Technical Data 210-12

Effective August 2013


Supersedes August 2012

Three-phase pad-mounted
compartmental type transformer

General
At Eatons Cooper Power Systems, we are
constantly striving to introduce new innovations
to the transformer industry, bringing you the
highest quality, most reliable transformers. Eatons
Cooper Power Systems Transformer Products
are ISO 9001 compliant, emphasizing process
improvement in all phases of design, manufacture,
and testing. In order to drive this innovation, we
have invested both time and money in the Thomas
A. Edison Technical Center, our premier research
facility in Franksville, Wisconsin. Headquarters
for the Systems Engineering Group of Eatons
Cooper Power Systems, such revolutionary
products as distribution-class UltraSIL
Polymer-Housed Evolution surge arresters and
EnvirotempFR3 fluid have been developed at
our Franksville lab.

With transformer sizes ranging from 45kVA to


12MVA and high voltages ranging from 2400V
to 46kV, Eatons Cooper Power Systems has
you covered. From fabrication of the tanks and
cabinets to winding of the cores and coils, to
production of arresters, switches, tap changers,
expulsion fuses, current limit fuses, bushings
(live and dead) and molded rubber goods, Eatons
Cooper Power Systems does it all. Eatons Cooper
Power Systems transformers are available with
electrical grade mineral oil or EnvirotempFR3
fluid, a less-flammable and bio-degradable fluid.
Electrical codes recognize the advantages of
using EnvirotempFR3 fluid both indoors and
outdoors for fire sensitive applications. The biobased fluid meets Occupational Safety and Health
Administration (OSHA) and Section 450.23 NEC
Requirements.

Technical Data 210-12

Three-phase pad-mounted compartmental type transformer

Effective August 2013

Bay-O-Net fusing

Drip shield

Liquid level gauge

Nameplate
laser-scribed anodized aluminum

LOW-VOLTAGE
BUSHING
Low-voltage
molded epoxy
bushings with
NEMA spades

LOWVOLTAGE
BUSHING
SUPPORT

LOADBREAK SWITCH

HIGH-VOLTAGE BUSHING

SILL
Suitable for skidding,
rolling, and jacking

5-position tap changer


Parking stand

Ground pad and strap for x0

Figure 1. Three-phase pad-mounted compartmental type transformer.

Table 1. Product Scope


Type

Three Phase, 50 or 60 Hz, 65 C Rise


(55 C, 55/65 C), 65/75 C, 75 C

Fluid Type

Mineral oil or EnvirotempFR3 fluid

Coil Configuration

2-winding or 4-winding or 3-winding (Low-High-Low), 3-winding (Low-Low-High)

Size

45 12,000 kVA

Primary Voltage

2,400 46,000 V

Secondary Voltage

208Y/120 V to 14,400 V
Inverter/Rectifier Bridge
K-Factor (up to K-19)
Vacuum Fault Interrupter (VFI)
UL Listed & Labeled and Classified

Specialty Designs

Factory Mutual (FM) Approved


Solar/Wind Designs
Differential Protection
Seismic Applications (including OSHPD)
Hardened Data Center

www.cooperpower.com

Removeable cabinet
walls

Technical Data 210-12

Three-phase pad-mounted compartmental type transformer

Effective August 2013

Table 2.Three-Phase Ratings


Three-Phase 50 or 60Hz
kVA Available1:
45, 75, 112.5, 150, 225, 300, 500, 750, 1000, 1500, 2000, 2500, 3000, 3750, 5000, 7500, 10000, 12000
1

Transformers are available in the standard ratings and configurations shown or can be customized to meet specific needs.

Table 3. Audible Sound Levels


NEMA TR-1 Average
Self-Cooled, Two Winding kVA Rating

Decibels (dB)

45-500

56

501-700

57

701-1000

58

1001-1500

60

1501-2000

61

2001-2500

62

2501-3000

63

3001-4000

64

4001-5000

65

5001-6000

66

6001-7500

67

7501-12000

68

Table 4. Insulation Test Levels


KV Class

Induced Test 180 or 400 Hz


7200 Cycle

kV BIL
Distribution

Applied Test 60Hz (kV)

1.2

30

10

2.5

45

15

60

19

8.7

75

26

95

34

125

40

25

150

50

34.5 (grd Y Only)

125

40

34.5

150

70

46

200

95

15
25 (grd Y Only)

TWICE RATED VOLTAGE

Table 5.Temperature Rise Ratings 0-3300 Feet (0-1000 meters)


Unit Rating (Temperature Rise Winding)

Standard

Optional

65 C

55 C, 55/65 C, 75 C

Ambient Temperature Max

40 C

50 C

Ambient Temperature 24 Hour Average

30 C

40 C

Temperature Rise Hotspot

80 C

65 C

www.cooperpower.com

Technical Data 210-12

Three-phase pad-mounted compartmental type transformer

Effective August 2013

A*
H

F-3
3.5"

I-3

E
F

PAD DIMENSIONS

CABINET/TANK DIMENSIONS

Figure 2. Transformer and pad dimensions.


* Add 9" for Bay-O-Net fusing.

Table 6. Fluid-filledaluminum windings 55/65C Rise1


65 Rise
kVA Rating

DEAD-FRONTLOOP OR RADIAL FEEDBAY-O-NET FUSING OIL FILLEDALUMINUM WINDINGS


OUTLINE DIMENSIONS (in.)
A*
B
C
D
E
F
G
H
I

Gallons of
Fluid

Approx. Total
Weight (lbs.)

45
75
112.5
150
225
300
500
750
1000
1500
2000
2500
3000
3750
5000
7500

50
50
50
50
50
50
50
64
64
73
73
73
73
84
84
94

110
115
120
125
140
160
190
270
350
410
490
530
620
660
930
1,580

2,100
2,250
2,350
2,700
3,150
3,650
4,650
6,500
8,200
10,300
12,500
14,500
16,700
19,300
25,000
41,900

kVA Rating

DEAD-FRONTLOOP OR RADIAL FEEDBAY-O-NET FUSING OIL FILLEDCOPPER WINDINGS


OUTLINE DIMENSIONS (in.)
A*
B
C
D
E
F
G
H
I

Gallons of
Fluid

Approx. Total
Weight (lbs.)

