Documente Academic
Documente Profesional
Documente Cultură
AbstractIn a cost-competitive environment, a large motor installation can make up a major part of a process project. This paper
explores the issues of reliability and cost for the sizing and protection of captive transformers of differing technologies, so that the
overall life-cycle cost of a captive motor-transformer installation
can be minimized.
Index TermsCaptive transformer, large motor, protective relaying, transformer selection.
Fig. 1. Captive motor/transformer single line.
I. INTRODUCTION
(1)
1705
where
per-unit starting voltage;
per-unit initial or nominal voltage;
per-unit motor starting impedance;
per-unit system short circuit impedance.
Equation (1) calculates the initial voltage at the instant the
varies as the motor accelerates to
motor is started. Since
full speed, the motor terminal voltage and the resultant torque
also will vary.
Increasing the short-circuit availability (stiffness) of the
system by increasing the size of the captive transformer with
a constant percent impedance reduces the system short-circuit
in the denominator, thus increasing the available
impedance
motor starting voltage. Another method of increasing available motor terminal voltage is to specify a lower impedance
transformer. Most transformer manufacturers have standard
impedance offerings, such as 5.50% which is a common
percent impedance for medium-voltage transformers. Lowering
the impedance will also increase the available short-circuit
availability, thus reducing the voltage drop. Reducing the
impedance below the standard impedance may increase the cost
of the transformer. If the impedance is reduced below 5.00%,
the cost of the transformer may increase substantially because
of design changes required by the increased short-circuit forces
on the transformer. The other criteria that must be verified in
either case is that the momentary and interrupting ratings of the
electrical switchgear are not exceeded.
Another consideration for selection of a captive transformer
is the number of starts or pulses that the motor and transformer
will experience. Each time a motor starts, significant forces
are exerted on the transformer windings. Manufacturers utilize
unique construction and design techniques for each type of
transformer. Three types of transformers that can be used for
captive motor installations include liquid, dry, and cast coil. The
cast-coil transformer is really a special type of dry transformer,
but will be treated as a separate category in this paper.
B. Liquid-Filled Transformers
Liquid-filled transformers have their windings immersed
in mineral oil, a less flammable liquid such as silicone, or an
approved high-fire-point hydrocarbon liquid. This category of
transformer is usually the lowest cost of all three types because
the liquid is a better dielectric and a more efficient heat transfer
medium than either air or epoxy. In the size range of 10005000
kVA, liquid-filled transformers can be constructed with a core
having a rectangular, oval, or round cross section.
The secondary (LV) windings are wound on a winding form
that fits tightly over the core. The secondary windings typically
are sheet wound with one or more layers of paper insulation between each turn. The current distribution in the sheet windings
greatly reduces the magnitude of vertical (axial) forces during a
short circuit. A layer (barrel) winding with conductors of rectangular shape is normally used for the primary (HV) winding. Insulation between layers is provided by one or more thicknesses
of aramid or kraft paper.
The radial short-circuit forces are inward on the LV windings and outward on the HV windings. The LV windings can
be solidly supported from the core so that the inward radial
Fig. 2.
1706
has a gap in the middle of the winding between the top and
bottom sections. If vertical clamping is used, the windings can
be of upset disc or all upwound disc construction. An upset disc
winding is wound from the inside out, but alternate discs are
upset or restacked. This allows the crossovers to go from the
top of one disc to the top of the other disc, and from the bottom
of one to the bottom of the other. An all upwound disc construction can also be used in which the disc sections are wound into
slots cut in glass polyester sheets. An upwound disc is similar
to the upset winding, but alternate discs are not restacked. The
crossover conductor transitions from the top of one disc to the
bottom of the next disc and the winding process continues. Additional insulation must be used for the crossover conductors
due to higher turn voltages.
Fig. 3 is a cross-sectional view of a dry-type transformer with
a disc HV winding and a barrel LV winding showing the axial
and radial component of forces that are exerted during motor
starting.
Primary windings are typically disc wound with aramid paper
as the conductor insulation. After the coils are wound, they are
placed in metal molds, inserted into a vacuum chamber and
filled with a gas-free epoxy mixture. After filling, the molds
are then removed from the casting chamber and placed in a
timetemperature curing oven. After the epoxy is cured, the
coils are removed from the molds and are ready for assembly on
the core. Since the epoxy flows between the discs and has excellent dielectric properties, close disc-to-disc spacing can be utilized which increases the disc-to-disc capacitance and allows for
more uniform distribution of impulse voltages.The radial component tends to push the secondary winding into the core while
driving the primary winding away from the core. Transformer
manufacturers can compensate for radial forces with a system
utilizing wedging sticks, inherent strength of the conductor material, and the winding geometry. Wedging sticks are placed between the secondary windings and the core legs to prevent the
secondary windings from collapsing into the core. The primary
winding is kept in place due to the tension in the winding and
the strength of the conductor material. Circular coil geometry allows for uniform distribution of radial forces in the windings and
reduces the conductor radial movement during short circuits.
