Databook

Code:
PrintingDate:
WATERFL2C

Water Cooled Inverter Screw


Chillers
EWWD~VZ A
Nominalcapacityrange:449-1053kW
Bestperformancesatfullloadandpartloads
Fullflexibilitywith3efficiencyversionsandlownoiseoption
Designedforwideapplicationrangeandcompactfooptrint

Performance according to EN14511-1 (2013)

WEBCSS-Rev.10.1
01/08/2016
R1.0.0

FEATURES AND BENEFITS

Features and Benefits


Low operating cost High Flexibility and Reliability.The EWWD~VZ A isthe result of carefuldesign, aimed to optimize
the energy efficiency of the chiller and with the clear target to reduce operating costs. The chiller series features Daikin
designsinglescrewcompressordrivenbyinverter.Heatexchangersarefloodedtypeforoptimizedheattransfer.
TheEWWD~VZArangeisavailablewith3differentefficiencyversions:
-EWWD~VZASSSILVER:averageEER5,39(upto5,51)andaverageESEER7,35(upto7,52)
-EWWD~VZAXSGOLD:averageEER5,55(upto5,67)andaverageESEER8,01(upto8,22)
-EWWD~VZAPSPLATINUM:averageEER5,75(upto5,81)andaverageESEER8,29(upto8,48)
Thosethreeefficiencylevelscanbecombinedwithnumerousoptionsresultinginseveraldifferentavailableconfigurations.

Leading class efficiency. TheEWWD~VZAseriesisdesignedtoachieve leadingclassefficiencyatbothfullloadand part


loadoperations.

Compactness.The EWWD~VZA seriesis designed toachieve thesmallest possible footprintmaking theproduct the ideal
solutiontofitthoughthetightestdoorwaysandconsequentlytheperfectproductforreplacementprojects.

Application flexibility. TheEWWD~VZAseriescansatisfyalarge varietyofapplicationsnotlimitedtotraditional comfort


coolingbutalsodatacenters,brinewater,icestorageandhightemperatureheatpump(upto65C).

Outstanding reliability. Depending on capacity, the EWWD~VZ A series features one or two independent refrigerant
circuits in order to guarantee highest possible redundancy and simplified maintenance activities. Units are equipped with
rugged compressor design with advanced and robust composite compressor gate-rotors material. Units are factory tested
beforeshipmentforanon-sitetroublefreeoperation.

Stepless capacity control. Cooling capacity is controlled by means of inverter driving the compressor motor. Units are
enjoyinginfinitely variablecapacity controlfrom 100%load downto minimumcapacity whichis variabledepending on unit
model. No any mechanical unloading system is used. This advanced capacity control method allows the unit to perfectly
matchthecooling(orheating)loadandconsequentlyprovidingextremelyaccuratewatertemperaturecontrol.

Variable Volume Ratio. Compressors are enjoying the Variable Volume Ratio (VVR) technology. This innovative system
allowsthecompressortoadaptthedischargepressureoftherefrigeranttothespecificoperatingconditions.Inthisway,itis
possible to prevent energy losses deriving from under or over compression phenomena that are typical of traditional
compressortechnologies(withfixed volumeratio).Thereduction ofenergylossesinside compressorbringstoan increased
unitefficiency.

Future readiness. The EWWD~VZ A series is designed for R134a refrigerant in order to achieve the highest possible unit
efficiency.Additionallytothis,ithasbeendesignedtobecompatiblefordropinofnextgenerationrefrigerantswithlower
GWP.Daikinisatfulldisposaltoprovidefurtherinformationaboutthisspecificsubject.

Superior control logic. The EWWD~VZ A series is enjoying MicroTech III controller that provides an easy to use control
environment. The control logic is designed to provide highest efficiency performances and continuous operation. Easy
interfacewithLonWorks,Bacnet,TCP/IPorModbuscommunicationprotocols.

Quiet operation. Verylowsoundlevelsare achievedatpartloadsthanksto thereductionofcompressorrotational speed.


Compressorsoundproofcabinetoptionisavailabletofurtherreducesoundlevel.

Low starting current. No any current spike is experienced at start up thanks to inverter driven compressor motors. The
startingcurrentisalwayslowerthanfullloadcurrent(FLA).
Displacement power factor always > 0,95. Thanks to inverter driven compressors, the EWWD~VZ A series always
operateswithadisplacementpowerfactor>0,95allowingtoavoidpowerfactorpenaltiesanddecreasingelectricallossesin
cablesandtransformers.

2/31

FEATURES AND BENEFITS


Codes and Certifications. The EWWD~VZ A series is CE marked, complying with European directive in force concerning
manufacturingandsafety.Unitsaredesignedandmanufacturedinaccordancewithapplicableselectionsofthefollowing:
Constructionofpressurevessel2014/68/EU
MachineryDirective2006/42/EC
LowVoltage2014/35/EU
ElectromagneticCompatibility2014/30/EU
Electrical&SafetycodesEN60204-1/EN61439-1/EN61439-2
Manufacturing&QualityStandardsUNIENISO9001:2008
EnvironmentalManagementSystemUNIENISO14001:2004
Health&SafetyManagementSystemBSOHSAS18001:2007

AdditionalinformationrelatedtoF-GASRegulation(EU)No517/2014oftheEuropeanParliamentandoftheCouncilof16th
April2014onfluorinatedgreenhousegasesandrepealingRegulation(EC)No842/2006.

Note: Equipment contains fluorinated greenhouse gases. Actual refrigerant charge depends on the final unit construction,
detailscanbefoundontheunitnameplate.

3/31

GENERAL CHARACTERISTICS

General Characteristics

Cabinet and structure. Thecabinetismadeofgalvanizedsteelandpaintedtoprovidehighresistancetocorrosion.Coloris


IvoryWhite(Munsell code5Y7.5/1, RAL7044). Unitis fittedwitheyehook forlifting withropes andfor aneasy handling.
Theweightisuniformlydistributedalongthebasesprofilesforasimplifiedunitinstallation.

Inverter Driven Single Screw Compressor. The EWWD~VZ A series is equipped with latest Daikin design Single Screw
Compressors. This technology is enjoying highly balanced loads resulting in reduced mechanical stress for the main
components. Lifetime and reliability are in this way improved and, at the same time, vibrations and noise emissions are
reduced.ThehighvolumetricefficiencyofDaikinsinglescrewcompressorsmakesthemtheidealsolutionforvariablespeed
applications.ThankstoinvertertechnologytheEWWD~VZAscrewcompressorsareabletomatchthecoolingoutputofthe
unit to the actual load requirement. Compressors rotational speed is continuously adjusted (stepless regulation) allowing
excellentwatertemperaturecontrolandefficientcapacitymodulation.
Compressors are enjoying the Variable Volume Ratio (VVR) technology. This innovative system allows the compressor to
adapt the discharge pressure of the refrigerant to the specific operating conditions. In this way, it is possible to prevent
energy losses deriving from under or over compression phenomena that are typical of traditional compressor technologies
(withfixedvolumeratio).Thereductionofenergylossesinsidecompressorbringstoanincreasedunitefficiency.
OilseparatorisintegratedwithintheCondensershell.
Refrigerant. The EWWD~VZ A series is designed for R134a refrigerant in order to achieve the highest possible unit
efficiency.Additionallytothis,ithasbeendesignedtobecompatiblefordropinofnextgenerationrefrigerantswithlower
GWP.Daikinisatfulldisposaltoprovidefurtherinformationaboutthisspecificsubject.
Evaporator. High efficiency flooded type shell and tube heat exchanger. Evaporator tubes have been selected in order to
achievethe highestheat transfer.Optimized nucleateboiling is guaranteedby specificallydesigned cavitieson the external
tubes surface. Internal tubes surface area has helical type design. The extremely high heat transfer coefficient allows the
reductionofthetemperaturedifferencebetweenchilledwaterandrefrigerantthusresultinginhigheroverallunitefficiency.
Theevaporatorisdesignedaccordingto2014/68/EUEuropeanstandard(Constructionofpressurevessel).Thewatersideis
designed for 10 bar maximum operating pressure; vents and drain are provided. Water connections are Victaulic type as
standard, flanged connections are available as optional. As standard unit evaporator is two water passes design. Nonstandard applications may require different number of water passes (contact Factory for further information). As standard,
thermalinsulation(20mmthickness)isfittedontheexternalevaporatorsurfacearea.
Condenser.Highefficiencyshellandtubetypeheatexchanger.Condensertubeshavebeenselectedinordertoachievethe
highestheattransfer. Optimizedcondensation isachieved byfinnedtype tubeexternal surfacearea. Internaltubes surface
areahashelicaltypedesign.Theextremelyhighheattransfercoefficientallowsthereductionofthetemperaturedifference
betweencondenserwaterandrefrigerantthusresultinginhigheroverallunitefficiency.
Thecondenserisdesignedaccordingto2014/68/EUEuropeanstandard(Constructionofpressurevessel).Thewatersideis
designed for 10 bar maximum operating pressure; vents and drain are provided. Water connections are Victaulic type as
standard, flanged connections are available as optional. Unit condenser is single water pass with counter-flow design for
optimizeheattransferbetweenwaterandrefrigerant.
WithinCondensershell,specificsectionisdedicatedtotheoilseparation.