45
75
112.5
150
225
300
500
750
1000
1500
2000
2500
3000
3750
5000
7500

50
50
50
50
50
50
50
64
64
73
73
73
73
84
84
94

110
115
115
120
140
160
200
255
300
410
420
500
720
800
850
1,620

2,100
2,350
2,500
2,700
3,250
3,800
4,800
6,500
7,800
10,300
11,600
14,000
18,700
20,500
25,000
46,900

68
68
68
68
72
72
89
89
89
89
72
72
84
85
96
102

39
39
49
49
51
51
53
57
59
86
87
99
99
108
108
122

42
42
42
42
42
42
42
42
42
42
42
42
46
47
48
54

26
26
26
26
30
30
30
30
30
30
30
30
37
38
48
48

68
68
68
68
72
72
72
72
72
72
72
72
84
85
96
102

72
72
72
72
76
76
93
93
93
93
76
76
88
88
100
100

43
43
53
53
55
55
57
61
63
90
91
103
103
112
112
126

20
20
20
20
20
20
20
20
20
24
24
24
24
24
24
24

1 Weights, gallons of fluid, and dimensions are for reference only and not for construction. Please contact Eatons Cooper Power Systems for exact dimensions.
* Add 9" for Bay-O-Net fusing.

Table 7. Fluid-FilledCopper Windings 55/65C Rise1


65 Rise

64
64
64
64
64
64
81
89
89
89
72
72
84
85
96
102

34
34
34
34
34
34
34
42
42
42
42
42
46
47
48
54

30
30
30
30
30
30
30
30
30
30
30
30
37
38
48
48

64
64
64
64
64
64
64
72
72
72
72
72
84
85
96
102

69
69
69
69
73
75
85
93
93
93
76
76
88
88
100
100

43
43
53
53
55
55
57
61
63
90
91
103
103
112
112
126

20
20
20
20
20
20
20
20
20
24
24
24
24
24
24
24

Weights, gallons of fluid, and dimensions are for reference only and not for construction. Please contact Eatons Cooper Power Systems for exact dimensions.

* Add 9" for Bay-O-Net fusing.


4

39
39
49
49
51
51
53
57
59
86
87
99
99
108
108
122

www.cooperpower.com

Technical Data 210-12

Three-phase pad-mounted compartmental type transformer

Effective August 2013

Standard features

Tank/cabinet features

Connections and neutral configurations

Bolted cover for tank access (45-1750 kVA)

Delta - Wye: Low voltage neutral shall be a fully insulated X0


bushing with removable ground strap.

Welded cover with hand hole (2000-12,000 kVA)

Three-point latching door for security

Grounded Wye-Wye: High voltage neutral shall be internally tied


to the low voltage neutral and brought out as the H0X0 bushing in
the secondary compartment with a removable ground strap.

Removable sill for easy installation

Lifting lugs (4)

Stainless steel cabinet hinges and mounting studs

Steel divider between HV and LV compartment

Wye-Wye: High voltage neutral shall be brought out as the


H0 bushing in the primary compartment and the low voltage
neutral shall be brought as the X0- bushing in the secondary
compartment.

20 Deep cabinet (45-1000 kVA)

24 Deep cabinet (1500-7500kVA)

30 Deep cabinet (34.5/19.92 kV)

Wye-Delta: High voltage neutral shall be brought out as the H0


bushing in the primary compartment. No ground strap shall be
provided (line to line rated fusing is required).

Pentahead captive bolt

Stainless steel 1-hole ground pads (45-500 kVA)

Stainless steel 2-hole ground pads (750-10,000 kVA)

Parking Stands

Delta-Delta: Transformer shall be provided without a neutral


bushing.

High and low voltage bushings

200 A bushing wells (15, 25, and 35kV)

200 A, 35 kV Large Interface

600 A (15, 25, and 35 kV) Integral bushings (dead-front)

Electrical-grade wet-process porcelain bushings (live-front)

Valves/plugs

One-inch upper filling plug

One-inch drain plug (45-500 kVA)

One-inch combination drain valve with sampling device in low


voltage compartment (750-12,000 kVA)

Automatic pressure relief valve

Nameplate

Laser-scribed anodized aluminum nameplate

Figure 3. Drain valve with sampler.

Figure 4. Automatic Pressure relief valve.

Figure 6. External Gauges.

Figure 7. External visible break with


gauges.

Figure 5. Liquid level gauge.

www.cooperpower.com

Technical Data 210-12

Three-phase pad-mounted compartmental type transformer

Effective August 2013

Optional features

Overcurrent protection

High and low voltage bushings

Bay-O-Net fusing (Current sensing, dual sensing, dual element,


high amperage overload)

Bay-O-Net expulsion fuse in series with a partial range under-oil


ELSP current limiting fuse (below 23 kV)

Cartridge fusing in series with a partial range under-oil ELSP current limiting fuse (above 23 kV)

200 A (15, 25 kV) bushing inserts

200 A (15, 25 kV) feed thru inserts

200 A (15, 25 kV) (HTN) bushing wells with removable studs

High-voltage 600 A (15, 25, 35kV) deadbreak one-piece bushings

Low voltage 6-, 8-holes spade

MagneX interrupter with ELSP current-limiting fuse

Low voltage 12-, 16-, 20-holes spade (750-2500 kVA)

Vacuum Fault Interrupter (VFI)

Low voltage bushing supports

Visible break window

Fuse/switch interlock

Tank/cabinet features

Valves/plugs

Stainless steel tank base and cabinet

Stainless steel tank base, cabinet sides and sill

Drain/sampling valve in high-voltage compartment


Globe type upper fill valve

100% stainless steel unit

Service entrance (2 inch) in sill or cabinet side

Overvoltage protection

Touch-up paint (domestic)

Distribution-, intermediate-, or station-class surge arresters

Copper ground bus bar

Elbow arresters (for dead-front connections)

Kirk-Key provisions

Metering/fan/control

Nitrogen blanket

Full metering package

Bus duct cutout

Current Transformers (CTs)

Metering Socket
NEMA 4 control box (optional stainless steel)

Special designs

Factory Mutual (FM)

UL Classified

NEMA 7 control box (explosion proof)

Triplex

Fan Packages

High altitude

Testing

K-Factors

Customer test witness

Step-up

Customer final inspection

Critical application

Zero Sequence Impedance Test

Modulation transformers

Heat Run Test

Seismic applications (including OSHPD)

ANSI Impulse Test

Audible Sound Level Test


RIV (Corona) Test

Switches

One, two, or three On/Off loadbreak switches

4-position loadbreak V-blade switch or T-blade switch

Dissolved Gas Analysis (DGA) Test

Delta-wye switch

8- or 24-Hour Leak Test

3-position V-Blade selector switch

Coatings (paint)

100 A, 150 A, 300 A tap changers

ANSI Bell Green

Dual voltage switch

ANSI #61 Light Gray

Visible break with VFI interrupter interlock

ANSI #70 Sky Gray

External visible break (15, 25, and 35 kV, up to 3 MVA)

Special paint available per request

External visible break with gauges (15, 25, and 35 kV, up to 3


MVA)

