3.1 Wiring
Shielded cables are preferred for the installation.
The wire must be min 0,5mm2 for input signals and min 1mm2 for supply and output cables.
Max distance between control system and power unit is 50m.

3.2 Supply

SUPPLY VOLTAGE & HEATER


HEATER WITH THERMOSTAT
SUPPLIED AS OPTION

The contents of this information are subject to change without notice or obligation. Information herein should be confirmed before placing orders.

Hgglunds Drives AB. S-890 42 Mellansel, SWEDEN

1(30)

AS-3

Connection, Engineering manual

04-04-02

3.3 Input signals


3.3.1. Remote speed setpoint.
The input for remote speed setpoint are isolated and can be bidirectional (forward and reverse
speed setpoint) or unidirectional (forward speed setpoint and fixed reverse speed if needed).
The setpoint can be a voltage or a current signal. The selection is made with a jumper on the
board (see also AS4.3) and in the set up menu (see AS5.2.6).

SETPOINT DRIVE 1

The contents of this information are subject to change without notice or obligation. Information herein should be confirmed before placing orders.

Hgglunds Drives AB. S-890 42 Mellansel, SWEDEN

2(30)

AS-3

Connection, Engineering manual

04-04-02

SETPOINT DRIVE 2

The contents of this information are subject to change without notice or obligation. Information herein should be confirmed before placing orders.

Hgglunds Drives AB. S-890 42 Mellansel, SWEDEN

3(30)

AS-3

Connection, Engineering manual

04-04-02

3.3.2.1 Configurable isolated analog inputs.


The signal for the configurable analog inputs must be positive. The input can be a voltage or
a current signal. The selection is made with a jumper on the board (see also AS4.3) and in
the set up menu (see AS5.2.6).

CONFIGURABLE ANALOG INPUT 1

CONFIGURABLE ANALOG INPUT 2

The contents of this information are subject to change without notice or obligation. Information herein should be confirmed before placing orders.

Hgglunds Drives AB. S-890 42 Mellansel, SWEDEN

4(30)

AS-3

Connection, Engineering manual

04-04-02

3.3.2.2 Configurable analog inputs.


The signal for the configurable analog inputs must be positive. The input can be a voltage or
a current signal. The selection is made with a jumper on the board (see AS4.5.2) and in the
set up menu (see AS5.2.6).

CONFIGURABLE ANALOG INPUT 3

CONFIGURABLE ANALOG INPUT 4

The contents of this information are subject to change without notice or obligation. Information herein should be confirmed before placing orders.

Hgglunds Drives AB. S-890 42 Mellansel, SWEDEN

5(30)

AS-3

Connection, Engineering manual

04-04-02

CONFIGURABLE ANALOG INPUT 5

CONFIGURABLE ANALOG INPUT 6

The contents of this information are subject to change without notice or obligation. Information herein should be confirmed before placing orders.

Hgglunds Drives AB. S-890 42 Mellansel, SWEDEN

6(30)

AS-3

Connection, Engineering manual

04-04-02

CONFIGURABLE ANALOG INPUT 7

CONFIGURABLE ANALOG INPUT 8

The contents of this information are subject to change without notice or obligation. Information herein should be confirmed before placing orders.

Hgglunds Drives AB. S-890 42 Mellansel, SWEDEN

7(30)

AS-3

Connection, Engineering manual

04-04-02

CONFIGURABLE ANALOG INPUT 9

CONNECTION OF ANALOG 2-WIRE SENSOR

The contents of this information are subject to change without notice or obligation. Information herein should be confirmed before placing orders.

Hgglunds Drives AB. S-890 42 Mellansel, SWEDEN

8(30)

AS-3

Connection, Engineering manual

04-04-02

3.3.2.3 Tank temperature analog input.


The tank temperature can be measured with a PT100 sensor.

PT-100 TANK TEMPERATURE INPUT

The contents of this information are subject to change without notice or obligation. Information herein should be confirmed before placing orders.