Electronic expansion valve.Unitisequippedwithlatesttechnologyelectronicexpansionvalvetoachieveprecisecontrolof


refrigerantmassflow.Astodayssystemrequiresimprovedenergyefficiency,tightertemperaturecontrolandwideoperating
range,theapplicationofelectronicexpansionvalveistherecommendedsolution.Electronicexpansionvalveprovidesunique
features such as short opening and closing times, high resolution, positive shut-off function eliminating the need for
additionalsolenoidvalve,continuousmodulationofmassflowwithreducedstressintherefrigerantcircuit.
Refrigerant Circuit.Eachunithasoneortwoindependentrefrigerantcircuitsandeachofthemincludes:

-Singlescrewcompressorinverterdriven
-Refrigerantcharge
-Independentrefrigerantcircuitintotheevaporator
-Watercooledcondenser
-Electronicexpansionvalve
-Liquidlineshutoffvalve
-Sightglasswithmoistureindicator
-Highpressureswitch
-Highpressuretransducer
-Lowpressuretransducer
-Oilpressuretransducer
-Suctiontemperaturesensor
Electrical Panel.PowerandcontrolsectionsarelocatedintothemainelectricalpanelIP54designed.Themainpaneldoors
areinterlockedto themainswitch (standard)in orderguaranteesafe operationwhen doorsareopened. Thepower section
includescompressorprotectiondevicesandcompressorstarters(invertertype).

4/31

GENERAL CHARACTERISTICS

MicroTech III Controller.TheMicroTechIIIcontrolsystemconsistsofamicroprocessor-basedcontrollerandanumberof


extensionmodules,whichvarydependingontheunitsizeandconfiguration.Thesystemprovidesthemonitoringandcontrol
functionsrequiredforanefficientandtroublefreeoperationofthechiller.
A display installed on the outside of the control panels door allows easy access to chiller operating status including water
temperaturesandrefrigerantpressuresandtemperatures.
Asophisticatedsoftwarewithpredictivelogicselectsthemostenergyefficientcombinationofcompressorloadandelectronic
expansionvalvepositionkeepingstableoperatingconditionsandmaximizingchillerefficiencyandreliability.
In addition to normal operating functionalities, MicroTech III controller will take corrective actions in case the chiller
operatingoutsiderecommendedworkingconditions.
Unitcontrollerisabletoprotectcriticalunitcomponentsthankstothesignalsreceivedbythevariousunitsensors(suchas
motortemperaturesensors,refrigerantandoilpressure/temperaturesensors,pressureswitches..etc..).

Maincontrolfeaturesare(formoreinformationrefertoUnitControlManual):

-Optimizedmanagementofcompressorssteplesscapacitycontrolthroughinverterdrive.
-Displayofevaporatorentering/leavingwatertemperatures.
-Displayofcondenserentering/leavingwatertemperatures.
-Displayofrefrigerantcondensing/evaporatingtemperaturesandpressures.
- Regulation of leaving evaporator water (cooling mode) or condenser water (heating mode). Temperature tolerance
0,1C.
-Displayofcompressorworkinghoursandnumberofcompressorstarts.
-Re-startincaseofpowerfailure(automaticormanualdependingonfailuretype).
-Softload(optimizedmanagementofthecompressorloadduringthestart-up).
-Setpointreset.
-Master/Slaveoperation(upto4chillersconnected).

Alarmssignaling(formoreinformationrefertoUnitControlManual):

-Phaseloss.
-Evaporatorwaterflowloss.
-Evaporatorwaterfreezingprotection.
-Externalalarm.
-Lowevaporatorrefrigerantpressure.
-Highrefrigerantpressure(transducer).
-Highrefrigerantpressure(switch).
-Lowpressureratio.
-Highrefrigerantdischargetemperature.
-Highoilpressuredifferential.
-Highmotortemperature.

Alarm logging: when alarm occurs, the alarm type, date, time and main unit working parameters are recorder and stored
intothecontrollermemory.Thelast25alarmsoccurredarestored.

Regulation type: Proportional-Integral-Derivative (PID) type based on the evaporator leaving water temperature set point
(coolingmode)orbasedonthecondenserleavingwatertemperaturesetpoint(heatingmode).

Connection to BMS: MicroTech III controlled is capable to communicate with BMS systems based on the most common
protocolssuchas:Modbus,LonWorks,BacNetIPandMS/TP(class4),EthernetTCP/IP.Communicationcards(optional)are
tobeselectedaccordingtotherequiredcommunicationprotocol.

5/31

GENERAL CHARACTERISTICS

Nomenclature

6/31

OPTIONS

Standard Options
Evaporator Victaulic kit (option 20 - STANDARD). Victaulicjointsandcounter-pipes.

Evaporator water design pressure 10 bar (option 27 STANDARD).

20 mm evaporator insulation (option 29 STANDARD). Thermalinsulationoftheevaporatorshell.

Condenser Victaulic kit (option 36 - STANDARD). Victaulicjointsandcounter-pipes.


Condenser water design pressure 10 bar (option 47a STANDARD).
Evaporator two passes (option 103a STANDARD). Two passes water side design. Refer to unit dimensional drawing
forwaterINLET/OUTLETdetails.
Condenser single pass (option 51 STANDARD). Single pass water side design. Refer to unit dimensional drawing for
waterINLET/OUTLETdetails.Waterconnectionscannotbereversed.
Electronic expansion valve (option 60 STANDARD).
Double set point (option 10 STANDARD). Possibility to pre-set two different chilled water temperature set points
(coolingmode)ortwodifferenthotwatertemperaturesetpoints(heatingmode).
Compressor thermal overload relays (option 11 STANDARD). Functionality Included in the compressor inverter
device.
Phase monitor (option 13 STANDARD). Functionality Included in the compressor inverter device. Protect the unit in
caseofphaselossorphasereversal.
Inverter compressor starter (option 14 STANDARD). Electronic device used as starter and for compressor capacity
control.
Under/over voltage control (option 15 STANDARD). FunctionalityIncludedinthecompressorinverterdevice.
Hour run meter (option 68 STANDARD). Standardfunctionalityofunitcontroller.
General fault contactor (option 69 STANDARD). Standardfunctionalityofunitcontroller.
Set point reset, demand limit and alarm from an external device (option 90 STANDARD). Standardfunctionalityof
unitcontroller.Setpointreset:possibilitytore-setthewatertemperaturesetpointbymeansofa4-20mAsignal.Demand
Limit:possibilitytolimitunit capacitybymeansof4-20 mAsignal.Alarmfromexternal device:unitcontrollercapability to
receiveanexternalalarm signal.Theuser candecidewhetherthis alarmsignalwill stoptheunitcontroller ornot.Refer to
unitcontrolmanualformoreinformation.
Main switch interlocked doors (option 97 STANDARD). Electrical panels doors are interlocked with the main switch
isolatorforsafeoperation.
Master/Slave (option 128 STANDARD). Standard controller functionality allowing to connect up to 4 units and
providingbasicsequencingfunctionalitiessuchas:balancingofworkinghoursofunit&compressors;balancingofunitloads
amongst connected units. An additional probe (NTC10K, not provided by Factory) must be installed on the common water
headerandconnectedtothemasterunit.
Double pressure relief valve with diverter (option 91 STANDARD).