Nameplate

Gauges and devices

Liquid level gauge (optional contacts)

Pressure vacuum gauge (optional contacts and bleeder)

Dial-type thermometer (optional alarm contacts)

Cover mounted pressure relief device

Ground connectors

Hexhead captive bolt

Breaker mounting provisions

External gauges in padlockable box

www.cooperpower.com

Stainless steel nameplate

Decals and labels

High voltage warning signs

Mr. Ouch

Bi-lingual warning

DOE compliant

Customer stock code

Customer stenciling

Shock and arc flash warning decal

Non-PCB decal

Three-phase pad-mounted compartmental type transformer

Technical Data 210-12


Effective August 2013

Construction
Core
The three-legged, step-lap mitered core construction is manufactured using a high-quality cutting machine. For maximum efficiency,
cores are precisely stacked, virtually eliminating gaps in the corner
joints.
Five-legged wound core or shell-type triplex designs are used for
wye-wye connected transformers, and other special transformer
designs.
Cores are manufactured with precision cut, burr-free, grain-oriented
silicon steel. Many grades of core steel are available for optimizing
core loss efficiency.

Coils
Pad-mounted transformers feature a rectangular coil configuration
with wire-wound, high-voltage primaries and sheet-wound
secondaries. The design minimizes axial stress developed by short
circuits and provides for magnetic balancing of tap connections.
Coils are wound using the highest quality winding machines providing exacting tension control and conductor placement for superior
short-circuit strength and maximum efficiency.
Extra mechanical strength is provided by diamond pattern, epoxycoated paper insulation, used throughout the coil, with additional
epoxy at heavy stress points. The diamond pattern distribution of the
epoxy and carefully arranged ducts, provide a network of passages
through which cooling fluid can freely circulate.

chemically inert product with minimal acid ions. Special additives


minimize oxygen absorption and inhibit oxidation. To ensure high
dielectric strength, the fluid is re-tested for dryness and dielectric
strength, refiltered, heated, dried, and stored under vacuum before
being added to the completed transformer.
Eatons Cooper Power Systems transformers filled with
EnvirotempFR3 fluid enjoy unique fire safety, environmental,
electrical, and chemical advantages, including insulation life extending properties.
A bio-based, sustainable, natural ester dielectric coolant,
EnvirotempFR3 fluid quickly and thoroughly biodegrades in
the environment and is non-toxic per acute aquatic and oral toxicity
tests.
Building for Environmental and Economic Sustainability (BEES)
total life cycle assessment software, utilized by the US Dept. of
Commerce, reports its overall environmental performance impact
score at 1/4th that reported for mineral oil. EnvirotempFR3 fluid
has also earned the EPA Environmental Technology Verification of
transformer materials.
With a fire point of 360C, EnvirotempFR3 fluid is FM
Approved and Underwriters Laboratories (UL) Classified LessFlammable per NEC Article 450-23, fitting the definition of a Listed
Product per NEC.

Coil assemblies are heat-cured under calculated hydraulic pressure


to ensure performance against short-circuit forces.

Core and coil assemblies


Pad-mounted transformer core and coil assemblies are braced with
heavy steel ends to prevent the rectangular coil from distorting
under short-circuit conditions. Plates are clamped in place using
presses, and welded or bolted to form a solid core and coil
assembly. Core and coil assemblies exceed ANSI and IEEE
requirements for short-circuit performance. Due to the rigidity of the
design, impedance shift after short-circuit is comparable to that of
circular wound assemblies.

Tanks
Transformer tanks are designed for high strength and ease of
handling, installation, and maintenance. Tanks are welded using
precision-cut, hot rolled, pickled and oiled steel. They are sealed to
protect the insulating fluid and other internal components.

Figure 8. VFI transformer with visible break.

Transformer tanks are pressure-tested to withstand 7 psig without


permanent distortion and 15 psig without rupture.

Pad-mounted VFI transformer

Tank finish
An advanced multi-stage finishing process exceeds IEEE Std
C57.12.28-2005 standards. The eight-stage pre-treatment process
assures coating adhesion and retards corrosion. It converts tank
surfaces to a nonmetallic, water insoluble iron phosphate coating.
The paint method consists of two distinct layers of paint. The first
is an epoxy primer (E-coat) layer which provides a barrier against
moisture, salt and corrosives. The two-component urethane final
coat seals and adds ultraviolet protection.

Vacuum processing
Transformers are dried and filled with filtered insulating fluid under
vacuum, while secondary windings are energized. Coils are heated
to drive out moisture, ensuring maximum penetration of fluid into
the coil insulation system.

Insulating fluid
Transformers from Eatons Cooper Power Systems are available
with electrical-grade mineral insulating oil or EnvirotempFR3
fluid. The highly refined fluids are tested and degassed to assure a

The VFI transformer combines a conventional distribution transformer from Eatons Cooper Power Systems with the proven Vacuum
Fault Interrupter (VFI). This combination provides both voltage transformation and transformer over current protection in one space saving and money saving package. The pad-mounted VFI transformer
protects the transformer and provides proper coordination with
upstream protective devices. When a transformer fault or overload
condition occurs, the VFI breaker trips and isolates the transformer.
The three-phase VFI breaker has independent single-phase initiation,
but is three-phase mechanically gang-tripped. A trip signal on any
phase will open all three phases. This feature eliminates single-phasing of three phase loads. It also enables the VFI breaker to be used
as a three-phase load break switch.
Due to the resettable characteristics of the VFI breaker, restoring
three-phase service is faster and easier.
The sealed visible break window and switch is an option that can
be installed to provide visible break contact. This feature provides
enhanced safety and allows an operator to see if the loadbreak
switch contacts are in an open or closed position before performing
maintenance.
www.cooperpower.com

Technical Data 210-12

Three-phase pad-mounted compartmental type transformer

Effective August 2013

Envirotran FM Approved special protection transformer

health or likelihood of an impending failure.

The Envirotran transformer from Eatons Cooper Power Systems


is FM Approved and suitable for indoor locations. Factory Mutual
Research Corporations (FMRC) approval of the Envirotran
transformer line makes it easy to comply with and verify compliance
with Section 450.23, 2008 NEC, Less-Flammable Liquid-Filled
Transformer Requirements for both indoor and outdoor locations.

Solar transformer

Envirotran FM Approved transformers offer the user the benefit


of a transformer that can be easily specified to comply with NEC,
and makes FM Safety Data Sheet compliance simpler, while also
providing maximum safety and flexibility for both indoor and outdoor
installations.
Because the FM Approved logo is readily visible on the
transformer and its nameplate, NEC compliance is now easily
verifiable by the inspector.
Envirotran FM Approved transformers are manufactured under
strict compliance with FMRC Standard 3990 and are filled with
FM Approved EnvirotempFR3 fluid, a fire-resistant dielectric
coolant.

