocessor control, compressor
discharge shut-off valve, liquid line shut-off valve, sight glass with moisture indicator, replaceable filter drier, charging
valves,highpressureswitch,highandlowpressuretransducers,oilpressuretransducerandinsulatedsuctionline.
Condensation control The compressor automatically unloads when high condensing pressure is detected. This to prevent
theshutdownoftherefrigerantcircuit(shutdownoftheunit)duetoahigh-pressurefault.
Low sound unit configurations (on request) The chillershall beprovided withan acousticalcompressor enclosure. This
enclosure shall be realized with a light, corrosion resistant aluminum structure and metal panels. The compressor soundproofenclosureshallbeinternallyfittedwithflexible,multi-layer,highdensitymaterials.
-TheelectricalpanelshallbeIP54and(withthedoorsopened)internallyprotectedagainstpossibleaccidentalcontactwith
electricalcomponents(IP20).
-Themainpanelshallbefittedwithamainswitchinterlockeddoor.
-Thepowersectionwillincludecompressorsprotectiondevices,compressorsstartersandcontrolcircuitpowersupply.
Controller The controller will be installed as standard and it will be used to modify unit set-points and check control
parameters.
Adisplayinstalledontheoutsideofthecontrolpanelsdoorwillalloweasyaccesstochilleroperatingstatusincludingwater
temperaturesandrefrigerantpressuresandtemperatures.
A sophisticated software with predictive logic will select the most energy efficient combination of compressor load and
electronicexpansionvalvepositionkeepingstableoperatingconditionsandmaximizingchillerefficiencyandreliability.
29/31
TECHNICAL SPECIFICATIONS
Inadditiontonormaloperatingfunctionalities,unitcontrollerwilltakecorrectiveactionsincasethechilleroperatingoutside
recommendedworkingconditions.
Unit controller shall be able to protect critical unit components thanks to the signals received by the various unit sensors
(suchasmotortemperaturesensors,refrigerantandoilpressure/temperaturesensors,pressureswitches..etc..).
ControllermainfeaturesControllershallguaranteefollowingminimumfunctions:
-Optimizedmanagementofcompressorssteplesscapacitycontrolthroughinverterdrive.
-Displayofevaporatorentering/leavingwatertemperatures.
-Displayofcondenserentering/leavingwatertemperatures.
-Displayofrefrigerantcondensing/evaporatingtemperaturesandpressures.
-Regulationofleavingevaporatorwater(coolingmode)orcondenserwater(heatingmode).Temp.tolerance0,1C.
-Displayofcompressorworkinghoursandnumberofcompressorstarts.
-Re-startincaseofpowerfailure(automaticormanualdependingonfailuretype).
-Softload(optimizedmanagementofthecompressorloadduringthestart-up).
-Setpointreset.
-Master/Slaveoperation(upto4chillersconnected).
Controllershallguaranteefollowingminimumalarmssignaling:
-Phaseloss.
-Evaporatorwaterflowloss.
-Evaporatorwaterfreezingprotection.
-Externalalarm.
-Lowevaporatorrefrigerantpressure.
-Highrefrigerantpressure(transducer).
-Highrefrigerantpressure(switch).
-Lowpressureratio.
-Highrefrigerantdischargetemperature.
-Highoilpressuredifferential.
-Highmotortemperature.
High Level Communications Interface (on request) The chiller shall be able to communicate to BMS (Building Management
System)basedonthemostcommonprotocolssuchas:
-ModbusRTU
-LonWorks
-BacNetBTPcertifiedoverIPandMS/TP(class4)(Native)
-EthernetTCP/IP.
Master/SlavetheunitshallbeabletooperateinMaster/Slavemodeinordertobeconnectedwithothersimilarunit(upto
4). The master unit shall manage the slave units connected in series on the hydraulic plant with the aim of optimize the
runninghoursofeachcompressorandtobalancetheloadbetweentheunits.
30/31