7/31

OPTIONS

Options on request

Heat Pump Version including Pursuit Mode (option 07a ON REQUEST). Reversibility on the water side. Unit
capability to follow two different set points (cooling mode or heating mode). During cooling mode operation, unit
microprocessorisfollowingevaporatorleavingwatertemperaturesetpoint.Whenthemachineisswitchedtoheatingmode
operation, the unit microprocessor is following condenser leaving water temperature set point. Cooling or heating mode
operation can be selected by means of a dedicated switch installed on the unit electrical panel. If, communication card is
selected,coolingorheatingmodeoperationcanbemanagedbyBMS.HeatPumpVersionoptionincludes20mmcondenser
insulation(option33).
In case pursuit mode operation is enabled via Microtech III, unit controller will try to follow bot set points (cooling and
heating). When the first set point is satisfied, either the cold or the hot one, the unit will maintain that set point. Ideal
applications are when cooling and heating loads are balanced. Pursuit mode operation is not recommended in case of
unbalancedloads(e.g.80%ofnominalcoolingloadand20%ofnominalheatingload).
Brine Version (option 08 ON REQUEST). Required in case of unit operation with chilled water temperatures below
+4C. Unit will be fitted with double thermal insulation on evaporator (40 mm thickness). Brine Version option includes
compressorthermalinsulationoption(option146).Refertotheunitoperatingenvelopeformoreinformationaboutminimum
allowedevaporatorleavingwatertemperatures.
Evaporator double flanges kit (option 104 ON REQUEST). Victaulic-to-flange adapter (shipped loose and including
counter-flanges,gasketsandbolts).
Condenser double flanges kit (option 26 ON REQUEST). Victaulic-to-flange adapter (shipped loose and including
counter-flanges,gasketsandbolts).
20 mm condenser insulation (option 33 ON REQUEST). Thermalinsulationofthecondensershell(includedwithoption
07aHeatPumpVersionandwithoption111Hightemperaturekit).
Discharge line shut off valve (option 61 ON REQUEST).Installedonthedischargelineofthecompressortofacilitate
maintenanceoperations.
Suction line shut off valve (option 62 ON REQUEST). Installed on the suction line of the compressor to facilitate
maintenanceoperations.
High-pressure side manometers (option 63 ON REQUEST).
Low-pressure side manometers (option 64 ON REQUEST).
Compressor soundproof system (option 76-b ON REQUEST). High performance soundproof cabinet installed around
compressorandspecificallydesignedinordertominimizeunitsoundlevels.
High temperature kit (option 111 ON REQUEST). Requiredincaseofcondenserleavingwatertemperaturehigherthan
approximately 48C (note: this limit may change depending on evaporator water temperature and on specific unit
version/size. Refer to operating envelope and to chiller selection software for detailed information). Specifically selected
componentsareusedinordertoallowtheunittooperateatsuchconditions.Unitdimensionsandweightmaychangefrom
standard.Hightemperaturekitoptionincludes20mmcondenserinsulation(option33)andheatpumpversion(option07a).
Refrigerant leak detection (option 121 ON REQUEST). Electronic device (shipped loose) for automatic detection of
refrigerant leak. The leak detection device should be installed within the machinery room in the most appropriate location
(refertotheleakdetection deviceinstallationmanual).When leakaboveapre-set concentrationofrefrigerant(2000 ppm)
isdetected,signalis senttounitcontroller (aspecificalarmis visualizedontheunit microprocessorsdisplay).The Factory
doesnotsupplyinterconnectingcablesbetweenleakdetectiondeviceandunitcontroller.
Knock down electrical panel (option 147 ON REQUEST). Electrical panel dismounted from the unit and shipped
separately.
Compressor thermal insulation (option 146 ON REQUEST). 20 mm thermal insulation of compressor suction side.
(Includedwithoption08Brineversion).
Cu-Ni 90-10 condenser tubes (option 50 ON REQUEST). Condenser tubes made of Cu-Ni 90-10 material and Cu-Ni
90-10 tube sheets cladding. Epoxy ceramic coating of water headers and sacrificial anodes. Unit performances may differ
from standard. Contact local Daikin office for more details. When selecting option 50, condenser double flanges kit option
(option26)mustbeselectedaswell.
Evaporator 3 passes (option 103b ON REQUEST). Three passes water side evaporator. May be required in case of
evaporatorwatertemperaturedifference higherthan8C.Unit performancesmaydifferfrom standard.Contactlocal Daikin
officeformoredetails.
Evaporator single pass (option 103 ON REQUEST). Single pass water side evaporator. May be required in case of
evaporator water temperature difference lower than 4C. Unit performances may differ from standard. Contact local Daikin
officeformoredetails.

8/31

OPTIONS
Energy meter including current limit (option 16a ON REQUEST). Electronic device installed within unit electrical
panel. Measures and display supply line individual phase voltage and current, active and reactive power input, active and
reactive energy consumption. An integrated RS485 module allows Modbus communication to BMS. It includes current limit
functionality.
Evaporator flow switch (option 58 ON REQUEST). Paddle flow switchshipped loose.Refer tounit installation manual
formoredetails.
Condenser flow switch (option 59 ON REQUEST). Paddle flow switch shipped loose. Refer to unit installation manual
formoredetails.
Compressor circuit breakers (option 95 ON REQUEST). Protection device including protection from current overload
andovercurrent.Incasethisoptionisselected,compressorfusesareremoved.
Ground fault relay (option 102 ON REQUEST). Unitshutsdownincaseofgroundfaultisdetected.
Rapid restart (option 110 ON REQUEST). Ideal solution for those critical applications that cannot afford the loose of
coolingorheating.Incaseofpowerfailureunitwillre-startasfastas15secondsfrompowerrestoration.Unitwillreachfull
loadwithin160secondsand180secondsrespectivelyforsinglecompressoranddualcompressorsunitmodels.Refertounit
controlmanualformoreinformationaboutthisoption.
Automatic transfer switch free standing (option 149 ON REQUEST). Free standing panel separate from the unit
allowing to connect two separate power supply lines (e.g. main supply line and secondary line from backup generator). In
caseoffailureofmainpowersupplyline,theautomatictransferswitchdevicewillautomaticallyswitchtothesecondaryline
ifpowerisdetected.
Inverter EN61800-3 Class C2 compliant (option 150 ON REQUEST). Additional RFI filters on the unit power supply
line.Reduces electromagnetic interferences.Increases the inverterimmunity level accordingto residential environment and
allowsitscompliancywithemissionslevelrequiredinC2category.
Rubber pads (option 152 ON REQUEST). Rubber pad mounts to be installed under the unit base frame during
installation.
Container kit (option 71 ON REQUEST).
Transport kit (option 112 ON REQUEST).