Fig. 4 illustrates a force model that can be used to depict the
is proporaxial forces in disc-type windings. The axial force
tional to the square of the ampere turns and inversely proportional to the distance between the discs. The bending moment
Fig. 5.
Impulse model.
is proportional to the axial force times the disc length, and the
deflection of the disc is proportional to the axial force times the
cube of the disc length. During motor starting, the captive transformer will be subjected to locked-rotor currents and forces.
Since air is the dielectric medium in dry-type transformers, the
only support to resist deflection of the disc is the strength of
the disc winding itself. Any increase in disc length will result in
greater deflection of the winding and higher bending moments.
Advantages of the dry-type transformers for captive load
applications include a relatively low cost and environmental
safety. A disadvantage in applications with frequent and
relatively high current pulses is lack of techniques to improve
the mechanical strength, such as compression bonding for
liquid-filled transformers and epoxy encapsulation for cast-coil
transformers. Dry transformers typically are less efficient than
liquid-filled or cast-coil units. The dry-type transformer can
also be adversely affected by environmental contaminants.
D. Cast Coil
The third type of transformer is the cast coil, which is really
a special type of dry-type transformer. The cast-coil technology
was first developed in Europe during the 1950s and later in the
U.S. in the late 1960s. The major difference between cast-coil
technology and that of liquid or dry is that the cast-coil transformer uses an epoxy resin as the major dielectric component
instead of air, mineral oil, or silicone. Epoxy has an excellent dielectric performance of over 3.5 that of air. While epoxy has
excellent dielectric properties, the epoxy has limited mechanical strength when used with no other material. Typically, fiberglass and aramid fiber are combined with epoxy for high me-
1707
Fig. 7.
chanical strength. Secondary windings are usually sheet windings insulated with an epoxy-coated aramid sheet. The inner
and outer surfaces of the cooling ducts are protected from the
environment with a glass-reinforced polyester sheet. After the
secondary coils are wound, they are placed in an oven where
the epoxy between the turns is cured, binding adjacent turns together. The final step is to fill the end caps of the windings with
epoxy, sealing the conductor from the environment.
Fig. 5 illustrates a model of a disc-type winding under an impulse condition. This closer disc spacing provides a higher basic
impulse level (BIL) than with conventional dry transformers.
Typical BIL levels with cast-coil transformers are similar to
those of liquid-filled units.
Cast-coil transformers have several distinct advantages over
dry and liquid-filled transformers. The main advantage of a
cast-coil transformer is that the polyester glass and epoxy
resin provides excellent mechanical strength and eliminates
conductor movement. Fig. 6 shows the typical winding arrangement of the cast-coil transformer.
As Fig. 6 illustrates, both the primary and secondary windings
are completely encapsulated in the epoxy resin. The forces on a
cast-coil transformer winding act as shown previously in Fig. 3.
As with other dry transformers, the radial component tends
to push the secondary winding into the core, while driving the
primary winding away from the core. In addition to using the
strength of the conductor material and winding geometry, the
cast-coil design incorporates the concrete-like epoxyconductor
matrix. Wedging sticks are placed between the secondary windings and the core legs to center the coils on the core legs. The
primary winding is completely embedded in a block of epoxy,
which prevents any winding movement.
Fig. 7 depicts a typical model used for axial forces in cast-coil
disc windings. The simple beam model clearly illustrates the
mechanical advantage of the epoxy support system over other
earlier technologies. Fig. 7 shows that the conductor is fully supported throughout the winding, eliminating any moments and
reinforcing the conductor. The epoxyconductor matrix forms a
physical structure which requires little maintenance and ensures
reliable operation during captive motor starting applications.
The epoxy resin essentially makes the cast-coil transformer
impervious to harsh environments and has no potential adverse
affects on the environment. Thus, it can be used virtually in any
TABLE I
TRANSFORMER COST AND LOSSES
1708
but their standard efficiency is higher than the standard efficiency of liquid units, and higher than the premium-efficiency
dry-type units. In addition, the 80 C rise cast-coil transformer
has a higher short-term overload capability than either dry or
liquid-filled transformers.
