APPLICATION :
For used in primary aerial cable on
pole.
CLASSIFICATION :
Temperature :
- Normal operation 90C.
- Emergency over load conditions
130C.
- Short circuit conditions 250C.
Voltage rating :
25 kV phase to phase.
AC TESTING VOLTAGE :
38 kV for 5 minutes
REFERENCE STANDARD :
ICEA S-66-524 / MEA / PEA
TIS 2341-2550
CONSTRUCTION :
Conductor : Compact stranded hard drawn Aluminium wire.
Conductor shield : Semi-conducting cross-linked polyethylene.
Insulation : Cross-linked polyethylene (Natural)
Sheath : Track resistant cross-linked polyethylene (Black)
Maximum
Nominal
Minimum
Number of
Conduc tor
of
Area
w ire
(approx.)
Insulation
mm
NO
mm
mm
mm
mm
/ km
M-km
kg / km
25
5.90
3.18
3.18
20.0
1.2000
2,827
119
317
1,000/R
35
6.95
3.18
3.18
21.0
0.8680
2,580
149
363
1,000/R
50
8.33
3.18
3.18
22.0
0.6410
2,314
186
432
1,000/R
70
12
9.73
3.18
3.18
24.5
0.4430
2,100
229
509
1,000/R
95
15
11.45
3.18
3.18
26.0
0.3200
1,887
279
615
1,000/R
120
15
12.95
3.18
3.18
27.0
0.2530
1,712
321
729
1,000/R
150
15
14.27
3.18
3.18
29.5
0.2060
1,600
371
826
1,000/R
185
30
15.98
3.18
3.18
31.0
0.1640
1,477
429
959
1,000/R
240
30
18.47
3.18
3.18
33.5
0.1250
1,328
520
1,170
1,000/R
of sheath
Overall
DC.
c onduc tor
(approx.)
resistanc e
Allow able
Sec tional
Thic kness
Diameter
Minimum
at 20C
insulation
resistanc e
at 15.6C
ampac ities
Cable
in free air
w eight
at 40C
(approx.)
Standard
pac king
ambient
R = Packing in reel
Page 1 of 1
APPLICATION :
For used in primary aerial cable on
pole.
CLASSIFICATION :
Temperature :
- Normal operation 90C.
- Emergency over load conditions
130C.
- Short circuit conditions 250C.
Voltage rating :
25 kV phase to phase.
AC TESTING VOLTAGE :
49 kV for 5 minutes
REFERENCE STANDARD :
ICEA S-66-524 / MEA / PEA
TIS 2341-2550
CONSTRUCTION :
Conductor : Compact stranded hard drawn Aluminium wire.
Conductor shield : Semi-conducting cross-linked polyethylene.
Insulation : Cross-linked polyethylene (Natural)
Sheath : Track resistant cross-linked polyethylene (Black)
Maximum
Diameter of Thic kness
Nominal
Minimum
Number of
Conduc tor
of
Area
w ire
(approx.)
Insulation
mm
NO
mm
mm
mm
mm
/ km
M-km
kg / km
25
5.90
4.45
3.18
22.5
1.2000
3,153
118
393
1,000/R
35
6.95
4.45
3.18
24.5
0.8680
2,890
148
443
1,000/R
50
8.33
4.45
3.18
25.5
0.6410
2,606
184
517
1,000/R
70
12
9.73
4.45
3.18
27.5
0.4430
2,375
227
599
1,000/R
95
15
11.45
4.45
3.18
29.0
0.3200
2,144
276
711
1,000/R
120
15
12.95
4.45
3.18
31.0
0.2530
1,952
318
831
1,000/R
150
15
14.27
4.45
3.18
32.5
0.2060
1,830
367
933
1,000/R
185
30
15.98
4.45
3.18
33.5
0.1640
1,694
425
1,073
1,000/R
240
30
18.47
4.45
3.18
36.5
0.1250
1,529
515
1,293
1,000/R
of sheath
Overall
DC.
c onduc tor
(approx.)
resistanc e
Allow able
Sec tional
Thic kness
Diameter
Minimum
at 20C
insulation
resistanc e
at 15.6C
ampac ities
Cable
in free air
w eight
at 40C
(approx.)
Standard
pac king
ambient
R = Packing in reel
Page 1 of 1
APPLICATION :
For used in primary aerial cable on
pole.
CLASSIFICATION :
Temperature :
- Normal operation 90C.
- Emergency over load conditions
130C.
- Short circuit conditions 250C.
Voltage rating :
25 kV phase to phase.
AC TESTING VOLTAGE :
11 kV for 5 minutes
REFERENCE STANDARD :
ICEA S-66-524 / MEA / PEA
CONSTRUCTION :
Conductor : Compact stranded hard drawn Aluminium wire.
Conductor shield : Semi-conducting cross-linked polyethylene.
Insulation : Track resistant cross-linked polyethylene (Black)
Thic kness
Maximum
Nominal
Minimum
Diameter of
Number of
Conduc tor
Area
w ire
(approx.)
mm
NO
mm
mm
mm
/ km
M-km
35
6.95
2.32
12.0
0.8680
1,220
149
Shield &
Insulation
Overall
DC.
c onduc tor
(approx.)
resistanc e
Allow able
Sec tional
of Cdr.
Diameter
Minimum
at 20C
insulation
resistanc e
at 15.6C
ampac ities
Cable
in free air
w eight
at 40C
(approx.)
AC Test
Standard
V oltage
pac king
kg / km
kg / km
160
11
500/R
ambient
50
8.33
2.45
14.0
0.6410
1,000
186
216
11
500/R
70
12
9.73
2.55
15.0
0.4430
1,000
237
300
11
500/R
95
15
11.45
2.65
18.0
0.3200
790
279
371
11
500/R
120
15
12.95
2.70
20.0
0.2530
730
321
456
11
500/R
185
30
15.98
2.80
22.5
0.1640
760
429
659
11
500/R
R = Packing in reel
Page 1 of 1
APPLICATION :
For used in primary aerial cable on
pole.
CLASSIFICATION :
Temperature :
- Normal operation 90C.
- Emergency over load conditions
130C.
- Short circuit conditions 250C.
Voltage rating :
35 kV phase to phase.
AC TESTING VOLTAGE :
17 kV for 5 minutes
REFERENCE STANDARD :
ICEA S-66-524 / MEA / PEA
CONSTRUCTION :
Conductor : Compact stranded hard drawn Aluminium wire.
Conductor shield : Semi-conducting cross-linked polyethylene.
Insulation : Track resistant cross-linked polyethylene (Black)
Thic kness
Maximum
Nominal
Minimum
Diameter of
Number of
Conduc tor
Area
w ire
(approx.)
mm
NO
mm
mm
mm
/ km
M-km
35
6.95
3.40
15.0
0.8680
1,530
148
Shield &
Insulation
Overall
DC.
c onduc tor
(approx.)
resistanc e
Allow able
Sec tional
of Cdr.
Diameter
Minimum
at 20C
insulation
resistanc e
at 15.6C
ampac ities
Cable
in free air
w eight
at 40C
(approx.)
AC Test
Standard
V oltage
pac king
kg / km
kg / km
200
17
500/R
ambient
50
8.33
3.55
16.0
0.6410
1,400
184
262
17
500/R
70
12
9.73
3.70
18.0
0.4430
1,250
234
360
17
500/R
95
15
11.45
3.85
20.0
0.3200
1,140
276
434
17
500/R
120
15
12.95
4.00
22.0
0.2530
1,080
318
531
17
500/R
185
30
15.98
4.10
25.0
0.1640
940
425
746
17
500/R
R = Packing in reel
Page 1 of 1
APPLICATION :
Preferably used for urban networks.
Exposed in aerial, direct burial,
conduit, open tray and underground
duct installation.
MAX. CONDUCTOR
TEMPERATURE :
90C (Normal Operation)
AC TEST VOLTAGE :
13 kV
REFERENCE STANDARD :
ICEA S-66-524
CONSTRUCTION :
Conductor : Compacted strand copper wire.
Conductor shield : Semi-conducting cross-linked polyethylene.
Insulation : Cross-linked polyethylene.
Insulation shield : Semi-conducting cross-linked polyethylene.
Shield : Annealed copper tape (or annealed copper wire).
Sheath : Polyvinyl chloride (Black). (Optional : Polyethylene)
Allowable
ampacities in
free air at
40C ambient
Cable
weight
(approx.)
M-km
kg / km
1,865
93
268
500/R
1,615
124
338
500/R
1,386
163
441
500/R
0.5240
1,235
200
546
500/R
0.3870
1,114
238
672
500/R
23
0.2680
960
298
937
500/R
2.03
25
0.1930
844
364
1,204
500/R
19.20
2.03
26
0.1530
751
422
1,463
500/R
2.29
20.50
2.03
28
0.1240
694
481
1,735
500/R
2.29
22.20
2.03
29
0.0991
632
555
2,144
500/R
18.47
2.29
24.70
2.03
32
0.0754
559
657
2,719
500/R
34
20.68
2.29
27.20
2.03
35
0.0601
502
756
3,363
500/R
400
55
23.39
2.29
30.40
2.03
39
0.0470
442
886
4,214
500/R
500
55
26.67
2.29
33.60
2.79
42
0.0366
395
1,025
5,282
500/R
630
55
30.00
2.29
37.20
2.79
47
0.0283
354
1,183
6,837
500/R
800
55
R = Packing in reel
34.00
2.29
41.00
2.79
51
0.0221
317
1,444
8,615
500/R
Nominal
Sectional
Area
Minimum
Number of
wire
Diameter of
Conductor
(approx.)
mm
NO
mm
mm
10
3.72
2.29
16
4.69
2.29
25
5.90
2.29
35
6.95
50
8.00
70
18
95
Diameter
over
insulation
(Approx.)
Maximum DC.
conductor
resistance at
20C
Thickness of
sheath
Overall
Diameter
(approx.)
mm
mm
mm
/ km
9.60
1.52
16
1.8300
10.60
1.52
17
1.1500
11.80
1.52
18
0.7270
2.29
12.90
1.52
19
2.29
13.90
1.52
20
9.73
2.29
15.70
2.03
18
11.45
2.29
17.40
120
18
12.95
2.29
150
18
14.27
185
34
15.98
240
34
300
Thickness of
Insulation
Minimum
insulation
resistance at
15.6C
Page 1 of 1
Standard
packing
APPLICATION :
Preferably used for urban networks.
Exposed in aerial, direct burial,
conduit, open tray and underground
duct installation.
MAX. CONDUCTOR
TEMPERATURE :
90C (Normal Operation)
AC TEST VOLTAGE :
27 kV
REFERENCE STANDARD :
ICEA S-66-524
CONSTRUCTION :
Conductor : Compacted strand copper wire.
Conductor shield : Semi-conducting cross-linked polyethylene.
Insulation : Cross-linked polyethylene.
Insulation shield : Semi-conducting cross-linked polyethylene.
Shield : Annealed copper tape (or annealed copper wire).
Sheath : Polyvinyl chloride (Black). (Optional : Polyethylene)
Nominal
Sectional
Area
Minimum
Number of
wire
Diameter of
Conductor
(approx.)
mm
NO
mm
mm
35
6.95
4.45
Thickness of
Insulation
Diameter
over
insulation
(Approx.)
Maximum DC.
conductor
resistance at
20C
Thickness of
sheath
Overall
Diameter
(approx.)
mm
mm
mm
/ km
17.20
2.03
24
0.5240
Minimum
insulation
resistance at
15.6C
Allowable
ampacities in
free air at
40C ambient
Cable weight
(approx.)
M-km
kg / km
2,032
199
735
500/R
Standard
packing
50
8.00
4.45
18.20
2.03
25
0.3870
1,857
238
871
500/R
70
18
9.73
4.45
20.00
2.03
27
0.2680
1,627
297
1,104
500/R
95
18
11.45
4.45
21.70
2.03
29
0.1930
1,450
363
1,382
500/R
120
18
12.95
4.45
23.50
2.03
31
0.1530
1,305
420
1,652
500/R
150
18
14.27
4.45
24.80
2.03
32
0.1240
1,215
478
1,932
500/R
185
34
15.98
4.45
26.50
2.03
34
0.0991
1,115
550
2,380
500/R
240
34
18.47
4.45
29.00
2.03
37
0.0754
996
652
2,972
500/R
300
34
20.68
4.45
31.50
2.03
39
0.0601
901
750
3,605
500/R
400
55
23.39
4.45
34.70
2.79
44
0.0470
800
870
4,615
500/R
500
55
26.67
4.45
37.90
2.79
48
0.0366
720
1,011
5,714
500/R
630
55
30.00
4.45
41.50
2.79
52
0.0283
649
1,171
7,203
500/R
800
55
34.00
4.45
45.30
2.79
56
0.0221
584
1,423
8,963
500/R
R = Packing in reel
Page 1 of 1
APPLICATION :
Preferably used for urban networks.
Exposed in aerial, direct burial,
conduit, open tray and underground
duct installation.
MAX. CONDUCTOR
TEMPERATURE :
90C (Normal Operation)
AC TEST VOLTAGE :
38 kV
REFERENCE STANDARD :
ICEA S-66-524
CONSTRUCTION :
Conductor : Compacted strand copper wire.
Conductor shield : Semi-conducting cross-linked polyethylene.
Insulation : Cross-linked polyethylene.
Insulation shield : Semi-conducting cross-linked polyethylene.
Shield : Annealed copper tape (or annealed copper wire).
Sheath : Polyvinyl chloride (Black). (Optional : Polyethylene)
Nominal
Sectional
Area
Minimum
Number of
wire
Diameter of
Conductor
(approx.)
mm
NO
mm
mm
35
6.95
6.60
Thickness of
Insulation
Diameter
over
insulation
(Approx.)
Maximum DC.
conductor
resistance at
20C
Thickness of
sheath
Overall
Diameter
(approx.)
mm
mm
mm
/ km
21.80
2.03
29
0.5240
Minimum
insulation
resistance at
15.6C
Allowable
ampacities in
free air at
40C ambient
Cable weight
(approx.)
M-km
kg / km
2,587
201
923
500/R
Standard
packing
50
8.00
6.60
22.60
2.03
30
0.3870
2,433
240
1,053
500/R
70
18
9.73
6.60
24.40
2.03
31
0.2680
2,157
301
1,297
500/R
95
18
11.45
6.60
26.10
2.03
34
0.1930
1,941
367
1,613
500/R
120
18
12.95
6.60
27.90
2.03
35
0.1530
1,761
424
1,895
500/R
150
18
14.27
6.60
29.20
2.03
37
0.1240
1,648
483
2,185
500/R
185
34
15.98
6.60
30.90
2.03
38
0.0991
1,522
556
2,617
500/R
240
34
18.47
6.60
33.40
2.03
41
0.0754
1,370
659
3,224
500/R
300
34
20.68
6.60
35.90
2.79
45
0.0601
1,247
758
4,014
500/R
400
55
23.39
6.60
39.10
2.79
49
0.0470
1,114
879
4,961
500/R
500
55
26.67
6.60
42.30
2.79
52
0.0366
1,008
1,022
6,083
500/R
630
55
30.00
6.60
45.90
2.79
56
0.0283
913
1,183
7,552
500/R
800
55
34.00
6.60
49.70
2.79
60
0.0221
826
1,413
9,337
500/R
R = Packing in reel
Page 1 of 1
APPLICATION :
Preferably used for urban networks.
Exposed in aerial, direct burial,
conduit, open tray and underground
duct installation.
MAX. CONDUCTOR
TEMPERATURE :
90C (Normal Operation)
AC TEST VOLTAGE :
49 kV
REFERENCE STANDARD :
ICEA S-66-524
CONSTRUCTION :
Conductor : Compacted strand copper wire.
Conductor shield : Semi-conducting cross-linked polyethylene.
Insulation : Cross-linked polyethylene.
Insulation shield : Semi-conducting cross-linked polyethylene.
Shield : Annealed copper tape (or annealed copper wire).
Sheath : Polyvinyl chloride (Black). (Optional : Polyethylene)
Diameter of
Conductor
(approx.)
Diameter
over
insulation
(Approx.)
Maximum DC.
conductor
resistance at
20C
Minimum
insulation
resistance at
15.6C
Allowable
ampacities in
free air at
40C ambient
Cable weight
(approx.)
M-km
kg / km
2,909
239
1,291
500/R
Nominal
Sectional
Area
Minimum
Number of
wire
mm
NO
mm
mm
50
8.00
8.76
70
18
9.73
8.76
28.80
2.03
37
0.2680
2,601
297
1,548
500/R
95
18
11.45
8.76
30.50
2.03
39
0.1930
2,356
362
1,848
500/R
120
18
12.95
8.76
32.30
2.03
41
0.1530
2,152
417
2,142
500/R
150
18
14.27
8.76
33.60
2.03
42
0.1240
2,022
474
2,439
500/R
185
34
15.98
8.76
35.30
2.79
45
0.0991
1,876
545
3,021
500/R
240
34
18.47
8.76
37.80
2.79
48
0.0754
1,698
643
3,652
500/R
300
34
20.68
8.76
40.30
2.79
51
0.0601
1,553
738
4,369
500/R
400
55
23.39
8.76
43.50
2.79
55
0.0470
1,397
854
5,296
500/R
500
55
26.67
8.76
46.70
2.79
58
0.0366
1,269
992
6,438
500/R
630
55
30.00
8.76
50.30
2.79
61
0.0283
1,154
1,146
7,930
500/R
800
55
34.00
8.76
54.10
2.79
65
0.0221
1,048
1,388
9,740
500/R
Thickness of
Insulation
Thickness of
sheath
Overall
Diameter
(approx.)
mm
mm
mm
/ km
27.00
2.03
36
0.3870
Standard
packing
R = Packing in reel
Page 1 of 1
APPLICATION :
For use in aerial, conduit and
underground duct installation.
CLASSIFICATION :
5 to 35 kV rating sunlight resistance,
AC and DC, 100% IL and 133% IL,
maximum conductor temperature
90C for normal operation, 130C for
emergency overload condition and
250C for short circuit condition.