9/31

TECHNICAL SPECIFICATIONS
EWWD~VZ-SS
MODEL

EWWD600V EWWD700V EWWD760V EWWD890V EWWDC10V


ZSSA1
ZSSA1
ZSSA1
ZSSA1
ZSSA1

COOLING PERFORMANCE
Capacity-Cooling
Capacitycontrol-Type
Capacitycontrol-Minimumcapacity
Unitpowerinput-Cooling
EER
ESEER
IPLV

kW

610
Stepless
20
110
5.51
7.25
9.08

704
Stepless
20
132
5.31
7.30
9.27

757
Stepless
20
142
5.31
7.40
9.20

894
Stepless
20
162
5.52
7.27
9.22

1,039
Stepless
20
196
5.28
7.52
9.40

IW
GPSS

IW
GPSS

IW
GPSS

IW
GPSS

IW
GPSS

mm
mm
mm

2120
1180
3460

2120
1180
3460

2120
1180
3460

2290
1240
3690

2480
1340
3830

kg
kg

2892
2977

2928
3033

2941
3053

3451
3611

4237
4488

FloodedS&T
Water
0
88
12
7
29.3
80.0
CC

FloodedS&T
Water
0
88
12
7
33.8
106
CC

FloodedS&T
Water
0
96
12
7
36.3
89.0
CC

FloodedS&T
Water
0
134
12
7
42.9
98.0
CC

FloodedS&T
Water
0
156
12
7
49.9
104
CC

S&T
Water
0
81
30
35
34.5
54.0

S&T
Water
0
102
30
35
40.2
41.0

S&T
Water
0
102
30
35
43.1
46.0

S&T
Water
0
126
30
35
50.7
44.0

S&T
Water
0
217
30
35
59.4
33.0

%
kW

CASING
Colour*
Material*
DIMENSIONS
Height
Width
Length
WEIGHT
UnitWeight
OperatingWeight
HEAT EXCHANGER - EVAPORATOR
Type*
Fluid
FoulingFactor
WaterVolume
Watertemperaturein
Watertemperatureout
Waterflowrate
Waterpressuredrop
Insulationmaterial*

l
C
C
l/s
kPa

HEAT EXCHANGER - CONDENSER


Type*
Fluid
FoulingFactor
WaterVolume
Watertemperaturein
Watertemperatureout
Waterflowrate
Waterpressuredrop

l
C
C
l/s
kPa

COMPRESSOR
Type
Oilcharge
Quantity

l
No.

Inverter
Inverter
Inverter
Inverter
Inverter
DrivenSingle DrivenSingle DrivenSingle DrivenSingle DrivenSingle
Screw
Screw
Screw
Screw
Screw
36.0
36.0
36.0
50.0
50.0
1
1
1
1
1

SOUND LEVEL**
SoundPower-Cooling
SoundPressurelevel@1mdistanceCooling

dB(A)

101

105

105

105

108

dB(A)

82

86

86

86

89

kg
No.

R134a
100
1

R134a
110
1

R134a
110
1

R134a
170
1

R134a
180
1

mm
mm

141.3
168.3

141.3
168.3

141.3
168.3

168.3
219.1

219.1
219.1

REFRIGERANT CIRCUIT
Refrigeranttype
Refrigerantcharge
N.ofcircuits
PIPING CONNECTIONS
Evaporatorwaterinlet/outlet
Condenserwaterinlet/outlet

All the perfrormances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0C;
condenser 30.0/35.0C, unit at full load operation; operating fluid: Water; fouling factor = 0. (*) IW: Ivory White; GPSS: Galvanized and
Painted Steel Sheet; S&T: Single Pass Shell & Tube; CC:Closed Cell; (**) The values are according to ISO 3744 and are referred to: evaporator
12/7 C, condenser 30/35 C, full load operation.

10/31

TECHNICAL SPECIFICATIONS
EWWD~VZ-XS
MODEL

EWWD450V EWWD500V EWWD610V EWWD710V EWWD800V EWWD900V


ZXSA1
ZXSA1
ZXSA1
ZXSA1
ZXSA1
ZXSA1

COOLING PERFORMANCE
Capacity-Cooling
Capacitycontrol-Type
Capacitycontrol-Minimumcapacity
Unitpowerinput-Cooling
EER
ESEER
IPLV

kW

449
Stepless
20
81.1
5.53
7.51
9.42

501
Stepless
20
89.6
5.58
7.92
9.59

613
Stepless
20
108
5.64
8.10
9.52

713
Stepless
20
128
5.54
8.20
9.66

793
Stepless
20
146
5.43
8.22
9.64

901
Stepless
20
158
5.67
7.92
9.48

IW
GPSS

IW
GPSS

IW
GPSS

IW
GPSS

IW
GPSS

IW
GPSS

mm
mm
mm

2090
1180
3460

2120
1180
3460

2120
1180
3690

2230
1220
3690

2290
1240
3690

2480
1340
3830

kg
kg

2968
3098

2911
3006

3102
3274

3470
3648

3451
3611

4257
4518

FloodedS&T
Water
0
70
12
7
21.6
89.0
CC

FloodedS&T
Water
0
88
12
7
24.0
63.0
CC

FloodedS&T
Water
0
136
12
7
29.4
59.0
CC

FloodedS&T
Water
0
134
12
7
34.2
63.0
CC

FloodedS&T
Water
0
134
12
7
38.0
55.0
CC

FloodedS&T
Water
0
168
12
7
43.2
67.0
CC

S&T
Water
0
81
30
35
25.4
31.0

S&T
Water
0
92
30
35
28.3
28.0

S&T
Water
0
126
30
35
34.7
22.0

S&T
Water
0
145
30
35
40.4
20.0

S&T
Water
0
126
30
35
45.2
24.0

S&T
Water
0
217
30
35
50.9
25.0

%
kW

CASING
Colour*
Material*
DIMENSIONS
Height
Width
Length
WEIGHT
UnitWeight
OperatingWeight
HEAT EXCHANGER - EVAPORATOR
Type*
Fluid
FoulingFactor
WaterVolume
Watertemperaturein
Watertemperatureout
Waterflowrate
Waterpressuredrop
Insulationmaterial*

l
C
C
l/s
kPa

HEAT EXCHANGER - CONDENSER


Type*
Fluid
FoulingFactor
WaterVolume
Watertemperaturein
Watertemperatureout
Waterflowrate
Waterpressuredrop

l
C
C
l/s
kPa

COMPRESSOR
Type
Oilcharge
Quantity

l
No.

Inverter
Inverter
Inverter
Inverter
Inverter
Inverter
DrivenSingle DrivenSingle DrivenSingle DrivenSingle DrivenSingle DrivenSingle
Screw
Screw
Screw
Screw
Screw
Screw
32.0
32.0
36.0
36.0
50.0
50.0
1
1
1
1
1
1

SOUND LEVEL**
SoundPower-Cooling
SoundPressurelevel@1mdistanceCooling

dB(A)

97

99

101

105

105

105

dB(A)

78

80

82

86

86

86

kg
No.

R134a
95
1

R134a
95
1

R134a
100
1

R134a
110
1

R134a
170
1

R134a
170
1

mm
mm

141.3
168.3

141.3
168.3

141.3
219.1

168.3
219.1

168.3
219.1

219.1
219.1

REFRIGERANT CIRCUIT
Refrigeranttype
Refrigerantcharge
N.ofcircuits
PIPING CONNECTIONS
Evaporatorwaterinlet/outlet
Condenserwaterinlet/outlet

All the perfrormances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0C;
condenser 30.0/35.0C, unit at full load operation; operating fluid: Water; fouling factor = 0. (*) IW: Ivory White; GPSS: Galvanized and
Painted Steel Sheet; S&T: Single Pass Shell & Tube; CC:Closed Cell; (**) The values are according to ISO 3744 and are referred to: evaporator
12/7 C, condenser 30/35 C, full load operation.

11/31

TECHNICAL SPECIFICATIONS
EWWD~VZ-XS
MODEL

EWWDC11V
ZXSA1

COOLING PERFORMANCE
Capacity-Cooling
Capacitycontrol-Type
Capacitycontrol-Minimumcapacity
Unitpowerinput-Cooling
EER
ESEER
IPLV

kW
%
kW

1,053
Stepless
20
192
5.46
8.17
9.58

CASING
Colour*
Material*

IW
GPSS

DIMENSIONS
Height
Width
Length

mm
mm
mm

2480
1340
3830

kg
kg

4552
4860

WEIGHT
UnitWeight
OperatingWeight
HEAT EXCHANGER - EVAPORATOR
Type*
Fluid
FoulingFactor
WaterVolume
Watertemperaturein
Watertemperatureout
Waterflowrate
Waterpressuredrop
Insulationmaterial*

l
C
C
l/s
kPa

FloodedS&T
Water
0
199
12
7
50.4
58.0
CC

HEAT EXCHANGER - CONDENSER


Type*
Fluid
FoulingFactor
WaterVolume
Watertemperaturein
Watertemperatureout
Waterflowrate
Waterpressuredrop

l
C
C
l/s
kPa

S&T
Water
0
241
30
35
59.9
25.0

l
No.

