The load C.T. is only required when there is more than one Mains Controller (DSE8660 / DSE7560 / DSE5560) on the same system. With the load C.T. fitted, the Mains Controller transfers the right amount of load to the grid before disconnecting the generators. This prevents the generators being shock loaded. Without the load C.T., the Mains Controller does not know how much load to transfer to the grid when other Controllers are still in island mode. This results in the Mains Controller transferring a pre determined amount of load before disconnecting the generators from the grid. Hence, there is either too much load, or not enough load transferred, and the generators are shock loaded as they are disconnected from the grid.