REFERENCE STANDARD :
UL 1072
CONSTRUCTION :
Stranded bare copper : Compact-stranded annealed uncoated copper.
per ASTM B-496 and UL 1072
Extruded semi-conducting strand shield : Extruded semi-conducting cross-linked
polyethylene compound.
Insulation : Cross-linked polyethylene (XLPE).
Extruded semi-conducting insulation shield : Extruded semi-conducting cross-linked
polyethylene compound.
Bare copper wire shield : Uncoated helically applied copper wires.
Tape separator : Polyester non-woven tape
Sunlight resistant PVC sheath : Extruded PVC sheath " Sunlight resistant".
Note : When desired for manufacturing reasons, the semi-conducting tape may be applied over stranded bare copper conductor.
Page 1 of 5
Approx.
Conduc tor
Insulation
Sheath
Diameter
Thic kness
Copper Shield
Thic kness
(AW G or kc mil)
(mm)
(mm)
(mm)
(mm)
(mm)
(kg / km)
6.8
2.29
20 / 0.8
1.52
21
635
Size
Outside
Diameter
A pprox. Cable
W eight
Ampac ities**
190
7.6
2.29
20 / 0.8
1.52
21
725
225
1/0
8.6
2.29
20 / 0.8
1.52
22
840
260
2/0
9.6
2.29
20 / 0.8
2.03
24
1,035
300
4/0
12.1
2.29
20 / 0.8
2.03
27
1,440
400
250
13.2
2.29
20 / 0.8
2.03
28
1,650
445
350
15.7
2.29
20 / 0.8
2.03
31
2,145
550
500
18.7
2.29
20 / 0.8
2.03
34
2,885
695
750
23.0
2.29
20 / 0.8
2.03
39
4,175
900
1000
26.9
2.29
20 / 0.8
2.03
43
5,395
1,075
** Ampacities for one insulated conductor isolated in air based on conductor temperature of 90C and ambient air temperature of
40C per Table 310-69 of the 1990 National Electrical Code (NFPA 70-1990)
Approx.
Conduc tor
Insulation
Sheath
Diameter
Thic kness
Copper Shield
Thic kness
(AW G or kc mil)
(mm)
(mm)
(mm)
(mm)
(mm)
(kg / km)
6.8
2.29
20 / 0.8
1.52
21
635
Size
Outside
Diameter
A pprox. Cable
W eight
Ampac ities**
190
7.6
2.29
20 / 0.8
1.52
21
725
225
1/0
8.6
2.29
20 / 0.8
1.52
22
840
260
2/0
9.6
2.29
20 / 0.8
2.03
24
1,035
300
4/0
12.1
2.29
20 / 0.8
2.03
27
1,440
400
250
13.2
2.29
20 / 0.8
2.03
28
1,650
445
350
15.7
2.29
20 / 0.8
2.03
31
2,145
550
500
18.7
2.29
20 / 0.8
2.03
34
2,885
695
750
23.0
2.29
20 / 0.8
2.03
39
4,175
900
1000
26.9
2.29
20 / 0.8
2.03
43
5,395
1,075
** Ampacities for one insulated conductor isolated in air based on conductor temperature of 90C and ambient air temperature of
40C per Table 310-69 of the 1990 National Electrical Code (NFPA 70-1990)
Page 2 of 5
Approx.
Conduc tor
Insulation
Sheath
Diameter
Thic kness
Copper Shield
Thic kness
(AW G or kc mil)
(mm)
(mm)
(mm)
(mm)
(mm)
(kg / km)
6.8
4.45
20 / 0.8
2.03
26
820
Size
Outside
Diameter
A pprox. Cable
W eight
Ampac ities**
195
7.6
4.45
20 / 0.8
2.03
27
920
225
1/0
8.6
4.45
20 / 0.8
2.03
28
1,045
260
2/0
9.6
4.45
20 / 0.8
2.03
29
1,195
300
4/0
12.1
4.45
20 / 0.8
2.03
31
1,615
400
250
13.2
4.45
20 / 0.8
2.03
33
1,835
445
350
15.7
4.45
20 / 0.8
2.03
36
2,375
550
500
18.7
4.45
20 / 0.8
2.03
39
3,135
685
750
23.0
4.45
20 / 0.8
2.03
44
4,430
885
1000
26.9
4.45
20 / 0.8
2.79
49
5,830
1,060
** Ampacities for one insulated conductor isolated in air based on conductor temperature of 90C and ambient air temperature of
40C per Table 310-69 of the 1990 National Electrical Code (NFPA 70-1990)
Approx.
Conduc tor
Insulation
Sheath
Diameter
Thic kness
Copper Shield
Thic kness
(AW G or kc mil)
(mm)
(mm)
(mm)
(mm)
(mm)
(kg / km)
6.8
5.46
20 / 0.8
2.03
26
895
Size
Outside
Diameter
A pprox. Cable
W eight
Ampac ities**
195
7.6
5.46
20 / 0.8
2.03
29
995
225
1/0
8.6
5.46
20 / 0.8
2.03
30
1,125
260
2/0
9.6
5.46
20 / 0.8
2.03
31
1,280
300
4/0
12.1
5.46
20 / 0.8
2.03
33
1,705
400
250
13.2
5.46
20 / 0.8
2.03
35
1,930
445
350
15.7
5.46
20 / 0.8
2.03
38
2,480
550
500
18.7
5.46
20 / 0.8
2.03
41
3,250
685
750
23.0
5.46
20 / 0.8
2.79
47
4,710
885
1000
26.9
5.46
20 / 0.8
2.79
52
6,020
1,060
** Ampacities for one insulated conductor isolated in air based on conductor temperature of 90C and ambient air temperature of
40C per Table 310-69 of the 1990 National Electrical Code (NFPA 70-1990)
Page 3 of 5
Approx.
Conduc tor
Insulation
Sheath
Diameter
Thic kness
Copper Shield
Thic kness
(AW G or kc mil)
(mm)
(mm)
(mm)
(mm)
(mm)
(kg / km)
7.6
6.60
20 / 0.8
2.03
31
1,095
225
1/0
8.6
6.60
20 / 0.8
2.03
32
1,225
260
2/0
9.6
6.60
20 / 0.8
2.03
33
1,380
300
4/0
12.1
6.60
20 / 0.8
2.03
36
1,845
395
250
13.2
6.60
20 / 0.8
2.03
37
2,075
440
350
15.7
6.60
20 / 0.8
2.03
40
2,605
545
500
18.7
6.60
20 / 0.8
2.03
43
3,385
680
750
23.0
6.60
20 / 0.8
2.79
50
4,865
870
1000
26.9
6.60
20 / 0.8
2.79
54
6,195
1,040
Size
Outside
Diameter
A pprox. Cable
W eight
Ampac ities**
** Ampacities for one insulated conductor isolated in air based on conductor temperature of 90C and ambient air temperature of
40C per Table 310-69 of the 1990 National Electrical Code (NFPA 70-1990)
Size
(AW G or kc mil)
Conduc tor
Insulation
Sheath
Diameter
Thic kness
Copper Shield
Thic kness
(mm)
(mm)
(mm)
(mm)
Approx.
Outside
Diameter
(mm)
A pprox. Cable
W eight
Ampac ities**
(kg / km)
7.6
8.76
20 / 0.8
2.03
36
1,320
225
1/0
8.6
8.76
20 / 0.8
2.03
37
1,460
260
2/0
9.6
8.76
20 / 0.8
2.03
38
1,625
300
4/0
12.1
8.76
20 / 0.8
2.03
40
2,080
395
250
13.2
8.76
20 / 0.8
2.03
42
2,315
440
350
15.7
8.76
20 / 0.8
2.79
46
3,005
545
500
18.7
8.76
20 / 0.8
2.79
49
3,815
680
750
23.0
8.76
20 / 0.8
2.79
54
5,235
870
1000
26.9
8.76
20 / 0.8
2.79
58
6,545
1,040
** Ampacities for one insulated conductor isolated in air based on conductor temperature of 90C and ambient air temperature of
40C per Table 310-69 of the 1990 National Electrical Code (NFPA 70-1990)
Page 4 of 5
Approx.
Conduc tor
Insulation
Sheath
Diameter
Thic kness
Copper Shield
Thic kness
(AW G or kc mil)
(mm)
(mm)
(mm)
(mm)
(mm)
(kg / km)
1/0
8.6
8.76
20 / 0.8
2.03
37
1,406
Size
Outside
Diameter
A pprox. Cable
W eight
Ampac ities**
260
2/0
9.6
8.76
20 / 0.8
2.03
38
1,625
300
4/0
12.1
8.76
20 / 0.8
2.03
40
2,080
395
250
13.2
8.76
20 / 0.8
2.03
42
2,315
440
350
15.7
8.76
20 / 0.8
2.79
46
3,005
545
500
18.7
8.76
20 / 0.8
2.79
49
3,815
680
750
23.0
8.76
20 / 0.8
2.79
54
5,235
870
1000
26.9
8.76
20 / 0.8
2.79
58
6,545
1,040
** Ampacities for one insulated conductor isolated in air based on conductor temperature of 90C and ambient air temperature of
40C per Table 310-69 of the 1990 National Electrical Code (NFPA 70-1990)
Approx.
Conduc tor
Insulation
Sheath
Diameter
Thic kness
Copper Shield
Thic kness
(AW G or kc mil)
(mm)
(mm)
(mm)
(mm)
(mm)
(kg / km)
1/0
8.6
10.67
20 / 0.8
2.03
41
1,670
260
2/0
9.6
10.67
20 / 0.8
2.03
42
1,840
300
4/0
12.1
10.67
20 / 0.8
2.79
46
2,450
395
250
13.2
10.67
20 / 0.8
2.79
47
2,700
440
350
15.7
10.67
20 / 0.8
2.79
50
3,270
545
500
18.7
10.67
20 / 0.8
2.79
53
4,140
680
750
23.0
10.67
20 / 0.8
2.79
58
5,550
870
1000
26.9
10.67
20 / 0.8
2.79
62
6,880
1,040
Size
Outside
Diameter
A pprox. Cable
W eight
Ampac ities**
** Ampacities for one insulated conductor isolated in air based on conductor temperature of 90C and ambient air temperature of
40C per Table 310-69 of the 1990 National Electrical Code (NFPA 70-1990)
Page 5 of 5
APPLICATION :
For use in aerial, conduit and
underground duct installation.
CLASSIFICATION :
5 to 35 kV enhance cable tray use,
rating sunlight resistance, AC and DC,
100% IL and 133% IL, maximum
conductor temperature 90C for
normal operation, 130C for
emergency overload condition and
250C for short circuit condition.
REFERENCE STANDARD :
UL 1072
CONSTRUCTION :
Stranded bare copper : Compact-stranded annealed uncoated copper.
per ASTM B-496 and UL 1072
Extruded semi-conducting strand shield : Extruded semi-conducting cross-linked
polyethylene compound.
Insulation : Cross-linked polyethylene (XLPE).
Extruded semi-conducting insulation shield : Extruded semi-conducting cross-linked
polyethylene compound.
Uncoated copper tape shield : Uncoated copper tape.
Sunlight resistant +cable tray use PVC sheath : Extruded PVC sheath "Sunlight
resistant cable tray use".
Note : When desired for manufacturing reasons, the semi-conducting tape may be applied over stranded bare copper conductor.
Page 1 of 5
Size
Conduc tor
Insulation
Sheath
Approx. Outside
Approx. Cable
Diameter
Thic kness
Thic kness
Diameter
W eight
(A W G or kc mil)
(mm)
(mm)
(mm)
(mm)
(kg / km)
Ampac ities**
6.8
2.29
1.52
19
545
190
7.6
2.29
1.52
20
640
225
1/0
8.6
2.29
1.52
21
755
260
2/0
9.6
2.29
1.52
22
900
300
4/0
12.1
2.29
2.03
25
1,355
400
250
13.2
2.29
2.03
27
1,570
445
350
15.7
2.29
2.03
29
2,070
550
500
18.7
2.29
2.03
32
2,815
695
750
23.0
2.29
2.03
38
4,110
900
1000
26.9
2.29
2.03
42
5,335
1,075
** Ampacities for one insulated conductor installed in a single layer in uncovered cable trays with a maintained space of not less
than one cable diameter between individual conductors based on conductor temperature of 90C and ambient air temperature of
40C per Table 310-69 of the 1990 National Electrical Code (NFPA 70-1990).
Conduc tor
Insulation
Sheath
Approx. Outside
Approx. Cable
Diameter
Thic kness
Thic kness
Diameter
W eight
(A W G or kc mil)
(mm)
(mm)
(mm)
(mm)
(kg / km)
6.8
2.29
1.52
19
545
Size
Ampac ities**
190
7.6
2.29
1.52
20
640
225
1/0
8.6
2.29
1.52
21
755
260
2/0
9.6
2.29
1.52
22
900
300
4/0
12.1
2.29
2.03
25
1,355
400
250
13.2
2.29
2.03
27
1,570
445
350
15.7
2.29
2.03
29
2,070
550
500
18.7
2.29
2.03
32
2,815
695
750
23.0
2.29
2.03
38
4,110
900
1000
26.9
2.29
2.03
42
5,335
1,075
** Ampacities for one insulated conductor installed in a single layer in uncovered cable trays with a maintained space of not less
than one cable diameter between individual conductors based on conductor temperature of 90C and ambient air temperature of
40C per Table 310-69 of the 1990 National Electrical Code (NFPA 70-1990).
Page 2 of 5
Size
Conduc tor
Insulation
Sheath
Approx. Outside
Approx. Cable
Diameter
Thic kness
Thic kness
Diameter
W eight
(A W G or kc mil)
(mm)
(mm)
(mm)
(mm)
(kg / km)
Ampac ities**
6.8
4.45
2.03
24
735
195
7.6
4.45
2.03
25
835
225
1/0
8.6
4.45
2.03
26
960
260
2/0
9.6
4.45
2.03
27
1,115
300
4/0
12.1
4.45
2.03
30
1,535
400
250
13.2
4.45
2.03
31
1,760
445
350
15.7
4.45
2.03
34
2,305
550
500
18.7
4.45
2.03
37
3,070
685
750
23.0
4.45
2.03
42
4,370
885
1000
26.9
4.45
2.79
47
5,770
1,060
** Ampacities for one insulated conductor installed in a single layer in uncovered cable trays with a maintained space of not less
than one cable diameter between individual conductors based on conductor temperature of 90C and ambient air temperature of
40C per Table 310-69 of the 1990 National Electrical Code (NFPA 70-1990).
Conduc tor
Insulation
Sheath
Approx. Outside
Approx. Cable
Diameter
Thic kness
Thic kness
Diameter
W eight
(A W G or kc mil)
(mm)
(mm)
(mm)
(mm)
(kg / km)
6.8
5.46
2.03
26
815
Size
Ampac ities**
195
7.6
5.46
2.03
27
915
225
1/0
8.6
5.46
2.03
28
1,045
260
2/0
9.6
5.46
2.03
29
1,200
300
4/0
12.1
5.46
2.03
32
1,630
400
250
13.2
5.46
2.03
33
1,855
445
350
15.7
5.46
2.03
36
2,410
550
500
18.7
5.46
2.03
39
3,185
685
750
23.0
5.46
2.03
44
4,505
885
1000
26.9
5.46
2.79
50
5,965
1,060
** Ampacities for one insulated conductor installed in a single layer in uncovered cable trays with a maintained space of not less
than one cable diameter between individual conductors based on conductor temperature of 90C and ambient air temperature of
40C per Table 310-69 of the 1990 National Electrical Code (NFPA 70-1990).
Page 3 of 5
Size
(A W G or kc mil)
Conduc tor
Insulation
Sheath
Approx. Outside
Approx. Cable
Diameter
Thic kness
Thic kness
Diameter
W eight
(mm)
(mm)
(mm)
(mm)
(kg / km)
Ampac ities**
7.6
6.60
2.03
29
1,015
225
1/0
8.6
6.60
2.03
30
1,145
260
2/0
9.6
6.60
2.03
31
1,305
300
4/0
12.1
6.60
2.03
34
1,775
395
250
13.2
6.60
2.03
36
2,005
440
350
15.7
6.60
2.03
38
2,540
545
500
18.7
6.60
2.03
41
3,325
680
750
23.0
6.60
2.79
48
4,810
870
1000
26.9
6.60
2.79
52
6,145
1,040
** Ampacities for one insulated conductor installed in a single layer in uncovered cable trays with a maintained space of not less
than one cable diameter between individual conductors based on conductor temperature of 90C and ambient air temperature of
40C per Table 310-69 of the 1990 National Electrical Code (NFPA 70-1990).
Size
(A W G or kc mil)
Conduc tor
Insulation
Sheath
Approx. Outside
Approx. Cable
Diameter
Thic kness
Thic kness
Diameter
W eight
(mm)
(mm)
(mm)
(mm)
(kg / km)
Ampac ities**
7.6
8.76
2.03
34
1,250
225
1/0
8.6
8.76
2.03
35
1,390
260
2/0
9.6
8.76
2.03
36
1,555
300
4/0
12.1
8.76
2.03
39
2,015
395
250
13.2
8.76
2.03
40
2,255
440
350
15.7
8.76
2.03
42
2,805
545
500
18.7
8.76
2.79
47
3,755
680
750
23.0
8.76
2.79
53
5,185
870
1000
26.9
8.76
2.79
57
6,500
1,040
** Ampacities for one insulated conductor installed in a single layer in uncovered cable trays with a maintained space of not less
than one cable diameter between individual conductors based on conductor temperature of 90C and ambient air temperature of
40C per Table 310-69 of the 1990 National Electrical Code (NFPA 70-1990).