Inverter
DrivenSingle
Screw
50.0
1

dB(A)

108

dB(A)

89

kg
No.

R134a
180
1

mm
mm

219.1
219.1

COMPRESSOR
Type
Oilcharge
Quantity
SOUND LEVEL**
SoundPower-Cooling
SoundPressurelevel@1mdistanceCooling
REFRIGERANT CIRCUIT
Refrigeranttype
Refrigerantcharge
N.ofcircuits
PIPING CONNECTIONS
Evaporatorwaterinlet/outlet
Condenserwaterinlet/outlet

All the perfrormances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0C;
condenser 30.0/35.0C, unit at full load operation; operating fluid: Water; fouling factor = 0. (*) IW: Ivory White; GPSS: Galvanized and
Painted Steel Sheet; S&T: Single Pass Shell & Tube; CC:Closed Cell; (**) The values are according to ISO 3744 and are referred to: evaporator
12/7 C, condenser 30/35 C, full load operation.

12/31

TECHNICAL SPECIFICATIONS
EWWD~VZ-PS
MODEL

EWWD505V EWWD715V EWWD910V


ZPSA1
ZPSA1
ZPSA1

COOLING PERFORMANCE
Capacity-Cooling
Capacitycontrol-Type
Capacitycontrol-Minimumcapacity
Unitpowerinput-Cooling
EER
ESEER
IPLV

kW

505
Stepless
20
87.5
5.77
8.15
9.61

718
Stepless
20
126
5.66
8.48
9.68

908
Stepless
20
156
5.81
8.25
9.57

IW
GPSS

IW
GPSS

IW
GPSS

mm
mm
mm

2090
1180
3690

2430
1330
3690

2480
1340
3830

kg
kg

3247
3375

4082
4349

4346
4660

FloodedS&T
Water
0
96
12
7
24.2
55.0
CC

FloodedS&T
Water
0
168
12
7
34.4
42.0
CC

FloodedS&T
Water
0
199
12
7
43.5
44.0
CC

S&T
Water
0
126
30
35
28.5
15.0

S&T
Water
0
217
30
35
40.6
17.0

S&T
Water
0
241
30
35
51.2
19.0

%
kW

CASING
Colour*
Material*
DIMENSIONS
Height
Width
Length
WEIGHT
UnitWeight
OperatingWeight
HEAT EXCHANGER - EVAPORATOR
Type*
Fluid
FoulingFactor
WaterVolume
Watertemperaturein
Watertemperatureout
Waterflowrate
Waterpressuredrop
Insulationmaterial*

l
C
C
l/s
kPa

HEAT EXCHANGER - CONDENSER


Type*
Fluid
FoulingFactor
WaterVolume
Watertemperaturein
Watertemperatureout
Waterflowrate
Waterpressuredrop

l
C
C
l/s
kPa

COMPRESSOR
Type
Oilcharge
Quantity

l
No.

Inverter
Inverter
Inverter
DrivenSingle DrivenSingle DrivenSingle
Screw
Screw
Screw
36.0
40.0
50.0
1
1
1

SOUND LEVEL**
SoundPower-Cooling
SoundPressurelevel@1mdistanceCooling

dB(A)

99

105

105

dB(A)

80

86

86

kg
No.

R134a
100
1

R134a
150
1

R134a
180
1

mm
mm

141.3
219.1

219.1
219.1

219.1
219.1

REFRIGERANT CIRCUIT
Refrigeranttype
Refrigerantcharge
N.ofcircuits
PIPING CONNECTIONS
Evaporatorwaterinlet/outlet
Condenserwaterinlet/outlet

All the perfrormances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0C;
condenser 30.0/35.0C, unit at full load operation; operating fluid: Water; fouling factor = 0. (*) IW: Ivory White; GPSS: Galvanized and
Painted Steel Sheet; S&T: Single Pass Shell & Tube; CC:Closed Cell; (**) The values are according to ISO 3744 and are referred to: evaporator
12/7 C, condenser 30/35 C, full load operation.

13/31

ELECTRICAL SPECIFICATIONS
EWWD~VZ-SS
MODEL

EWWD600V EWWD700V EWWD760V EWWD890V EWWDC10V


ZSSA1
ZSSA1
ZSSA1
ZSSA1
ZSSA1

POWER SUPPLY
Phases
Frequency
Voltage
VoltagetoleranceMinimum
VoltagetoleranceMaximum

No.
Hz
V
%
%

3
50
400
-10%
10%

3
50
400
-10%
10%

3
50
400
-10%
10%

3
50
400
-10%
10%

3
50
400
-10%
10%

A
A
A
A

179
171
256
282

214
202
306
336

245
220
350
385

295
249
421
463

344
300
491
540

No.
V
%
%
A

3
400
-10%
10%
256
VFD

3
400
-10%
10%
306
VFD

3
400
-10%
10%
350
VFD

3
400
-10%
10%
421
VFD

3
400
-10%
10%
491
VFD

UNIT
Maximumstartingcurrent
Nominalrunningcurrentcooling
Maximumrunningcurrent
Maximumcurrentforwiressizing
COMPRESSORS
Phases
Voltage
VoltagetoleranceMinimum
VoltagetoleranceMaximum
Maximumrunningcurrent
Startingmethod

Allowed voltage tolerance 10%. Voltage unbalance between phases must be within 3%. Maximum starting current: starting current of biggest
compressor plus current of the other compressor at 75% of maximum load. In case of inverter driven units, no inrush current at start up is experienced.
Nominal running current in cooling is referred to the following conditions: evaporator 12/7C; condenser 30/35C. Maximum running current is based on
max compressor absorbed current in its envelope. Maximum current for wires sizing is based on minimum allowed voltage. Maximum current for wires
sizing: compressors full load ampere x 1,1. The data are referred to the standard unit without options. All data are subject to change without notice.
Please refer to unit nameplate data.

14/31

ELECTRICAL SPECIFICATIONS
EWWD~VZ-XS
MODEL

EWWD450V EWWD500V EWWD610V EWWD710V EWWD800V EWWD900V


ZXSA1
ZXSA1
ZXSA1
ZXSA1
ZXSA1
ZXSA1

POWER SUPPLY
Phases
Frequency
Voltage
VoltagetoleranceMinimum
VoltagetoleranceMaximum

No.
Hz
V
%
%

3
50
400
-10%
10%

3
50
400
-10%
10%

3
50
400
-10%
10%

3
50
400
-10%
10%

3
50
400
-10%
10%

3
50
400
-10%
10%

A
A
A
A

155
126
222
244

173
140
247
272

179
171
256
282

214
201
306
336

256
229
366
403

295
249
421
463

No.
V
%
%
A

3
400
-10%
10%
222
VFD

3
400
-10%
10%
247
VFD

3
400
-10%
10%
256
VFD

3
400
-10%
10%
306
VFD

3
400
-10%
10%
366
VFD

3
400
-10%
10%
421
VFD

UNIT
Maximumstartingcurrent
Nominalrunningcurrentcooling
Maximumrunningcurrent
Maximumcurrentforwiressizing
COMPRESSORS
Phases
Voltage
VoltagetoleranceMinimum
VoltagetoleranceMaximum
Maximumrunningcurrent
Startingmethod

MODEL

EWWDC11V
ZXSA1

POWER SUPPLY
Phases
Frequency
Voltage
VoltagetoleranceMinimum
VoltagetoleranceMaximum

No.
Hz
V
%
%

3
50
400
-10%
10%

A
A
A
A

344
299
491
540

No.
V
%
%
A

3
400
-10%
10%
491
VFD

UNIT
Maximumstartingcurrent
Nominalrunningcurrentcooling
Maximumrunningcurrent
Maximumcurrentforwiressizing
COMPRESSORS
Phases
Voltage
VoltagetoleranceMinimum
VoltagetoleranceMaximum
Maximumrunningcurrent
Startingmethod

Allowed voltage tolerance 10%. Voltage unbalance between phases must be within 3%. Maximum starting current: starting current of biggest
compressor plus current of the other compressor at 75% of maximum load. In case of inverter driven units, no inrush current at start up is experienced.
Nominal running current in cooling is referred to the following conditions: evaporator 12/7C; condenser 30/35C. Maximum running current is based on
max compressor absorbed current in its envelope. Maximum current for wires sizing is based on minimum allowed voltage. Maximum current for wires
sizing: compressors full load ampere x 1,1. The data are referred to the standard unit without options. All data are subject to change without notice.
Please refer to unit nameplate data.