As a result of the increasing number of states that are adopting


aggressive Renewable & Alternative Energy Portfolio Standards,
the solar energy market is growingnearly doubling year over
year. Eatons Cooper Power Systems, a key innovator and supplier
in this expanding market, is proud to offer Envirotran transformers
specifically designed for Solar Photovoltaic medium-voltage
applications. Eatons Cooper Power Systems is working with top
solar photovoltaic developers, integrators and inverter manufacturers
to evolve the industry and change the way we distribute power.
In accordance with this progressive stance, every Eatons
Cooper Power Systems Envirotran Solar transformer is filled with
non-toxic, biodegradable EnvirotempFR3 dielectric fluid,
made from renewable seed oils. On top of its biodegradability,
EnvirotempFR3 fluid substantially extends the life of the
transformer insulation, saving valuable resources. What better way
to distribute green power than to use a green transformer. In fact,
delaying conversion to Envirotran transformers places the burden
of todays environmental issues onto tomorrows generations.
Eatons Cooper Power Systems can help you create a customized
transformer, based on site specific characteristics including:
temperature profile, site altitude, solar profile and required system
life. Some of the benefits gained from this custom rating include:

Reduction in core losses

Improved payback on investment

Reduction in footprint

Data Center transformer

Improved fire safety

With focus rapidly shifting from simply maximizing uptime and


supporting demand to improving energy utilization, the data
center industry is continually looking for methods to increase its
energy efficiency and reliability. Utilizing cutting edge technology,
Eatons Cooper Power Systems Hardened Data Center (HDC)
transformers are the solution. Designed with special attention given
to surge protection, HDC liquid-filled transformers provide superior
performance under the harshest electrical environments. Contrary
to traditional dry-type units, HDC transformers provide unsurpassed
reliability, overloadability, operational life, efficiency, thermal loading
and installed footprint. These Eatons Cooper Power Systems units
have reliably served more than 100 MW of critical data center
capacity for a total of more than 6,000,000 hours without any
reported downtime caused by a thermal or short-circuit coil failure.

Reduced environmental impact

The top priority in data center operations is uninterrupted service.


Envirotran HDC transformers from Eatons Cooper Power Systems,
having substantially higher levels of insulation, are less susceptible
to voltage surges. Eatons Cooper Power Systems has experienced
zero failures due to switching transients. The ANSI and IEEE
standard impulse withstand ratings are higher for liquid-filled
transformers, making them less susceptible to insulation failure.
The Envirotran HDC transformer provides ultimate protection by
increasing the BIL rating one level higher than standard liquid-filled
transformer ratings. The cooling system of liquid-filled transformers
provides better protection from severe overloadsoverloads that
can lead to significant loss of life or failure.

The United States Department of Energy (DOE) has mandated


efficiency values for most liquid type, medium voltage transformers.
As a result, all applicable Eatons Cooper Power Systems
transformers are designed to meet or exceed the standard efficiency
values per DOE 2010; Final Ruling, 10 CFR Part 431.

Special application transformers

Data center design typically includes multiple layers of redundancy,


ensuring maximum uptime for the critical IT load. When best in
class transformer manufacturing lead times are typically weeks, not
days, an unexpected transformer failure will adversely affect the
facilitys reliability and profitability. Therefore, the ability to determine
the electrical and mechanical health of a transformer can reduce
the probability of costly, unplanned downtime. Routine diagnostic
tests, including key fluid properties and dissolved gas analysis
(DGA), can help determine the health of a liquid-filled transformer.
Although sampling is not required for safe operation, it will provide
the user with valuable information, leading to scheduled repair or
replacement, and minimizing the duration and expense of an outage.
With a dry-type transformer, there is no reliable way to measure the
8

www.cooperpower.com

For the solar photovoltaic industry, Eatons Cooper Power Systems is


offering standard step up transformers and dual secondary designs,
including 4-winding, 3-winding (Low-High-Low) and 3-winding (LowLow-High) designs.

Wind transformer
Eatons Cooper Power Systems is offering custom designs for
renewable energy power generation. Eatons Cooper Power
Systems manufactures Generator Step-Up (GSU) transformers for
installation at the base of every wind turbine. Additionally, grounding
transformers are available for wind power generation.

DOE efficiency

Underwriters Laboratories (UL) Listed and Labeled/


Classified
The Envirotran transformer from Eatons Cooper Power Systems
can be specified as UL Listed & Labeled, and/or UL Classified.
Underwriters Laboratories (UL) listing is a verification of the
design and construction of the transformer to the ANSI and IEEE
standards. UL listing generally is the most efficient, cost-effective
solution for complying with relevant state and local electrical codes.
UL Combination Classification/Listing is another way in which
to comply with Section 450.23, 2008 NEC requirements. This
combines the UL listed transformer with a UL Classified LessFlammable Liquid and complies with the use restrictions found
within the liquid Classification.

Three-phase pad-mounted compartmental type transformer

Technical Data 210-12


Effective August 2013

K-Factor transformer

Inverter/rectifier bridge

With a drastic increase in the use of ferromagnetic devices, arcing devices, and electric power converters, higher frequency loads
have increased significantly. This harmonic loading has the potential
to generate higher heat levels within a transformers windings and
leads by as much as 300%. Harmonic loading has the potential to
induce premature failure in standard-design distribution transformers.

Eatons Cooper Power Systems complements its range of applications for transformers by offering dual winding designs. These
designs are intended for connection to 12-pulse rectifier bridges.

In addition to standard UL K-Factor ratings, transformers can be


designed to customer-provided specifications detailing precise loading scenarios. Onsite measurements of magnitude and frequency,
alongside harmonic analysis of the connected load can be performed
by Eatons Cooper Power Systems engineers or a third party consultant. These field measurements are used to determine exact customer needs and outline the transformer specifications.
Eatons Cooper Power Systems will design harmonic-resistant
transformers that will be subjected to the unique harmonic loads.
These units are designed to maintain normal temperature rise under
harmonic, full-load conditions. Standard UL K-Factor designs can
result in unnecessary costs when the next-highest K-Factor must
be selected for a calculated design factor. To save the customer
these unnecessary costs, Eatons Cooper Power Systems can design
the transformer to the specific harmonic spectrum used in the application. K-factor transformers from Eatons Cooper Power Systems
are filled with mineral oil or EnvirotempFR3 fluid and enjoy the
added benefits of dielectric cooling such as higher efficiencies than
dry-type transformers.