Hgglunds Drives AB. S-890 42 Mellansel, SWEDEN

9(30)

AS-3

Connection, Engineering manual

04-04-02

3.3.3. Digital speed encoder.


If a differential encoder is used and the input 2 pulse comes before the input 1 pulse, the Rpm
signal will be positive.
If a single pulse encoder is used, a low level on the direction signal will give positive sign of
the Rpm signal. If the signal has wrong sign the polarity can be changed with parameter P1I06
for drive 1 and parameter P2I06 for drive 2.

DIGITAL SPEED ENCODER DRIVE 1

The contents of this information are subject to change without notice or obligation. Information herein should be confirmed before placing orders.

Hgglunds Drives AB. S-890 42 Mellansel, SWEDEN

10(30)

AS-3

Connection, Engineering manual

04-04-02

DIGITAL SPEED ENCODER DRIVE 2

The contents of this information are subject to change without notice or obligation. Information herein should be confirmed before placing orders.

Hgglunds Drives AB. S-890 42 Mellansel, SWEDEN

11(30)

AS-3

Connection, Engineering manual

04-04-02

3.3.4. Electric motor started inputs.


The inputs must be high (switch closed) when the motor is stopped and open at motor start.
The inputs are used for bypass of charge pressure alarm and delay of drive start.

INPUT SIGNALS FROM STARTER UNIT

The contents of this information are subject to change without notice or obligation. Information herein should be confirmed before placing orders.

Hgglunds Drives AB. S-890 42 Mellansel, SWEDEN

12(30)

AS-3

Connection, Engineering manual

04-04-02

3.3.5. Emergency stop input.


Emergency stop input must be connected for the system to operate. If the input is opened, the
output to fte pumps will be set to zero without ramp to destroke the pumps as quickly as
possible.The electric motor interlock contacts will open after a time delay set with parameter
DMD 0x and with a rotary switch on top left of main board (see AS4.5.4).

EMERGENCY STOP INPUT

The contents of this information are subject to change without notice or obligation. Information herein should be confirmed before placing orders.

Hgglunds Drives AB. S-890 42 Mellansel, SWEDEN

13(30)

AS-3

Connection, Engineering manual

04-04-02

3.3.6. Configurable digital inputs.


The input functions are configured in the set up menu (see AS5.2.3). All inputs are
configurable but the first 24 inputs are as first choice selected for monitoring of the power unit
switches.

DIGITAL INPUT SIGNALS

The contents of this information are subject to change without notice or obligation. Information herein should be confirmed before placing orders.

Hgglunds Drives AB. S-890 42 Mellansel, SWEDEN

14(30)

AS-3

Connection, Engineering manual

04-04-02

DIGITAL INPUT SIGNALS

The contents of this information are subject to change without notice or obligation. Information herein should be confirmed before placing orders.

Hgglunds Drives AB. S-890 42 Mellansel, SWEDEN

15(30)

AS-3

Connection, Engineering manual

04-04-02

DIGITAL INPUT SIGNALS

The contents of this information are subject to change without notice or obligation. Information herein should be confirmed before placing orders.

Hgglunds Drives AB. S-890 42 Mellansel, SWEDEN

16(30)

AS-3

Connection, Engineering manual

04-04-02

3.4 Output signals


3.4.1. Pump strokers.

Pumps with separate coils for A and B side can be used. If pumps with a common coil for both
directions is used, the drive can only be controlled in one direction.

The contents of this information are subject to change without notice or obligation. Information herein should be confirmed before placing orders.

Hgglunds Drives AB. S-890 42 Mellansel, SWEDEN

17(30)

AS-3

Connection, Engineering manual

04-04-02

3.4.2. Starter interlock outputs.


The normally open contact of the auxiliary relay must be connected in the stop circuit for the
electric motors. The output will open at alarm.
Note! The polarity for the freewheeling diode over the relay coil. The function of the diode is to
protect against induced voltage at switch off and should be mounted close to the relay coil.

