Sunteți pe pagina 1din 50

6HUYLFH0DQXDO

02'(/A16CM4H4R18
A16CM4H4R24
A16CM4H4R30
 5HIULJHUDQW5$ 

Downloaded from www.Manualslib.com manuals search engine

7DEOHRI&RQWHQWV

7DEOHRI&RQWHQWV
6XPPDU\DQG)HDWXUHV
6DIHW\3UHFDXWLRQV
6SHFLFDWLRQV
&RQVWUXFWLRQ9LHZV
5HIULJHUDQW6\VWHP'LDJUDP
6FKHPDWLF'LDJUDP
(OHFWULFDO'DWD
(OHFWULFDO:LULQJ
3ULQWHG&LUFXLW%RDUG 

)XQFWLRQDQG&RQWURO
,QVWDOODWLRQ0DQXDO
,QVWDOODWLRQ'LPHQVLRQ'LDJUDP
,QVWDOOLQJ7KH2XWGRRU8QLW
(OHFWULFDO&RQQHFWLRQV
&KHFN$IWHU,QVWDOODWLRQ

([SORGHG9LHZVDQG3DUWV/LVW
7URXEOHVKRRWLQJ
0DOIXQFWLRQ,QGLFDWRU
0DOIXQFWLRQ&KHFNLQJDQG(OLPLQDWLRQ

5HPRYDO3URFHGXUH
5HPRYDO3URFHGXUH . 
5HPRYDO3URFHGXUH .. 

Downloaded from www.Manualslib.com manuals search engine

6XPPDU\DQG)HDWXUHV

6XPPDU\DQG)HDWXUHV

2XWGRRU8QLW
A16CM4H4R18

A16CM4H4R24
A16CM4H4R30


Downloaded from www.Manualslib.com manuals search engine

6DIHW\3UHFDXWLRQV

6DIHW\3UHFDXWLRQV
Installing, starting up, and servicing air conditioner can be
hazardous due to system pressure, electrical components,
and equipment location, etc.
Only trained, qualified installers and service personnel are
allowed to install, start-up, and service this equipment.
Untrained personnel can perform basic maintenance functions such as cleaning coils. All other operations should
be performed by trained service personnel.

Make sure the outdoor unit is installed on a stable, level


surface with no accumulation of snow, leaves, or trash
beside.

When handling the equipment, observe precautions in the


manual and on tags, stickers, and labels attached to the
equipment. Follow all safety codes. Wear safety glasses
andwork gloves. Keep quenching cloth and fire extinguisher
nearby when brazing.

Follow all the installation instructions to minimize the risk


of damage from earthquakes, typhoons or strong winds.

Read the instructions thoroughly and follow all warnings or


cautions in literature and attached to the unit. Consult local
building codes and current editions of national as well as
local electrical codes.
Recognize the following safety information:

Warning

Incorrect handling could result in


personal injury or death.

Caution

Incorrect handling may result in


minor injury,or damage to product
or property.

Warning
All electric work must be performed by a licensed technician
according to local regulations and the instructions given in
this manual.
Before installing, modifying, or servicing system, main
electrical disconnect switch must be in the OFF position.
There may be more than 1 disconnect switch. Lock out
and tag switch with a suitable warning label.
Never supply power to the unit unless all wiring and tubing are completed, reconnected and checked.
This system adopts highly dangerous electrical voltage.
Incorrect connection or inadequate grounding can cause
personal injury or death. Stick to the wiring diagram and
all the instructions when wiring.
Have the unit adequately grounded in accordance with
local electrical codes.
Have all wiring connected tightly. Loose connection may
lead to overheating and a possible fire hazard.
All installation or repair work shall be performed by your dealer or a specialized subcontractor as there is the risk of fire,
electric shock, explosion or injury.


Downloaded from www.Manualslib.com manuals search engine

Make sure the ceiling/wall is strong enough to bear the


weight of the unit.
Make sure the noise of the outdoor unit does not disturb
neighbors.

Avoid contact between refrigerant and fire as it generates


poisonous gas.
Apply specified refrigerant only. Never have it mixed with
any other refrigerant. Never have air remain in the
refrigerant line as it may lead to rupture and other hazards.
Make sure no refrigerant gas is leaking out when installation is completed.
Should there be refrigerant leakage, the density of refrigerant in the air shall in no way exceed its limited value,
or it may lead to explosion.
Keep your fingers and clothing away from any moving
parts.
Clear the site after installation. Make sure no foreign objects are left in the unit.
Always ensure effective grounding for the unit.

Caution
Never install the unit in a place where a combustible gas
might leak, or it may lead to fire or explosion.
Make a proper provision against noise when the unit is
installed at a telecommunication center or hospital.
Provide an electric leak breaker when it is installed in a
watery place.
Never wash the unit with water.
Handle unit transportation with care. The unit should not
be carried by only one person if it is more than 20kg.
Never touch the heat exchanger fins with bare hands.
Never touch the compressor or refrigerant piping without
wearing glove.
Do not have the unit operate without air filter.
Should any emergency occur, stop the unit and disconnect the power immediately.
Properly insulate any tubing running inside the room to
prevent the water from damaging the wall.

6SHFLFDWLRQV

6SHFLFDWLRQV
3DUDPHWHU

8QLW

9DOXH

0RGHO

A16CM4H4R18

3URGXFW&RGH

&%:

5DWHG9ROWDJH
3RZHU
6XSSO\

5DWHG)UHTXHQF\



+]



3KDVHV

3RZHU6XSSO\0RGH

2XWGRRU

&RROLQJ&DSDFLW\ 0LQ 0D[

%WXK

 a

+HDWLQJ&DSDFLW\ 0LQ 0D[

%WXK

 a

&RROLQJ3RZHU,QSXW 0LQ 0D[

 a

+HDWLQJ3RZHU,QSXW 0LQ 0D[

 a

6((5

%WXZK



+63)

%WXZK




Downloaded from www.Manualslib.com manuals search engine

6SHFLFDWLRQV

0,768%,6+,(/(&75,& *8$1*=+28 &2035(6625


&2/7'

&RPSUHVVRU0DQXIDFWXUHU7UDGHPDUN
&RPSUHVVRU0RGHO

61%)*<0&

&RPSUHVVRU2LO

39()96

&RPSUHVVRU7\SH

5RWDU\

/5$



&RPSUHVVRU5/$



&RPSUHVVRU3RZHU,QSXW

2YHUORDG3URWHFWRU


17/

7KURWWOLQJ0HWKRG

(OHFWURQH[SDQVLRQYDOYH

2SHUDWLRQWHPS

&

a

$PELHQWWHPS FRROLQJ

&

a

$PELHQWWHPS KHDWLQJ

&

&RQGHQVHU)RUP

a
$OXPLQXP)LQFRSSHU7XEH

3LSH'LDPHWHU

PP



5RZVQ*DS

PP



&RLO/HQJWK /;';: 

PP

;;

)DQ0RWRU6SHHG

USP







2XWSXWRI)DQ0RWRU
2XWGRRU )DQ0RWRU5/$
8QLW
)DQ0RWRU&DSDFLWRU
$LU)ORZ9ROXPHRI2XWGRRU8QLW



PK



)DQ7\SH
)DQ'LDPHWHU

$[LDORZ
PP

'HIURVWLQJ0HWKRG

$XWRPDWLF'HIURVWLQJ

&OLPDWH7\SH

7

,VRODWLRQ

0RLVWXUH3URWHFWLRQ
3HUPLVVLEOH([FHVVLYH2SHUDWLQJ3UHVVXUHIRU
WKH'LVFKDUJH6LGH
3HUPLVVLEOH([FHVVLYH2SHUDWLQJ3UHVVXUHIRU
WKH6XFWLRQ6LGH



,3
03D



03D



6RXQG3UHVVXUH/HYHO +0/

G% $



6RXQG3RZHU/HYHO +0/

G% $



'LPHQVLRQ :;+;' 

PP

;;

'LPHQVLRQRI&DUWRQ%R[ /:+

PP

;;

'LPHQVLRQRI3DFNDJH /:+

PP

;;

1HW:HLJKW

NJ



*URVV:HLJKW

NJ

5HIULJHUDQW


5$

5HIULJHUDQW&KDUJH

NJ



/HQJWK



JP



*DV$GGLWLRQDO&KDUJH
&RQQHFWLRQ2XWHU'LDPHWHU/LTXLG3LSH
3LSH
2XWHU'LDPHWHU*DV3LSH

PP

PP



0D['LVWDQFH+HLJKW

0D['LVWDQFH/HQJWK




Downloaded from www.Manualslib.com manuals search engine

6SHFLFDWLRQV

3DUDPHWHU

8QLW

9DOXH

0RGHO

A16CM4H4R24

A16CM4H4R30

3URGXFW&RGH

&%:

&%:





+]





5DWHG9ROWDJH
3RZHU
6XSSO\

5DWHG)UHTXHQF\
3KDVHV

3RZHU6XSSO\0RGH

2XWGRRU

2XWGRRU

&RROLQJ&DSDFLW\ 0LQ 0D[

%WXK

 a

 a

+HDWLQJ&DSDFLW\ 0LQ 0D[

%WXK

 a

 a

&RROLQJ3RZHU,QSXW 0LQ 0D[

 a

 a

+HDWLQJ3RZHU,QSXW 0LQ 0D[

 a

 a

&RROLQJ3RZHU&XUUHQW





+HDWLQJ3RZHU&XUUHQW





5DWHG,QSXW





5DWHG&XUUHQW





6((5

%WXZK





+63)

%WXZK






Downloaded from www.Manualslib.com manuals search engine

6SHFLFDWLRQV

&RPSUHVVRU0DQXIDFWXUHU7UDGHPDUN
&RPSUHVVRU0RGHO
&RPSUHVVRU2LO
&RPSUHVVRU7\SH

0,768%,6+,(/(&75,&
*8$1*=+28 &2035(6625
&2/7'

0,768%,6+,(/(&75,&
*8$1*=+28
&2035(6625&2/7'

71%)/+0&

71%)/+0&

39()96

39()96

5RWDU\

5RWDU\





&RPSUHVVRU5/$





&RPSUHVVRU3RZHU,QSXW





/5$

2YHUORDG3URWHFWRU
7KURWWOLQJ0HWKRG

&6&

&6&

(OHFWURQH[SDQVLRQYDOYH

(OHFWURQH[SDQVLRQYDOYH

 

 

2SHUDWLRQWHPS

&

$PELHQWWHPS FRROLQJ

&

 

 

$PELHQWWHPS KHDWLQJ

&

 

 

$OXPLQXP)LQFRSSHU7XEH

$OXPLQXP)LQFRSSHU7XEH


&RQGHQVHU)RUP
3LSH'LDPHWHU

PP



5RZVQ*DS

PP





&RLO/HQJWK /;';: 

PP

;;

;;

USP





)DQ0RWRU6SHHG
2XWGRRU 2XWSXWRI)DQ0RWRU
8QLW
)DQ0RWRU5/$
)DQ0RWRU&DSDFLWRU
$LU)ORZ9ROXPHRI2XWGRRU8QLW

















$[LDORZ

$[LDORZ

P K

)DQ7\SH
)DQ'LDPHWHU

PP

'HIURVWLQJ0HWKRG
&OLPDWH7\SH
,VRODWLRQ





$XWRPDWLF'HIURVWLQJ

$XWRPDWLF'HIURVWLQJ

7

7

,3

,3









0RLVWXUH3URWHFWLRQ
3HUPLVVLEOH([FHVVLYH2SHUDWLQJ3UHVVXUH
IRUWKH'LVFKDUJH6LGH
3HUPLVVLEOH([FHVVLYH2SHUDWLQJ3UHVVXUH
IRUWKH6XFWLRQ6LGH

03D

'LPHQVLRQ :;+;' 

PP

;;

;;

'LPHQVLRQRI&DUWRQ%R[ /:+

PP

;;

;;

'LPHQVLRQRI3DFNDJH /:+

PP

;;

;;

1HW:HLJKW

NJ





*URVV:HLJKW

NJ

03D

5HIULJHUDQW





5$

5$

5HIULJHUDQW&KDUJH

NJ





/HQJWK





*DV$GGLWLRQDO&KDUJH

JP





2XWHU'LDPHWHU/LTXLG3LSH

PP

2XWHU'LDPHWHU*DV3LSH

PP













&RQQHFWLRQ0D['LVWDQFH+HLJKW
3LSH
0D['LVWDQFH/HQJWK

7KHDERYHGDWDLVVXEMHFWWRFKDQJHZLWKRXWQRWLFH3OHDVHUHIHUWRWKHQDPHSODWHRIWKHXQLW


Downloaded from www.Manualslib.com manuals search engine

&RQVWUFWLRQ9LHZV

&RQVWUXFWLRQ9LHZV
 A16CM4H4R18

316

899

378

596

815

343

550

8QLWPP
 A16CM4H4R24A16CM4H4R30

892

700

341

396

946

368

560

8QLWPP


Downloaded from www.Manualslib.com manuals search engine

5HIULJHUDQW6\VWHP'LDJUDP

5HIULJHUDQW6\VWHP'LDJUDP
outdoor

indoor

filter
A heat exchanger

A1

A3

filter

B heat exchanger

fan

A2

outdoor heat exchanger

4-way valve
B1

B3

SP

filter

B2

high pressure switch


Note: Not available for 14K/18K
model

discharge silencer

C heat exchanger

C1

C3

filter

C2

D1

D3

filter

D2

gas -liquid separator


Note: Not available for 14K/18K model

A1:Aunit electronic expansion valve B1:B-unit electronic expansion valve


C1:C-unit electronic expansion valve D1:D-unit electronic expansion valve
A2:A-unit gas pipe temperature sensor B2:B-unit gas pipe temperature sensor
C2:C-unit gas pipe temperature sensor D2:D-unit gas pipe temperature sensor
A3:Aunit liquid pipe temperature sensor B3:B-unit liquid pipe temperature sensor
C3:C-unit liquid pipe temperature sensor D3:D-unit liquid pipe temperature sensor


Downloaded from www.Manualslib.com manuals search engine

inverter compressor

D heat exchanger

discharge temperature
sensor

6FKHPDWLF'LDJUDP

6FKHPDWLF'LDJUDP
(OHFWULFDO'DWD
0HDQLQJRIPDUNV

6\PERO

&RORUV\PERO

:+

:+,7(

<(
5'
<(*1
97

6\PERO

&RORUV\PERO

6\PERO

*1

*5((1

6$7

<(//2:

%1

%52:1

&203

5('

%8

%/8(

<(//2:*5((1
9,2/(7

%.

%/$&.

2*

25$1*(

3DUWVQDPH
29(5/2$'
&2035(6625
3527(&7,9(($57+



(OHFWULFDO:LULQJ
 A16CM4H4R18

6BN
7BU

L2

INDOOR UNIT A

5YEGN(GN)

L2

INDOOR UNIT B

4BU

N(1)

2BN

XTB

EKV

EKV

WH

G
COMP
HEATER

RT2

OUTROOM
TEM.SENSOR
OUTTUBE
TEM.SENSOR

BK

EH

16RD

3
HEAT-C

15RD 1

FA

L
L7

WH

FB
OFAN1

LX1-1

U
AP1: Main Board

OG

LX1-2

TUBE-B

BU

L4

YE

L4

BN

YE BU

YEGN(GN)

WARNING
Please don't touch any terminal when the voltage

FAN MOTOR

WH
BK

RD
0

RT4 RT5
Gas Valve Liquid Valve
TEM.SENSOR TEM.SENSOR

BK
BK

RD

SAT

9BU
S

COMP.

10YE

L4

RD
X1

of terminal P(DC+) and N(DC-) at AP1 is higher


than 30V to prevent the risk of electrical shock!

L7

TUBE-A

C1
WH BK RD

14WH
13WH

OVC-COMP
L3

4YV

4V
COM-INNER

FB

FA

2
3

L6

BK
GY

XTA

YEGN(GN)

T-SENSOR

EXHAUST
TEM.SENSOR

2
3

RT1

RT3

N(1)

YEGN(GN)

N1
AC-L
N2

8YEGN(GN)

1BN

3BU

BU
BN
BU

AC-L1
N1
N1
AP2 AC-L2
N2
E(PE)

L1 L5

L1
L2

XT1

L1
L2

POWER

11RD

C(T)

12YEGN(GN)

RT6 RT7
Gas Valve Liquid Valve
TEM.SENSOR TEM.SENSOR


Downloaded from www.Manualslib.com manuals search engine

6FKHPDWLF'LDJUDP

 A16CM4H4R24

LOAD

LINE

INDOOR UNIT A

5BU

AC-L2
N2

E(PE)

1BN

BU
BN L2
BU

N1

N1
AC-L
N2

T-SENSOR

YEGN(GN)

TERMINAL
BLOCK
INDOOR UNIT B

7BU

ELECTRONIC
EXPANSION VALVE

TERMINAL
BLOCK
INDOOR UNIT C

FB

FA

3BN

N(1)

19BU

COM-INNER

WH

XTB
G

EKV

EKV

EKV

BK

WH
FA

C1

YE BU

FC

YEGN(GN)

FAN MOTOR

24RD

RD 0
RT8 RT9
QC
YC
Liquid Valve
Gas Valve
Tem.Sensor
Tem.Sensor

BK

COMP

COMP.