Page 4 of 5
Size
Conduc tor
Insulation
Sheath
Approx. Outside
Approx. Cable
Diameter
Thic kness
Thic kness
Diameter
W eight
(A W G or kc mil)
(mm)
(mm)
(mm)
(mm)
(kg / km)
Ampac ities**
1/0
8.6
8.76
2.03
35
1,390
260
2/0
9.6
8.76
2.03
36
1,555
300
4/0
12.1
8.76
2.03
39
2,015
395
250
13.2
8.76
2.03
40
2,255
440
500
15.7
8.76
2.03
42
2,805
545
500
18.7
8.76
2.79
47
3,755
680
750
23.0
8.76
2.79
53
5,185
870
1000
26.9
8.76
2.79
57
6,500
1,040
** Ampacities for one insulated conductor installed in a single layer in uncovered cable trays with a maintained space of not less
than one cable diameter between individual conductors based on conductor temperature of 90C and ambient air temperature of
40C per Table 310-69 of the 1990 National Electrical Code (NFPA 70-1990).
Size
Conduc tor
Insulation
Sheath
Approx. Outside
Approx. Cable
Diameter
Thic kness
Thic kness
Diameter
W eight
(A W G or kc mil)
(mm)
(mm)
(mm)
(mm)
(kg / km)
1/0
8.6
10.67
2.03
39
1,605
Ampac ities**
260
2/0
9.6
10.67
2.03
40
1,775
300
4/0
12.1
10.67
2.03
42
2,250
395
250
13.2
10.67
2.03
44
2,495
440
500
15.7
10.67
2.79
48
3,210
545
500
18.7
10.67
2.79
51
4,090
680
750
23.0
10.67
2.79
56
5,505
870
1000
26.9
10.67
2.79
60
6,840
1,040
** Ampacities for one insulated conductor installed in a single layer in uncovered cable trays with a maintained space of not less
than one cable diameter between individual conductors based on conductor temperature of 90C and ambient air temperature of
40C per Table 310-69 of the 1990 National Electrical Code (NFPA 70-1990).
Page 5 of 5
APPLICATION :
Preferably used for urban networks.
Exposed in aerial, direct burial,
conduit, open tray and underground
duct installation.
MAX. CONDUCTOR
TEMPERATURE :
90C (Normal Operation)
AC TESTING VOLTAGE :
6.5 kV
REFERENCE STANDARD :
IEC 60502-2
CONSTRUCTION :
Conductor : Compact round stranded copper.
Conductor shield : Semi-conducting cross-linked polyethylene.
Insulation : Cross-linked polyethylene.
Insulation shield : Semi-conducting cross-linked polyethylene.
Sheath : Annealed copper wire with copper contact tape (or annealed copper tape)
Separator tape : Spunbond tape (Optional : Water Blocking Tape)
Sheath : Black polyethylene (ST 7) (Optional : Polyvinyl Chloride)
Nominal
sectional
area
Minimum
Number of
wire
mm
Diameter of
Conductor
(approx.)
Thickness of
Insulation
Diameter
over
insulation
(Approx.)
Number
of wire
mm
mm
mm
Thickness of
Sheath
Overall
diameter
(approx.)
Maximum DC.
resistance of
Cdr. at 20C
Minimum
insulation
resistance at
20C
Allowable
ampacities in
free air at
40C
Cable
weight
(approx.)
Standard
packing
mm
mm
/ km
M-km
kg / km
m / reel
500
Diameter
of wire
mm
10
3.7
2.0
9.0
20
0.80
1.8
19
1.83
1,017
100
340
16
4.7
2.0
10.5
20
0.80
1.8
20
1.15
877
130
410
500
25
5.9
2.0
11.7
20
0.80
1.8
21
0.727
749
170
510
500
35
7.0
2.0
12.7
20
0.80
1.8
22
0.524
666
205
610
500
50
8.0
2.0
13.8
20
0.80
1.8
23
0.387
599
245
740
500
70
18
9.7
2.0
15.5
20
0.80
1.8
25
0.268
514
305
960
500
95
18
11.5
2.0
17.2
20
0.80
1.8
26
0.193
451
375
1,220
500
120
18
13.0
2.0
19.0
20
0.80
1.8
28
0.153
401
430
1,470
500
150
18
14.3
2.0
20.3
25
0.90
1.8
30
0.124
370
490
1,790
500
185
34
16.0
2.0
22.0
25
0.90
1.9
32
0.0991
336
560
2,160
500
240
34
18.5
2.0
24.5
30
1.03
1.9
35
0.0754
297
655
2,800
500
300
34
20.7
2.0
27.0
30
1.03
2.0
38
0.0601
266
750
3,420
500
400
55
23.4
2.0
30.2
30
1.03
2.1
41
0.047
234
880
4,270
500
500
55
26.7
2.2
33.9
30
1.03
2.2
45
0.0366
228
980
5,330
500
630
55
30.0
2.4
37.9
30
1.03
2.3
49
0.0283
222
1,150
6,750
500
800
55
34.0
2.6
42.3
30
1.03
2.5
54
0.0221
214
1,300
8,500
500
Page 1 of 1
APPLICATION :
Preferably used for urban networks.
Exposed in aerial, direct burial,
conduit, open tray and underground
duct installation.
MAX. CONDUCTOR
TEMPERATURE :
90C (Normal Operation)
AC TESTING VOLTAGE :
12.5 kV
REFERENCE STANDARD :
IEC 60502-2
CONSTRUCTION :
Conductor : Compact round stranded copper.
Conductor shield : Semi-conducting cross-linked polyethylene.
Insulation : Cross-linked polyethylene.
Insulation shield : Semi-conducting cross-linked polyethylene.
Sheath : Annealed copper wire with copper contact tape (or annealed copper tape)
Separator tape : Spunbond tape (Optional : Water Blocking Tape)
Sheath : Black polyethylene (ST 7) (Optional : Polyvinyl Chloride)
Nominal
sectional
area
Minimum
Number of
wire
mm
Diameter of
Conductor
(approx.)
Thickness of
Insulation
Diameter
over
insulation
(Approx.)
Number
of wire
Thickness of
Sheath
Overall
diameter
(approx.)
Maximum DC.
resistance of
Cdr. at 20C
Diameter
of wire
Minimum
insulation
resistance at
20C
Allowable
ampacities in
free air at
40C
Cable
weight
(approx.)
Standard
packing
mm
mm
mm
mm
mm
mm
/ km
M-km
kg / km
m / reel
10
3.7
2.5
10.0
20
0.80
1.8
20
1.83
1,194
100
360
500
16
4.7
2.5
11.5
20
0.80
1.8
21
1.15
1,037
130
430
500
25
5.9
2.5
12.7
20
0.80
1.8
22
0.727
892
170
530
500
35
7.0
2.5
13.7
20
0.80
1.8
23
0.524
796
205
640
500
50
8.0
2.5
14.8
20
0.80
1.8
24
0.387
719
245
760
500
70
18
9.7
2.5
16.5
20
0.80
1.8
25
0.268
621
305
990
500
95
18
11.5
2.5
18.2
20
0.80
1.8
27
0.193
547
375
1,250
500
120
18
13.0
2.5
20.0
20
0.80
1.8
29
0.153
487
430
1,510
500
150
18
14.3
2.5
21.3
25
0.90
1.8
31
0.124
450
490
1,820
500
185
34
16.0
2.5
23.0
25
0.90
1.9
33
0.0991
410
560
2,200
500
240
34
18.5
2.6
25.7
30
1.03
2.0
36
0.0754
376
655
2,860
500
300
34
20.7
2.8
28.6
30
1.03
2.1
39
0.0601
361
750
3,520
500
400
55
23.4
3.0
32.2
30
1.03
2.2
43
0.0407
340
880
4,390
500
500
55
26.7
3.2
35.9
30
1.03
2.3
47
0.0366
322
980
5,460
500
630
55
30.0
3.2
39.5
30
1.03
2.4
51
0.0283
289
1,150
6,910
500
800
55
34.0
3.2
43.5
30
1.03
2.5
56
0.0221
260
1,300
8,580
500
Page 1 of 1
APPLICATION :
Preferably used for urban networks.
Exposed in aerial, direct burial,
conduit, open tray and underground
duct installation.
MAX. CONDUCTOR
TEMPERATURE :
90C (Normal Operation)
AC TESTING VOLTAGE :
21 kV
REFERENCE STANDARD :
IEC 60502-2
CONSTRUCTION :
Conductor : Compact round stranded copper.
Conductor shield : Semi-conducting cross-linked polyethylene.
Insulation : Cross-linked polyethylene.
Insulation shield : Semi-conducting cross-linked polyethylene.
Sheath : Annealed copper wire with copper contact tape (or annealed copper tape)
Separator tape : Spunbond tape (Optional : Water Blocking Tape)
Sheath : Black polyethylene (ST 7) (Optional : Polyvinyl Chloride)
Nominal
sectional
area
Minimum
Number of
wire
mm
Diameter of
Conductor
(approx.)
Thickness of
Insulation
Diameter
over
insulation
(Approx.)
Number
of wire
Thickness of
Sheath
Overall
diameter
(approx.)
Maximum DC.
resistance of
Cdr. at 20C
Diameter
of wire
Minimum
insulation
resistance at
20C
Allowable
ampacities in
free air at
40C
Cable
weight
(approx.)
Standard
packing
mm
mm
mm
mm
mm
mm
/ km
M-km
kg / km
m / reel
16
4.7
3.4
14.0
20
0.80
1.8
23
1.15
1,178
130
520
500
25
5.9
3.4
14.4
20
0.80
1.8
24
0.727
1,121
170
630
500
35
7.0
3.4
15.4
20
0.80
1.8
25
0.524
1,007
205
730
500
50
8.0
3.4
16.5
20
0.80
1.8
26
0.387
915
245
860
500
70
18
9.7
3.4
18.2
20
0.80
1.8
27
0.268
796
305
1,090
500
95
18
11.5
3.4
19.9
20
0.80
1.8
29
0.193
705
375
1,360
500
120
18
13.0
3.4
21.7
20
0.80
1.9
31
0.153
632
430
1,630
500
150
18
14.3
3.4
23.0
25
0.90
1.9
33
0.124
586
490
1,960
500
185
34
16.0
3.4
24.7
25
0.90
2.0
35
0.0991
536
555
2,340
500
240
34
18.5
3.4
27.2
30
1.03
2.1
38
0.0754
477
655
3,030
500
300
34
20.7
3.4
29.7
30
1.03
2.2
41
0.0601
429
745
3,650
500
400
55
23.4
3.4
33.0
30
1.03
2.3
44
0.047
380
855
4,510
500
500
55
26.7
3.4
36.2
30
1.03
2.4
48
0.0366
340
975
5,580
500
630
55
30.0
3.4
39.8
30
1.03
2.6
52
0.0283
306
1,150
7,050
500
800
55
34.0
3.4
43.6
30
1.03
2.7
57
0.0221
275
1,300
8,710
500
Page 1 of 1
APPLICATION :
Preferably used for urban networks.
Exposed in aerial, direct burial,
conduit, open tray and underground
duct installation.
MAX. CONDUCTOR
TEMPERATURE :
90C (Normal Operation)
AC TESTING VOLTAGE :
30.5 kV
REFERENCE STANDARD :
IEC 60502-2
CONSTRUCTION :
Conductor : Compact round stranded copper.
Conductor shield : Semi-conducting cross-linked polyethylene.
Insulation : Cross-linked polyethylene.
Insulation shield : Semi-conducting cross-linked polyethylene.
Sheath : Annealed copper wire with copper contact tape (or annealed copper tape)
Separator tape : Spunbond tape (Optional : Water Blocking Tape)
Sheath : Black polyethylene (ST 7) (Optional : Polyvinyl Chloride)
Nominal
sectional
area
Minimum
Number of
wire
mm
Diameter of
Conductor
(approx.)
Thickness of
Insulation
Diameter
over
insulation
(Approx.)
Number
of wire
Thickness
of Sheath
Overall
diameter
(approx.)
Diameter
of wire
Maximum
DC.
resistance
of Cdr. at
20C
Minimum
Allowable
insulation
ampacities
resistance at in free air at
20C
40C
Cable
weight
(approx.)
Standard
packing
mm
mm
mm
mm
mm
mm
/ km
M-km
kg / km
m / reel
25
5.9
4.5
17.4
20
0.80
1.8
26
0.727
1,266
160
700
500
35
7.0
4.5
17.6
20
0.80
1.8
27
0.524
1,232
195
810
500
50
8.0
4.5
18.7
20
0.80
1.8
28
0.387
1,126
235
940
500
70
18
9.7
4.5
20.4
20
0.80
1.8
30
0.268
987
295
1,170
500
95
18
11.5
4.5
22.1
20
0.80
1.9
32
0.193
880
355
1,460
500
120
18
13.0
4.5
23.9
20
0.80
1.9
33
0.153
792
430
1,730
500
150
18
14.3
4.5
25.2
25
0.90
2.0
35
0.124
737
465
2,080
500
185
34
16.0
4.5
26.9
25
0.90
2.0
38
0.0991
677
530
2,490
500
240
34
18.5
4.5
29.4
30
1.03
2.0
41
0.0754
605
620
3,160
500
300
34
20.7
4.5
31.9
30
1.03
2.3
43
0.0601
547
705
3,790
500
400
55
23.4
4.5
35.2
30
1.03
2.3
47
0.047
486
810
4,670
500
500
55
26.7
4.5
38.4
30
1.03
2.5
50
0.0366
437
930
5,750
500
630
55
30.0
4.5
42.0
30
1.03
2.6
55
0.0283
394
1,095
7,210
500
800
55
34.0
4.5
45.8
30
1.03
2.8
59
0.0221
354
1,240
8,920
500
Page 1 of 1
APPLICATION :
Preferably used for urban networks.
Exposed in aerial, direct burial,
conduit, open tray and underground
duct installation.
MAX. CONDUCTOR
TEMPERATURE :
90C (Normal Operation)
AC TESTING VOLTAGE :
42 kV
REFERENCE STANDARD :
IEC 60502-2
CONSTRUCTION :
Conductor : Compact round stranded copper.
Conductor shield : Semi-conducting cross-linked polyethylene.
Insulation : Cross-linked polyethylene.
Insulation shield : Semi-conducting cross-linked polyethylene.
Sheath : Annealed copper wire with copper contact tape (or annealed copper tape)
Separator tape : Polyester tape (Optional : Water Blocking Tape)
Sheath : Black polyethylene (ST 7) (Optional : Polyvinyl Chloride)
Nominal
sectional
area
Minimum
Number of
wire
mm
Diameter of
Conductor
(Approx.)
Thickness
of
insulation
(Min Avg)
Diameter
over
insulation
(Approx.)
Number
of wire
Nom.
diameter
of wire
mm
Thickness
of
sheath
(Min Avg)
Overall
diameter
(Approx.)
Cable
weight
(Approx.)
Max.
pulling
tension
(Cdr)
Set by
formers
Standard
packing
mm
mm
mm
mm
mm
kg / km
kN
mm
mm
m / reel
35
50
70
95
120
150
185
240
300
400
500
630
800
7
7
18
18
18
18
34
34
34
55
55
81
81
6.9
8.0
9.7
11.3
12.9
14.1
16.0
18.4
20.4
23.3
26.5
30.0
33.9
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5
19.0
20.0
22.0
23.5
25.5
26.5
28.5
31.0
33.0
36.5
39.5
43.0
47.0
0.80
0.80
0.80
0.80
0.80
0.90
0.90
1.03
1.03
1.03
1.03
1.03
1.03
20
20
20
20
20
25
25
30
30
30
30
30
30
1.8
1.8
1.9
1.9
2.0
2.0
2.1
2.2
2.2
2.3
2.4
2.5
2.7
26
27
29
31
33
35
37
40
42
45
49
53
58
845
985
1,240
1,525
1,815
2,190
2,595
3,300
3,940
4,835
5,960
7,420
9,220
2.5
3.5
4.9
6.7
8.4
10.5
13.0
16.9
21.1
28.1
35.1
44.3
56.2
520
540
580
620
660
700
740
800
840
900
980
1,060
1,160
390
405
435
465
495
525
555
600
630
675
735
795
870
500
500
500
500
500
500
500
500
500
500
500
500
500
1000
91
39.8
5.5
53.0
1.03
30
2.8
64
11,400
70.2
1,280
960
500
1200
127
42.9
5.5
56.0
1.03
30
2.9
67
13,090
84.3
1,340
1005
500
Page 1 of 3
at 90C
Hz
Min. IR
at 20C
Max.
Positive/Negative sequence
capacitance
impedance
area
at 20C
of cable
Trefoil
Flat*
Trefoil
Flat*
mm
/km
/km
/km
/km
/km
M-km
F/km
35
0.524
0.668
0.668
0.142
0.200
1420
0.156
50
0.387
0.494
0.494
0.136
0.194
1301
70
0.268
0.342
0.342
0.128
0.186
95
0.193
0.247
0.246
0.121
120
0.153
0.196
0.196
150
0.124
0.159
185
Trefoil
Flat*
/km
/km
Short circuit
Zero sequence
current for 1
impedance
second
Cdr.
Screen**
kA
kA
5.0
1.6
0.170
7.2
1.6
1149
0.193
10.0
1.6
0.179
1031
0.215
13.6
1.6
0.117
0.175
931
0.238
17.2
1.6
0.159
0.115
0.173
871
0.254
21.5
2.4
0.0991
0.1276 0.1271
0.111
0.169
796
0.278
26.5
2.4
240
0.0754
0.0978 0.0972
0.107
0.165
717
0.309
34.3
3.7
300
0.0601
0.0788 0.0780
0.104
0.162
654
0.338
42.9
3.7
400
0.0470
0.0628 0.0616
0.100
0.158
586
0.378
57.2
3.7
500
0.0366
0.0504 0.0489
0.097
0.156
528
0.419
71.5
3.7
630
0.0283
0.0408 0.0389
0.095
0.153
475
0.466
90.1
3.7
800
0.0221
0.0341 0.0316
0.092
0.150
429
0.516
3.7
1000
0.0176
0.0295 0.0266
0.088
0.146
374
0.591
3.7
1200
0.0151
0.0270 0.0238
0.087
0.145
351
0.631
3.7
/km
Page 2 of 3
In air
In ground
In PE duct in ground
Nominal
Trefoil
sectional
Flat
Trefoil
Flat
Trefoil
Flat
area
mm
0.5 x De
0.5 x De
35
182
216
168
175
145
149
50
218
258
198
206
171
175
70
271
322
241
252
209
214
95
330
393
288
300
249
255
120
382
453
327
341
283
289
150
433
511
366
378
315
317
185
498
586
413
426
355
356
240
586
681
475
482
400
390
300
670
775
533
537
447
431
400
775
891
603
604
503
478
500
894
1022
680
675
564
527
630
1024
1164
762
751
627
577
800
1157
1311
841
824
689
624
1000
1301
1475
917
897
752
671
1200
1389
1573
964
941
790
699
Sheath bonded at both Sheath bonded at both Sheath bonded at both Sheath bonded at both
end
end
end
end
Condition:
1.