STARTER INTERLOCK

The contents of this information are subject to change without notice or obligation. Information herein should be confirmed before placing orders.

Hgglunds Drives AB. S-890 42 Mellansel, SWEDEN

18(30)

AS-3

Connection, Engineering manual

04-04-02

The contents of this information are subject to change without notice or obligation. Information herein should be confirmed before placing orders.

Hgglunds Drives AB. S-890 42 Mellansel, SWEDEN

19(30)

AS-3

Connection, Engineering manual

04-04-02

3.4.3. Configurable digital outputs.


The output functions are configured in the set up menu (see AS5.2.4).

DIGITAL OUTPUT SIGNALS

Note! All outputs must be protected against induced voltage at switch off by e.g. free wheeling
diode (see 3.4.2), varistor, RC circuit or other overvoltage protection device mounted close to
the load.

The contents of this information are subject to change without notice or obligation. Information herein should be confirmed before placing orders.

Hgglunds Drives AB. S-890 42 Mellansel, SWEDEN

20(30)

AS-3

Connection, Engineering manual

04-04-02

3.4.4. Configurable analog outputs.


The outputs are isolated and needs external supply. If no isolation is needed the card can be
supplied from Spider terminals. The output functions are configured in the set up menu (see
AS5.2.7).

CONFIGURABLE ANALOG OUTPUT 1

CONFIGURABLE ANALOG OUTPUT 2

The contents of this information are subject to change without notice or obligation. Information herein should be confirmed before placing orders.

Hgglunds Drives AB. S-890 42 Mellansel, SWEDEN

21(30)

AS-3

Connection, Engineering manual

04-04-02

CONFIGURABLE ANALOG OUTPUT 3

CONFIGURABLE ANALOG OUTPUT 4

The contents of this information are subject to change without notice or obligation. Information herein should be confirmed before placing orders.

Hgglunds Drives AB. S-890 42 Mellansel, SWEDEN

22(30)

AS-3

Connection, Engineering manual

04-04-02

3.5 Interconnection terminal


For internal connection use.

INTERCONNECTION TERMINAL

The contents of this information are subject to change without notice or obligation. Information herein should be confirmed before placing orders.

Hgglunds Drives AB. S-890 42 Mellansel, SWEDEN

23(30)

AS-3

Connection, Engineering manual

04-04-02

3.6 Serial ports


3.6.1. SpiderCom port.
Connector for RS232 serial communication. Port is used for log data dump and for setup of system
via a PC and SpiderCom software.

SERIAL CONNECTOR PINOUT

Pin1
Pin2
Pin3
Pin4
Pin5
Pin6
Pin7
Pin8
Pin9

CD, Carrier detect


RXD, Receive data
TXD, Transmit data
DTR, Data terminal ready
GND, System ground
DSR, Data set ready
RTS, Request to send
CTS, Clear to send
RI, Ring indicator

3.6.2. Optional fieldbus connection.


Profibus connection for external serial control

PROFIBUS CONNECTOR PINOUT

Pin1
Pin2
Pin3
Pin4
Pin5
Pin6
Pin7
Pin8
Pin9

Not connected
Not connected
B-line, Pos TXD/RXD
RTS, Request to send
GND BUS
+5V BUS
Not connected
A-line, Neg TXD/RXD
Not connected

The contents of this information are subject to change without notice or obligation. Information herein should be confirmed before placing orders.

Hgglunds Drives AB. S-890 42 Mellansel, SWEDEN

24(30)

AS-3

Connection, Engineering manual

04-04-02

The contents of this information are subject to change without notice or obligation. Information herein should be confirmed before placing orders.