16YEGN(GN)

HEAT-C

RD

RD 0
RT6 RT7
QB
YB
Gas Valve Liquid Valve
Tem.Sensor Tem.Sensor

BK

Overload
Protector

X1

TUBE-C

BK
0

YE
RD

SAT
U

L5 13BU
14YE
15RD

BU

LX2-1

TUBE-B

RD 0
RT4 RT5
QA
YA
Gas Valve Liquid Valve
TEM.Sensor Tem.Sensor

BK

17WH

LX2-2

LX1-1
LX1-2
AP1: Main Board

WH

BN

BU
OG

WH

TUBE-A

CAP.

RD

OVC-COMP

FB

OFAN
WH BK

RD
5

HPS
High Pressure Switch

18WH

FC

XTC
G

YEGN(GN)

20YE
HPP

GY

YEGN(GN)

L4

BK

2BN

N(1)

4-WAY
VALVE

4YV

4V

6BU

EXHAUST
TEM.SENSOR
OUTROOM
TEM.SENSOR
OUTTUBE
TEM.SENSOR

WH

12YEGN(GN)
G

RT2
RT3

N(1)

XTA

RT1

10BU

L3

TERMINAL
BLOCK

BK

AC-L1
AP2:
N1
Filter Board

9YEGN(GN)

POWER

L1 11BN

21BN L
L'
22BU NFILTER N'
G

L1
L2

XT1

L1
L2

23RD

Compressor
Band Heater

WARNING

Please don't touch any terminal when the voltage


of terminal P(DC+) and N(DC-) at AP1 is higher
than 30V to prevent the risk of electrical shock!

 A16CM4H4R30

LOAD

L1

LINE

21BN
22BU

11BN
10BU

L'
N'

AC-L1
N1

FILTER

9YEGN(GN)

AP2

INDOOR UNIT A

5BU

L2

BU
BN L3
BU

N1
AC-L2
N2

E(PE)

N1
AC-L
N2

RT1
T-SENSOR

EXHAUST
TEM.SENSOR
OUTROOM
TEM.SENSOR
OUTTUBE
TEM.SENSOR

XT1
L1
L2

POWER
L1
L2

RT2

N(1)

INDOOR UNIT B

YEGN(GN)
G

1BN

6BU

2
3
XTB

INDOOR UNIT C

7BU

3BN

N(1)

2
3
XTC

YEGN(GN)
INDOOR UNIT D

N(1)

8BU

4BN

20YE

EKV

EKV

EKV

BK
FA

WH BK

C1
BN

RD

FB

TUBE-A

OFAN

TEM.SENSOR

BU

FC

FD LX1-1

TUBE-B

TEM.SENSOR TEM.SENSOR

LX2-1

RD
BK

RT8

YE
RD
BK 0
0
RT10
RT9

Please don't touch any terminal when the voltage


of terminal P(DC+) and N(DC-) at AP1 is higher
than 30V to prevent the risk of electrical shock!

HEAT-C W RD

15RD

RD
0
24RD
RT11

Liquid Valve
Gas Valve
TEM.SENSOR TEM.SENSOR

BN:BROWN

WH:WHITE

BU:BLUE

YE:YELLOW

SAT

U
COMP.

V
X1

Gas Valve
Liquid Valve
TEM.SENSOR TEM.SENSOR

13BU
14YE

G
WARNING

L5

BU
YE

LX1-2
AP1: Main Board
TUBE-C
TUBE-D

HP

18WH
17WH

OVC-COMP

LX2-2

WH OG

BK
YE BU WH
RD
RD BK 0
0
BK 0
0
RT6 RT7
YEGN(GN) Gas Valve RT4 LiquidRT5
Liquid Valve
Valve
Gas Valve
TEM.SENSOR

FAN MOTOR

YE

RD
5

19BU

FC FD

4YV

4V
HPP

EKV

WH

L4
COM-INNER

FA FB

2
3
XTD

RT3

BK
GY
WH
RD

2BN

N(1)

YEGN(GN)
G

YEGN(GN)
G

12YEGN(GN)

2
3
XTA

W 16YEGN(GN)
G

23RD

COMP
HEATER

BK:BLACK

RD:RED

GY:GRAY

YEGN:YELLOW GREEN

7KHVHFLUFXLWGLDJUDPVDUHVXEMHFWWRFKDQJHZLWKRXWQRWLFHSOHDVHUHIHUWRWKHRQHVXSSOLHGZLWKWKHXQLW

Downloaded from www.Manualslib.com manuals search engine

6FKHPDWLF'LDJUDP

3ULQWHG&LUFXLW%RDUG
 A16CM4H4R18

7239,(:
1

1
2
3
10

11

5
6

12

Outdoor fan

4-way valve

9
13

10

14

11
12
13

17

16

%277209,(:

Compressor interface
Unit A liquid valve
and gas valve
Unit B liquid valve
and gas valve
Compressor overload
protector
Temperature sensor
Compressor electric
heater

15

14
15

Chassis electric
heater (reserved)
Unit A electronic
expansion valve
Unit B electronic
expansion valve
Communication
interface with indoor
unit
Communication
neutral wire
Live wire of power
supply
Neutral ire of power
supply

16

Reactor interface1

17

Reactor interface2


Downloaded from www.Manualslib.com manuals search engine

6FKHPDWLF'LDJUDP

 A16CM4H4R24A16CM4H4R30

7239,(:
1

6 7

10

11

12

13

Compressor interface

Temperature sensor
interface of unit A liquid
valve and gas valve

Temperature sensor
interface of unit B liquid
valve and gas valve

Temperature sensor
interface of unit C liquid
valve and gas valve

14
15
16

5
17

6
18

7
8
9

22

21

%277209,(:

20

19

Temperature sensor
interface of unit D liquid
valve and gas valve
Temperature sensor
interface
Interface of compressor
overload protector
Interface of chassis
electric heater
Interface of compressor
electric heater belt

10

Outdoor fan interface

11

4-way valve interface

12

High voltage protection


interface
Interface of electronic
expansion valve A
Interface of electronic
expansion valve B
Interface of electronic
expansion valve C
Interface of electronic
expansion valve D
Communication wire
interface
Communication neutral
wire interface

13
14
15
16
17
18

19 Input neutral wire interface


Downloaded from www.Manualslib.com manuals search engine

20

Input live wire interface

21

PFC input live wire


interface

22

PFC input neutral wire


interface

)XQFWLRQDQG&RQWURO

)XQFWLRQDQG&RQWURO
1 Basic functions of the system
1.1 Cooling Mode
1.1.1 Cooling conditions and process:
If the compressor is in stop status and start the unit for cooling operation, when one of the indoor units reaches the cooling
operation condition, the unit start cooling operation; in this case, the electronic expansion valve, the outdoor fan and the
compressor start operation.
1.1.2 Stop in cooling operation
1.1.2.1 Compressor stops
The compressor stops immediately, the outdoor fan stops after 1min.
1.1.2.2 Some of the indoor units reach the stop condition (the compressor does not stop)
The compressor operates immediately according to the required frequency. For the indoor unit with no requirement, the
corresponding electronic expansion valve is closed to OP.
1.1.3 Cooling mode transfers to heating mode
When the unit transfers to heating mode, the 4-way valve is energized after the compressor stops for 2min. The other disposals
are the same as stopping in cooling mode.
1.1.4 4-way valve: in this mode, the 4-way valve is closed.
1.1.5 Outdoor fan control in cooling mode
The outdoor fan starts before 5s of the starting of compressor. The outdoor fan will run in high speed for 3min after starting and
then it will run in set speed. The fan shall run at every speed for at least 80s. (When the quantity of running indoor unit is
changed, the unit will enter the control described in 1.3.5.1 and 1.3.5.2);
When the compressor stops, the outdoor fan runs at present speed and stops after 1min.

1.2 Dry Mode


1.2.1 The dry conditions and process are the same as those in cooling mode;
1.2.2 The status of 4-way valve: closed;
1.2.3 The temperature setting range: 16 ~ 30;
1.2.4 Protection function: the same as those in cooling mode;
1.2.5 In dry mode, the maximum value A of the capacity requirement percentage of single unit is 90% of that in cooling mode.
The open condition of the electronic expansion valve, outdoor fan and compressor is the same as those in cooling mode.