2.
3.
4.
5.
6.
7.
Conductor temperature 90 C
Ambient air temperature 40 C
Ground temperature 30 C
Depth of laying 1.0 m in ground
Thermal resistivity of soil 1.2 K.m/W
Axial spacing between phase cable in flat formation 2xODcable or 2xODduct
Shields bonded at both end
Page 3 of 3
APPLICATION :
Preferably used for urban networks.
Exposed in aerial, direct burial,
conduit, open tray and underground
duct installation.
MAX. CONDUCTOR
TEMPERATURE :
90C (Normal Operation)
AC TESTING VOLTAGE :
63 kV
REFERENCE STANDARD :
IEC 60502-2
CONSTRUCTION :
Conductor : Compact round stranded copper.
Conductor shield : Semi-conducting cross-linked polyethylene.
Insulation : Cross-linked polyethylene.
Insulation shield : Semi-conducting cross-linked polyethylene.
Sheath : Annealed copper wire with copper contact tape (or annealed copper tape)
Separator tape : Spunbond tape (Optional : Water Blocking Tape)
Sheath : Black polyethylene (ST 7) (Optional : Polyvinyl Chloride)
N o minal
sect io nal
ar ea
M i ni mum
N umb er
o f wi r e
mm
D i amet er
of
C o nd uct o r
( ap p r o x.)
mm
T hickness
of
I nsul at i o n
mm
D iamet er
o ver
i nsul at i o n
( A p p r o x. )
C o p p er wir e
shi el d
N umb er
o f wi r e
mm
T hi ckness
o f Sheat h
Over all
d iamet er
( ap p r o x. )
M axi mum
DC.
r esi st ance
o f C d r . at
2 0 C
M inimum
i nsul at i o n
r esi st ance
at 2 0 C
A l l o wab l e
amp aci t i es
i n f r ee ai r
at 4 0 C
C ab l e
wei g ht
( ap p r o x.)
St and ar d
p acki ng
mm
mm
/ km
M - km
kg / km
m / r eel
D i amet er
o f wi r e
mm
50
8.0
8.0
25.9
20
0.80
2.0
36
0.387
1,656
235
1,270
500
70
18
9.7
8.0
27.6
20
0.80
2.1
38
0.268
1,476
295
1,560
500
95
18
11.5
8.0
29.3
20
0.80
2.1
40
0.193
1,334
355
1,850
500
120
18
13.0
8.0
31.1
20
0.80
2.2
42
0.153
1,216
410
2,160
500
150
18
14.3
8.0
32.4
25
0.90
2.3
44
0.124
1,141
460
2,530
500
185
34
16.0
8.0
34.1
25
0.90
2.3
45
0.0991
1,057
525
2,920
500
240
34
18.5
8.0
36.6
30
1.03
2.4
48
0.0754
955
620
3,620
555
300
34
20.7
8.0
39.1
30
1.03
2.5
51
0.0601
872
710
4,290
500
400
55
23.4
8.0
42.2
30
1.03
2.6
55
0.047
782
815
5,240
500
500
55
26.7
8.0
45.6
30
1.03
2.7
59
0.0366
709
940
6,390
500
630
55
30.0
8.0
49.2
30
1.03
2.9
63
0.0283
644
1,095
7,860
250
800
55
34.0
8.0
53.0
30
1.03
3.0
67
0.0221
585
1,235
9,590
250
Page 1 of 1
APPLICATION :
Preferably used for urban networks.
Exposed in aerial, direct burial,
conduit, open tray and underground
duct installation.
MAX. CONDUCTOR
TEMPERATURE :
90C (Normal Operation)
AC TESTING VOLTAGE :
12.5 kV
REFERENCE STANDARD :
IEC 60502-2
CONSTRUCTION :
Conductor : Compact round stranded copper.
Conductor shield : Semi-conducting cross-linked polyethylene.
Insulation : Cross-linked polyethylene.
Insulation shield : Semi-conducting cross-linked polyethylene.
Sheath : Copper tape shield
Bedding : Black polyethylene (Optional : Polyvinyl chloride)
Armour : Double Aluminum tape
Sheath : Black polyethylene (ST7) (Optional : Polyvinyl Chloride)
Nominal
sectional
area
Diameter
Thickness
Diameter
over
of
over armour
insulation
Aluminum
(approx.)
(Approx.) tape armour
M inimum
Number
of wire
Diameter
of
Conductor
(approx.)
mm
mm
mm
7
7
7
7
7
18
18
18
18
34
34
34
55
55
81
81
3.7
4.7
5.9
6.9
8.0
9.7
11.4
12.9
14.2
16.0
18.4
20.5
23.4
26.6
30.0
33.9
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.6
2.8
3.0
3.2
3.2
3.2
9.5
10.5
11.7
12.7
13.8
15.5
17.2
19.0
20.2
22.1
24.7
27.4
31.2
34.9
38.5
42.4
mm
10
16
25
35
50
70
95
120
150
185
240
300
400
500
630
800
Thickness
of
Insulation
mm
2x
2x
2x
2x
2x
2x
2x
2x
2x
2x
2x
2x
2x
2x
2x
2x
0.5
0.5
0.5
0.5
0.5
0.5
0.5
0.5
0.5
0.5
0.5
0.5
0.5
0.5
0.5
0.5
Thickness
of Sheath
Overall
diameter
(approx.)
M aximum DC.
resistance of
Cdr. at 20C
M inimum
insulation
resistance at
20C
Ampacities
Allowable
direct burial in
ampacities in
ground at
free air at
30C
40C
ambient**
Cable
weight
(approx.)
Standard
packing
mm
mm
mm
/ km
M -km
kg / km
m / reel
17.6
18.6
19.8
20.9
21.9
23.6
25.3
27.1
28.3
30.2
32.8
36.0
39.8
43.7
48.0
51.9
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.9
1.9
2.0
2.1
2.1
2.3
2.4
2.5
2.6
23
24
25
26
27
29
30
32
34
36
38
42
46
50
54
59
1.83
1.15
0.727
0.524
0.387
0.268
0.193
0.153
0.124
0.0991
0.0754
0.0601
0.047
0.0366
0.0283
0.0221
1,199
1,041
896
800
720
623
551
490
455
411
379
365
341
324
291
261
91
118
151
181
213
260
311
353
397
449
520
587
670
760
859
1,026
98
127
167
201
240
299
368
421
480
549
642
735
862
960
1,127
1,274
491
575
696
816
960
1,209
1,500
1,799
2,090
2,499
3,127
3,831
4,775
5,911
7,440
9,222
1,000
1,000
1,000
1,000
1,000
1,000
1,000
1,000
1,000
1,000
1,000
500
500
500
500
500
** Depth of laying in Ground = 1 m, Rho = 1.2C m/watt, Spacing of cable = 2 x cable overall diameter
Page 1 of 1
APPLICATION :
Preferably used for urban networks.
Exposed in aerial, direct burial,
conduit, open tray and underground
duct installation.
MAX. CONDUCTOR
TEMPERATURE :
90C (Normal Operation)
AC TESTING VOLTAGE :
21 kV
REFERENCE STANDARD :
IEC 60502-2
CONSTRUCTION :
Conductor : Compact round stranded copper.
Conductor shield : Semi-conducting cross-linked polyethylene.
Insulation : Cross-linked polyethylene.
Insulation shield : Semi-conducting cross-linked polyethylene.
Sheath : Copper tape shield
Bedding : Black polyethylene (Optional : Polyvinyl chloride)
Armour : Double Aluminum tape
Sheath : Black polyethylene (ST7) (Optional : Polyvinyl Chloride)
Nominal
sectional
area
M inimum
Number
of wire
Diameter
of
Conductor
(approx.)
mm
mm
mm
7
7
7
7
18
18
18
18
34
34
34
55
55
81
81
4.7
5.9
6.9
8.0
9.7
11.4
12.9
14.2
16.0
18.4
20.5
23.4
26.6
30.0
33.9
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
12.3
13.5
14.5
15.6
17.3
19.0
20.8
22.0
23.9
26.3
28.6
32.0
35.3
38.9
42.8
mm
16
25
35
50
70
95
120
150
185
240
300
400
500
630
800
Thickness
of
Insulation
Diameter
Thickness
Diameter
over
of
over armour
insulation
Aluminum
(approx.)
(Approx.) tape armour
mm
2x
2x
2x
2x
2x
2x
2x
2x
2x
2x
2x
2x
2x
2x
2x
0.5
0.5
0.5
0.5
0.5
0.5
0.5
0.5
0.5
0.5
0.5
0.5
0.5
0.5
0.5
Ampacities
Allowable
direct burial in
ampacities in
ground at
free air at
30C
40C
ambient**
Thickness
of Sheath
Overall
diameter
(approx.)
M aximum DC.
resistance of
Cdr. at 20C
M inimum
insulation
resistance at
20C
mm
mm
mm
/ km
M -km
kg / km
m / reel
20.4
21.6
22.7
23.7
25.4
27.1
28.9
30.1
32.0
34.9
37.2
40.6
44.1
48.4
52.3
1.8
1.8
1.8
1.8
1.8
1.9
1.9
2.0
2.0
2.1
2.2
2.3
2.4
2.5
2.6
25
27
28
29
30
32
34
36
37
41
43
47
50
55
59
1.15
0.727
0.524
0.387
0.268
0.193
0.153
0.124
0.0991
0.0754
0.0601
0.047
0.0366
0.0283
0.0221
1,295
1,126
1,011
916
799
711
634
591
536
479
434
381
342
307
276
111
143
171
202
247
296
336
377
427
494
558
637
722
816
974
127
167
201
240
299
368
421
480
544
642
730
838
956
1,127
1,274
648
772
895
1,042
1,296
1,603
1,895
2,204
2,605
3,261
3,929
4,834
5,943
7,474
9,258
1,000
1,000
1,000
1,000
1,000
1,000
1,000
1,000
1,000
1,000
500
500
500
500
500
Cable
weight
(approx.)
Standard
packing
** Depth of laying in Ground = 1 m, Rho = 1.2C m/watt, Spacing of cable = 2 x cable overall diameter
Page 1 of 1
APPLICATION :
Preferably used for urban networks.
Exposed in aerial, direct burial,
conduit, open tray and underground
duct installation.
MAX. CONDUCTOR
TEMPERATURE :
90C (Normal Operation)
AC TESTING VOLTAGE :
30.5 kV
REFERENCE STANDARD :
IEC 60502-2
CONSTRUCTION :
Conductor : Compact round stranded copper.
Conductor shield : Semi-conducting cross-linked polyethylene.
Insulation : Cross-linked polyethylene.
Insulation shield : Semi-conducting cross-linked polyethylene.
Sheath : Copper tape shield
Bedding : Black polyethylene (Optional : Polyvinyl chloride)
Armour : Double Aluminum tape
Sheath : Black polyethylene (ST7) (Optional : Polyvinyl Chloride)
Nominal
sectional
area
Diameter
Thickness
Diameter
over
of
over armour
insulation
Aluminum
(approx.)
(Approx.) tape armour
M inimum
Number
of wire
Diameter
of
Conductor
(approx.)
mm
mm
mm
7
7
7
18
18
18
18
34
34
34
55
55
81
81
5.9
6.9
8.0
9.7
11.4
12.9
14.2
16.0
18.4
20.5
23.4
26.6
30.0
33.9
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
15.7
16.7
17.8
19.5
21.2
23.0
24.2
26.1
28.5
30.8
34.2
37.5
41.1
45.0
mm
25
35
50
70
95
120
150
185
240
300
400
500
630
800
Thickness
of
Insulation
mm
2x
2x
2x
2x
2x
2x
2x
2x
2x
2x
2x
2x
2x
2x
0.5
0.5
0.5
0.5
0.5
0.5
0.5
0.5
0.5
0.5
0.5
0.5
0.5
0.5
M aximum DC.
resistance of
Cdr. at 20C
M inimum
insulation
resistance at
20C
Ampacities
Allowable
direct burial in
ampacities in
ground at
free air at
30C
40C
ambient**
Thickness
of Sheath
Overall
diameter
(approx.)
Cable
weight
(approx.)
mm
mm
mm
/ km
M -km
kg / km
m / reel
23.8
24.9
25.9
27.6
29.3
31.1
32.3
34.7
37.1
39.4
43.0
46.3
50.6
54.7
1.8
1.8
1.9
1.9
2.0
2.0
2.1
2.1
2.2
2.3
2.4
2.5
2.6
2.7
29
30
31
33
35
37
38
40
43
45
49
53
57
62
0.727
0.524
0.387
0.268
0.193
0.153
0.124
0.0991
0.0754
0.0601
0.047
0.0366
0.0283
0.0221
1,367
1,237
1,127
990
886
795
743
677
607
552
487
439
395
356
143
171
201
246
295
335
376
426
493
558
634
721
816
974
157
191
230
289
348
421
456
519
608
691
794
911
1,073
1,215
872
998
1,161
1,421
1,736
2,034
2,349
2,790
3,424
4,102
5,040
6,143
7,692
9,517
1,000
1,000
1,000
1,000
1,000
1,000
1,000
1,000
500
500
500
500
500
500
Standard
packing
** Depth of laying in Ground = 1 m, Rho = 1.2C m/watt, Spacing of cable = 2 x cable overall diameter
Page 1 of 1
APPLICATION :
Preferably used for urban networks.
Exposed in aerial, direct burial,
conduit, open tray and underground
duct installation.
MAX. CONDUCTOR
TEMPERATURE :
90C (Normal Operation)
AC TESTING VOLTAGE :
42 kV
REFERENCE STANDARD :
IEC 60502-2
CONSTRUCTION :
Conductor : Compact round stranded copper.
Conductor shield : Semi-conducting cross-linked polyethylene.
Insulation : Cross-linked polyethylene.
Insulation shield : Semi-conducting cross-linked polyethylene.
Sheath : Copper tape shield
Bedding : Black polyethylene (Optional : Polyvinyl chloride)
Armour : Double Aluminum tape
Sheath : Black polyethylene (ST7) (Optional : Polyvinyl Chloride)
Nominal
sectional
area
Diameter
Thickness
Diameter
over
of
over armour
insulation
Aluminum
(approx.)
(Approx.) tape armour
M inimum
Number
of wire
Diameter
of
Conductor
(approx.)
mm
mm
mm
7
7
18
18
18
18
34
34
34
55
55
81
81
6.9
8.0
9.7
11.4
12.9
14.2
16.0
18.4
20.5
23.4
26.6
30.0
33.9
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5
18.7
19.8
21.5
23.2
25.0
26.2
28.1
30.5
32.8
36.2
39.5
43.1
47.0
mm
35
50
70
95
120
150
185
240
300
400
500
630
800
Thickness
of
Insulation
mm
2x
2x
2x
2x
2x
2x
2x
2x
2x
2x
2x
2x
2x
0.5
0.5
0.5
0.5
0.5
0.5
0.5
0.5
0.5
0.5
0.5
0.5
0.5
Thickness
of Sheath
Overall
diameter
(approx.)
M aximum DC.
resistance of
Cdr. at 20C
M inimum
insulation
resistance at
20C
Ampacities
Allowable
direct burial in
ampacities in
ground at
free air at
30C
40C
ambient**
Cable
weight
(approx.)
Standard
packing
mm
mm
mm
/ km
M -km
kg / km
m / reel
26.9
27.9
29.9
31.3
33.1
34.8
36.7
39.1
41.6
45.0
49.0
52.6
56.7
1.9
1.9
2.0
2.0
2.1
2.1
2.2
2.3
2.3
2.4
2.5
2.6
2.8
32
33
35
37
39
40
43
45
48
51
55
59
64
0.524
0.387
0.268
0.193
0.153
0.124
0.0991
0.0754
0.0601
0.047
0.0366
0.0283
0.0221
1,417
1,297
1,146
1,031
929
870
795
716
652
578
522
471
426
171
202
247
296
336
377
427
495
559
636
723
818
973
206
245
304
368
421
475
544
637
725
838
965
1,073
1,215
1,111
1,265
1,544
1,850
2,170
2,507
2,939
3,582
4,269
5,199
6,386
7,875
9,740
1,000
1,000
1,000
1,000
1,000
1,000
500
500
500
500
500
500
500
** Depth of laying in Ground = 1 m, Rho = 1.2C m/watt, Spacing of cable = 2 x cable overall diameter
Page 1 of 1
APPLICATION :
Preferably used for urban networks.
Exposed in aerial, direct burial,
conduit, open tray and underground
duct installation.
MAX. CONDUCTOR
TEMPERATURE :
90C (Normal Operation)
AC TESTING VOLTAGE :
63 kV
REFERENCE STANDARD :
IEC 60502-2
CONSTRUCTION :
Conductor : Compact round stranded copper.
Conductor shield : Semi-conducting cross-linked polyethylene.
Insulation : Cross-linked polyethylene.
Insulation shield : Semi-conducting cross-linked polyethylene.