Modulation transformer
Bundled with an Outboard Modulation Unit (OMU) and a Control
and Receiving Unit (CRU), a Modulation Transformer Unit (MTU) is
designed to remotely achieve two way communication.
The use of an MTU reduces travel time and expense versus traditional meter reading performed by high voltage electricians.
Additionally, with MTU it is possible to manage and evaluate energy
consumption data, providing reduced metering costs and fewer tenant complaints.
An MTU utilizes existing utility infrastructure, therefore eliminating
the need to engineer and construct a dedicated communication network.

Product attributes
To set us apart from other transformer manufactures, Eatons Cooper
Power Systems includes the following guarantees with every threephase pad-mounted transformer.

Engineered to order (ETO)


Providing the customer with a well developed, cost-effective solution
is the number one priority at Eatons Cooper Power Systems. Using
customer specifications, Eatons Cooper Power Systems will work
with the customer from the beginning to the end to develop a solution to fit their needs. Whether it is application specific, site specific,
or a uniquely specified unit, Eatons Cooper Power Systems will
provide transformers with the best in class value and performance,
saving the customer time and money.

Made in the U.S.A.


Eatons Cooper Power Systems three-phase pad-mounted transformers are produced right here in the United States of America.
Our manufacturing facilities are positioned strategically for rapid
shipment of products. Furthermore, should the need arise, Eatons
Cooper Power Systems has a broad network of authorized service
repair shops throughout the United States.

Superior paint performance


Protecting transformers from natures elements worldwide,
Eatons Cooper Power Systems E-coat system provides unrivaled
transformer paint life, and exceeds IEEE Std C57.12.28-2005 and
IEEE Std C57.12.29-2005 standards. In addition to the outside of
the unit, each transformer receives a gray E-coat covering in the
interior of the tank and cabinet, providing superior rust resistance
and greater visibility during service.
If the wide range of standard paint selections does not suit the customers needs, Eatons Cooper Power Systems will customize the
paint color to meet their requirements.

Rectangular coil design


Eatons Cooper Power Systems utilizes a rectangular coil design. This
winding technique results in a smaller overall unit footprint as well
as reducing the transformer weight. The smaller unit size does not
hinder the transformer performance in the least. Units have proven
short circuit withstand capabilities up to 12 MVA.

Testing
Eatons Cooper Power Systems performs routing testing on each
transformer manufactured including the following tests:

Figure 9. Modular transformer.

Insulation Power Factor: This test verifies that vacuum processing


has thoroughly dried the insulation system to required limits.

Ratio, Polarity, and Phase Relation: Assures correct winding ratios


and tap voltages; checks insulation of HV and LV circuits. Checks
entire insulation system to verify all live-to-ground clearances.

Resistance: This test verifies the integrity of internal high-voltage


and low-voltage connections; provides data for loss upgrade calculations.

Applied Potential: Applied to both high-voltage and low-voltage


windings, this test stresses the entire insulation system to verify
all live-to-ground clearances.

Induced Potential: 3.46 times normal plus 1000 volts for reduced
neutral designs.

Loss Test: These design verification tests are conducted to assure


that guaranteed loss values are met and that test values are
within design tolerances. Tests include no-load loss and excitation
www.cooperpower.com

Technical Data 210-12

Three-phase pad-mounted compartmental type transformer

Effective August 2013

current along with impedance voltage and load loss.

 eak Test: Pressurizing the tank to 7 psig assures a complete


L
seal, with no weld or gasket leaks, to eliminate the possibility of
moisture infiltration or fluid oxidation.

Design performance tests


The design performance tests include the following:

Temperature Rise: Our automated heat run facility ensures that


any design changes meet ANSI and IEEE temperature rise
criteria.

Audible Sound Level: Ensures compliance with NEMA


requirements.

Lightning Impulse: To assure superior dielectric performance,


this test consists of one reduced wave, two chopped waves and
one full wave in sequence, precisely simulating the harshest
conditions.

Thomas A Edison Research and Test Facility


We are constantly striving to introduce new innovations to the
transformer industry, bringing you the highest quality transformer
for the lowest cost. Eatons Cooper Power Systems Transformer
Products are ISO 9001 compliant, emphasizing process improvement
in all phases of design, manufacture, and testing. We have invested
millions of dollars in the Thomas A. Edison Technical Center, our
premier research facility in Franksville, Wisconsin affirming our
dedication to introducing new innovations and technologies to the
transformer industry. Headquarters for the Systems Engineering
group of Eatons Cooper Power Systems, this research facility is fully
available for use by our customers to utilize our advanced electrical
and chemical testing labs.

10

www.cooperpower.com

Three-phase pad-mounted compartmental type transformer

Technical Data 210-12


Effective August 2013

www.cooperpower.com

11

Technical Data 210-12

Three-phase pad-mounted compartmental type transformer

Effective August 2013

Eaton
1000 Eaton Boulevard
Cleveland, OH 44122
United States
Eaton.com
Eatons Cooper Power Systems Business
2300 Badger Drive
Waukesha, WI 53188
United States
Cooperpower.com
2013 Eaton
All Rights Reserved
Printed in USA
Publication No. 210-12
August 2013

Eaton, Cooper Power Systems, MagneX,


UltraSIL, Evolution, and Envirotran are valuable
trademarks of Eaton in the U.S. and other
countries. You are not permitted to use the
these trademarks without the prior written
consent of Eaton.
IEEE Std C57.12.28-2005 and Std
C57.12.29-2005 standards are trademarks
of the Institute of Electrical and Electronics
Engineers, Inc., (IEEE). This publication is not
endorsed or approved by the IEEE.
IEEE is a registered trademark of the Institute
of Electrical and Electronics Engineers, Inc.
ANSI is a registered trademark of American
National Standards Institute.
National Electrical Code and NEC are
registered trademarks of the National Fire
Protection Association, Inc., Quincy, MA.
Underwriters Laboratories and UL are
registered trademarks of UL LLC.
FM Approved, FMRC, and Factory Mutual
Research Corporation are trademarks of FM
Global.
Envirotemp and FR3 are licensed
trademarks of Cargill, Incorporated.

3 - P H T R A NSF OR MER L E SS
S T R ING IN V ER T ER S

PVI 14TL
PVI 20TL
PVI 23TL
PVI 28TL
PVI 36TL
features
600 or 1000 VDC
Best-in-class efficiency
Touch-safe fuses
Quick and easy installation
Dual MPP tracking zones
Wide MPPT range
Lightweight, compact
design
Modbus communications

3-ph transformerless string inverters

User-interactive LCD

Solectria Renewables PVI 14TL, PVI 20TL, PVI 23TL, PVI 28TL, and PVI 36TL are

Integrated DC fused string


combiner

compact, transformerless three-phase inverters with a dual MPP tracker. These

DC arc-fault protection

inverters come standard with AC and DC disconnects, user-interactive LCD, and an


8-position string combiner. Its small, lightweight design makes for quick and easy

options

installation and maintenance. These inverters include an enhanced DSP control,

Web-based monitoring

comprehensive protection functions, and advanced thermal design enabling highest

Shade cover

reliability and uptime. They also come with a standard 10 year warranty with options

DC/AC disconnect covers

for 15 and 20 years. Options include web-based monitoring, shade cover, DC/AC

Roof mount array bracket

disconnect covers, DC combiners bypass, and roof mount array bracket.