Hgglunds Drives AB. S-890 42 Mellansel, SWEDEN

25(30)

AS-3

Connection, Engineering manual

04-04-02

3.7 Terminal functions


Table of terminal functions.
Row Type
1 Power Input

Name
DC1

Pump 4

PO4

Pump 3

PO3

Pump 2

PO2

Pump 1

PO1

Digital outputs

DO1

No.
4
3
2
1
4
3
2
1
4
3
2
1
4
3
2
1
4
3
2
1

Function
24V_IN (+)
24V_IN (+)
GND (-)
GND(-)
Common pump 4
Stroker conn. Pump 4. High B
Common pump 4
Stroker conn. Pump 4. High A
Common pump 3
Stroker conn. Pump 3. High B
Common pump 3
Stroker conn. Pump 3. High A
Common pump 2
Stroker conn. Pump 2. High B
Common pump 2
Stroker conn. Pump 2. High A
Common pump 1
Stroker conn. Pump 1. High B
Common pump 1
Stroker conn. Pump 1. High A

14
13
12
11
10
9
8
7
6
5
4
3
2
1

Configurable Digital output 6


Configurable Digital output 6
Configurable Digital output 5
Configurable Digital output 5
Configurable Digital output 4
Configurable Digital output 4
Configurable Digital output 3
Configurable Digital output 3
Configurable Digital output 2
Configurable Digital output 2
Configurable Digital output 1
Configurable Digital output 1
24V_DO
GND

The contents of this information are subject to change without notice or obligation. Information herein should be confirmed before placing orders.

Hgglunds Drives AB. S-890 42 Mellansel, SWEDEN

26(30)

AS-3

Connection, Engineering manual

Row Type
3 Digital outputs

Name
DO2

No.
14
13
12
11
10
9
8
7
6
5
4
3
2
1

EO1

8
7
6
5
4
3
2
1

Interlock Electric motor 3


Interlock Electric motor 3
Interlock Electric motor 2
Interlock Electric motor 2
Interlock Electric motor 1
Interlock Electric motor 1
24V_DO
GND

8
7
6
5
4
3
2
1

E-motor 3 started
E-motor 2 started
E-motor 1 started
24V_EI
24V_EI
GND
Em.stop
24V_EM

04-04-02

Function
Configurable Digital output 13
Configurable Digital output 12
Configurable Digital output 11
Common Digital output 11-13
Configurable Digital output 10
Configurable Digital output 10
Configurable Digital output 9
Configurable Digital output 9
Configurable Digital output 8
Configurable Digital output 8
Configurable Digital output 7
Configurable Digital output 7
24V_DO
GND

E-motor interlocks

E-motor started
inputs

EI

Em stop

EM

Digital speed
encoder Drive 1

DE1

8
7
6
5
4
3
2
1

Pulse 0 Drive 1+
Pulse 2 Drive 1 Pulse 2 Drive 1+
Pulse 1 Drive 1 Pulse 1 Drive 1+
12V+
24V_DE
GND

Digital speed
encoder Drive 2

DE2

8
7
6
5
4
3
2
1

Pulse 0 Drive 2+
Pulse 2 Drive 2 Pulse 2 Drive 2+
Pulse 1 Drive 2 Pulse 1 Drive 2+
12V+
24V_DE
GND

The contents of this information are subject to change without notice or obligation. Information herein should be confirmed before placing orders.

Hgglunds Drives AB. S-890 42 Mellansel, SWEDEN

27(30)

AS-3

Connection, Engineering manual

Row Type
8 Configurable
digital inputs
Predefined
monitoring inputs

10

11

Name
DI1

No.
8
7
6
5
4
3
2
1

Function
Config input 6
Config input 5
Config input 4
Config input 3
Config input 2
Config input 1
24V_DI_1
GND

Configurable
digital inputs
Predefined
monitoring inputs

DI2

12
11
10
9
8
7
6
5
4
3
2
1

Config input 15
Config input 14
Config input 13
Config input 12
Config input 11
Config input 10
Config input 9
Config input 8
Config input 7
24V_DI_1
24V_DI_1
GND

