Meeting Date:
December 1, 2016
Applicant:
To allow drive-through window and to construct two (2) multi-tenant retail buildings
Existing Zoning:
Parcel ID Number:
16-B-038-0-00-022-0
Location:
Size:
A 4,804 sq. ft. and 7,776 sq. ft. building on a 1.59-acre site
Public Utilities:
Engineering Comments:
BUILDING
{B6*} A Building Permit is required for new buildings. Plans shall be submitted for permit review by the Chief
Building Official for conformance with the Ohio Building Code and necessary permits obtained.
As part of an agreement between Shibley Properties and the City of Mentor, the building slab and sanitary
sewer lateral from the former Parks garage shall be removed.
STORMWATER/SUBDIVISION
{ST4} Stormwater detention required per City Ordinance. Calculations for drainage and detention required for
City review and approval.
{ST8} Provide emergency overflow for proposed detention facility.
/var/www/apps/conversion/tmp/scratch_5/338735437.doc
CUP-11-16-7247, SITE-08-16-7034
{ST16} Site may be subject to NPDES Stormwater Permit requirements if over 1 acre of land disturbance
occurs. Copy of permit or permit application required prior to start of construction.
{ST17} Site may be subject to City stormwater quality requirements if over 1 acre of land disturbance occurs.
Site plan shall detail the installation and long term maintenance plan of post-construction best
management practices to manage stormwater quality per City requirements.
{ST18} Erosion control plan including schedule for installation to be included in construction plans. (Refer to
Chapter 1353 of the Mentor Code of Ordinances)
{ST26} Storm sewer design shall be based on a minimum 2-year frequency, with a hydraulic gradient check at a
10-year frequency showing no surcharging. Drainage calculations shall be provided for review and shall
be sealed by a registered professional engineer.
(ST27) BMP Maintenance Agreement for stormwater management practices shall be submitted with permit
application. Typical agreement form available upon request.
Offsite stormwater discharge requires easement from adjacent property owner (City of Mentor).
CIVIL/SITE
{CS1} Final site plan to conform to City standards (available upon request) as part of next submittal.
{CS7}*All utilities servicing site shall be bored under Center Street as necessary.
{CS9}*If pavement open cut is proposed for any utility on Center Street, it will require approval from Mentor
City Council. Right-of-way permit and Council approval to be coordinated through City Engineering
Department.
{CS11} All easements and ownership rights over subject property shall be identified on site plan.
{CS14} All existing utilities and proposed service connections shall be indicated on plan in their entirety.
{CS19} If any existing drive apron is to be abandoned, reconstruct curb to match adjacent curbing. Area behind
curb shall be restored.
Right in/right out drives shall be signed and constructed to City standards.
Provide details on plans.
Provide engineering site plan that is scalable and provide dimensioning for all drives, parking spaces and
drive aisles.
TRAFFIC
{T1} Provide copies of filed cross easements between adjoining properties to permit traffic movement as
proposed and required by permit plan.
(T2.1) The applicant pursuant to 1133.05(f) or 1113.02(p) of the Mentor Code of Ordinances is required to
provide a trip generation study.
(C6)
Handicap parking with van accessibility and curb ramps shall be provided and be designed in accordance
with Chapter 11 of the Ohio Building Code. Handicap signing and mounting heights shall be detailed on
the plans. Signs shall be mounted to a 7 height to bottom of sign.
(T9)
Provide dimensions for all parking stalls and aisles. Parking stalls shall be a minimum of 9 X 18.
(Mentor Code of Ordinances 1173.02 and 1173.05(c))
Provide cross access easements for access to Yours Truly parcel and both subject parcels. Provide a
revocable license agreement for the City park driveway.
Applicant shall provide written confirmation and plan modifications with next submittal as to the disposition of each
of the above comments.
CUP-11-16-7247, SITE-08-16-7034
5.
6.
The proposed fire pit table for Yours Truly shall comply with the OFC and be listed for the use proposed.
For Yours Truly, sprinkler protection is required when an A-2 use group exceeds 5,000 sq. ft. and / or 100
occupants, which it appears it does.
CUP-11-16-7247, SITE-08-16-7034
CUP-11-16-7247, SITE-08-16-7034
/var/www/apps/conversion/tmp/scratch_5/338735437.doc
CUP-11-16-7247, SITE-08-16-7034