DC combiners bypass

PVI 14TL

PVI 20TL

PVI 23TL

PVI 28TL

PVI 36TL

DC Input
Absolute Maximum Open Circuit Voltage

600 VDC

1000 VDC

Operating Voltage Range (MPPT)

180-580 VDC

260-580 VDC

Max Power Input Voltage Range (MPPT)

300-540 VDC

300-550 VDC

300-900 VDC
480-800 VDC

MPP Trackers

280-950 VDC

500-800 VDC

540-800 VDC

2 with 4-fused inputs per tracker

Maximum Operating Input Current

25 A per MPPT (50 A)

35 A per MPPT (70 A)

25 A per MPPT (50 A)

29 A per MPPT (58 A)

37.5 A per MPPT


(75 A)

Maximum Short Circuit Current

45 A per MPPT (90 A)

45.5 A per MPPT


(91 A)

41 A per MPPT (82 A)

48 A per MPPT (96 A)

60 A per MPPT
(120 A)

Maximum PV Power (per MPPT)

9.5 kW

13.5 kW

15.5 kW

19 kW

27 kW

Strike Voltage

300 V

330 V

AC Output
Nominal Output Voltage

208 VAC, 3-Ph

480 VAC, 3-Ph

AC Voltage Range (Standard)

-12%/+10%

Continuous Output Power (VAC)

14 kW

20 kW

23 kW

28 kW

36 kW

Maximum Output Current (VAC)

39 A

24 A

27.7 A

33.7 A

43 A

Maximum Backfeed Current

0A

Nominal Output Frequency

60 Hz

Output Frequency Range

59.3-60.5 Hz (adjustable 55-65 Hz)


Unity, >0.99
( 0.8 adjustable)

Power Factor

57-63 Hz

Unity, >0.99
( 0.9 adjustable)

Unity, >0.99
( 0.8 adjustable)

Total Harmonic Distortion (THD) @ Rated Load

< 3%

Grid Connection Type

3+/N/GND

Efficiency
Peak Efficiency

96.9%

97.4%

CEC Efficiency

96.0%

97.0%

98.0%

4W

2W

1W

Tare Loss

98.6%

98.5%

Integrated String Combiner


8 Fused Positions (4 positions per MPPT)

15 or 30 A
(30 A only for
combined inputs)

15 A (fuse by-pass available)

Temperature
-13F to +140F (-25C to +60C)
Derating occurs over +50C

Ambient Temperature Range

-13F to +140F (-25C to +60C)


Derating occurs over +45C
-22F to +158F
(-30C to +70C)

Storage Temperature Range


Relative Humidity (non-condensing)

-58F to +158F
(-50C to +70C)
0-95%

Operating Altitude

13,123 ft/4000 m (derating from 6,562 ft/2000 m)

Data Monitoring
Optional SolrenView Web-based Monitoring

Integrated

Optional Revenue Grade Monitoring

External

External Communication Interface

RS-485 Modbus RTU

Testing & Certifications


Safety Listings & Certifications

UL 1741/IEEE 1547, CSA C22.2#107.1, FCC part 15 B

Testing Agency

ETL

Warranty
Standard

10 year

Optional

15, 20 year; extended service agreement

Enclosure
dBA (Decibel) Rating

< 50 dBA @ 1m

AC/DC Disconnect
Dimensions (H x W x D)
Weight

Standard, fully-integrated
41.6 in. x 21.4 in. x 8.5 in.
(1057 mm x 543 mm x 216 mm)
141 lbs (64 kg)

39.4 in. x 23.6 in. x 9.1 in.


(1000 mm x 600 mm x 230 mm)

132 lbs (60 kg)

104 lbs (47.3 kg)

Enclosure Rating

Type 4

Enclosure Finish

Polyester powder coated aluminum

www.solectria.com | inverters@solectria.com | 978.683.9700

Copyright Solectria Renewables, LLC. All information subject to change without notice. January 2015 DOCR-070252-J

SPECIFICATIONS

Solidlock

Fixed Knot
Are you looking for an agricultural fence thats strong, virtually maintenance free, and comes in sizes suited for practically
all animals and applications?
Look no further than Solidlock.
Our fixed knot design combined with high tensile wire makes Solidlock the strongest woven wire fence you can buy.
This design locks the line wire and stay wire together, giving you the strength you require. Plus Solidlocks use of high
tensile wire and solid vertical stays means next to no maintenance. You can spend less time worrying about your fence
- whether you want to keep animals in or out.
Theres a Solidlock fence option to fit virtually any application you require. Our fence is available in varieties ranging
from 42 inches to 120 inches tall. We have larger staggered openings or smaller 3 x 3 inch openings for horse applications.
Solidlock fence is available in Class 3 (heavy coat) galvanized for long life. You can also get Solidlock with Bezinal +
Paint advanced coating. Choose either a black or green finish and enjoy the benefits of a product that will last four to
six times longer than a standard Class 1 fence.
23/120
8

Solidlock Game

Solidlock Cattle

available in 6 and 12 stay

available in 6 and 12 stay

Solidlock Horse
available in 3 stay

8
8

20/96

17/96

7
7

7
17/75

7
7

10/60

7
15/61

15/61

4
4
3
3
3
3
3
3

4
4
6
6

4
4
3
3
3
3
3
3

13/48

9/49

13/48

6
8/42

6
6
5
5

6
6
6
5
5

4
4
3
3
3
3
3
3

Solidlock 12.5g Game Fence


Fence
Design

Height

Vertical
Stay
Spacing

Roll
Length

Top and
Bottom Wire
Diameter

Main Wire
Diameter

118218
118257
118248
118269
118229
118280
118271
118288
118376
118241
118371
118318

1060 6
1060 12
1561 6
1775 6
1775 12
1796 6
2096 3
2096 6
2096 6
2096 12
2096 12
23120 6

