Documente Academic
Documente Profesional
Documente Cultură
Copyright
This document and parts thereof must not be reproduced or copied without written
permission from ABB, and the contents thereof must not be imparted to a third
party, nor used for any unauthorized purpose.
The software or hardware described in this document is furnished under a license
and may be used, copied, or disclosed only in accordance with the terms of such
license.
Trademarks
ABB and Relion are registered trademarks of the ABB Group. All other brand or
product names mentioned in this document may be trademarks or registered
trademarks of their respective holders.
Warranty
Please inquire about the terms of warranty from your nearest ABB representative.
http://www.abb.com/substationautomation
Disclaimer
The data, examples and diagrams in this manual are included solely for the concept
or product description and are not to be deemed as a statement of guaranteed
properties. All persons responsible for applying the equipment addressed in this
manual must satisfy themselves that each intended application is suitable and
acceptable, including that any applicable safety or other operational requirements
are complied with. In particular, any risks in applications where a system failure and/
or product failure would create a risk for harm to property or persons (including but
not limited to personal injuries or death) shall be the sole responsibility of the
person or entity applying the equipment, and those so responsible are hereby
requested to ensure that all measures are taken to exclude or mitigate such risks.
This document has been carefully checked by ABB but deviations cannot be
completely ruled out. In case any errors are detected, the reader is kindly requested
to notify the manufacturer. Other than under explicit contractual commitments, in
no event shall ABB be responsible or liable for any loss or damage resulting from
the use of this manual or the application of the equipment.
Conformity
This product complies with the directive of the Council of the European
Communities on the approximation of the laws of the Member States relating to
electromagnetic compatibility (EMC Directive 2004/108/EC) and concerning
electrical equipment for use within specified voltage limits (Low-voltage directive
2006/95/EC). This conformity is the result of tests conducted by ABB in
accordance with the product standards EN 50263 and EN 60255-26 for the EMC
directive, and with the product standards EN 60255-1 and EN 60255-27 for the low
voltage directive. The product is designed in accordance with the international
standards of the IEC 60255 series.
Table of contents
Table of contents
Section 1
Introduction.......................................................................5
This manual........................................................................................5
Intended audience..............................................................................5
Product documentation.......................................................................5
Product documentation set............................................................5
Document revision history.............................................................6
Related documentation..................................................................6
Symbols and conventions...................................................................7
Symbols.........................................................................................7
Document conventions..................................................................7
Functions, codes and symbols......................................................8
Section 2
RET630 overview...........................................................13
Overview...........................................................................................13
Product version history................................................................13
PCM600 and IED connectivity package version..........................13
Operation functionality......................................................................14
Product variants...........................................................................14
Optional functions........................................................................14
Physical hardware............................................................................15
Local HMI.........................................................................................16
Display.........................................................................................16
LEDs............................................................................................19
Keypad........................................................................................19
Web HMI...........................................................................................19
Authorization.....................................................................................21
Communication.................................................................................21
Section 3
RET630 variants.............................................................23
Presentation of preconfigurations.....................................................23
Preconfigurations.........................................................................24
Preconfiguration A for two-winding HV/MV transformer...................26
Application...................................................................................26
Functions.....................................................................................29
Input/output signal interfaces.......................................................30
Preprocessing blocks and fixed signals ......................................32
Control functions..........................................................................32
Transformer bay control QCCBAY.........................................32
Apparatus control SCILO, GNRLCSWI, DAXCBR,
DAXSWI.................................................................................32
RET630
Application Manual
Table of contents
Protection functions.....................................................................34
Differential protection for two-winding transformer
TR2PTDF...............................................................................34
Non-directional overcurrent protection PHxPTOC.................35
Negative-sequence overcurrent protection NSPTOC............36
Non-directional earth-fault protection EFxPTOC....................36