1.3 Heating Mode


1.3.1 Cooling conditions and process:
When one of the indoor units reaches the heating operation condition, the unit starts heating operation.
1.3.2 Stop in heating operation:
1.3.2.1 When all the indoor units reach the stop condition, the compressor stops and the outdoor fan stops after 1min;
1.3.2.2 Some of the indoor units reach the stop condition
The compressor reduces the frequency immediately and operates according to the required frequency;
1.3.2.3 Heating mode transfers to cooling mode(dry mode), fan mode
a. The compressor stops; b. the power of 4-way valve is cut off after 2min; c. the outdoor fan stops after 1min; d. the status of
4-way valve: energized;


Downloaded from www.Manualslib.com manuals search engine

)XQFWLRQDQG&RQWURO

1.3.3 Outdoor fan control in heating mode


The outdoor fan starts before 5s of the starting of compressor and then it will run in high speed for 40s;
The fan shall run at every speed for at least 80s;
When the compressor stops, the outdoor fan stops after 1min.
1.3.4 Defrosting function
When the defrosting condition is met, the compressor stops; the electronic expansion valve of all indoor units open in big angle;
the outdoor fan stops after 40s of the stop of compressor, meanwhile, the 4-way valve reverses the direction; after the 4-way
valve reverses the direction, the compressor starts; then begin to calculate the time of defrosting, the frequency of the
compressor rises to reach the defrosting frequency.
1.3.5 Oil-returned control in heating mode
1.3.5.1 Oil-returned condition
The whole unit is operating in low frequency for a long time
1.3.5.2 Oil-returned process in heating mode
The indoor unit displays H1
1.3.5.3 Oil-returned finished condition in heating mode
The duration reaches 5min

1.4 Fan Mode


The compressor, the outdoor fan and the 4-way valve are closed; temperature setting range is 1630.

2. Protection Function
2.1 Mode Conflict Protection of indoor unit
When the setting mode is different of different indoor unit, the unit runs in below status:
a. The mode of the first operating indoor unit is the basic mode, then compare the mode of the other indoor units to see if there
is a conflict. Cooling mode (dry mode) is in conflict with heating mode.
b. Fan mode is in conflict with heating mode and the heating mode is the basic mode. No matter which indoor unit operates first,
the unit will run in heating mode.

2.2 Overload protection function


When the tube temperature is a little low, the compressor raises the operation frequency; when the tube temperature is a little
high, the compressor frequency is restricted or lows down the operation frequency; when the tube temperature is too high, the
compressor protection stops running.
If the discharge temperature protection continuously appears for 6 times, the compressor cant resume running. The
compressor can resume running after cutting off the power and then putting through the power. (if the running time of the
compressor is longer than 7min, the protection times record will be cleared)

2.3 Discharge Protection Function


When the discharge temperature is a little low, the compressor raises the operation frequency; when the discharge temperature
is a little high, the compressor frequency is restricted or lows down the operation frequency; when the discharge temperature is
too high, the compressor protection stops running.
If the discharge temperature protection continuously appears for 6 times, the compressor cant resume running. The
compressor can resume running after cutting off the power and then putting through the power. (if the running time of the
compressor is longer than 7min, the protection times record will be cleared)


Downloaded from www.Manualslib.com manuals search engine

)XQFWLRQDQG&RQWURO

2.4 Communication malfunction


Detection of the quantity of installed indoor units:
After 3min of energizing, if the outdoor unit does not receive the communication data of certain indoor unit, the outdoor unit will
judge that indoor unit is not installed and will treat it as it is not installed. If the outdoor unit receives the communication data of
that indoor unit later, the outdoor unit will treat that unit as it is installed.

2.5 Overcurrent Protection


a. Overcurrent protection of complete unit; b. phase wire current protection; c. compressor phase current protection

2.6 Compressor high-pressure protection


2.6.1 When the high-pressure switch is detected cut off for 3s continuously, the compressor will enter high-pressure protection
as it stops when reaching set temperature. Meanwhile, the outdoor unit will send the signal of high-pressure protection to the
indoor units;
2.6.2 After the appearance of high-pressure protection, when the high-pressure switch is detected closed for 6s continuously,
the compressor can resume running only after cutting off the power and then putting through the power.

2.7 Compressor overload protection


If the compressor overload switch is detected having movement, the indoor unit will display the corresponding malfunction as it
stops when the indoor temperature reaching set temperature. When the compressor stops for more than 3min and the
compressor overload switch is reset, the unit will resume operation status automatically. If the protection appears for more than
6 times (if the running time of the compressor is longer than 30min, the protection times record will be cleared), the unit can not
resume operation status automatically, but can resume running only after cutting off the power and then putting through the
power.

2.8 Compressor Phase-lacking Protection


When the compressor starts, if one of the three phases is detected open, the compressor will enter phase-lacking protection.
The malfunction will be cleared after 1min, the unit will restart and then detect if there is still has phase-lacking protection. If the
phase-lacking protection is detected for 6 times continuously, the compressor will not restart but can resume running only after
cutting off the power and then putting through the power. If the running time of the compressor is longer than 7min, the
protection times record will be cleared.

2.9 IPM Protection


2.9.1 When the IMP module protection is detected, the unit will stop as the indoor temperature reaching set temperature, PFC is
closed, display IMP protection malfunction. After the compressor stops for 3min, the unit will resume operation status
automatically; if the IMP protection is detected for more than 6 times continuously (If the running time of the compressor is
longer than 7min, the protection times record will be cleared), the system will stop and send the signal of module protection to
indoor unit. The unit can not resume operation status automatically, but can resume running only after cutting off the power and
then putting through the power.
2.9.2 IMP module overheating protection
2.9.2.1 When TIMP85, prohibit to raise frequency;
2.9.2.2 When TIMP 90, the operation frequency of compressor lows down by 15% every 90s according to the present
capacity requirement of the complete unit. It will keep 90s after lowing down the frequency. After lowing down the frequency, if
TIMP 90, the unit will circulate the above movement until reaching the minimum frequency; if 85TIMP90, the unit will
run at this frequency; when TIMP 85, the unit will run at the frequency according to the capacity requirement;
2.9.2.3 When TIMP 95, the compressor stops. After the compressor stops for 3min, if TIMP85, the compressor and the
outdoor fan will resume operation.


Downloaded from www.Manualslib.com manuals search engine

,QVWDOODWLRQ0DQXDO

,QVWDOODWLRQ0DQXDO
,QVWDOODWLRQ'LPHQVLRQ'LDJUDP
A16CM4H4R18

Warning
Be sure to cut off the power supply before cleaning the air conditioner; otherwise electric shock might happen.
Wetting of air conditioner may cause the risk of electric shock. Make sure not to wash your air conditioner in any case.
Volatile liquids such as thinner or gasoline will cause damage to the appearance of air conditioner. (Only use soft dry
cloth moist cloth clean the air conditionercabinet).
This product must not be disposed together with the domestic waste.This product has to be disposed at an authorized
place for recycling of electrical and electronic appliances.
The temperature of refrigerant circuit will be high,please keep the interconnection cable away from the copper tube.

OUTDOOR UNIT

N o. Description
1

Air outlet grille

Valve

Note:the above figures are only intended to a simple


diagram of theappliance and may not correspond to the
appearance of the units that have been purchased.

A16CM4H4R24,A16CM4H4R30

Warning
If the supply cable is damaged, it must be replaced by the manufacturer or its service agent or a similarly qualified person in order to avoid a hazard.
Be sure to cut off the power supply before cleaning the air conditioner;otherwise electric shock might happen.
Wetting of air conditioner may cause the risk of electric shock. Make sure not to wash your air conditioner in any case.
Volatile liquids such as thinner or gasoline will cause damage to the appearance of air conditioner. (Only use soft dry cloth moist cloth clean
the air conditioner cabinet).
Do not dispose this product as unsorted municipal waste.
Collection of such waste separately for special treatment
is necessary.

The temperature of refrigerant circuit will be high,please keep the


interconnection cable away from the copper tube.

OUTDOOR UNIT

N o. Description
1

Air outlet grille

Valve

Note: the above figures are only intended to be a simple


diagram of the appliance and may not correspond to the
appearance of the units that have been purchased.


Downloaded from www.Manualslib.com manuals search engine

,QVWDOODWLRQ0DQXDO

,QVWDOOLQJ7KH2XWGRRU8QLW
Location
Use bolts to secure the unit to a flat, solid floor.
When mounting the unit on a wall or the roof, make
sure the support is firmly secured so that it cannot
move in the event of intense vibrations or a strong
wind.

