Based on the 2012 edition of the Life Safety Code, for all Healthcare facilities
Revision 4: 12-1-2016
Notification Devices
Devices/Function
Waterflow switches
Smoke detectors
Heat detectors
Duct detectors
Manual pull stations
Low air pressure switches
Low water level switches
Tamper switches
Strobes
Horns
Bells
Chimes
Magnetic hold-open
Air handler shut-down
Kitchen hood suppression sys
Elevator recall
Magnetic locks / Electric strikes
Fire pump
Smoke dampers
CO2/Clean agent suppression
Sprinkler dry-pipe/pre-action
Overhead rolling fire doors
Charger test
Discharge test
Load voltage test
Frequency
Semi-annually
Annually
Annually
Annually
Annually
Quarterly
Quarterly
Semi-annually
Annually
Annually
Annually
Annually
Annually
Annually
Annually
Annually
Annually
Annually
Annually
Annually
Annually
Annually
Annually
Annually
Semi-annually
2-Years*
Annually
NFPA Standard
72-2010; 14.4.5
72-2010; 14.4.5
72-2010; 14.4.5
72-2010; 14.4.5
72-2010; 14.4.5
72-2010; 14.4.5
72-2010; 14.4.5
72-2010; 14.4.5
72-2010; 14.4.5
72-2010; 14.4.5
72-2010; 14.4.5
72-2010; 14.4.5
72-2010; 14.4.5
72-2010; 14.4.5
72-2010; 14.4.5
72-2010; 14.4.5
72-2010; 14.4.5
72-2010; 14.4.5
72-2010; 14.4.5
72-2010; 14.4.5
72-2010; 14.4.5
72-2010; 14.4.5
72-2010; 14.4.5
72-2010; 14.4.5
72-2010; 14.4.5
72-2010; 14.4.5
72-2010; 14.4.5
Monthly
Annually
Monthly
Semi-annually
Semi-annually
Monthly
Semi-annually
Annually
Semi-annually
Annually
10-2010; 7.2.1.2
10-2010; 7.3.1.1.1
17A-2009; 7.2.1
17A-2009; 7.3.3
12A-2009; 7.1.1
12-2011 4.8.1
12-2011; 4.8.3.5.1
12-2011; 4.8.3.2
2001-2012; 7.1.3
2001-2012; 7.1.1
Alternative suppression
systems
Inspection
Maintenance
Kitchen hood system inspection
Kitchen hood system test
Halon system inspection & test
CO2 system inspection
CO2 system tank weigh
CO2 system test
Clean agent system inspection
Clean agent system test
Date of
Most Recent
Compliant?
Yes
No
N/A
Comment
Devices/Function
Fire pump churn test
Control valve inspection
Pressure Gauge Inspection
Fire department connections
Fire hose valve Inspection
Pre-action/Dry pipe valve priming
water test
Sprinkler inspection
Piping & hanger inspection
Pre-action/Dry pipe valve trip test
Main drain test
Water-based suppression
systems
Frequency
Monthly
Monthly
Monthly
Quarterly
Quarterly
NFPA Standard
25-2011; 8.3.1
25-2011; 13.3.2.1.1
25-2011; 13.2.7.1
25-2011; 13.7.1
25-2011; 13.5.6.1
Quarterly
25-2011; 13.4.3.2.1
Annually
Annually
Annually
Quarterly*
Annually
Annually
Annually
Annually
Annually
Annually
Annually
Annually
3-Years
5-Years, then
every 3-Years
5-Years
5-Years
5-Years
5-Years
5-Years
10-Years
20-Years
50-Years
25-2011; 5.2.1
25-2011; 5.2.2
25-2011; 13.4.3.2.2
25-2011; 13.2.5.1
25-2011; 13.2.5
25-2011; 13.3.3.1
25-2011; 13.6.2
25-2011; 5.3.4
25-2011; 7.3.2
25-2011; 13.5.6.2.1
25-2011; 8.3.3
1962-2008; 4.3.4
25-2011; 13.5.6.2.2
Weekly
Weekly
20 days to 40
days
Annually*
Annually
3-Years
20 days to 40
days
As per policy
After breach
After breach
110-2010; 8.4.1
110-2010; 8.3.7.1
110-2010; 8.4.2 and
99-2012; 6.4.4.1.1.4
110-2010; 8.4.2.3
110-2010; 8.3.8
110-2010; 8.4.9
110-2010; 8.4.6 and
99-2012; 6.4.4.1.1.4
99-2012; 5.1.14.4.5
99-2012; 5.1.12.1.1
99-2012; 5.1.12.1.1
1962-2008; 4.3.2
25-2011; 13.4.2.1
25-2011; 5.3.2
25-2011; 6.3.1
25-2011; 7.3.1
25-2011; 14.2.1
25-2011; 5.3.1.1.1.6
25-2011; 5.3.1.1.1.3
25-2011; 5.3.1.1.1
Date of
Most Recent
Compliant?
Yes
No
N/A
Comment
Devices/Function
Policy
Alternative Life Safety
Measures
Frequency
Review policy
As needed per
policy
Implementation
Fire Watch
Drop test
Annual test/inspection
Illumination inspection
Test of all elevators equipped with
Fire Fighter Service
Inspect fire suppression system
Remove grease
Risk assessment to determine
Category designation of systems
Date of
Most Recent
Compliant?
Yes
No
N/A
Comment
101-2012; 4.6.10.1
Monthly
101-2012; 9.4.6.2
Monthly
Semi-annually
17A-2009; 7.2.1
96- 2011; 11.4
Annually
99-2012; 4.2
Continuous
NFPA Standard
101-2012; 4.6.10.1
*= If Required