Thermal overload protection T2PTTR....................................37
Three-phase overvoltage protection PHPTOV.......................38
Three-phase undervoltage protection PHPTUV.....................39
Circuit-breaker failure protection CCBRBRF..........................40
Tripping logic TRPPTRC........................................................41
Combined operate and start alarm signal..............................41
Other output and alarm signals..............................................42
Supervision functions..................................................................42
Trip circuit supervision TCSSCBR.........................................42
Fuse failure supervision SEQRFUF.......................................42
Circuit-breaker condition monitoring SSCBR.........................43
Measurement and analog recording functions............................43
Binary recording and LED configuration......................................45
Preconfiguration B for two-winding HV/MV transformer,
including numerical REF protection..................................................48
Application...................................................................................48
Functions.....................................................................................50
Input/output signal interfaces.......................................................51
Preprocessing blocks and fixed signals ......................................53
Control functions..........................................................................53
Transformer bay control QCCBAY.........................................53
Apparatus control SCILO, GNRLCSWI, DAXCBR,
DAXSWI.................................................................................53
Protection functions.....................................................................55
Differential protection for two-winding transformer
TR2PTDF...............................................................................55
Stabilized restricted earth-fault protection LREFPNDF..........56
Non-directional overcurrent protection PHxPTOC.................56
Negative-sequence overcurrent protection NSPTOC............57
Non-directional earth-fault protection EFxPTOC....................58
Thermal overload protection T2PTTR....................................59
Three-phase overvoltage protection PHPTOV.......................60
Three-phase undervoltage protection PHPTUV.....................61
Circuit-breaker failure protection CCBRBRF..........................62
Tripping logic TRPPTRC........................................................63
Combined operate and start alarm signal..............................63
Other output and alarm signals..............................................64
Supervision functions..................................................................64
2
RET630
Application Manual
Table of contents
Section 4
Section 5
RET630
Application Manual
Glossary.........................................................................79
Section 1
Introduction
1MRS756786 D
Section 1
Introduction
1.1
This manual
The application manual contains descriptions of preconfigurations. The manual can
be used as a reference for configuring control, protection, measurement, recording
and LED functions. The manual can also be used when creating configurations
according to specific application requirements.
1.2
Intended audience
This manual addresses the protection and control engineer responsible for
planning, pre-engineering and engineering.
The protection and control engineer must be experienced in electrical power
engineering and have knowledge of related technology, such as protection schemes
and principles.
1.3
Product documentation
1.3.1
RET630
Application Manual
Section 1
Introduction
1MRS756786 D
PCM600 project and insert IEDs to the project structure. The manual also
recommends a sequence for engineering of protection and control functions, LHMI
functions as well as communication engineering for IEC 60870-5-103, IEC 61850
and DNP3.
The installation manual contains instructions on how to install the IED. The
manual provides procedures for mechanical and electrical installation. The chapters
are organized in chronological order in which the IED should be installed.
The operation manual contains instructions on how to operate the IED once it has
been commissioned. The manual provides instructions for monitoring, controlling
and setting the IED. The manual also describes how to identify disturbances and
how to view calculated and measured power grid data to determine the cause of a
fault.
The point list manual describes the outlook and properties of the data points
specific to the IED. The manual should be used in conjunction with the
corresponding communication protocol manual.
The technical manual contains application and functionality descriptions and lists
function blocks, logic diagrams, input and output signals, setting parameters and
technical data sorted per function. The manual can be used as a technical reference
during the engineering phase, installation and commissioning phase, and during
normal service.
1.3.2
Product version
History
A/2009-09-15
1.0
First release
B/2009-12-23
1.0
Content updated
C/2011-02-23
1.1
D/2012-08-29
1.2
1.3.3
Related documentation
Name of the document
Document ID
1MRS756789
1MRS756793
1MRS757203
Installation Manual
1MRS755958
RET630
Application Manual
Section 1
Introduction
1MRS756786 D
Document ID
Operation Manual
1MRS756509
Technical Manual
1MRS756508
Engineering Manual
1MRS756800
Commissioning Manual
1MRS756801
1.4
1.4.1
Symbols
The electrical warning icon indicates the presence of a hazard
which could result in electrical shock.
The tip icon indicates advice on, for example, how to design your
project or how to use a certain function.
Although warning hazards are related to personal injury, it is necessary to
understand that under certain operational conditions, operation of damaged
equipment may result in degraded process performance leading to personal injury
or death. Therefore, comply fully with all warning and caution notices.
1.4.2
Document conventions
A particular convention may not be used in this manual.
RET630
Application Manual
Section 1
Introduction
1MRS756786 D
1.4.3
Abbreviations and acronyms in this manual are spelled out in the glossary. The
glossary also contains definitions of important terms.
Push-button navigation in the LHMI menu structure is presented by using the
push-button icons.
and
.
To navigate between the options, use
HMI menu paths are presented in bold.
Select Main menu/Settings.
WHMI menu names are presented in bold.