15/31

ELECTRICAL SPECIFICATIONS
EWWD~VZ-PS
MODEL

EWWD505V EWWD715V EWWD910V


ZPSA1
ZPSA1
ZPSA1

POWER SUPPLY
Phases
Frequency
Voltage
VoltagetoleranceMinimum
VoltagetoleranceMaximum

No.
Hz
V
%
%

3
50
400
-10%
10%

3
50
400
-10%
10%

3
50
400
-10%
10%

A
A
A
A

173
138
247
272

214
200
306
336

295
247
421
463

No.
V
%
%
A

3
400
-10%
10%
247
VFD

3
400
-10%
10%
306
VFD

3
400
-10%
10%
421
VFD

UNIT
Maximumstartingcurrent
Nominalrunningcurrentcooling
Maximumrunningcurrent
Maximumcurrentforwiressizing
COMPRESSORS
Phases
Voltage
VoltagetoleranceMinimum
VoltagetoleranceMaximum
Maximumrunningcurrent
Startingmethod

Allowed voltage tolerance 10%. Voltage unbalance between phases must be within 3%. Maximum starting current: starting current of biggest
compressor plus current of the other compressor at 75% of maximum load. In case of inverter driven units, no inrush current at start up is experienced.
Nominal running current in cooling is referred to the following conditions: evaporator 12/7C; condenser 30/35C. Maximum running current is based on
max compressor absorbed current in its envelope. Maximum current for wires sizing is based on minimum allowed voltage. Maximum current for wires
sizing: compressors full load ampere x 1,1. The data are referred to the standard unit without options. All data are subject to change without notice.
Please refer to unit nameplate data.

16/31

SOUND LEVELS
EWWD~VZ-SS
Sound pressure level at 1 m from the unit (rif. 2 x 10-5 Pa)

MODEL

63Hz

125Hz

250Hz

500Hz

1000Hz

2000Hz

4000Hz

8000Hz

db(A)

Power db
(A)

600
700
760
890
C10

65.7
69.7
69.7
69.7
72.7

67.5
71.5
71.5
71.5
74.5

74.5
78.5
78.5
78.5
81.5

82.2
86.2
86.2
86.2
89.2

75.8
79.8
79.8
79.8
82.8

73.8
77.8
77.8
77.8
80.8

65.7
69.7
69.7
69.7
72.7

58.3
62.3
62.3
62.3
65.3

82
86
86
86
89

101
105
105
105
108

The values are according to ISO 3744 and are referred to: evaporator 12/7 C, condenser 30/35 C, full load operation.

17/31

SOUND LEVELS
EWWD~VZ-XS
Sound pressure level at 1 m from the unit (rif. 2 x 10-5 Pa)

MODEL

63Hz

125Hz

250Hz

500Hz

1000Hz

2000Hz

4000Hz

8000Hz

db(A)

Power db
(A)

450

58.4

66.2

76.0

73.2

73.9

72.0

62.9

53.7

78

97

500
610

60.4
65.7

68.2
67.5

78.0
74.5

75.2
82.2

75.9
75.8

74.0
73.8

64.9
65.7

55.7
58.3

80
82

99
101

710
800

69.7
69.7

71.5
71.5

78.5
78.5

86.2
86.2

79.8
79.8

77.8
77.8

69.7
69.7

62.3
62.3

86
86

105
105

900
C11

69.7
72.7

71.5
74.5

78.5
81.5

86.2
89.2

79.8
82.8

77.8
80.8

69.7
72.7

62.3
65.3

86
89

105
108

The values are according to ISO 3744 and are referred to: evaporator 12/7 C, condenser 30/35 C, full load operation.

18/31

SOUND LEVELS
EWWD~VZ-PS
Sound pressure level at 1 m from the unit (rif. 2 x 10-5 Pa)

MODEL

63Hz

125Hz

250Hz

500Hz

1000Hz

2000Hz

4000Hz

8000Hz

db(A)

Power db
(A)

505

60.4

68.2

78.0

75.2

75.9

74.0

64.9

55.7

80

99

715

69.7

71.5

78.5

86.2

79.8

77.8

69.7

62.3

86

105

910

69.7

71.5

78.5

86.2

79.8

77.8

69.7

62.3

86

105

The values are according to ISO 3744 and are referred to: evaporator 12/7 C, condenser 30/35 C, full load operation.

19/31

OPERATING LIMITS

Operating Limits

EWWD-VZSS - Silver Version

Legend:

ELWT:EvaporatorLeavingWaterTemperature(C)
CLWT:CondenserLeavingWaterTemperature(C)

Ref. 1:StandardUnit.

Ref. 2:StandardUnitplusBrineVersion(option08-onrequest).

Ref. 3:StandardUnitplusHightemperaturekit(option111-onrequest).

Ref. 4:StandardUnitplusHightemperaturekit(option111-onrequest)plusBrineVersion(option08-onrequest).

Notes:

- The above graph refers to the unit operating at full load. Unit may be able to operate outside the above envelope with
compressorsunloading.Pleasecontactfactoryforfurtherdetails.

- For operation with EWLT below 4C, the unit must operate with glycol mixture. The glycol percentage must be provided
accordingtotheminimumELWTneeded.

-Theabovegraphicrepresentsaguidelineabouttheoperatinglimitsoftherange.PleaserefertothelatestChillerSelection
Software(CSS)forrealoperatinglimitsworkingconditionsforeachsize.

-Inareas2,3and4chillermaynotunloadtotheminimumcapacity.Pleaserefertochillerselectionsoftware.

20/31

OPERATING LIMITS
Operating

Limits

EWWD-VZXS & EWWD-VZPS - Gold & Platinum Version

Legend:

ELWT:EvaporatorLeavingWaterTemperature(C)
CLWT:CondenserLeavingWaterTemperature(C)
Ref. 1:StandardUnit.
Ref. 2:StandardUnitplusBrineVersion(option08-onrequest).
Ref. 3:StandardUnitplusHightemperaturekit(option111-onrequest).
Ref. 4:StandardUnitplusHightemperaturekit(option111-onrequest)plusBrineVersion(option08-onrequest).
Notes:

- The above graph refers to the unit operating at full load. Unit may be able to operate outside the above envelope with
compressorsunloading.Pleasecontactfactoryforfurtherdetails.

- For operation with EWLT below 4C, the unit must operate with glycol mixture. The glycol percentage must be provided
accordingtotheminimumELWTneeded.

-Theabovegraphicrepresentsaguidelineabouttheoperatinglimitsoftherange.PleaserefertothelatestChillerSelection
Software(CSS)forrealoperatinglimitsworkingconditionsforeachsize.

-Inareas2,3and4chillermaynotunloadtotheminimumcapacity.Pleaserefertochillerselectionsoftware.