Tighten the connections using two wrenches working


in opposite directions.
Caution: Installation Must be Performed in Accordance
with the NEC/CEC by Authorized Personnel Only.
Install the drain fitting and the drain hose (for
model with heat pump only)
Do not install the outdoor unit in pits or air vents
Condensation is produced and flows from the outdoor unit
Installing the pipes
when the appliance is operating in the heating mode. In order
Use suitable connecting pipes and equipment for the not to disturb neighbours and to respect the environment,
refrigerant R410A.
install a drain fitting and a drain hose to channel the condensate water. Install the drain fitting and rubber washer on the
The refrigerant pipes must not exceed the maximum outdoor unit chassis and connect a drain hose to it as shown
lengths .
in the figure.
Models(m)

18K

24K/30K

Max.connection pipe length

20

70

Max.connection pipe length


(Simple one indoor unit)

10

20

Drain-water hole
Bottom frame
Drain plug

The refrigerant pipes must not exceed the maximum


heights 5m(18K) 10m(24K/30K).

Drain connecter
Hose (available commercially,
inner dia. 16mm)

Wrap all the refrigerant pipes and joints.

Humid air left inside the refrigerant circuit can cause compressor malfunction. After having connected the indoor
and outdoor units, bleed the air and humidity from the
refrigerant circuit using a vacuum pump.
(1) Unscrew and remove the caps from the 2-way and 3way valves.
(2) Unscrew and remove the cap from the service valve.
(3) Connect the vacuum pump hose to the service valve.
(4) Operate the vacuum pump for 10-15 minutes until an
absolute vacuum of 10 mm Hg has been reached.
(5) With the vacuum pump still in operation, close the
low-pressure knob on the vacuum pump coupling. Stop
the vacuum pump.
(6) Open the 2-way valve by 1/4 turn and then close it
after 10 seconds.
. Check all the joints for leaks using
liquid soap or an electronic leak device.
(7) Turn the body of the 2-way and 3-way valves. Disconnect the vacuum pump hose.
(8) Replace and tighten all the caps on the valves.
Diameter (mm)

Twisting moment (N.m)

15-20

9.52

35-40

16

60-65

12

45-50

19

70-75

(9) If the specification of outdoor unit gas valve is 3/8,


but curstomer needs to install 1/2 indoor unit so that
it is need to use a pipe joint subassembly (Code 06643008)
to make a conversion joint with outdoor unit gas valve and
connection pipe, as show in following.

Vacuum pump

Vacuum pump

Vacuum pump

(8) Secure

INDOOR
UNIT
Refrigerant fluid direction of fiow

2-way valve

3-way valve
(6) Open by 1/4 turn
(7) Turn to open fully
Secure
inlet
(2) Turn
(8) Secure

(7) Turn to open fully

(2) Turn
Valve cap

Valve cap
(2) Turn
(8) Secure
Connect to the
indoor unit

conversion joint


Downloaded from www.Manualslib.com manuals search engine

,QVWDOODWLRQ0DQXDO

Use suitable instruments for the refrigerant R410A.

Do not use any other refrigerant than R410A.


Do not use mineral oils to clean the unit.

INSTALLATION DIMENSION DIAGRAM


The installation must be done by trained and qualified service personnel
with reliability according to this manual.
Contact service center before installation to avoid the malfunction due to
unprofessional installation.

When picking up and moving the units, you must be guided by trained and
qualified person.

Ensure that the recommended space is left around


the a ppliance .

A16CM4H4R18
50cm or more
Space to the cover

30cm or above
(Air inlet side)

30cm or above
Space to the cover

50cm or above
Space to the wall

200cm or above
(Air outlet side)

A16CM4H4R24, A16CM4H4R30
50cm or more
Space to the cover

30cm or above
Space to the cover

30cm or above
(Air inlet side)

50cm or above
Space to the wall

200cm or above
(Air outlet side)

This is just the schematic plan, please refer to the actual product.


Downloaded from www.Manualslib.com manuals search engine

,QVWDOODWLRQ0DQXDO

(OHFWULFDO&RQQHFWLRQV
A16CM4H4R18
1. Remove the handle at the right side plate of the
outdoor unit (six screw).

A16CM4H4R18

2. Remove the cable clamp, connect the connection cable and power cable
with the terminal at the row of connection and fix.
the connection. The fitting line distributing must be
consistent with the indoor unit. terminal of line bank.
Wiring should meet that of indoor unit.

3. Fix power connection wire by wire clamp.

Front
side plate
To unit A

4. Ensure wire has been fixed well.


5. Install the handle.

L1 L2

connecting
cable

power
cable

An all-pole disconnection switch having a contact


separation of at least 3mm in all pole should be
connected in fixed wiring.
Wrong wire connection may cause malfunction of some
electric components.After fixing cable, ensure that
leads between connection to fixed point have some space.

To unit B

connecting
cable

To the power supply

L1

L2
L2
L1

The connection pipes and the connectiong wirings of


the unit A and unit B must be corresponding to each
other respective.
The appliance shall be installed in accordance with
national wiring regulations.

Note: the above figures are only intended to be a simple


diagram of the appliance and may not correspond to the
appearance of the units that have been purchased.
All power cables and connection cables must be protected with conduits.


Downloaded from www.Manualslib.com manuals search engine

,QVWDOODWLRQ0DQXDO

A16CM4H4R24
1. Remove the handle at the right side plate of the
outdoor unit (ten screw).
2. Remove the cable clamp, connect the connection cable
and power cable with the terminal at the row of connection
and fix the connection. The fitting line distributing must be
consistent with the indoor unit. terminal of line bank.
To unit A

Wiring should meet that of indoor unit.

To unit B

To unit C

L1 L2

3. Fix power connection wire by wire clamp.


4. Ensure wire has been fixed well.
5. Install the handle.

connection
cable

power
cable

connection
cable

connection
cable

To the power supply

An all-pole disconnection switch having a contact


separation of at least 3mm in all pole should be

Outdoor unit

L1 L2
L1
L2

connected in fixed wiring.


Wrong wire connection may cause malfunction of some
electric components.After fixing cable, ensure that
leads between connection to fixed point have some space.

Indoor unit

N(1)

2 3
A

The connection pipes and the connectiong wirings of


the unit A ,unit B and unit C must be corresponding to each
other respective.

N(1)

2 3

N(1)

2 3
C

connection cable C
B

The appliance shall be installed in accordance with


national wiring regulations.

connection cable

connection cable A

Do not install the outdoor unit where it is exposed


to the sunlight.
Note:the above figure are only intended to be a simple
diagram of the appliance and may not correspond to the
appearance of the units that have been purchased.

Power cable
1)

The power cable should be put in from the hole under


connection cable cover.

2)

If connecting with two indoor units, the connection cable


should be put in from hole A and hole B.

3)

If connecting with three indoor units, the connection cable


should be put in from hole A , B and C.

4)

If connecting with four indoor units, the connection cable


should be put in from hole A, B , C and D.

All power cables and connection cables must be protected with conduits.

Downloaded from www.Manualslib.com manuals search engine

,QVWDOODWLRQ0DQXDO

A16CM4H4R30

D connection cable

1. Remove the handle at the right side plate of the

connection cable C

outdoor unit (ten screw).


2. Remove the cable clamp, connect the connection cable and

power cable with the terminal at the row of connection and fix
the connection. The fitting line distributing must be consistent
with the indoor unit, terminal of line bank.
Wiring should meet that of indoor unit.

connection cable

connection cable A

3. Fix power connection wire by wire clamp.


4. Ensure wire has been fixed well.
5. Install the handle.

An all-pole disconnection switch having a contact


separation of at least 3mm in all pole should be
connected in fixed wiring.

Power cable
1)

Wrong wire connection may cause malfunction of some


electric components.After fixing cable, ensure that
2)
leads between connection to fixed point have some space.
The connect ion pipe s and the connectiong wirings of
the unit A ,unit B,unit C and unit D must be corresponding
to each other respective.

3)
4)

The appliance shall be installed in accordance with


national wiring regulations.

The power cable should be put in from the hole under


connection cable cover.
If connecting with two indoor units, the connection cable
should be put in from hole A and hole B
If connecting with three indoor units, the connection cable
should be put in from hole A , B and C
If connecting with four indoor units, the connection cable
should be put in from hole A, B , C and D.

All power cables and connection cables must be protected with


conduits.

Do not install the outdoor unit where it is exposed


to the sunlight.

To unit B

To unit A

To unit D

To unit C

L1 L2

power
cable

connection
cable

connection
cable

connection
cable

connection
cable

To the power supply

L1 L2

Outdoor unit

L1
L2

Indoor unit

N(1) 2

N(1) 2

N(1) 2

N(1) 2

3
D

HANDLING
After having removed the packaging, check that the
contents are intact and complete.
The outdoor unit must always be kept up right.

Handling must be done by suitablye quipped qualified


technical personnel using equipment that is suitable for
the weight of the appliance.


Downloaded from www.Manualslib.com manuals search engine

,QVWDOODWLRQ0DQXDO

&KHFN$IWHU,QVWDOODWLRQ
Check Items

Problems Owing to Improper Installation

Is the installation reliable?