Sheath : Copper tape shield
Bedding : Black polyethylene (Optional : Polyvinyl chloride)
Armour : Double Aluminum tape
Sheath : Black polyethylene (ST7) (Optional : Polyvinyl Chloride)
Nominal
sectional
area
M inimum
Number
of wire
Diameter
of
Conductor
(approx.)
mm
mm
mm
7
18
18
18
18
34
34
34
55
55
81
81
8.0
9.7
11.4
12.9
14.2
16.0
18.4
20.5
23.4
26.6
30.0
33.9
8.0
8.0
8.0
8.0
8.0
8.0
8.0
8.0
8.0
8.0
8.0
8.0
24.8
26.5
28.2
30.0
31.2
33.1
35.5
37.8
41.2
44.5
48.1
52.0
mm
50
70
95
120
150
185
240
300
400
500
630
800
Thickness
of
Insulation
Diameter
Thickness
Diameter
over
of
over armour
insulation
Aluminum
(approx.)
(Approx.) tape armour
mm
2x
2x
2x
2x
2x
2x
2x
2x
2x
2x
2x
2x
0.5
0.5
0.5
0.5
0.5
0.5
0.5
0.5
0.5
0.5
0.5
0.5
Thickness
of Sheath
Overall
diameter
(approx.)
M aximum DC.
resistance of
Cdr. at 20C
M inimum
insulation
resistance at
20C
Ampacities
Allowable
direct burial in
ampacities in
ground at
free air at
30C
40C
ambient**
Cable
weight
(approx.)
Standard
packing
mm
mm
mm
/ km
M -km
kg / km
m / reel
32.9
35.1
36.7
38.6
40.0
41.9
44.3
46.8
50.7
54.2
57.8
61.9
2.1
2.1
2.2
2.3
2.3
2.4
2.4
2.5
2.6
2.7
2.8
3.0
39
41
43
45
46
48
51
53
57
61
65
69
0.387
0.268
0.193
0.153
0.124
0.0991
0.0754
0.0601
0.047
0.0366
0.0283
0.0221
1,657
1,480
1,343
1,220
1,148
1,057
958
878
784
712
646
587
201
246
295
335
375
425
493
557
634
720
817
972
230
289
348
402
451
515
608
696
799
921
1,073
1,210
1,581
1,895
2,233
2,571
2,905
3,354
4,000
4,730
5,745
6,917
8,439
10,346
1,000
500
500
500
500
500
500
500
500
500
250
250
** Depth of laying in Ground = 1 m, Rho = 1.2C m/watt, Spacing of cable = 2 x cable overall diameter
Page 1 of 1
APPLICATION :
Preferably used for urban networks.
Exposed in aerial, direct burial,
conduit, open tray and underground
duct installation.
MAX. CONDUCTOR
TEMPERATURE :
90C (Normal Operation)
AC TESTING VOLTAGE :
12.5 kV
REFERENCE STANDARD :
IEC 60502-2
CONSTRUCTION :
Conductor : Compact round stranded copper.
Conductor shield : Semi-conducting cross-linked polyethylene.
Insulation : Cross-linked polyethylene.
Insulation shield : Semi-conducting cross-linked polyethylene.
Sheath : Copper tape shield
Bedding : Black polyethylene (Optional : Polyvinyl chloride)
Armour : Double Aluminum tape
Binding tape : Polyester and/or Spunbond tape (Optional : Water blocking tape
Sheath : Black polyethylene (ST7) (Optional : Polyvinyl Chloride)
Nominal
sectional
area
Diameter
over
insulation
(Approx.)
Armour
aluminum
wire
diameter
M inimum
insulation
resistance at
20C
Ampacities
Allowable
direct burial in
ampacities in
ground at
free air at
30C
40C
ambient**
M inimum
Number
of wire
Diameter
of
Conductor
(approx.)
mm
mm
mm
mm
mm
mm
mm
/ km
M -km
kg / km
m / reel
7
7
7
7
7
18
18
18
18
34
34
34
55
55
81
81
3.7
4.7
5.9
6.9
8.0
9.7
11.4
12.9
14.2
16.0
18.4
20.5
23.4
26.6
30.0
33.9
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.6
2.8
3.0
3.2
3.2
3.2
9.5
10.5
11.7
12.7
13.8
15.5
17.2
19.0
20.2
22.1
24.7
27.4
31.2
34.9
38.5
42.4
1.25
1.25
1.6
1.6
1.6
1.6
1.6
1.6
1.6
2
2
2
2
2.5
2.5
2.5
18.1
19.1
21.0
22.1
23.1
24.8
26.5
28.3
29.5
32.2
34.8
38.0
41.8
46.7
51.0
54.9
1.6
1.6
1.7
1.7
1.8
1.8
1.9
1.9
2.0
2.0
2.1
2.2
2.3
2.5
2.6
2.7
24
25
27
28
29
31
33
35
36
39
42
45
49
55
59
63
1.83
1.15
0.727
0.524
0.387
0.268
0.193
0.153
0.124
0.0991
0.0754
0.0601
0.047
0.0366
0.0283
0.0221
1,199
1,041
896
800
720
623
551
490
455
411
379
365
341
324
291
261
91
118
151
181
213
260
311
353
397
449
520
587
670
760
859
1,026
98
127
167
201
240
299
368
421
480
549
642
735
862
960
1,127
1,274
537
621
801
925
1,085
1,342
1,653
1,947
2,262
2,752
3,392
4,141
5,099
6,456
8,034
9,853
1,000
1,000
1,000
1,000
1,000
1,000
1,000
1,000
1,000
1,000
500
500
500
500
500
500
mm
10
16
25
35
50
70
95
120
150
185
240
300
400
500
630
800
Thickness
of
Insulation
Diameter
over armour
(approx.)
Thickness
of Sheath
Overall
diameter
(approx.)
M aximum DC.
resistance of
Cdr. at 20C
Cable
weight
(approx.)
Standard
packing
** Depth of laying in Ground = 1 m, Rho = 1.2C m/watt, Spacing of cable = 2 x cable overall diameter
Page 1 of 1
APPLICATION :
Preferably used for urban networks.
Exposed in aerial, direct burial,
conduit, open tray and underground
duct installation.
MAX. CONDUCTOR
TEMPERATURE :
90C (Normal Operation)
AC TESTING VOLTAGE :
21 kV
REFERENCE STANDARD :
IEC 60502-2
CONSTRUCTION :
Conductor : Compact round stranded copper.
Conductor shield : Semi-conducting cross-linked polyethylene.
Insulation : Cross-linked polyethylene.
Insulation shield : Semi-conducting cross-linked polyethylene.
Sheath : Copper tape shield
Bedding : Black polyethylene (Optional : Polyvinyl chloride)
Armour : Double Aluminum tape
Binding tape : Polyester and/or Spunbond tape (Optional : Water blocking tape
Sheath : Black polyethylene (ST7) (Optional : Polyvinyl Chloride)
Nominal
sectional
area
M inimum
Number
of wire
mm
mm
mm
mm
mm
mm
mm
/ km
M -km
kg / km
m / reel
7
7
7
7
18
18
18
18
34
34
34
55
55
81
81
4.7
5.9
6.9
8.0
9.7
11.4
12.9
14.2
16.0
18.4
20.5
23.4
26.6
30.0
33.9
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
12.3
13.5
14.5
15.6
17.3
19.0
20.8
22.0
23.9
26.3
28.6
32.0
35.3
38.9
42.8
1.6
1.6
1.6
1.6
1.6
1.6
1.6
2
2
2
2
2
2.5
2.5
2.5
21.6
22.8
23.9
24.9
26.6
28.3
30.1
32.1
34.0
36.9
39.2
42.6
47.1
51.4
55.3
1.7
1.7
1.8
1.8
1.9
1.9
2.0
2.1
2.1
2.2
2.2
2.4
2.5
2.6
2.8
28
29
30
31
33
35
37
39
41
44
46
50
55
60
64
1.15
0.727
0.524
0.387
0.268
0.193
0.153
0.124
0.0991
0.0754
0.0601
0.047
0.0366
0.0283
0.0221
1,295
1,126
1,011
916
799
711
634
591
536
479
434
381
342
307
276
111
143
171
202
247
296
336
377
427
494
558
637
722
816
974
127
167
201
240
299
368
421
480
544
642
730
838
956
1,127
1,274
761
889
1,028
1,174
1,448
1,751
2,070
2,473
2,881
3,559
4,232
5,183
6,486
8,067
9,929
1,000
1,000
1,000
1,000
1,000
1,000
1,000
1,000
500
500
500
500
500
500
500
mm
16
25
35
50
70
95
120
150
185
240
300
400
500
630
800
Thickness
of
Insulation
Diameter
over
insulation
(Approx.)
Armour
aluminum
wire
diameter
Diameter
over armour
(approx.)
Thickness
of Sheath
Overall
diameter
(approx.)
M aximum DC.
resistance of
Cdr. at 20C
M inimum
insulation
resistance at
20C
Ampacities
Allowable
direct burial in
ampacities in
ground at
free air at
30C
40C
ambient**
Diameter
of
Conductor
(approx.)
Cable
weight
(approx.)
Standard
packing
** Depth of laying in Ground = 1 m, Rho = 1.2C m/watt, Spacing of cable = 2 x cable overall diameter
Page 1 of 1
APPLICATION :
Preferably used for urban networks.
Exposed in aerial, direct burial,
conduit, open tray and underground
duct installation.
MAX. CONDUCTOR
TEMPERATURE :
90C (Normal Operation)
AC TESTING VOLTAGE :
30.5 kV
REFERENCE STANDARD :
IEC 60502-2
CONSTRUCTION :
Conductor : Compact round stranded copper.
Conductor shield : Semi-conducting cross-linked polyethylene.
Insulation : Cross-linked polyethylene.
Insulation shield : Semi-conducting cross-linked polyethylene.
Sheath : Copper tape shield
Bedding : Black polyethylene (Optional : Polyvinyl chloride)
Armour : Double Aluminum tape
Binding tape : Polyester and/or Spunbond tape (Optional : Water blocking tape
Sheath : Black polyethylene (ST7) (Optional : Polyvinyl Chloride)
Nominal
sectional
area
Diameter
over
insulation
(Approx.)
Armour
aluminum
wire
diameter
M inimum
Number
of wire
Diameter
of
Conductor
(approx.)
mm
mm
mm
mm
7
7
7
18
18
18
18
34
34
34
55
55
81
81
5.9
6.9
8.0
9.7
11.4
12.9
14.2
16.0
18.4
20.5
23.4
26.6
30.0
33.9
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
15.7
16.7
17.8
19.5
21.2
23.0
24.2
26.1
28.5
30.8
34.2
37.5
41.1
45.0
1.6
1.6
1.6
1.6
2
2
2
2
2
2
2.5
2.5
2.5
2.5
mm
25
35
50
70
95
120
150
185
240
300
400
500
630
800
Thickness
of
Insulation
Diameter
over armour
(approx.)
M aximum DC.
resistance of
Cdr. at 20C
M inimum
insulation
resistance at
20C
Ampacities
Allowable
direct burial in
ampacities in
ground at
free air at
30C
40C
ambient**
Thickness
of Sheath
Overall
diameter
(approx.)
Cable
weight
(approx.)
mm
mm
mm
/ km
M -km
kg / km
m / reel
25.0
26.1
27.1
28.8
31.3
33.1
34.3
36.7
39.1
41.4
46.0
49.3
53.6
57.7
1.8
1.9
1.9
1.9
2.0
2.1
2.1
2.2
2.3
2.3
2.5
2.6
2.7
2.8
31
33
34
35
38
40
41
44
46
49
54
57
62
66
0.727
0.524
0.387
0.268
0.193
0.153
0.124
0.0991
0.0754
0.0601
0.047
0.0366
0.0283
0.0221
1,367
1,237
1,127
990
886
795
743
677
607
552
487
439
395
356
143
171
201
246
295
335
376
426
493
558
634
721
816
974
157
191
230
289
348
421
456
519
608
691
794
911
1,073
1,215
1,010
1,148
1,304
1,571
1,976
2,307
2,617
3,089
3,747
4,420
5,575
6,718
8,317
10,192
1,000
1,000
1,000
1,000
1,000
1,000
500
500
500
500
500
500
500
250
Standard
packing
** Depth of laying in Ground = 1 m, Rho = 1.2C m/watt, Spacing of cable = 2 x cable overall diameter
Page 1 of 1
APPLICATION :
Preferably used for urban networks.
Exposed in aerial, direct burial,
conduit, open tray and underground
duct installation.
MAX. CONDUCTOR
TEMPERATURE :
90C (Normal Operation)
AC TESTING VOLTAGE :
42 kV
REFERENCE STANDARD :
IEC 60502-2
CONSTRUCTION :
Conductor : Compact round stranded copper.
Conductor shield : Semi-conducting cross-linked polyethylene.
Insulation : Cross-linked polyethylene.
Insulation shield : Semi-conducting cross-linked polyethylene.
Sheath : Copper tape shield
Bedding : Black polyethylene (Optional : Polyvinyl chloride)
Armour : Double Aluminum tape
Binding tape : Polyester and/or Spunbond tape (Optional : Water blocking tape
Sheath : Black polyethylene (ST7) (Optional : Polyvinyl Chloride)
Nominal
sectional
area
Diameter
over
insulation
(Approx.)
Armour
aluminum
wire
diameter
M aximum DC.
resistance of
Cdr. at 20C
M inimum
insulation
resistance at
20C
Ampacities
Allowable
direct burial in
ampacities in
ground at
free air at
30C
40C
ambient**
M inimum
Number
of wire
Diameter
of
Conductor
(approx.)
mm
mm
mm
mm
mm
mm
mm
/ km
M -km
kg / km
m / reel
7
7
18
18
18
18
34
34
34
55
55
81
81
6.9
8.0
9.7
11.4
12.9
14.2
16.0
18.4
20.5
23.4
26.6
30.0
33.9
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5
18.7
19.8
21.5
23.2
25.0
26.2
28.1
30.5
32.8
36.2
39.5
43.1
47.0
1.6
1.6
2
2
2
2
2
2
2.5
2.5
2.5
2.5
2.5
28.1
29.1
31.6
33.3
35.1
36.8
38.7
41.1
44.6
48.0
52.0
55.6
59.7
1.9
2.0
2.0
2.1
2.1
2.2
2.2
2.3
2.5
2.6
2.7
2.8
2.9
35
36
38
40
42
44
46
48
53
56
60
64
68
0.524
0.387
0.268
0.193
0.153
0.124
0.0991
0.0754
0.0601
0.047
0.0366
0.0283
0.0221
1,417
1,297
1,146
1,031
929
870
795
716
652
578
522
471
426
171
202
247
296
336
377
427
495
559
636
723
818
973
206
245
304
368
421
475
544
637
725
838
965
1,073
1,215
1,260
1,433
1,791
2,122
2,442
2,806
3,236
3,893
4,816
5,788
7,014
8,544
10,434
1,000
1,000
1,000
1,000
500
500
500
500
500
500
500
500
250
mm
35
50
70
95
120
150
185
240
300
400
500
630
800
Thickness
of
Insulation
Diameter
over armour
(approx.)
Thickness
of Sheath
Overall
diameter
(approx.)
Cable
weight
(approx.)
Standard
packing
** Depth of laying in Ground = 1 m, Rho = 1.2C m/watt, Spacing of cable = 2 x cable overall diameter
Page 1 of 1
APPLICATION :
Preferably used for urban networks.
Exposed in aerial, direct burial,
conduit, open tray and underground
duct installation.
MAX. CONDUCTOR
TEMPERATURE :
90C (Normal Operation)
AC TESTING VOLTAGE :
63 kV
REFERENCE STANDARD :
IEC 60502-2
CONSTRUCTION :
Conductor : Compact round stranded copper.
Conductor shield : Semi-conducting cross-linked polyethylene.
Insulation : Cross-linked polyethylene.
Insulation shield : Semi-conducting cross-linked polyethylene.
Sheath : Copper tape shield
Bedding : Black polyethylene (Optional : Polyvinyl chloride)
Armour : Double Aluminum tape
Binding tape : Polyester and/or Spunbond tape (Optional : Water blocking tape
Sheath : Black polyethylene (ST7) (Optional : Polyvinyl Chloride)
Nominal
sectional
area
M inimum
Number
of wire
mm
mm
mm
mm
mm
mm
mm
/ km
M -km
7
18
18
18
18
34
34
34
55
55
81
81
8.0
9.7
11.4
12.9
14.2
16.0
18.4
20.5
23.4
26.6
30.0
33.9
8.0
8.0
8.0
8.0
8.0
8.0
8.0
8.0
8.0
8.0
8.0
8.0
24.8
26.5
28.2
30.0
31.2
33.1
35.5
37.8
41.2
44.5
48.1
52.0
2
2
2
2
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
34.9
37.1
38.7
40.6
43.0
44.9
47.3
49.8
53.7
57.2
60.8
64.9
2.2
2.2
2.3
2.3
2.4
2.5
2.6
2.6
2.8
2.9
3.0
3.1
42
44
46
48
51
53
55
58
62
66
70
74
0.387
0.268
0.193
0.153
0.124
0.0991
0.0754
0.0601
0.047
0.0366
0.0283
0.0221
1,657
1,480
1,343
1,220
1,148
1,057
958
878
784
712
646
587
201
246
295
335
375
425
493
557
634
720
817
972
mm
50
70
95
120
150
185
240
300
400
500
630
800
Thickness
of
Insulation
Diameter
over
insulation
(Approx.)
Armour
aluminum
wire
diameter
Diameter
over armour
(approx.)
Thickness
of Sheath
Overall
diameter
(approx.)
M aximum DC.
resistance of
Cdr. at 20C
M inimum
insulation
resistance at
20C
Ampacities
Allowable
direct burial in
ampacities in
ground at
free air at
30C
40C
ambient**
Diameter
of
Conductor
(approx.)
Cable
weight
(approx.)