60
60
61
75
75
96
96
96
96
96
96
120

6
12
6
6
12
6
3
6
6
12
12
6

330
660
330
330
330
330
165
330
500
330
660
330

12.5g
12.5g
12.5g
12.5g
12.5g
12.5g
12.5g
12.5g
12.5g
12.5g
12.5g
12.5g

12.5g
12.5g
12.5g
12.5g
12.5g
12.5g
12.5g
12.5g
12.5g
12.5g
12.5g
12.5g

210 lbs
294 lbs
279 lbs
327 lbs
236 lbs
355 lbs
340 lbs
396 lbs
601 lbs
264 lbs
564 lbs
492 lbs

Class 3
Class 3
Class 3
Class 3
Class 3
Class 3
Class 3
Class 3
Class 3
Class 3
Class 3
Class 3

136692
136261

2096 6
2096 6

96
96

6
6

330
330

12.5g
12.5g

12.5g
12.5g

396 lbs
396 lbs

Green
Black

Height

Vertical
Stay
Spacing

Roll
Length

Top and
Bottom Wire
Diameter

Main Wire
Diameter

42
42
42
49
49
49
48
48

6
12
12
6
12
12
6
12

330
330
660
330
330
660
330
330

12.5g
12.5g
12.5g
12.5g
12.5g
12.5g
12.5g
12.5g

12.5g
12.5g
12.5g
12.5g
12.5g
12.5g
12.5g
12.5g

Height

Vertical
Stay
Spacing

Roll
Length

Top and
Bottom Wire
Diameter

Main Wire
Diameter

48
48
61
61

3
3
3
3

100
200
100
200

Part
Number

Roll
Weight

Finish

Solidlock 12.5g Cattle Fence


Part
Number

118185
118144
118221
118199
118162
118239
118226
118310

Fence
Design

842 - 6
842 - 12
842 - 12
949 - 6
949 - 12
949 - 12
1348 - 6
1348 - 12

Roll
Weight

157 lbs
110 lbs
220 lbs
182 lbs
129 lbs
257 lbs
234 lbs
176 lbs

Finish

Class 3
Class 3
Class 3
Class 3
Class 3
Class 3
Class 3
Class 3

Solidlock 12.5g Horse Fence


Part
Number

118150
118225
118174
118249

Fence
Design

1348 - 3
1348 - 3
1561 - 3
1561 - 3

12.5g
12.5g
12.5g
12.5g

12.5g
12.5g
12.5g
12.5g

Roll
Weight

117 lbs
233 lbs
140 lbs
280 lbs

Finish

Class 3
Class 3
Class 3
Class 3

Solidlock 14g Sheep & Goat Fence


Part
Number

141324
137452
137453

Fence
Design

1048 - 3
1048 - 12
1048 - 12

Height

48
48
48

Vertical
Stay
Spacing
3
12
12

Roll
Length

165
330
660

Top and
Bottom Wire
Diameter
12.5g
12.5g
12.5g

Main Wire
Diameter

14g
14g
14g

Roll
Weight

109 lbs
105 lbs
210 lbs

Finish

Class 3
Class 3
Class 3

MAX POWER CS6X310|315|320P


Canadian Solars new Quartech modules have significantly raised the standard of module efficiency in
the solar industry. They introduced innovative four
busbar cell technology, which demonstrates higher
power output and higher system reliability.
Worldwide, our customers have embraced this next
generation of modules for their excellent performance, superior reliability and enhanced value.

NEW TECHNOLOGY
Reduces cell series resistance
Reduces stress between cell interconnectors
Improves module conversion efficiency
Improves product reliability

KEY FEATURES

insurance-backed warranty
non-cancellable, immediate warranty insurance
linear power output warranty
product warranty on materials
and workmanship
MANAGEMENT SYSTEM CERTIFICATES*
ISO 9001: 2008 / Quality management system

Higher energy yield


Outstanding performance at low irradiance
Maximum energy yield at low NOCT
Improved energy production through
reduced cell series resistance

ISO/TS 16949: 2009 / The automotive industry quality management system


ISO 14001: 2004 / Standards for environmental management system
OHSAS 18001: 2007 / International standards for occupational health & safety

PRODUCT CERTIFICATES*
IEC 61215 / IEC 61730: VDE/ MCS/ CE/ JET /SII/ KEMCO/ CEC AU/CQC/ INMETRO

UL 1703 / IEC 61215 performance: CEC listed (US)


Increased system reliability
Long term system reliability with IP67 UL 1703: CSA / IEC 61701 ED2: VDE / IEC 62716: VDE / IEC60068-2-68: SGS
PV CYCLE (EU) / UNI9177 Reaction to Fire: Class 1
junction box
Enhanced system reliability in extreme
temperature environment with special
* As there are different certification requirements in different markets, please contact
cell level stress release technology

your local Canadian Solar sales representative for the specific certificates applicable to
the products in the region in which the products are to be used.

Extra value to customers


Positive power tolerance up to 5 W
Stronger 40 mm robust frame to hold
snow load up to 5400 Pa and
wind load up to 2400 Pa
Anti-glare project evaluation
Salt mist, ammonia and blowing sand
resistance apply to seaside, farm and
desert environments

CANADIAN SOLAR INC. is committed to providing high quality


solar products, solar system solutions and services to customers
around the world. As a leading manufacturer of solar modules and
PV project developer with about 10 GW of premium quality
modules deployed around the world since 2001, Canadian Solar
Inc. (NAS-DAQ: CSIQ) is one of the most bankable solar companies
worldwide.

CANADIAN SOLAR INC.


545 Speedvale Avenue West, Guelph, Ontario N1K 1E6, Canada, www.canadiansolar.com, support@canadiansolar.com

MODULE / ENGINEERING DRAWING (mm)


Rear View

CS6X-310P / I-V CURVES

Frame Cross Section A-A


35

40

10

1954
1400
1155

Grounding
hole
25

A
10

11
8-11 7 -

Mounting
hole

Mounting Hole

5 10 15 20 25 30 35 40 45

V
5 10 15 20 25 30 35 40 45 50

7
R

ELECTRICAL DATA / STC*


Electrical Data CS6X
Nominal Max. Power (Pmax)
Opt. Operating Voltage (Vmp)
Opt. Operating Current (Imp)
Open Circuit Voltage (Voc)
Short Circuit Current (Isc)
Module Eciency
Operating Temperature
Max. System Voltage
Module Fire Performance

Max. Series Fuse Rating
Application Classification
Power Tolerance

11

40

932
982

310P
315P
320P
310 W
315W
320 W
36.4 V
36.6V
36.8 V
8.52 A
8.61A
8.69 A
44.9 V
45.1V
45.3 V
9.08 A
9.18A
9.26 A
16.16% 16.42 % 16.68 %
-40C ~ +85C
1000 V (IEC)or1000V ( UL)
TYPE 1 (UL 1703) or
CLASS C (IEC 61730)
15 A
Class A
0~+5W

* Under Standard Test Conditions (STC) of irradiance of 1000 W/m2, spectrum AM


1.5 and cell temperature of 25C.