F. Proper Transformer Sizing
The transformer size should be selected to be adequate for
the load of the application, the mechanical duty imposed by the
application, and the voltage drop requirements for starting the
motor. In this section, methods to determine the minimum transformer kVA required to handle the load and mechanical duty
imposed on the transformer by high starting currents and pulsating loads are presented.
In addition to the high inrush currents during motor starting,
some captive transformer applications also have periodic high
current pulses that place unusual thermal and mechanical duty
on the transformer. Some examples of these applications include
chippers, reversing hot mills, crop shears, punch presses, car
shredders and fragmentizers, hammer mills, and reciprocating
compressors or pumps.
The equivalent rms load for a typical load cycle of the motor
should be calculated that includes motor starting, steady load,
and pulsating load, if any. The equation for determining the
equivalent rms load is
(2)
where
motor inrush kVA;
steady kVA;
pulse kVA;
time that the kVA is at ;
time that the kVA is at ;
time that the kVA is at .
The maximum kVA rating of the transformer must be at least
as large as the thermal rating calculated by (2).
The forces produced in a transformer by motor starting currents or pulsating loads are the same as those produced by a
full short circuit except for a lower magnitude. The forces produced in the transformer are proportional to the pulse current
squared. Over a period of time, thousands of lower magnitude
short-circuit-type events can damage a transformer. Fig. 8 was
developed to provide guidance in sizing transformers with pulsating-type loads and has been used for many years in sizing
liquid-filled transformers in the 10005000-kVA range for pulsating or short-time loads [1]. It is based on the forced-air cooled
(FA) rating of the transformer, which is 1.15 the base natural
cooled (OA) rating for liquid-filled transformers with base ratings of 2000 kVA or less and 1.25 the base rating for liquidfilled transformers with base ratings of 210010 000 kVA. Most
liquid-filled transformers in the 10005000-kVA range are sold
with either an FA rating or with provisions for a future FA rating.
When a request for quotation is sent to transformer manufacturers, any pulsating-type load that the transformer will experience should be described so that each manufacturer can determine if a design with a higher mechanical strength than the
standard design is required.
Fig. 8.
1709
TABLE II
MOTOR FAILURES AND PROTECTION
1710
TABLE IV
TRANSFORMER FAILURES AND PROTECTION
Fig. 9.
Motor protectiondiagram.
TABLE III
PROTECTIONDEVICE NUMBERS
Fig. 10.
Transformer protectiondiagram.
1711
Fig. 11.
Suggested protection.
1712
Fig. 12.
1713
IV. CONCLUSIONS
A. Transformer Selection and Sizing
Fig. 13.
maximum measurement of 162 A. Clearly, the variation in inrush current between the phases was high enough that the definite-time relay function would not be adequate.
One suggestion was that a window CT around all three conductors would give a more accurate measure for the ground-fault
current, in place of the residual connection. This is due to the
decaying asymmetrical components (X/R was roughly 50) and
the remmanence in the CT cores. It was believed that the transformer starting currents put the existing three CTs in temporary
dc saturation.
The team concluded that the transformer inrush current was
tripping the ground-fault function. Fig. 13 is a coordination diagram of the definite-time ground-fault relay and the upstream
bus protection curve that it must coordinate with. A possible solution was to use the second ground-fault function of the motor
protection relay. This second ground-fault function is normally
used as an alarm, but can be configured as a trip if needed. The
two definite-time ground-fault functions were set to 0.2 s, 122
A, and 9 s, 60 A. Fig. 13 also shows the final settings. These
values were chosen to allow time for the motor to start with the
compressor load, with an estimated duration of 7 s.
One thing learned from this startup is that the flexibility of the
relay allowed the team to set the ground-fault protection at an
acceptable level. An issue is that a transformer protection relay
would have been better to work with the inrush and harmonic
currents. Full protection of this system would require two relays
with the required motor and transformer protection functions, as
discussed above.
1714
Miroslav Ristic (M98) received the B.Sc.E.E. degree from the University of Novi Sad, Novi Sad, Yugoslavia.
He is currently an Applications Consultant with
GE MultiLin, Markham, ON, Canada. Prior to this,
he was an Applications Engineer with GE Large
Motors, where he was involved in applications
with large motors and industrial generators. He was
with the Electric Power System in Yugoslavia for
more than ten years. He has served on the Board of
Electric Power Transmission Network of Yugoslavia
and the Board of Power Stations and Electricity Production of Yugoslavia.
Mr. Ristic is a Licensed Professional Engineer in the Province of Ontario,
Canada.