21/31

OPERATING LIMITS
Water heat exchangers - maximum/maximum water t
Theminimumandmaximumallowedtatfullloadconditionsarerespectively4Cand8C.Contactfactoryincaseloweror
highertarerequired.

Requirements for operation and storage


Unitisdesignedforindoorinstallationonly.
Environmentalconditionsmustbewithinthefollowinglimits:

Limitsforoperation:
-Maximumambienttemperature:42C
-Minimumambienttemperature:5C
-Maximumrelativehumidity:95%notcondensing

Limitsforstorage:
-Maximumambienttemperature50C
-Minimumambienttemperature:-20C
-Maximumrelativehumidity:95%notcondensing

Storagebelowtheminimumtemperaturemaycausedamagetocomponents.
Storageabovethemaximumtemperaturecausesopeningofsafetyvalves.
Storageincondensingatmospheremaydamageelectroniccomponents.

Water treatment
Before putting the unit into operation, clean the water circuit. Dirt, scales, corrosion debris and other materials can
accumulate inside the heat exchanger and reduce its heat exchanging capacity. Pressure drops can increase as well, thus
reducing water flow. Proper water treatment therefore reduces the risk of corrosion, erosion, scaling, etc.. The most
appropriate water treatment must be determined locally, according to the type of system and water characteristics. The
manufacturerisnotresponsiblefordamagetoormalfunctioningofequipmentcausedbyimproperlytreatedwater.

22/31

OPERATING LIMITS

23/31

DIMENSIONAL DRAWING

LEGEND

1.ELECTRICALPANEL
2.POWERSUPPLYCABLEENTRY
3.EVAPORATORWATERINLET
4.EVAPORATORWATEROUTLET
5.CONDENSERWATERINLET
6.CONDENSERWATEROUTLET

Unitdimensionsbelowareinmm

MODEL

EWWD600VZSSA1
EWWD700VZSSA1
EWWD760VZSSA1
EWWD890VZSSA1
EWWDC10VZSSA1

1179
1179
1179
1219
1303

3634
3634
3634
3510
3822

2122
2122
2122
2292
2487

830
830
830
999
1013

431
431
431
431
485

965
965
965
981
1101

270
270
270
340
292

232
232
232
135
326

185
185
185
205
150

168.3
168.3
168.3
219.1
219.1

139.7
139.7
139.7
168.3
219.1

3170
3170
3170
3170
3170

490
490
490
550
670

24/31

DIMENSIONAL DRAWING

LEGEND

1.ELECTRICALPANEL
2.POWERSUPPLYCABLEENTRY
3.EVAPORATORWATERINLET
4.EVAPORATORWATEROUTLET
5.CONDENSERWATERINLET
6.CONDENSERWATEROUTLET

Unitdimensionsbelowareinmm

MODEL

EWWD450VZXSA1
EWWD500VZXSA1
EWWD610VZXSA1
EWWD710VZXSA1
EWWD800VZXSA1
EWWD900VZXSA1
EWWDC11VZXSA1

1179
1179
1179
1219
1877
1303
1303

3634
3634
3490
3510
3510
3822
3822

2093
2093
2122
2234
2234
2487
2487

828
828
830
762
762
1013
1013

431
431
431
431
431
485
485

965
965
965
981
981
1101
1101

270
270
270
340
340
292
292

232
232
135
135
135
326
326

185
185
185
205
205
150
150

168.3
168.3
219.1
219.1
219.1
219.1
219.1

139.7
139.7
139.7
168.3
168.3
219.1
219.1

3170
3170
3170
3170
3170
3170
3170

490
490
550
550
550
670
670

25/31

DIMENSIONAL DRAWING

LEGEND

1.ELECTRICALPANEL
2.POWERSUPPLYCABLEENTRY
3.EVAPORATORWATERINLET
4.EVAPORATORWATEROUTLET
5.CONDENSERWATERINLET
6.CONDENSERWATEROUTLET

Unitdimensionsbelowareinmm

MODEL

EWWD505VZPSA1
EWWD715VZPSA1

1179
1276

3490
3822

2093
2429

757
822

431
485

965
1101

270
292

135
326

185
150

219.1
219.1

139.7
219.1

3170
3170

550
670

EWWD910VZPSA1

1303

3822

2487

1013

485

1101

1101

326

150

219.1

219.1

3170

670

26/31

INSTALLATION NOTES

Installation Notes
Warning Installationandmaintenanceoftheunitmustbeperformedonlybyqualifiedpersonnelwhohaveknowledgewith
localcodesandregulations,andexperiencewiththistypeofequipment.Mustbeavoidedtheunitinstallationinplacesthat
couldbeconsidereddangerousforallthemaintenanceoperations.

Handling Avoid bumping and/or jolting during loading/unloading unit from the truck and moving it. Secure the unit inside
thetrucktopreventitfrommovingand causingdamages.Donotallowanypart oftheunittofallduringtransportation or
loading/unloading.
Use extreme caution when handling the unit to prevent damage to the control or the refrigerant piping. The unit mustbe
lifted by attaching cables or chains at the lifting holes in each corner. For more information please refer to the unit
InstallationManual.
Location Unitisdesignedforindoorinstallationonly.Theunitmustbemountedonaleveledbaseofconcreteorsteel.The
unitmustbeinstalledonarobustandperfectlyleveledfoundation;itmightbenecessarytouseweightdistributionbeams.
Rubber mounts/pads as well as vibration isolators in all water piping connected to the chiller are recommended to avoid
transmissionofvibrationandnoise.

Space requirements Every side of the machine must be accessible for all post installation maintanance activities. The
minimumspacerequiredisshownonthefollowingdrawing:

Acoustic protection When noise level must meet special requirements, it is necessary to pay the maximum attention to
ensuretheperfectinsulationoftheunitfromthesupportbasebyapplyingappropriateanti-vibrationdevicesontheunit,on
thewaterpipesandontheelectricalconnections.
Storage Theenvironmentconditionshavetobeinthefollowinglimits:
-Maximumambienttemperature50C
-Minimumambienttemperature:-20C
-Maximumrelativehumidity:95%notcondensing
Storagebelowtheminimumtemperaturemaycausedamagetocomponents.Storageabovethemaximumtemperature
causesopeningofsafetyvalves.Storageincondensingatmospheremaydamageelectroniccomponents

27/31

TECHNICAL SPECIFICATIONS

Technical Specifications

General ThechillerwillbedesignedandmanufacturedinaccordancewiththefollowingEuropeandirectives:

-Constructionofpressurevessel2014/68/EU
-MachineryDirective2006/42/EC
-LowVoltage2014/35/EU
-ElectromagneticCompatibility2014/30/EU
-Electrical&SafetycodesEN60204-1/EN61439-1/EN61439-2
-Manufacturing&QualityStandardsUNIENISO9001:2008
-EnvironmentalManagementSystemUNIENISO14001:2004
-Health&SafetyManagementSystemBSOHSAS18001:2007

To avoid any losses, the unit will be tested at full load in the factory (at the nominal working conditions and water
temperatures). The chiller will be delivered to the job site completely assembled and charged with refrigerant and oil. The
installationofthechillermustcomplywiththemanufacturersinstructionsforriggingandhandlingequipment.

Theunitwillbeabletostartupandoperate(asstandard)atfullloadwith:

-evaporatorleavingfluidtemperaturebetween...............Cand...............C
-condenserleavingfluidtemperaturebetween...............Cand...............C

Refrigerant OnlyHFC134acanbeused.