The unit may drop, vibrate or make noises

Has the gas leakage been checked?

May cause unsatisfactory cooling (heating)


effect

Is the thermal insulation of the unit

May cause condensation and water dropping

sufficient?
Is the drainage smooth?

May cause condensation and water dropping

Does the power supply voltage accord

The unit may bread down or the components

with the rated voltage specified on the

may be burned out

nameplate?
Are the lines and pipelines correctly

The unit may bread down or the components

installed?

may be burned out

Has the unit been safely grounded?

Risk of electrical leakage.

Are the models of lines in conformity

The unit may bread down or the components

with requirements?

may be burned out

Are there any obstacles near the air

The unit may bread down or the components

inlet and outlet of the indoor and outdoor

may be burned out

units?
Have the length of refrigerating pipe

It is not easy to decide the charge amount

and refrigerant charge amount been

of refrigerant.

recorded?


Downloaded from www.Manualslib.com manuals search engine

([SORGHG9LHZVDQG3DUWVOLVW

([SORGHG9LHZVDQG3DUWV/LVW
 A16CM4H4R18

22

21

19

20

23

24
18
17
25

16
15

14

26

27

13

12
11

10


Downloaded from www.Manualslib.com manuals search engine

([SORGHG9LHZVDQG3DUWVOLVW

'HVFULSWLRQ

12
3URGXFWFRGH


)URQW*ULOO





3DUW&RGH
A16CM4H4R18

4W\

&%:


&DELQHW

3

&KDVVLV6XEDVV\

3

'UDLQDJH-RLQW



&RPSUHVVRU*DVNHW



&RPSUHVVRUDQGWWLQJV



0DJQHW&RLO

ZD\9DOYH$VV\

7HPSHUDWXUH6HQVRU










7HPSHUDWXUH6HQVRU



&XWRII9DOYH





&XWRII9DOYH





%ORFN



+DQGOH$VV\



(OHFWULFH[SDQGYDOYHWWLQJ





(OHFWULFH[SDQGYDOYHWWLQJ





3)&,QGXFWDQFH





&ODSERDUG6XE$VV\





7HPSHUDWXUH6HQVRU





5HDU*ULOO





&RQGHQVHU$VV\





7RS&RYHU

3



0RWRU6XSSRUW6XE$VV\





/HIW6LGH3ODWH

3



(OHFWULF%R[$VV\



)DQ0RWRU



$[LDO)ORZ)DQ

7KHGDWDDERYHDUHVXEMHFWWRFKDQJHZLWKRXWQRWLFH


Downloaded from www.Manualslib.com manuals search engine

3









([SORGHG9LHZVDQG3DUWVOLVW

 A16CM4H4R24

35

34

33

32

31

30

28

29

27
26

36

25
37
38
39

24
23
22

40

21
20
19
18
17
16
15

10

11

12

13

14


Downloaded from www.Manualslib.com manuals search engine

Exploded Views and Parts list

Description

NO.
Product code
1

Front Grill

Cabinet

Drainage Plug

Chassis Sub-assy

Drainage Connecter

Part Code
A16CM4H4R24

Qty

CB228W01700
01473049

01433047P

06813401

01203942P

06123401

Compressor and Fittings

00105036

Compressor Gasket

76710207

Gas-liquid Separator Assy

07225017

Inhalation Tube

03723455

10

Right Side Plate

0130319401P

11

Valve Support Assy

0710306603

12

Cut off Valve

07130239

13

Cut off Valve

07133185

14

big handle Assy

02113043

15

Terminal cover Sub-Assy

01253057

16

Temperature Sensor

39000073

17

Temperature Sensor

3900007301

18

Temperature Sensor

3900007302

19

Electric Expand Valve Fitting

4300008402

20

Electronic Expansion Valve assy

07133456

21

Electric Expand Valve Fitting

43000084

22

Electric Expand Valve Fitting

4300008401

23

Magnet Coil

4300040033

24

4-Way Valve Assy

03123415

25

Wiring clamp

26115004

26

PFC

43120129

01233420

3900030901

27

Clapboard Assy

28

Temperature Sensor

29

Rear Grill

01473043

30

Condenser Assy

01113710

31

Top Cover

01255005P

32

Motor Support Sub-Assy

0170512001

33

Condenser Support Plate

01173415

34

Left Side Plate

01305041P

35

Left Handle

26235401

36

Electric Box (Fireproofing)

01413148

37

Electric Box Assy

38

Tube Connector Sub-assy

39

Fan Motor

40

Axial Flow Fan

The data above are subject to change without notice.

26
Downloaded from www.Manualslib.com manuals search engine

0260370301

06643008

1501506304

10335008

([SORGHG9LHZVDQG3DUWVOLVW

 A16CM4H4R30

36

35

34

33

32

31

29

30

28
27
37

26

38

25
24

39
40

23

41

22
21
20
19
18
17
16
15

10

11

12

13

14


Downloaded from www.Manualslib.com manuals search engine

([SORGHG9LHZVDQG3DUWVOLVW

'HVFULSWLRQ

12
3URGXFWFRGH


)URQW*ULOO

&DELQHW

'UDLQDJH3OXJ

&KDVVLV6XEDVV\

'UDLQDJH&RQQHFWHU




3DUW&RGH
A16CM4H4R30

4W\

&%:


3



3



&RPSUHVVRUDQG)LWWLQJV



&RPSUHVVRU*DVNHW



*DVOLTXLG6HSDUDWRU$VV\



,QKDODWLRQ7XEH





5LJKW6LGH3ODWH

3



9DOYH6XSSRUW$VV\





&XWRII9DOYH





&XWRII9DOYH





7HUPLQDOFRYHU6XE$VV\





7HPSHUDWXUH6HQVRU





7HPSHUDWXUH6HQVRU





7HPSHUDWXUH6HQVRU





7HPSHUDWXUH6HQVRU





ELJKDQGOH$VV\





(OHFWULF([SDQG9DOYH)LWWLQJ





(OHFWULF([SDQG9DOYH)LWWLQJ





(OHFWULF([SDQG9DOYH)LWWLQJ





(OHFWULF([SDQG9DOYH)LWWLQJ





0DJQHW&RLO





:D\9DOYH$VV\





:LULQJFODPS






3)& 






&ODSERDUG$VV\





7HPSHUDWXUH6HQVRU





5HDU*ULOO





&RQGHQVHU$VV\





7RS&RYHU

3



0RWRU6XSSRUW6XE$VV\





&RQGHQVHU6XSSRUW3ODWH



/HIW6LGH3ODWH





3

/HIW+DQGOH





(OHFWULF%R[ )LUHSURRQJ





(OHFWULF%R[$VV\





7XEH&RQQHFWRU6XEDVV\





)DQ0RWRU





$[LDO)ORZ)DQ



7KHGDWDDERYHDUHVXEMHFWWRFKDQJHZLWKRXWQRWLFH


Downloaded from www.Manualslib.com manuals search engine

7URXEOHVKRRWLQJ

7URXEOHVKRRWLQJ
0DOIXQFWLRQ,QGLFDWRU
Note:

: off

: on

: blink

When several malfunctions occur at the same time, they will be displayed in circulation and every malfunction is
displayed for 5s.

NO
0

Malfunction description
Normal stop

1
2

Compressor run
Compressor overload protection

3
4
5
6
7
8
9

Discharge protection
Outdoor unit overload protection
High pressure protection
Over current protection
IMP protection
IMP over heating protection
PFC protection (including PFC overheating protection)

10
11
12
13
14
15

Phase current protection


Over voltage protection
Insufficient voltage protection
Start failure
Compressor desynchronizing
Compressor phase-lacking protection

16

Compressor phase current detection malfunction

17
18
19
20
21
22
23
24

Memory chip mistake


DC power supply circuit-short
Defrosting
Oil return
Complete unit frequency restriction protection
Complete unit frequency dropping protection
Unit A frequency restriction or frequency dropping protection
Unit B frequency restriction or frequency dropping protection

25
26
27
28
29
30
31

Unit C frequency restriction or frequency dropping protection


Unit D frequency restriction or frequency dropping protection
Outdoor ambient temperature sensor protection
Outdoor tube temperature sensor protection
Discharge temperature sensor protection
IPM thermal resistance malfunction
Unit A liquid pipe temperature sensor malfunction

32
33
34

Unit A gas pipe temperature sensor malfunction


Unit B liquid pipe temperature sensor malfunction
Unit B gas pipe temperature sensor malfunction