Standard
packing
kg / km
m / reel
230
289
348
402
451
515
608
696
799
921
1,073
1,210
1,872
2,200
2,548
2,885
3,411
3,881
4,578
5,316
6,395
7,608
9,171
11,100
500
500
500
500
500
500
500
500
500
250
250
250
** Depth of laying in Ground = 1 m, Rho = 1.2C m/watt, Spacing of cable = 2 x cable overall diameter
Page 1 of 1
APPLICATION :
Preferably used for urban networks.
Exposed in aerial, direct burial,
conduit, open tray and underground
duct installation
MAX. CONDUCTOR
TEMPERATURE :
90C (Normal Operation)
AC TESTING VOLTAGE :
12.5 kV
REFERENCE STANDARD :
IEC 60502-2
CONSTRUCTION :
Conductor : Compact round stranded copper.
Conductor shield : Semi-conducting cross-linked polyethylene.
Insulation : Cross-linked polyethylene.
Insulation shield : Semi-conducting cross-linked polyethylene.
Sheath : Copper tape shield
Filler : Polypropylene (Nonhygroscopic material)
Binding tape : Polyester and/or Spunbond tape (Optional : Water blocking tape)
Sheath : Black polyethylene (ST7) (Optional : Polyvinyl Chloride)
Nominal
sectional
area
Minimum
Number of
wire
mm
Diameter of
Conductor
(approx.)
Thickness of
Insulation
Diameter
over
insulation
(Approx.)
Thickness of
Sheath
Overall
diameter
(approx.)
mm
mm
mm
mm
mm
Maximum
Minimum
DC.
insulation
resistance of resistance at
Cdr. at 20C
20C
/ km
M-km
Ampacities
direct burial
in ground at
30C
ambient**
Allowable
ampacities in
free air at
40C
Cable
weight
(approx.)
Standard
packing
kg / km
m / reel
10
3.7
2.5
9.5
1.9
33
1.83
1,199
85
82
919
1,000
16
4.7
2.5
10.5
2.0
35
1.15
1,041
107
107
1,162
1,000
25
5.9
2.5
11.7
2.1
38
0.727
896
138
143
1,516
1,000
35
6.9
2.5
12.7
2.1
40
0.524
800
168
173
1,858
1,000
50
8.0
2.5
13.8
2.2
43
0.387
720
194
204
2,290
500
70
18
9.7
2.5
15.5
2.3
47
0.268
623
235
250
3,037
500
95
18
11.4
2.5
17.2
2.5
51
0.193
551
281
306
3,936
500
120
18
12.9
2.5
19.0
2.6
55
0.153
490
316
347
4,809
500
150
18
14.2
2.5
20.2
2.7
58
0.124
455
352
393
5,704
500
185
34
16.0
2.5
22.1
2.8
62
0.0991
411
398
449
6,915
500
240
34
18.4
2.6
24.7
3.0
68
0.0754
379
449
520
8,817
250
300
34
20.5
2.8
27.4
3.2
75
0.0601
365
495
581
11,016
250
400
55
23.4
3.0
31.2
3.4
84
0.047
341
546
658
13,857
250
APPLICATION :
Preferably used for urban networks.
Exposed in aerial, direct burial,
conduit, open tray and underground
duct installation
MAX. CONDUCTOR
TEMPERATURE :
90C (Normal Operation)
AC TESTING VOLTAGE :
21 kV
REFERENCE STANDARD :
IEC 60502-2
CONSTRUCTION :
Conductor : Compact round stranded copper.
Conductor shield : Semi-conducting cross-linked polyethylene.
Insulation : Cross-linked polyethylene.
Insulation shield : Semi-conducting cross-linked polyethylene.
Sheath : Copper tape shield
Filler : Polypropylene (Nonhygroscopic material)
Binding tape : Polyester and/or Spunbond tape (Optional : Water blocking tape)
Sheath : Black polyethylene (ST7) (Optional : Polyvinyl Chloride)
Nominal
sectional
area
Minimum
Number of
wire
mm
Diameter of
Conductor
(approx.)
Thickness of
Insulation
Diameter
over
insulation
(Approx.)
Thickness of
Sheath
Overall
diameter
(approx.)
mm
mm
mm
mm
mm
Maximum
Minimum
DC.
insulation
resistance of resistance at
Cdr. at 20C
20C
/ km
M-km
Ampacities
direct burial
in ground at
30C
ambient**
Allowable
ampacities in
free air at
40C
Cable
weight
(approx.)
Standard
packing
kg / km
m / reel
16
4.7
3.4
12.3
2.1
39
1.15
1,295
107
107
1,360
1,000
25
5.9
3.4
13.5
2.2
42
0.727
1,126
138
143
1,728
500
35
6.9
3.4
14.5
2.3
45
0.524
1,011
168
173
2,100
500
50
8.0
3.4
15.6
2.4
47
0.387
916
199
209
2,547
500
70
18
9.7
3.4
17.3
2.5
51
0.268
799
240
255
3,316
500
95
18
11.4
3.4
19.0
2.6
55
0.193
711
281
306
4,215
500
120
18
12.9
3.4
20.8
2.7
59
0.153
634
316
352
5,110
500
150
18
14.2
3.4
22.0
2.8
62
0.124
591
352
398
6,022
500
185
34
16.0
3.4
23.9
2.9
66
0.0991
536
398
449
7,254
250
240
34
18.4
3.4
26.3
3.1
72
0.0754
479
449
520
9,254
250
300
34
20.5
3.4
28.6
3.3
78
0.0601
434
495
587
11,298
250
400
55
23.4
3.4
32.0
3.5
86
0.047
381
546
658
14,078
250
Page 1 of 1
APPLICATION :
Preferably used for urban networks.
Exposed in aerial, direct burial,
conduit, open tray and underground
duct installation
MAX. CONDUCTOR
TEMPERATURE :
90C (Normal Operation)
AC TESTING VOLTAGE :
30.5 kV
REFERENCE STANDARD :
IEC 60502-2
CONSTRUCTION :
Conductor : Compact round stranded copper.
Conductor shield : Semi-conducting cross-linked polyethylene.
Insulation : Cross-linked polyethylene.
Insulation shield : Semi-conducting cross-linked polyethylene.
Sheath : Copper tape shield
Filler : Polypropylene (Nonhygroscopic material)
Binding tape : Polyester and/or Spunbond tape (Optional : Water blocking tape)
Sheath : Black polyethylene (ST7) (Optional : Polyvinyl Chloride)
Nominal
sectional
area
Minimum
Number
of wire
mm
Diameter of
Thickness
Conductor
of Insulation
(approx.)
Diameter
over
insulation
(Approx.)
Thickness
of Sheath
Overall
diameter
(approx.)
Maximum
DC.
resistance
of Cdr. at
20C
Minimum
insulation
resistance
at 20C
Ampacities
Allowable
direct burial
ampacities
in ground at
in free air at
30C
40C
ambient**
Cable
weight
(approx.)
Standard
packing
mm
mm
mm
mm
mm
/ km
M-km
kg / km
m / reel
25
5.9
4.5
15.7
2.4
47
0.727
1,367
138
148
2,032
500
35
6.9
4.5
16.7
2.5
50
0.524
1,237
163
173
2,421
500
50
8.0
4.5
17.8
2.6
52
0.387
1,127
194
209
2,886
500
70
18
9.7
4.5
19.5
2.7
56
0.268
990
235
255
3,681
500
95
18
11.4
4.5
21.2
2.8
60
0.193
886
281
311
4,607
500
120
18
12.9
4.5
23.0
2.9
64
0.153
795
316
352
5,528
500
150
18
14.2
4.5
24.2
3.0
67
0.124
743
352
398
6,460
250
185
34
16.0
4.5
26.1
3.1
72
0.0991
677
393
449
7,826
250
240
34
18.4
4.5
28.5
3.3
78
0.0754
607
444
520
9,767
250
300
34
20.5
4.5
30.8
3.4
83
0.0601
552
490
587
11,814
250
400
55
23.4
4.5
34.2
3.7
91
0.047
487
541
658
14,681
250
Page 1 of 1
APPLICATION :
Preferably used for urban networks.
Exposed in aerial, direct burial,
conduit, open tray and underground
duct installation
MAX. CONDUCTOR
TEMPERATURE :
90C (Normal Operation)
AC TESTING VOLTAGE :
42 kV
REFERENCE STANDARD :
IEC 60502-2
CONSTRUCTION :
Conductor : Compact round stranded copper.
Conductor shield : Semi-conducting cross-linked polyethylene.
Insulation : Cross-linked polyethylene.
Insulation shield : Semi-conducting cross-linked polyethylene.
Sheath : Copper tape shield
Filler : Polypropylene (Nonhygroscopic material)
Binding tape : Polyester and/or Spunbond tape (Optional : Water blocking tape)
Sheath : Black polyethylene (ST7) (Optional : Polyvinyl Chloride)
Nominal
sectional
area
Minimum
Number
of wire
mm
Diameter of
Thickness
Conductor
of Insulation
(approx.)
Diameter
over
insulation
(Approx.)
Thickness
of Sheath
Overall
diameter
(approx.)
Maximum
DC.
resistance
of Cdr. at
20C
Minimum
insulation
resistance
at 20C
Ampacities
Allowable
direct burial
ampacities
in ground at
in free air at
30C
40C
ambient**
Cable
weight
(approx.)
Standard
packing
mm
mm
mm
mm
mm
/ km
M-km
kg / km
m / reel
35
6.9
5.5
18.7
2.6
54
0.524
1,417
163
179
2,726
500
50
8.0
5.5
19.8
2.7
57
0.387
1,297
194
209
3,206
500
70
18
9.7
5.5
21.5
2.8
61
0.268
1,146
235
260
4,023
500
95
18
11.4
5.5
23.2
2.9
64
0.193
1,031
281
311
4,971
500
120
18
12.9
5.5
25.0
3.0
68
0.153
929
316
357
5,916
250
150
18
14.2
5.5
26.2
3.1
72
0.124
870
352
398
6,970
250
185
34
16.0
5.5
28.1
3.3
77
0.0991
795
393
454
8,294
250
240
34
18.4
5.5
30.5
3.4
82
0.0754
716
444
520
10,236
250
300
34
20.5
5.5
32.8
3.6
88
0.0601
652
490
587
12,351
250
400
55
23.4
5.5
36.2
3.8
95
0.047
578
541
658
15,228
250
Page 1 of 1
APPLICATION :
Preferably used for urban networks.
Exposed in aerial, direct burial,
conduit, open tray and underground
duct installation
MAX. CONDUCTOR
TEMPERATURE :
90C (Normal Operation)
AC TESTING VOLTAGE :
63 kV
REFERENCE STANDARD :
IEC 60502-2
CONSTRUCTION :
Conductor : Compact round stranded copper.
Conductor shield : Semi-conducting cross-linked polyethylene.
Insulation : Cross-linked polyethylene.
Insulation shield : Semi-conducting cross-linked polyethylene.
Sheath : Copper tape shield
Filler : Polypropylene (Nonhygroscopic material)
Binding tape : Polyester and/or Spunbond tape (Optional : Water blocking tape)
Sheath : Black polyethylene (ST7) (Optional : Polyvinyl Chloride)
Nominal
sectional
area
Minimum
Number
of wire
mm
Diameter of
Thickness
Conductor
of Insulation
(approx.)
mm
mm
Diameter
over
insulation
(Approx.)
mm
Thickness
of Sheath
Overall
diameter
(approx.)
Maximum
DC.
resistance
of Cdr. at
20C
Minimum
insulation
resistance
at 20C
mm
mm
/ km
M-km
Ampacities
Allowable
direct burial
ampacities
in ground at
in free air at
30C
40C
ambient**
A
Cable
weight
(approx.)
Standard
packing
kg / km
m / reel
50
8.0
8.0
24.8
3.1
68
0.387
1,657
194
214
4,161
250
70
18
9.7
8.0
26.5
3.2
73
0.268
1,480
235
260
5,144
250
95
18
11.4
8.0
28.2
3.3
77
0.193
1,343
275
311
6,155
250
120
18
12.9
8.0
30.0
3.4
81
0.153
1,220
311
357
7,169
250
150
18
14.2
8.0
31.2
3.5
84
0.124
1,148
347
398
8,166
250
185
34
16.0
8.0
33.1
3.6
88
0.0991
1,057
388
454
9,522
250
240
34
18.4
8.0
35.5
3.8
94
0.0754
958
444
520
11,583
250
300
34
20.5
8.0
37.8
4.0
99
0.0601
878
490
587
13,783
250
400
55
23.4
8.0
41.2
4.2
108
0.047
784
541
658
16,950
250
Page 1 of 1
APPLICATION :
Preferably used for urban networks.
Exposed in aerial, direct burial,
conduit, open tray and underground
duct installation.
MAX. CONDUCTOR
TEMPERATURE :
90C (Normal Operation)
AC TESTING VOLTAGE :
12.5 kV
REFERENCE STANDARD :
IEC 60502-2
CONSTRUCTION :
Conductor : Compact round stranded copper.
Conductor shield : Semi-conducting cross-linked polyethylene.
Insulation : Cross-linked polyethylene.
Insulation shield : Semi-conducting cross-linked polyethylene.
Sheath : Copper tape shield
Filler : Polypropylene (Nonhygroscopic material)
Binding tape : Polyester and/or Spunbond tape
Bedding : Black polyethylene (Optional : Polyvinyl chloride)
Armour : Double steel tape
Sheath : Black polyethylene (ST7) (Optional : Polyvinyl Chloride)
Nominal
sectional
area
M inimum
Number
of wire
mm
10
16
25
35
50
70
95
120
150
185
240
300
400
7
7
7
7
7
18
18
18
18
34
34
34
55
Diameter
Thickness
Diameter
over
of Steel
over armour
insulation
tape armour
(approx.)
(Approx.)
Diameter
of
Conductor
(approx.)
Thickness
of
Insulation
mm
mm
mm
mm
3.7
4.7
5.9
6.9
8.0
9.7
11.4
12.9
14.2
16.0
18.4
20.5
23.4
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.6
2.8
3.0
9.5
10.5
11.7
12.7
13.8
15.5
17.2
19.0
20.2
22.1
24.7
27.4
31.2
2x0.2
2x0.2
2x0.5
2x0.5
2x0.5
2x0.5
2x0.5
2x0.5
2x0.5
2x0.5
2x0.5
2x0.5
2x0.8
Ampacities
Allowable
direct burial in
ampacities in
ground at
free air at
30C
40C
ambient**
Thickness
of Sheath
Overall
diameter
(approx.)
M aximum DC.
resistance of
Cdr. at 20C
M inimum
insulation
resistance at
20C
mm
mm
mm
/ km
M -km
29.7
31.7
35.5
37.8
40.3
44.2
47.7
51.8
54.5
58.7
64.5
71.7
81.5
2.0
2.1
2.2
2.3
2.4
2.5
2.6
2.7
2.8
2.9
3.1
3.3
3.6
35
37
41
44
47
51
54
59
62
66
72
80
90
1.83
1.15
0.727
0.524
0.387
0.268
0.193
0.153
0.124
0.0991
0.0754
0.0601
0.047
1,199
1,041
896
800
720
623
551
490
455
411
379
365
341
83
105
135
165
190
230
275
310
345
390
440
485
535
Cable
weight
(approx.)
Standard
packing
kg / km
m / reel
80
105
140
170
200
245
300
340
385
440
510
570
645
1,270
1,542
2,285
2,697
3,208
4,067
5,034
6,030
6,992
8,333
10,412
12,828
16,849
1,000
1,000
500
500
500
500
500
500
500
250
250
250
250
APPLICATION :
Preferably used for urban networks.
Exposed in aerial, direct burial,
conduit, open tray and underground
duct installation.
MAX. CONDUCTOR
TEMPERATURE :
90C (Normal Operation)
AC TESTING VOLTAGE :
21 kV
REFERENCE STANDARD :
IEC 60502-2
CONSTRUCTION :
Conductor : Compact round stranded copper.
Conductor shield : Semi-conducting cross-linked polyethylene.
Insulation : Cross-linked polyethylene.
Insulation shield : Semi-conducting cross-linked polyethylene.
Sheath : Copper tape shield
Filler : Polypropylene (Nonhygroscopic material)
Binding tape : Polyester and/or Spunbond tape
Bedding : Black polyethylene (Optional : Polyvinyl chloride)
Armour : Double steel tape
Sheath : Black polyethylene (ST7) (Optional : Polyvinyl Chloride)
Nominal
sectional
area
M inimum
Number
of wire
mm
16
25
35
50
70
95
120
150
185
240
300
400
7
7
7
7
18
18
18
18
34
34
34
55
Diameter
of
Conductor
(approx.)
Thickness
of
Insulation
Diameter
Thickness
Diameter
over
of Steel
over armour
insulation
tape armour
(approx.)
(Approx.)
mm
mm
mm
mm
4.7
5.9
6.9
8.0
9.7
11.4
12.9
14.2
16.0
18.4
20.5
23.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
12.3
13.5
14.5
15.6
17.3
19.0
20.8
22.0
23.9
26.3
28.6
32.0
2x0.5
2x0.5
2x0.5
2x0.5
2x0.5
2x0.5
2x0.5
2x0.5
2x0.5
2x0.5
2x0.5
2x0.8
Ampacities
Allowable
direct burial in
ampacities in
ground at
free air at
30C
40C
ambient**
Thickness
of Sheath
Overall
diameter
(approx.)
M aximum DC.
resistance of
Cdr. at 20C
M inimum
insulation
resistance at
20C
mm
mm
mm
/ km
M -km
36.8
39.6
41.9
44.4
48.1
51.8
55.9
58.6
62.8
69.2
74.4
83.2
2.2
2.3
2.4
2.5
2.6
2.7
2.9
3.0
3.1
3.3
3.4
3.7
43
46
48
51
55
59
63
66
70
77
83
92
1.15
0.727
0.524
0.387
0.268
0.193
0.153
0.124
0.0991
0.0754
0.0601
0.047
1,295
1,126
1,011
916
799
711
634
591
536
479
434
381
105
135
165
195
235
275
310
345
390
440
485
535
Cable
weight
(approx.)