Performance Chillershallsupplythefollowingperformances:

-Numberofchiller(s):unit(s)
-Coolingcapacityforsinglechiller:kW
-Powerinputforsinglechillerincoolingmode:kW
-Evaporatorheatexchangerenteringwatertemperatureincoolingmode:C
-Evaporatorheatexchangerleavingwatertemperatureincoolingmode:C
-Evaporatorheatexchangerwaterflow:l/s
-Condenserheatexchangerenteringwatertemperatureincoolingmode:C
-Condenserheatexchangerleavingwatertemperatureincoolingmode:C
-Condenserheatexchangerwaterflow:l/s

Operatingvoltage range should be400V 10%, 3ph, 50Hz(or 380V 10%, 3ph,60Hz), voltage unbalance maximum 3%,
withoutneutralconductorandshallonlyhaveonepowerconnectionpoint.
Unit description Sound level and vibrations Sound pressure level at 1 meter distance in free field, semispherical
conditions, shall not exceed dB(A). The sound pressure levels must be rated in accordance to ISO 3744. Vibration on
thebaseframeshouldnotexceed2mm/s.
Dimensions Unitdimensionsshallnotexceedfollowingindications:

Unitlength...............mm
Unitwidth...............mm
Unitheight...............mm

Compressors Theunitshallbeequippedwith:

-Semi-hermetic,single-screwtypewithonemainhelicalrotorandtwogaterotors.Thegaterotorswillbeconstructedofa
carbonimpregnatedengineeredcompositematerial.Thegaterotorsupportswillbeconstructedofcastiron.

-Compressors rotational speedshall be continuously adjustedby means of inverter(stepless regulation) allowing accurate
watertemperaturecontrolandefficientcapacitymodulation.

- Compressor shall be able to adapt the discharge pressure of the refrigerant to any operating conditions by means of
variablevolumeratiosystem.

- Refrigerant system differential pressure shall provide oil injection on all moving compressor parts to correctly lubricate
them.Electricaloilpumplubricatingsystemisnotacceptable.

28/31

TECHNICAL SPECIFICATIONS

-The compressors oil cooling must be realized, whennecessary, by refrigerant liquid injection. External oil cooling system
willnotbeaccepted.
-Theoilseparatorshallbeintegratedwithinthecondenserandshallnotrequireoilpump

-Thecompressorshallbedirectdriventype,withoutgeartransmissionbetweenthescrewandtheelectricalmotor.

- Compressor shall be equipped with two thermal protections realized by means of thermistors for high temperature
protection: one temperature sensor to protect electrical motor and another sensor to protect unit and lubricating oil from
highdischargegastemperature.

-Noanyoil-crankcaseheaterwillbeacceptedontheunit.

-Compressorshallbefullyfieldserviceable.

Evaporator The units shall be equipped with a flooded shell & tube evaporator with water flowing inside the tubes and
refrigerantboiling outside. Thetubes are enhanced formaximum heat transferand rolled into steeltube sheet and sealed.
Thetubesareindividuallyreplaceable.

-Theexternalshellshallbeinsulatedwithflexible,closedcellpolyurethaneinsulationmaterial(20-mmthick).

-ThewaterconnectionsshallbeVICTAULICtypeconnectionsasstandardtoensurequickmechanicaldisconnectionbetween
theunitandthehydronicnetwork.

-TheevaporatorwillbemanufacturedinaccordancetoPEDstandard(2014/68/EU).

-Thewatersideshallbedesignedfor10barofmaximumoperatingpressure;ventsanddrainshallbeprovided.

Condenser The unit shall be equipped with single-passcounter-flow shell & tube heat exchanger with water flowing inside
thetubesandrefrigerantcondensingoutside.
Thelowersideofthecondensershallbeprovidedwithsubcoolingsectionforimprovedunitperformances.Thetubesshallbe
enhancedformaximumheattransferandrolledintosteeltubesheetandsealed.Thetubesshallbeindividuallyreplaceable.

-ThewaterconnectionsshallbeVICTAULICtypeconnectionsasstandardtoensurequickmechanicaldisconnectionbetween
theunitandthehydronicnetwork.

-ThecondenserwillbemanufacturedinaccordancetoPEDstandard(2014/68/EU).

-Thewatersideshallbedesignedfor10barofmaximumoperatingpressure;ventsanddrainshallbeprovided.

-Theoilseparatingsectionshallbeintegratedwithinthecondenser.
Refrigerant circuit The unit shall have one or two independent refrigerant circuits and one variable frequency driver per
compressor(Inverter).
The circuit shall include as standard: electronic expansion device piloted by units microprocessor control, compressor
discharge shut-off valve, liquid line shut-off valve, sight glass with moisture indicator, replaceable filter drier, charging
valves,highpressureswitch,highandlowpressuretransducers,oilpressuretransducerandinsulatedsuctionline.

Condensation control The compressor automatically unloads when high condensing pressure is detected. This to prevent
theshutdownoftherefrigerantcircuit(shutdownoftheunit)duetoahigh-pressurefault.
Low sound unit configurations (on request) The chillershall beprovided withan acousticalcompressor enclosure. This
enclosure shall be realized with a light, corrosion resistant aluminum structure and metal panels. The compressor soundproofenclosureshallbeinternallyfittedwithflexible,multi-layer,highdensitymaterials.

Electrical control panel Powerandcontrolshallbelocatedinthemainpanelthatwillbemanufacturedtoensureprotection


againstallweatherconditions.

-TheelectricalpanelshallbeIP54and(withthedoorsopened)internallyprotectedagainstpossibleaccidentalcontactwith
electricalcomponents(IP20).

-Themainpanelshallbefittedwithamainswitchinterlockeddoor.

-Thepowersectionwillincludecompressorsprotectiondevices,compressorsstartersandcontrolcircuitpowersupply.

Controller The controller will be installed as standard and it will be used to modify unit set-points and check control
parameters.
Adisplayinstalledontheoutsideofthecontrolpanelsdoorwillalloweasyaccesstochilleroperatingstatusincludingwater
temperaturesandrefrigerantpressuresandtemperatures.
A sophisticated software with predictive logic will select the most energy efficient combination of compressor load and
electronicexpansionvalvepositionkeepingstableoperatingconditionsandmaximizingchillerefficiencyandreliability.

29/31

TECHNICAL SPECIFICATIONS

Inadditiontonormaloperatingfunctionalities,unitcontrollerwilltakecorrectiveactionsincasethechilleroperatingoutside
recommendedworkingconditions.
Unit controller shall be able to protect critical unit components thanks to the signals received by the various unit sensors
(suchasmotortemperaturesensors,refrigerantandoilpressure/temperaturesensors,pressureswitches..etc..).

ControllermainfeaturesControllershallguaranteefollowingminimumfunctions:
-Optimizedmanagementofcompressorssteplesscapacitycontrolthroughinverterdrive.
-Displayofevaporatorentering/leavingwatertemperatures.
-Displayofcondenserentering/leavingwatertemperatures.
-Displayofrefrigerantcondensing/evaporatingtemperaturesandpressures.
-Regulationofleavingevaporatorwater(coolingmode)orcondenserwater(heatingmode).Temp.tolerance0,1C.
-Displayofcompressorworkinghoursandnumberofcompressorstarts.
-Re-startincaseofpowerfailure(automaticormanualdependingonfailuretype).
-Softload(optimizedmanagementofthecompressorloadduringthestart-up).
-Setpointreset.
-Master/Slaveoperation(upto4chillersconnected).

Controllershallguaranteefollowingminimumalarmssignaling:
-Phaseloss.
-Evaporatorwaterflowloss.
-Evaporatorwaterfreezingprotection.
-Externalalarm.
-Lowevaporatorrefrigerantpressure.
-Highrefrigerantpressure(transducer).
-Highrefrigerantpressure(switch).
-Lowpressureratio.
-Highrefrigerantdischargetemperature.
-Highoilpressuredifferential.
-Highmotortemperature.

High Level Communications Interface (on request) The chiller shall be able to communicate to BMS (Building Management
System)basedonthemostcommonprotocolssuchas:
-ModbusRTU
-LonWorks
-BacNetBTPcertifiedoverIPandMS/TP(class4)(Native)
-EthernetTCP/IP.

Master/SlavetheunitshallbeabletooperateinMaster/Slavemodeinordertobeconnectedwithothersimilarunit(upto
4). The master unit shall manage the slave units connected in series on the hydraulic plant with the aim of optimize the
runninghoursofeachcompressorandtobalancetheloadbetweentheunits.

30/31