Documente Academic
Documente Profesional
Documente Cultură
B S Rigby
* eThekwini Electricity
1 Jeff Taylor Crescent
Durban, South Africa
I.
INTRODUCTION
THEORY
IEEE Africon 2011 - The Falls Resort and Conference Centre, Livingstone, Zambia, 13 - 15 September 2011
III.
REAL-TIME MODEL
IEEE Africon 2011 - The Falls Resort and Conference Centre, Livingstone, Zambia, 13 - 15 September 2011
12
ZCIM1r1 vs ZCRE1r1
AvonMersey1
Z1 Z2 Z3
9.66667
7.33333
X (Ohms)
2.66667
0.33333
-2
-6
-3.66667
-1.33333
3.33333
5.66667
R (Ohms)
ZCIM1r3 vs ZCRE1r3
AvonMersey1M
Z1 Z2 Z3
RESULTS
9.66667
7.33333
X (Ohms)
A. No Mutual Coupling
To establish a base case, the real-time model was first used
to study the system with the topology shown in Fig. 1 (both
lines in service) but with no mutual coupling represented
between circuits AB and CD. In these studies, and those to
follow, the system was intentionally considered with no load
transfer down the lines, and no source beyond Bus R in order
to remove the additional complicating effects of load transfer
and remote-end infeed on the impedances seen by the relay at
A, at least for this phase of the research study.
2.66667
0.33333
-2
-6
-3.66667
-1.33333
3.33333
5.66667
R (Ohms)
IEEE Africon 2011 - The Falls Resort and Conference Centre, Livingstone, Zambia, 13 - 15 September 2011
the real-time model of the relay at the remote end of the line
(relay B) for a C-g fault located 20% along the line from A
(i.e. at the intended reach of the remote-end relays Zone 1).
By contrast with Fig. 5, Fig. 6 shows that the impact of mutual
coupling causes the relay at the remote end to overreach
noticeably for this system condition. The behaviour of the
relays at both A and B is therefore consistent with that
expected from the analysis in [1] for mutually-coupled parallel
lines under these test conditions.
12
ZCIM1r4 vs ZCRE1r4
AvonMersey1M
Z1 Z2 Z3
9.66667
X (Ohms)
7.33333
2.66667
0.33333
-2
-6
-3.66667
-1.33333
3.33333
5.66667
Figure 7: Percentage error in Zone 1 reach for C-g fault at 80% along line AB
versus distance between coupled lines when both lines are in service.
R (Ohms)
100 %
(1)
ZCIM1r3 vs ZCRE1r3
AvonMersey1M
Z1 Z2 Z3
9.66667
7.33333
X (Ohms)
12
2.66667
0.33333
-2
-6
-3.66667
-1.33333
3.33333
5.66667
R (Ohms)
IEEE Africon 2011 - The Falls Resort and Conference Centre, Livingstone, Zambia, 13 - 15 September 2011
relay only after the remote relay has tripped. In other words,
relay A does not initially see the fault in Zone 2, even though
the fault is on the protected line, because of the effect of
mutual coupling. Once the relay at the remote end trips, it
clears the current feeding into the fault from that end, and
hence there is no longer any zero sequence current in the
neighbouring line CD to cause mutual coupling effects on the
relay at A; at this point, relay A sees the fault for the first time
(in its Zone 2) and, having already received a permissive
signal from the relay at B, is able to trip without time delay.
Figure 9: Response of the protection relays at A and B to the same C-g fault
considered in Fig. 8 (100% along the line AB) when the relays are connected
closed-loop.
15
ZCIM1r3 vs ZCRE1r3
AvonMersey1M
Z1 Z2 Z3
12.16667
12
X (Ohms)
9.33333
AvonMersey1M
Z1 Z2 Z3
9.66667
6.5
7.33333
X (Ohms)
3.66667
0.83333
2.66667
-2
-6
ZCIM1r3 vs ZCRE1r3
-3.66667
-1.33333
3.33333
5.66667
0.33333
R (Ohms)
-2
-6
-3.66667
-1.33333
3.33333
5.66667
R (Ohms)
IEEE Africon 2011 - The Falls Resort and Conference Centre, Livingstone, Zambia, 13 - 15 September 2011
Fig. 12: Percentage error in Zone 1 reach for C-g fault at 80% along line AB
versus distance between coupled lines when line CD is out of service and
grounded at both ends.
CONCLUSION