Standard
packing
kg / km
m / reel
105
140
170
205
250
300
345
390
440
510
575
645
2,159
2,609
3,037
3,563
4,422
5,435
6,483
7,465
8,833
11,031
13,217
17,138
500
500
500
500
500
500
500
250
250
250
250
250
Page 1 of 1
APPLICATION :
Preferably used for urban networks.
Exposed in aerial, direct burial,
conduit, open tray and underground
duct installation.
MAX. CONDUCTOR
TEMPERATURE :
90C (Normal Operation)
AC TESTING VOLTAGE :
30.5 kV
REFERENCE STANDARD :
IEC 60502-2
CONSTRUCTION :
Conductor : Compact round stranded copper.
Conductor shield : Semi-conducting cross-linked polyethylene.
Insulation : Cross-linked polyethylene.
Insulation shield : Semi-conducting cross-linked polyethylene.
Sheath : Copper tape shield
Filler : Polypropylene (Nonhygroscopic material)
Binding tape : Polyester and/or Spunbond tape
Bedding : Black polyethylene (Optional : Polyvinyl chloride)
Armour : Double steel tape
Sheath : Black polyethylene (ST7) (Optional : Polyvinyl Chloride)
Diamet er
Nominal
of
sect iona M inimum Conduct
Number
l area
or
of wire (approx.)
mm
25
35
50
70
95
120
150
185
240
300
400
7
7
7
18
18
18
18
34
34
34
55
Diamet er
over
armour
(approx.)
Thickness
of Sheat h
Overall
diamet er
(approx.)
M aximum
DC.
resist ance of
Cdr. at 20C
M inimum
insulat ion
resist ance
at 20C
Ampacit ies
direct burial
in ground at
30C
ambient **
Allowable
ampacit ies
in f ree air
at 40C
Cable
weight
(approx.)
St andard
packing
mm
mm
mm
mm
mm
mm
mm
/ km
M -km
kg / km
m / reel
5.9
6.9
8.0
9.7
11.4
12.9
14.2
16.0
18.4
20.5
23.4
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
15.7
16.7
17.8
19.5
21.2
23.0
24.2
26.1
28.5
30.8
34.2
2x0.5
2x0.5
2x0.5
2x0.5
2x0.5
2x0.5
2x0.5
2x0.5
2x0.5
2x0.8
2x0.8
44.5
46.8
49.3
53.0
56.8
60.9
63.6
68.7
74.1
80.6
88.1
2.5
2.6
2.7
2.8
2.9
3.0
3.1
3.3
3.4
3.6
3.9
51
53
56
60
64
68
71
77
82
89
97
0.727
0.524
0.387
0.268
0.193
0.153
0.124
0.0991
0.0754
0.0601
0.047
1,367
1,237
1,127
990
886
795
743
677
607
552
487
135
160
190
230
275
310
345
385
435
480
530
145
170
205
250
305
345
390
440
510
575
645
3,052
3,497
4,046
4,932
5,976
7,028
8,030
9,592
11,676
14,773
17,972
500
500
500
500
500
250
250
250
250
250
250
Page 1 of 1
APPLICATION :
Preferably used for urban networks.
Exposed in aerial, direct burial,
conduit, open tray and underground
duct installation.
MAX. CONDUCTOR
TEMPERATURE :
90C (Normal Operation)
AC TESTING VOLTAGE :
42 kV
REFERENCE STANDARD :
IEC 60502-2
CONSTRUCTION :
Conductor : Compact round stranded copper.
Conductor shield : Semi-conducting cross-linked polyethylene.
Insulation : Cross-linked polyethylene.
Insulation shield : Semi-conducting cross-linked polyethylene.
Sheath : Copper tape shield
Filler : Polypropylene (Nonhygroscopic material)
Binding tape : Polyester and/or Spunbond tape
Bedding : Black polyethylene (Optional : Polyvinyl chloride)
Armour : Double steel tape
Sheath : Black polyethylene (ST7) (Optional : Polyvinyl Chloride)
Nominal
sectional
area
M inimum
Number
of wire
mm
35
50
70
95
120
150
185
240
300
400
7
7
18
18
18
18
34
34
34
55
Diameter
of
Conductor
(approx.)
Thickness
of
Insulation
Diameter
Thickness
Diameter
over
of Steel
over armour
insulation
tape armour
(approx.)
(Approx.)
mm
mm
mm
mm
6.9
8.0
9.7
11.4
12.9
14.2
16.0
18.4
20.5
23.4
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5
18.7
19.8
21.5
23.2
25.0
26.2
28.1
30.5
32.8
36.2
2x0.5
2x0.5
2x0.5
2x0.5
2x0.5
2x0.5
2x0.5
2x0.8
2x0.8
2x0.8
Ampacities
Allowable
direct burial in
ampacities in
ground at
free air at
30C
40C
ambient**
Thickness
of Sheath
Overall
diameter
(approx.)
M aximum DC.
resistance of
Cdr. at 20C
M inimum
insulation
resistance at
20C
mm
mm
mm
/ km
M -km
51.3
53.8
57.5
61.3
65.2
69.1
73.2
79.8
84.9
92.6
2.7
2.8
3.0
3.1
3.2
3.3
3.4
3.6
3.8
4.0
58
61
65
69
73
77
81
88
94
102
0.524
0.387
0.268
0.193
0.153
0.124
0.0991
0.0754
0.0601
0.047
1,417
1,297
1,146
1,031
929
870
795
716
652
578
160
190
230
275
310
345
385
435
480
530
Cable
weight
(approx.)
Standard
packing
kg / km
m / reel
175
205
255
305
350
390
445
510
575
645
3,934
4,500
5,438
6,510
7,558
8,745
10,181
13,166
15,479
18,735
500
500
500
250
250
250
250
250
250
250
Page 1 of 1
APPLICATION :
Preferably used for urban networks.
Exposed in aerial, direct burial,
conduit, open tray and underground
duct installation.
MAX. CONDUCTOR
TEMPERATURE :
90C (Normal Operation)
AC TESTING VOLTAGE :
63 kV
REFERENCE STANDARD :
IEC 60502-2
CONSTRUCTION :
Conductor : Compact round stranded copper.
Conductor shield : Semi-conducting cross-linked polyethylene.
Insulation : Cross-linked polyethylene.
Insulation shield : Semi-conducting cross-linked polyethylene.
Sheath : Copper tape shield
Filler : Polypropylene (Nonhygroscopic material)
Binding tape : Polyester and/or Spunbond tape
Bedding : Black polyethylene (Optional : Polyvinyl chloride)
Armour : Double steel tape
Sheath : Black polyethylene (ST7) (Optional : Polyvinyl Chloride)
Nominal
sectional
area
M inimum
Number
of wire
mm
50
70
95
120
150
185
240
300
400
7
18
18
18
18
34
34
34
55
Diameter
of
Conductor
(approx.)
Thickness
of
Insulation
Diameter
Thickness
Diameter
over
of Steel
over armour
insulation
tape armour
(approx.)
(Approx.)
mm
mm
mm
mm
8.0
9.7
11.4
12.9
14.2
16.0
18.4
20.5
23.4
8.0
8.0
8.0
8.0
8.0
8.0
8.0
8.0
8.0
24.8
26.5
28.2
30.0
31.2
33.1
35.5
37.8
41.2
2x0.5
2x0.5
2x0.5
2x0.8
2x0.8
2x0.8
2x0.8
2x0.8
2x0.8
Ampacities
Allowable
direct burial in
ampacities in
ground at
free air at
30C
40C
ambient**
Thickness
of Sheath
Overall
diameter
(approx.)
M aximum DC.
resistance of
Cdr. at 20C
M inimum
insulation
resistance at
20C
mm
mm
mm
/ km
M -km
65.0
69.7
73.4
78.7
81.4
85.6
91.0
96.3
104.9
3.2
3.3
3.5
3.6
3.7
3.9
4.0
4.2
4.4
73
78
82
87
90
95
100
106
115
0.387
0.268
0.193
0.153
0.124
0.0991
0.0754
0.0601
0.047
1,657
1,480
1,343
1,220
1,148
1,057
958
878
784
190
230
270
305
340
380
435
480
530
Cable
weight
(approx.)
Standard
packing
kg / km
m / reel
210
255
305
350
390
445
510
575
645
5,799
6,905
8,082
10,058
11,160
12,754
15,026
17,478
21,035
250
250
250
250
250
250
250
250
250
Page 1 of 1
APPLICATION :
Preferably used for urban networks.
Exposed in aerial, direct burial,
conduit, open tray and underground
duct installation.
MAX. CONDUCTOR
TEMPERATURE :
90C (Normal Operation)
AC TESTING VOLTAGE :
12.5 kV
REFERENCE STANDARD :
IEC 60502-2
CONSTRUCTION :
Conductor : Compact round stranded copper.
Conductor shield : Semi-conducting cross-linked polyethylene.
Insulation : Cross-linked polyethylene.
Insulation shield : Semi-conducting cross-linked polyethylene.
Sheath : Copper tape shield
Filler : Polypropylene (Nonhygroscopic material)
Binding tape : Polyester and/or Spunbond tape
Bedding : Black polyethylene (Optional : Polyvinyl chloride)
Armour : Galvanized steel wire
Binding tape : Polyester and/or Spunbond tape (Optional : Water blocking tape
Sheath : Black polyethylene (ST7) (Optional : Polyvinyl Chloride)
Diamet er
Nominal M inimu
of
sect ion
Conduct
m
al area Number
or
of wire (approx.)
mm
10
16
25
35
50
70
95
120
150
185
240
300
400
7
7
7
7
7
18
18
18
18
34
34
34
55
Diamet er
Thicknes Diamet er Thicknes Armour
over
s of
over
s of
aluminum
armour
Insulat io insulat ion Separat i
wire
(approx.
n
(Approx.) on sheat h diamet er
)
Thicknes
s of
Sheat h
Overall
diamet er
(approx.)
M aximum
DC.
resist ance
of Cdr. at
20C
M inimum
insulat ion
resist ance
at 20C
A mpacit ies
direct burial
in ground at
30C
ambient **
Allowable
ampacit ies
in f ree air
at 40C
mm
mm
mm
mm
mm
mm
mm
mm
/ km
M -km
3.7
4.7
5.9
6.9
8.0
9.7
11.4
12.9
14.2
16.0
18.4
20.5
23.4
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.6
2.8
3.0
9.5
10.5
11.7
12.7
13.8
15.5
17.2
19.0
20.2
22.1
24.7
27.4
31.2
1.2
1.2
1.2
1.2
1.3
1.4
1.4
1.5
1.5
1.6
1.7
1.8
2.0
2.00
2.00
2.00
2.00
2.50
2.50
2.50
2.50
2.50
2.50
2.50
3.15
3.15
32.9
34.9
37.5
39.8
43.3
47.2
50.7
54.8
57.5
61.7
67.5
76.0
84.6
2.1
2.2
2.3
2.3
2.5
2.6
2.7
2.8
3.0
3.1
3.3
3.5
3.8
40
42
45
47
51
55
59
63
66
71
77
86
95
1.83
1.15
0.727
0.524
0.387
0.268
0.193
0.153
0.124
0.0991
0.0754
0.0601
0.047
1,199
1,041
896
800
720
623
551
490
455
411
379
365
341
83
105
135
165
190
230
275
310
345
390
440
485
535
80
105
140
170
200
245
300
340
385
440
510
570
645
Cable
St andar
weight
d
(approx.
packing
)
kg / km
m / reel
2,270 1,000
2,607 500
3,056 500
3,515 500
4,493 500
5,491 500
6,562 500
7,651 500
8,719 250
##### 250
##### 250
##### 250
##### 250
APPLICATION :
Preferably used for urban networks.
Exposed in aerial, direct burial,
conduit, open tray and underground
duct installation.
MAX. CONDUCTOR
TEMPERATURE :
90C (Normal Operation)
AC TESTING VOLTAGE :
21 kV
REFERENCE STANDARD :
IEC 60502-2
CONSTRUCTION :
Conductor : Compact round stranded copper.
Conductor shield : Semi-conducting cross-linked polyethylene.
Insulation : Cross-linked polyethylene.
Insulation shield : Semi-conducting cross-linked polyethylene.
Sheath : Copper tape shield
Filler : Polypropylene (Nonhygroscopic material)
Binding tape : Polyester and/or Spunbond tape
Bedding : Black polyethylene (Optional : Polyvinyl chloride)
Armour : Galvanized steel wire
Binding tape : Polyester and/or Spunbond tape (Optional : Water blocking tape
Sheath : Black polyethylene (ST7) (Optional : Polyvinyl Chloride)
Diameter
Nominal
of
sectional M inimum
Number Conductor
area
(approx.)
of wire
mm
16
25
35
50
70
95
120
150
185
240
300
400
7
7
7
7
18
18
18
18
34
34
34
55
Thickness
of
Insulation
Diameter
over
insulation
(Approx.)
Thickness
of
Separation
sheath
Armour
aluminum
wire
diameter
Diameter
over
armour
(approx.)
Thickness
of Sheath
Overall
diameter
(approx.)
M aximum
M inimum
DC.
insulation
resistance of resistance at
Cdr. at 20C
20C
Ampacities
Allowable
direct burial in
ampacities in
ground at
free air at
30C
40C
ambient**
Cable
Standard
weight
packing
(approx.)
mm
mm
mm
mm
mm
mm
mm
mm
/ km
M -km
kg / km
m / reel
4.7
5.9
6.9
8.0
9.7
11.4
12.9
14.2
16.0
18.4
20.5
23.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
12.3
13.5
14.5
15.6
17.3
19.0
20.8
22.0
23.9
26.3
28.6
32.0
1.2
1.3
1.3
1.4
1.4
1.5
1.6
1.6
1.7
1.8
1.9
2.0
2.00
2.50
2.50
2.50
2.50
2.50
2.50
2.50
2.50
3.15
3.15
3.15
38.8
42.6
44.9
47.4
51.1
54.8
58.9
61.6
65.8
73.5
78.7
86.3
2.3
2.5
2.5
2.6
2.8
2.9
3.0
3.1
3.2
3.4
3.6
3.8
46
51
53
56
60
64
68
71
75
83
89
97
1.15
0.727
0.524
0.387
0.268
0.193
0.153
0.124
0.0991
0.0754
0.0601
0.047
1,295
1,126
1,011
916
799
711
634
591
536
479
434
381
105
135
165
195
235
275
310
345
390
440
485
535
105
140
170
205
250
300
345
390
440
510
575
645
2,960
3,885
4,377
4,984
5,968
7,084
8,241
9,301
10,801
14,041
16,497
19,843
500
500
500
500
500
500
250
250
250
250
250
250
APPLICATION :
Preferably used for urban networks.
Exposed in aerial, direct burial,
conduit, open tray and underground
duct installation.
MAX. CONDUCTOR
TEMPERATURE :
90C (Normal Operation)
AC TESTING VOLTAGE :
30.5 kV
REFERENCE STANDARD :
IEC 60502-2
CONSTRUCTION :
Conductor : Compact round stranded copper.
Conductor shield : Semi-conducting cross-linked polyethylene.
Insulation : Cross-linked polyethylene.
Insulation shield : Semi-conducting cross-linked polyethylene.
Sheath : Copper tape shield
Filler : Polypropylene (Nonhygroscopic material)
Binding tape : Polyester and/or Spunbond tape
Bedding : Black polyethylene (Optional : Polyvinyl chloride)
Armour : Galvanized steel wire
Binding tape : Polyester and/or Spunbond tape (Optional : Water blocking tape
Sheath : Black polyethylene (ST7) (Optional : Polyvinyl Chloride)
Diameter
Nominal
of
sectional M inimum
Number Conductor
area
(approx.)
of wire
mm
25
35
50
70
95
120
150
185
240
300
400
7
7
7
18
18
18
18
34
34
34
55
Thickness
of
Insulation
Diameter
over
insulation
(Approx.)
Thickness
of
Separation
sheath
Armour
aluminum
wire
diameter
Diameter
over
armour
(approx.)
Thickness
of Sheath
Overall
diameter
(approx.)
M aximum
M inimum
DC.
insulation
resistance of resistance at
Cdr. at 20C
20C
Ampacities
Allowable
direct burial in
ampacities in
ground at
free air at
30C
40C
ambient**
Cable
Standard
weight
packing
(approx.)
mm
mm
mm
mm
mm
mm
mm
mm
/ km
M -km
kg / km
m / reel
5.9
6.9
8.0
9.7
11.4
12.9
14.2
16.0
18.4
20.5
23.4
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
15.7
16.7
17.8
19.5
21.2
23.0
24.2
26.1
28.5
30.8
34.2
1.4
1.4
1.5
1.5
1.6
1.7
1.7
1.8
1.9
2.0
2.1
2.50
2.50
2.50
2.50
2.50
2.50
2.50
3.15
3.15
3.15
3.15
47.5
49.8
52.3
56.0
59.8
63.9
66.6
73.0
78.4
83.7
91.2
2.6
2.7
2.8
2.9
3.1
3.2
3.3
3.4
3.6
3.8
4.0
56
58
61
65
69
73
76
83
89
94
102
0.727
0.524
0.387
0.268
0.193
0.153
0.124
0.0991
0.0754
0.0601
0.047
1,367
1,237
1,127
990
886
795
743
677
607
552
487
135
160
190
230
275
310
345
385
435
480
530
145
170
205
250
305
345
390
440
510
575
645
4,470
4,999
5,588
6,616
7,789
8,977
10,058
12,609
14,962
17,397
20,801
500
500
500
500
250
250
250
250
250
250
250
APPLICATION :
Preferably used for urban networks.
Exposed in aerial, direct burial,
conduit, open tray and underground
duct installation.
MAX. CONDUCTOR
TEMPERATURE :
90C (Normal Operation)
AC TESTING VOLTAGE :
42 kV
REFERENCE STANDARD :
IEC 60502-2
CONSTRUCTION :
Conductor : Compact round stranded copper.