Configurable
digital inputs
Predefined
monitoring inputs

DI3

12
11
10
9
8
7
6
5
4
3
2
1

Config input 24
Config input 23
Config input 22
Config input 21
Config input 20
Config input 19
Config input 18
Config input 17
Config input 16
24V_DI_1
24V_DI_1
GND

Configurable
digital inputs

DI4

12
11
10
9
8
7
6
5
4
3
2
1

Config input 33
Config input 32
Config input 31
Config input 30
Config input 29
Config input 28
Config input 27
Config input 26
Config input 25
24V_DI_2
24V_DI_2
GND

04-04-02

(Drain filter)
(Low oil level in tank)
(Min oil level in tank)
(Min oil temperature in tank)
(High oil temperature in tank)
(Max oil temperature in tank)

(Work pressure, pump 2)


(Charge pressure, pump 2)
(Suction line, pump 2)
(Return filter 100%, pump 2)
(Work pressure, pump 1)
(Charge pressure, pump 1)
(Suction line, pump 1)
(Return filter 100%, pump 1)

(Work pressure, pump 4)


(Charge pressure, pump 4)
(Suction line, pump 4)
(Return filter 100%, pump 4)
(Work pressure, pump 3)
(Charge pressure, pump 3)
(Suction line, pump 3)
(Return filter 100%, pump 3)

The contents of this information are subject to change without notice or obligation. Information herein should be confirmed before placing orders.

Hgglunds Drives AB. S-890 42 Mellansel, SWEDEN

28(30)

AS-3

Connection, Engineering manual

Row Type
12 Configurable
digital inputs

Name
DI5

No.
12
11
10
9
8
7
6
5
4
3
2
1

Function
Config input 43
Config input 42
Config input 41
Config input 40
Config input 39
Config input 38
Config input 37
Config input 36
Config input 35
Config input 34
24V_DI_2
GND

13

Analog inputs
Isolated

AI1

12
11
10
9
8
7
6
5
4
3
2
1

Config input 2 Config input 2+


Config input 1 Config input 1+
Remote speed setpoint Drive 2 Remote speed setpoint Drive 2 +
Remote speed setpoint Drive 1 Remote speed setpoint Drive 1 +
Isolated 10VREF Isolated 10VREF+
Isolated GND
Isolated GND

14

Analog inputs
Not isolated

AI2

12
11
10
9
8
7
6
5
4
3
2
1

Config input 6 Config input 6+


Config input 5 Config input 5+
Config input 4 Config input 4+
Config input 3 Config input 3+
24V_AI
24V_AI
GND
GND

04-04-02

The contents of this information are subject to change without notice or obligation. Information herein should be confirmed before placing orders.

Hgglunds Drives AB. S-890 42 Mellansel, SWEDEN

29(30)

AS-3

Connection, Engineering manual

Row Type
15 Analog inputs
Not isolated

16

Analog outputs

Name
AI3

No.
14
13
12
11
10
9
8
7
6
5
4
3
2
1

AO2

6
5
4
3
2
1
6
5
4
3
2
1

Current output 4
Voltage output 4
Current output 3
Voltage output 3
24VDC (externally supplied)
GND (external)
Current output 2
Voltage output 2
Current output 1
Voltage output 1
24VDC (externally supplied)
GND (external)

8
7
6
5
4
3
2
1
6
5
4
3
2
1

DATA2NC
DATA2+
0VCAN2
DATA1NC
DATA1+
0VCAN1
For interconnection purpose
For interconnection purpose
For interconnection purpose
For interconnection purpose
For interconnection purpose

AO1

17

CAN1

CA

CAN2

Spare terminals

IC

04-04-02

Function
Tank temp, force high
Tank temp, sense high
Tank temp, sense low
Tank temp, force low
Config input 9 Config input 9+
Config input 8 Config input 8+
Config input 7 Config input 7+
24V_AI
24V_AI
GND
GND

For interconnection purpose