35
36

Unit C liquid pipe temperature sensor malfunction


Unit C gas pipe temperature sensor malfunction

37
38
39

Unit D liquid pipe temperature sensor malfunction


Unit D gas pipe temperature sensor malfunction
Unit A mode conflict

40

Unit B mode conflict

41
42

Unit C mode conflict


Unit D mode conflict

LED1

LED2

LED3

LED4


Downloaded from www.Manualslib.com manuals search engine

7URXEOHVKRRWLQJ

43

Communication failure with Unit A

44
45
46
47
48
49
50
51
52

Communication failure with Unit B


Communication failure with Unit C
Communication failure with Unit D
Unit A freeze protection
Unit B freeze protection
Unit C freeze protection
Unit D freeze protection
Unit A overheating prevention protection
Unit B overheating prevention protection

53
54
55
56
57
58

Unit C overheating prevention protection


Unit D overheating prevention protection
Unit A communication wire misconnection or expansion valve malfunction
Unit B communication wire misconnection or expansion valve malfunction
Unit C communication wire misconnection or expansion valve malfunction
Unit D communication wire misconnection or expansion valve malfunction

0DOIXQFWLRQ&KHFNLQJDQG(OLPLQDWLRQ
Note: discharge the position in below pictures with discharge resistance after open the top cover and
check if the voltage is below 20V with universal meter, then begin to check.
18K:

24/30K:

(1) IPM protection malfunction:


Main checking point:

If the input voltage of the unit is within normal range?

If the connection wire of compressor is connected well? Is it loose? If the connection sequence is correct?

If the resistance of compressor coil is normal? If the isolation of compressor coil with copper pipe is good?

If the unit is overloaded? If the heat radiation of the unit is good?

If the refrigerant charge is suitable?

Flow chart:


Downloaded from www.Manualslib.com manuals search engine

7URXEOHVKRRWLQJ

Energize the unit

Please check:
1. if the indoor and outdoor heat exchanges are
dirty, if there is obstacle to affect the radiation;
2. if the indoor and outdoor fans are running
normally;
3. if the pressure of the system is too high;
4. if the refrigerant is too much which causes
the high level of pressure;

yes
If the above cases are existed?

no

Correct according to the service


manual and then energize the
unit to operate

no
If the wire of compressor is connected
well and correctly?

yes

Reconnect the wire of the


compressor according to the
correct wiring method

Test the resistance between


the three phases

no
If the resistance is normal?

yes
Test the isolation impedance
between the three phases of the
compressor and thecopper pipe

yes

If the resistance is above 500M

no
Replace the
compressor

yes
Malfunction is eliminated
no
Replace the outdoor
mainboard

End


Downloaded from www.Manualslib.com manuals search engine

7URXEOHVKRRWLQJ

(2) PFC protection malfunction


Main checking points:
If the power supply is normal;
Check if the connection wire of induction is connected well and if the induction is broken;
Flow chart:

Start

Check If the power supply is normal

Turn on the unit after the

yes

power supply resumes to

Power supply is abnormal

normal situation

no

Check if the outdoor induction is broken

yes
The induction is broken

Replace the induction

no
no
Malfunction is eliminated
Replace the outdoor
mainboard
yes

End


Downloaded from www.Manualslib.com manuals search engine

7URXEOHVKRRWLQJ

(3) Capacity charging malfunction


Main checking points:
If the wiring of the induction is connected well and if the induction is broken;
If the mainboard is broken;
Flow chart:
Energize the unit and wait
for 1min

Test the voltage between the two


ends of the electrolytic capacitor
with the DC shift of the universal
meter

yes
The voltage is above 100V

The detection circuit of


the outdoor mainboard
has malfunction

Replace the outdoor mainboard

no

Check if the induction wiring is loose


or the induction is cut off

The induction is cut off or the


wiring is loose

yes

Replace the induction or


reconnect the loose wire

Malfunction is eliminated

yes

no
no

Replace the outdoor


mainboard

End


Downloaded from www.Manualslib.com manuals search engine

7URXEOHVKRRWLQJ

(4) Anti-high temperature and overload malfunction


Main checking points:
If the outdoor ambient temperature is within the normal range;
If the outdoor fan is running normally;
If the indoor and outdoor radiation environment is good;
Flow chart:

Start

yes

If the outdoor ambient temperature


is above 53

It is a normal protection, please


operate the unit after the outdoor
ambient temperature has changed

no

yes

Improve the radiation


environment of the unit

no

Check if the terminal of the fan is


connected well, if the fan is broken

If the indoor and outdoor radiation


is insufficient

no

If the outdoor fan is working normally

yes
Replace fan capacitor
Replace outdoor
mainboard
Replace outdoor fan

End


Downloaded from www.Manualslib.com manuals search engine

7URXEOHVKRRWLQJ

(5) Temperature sensor malfunction


Main checking points:
 If the temperature; sensor is damaged or broken
If the terminal of the temperature sensor is loosended or not connected;
If the mainboard is broken;
Flow chart:

Start

Check whether the wiring terminal between


temperature sensor and controller is loosened or poorly

yes

contacted?
Insert the temperature
sensor tightly
no
no

Check whether the


temperature senspr is normal according to

Eliminate the
malfunction

no

yes

Replace the temperature sensor


with the same model

resistance table

no
yes

yes
Eliminate the malfunction

Replace the controller with


the same model

End


Downloaded from www.Manualslib.com manuals search engine

7URXEOHVKRRWLQJ
(6) Start failure malfunction
Main checking points:
 If the connection wire of the compressor is connected properly;
If the stop duration of the compressor is sufficient;
If the compressor is broken;
If the
; refrigerant charging amount is too much;
Flow chart:
Energize and
start the unit

no

If the stop duration of the compressor


is longer than 3min

yes

If the connection wire of the compressor


is connected well and correctly

yes

no

no

If the refrigerant charging


amount is too much

Charge the refrigerant


according to the
service manual

yes
Eliminate the malfunction
no

not enough, the high and low


pressure of the system is not
balanced, restart it after 3min

Replace the outdoor


mainboard

yes
Eliminate the malfunction
no
Replace the compressor

End


Downloaded from www.Manualslib.com manuals search engine

Eliminate the malfunction

yes

yes

The stop duration of the unit is

Reconnect the connection wire


of the compressor according
to the wiring diagram

no

7URXEOHVKRRWLQJ
(7) Communication malfunction
Main checking points:
 If the connection wire between the indoor unit and outdoor unit is connected well, if the wires inside the unit is connected well;
If the indoor mainboard or outdoor main board is broken;
Flow chart:

Communication malfunction of some


indoor units

De-energize,check the connection


wire of indoor and outdoor unit and
the wire of the eletric box is
connected correctly

Connected correctly

no

Reconnect according to
the wiring diagram

yes
Eliminate the malfunction
no

yes

De-energize, change the communication wire of the wellcommunicated indoor unit and malfunction indoor unit,
then energize the unit and wait for 3min

The malfunction indoor unit


resumes normal

yes

Replace outdoor
mainboard

no

Replace the mainboard of the


malfunction indoor unit

End


Downloaded from www.Manualslib.com manuals search engine

7URXEOHVKRRWLQJ

All the indoor units appear


communication malfunction

De-energize,check the connection


wire of indoor and outdoor unit and
the wire of the eletric box is
connected correctly

no

Reconnect according to

Connected correctly?

yes

Eliminate the malfunction

the wiring diagram


yes
De-energize, check if the connection wire between
the outdoor mainboard and the filter board
according to the wiring diagram

Reconnect according to
the wiring diagram

no
Connected correctly?

yes
Eliminate the malfunction
no

yes

yes
The connection wire is broken?

Replace the
connection wire

yes
Eliminate the malfunction

no

no
Check if there is power input
bewtween the netrual wire and live
wire of the outdoor mainboard

no

There is power input?

Replace the filter board of


the outdoor unit

no

yes
Replace the outdoor
mainboard

Resume communication?

yes

End


Downloaded from www.Manualslib.com manuals search engine

yes
Eliminate the malfunction

no

Replace indoor
mainboard

7URXEOHVKRRWLQJ
(8) Compressor overload, diacharge protection malfunction
Main checking points:
 If the eletric expansion valve is connected well or it is broken;
If there is refrigerant leakage;
If the overload protector is broken;
Flow chart:
Start

If the overload protector is connected well?

no

yes

no

Check the resistance between the two


ends of the overload protector in ambient temperature,
if the resistance is below 1k
yes

If the wiring of the eletric expansion valve


is coonected well?