Conductor shield : Semi-conducting cross-linked polyethylene.
Insulation : Cross-linked polyethylene.
Insulation shield : Semi-conducting cross-linked polyethylene.
Sheath : Copper tape shield
Filler : Polypropylene (Nonhygroscopic material)
Binding tape : Polyester and/or Spunbond tape
Bedding : Black polyethylene (Optional : Polyvinyl chloride)
Armour : Galvanized steel wire
Binding tape : Polyester and/or Spunbond tape (Optional : Water blocking tape
Sheath : Black polyethylene (ST7) (Optional : Polyvinyl Chloride)
Diameter
Nominal
of
sectional M inimum
Number Conductor
area
(approx.)
of wire
mm
35
50
70
95
120
150
185
240
300
400
7
7
18
18
18
18
34
34
34
55
Thickness
of
Insulation
Diameter
over
insulation
(Approx.)
Thickness
of
Separation
sheath
Armour
aluminum
wire
diameter
Diameter
over
armour
(approx.)
Thickness
of Sheath
Overall
diameter
(approx.)
M aximum
M inimum
DC.
insulation
resistance of resistance at
Cdr. at 20C
20C
Ampacities
Allowable
direct burial in
ampacities in
ground at
free air at
30C
40C
ambient**
Cable
Standard
weight
packing
(approx.)
mm
mm
mm
mm
mm
mm
mm
mm
/ km
M -km
kg / km
m / reel
6.9
8.0
9.7
11.4
12.9
14.2
16.0
18.4
20.5
23.4
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5
18.7
19.8
21.5
23.2
25.0
26.2
28.1
30.5
32.8
36.2
1.5
1.6
1.6
1.7
1.7
1.8
1.9
2.0
2.0
2.2
2.50
2.50
2.50
2.50
3.15
3.15
3.15
3.15
3.15
3.15
54.3
56.8
60.5
64.3
69.5
73.4
77.5
82.9
88.0
95.7
2.9
3.0
3.1
3.2
3.4
3.5
3.6
3.8
3.9
4.2
63
66
70
74
79
83
88
93
99
107
0.524
0.387
0.268
0.193
0.153
0.124
0.0991
0.0754
0.0601
0.047
1,417
1,297
1,146
1,031
929
870
795
716
652
578
160
190
230
275
310
345
385
435
480
530
175
205
255
305
350
390
445
510
575
645
5,590
6,238
7,252
8,423
10,474
11,791
13,417
15,810
18,203
21,743
500
250
250
250
250
250
250
250
250
250
Page 1 of 1
APPLICATION :
Preferably used for urban networks.
Exposed in aerial, direct burial,
conduit, open tray and underground
duct installation.
MAX. CONDUCTOR
TEMPERATURE :
90C (Normal Operation)
AC TESTING VOLTAGE :
63 kV
REFERENCE STANDARD :
IEC 60502-2
CONSTRUCTION :
Conductor : Compact round stranded copper.
Conductor shield : Semi-conducting cross-linked polyethylene.
Insulation : Cross-linked polyethylene.
Insulation shield : Semi-conducting cross-linked polyethylene.
Sheath : Copper tape shield
Filler : Polypropylene (Nonhygroscopic material)
Binding tape : Polyester and/or Spunbond tape
Bedding : Black polyethylene (Optional : Polyvinyl chloride)
Armour : Galvanized steel wire
Binding tape : Polyester and/or Spunbond tape (Optional : Water blocking tape
Sheath : Black polyethylene (ST7) (Optional : Polyvinyl Chloride)
Diameter
Nominal
of
sectional M inimum
Number Conductor
area
(approx.)
of wire
mm
50
70
95
120
150
185
240
300
400
7
18
18
18
18
34
34
34
55
Thickness
of
Insulation
Diameter
over
insulation
(Approx.)
Thickness
of
Separation
sheath
Armour
aluminum
wire
diameter
Diameter
over
armour
(approx.)
Thickness
of Sheath
Overall
diameter
(approx.)
M aximum
M inimum
DC.
insulation
resistance of resistance at
Cdr. at 20C
20C
Ampacities
Allowable
direct burial in
ampacities in
ground at
free air at
30C
40C
ambient**
Cable
Standard
weight
packing
(approx.)
mm
mm
mm
mm
mm
mm
mm
mm
/ km
M -km
kg / km
m / reel
8.0
9.7
11.4
12.9
14.2
16.0
18.4
20.5
23.4
8.0
8.0
8.0
8.0
8.0
8.0
8.0
8.0
8.0
24.8
26.5
28.2
30.0
31.2
33.1
35.5
37.8
41.2
1.8
1.8
1.9
2.0
2.0
2.1
2.2
2.3
2.4
3.15
3.15
3.15
3.15
3.15
3.15
3.15
3.15
3.15
69.3
74.0
77.7
81.8
84.5
88.7
94.1
99.4
108.0
3.4
3.5
3.6
3.8
3.9
4.0
4.2
4.3
4.6
79
84
88
92
95
100
105
111
120
0.387
0.268
0.193
0.153
0.124
0.0991
0.0754
0.0601
0.047
1,657
1,480
1,343
1,220
1,148
1,057
958
878
784
190
230
270
305
340
380
435
480
530
210
255
305
350
390
445
510
575
645
8,654
10,005
11,279
12,667
13,826
15,524
18,014
20,600
24,422
250
250
250
250
250
250
250
250
250
Page 1 of 1
APPLICATION :
Preferably used for urban networks.
Exposed in aerial, direct burial,
conduit, open tray and underground
duct installation.
MAX. CONDUCTOR
TEMPERATURE :
90C (Normal Operation)
AC TESTING VOLTAGE :
12.5 kV
CONSTRUCTION :
REFERENCE STANDARD :
IEC 60502-2
Diamet er
Diamet er
Diamet er
Diamet er
Nominal
Thickness
Thickness
Armour
of
over
over lead
over
sect ional Number
of
of lead
st eel wire
Conduct or
insulation
sheath
armour
area
Insulation
sheat h
diamet er
of wire
(approx.)
(Approx.)
(approx.)
(approx.)
mm
10
16
25
35
50
70
95
120
150
185
240
300
400
7
7
7
7
7
18
18
18
18
34
34
34
55
Overall
Thickness
diamet er
of Sheat h
(approx.)
M aximum
DC.
resist ance
of Cdr. at
20C
M inimum
insulat ion
resist ance
at 20C
Ampacit ies
direct burial
in ground at
30C
ambient **
Allowable
ampacit ies
in f ree air at
40C
ambient
Cable
weight
(approx.)
St andard
packing
mm
mm
mm
mm
mm
mm
mm
mm
mm
/ km
M -km
kg / km
m / reel
3.7
4.7
5.9
6.9
8.0
9.7
11.4
12.9
14.2
16.0
18.4
20.5
23.4
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.6
2.8
3.0
9.5
10.5
11.7
12.7
13.8
15.5
17.2
19.0
20.2
22.1
24.7
27.4
31.2
1.5
1.5
1.6
1.7
1.8
1.9
2.0
2.1
2.1
2.2
2.4
2.6
2.8
31.9
33.9
36.9
39.4
42.1
46.0
49.9
54.2
56.9
61.3
67.5
75.1
84.1
2.0
2.0
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
3.2
3.2
3.2
38.3
40.3
44.5
47.0
49.9
53.8
57.9
62.4
65.1
69.7
77.4
85.2
94.6
2.2
2.3
2.5
2.6
2.7
2.8
2.9
3.0
3.2
3.3
3.5
3.7
4.0
45
48
52
55
58
62
67
71
74
79
87
96
106
1.83
1.15
0.727
0.524
0.387
0.268
0.193
0.153
0.124
0.0991
0.0754
0.0601
0.047
1,199
1,041
896
800
720
623
551
490
455
411
379
365
341
81
103
132
162
186
225
270
304
338
382
431
475
524
78
103
137
167
196
240
294
333
377
431
500
559
632
4,025
4,488
5,681
6,424
7,357
8,762
10,340
12,017
13,317
15,353
19,458
23,465
28,531
500
500
500
500
500
500
250
250
250
250
250
250
250
APPLICATION :
Preferably used for urban networks.
Exposed in aerial, direct burial,
conduit, open tray and underground
duct installation.
MAX. CONDUCTOR
TEMPERATURE :
90C (Normal Operation)
AC TESTING VOLTAGE :
21 kV
CONSTRUCTION :
REFERENCE STANDARD :
IEC 60502-2
Diamet er
Diamet er
Diamet er
Diamet er
Nominal
Thickness
Thickness
Armour
of
over
over lead
over
sect ional Number
of
of lead
st eel wire
Conduct or
insulation
sheath
armour
area
Insulation
sheat h
diamet er
of wire
(approx.)
(Approx.)
(approx.)
(approx.)
mm
16
25
35
50
70
95
120
150
185
240
300
400
7
7
7
7
18
18
18
18
34
34
34
55
Overall
Thickness
diamet er
of Sheat h
(approx.)
M aximum
DC.
resist ance
of Cdr. at
20C
M inimum
insulat ion
resist ance
at 20C
Ampacit ies
direct burial
in ground at
30C
ambient **
Allowable
ampacit ies
in f ree air at
40C
ambient
Cable
weight
(approx.)
St andard
packing
mm
mm
mm
mm
mm
mm
mm
mm
mm
/ km
M -km
kg / km
m / reel
4.7
5.9
6.9
8.0
9.7
11.4
12.9
14.2
16.0
18.4
20.5
23.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
12.3
13.5
14.5
15.6
17.3
19.0
20.8
22.0
23.9
26.3
28.6
32.0
1.7
1.7
1.8
1.9
2.0
2.1
2.2
2.3
2.4
2.5
2.6
2.8
38.4
41.0
43.7
46.4
50.3
54.2
58.5
61.4
65.8
72.4
77.8
85.8
2.5
2.5
2.5
2.5
2.5
2.5
2.5
3.2
3.2
3.2
3.2
3.2
46.0
48.6
51.5
54.4
58.3
62.4
66.9
71.1
75.7
82.5
88.1
96.3
2.5
2.6
2.7
2.8
2.9
3.1
3.2
3.4
3.5
3.7
3.8
4.1
54
57
60
63
67
72
76
81
86
93
99
107
1.15
0.727
0.524
0.387
0.268
0.193
0.153
0.124
0.0991
0.0754
0.0601
0.047
1,295
1,126
1,011
916
799
711
634
591
536
479
434
381
103
132
162
191
230
270
304
338
382
431
475
524
103
137
167
201
245
294
338
382
431
500
564
632
5,790
6,478
7,352
8,330
9,748
11,451
13,150
15,471
17,679
21,003
24,267
29,099
500
500
500
500
250
250
250
250
250
250
250
250
APPLICATION :
Preferably used for urban networks.
Exposed in aerial, direct burial,
conduit, open tray and underground
duct installation.
MAX. CONDUCTOR
TEMPERATURE :
90C (Normal Operation)
AC TESTING VOLTAGE :
30.5 kV
CONSTRUCTION :
REFERENCE STANDARD :
IEC 60502-2
Diamet er
Diamet er
Diamet er
Diamet er
Nominal
Thickness
Thickness
Armour
of
over
over lead
over
sect ional Number
of
of lead
st eel wire
Conduct or
insulation
sheath
armour
area
Insulation
sheat h
diamet er
of wire
(approx.)
(Approx.)
(approx.)
(approx.)
mm
25
35
50
70
95
120
150
185
240
300
400
7
7
7
18
18
18
18
34
34
34
55
Overall
Thickness
diamet er
of Sheat h
(approx.)
M aximum
DC.
resist ance
of Cdr. at
20C
M inimum
insulat ion
resist ance
at 20C
Ampacit ies
direct burial
in ground at
30C
ambient **
Allowable
ampacit ies
in f ree air at
40C
ambient
Cable
weight
(approx.)
St andard
packing
mm
mm
mm
mm
mm
mm
mm
mm
mm
/ km
M -km
kg / km
m / reel
5.9
6.9
8.0
9.7
11.4
12.9
14.2
16.0
18.4
20.5
23.4
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
15.7
16.7
17.8
19.5
21.2
23.0
24.2
26.1
28.5
30.8
34.2
1.9
1.9
2.0
2.1
2.2
2.3
2.4
2.5
2.6
2.8
3.0
46.5
48.8
51.5
55.4
59.4
63.7
66.6
71.9
77.5
83.2
91.1
2.5
2.5
2.5
2.5
2.5
3.2
3.2
3.2
3.2
3.2
3.2
54.5
56.8
59.7
63.6
67.8
73.6
76.5
82.0
87.8
93.7
101.8
2.8
2.9
3.0
3.1
3.3
3.4
3.5
3.7
3.8
4.0
4.3
63
66
69
73
77
83
86
92
98
105
113
0.727
0.524
0.387
0.268
0.193
0.153
0.124
0.0991
0.0754
0.0601
0.047
1,367
1,237
1,127
990
886
795
743
677
607
552
487
132
157
186
225
270
304
338
377
426
470
519
142
167
201
245
299
338
382
431
500
564
632
7,828
8,532
9,563
11,042
12,775
15,362
16,936
19,529
22,697
26,381
31,309
500
250
250
250
250
250
250
250
250
250
250
APPLICATION :
Preferably used for urban networks.
Exposed in aerial, direct burial,
conduit, open tray and underground
duct installation.
MAX. CONDUCTOR
TEMPERATURE :
90C (Normal Operation)
AC TESTING VOLTAGE :
42 kV
CONSTRUCTION :
REFERENCE STANDARD :
IEC 60502-2
Diamet er
Diamet er
Diamet er
Diamet er
Nominal
Thickness
Thickness
Armour
of
over
over lead
over
sect ional Number
of
of lead
st eel wire
Conduct or
insulation
sheath
armour
area
Insulation
sheat h
diamet er
of wire
(approx.)
(Approx.)
(approx.)
(approx.)
mm
35
50
70
95
120
150
185
240
300
400
7
7
18
18
18
18
34
34
34
55
Overall
Thickness
diamet er
of Sheat h
(approx.)
M aximum
DC.
resist ance
of Cdr. at
20C
M inimum
insulat ion
resist ance
at 20C
Ampacit ies
direct burial
in ground at
30C
ambient **
Allowable
ampacit ies
in f ree air at
40C
ambient
Cable
weight
(approx.)
St andard
packing
mm
mm
mm
mm
mm
mm
mm
mm
mm
/ km
M -km
kg / km
m / reel
6.9
8.0
9.7
11.4
12.9
14.2
16.0
18.4
20.5
23.4
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5
18.7
19.8
21.5
23.2
25.0
26.2
28.1
30.5
32.8
36.2
2.1
2.2
2.3
2.4
2.4
2.5
2.6
2.8
2.9
3.1
53.7
56.4
60.3
64.3
68.4
72.3
76.6
82.4
87.9
95.8
2.5
2.5
2.5
3.2
3.2
3.2
3.2
3.2
3.2
3.2
61.9
64.8
68.7
74.2
78.5
82.4
86.9
92.9
98.6
106.7
3.1
3.2
3.3
3.5
3.6
3.7
3.8
4.0
4.2
4.4
71
74
78
84
89
93
97
104
110
118
0.524
0.387
0.268
0.193
0.153
0.124
0.0991
0.0754
0.0601
0.047
1,417
1,297
1,146
1,031
929
870
795
716
652
578
157
186
225
270
304
338
377
426
470
519
172
201
250
299
343
382
436
500
564
632
9,876
10,966
12,517
15,108
16,809
18,708
21,063
24,645
28,134
33,199
250
250
250
250
250
250
250
250
250
250
APPLICATION :
Preferably used for urban networks.
Exposed in aerial, direct burial,
conduit, open tray and underground
duct installation.
MAX. CONDUCTOR
TEMPERATURE :
90C (Normal Operation)
AC TESTING VOLTAGE :
63 kV
CONSTRUCTION :
REFERENCE STANDARD :
IEC 60502-2
Diamet er
Diamet er
Diamet er
Diamet er
Nominal
Thickness
Thickness
Armour
of
over
over lead
over
sect ional Number
of
of lead
st eel wire
Conduct or
insulation
sheath
armour
area
Insulation
sheat h
diamet er
of wire
(approx.)
(Approx.)
(approx.)
(approx.)
mm
50
70
95
120
150
185
240
300
400
7
18
18
18
18
34
34
34
55
Overall
Thickness
diamet er
of Sheat h
(approx.)
M aximum
DC.
resist ance
of Cdr. at
20C
M inimum
insulat ion
resist ance
at 20C
Ampacit ies
direct burial
in ground at
30C
ambient **
Allowable
ampacit ies
in f ree air at
40C
ambient
Cable
weight
(approx.)
St andard
packing
mm
mm
mm
mm
mm
mm
mm
mm
mm
/ km
M -km
kg / km
m / reel
8.0
9.7
11.4
12.9
14.2
16.0
18.4
20.5
23.4
8.0
8.0
8.0
8.0
8.0
8.0
8.0
8.0
8.0
24.8
26.5
28.2
30.0
31.2
33.1
35.5
37.8
41.2
2.5
2.6
2.7
2.8
2.9
3.0
3.1
3.2
3.4
68.2
73.3
77.0
81.3
84.4
88.6
94.2
99.7
108.9
3.2
3.2
3.2
3.2
3.2
3.2
3.2
3.2
3.2
78.3
83.6
87.3
91.8
95.1
99.3
105.1
110.8
120.4
3.6
3.8
3.9
4.0
4.1
4.2
4.4
4.6
4.9
88
94
98
103
106
111
117
123
133
0.387
0.268
0.193
0.153
0.124
0.0991
0.0754
0.0601
0.047
1,657
1,480
1,343
1,220
1,148
1,057
958
878
784
186
225
265
299
333
372
426
470
519
206
250
299
343
382
436
500
564
632
15,230
17,372
19,260
21,383
23,310
25,685
29,204
32,898
38,853
250
250
250
250
250
250
250
250
250
Page 1 of 1