Sunteți pe pagina 1din 4

Preliminary MEP Ecology Schedule For: SP ESP 24H + CARBON and FAN

Sirius Products, Office 3103, Regal Tower, Business Bay, Dubai, UAE.
Project: JJ KITCHEN DUBAI MARINA
For Units:
Drawing Ref:
Date: 30/Nov/2016
General Information
Air Volume Range

2763 CFM

Total Weight

471 Kg

Maximum Static Pressure

1000 Pa

Unit Static Pressure

280 Pa

Electrical Load Fan

4.5 KW, 400V/3ph/50Hz

Electrical Load Filtration

6Amp/230V/1ph/50Hz

Maximum Operating Conditions

Room ambient 50C 70%rh


Internal Duct 100C 90%rh

Layout Drawing

Rev: 01

System Requirements
1.
2.
3.
4.
5.
6.

Locally isolated electrical feeds.


1m duct before and after the filtration units. This reduces pressure and improves performance.
Flat, safe and appropriate load bearing platform.
Ideally installed 10m from the end of the duct to allow for O3 reactions.
Additional activated filters if discharging at low level or within close proximity to receptors in order to comply with WHO
ozone limits.
Use Type 'C' MCB

This system should be installed and maintained in accordance with the following documents:
1.

Sirius Products Electrostatic Precipitator Operation and Maintenance Manual: Issue ESP001

Standard Service Access and Filtration Unit End Detail Specification

Connection Type
To correctly wire the units, you will
need to provide a suitably fused
single phase power supply and local
isolator. Allow 3 Amps per cell
module.
Step 1: Wire the power cable into
isolator in each unit.

Step 2: Before turning


the unit on, use a
voltmeter to check that
the power supply meets
the specifications stated
on the ESPs date plates
(located on the front of
the electrical box). A
good reading is between
230-240V.

2-STAGE FILTRATION ( Flow : 2763 CFM )

750

1050

750

No.

Date

Rev.
By

Revision Description

Client:
JJ KITCHEN
Project :
JJ KITCHEN
DUBAI MARINA

ELEVATION

PLAN

FILTER'S DETAILS

Drawing Title :
CARBON FILTER DETAILS

No.

Stage

Pre-Filter

2 Carbon Filter

Description

Nominal Size
H x W x T (mm)
592 x 592 x 44

AAF - Perfect Pleat Ultra


AAF - Varisorb XL with
SAAF media

Unit Weight
(Kg)
1.5

Qty.
Drawing No.:
JJ-2016-10-001

Rev:
01

1
Scale: NTS

287 x 592 x 44

1.08

592 x 592 x 292

287 x 592 x 292

Drawn By: MS

Date: 30-Nov-2016

P.O. Box.:184893 Dubai, UAE


Tel. No: 04- 2540902
Email: info@greencrystal.ae

EXTRACT FAN ( 2763 CFM @ 1000 Pa)


System Air Model MUB/T 062 630D4 IE2
made in Germany

Brand:
Discharge

Technical Parameters
Voltage
Motor circuit connection
Frequency

400 V
D
50 Hz

Phase
Input power (P1)

4498 W

Current
Starting Current

8.12 A
60.9 A

Max. airflow
Fan impeller speed

1450 r.p.m

Max. temperature of transported air


Discharge
Air Inlet

800

Weight

102 kg

Insulation class, motor

Enclosure class, Motor

55 IP
67 dB(A)

Hydraulic data
Required point

800

Q
[cfm]

Ps
[Pa]

Q
[cfm]

Ps
[Pa]

P
[W]

n
[ r.p.m]

I
[A]

SEP

2763

1000

5242

896

4449

1462

7.75

1.8

400

2931

1123

3757

1465

6.83

2.72

400

No.

Date

Rev.
By

Revision Description

Client:

630D4
LwA Inlet
LwA Outlet
LwA Surrounding

Project :
JJ CHICKEN
DUBAI MARINA

Mid-frequency band, Hz

SIDE ELEVATION

U
[V]

JJ CHICKEN

Max.
Efficiency
Selection

Working point

Hz
dB(A)

Tot 63

125 250 500 1k

2k

4k

8k

86

73

75

79

81

80

77

72

65

dB(A)

88

75

77

81

83

82

79

74

67

dB(A)

75

62

64

68

70

69

66

61

54

Drawing Title :
Kitchen Extract Fan Details

Performance Diagrams
Drawing No.:

800

JJ-2016-10-002

Rev:
01

Scale: NTS
Drawn By: MS

Date: 30-Nov-2016

P.O. Box.:184893 Dubai, UAE


Tel. No: 04- 2540902
Email: info@greencrystal.ae

PLAN
NOTE: Fan Speed Controlled by VFD