cooling tower. Range is the temperature difference between the hot water entering the cooling tower and the cold water leaving. The range is virtually identical with the condenser rise. Note that the range is not determined by performance of the tower, but is determined by the heat loading. Approach is the difference between the temperature of the water leaving the tower and the wet bulb temperature of the entering air. The approach is affected by the cooling tower capability. For a given heat loading, water flow rate, and entering air conditions, a larger tower will produce a smaller approach; i.e., the water leaving the tower will be colder.
Ambient wet bulb temperature and its effect on
performance Ambient wet bulb temperature is a condition measured by a device called a psychrometer. The measured wet bulb temperature is a function of relative humidity and ambient air temperature. Wet bulb temperature essentially measures how much water vapor the atmosphere can hold at current weather conditions. A lower wet bulb temperature means the air is drier and can hold more water vapor than it can at a higher wet bulb temperature. When selecting a cooling tower cell, the highest or the design wet bulb temperature your geographical area will encounter must be used. Highest wet bulb temperatures occur during the summer, when air temperatures and humidity are highest.
The temperature of air as read on the ordinary thermometer is
called DBT. WBT is the reading when the bulb of a thermometer is covered with a wet cloth, and the instrument is whirled around in a sling. RH is the ratio of the quantity of water vapor present in a cubic feet of air to the greatest amount of vapor which that air could hold at a given temperature. When the relative humidity is 100%, the air cannot hold any more water and therefore, water will not evaporate in 100% humid air. When the RH is 100% the WBT is the same as the DBT, because the water cannot evaporate any more. But when the RH is less than 100%, the WBT will be less than the DBT and water will evaporate. The capability of the cooling tower is a measure of how close the tower can bring the water temperature to the WBT of the entering air. A larger cooling tower [i.e., more air and/or more fill] will produce a closer approach [colder leaving water] for a given heat load, flow rate and entering air condition. The lower the WBT, which indicates either cool air, low humidity or a combination of the two, the lower can the cooling tower can cool the water. The thermal performance of the cooling tower is thus affected by the entering WBT; the entering air DBT has an insignificant effect on thermal performance. In actual practice, the final cold water temperature will always be at least a few degrees above WBT, depending on design conditions. It is not customary in the cooling tower industry to guarantee any approach less than 5 oF.
Tower Characteristic (MeM or NTU) is a characteristic of the
tower that relates tower design and operating characteristics to the amount of heat that can be transferred. For a given set of operating conditions, the design constants that depend on the tower fill. For a tower that is to be evaluated using the characteristic curve method, the manufacturer will provide a tower characteristic curve.