Replace the
overload
protector

no

Reconnect according
to the wiring diagram

Check the coil of the eletric


expansion valve, replace
it if it is broken

Eliminate the malfunction

yes

no
Check the refrigerant status, if there is
refrigerant leakage, recharge it according
to the service manual

yes
Eliminate the malfunction
no
Replace outdoor
mainboard

End

Noted: the detection method of the coil of the eletric expansion valve: there is five pieces of the coil of the eletric expansion valve,
the resistance of one of them (the leftmost or the rightmost one) is almost the same as the resistance of other terminal (within
100

). Judge the condition of the electronic expansion valve through detecting these resistance.


Downloaded from www.Manualslib.com manuals search engine

7URXEOHVKRRWLQJ
(9) Compressor desynchronizing malfunction
Main checking points:
 If the pressure of the system is too high;
If the eletric expansion valve is working normally or it is broken;
If the radiation of the unit is good;
Flow chart:

The unit appears desynchronizing


as soon as energizing and starting

no

The stop duration of the compressor is longer


than 3min?

yes

The wiring of the compressor is

no

Reconnect the wire properly

connected properly?

yes

no

yes

Eliminate the malfunction

no

Replace the eletric


expansion valve

The eletric expansion valve is broken?

yes

no

yes
Eliminate the malfunction

Replace outdoor mainboard

yes
Eliminate the malfunction

no

Replace the compressor

End


Downloaded from www.Manualslib.com manuals search engine

7URXEOHVKRRWLQJ

$SSHQGL[5HVLVWDQFH7DEOHRI$PELHQW7HPSHUDWXUH6HQVRUIRU,QGRRUDQG2XWGRRU8QLWV .
7HPS 5HVLVWDQFH N

7HPS 5HVLVWDQFH N

7HPS

5HVLVWDQFH N

7HPS

5HVLVWDQFH N






























































































































































































































































































































































































































































































































































































































Downloaded from www.Manualslib.com manuals search engine

7URXEOHVKRRWLQJ

$SSHQGL[5HVLVWDQFH7DEOHRI2XWGRRUDQG,QGRRU7XEH7HPSHUDWXUH6HQVRUV .
7HPS 5HVLVWDQFH N

7HPS 5HVLVWDQFH N


7HPS

5HVLVWDQFH N

7HPS

5HVLVWDQFH N




























































































































































































































































































































































































































































































































































































































Downloaded from www.Manualslib.com manuals search engine

7URXEOHVKRRWLQJ

$SSHQGL[5HVLVWDQFH7DEOHIRU2XWGRRU'LVFKDUJH7HPSHUDWXUH6HQVRU .

7HPS 5HVLVWDQFH N

7HPS

5HVLVWDQFH N
















































































































































































































































































































7HPS 5HVLVWDQFH N

7HPS 5HVLVWDQFH N













































































































































































































































































































1RWH7KHLQIRUPDWLRQDERYHLVIRUUHIHUHQFHRQO\


Downloaded from www.Manualslib.com manuals search engine

5HPRYDO3URFHGXUH

5HPRYDO3URFHGXUH
5HPRYDO3URFHGXUH .
:DUQLQJ%HVXUHWRZDLWIRUDPLQLPXPRIPLQXWHVDIWHU
WXUQLQJRIIDOOSRZHUVXSSOLHVEHIRUHGLVDVVHPEO\

3URFHGXUH

6WHSV
5HPRYHWRSFRYHUDQGKDQGOH

%HIRUHGLVDVVHPEO\

7ZLVWRIIWKHVFUHZVXVHGIRU[LQJWKHKDQGOHSXOO
WKHKDQGOHXSZDUGWRUHPRYHLW

+DQGOH

7RSSDQHO

7ZLVW RII WKH VFUHZV XVHG IRU [LQJ WKH WRS FRYHU
SXOOWKHWRSFRYHUXSZDUGWRUHPRYHLW


Downloaded from www.Manualslib.com manuals search engine

5HPRYDO3URFHGXUH

3URFHGXUH

6WHSV
5HPRYHIURQWJULOOHDQGIURQWSDQHO


5HPRYH WKH VFUHZV FRQQHFWLQJ WKH IURQW JULOOH


DQGWKHIURQWSDQHO5HPRYHWKHIURQWJULOOH

)URQWJULOOH

7ZLVW RII WKH VFUHZV IL[LQJ WKH SDQHO SXOO LW


XSZDUGORRVHQWKHFODVSRQWKHULJKWVLGHURWDWH
LWWRWKHOHIWDQGWKHQUHPRYHWKHIURQWSDQHO

)URQWSDQHO
5HPRYHULJKWVLGHSODWH



5HPRYH WKH VFUHZV FRQQHFWLQJ WKH ULJKW VLGH


SODWHZLWKWKHFKDVVLVWKHYDOYHVXSSRUWDQGWKH
HOHFWULFER[DQGWKHQUHPRYHWKHULJKWVLGHSODWH
DVV\
ULJKWVLGH
SODWH

5HPRYHWKHVFUHZVFRQQHFWLQJWKHOHIWVLGHSOD
WHDQGWKHFKDVVLVDQGWKHQUHPRYHWKHOHIWVLGH
SODWHDVV\

/HIW6LGH3ODWH


Downloaded from www.Manualslib.com manuals search engine

5HPRYDO3URFHGXUH

3URFHGXUH

6WHSV
5HPRYHWKHD[LDORZIDQ


5HPRYH WKH QXWV [LQJ WKH EODGH DQG WKHQUHPRYH


WKHD[LDORZIDQ
$[LDO)ORZ)DQ

5HPRYHWKHWDSSLQJVFUHZV[LQJWKHPRWRUGLV
FRQQHFWWKHOHDGLQJZLUHLQVHUWRIWKHPRWRUDQGWKHQ
UHPRYHWKHPRWRU5HPRYHWKHWDSSLQJVFUHZV
[LQJWKHPRWRUVXSSRUWDQGWKHQSXOOWKHPRWRUVXS
SRUWXSZDUGVWRUHPRYHLW
IDQPRWRU
[LQJIUDPH

IDQPRWRU
5HPRYH(OHFWULF%R[$VV\
5HPRYHWKHVFUHZV[LQJWKHHOHFWULFER[VXEDVV\
ORRVHQWKHZLUHEXQGOHSXOORXWWKHZLULQJWHUPLQDOV
DQGWKHQSXOOWKHHOHFWULFER[XSZDUGVWRUHPRYHLW


Downloaded from www.Manualslib.com manuals search engine

(OHFWULF%R[

5HPRYDO3URFHGXUH

3URFHGXUH

6WHSV
5HPRYHVRXQGSURRIVSRQJH

7HDUXSWKHVRXQGSURRIVSRQJHFDUHIXOO\

6RXQGSURRI
VSRQJH

5HPRYHUHDFWRU

5HPRYH VFUHZV FRQQHFWLQJ UHDFWRU DQG PLGGOH


LVRODWLRQVKHHWDQGWKHQUHPRYHWKHUHDFWRU

UHDFWRU

5HPRYHZD\YDOYH
ZD\
'LVFKDUJH WKH UHIULJHUDQW FRPSOHWHO\XQVROGHU

YDOYH

WKH SLSHOLQHV FRQQHFWLQJ WKH FRPSUHVVRU DQG WKH


FRQGHQVHUDVV\DQGWKHQUHPRYHWKHZD\YDOYH
DVV\


Downloaded from www.Manualslib.com manuals search engine

5HPRYDO3URFHGXUH

3URFHGXUH

6WHSV
5HPRYHHOHFWURQLFH[SDQVLRQYDOYHDQGFXWRIIYDOYH

HOHFWURQLFH[SDQVLRQYDOYH
5HPRYH HOHFWURQLF H[SDQVLRQ YDOYH DQG FXWRII
YDOYH 8QVROGHU WKH VSRW ZHOG EHWZHHQ HOHFWURQLF
H[SDQVLRQ YDOYH DQG FXWRII YDOYH DV ZHOO DV WKH
VSRW ZHOG RI FRQQHFWLRQ SLSH IRU FRQGHQVHU DQG
WKHQ UHPRYH WKH H[SDQVLRQ YDOYH 0HDQZKLOH
URWDWH RXW WKH HOHFWURQLF FRLO DQG WKHQ SXOO LW

FXWRIIYDOYH

XSZDUGVWRUHPRYHLW

5HPRYHYDOYHVXSSRUWVXEDVV\

5HPRYHVFUHZV[LQJYDOYHVXSSRUWDQGFKDVVLV
DQGWKHQUHPRYHWKHYDOYHVXSSRUWVXEDVV\

YDOYHVXSSRUW
VXEDVV\

5HPRYHLVRODWLRQVKHHW
5HPRYH VFUHZV IL[LQJ LVRODWLRQ VKHHW DQG WKHQ
UHPRYHWKHLVRODWLRQVKHHW

LVRODWLRQVKHHW


Downloaded from www.Manualslib.com manuals search engine

S-ar putea să vă placă și