Click Information in the WHMI menu structure.
LHMI messages are shown in Courier font.
.
To save the changes in non-volatile memory, select Yes and press
Parameter names are shown in italics.
The function can be enabled and disabled with the Operation setting.
The ^ character in front of an input or output signal name in the function block
symbol given for a function, indicates that the user can set an own signal name
in PCM600.
The * character after an input or output signal name in the function block
symbol given for a function, indicates that the signal must be connected to
another function block in the application configuration to achieve a valid
application configuration.
Description
IEC 61850
IEC 60617
ANSI
Protection
Three-phase non-directional
overcurrent protection, low stage
PHLPTOC
3I>
51P-1
Three-phase non-directional
overcurrent protection, high stage
PHHPTOC
3I>>
51P-2
Three-phase non-directional
overcurrent protection, instantaneous
stage
PHIPTOC
3I>>>
50P/51P
DPHLPDOC
3I>
67-1
DPHHPDOC
3I>>
67-2
EFLPTOC
I0>
51N-1
EFHPTOC
I0>>
51N-2
DEFLPDEF
I0>
67N-1
DEFHPDEF
I0>>
67N-2
LREFPNDF
dI0Lo>
87NL
RET630
Application Manual
Section 1
Introduction
1MRS756786 D
Description
High-impedance based restricted earthfault protection
IEC 61850
IEC 60617
ANSI
HREFPDIF
dI0Hi>
87NH
NSPTOC
I2>
46
T2PTTR
3Ith>T/G
49T/G
INRPHAR
3I2f>
68
TR2PTDF
3dI>T
87T
PHPTOV
3U>
59
PHPTUV
3U<
27
Positive-sequence overvoltage
protection
PSPTOV
U1>
47O+
Positive-sequence undervoltage
protection
PSPTUV
U1<
47U+
Negative-sequence overvoltage
protection
NSPTOV
U2>
47O-
ROVPTOV
U0>
59G
DAPFRC
df/dt>
81R
Overfrequency protection
DAPTOF
f>
81O
Underfrequency protection
DAPTUF
f<
81U
Overexcitation protection
OEPVPH
U/f>
24
Three-phase underimpedance
protection
UZPDIS
Z< GT
21GT
CCBRBRF
3I>/I0>BF
51BF/51NBF
Tripping logic
TRPPTRC
IO
94
MAPGAPC
MAP
MAP
Bay control
QCCBAY
CBAY
CBAY
Interlocking interface
SCILO
GNRLCSWI
I O CB/DC
I O CB/DC
Circuit breaker
DAXCBR
I O CB
I O CB
Disconnector
DAXSWI
I O DC
I O DC
LOCREM
R/L
R/L
Synchrocheck
SYNCRSYN
SYNC
25
OLATCC
COLTC
90V
SPC8GGIO
DPGGIO
SPGGIO
MVGGIO
Negative-sequence overcurrent
protection
Control
RET630
Application Manual
Section 1
Introduction
1MRS756786 D
Description
IEC 61850
IEC 60617
ANSI
SLGGIO
VSGGIO
PCGGIO
Event counter
CNTGGIO
SSCBR
CBCM
CBCM
SEQRFUF
FUSEF
60
CCRDIF
MCS 3I
MCS 3I
Trip-circuit supervision
TCSSCBR
TCS
TCM
SPVNZBAT
U<>
U<>
Energy monitoring
EPDMMTR
MVEXP
TPOSSLTC
TPOSM
84M
CMMXU
3I
3I
VPHMMXU
3Upe
3Upe
VPPMMXU
3Upp
3Upp
RESCMMXU
I0
I0
RESVMMXU
U0
U0
PWRMMXU
PQf
PQf
CSMSQI
I1, I2
I1, I2
VSMSQI
U1, U2
V1, V2
A1RADR
ACH1
ACH1
A2RADR
ACH2
ACH2
A3RADR
ACH3
ACH3
A4RADR
ACH4
ACH4
B1RBDR
BCH1
BCH1
B2RBDR
BCH2
BCH2
B3RBDR
BCH3
BCH3
B4RBDR
BCH4
BCH4
Binary receive
GOOSEBINRCV
GOOSEDPRCV
Interlock receive
GOOSEINTLKRCV
Measurement
10
RET630
Application Manual
Section 1
Introduction
1MRS756786 D
Description
RET630
Application Manual
IEC 61850
IEC 60617
ANSI
Integer receive
GOOSEINTRCV
GOOSEMVRCV
GOOSESPRCV
11
12
Section 2
RET630 overview
1MRS756786 D
Section 2
RET630 overview
2.1
Overview
RET630 is a comprehensive transformer management IED for protection, control,
measuring and supervision of power transformers, unit and step-up transformers
including power generator-transformer blocks in utility and industry power
distribution networks. RET630 is a member of ABBs Relion product family and
a part of its 630 series characterized by functional scalability and flexible
configurability. RET630 also features necessary control functions constituting an
ideal solution for transformer bay control and voltage regulation.