ELECTRICAL DATA / NOCT*


Electrical Data CS6X
Nominal Max. Power (Pmax)
Opt. Operating Voltage (Vmp)
Opt. Operating Current (Imp)
Open Circuit Voltage (Voc)
Short Circuit Current (Isc)

310P
225 W
33.2 V
6.77 A
41.3 V
7.36 A

315P
228 W
33.4 V
6.84 A
41.5 V
7.44 A

320P
232 W
33.6 V
6.91 A
41.6 V
7.50 A

* Under Nominal Operating Cell Temperature (NOCT), irradiance of 800 W/m2,


spectrum AM 1.5, ambient temperature 20C, wind speed 1 m/s.

1000 W/m2
800 W/m2
600 W/m2
400 W/m2

5C
25C
45C
65C

MODULE / MECHANICAL DATA


Specification
Data
Cell Type
Poly-crystalline, 6 inch
Cell Arrangement 72 (6 12)
Dimensions
1954 982 40 mm (76.93 38.7 1.57 in)
Weight
22 kg (48.5 lbs)
Front Cover
3.2 mm tempered glass
Frame Material
Anodized aluminium alloy
J-BOX
IP67, 3 diodes
Cable
4 mm2 (IEC) or 4 mm2 & 12 AWG
1000 V (UL), 1150 mm(45.3 in)
Connectors
MC4 or MC4 comparable
Stand. Packaging 26 pcs, 620 kg

(quantity & weight per pallet)
Module Pieces
624 pcs (40 HQ)
per Container

TEMPERATURE CHARACTERISTICS
Specification
Temperature Coecient (Pmax)
Temperature Coecient (Voc)
Temperature Coecient (Isc)
Nominal Operating Cell Temperature

PARTNER SECTION

PERFORMANCE AT LOW IRRADIANCE


Industry leading performance at low irradiation, +96.0 %
module efficiency from an irradiance of 1000 W/m2 to
200 W/m2 (AM 1.5, 25C).
The specification and key features described in this Datasheet may deviate slightly
and are not guaranteed. Due to on-going innovation, research and product
enhancement, Canadian Solar Inc. reserves the right to make any adjustment to
the information described herein at any time without notice. Please always obtain
the most recent version of the datasheet which shall be duly incorporated into
the binding contract made by the parties governing all transactions related to the
purchase and sale of the products described herein.
Caution: For professional use only. The installation and handling of PV modules
requires professional skills and should only be performed by qualified professionals.
Please read the safety and installation instructions before using the modules.

CANADIAN SOLAR INC. July 2015. All rights reserved, PV Module Product Datasheet I V5.2_EN

Data
-0.43% / C
-0.34% / C
0.065% / C
452C

NEXTracker 120

A Breakthrough in Solar PV Tracking


NEXTracker120 is a unique balanced-mass, independent row horizontal tracker
designed for both crystalline silicon and thin film modules. Its innovative
and robust design significantly reduces foundations, enables longer rows, and
supports wider rotation angles. This eliminates many of the design, cost and
performance compromises inherent in linked-row trackers.

Lower Installation Costs with Fewer Foundations and No Grounding


NEXTracker120s balanced design requires 25-50% fewer foundations than conventional trackers, and allows
33% longer rows. This cuts material and installation costs, lowers geotechnical risk and accelerates project schedules.
NEXTracker120 is also self-grounding, eliminating added parts and installation steps.

More Site Flexibility and Less Site Preparation


NEXTracker120s independently-driven rows free developers from the rectilinear constraints of typical linked-row
trackers, allowing 10-30% more power capacity per site. The elimination of linkages between rows significantly reduces
grading and access lanes.

Lower Installation Costs with Fewer Foundations and No Grounding


NEXTracker120s balanced design aligns the modules with the tracking axis, reducing drive system wear, and requires
80% less power to operate compared to conventional systems. In addition, the wide 120 range of motion combined with
greater layout flexibility can increase energy yield by up to 2%.

Reduced Operating Costs with Greater Safety and Security


NEXTracker120s unlinked rows allow unimpeded maintenance access for 5 times faster cleaning and inspection.
NeXTracker120 stows much faster than conventional trackers, with ultra-low backup power (if required) and includes antitheft mounting hardware.
NEXTracker, Inc. Contents subject to change without notice.

May 2015

NEXTracker Product Features


Tracking Technology:

Horizontal single-axis balanced-mass tracker with independently-driven rows

Control System:

Closed-loop control per each row for maximum accuracy

Communications:

Wireless Zigbee mesh network/SCADA; no communication wiring required

Module Compatability:

Framed or frameless c-Si and thin film modules; portrait and landscape mounting options

Modules per Row:

80 72-cell c-Si modules mounted in portrait/ 210 CdTe modules mounted in landscape

DC Capacity:

23-35kWp per tracker (row) depending on module type

Standard Wind Design:


100mph/161kph, 3 second gust with 30psf snow load per ASCE 7-10, 0; configurable for
higher wind speeds and snow loads

Wind Protection:

Wind stow mode (user-configurable)

Torsional Limiter:

Included at every foundation/bearing; provides additional wind protection

Rotational Range:

58 (up to 60 possible depending on dead-band settings and installation tolerances)

Drive System:

One slew gear and 24V DC motor per row

Power Consumption:

< 80kWh/MWp/year (motor)

Foundation Types:

Compatible with all major foundation types (driven pier, concrete foundation, ground screw)

Ground Coverage Ratio:

Any: fully configurable by customer; typical range form 33%-50%

Principal Materials:

Galvanized and stainless steel

Installation Method:

Rapid field assembly, no welding required

Grounding Method:

Tracker is self-grounding; no grounding materials or labor required

Compliance:

Grounding/bonding: UL2703; Structural design; ASCE7-10

Other Available Options:

Snow and flood stowing sensors

Warranty:

10 years on structural components, 5 years on drive and control systems

Typical Dimensions:

Height 2.1m/6.8ft (@ 60), Width 2.0m/6.4 ft, Lenght 85m/283 ft


Please refer to NEXTracker engineering documentation for definitive technical specifications

Typical 72-cell c-Si configuration: 85m row with 80 modules mounted in portrait:

6.4ft
[1.96m]

6.8ft
[2.08m]
4.0ft
[1.22m]

60

3.3ft
[1.00m]

6200 Paseo Padre Parkway


Fremont, CA 94555 USA

1.2ft
[.36m]

NEXTracker, Inc. Contents subject to change without notice.

+1 510 270 2500


www.nextracker.com
May 2015

S-ar putea să vă placă și