The supported communication protocols including IEC 61850 offer seamless
connectivity to various station automation and SCADA systems.
2.1.1
2.1.2
1.0
First release
1.1
1.2
No new functions
Protection and Control IED Manager PCM600 Ver. 2.4 SP1 or later
ABB RET630 Connectivity Package Ver. 1.2 or later
RET630
Application Manual
Product history
Application Configuration
Parameter Setting
Signal Matrix
Signal Monitoring
Disturbance Handling
Event Viewer
Graphical Display Editor
Hardware Configuration
13
Section 2
RET630 overview
1MRS756786 D
IED Users
Communication Management
Configuration Migration
2.2
Operation functionality
2.2.1
Product variants
The IED capabilities can be adjusted by selecting a product variant. The IED
capabilities can be extended by adding HW and/or SW options to the basic variant.
For example, the physical communication connector can be either an electrical or
optical Ethernet connector.
The number of binary inputs and outputs depends on the amount of the optional
BIO modules selected. For a 4U IED, it is possible to take 2 additional BIO
modules at the maximum, and for a 6U IED, it is possible to take 4 additional BIO
modules at the maximum.
2.2.2
Optional functions
Some of the available functions are optional, that is, they are included in the
delivered product only when defined by the order code.
14
RET630
Application Manual
Section 2
RET630 overview
1MRS756786 D
2.3
Physical hardware
The mechanical design of the IED is based on a robust mechanical rack. The HW
design is based on the possibility to adapt the HW module configuration to
different customer applications.
Table 2:
IED contents
Content options
LHMI
Communication and
CPU module
Auxiliary power/binary
output module
8 RTD-inputs (sensor/R/V/mA)
4 outputs (mA)
All external wiring, that is CT and VT connectors, BI/O connectors, power supply
connector and communication connections, can be disconnected from the IED
modules with wiring, for example, in service situations. The CT connectors have a
build-in mechanism which automatically short-circuits CT secondaries when the
connector is disconnected from the IED.
RET630
Application Manual
15
Section 2
RET630 overview
2.4
1MRS756786 D
Local HMI
GUID-3AB0ED40-9988-4C03-839D-C330B6FADD70 V1 EN
Figure 1:
LHMI
Display
Buttons
LED indicators
Communication port
2.4.1
Display
The LHMI includes a graphical monochrome display with a resolution of 320 x
240 pixels. The character size can vary. The amount of characters and rows fitting
the view depends on the character size and the view that is shown.
The display view is divided into four basic areas.
16
RET630
Application Manual
Section 2
RET630 overview
1MRS756786 D
A071258 V2 EN
Figure 2:
Display layout
1 Path
2 Content
3 Status
4 Scroll bar (appears when needed)
The function button panel shows on request what actions are possible with the
function buttons. Each function button has a LED indication that can be used as a
feedback signal for the function button control action. The LED is connected to the
required signal with PCM600.
RET630
Application Manual
17
Section 2
RET630 overview
1MRS756786 D
GUID-6828CE38-2B88-4BB5-8F29-27D2AC27CC18 V1 EN
Figure 3:
The alarm LED panel shows on request the alarm text labels for the alarm LEDs.
GUID-3CBCBC36-EFCE-43A0-9D62-8D88AD6B6287 V1 EN
Figure 4:
The function button and alarm LED panels are not visible at the same time. Each
panel is shown by pressing one of the function buttons or the Multipage button.
Pressing the ESC button clears the panel from the display. Both the panels have
dynamic width that depends on the label string length that the panel contains.
18
RET630
Application Manual
Section 2
RET630 overview
1MRS756786 D
2.4.2
LEDs
The LHMI includes three protection status LEDs above the display: Ready, Start
and Trip.
There are 15 programmable alarm LEDs on the front of the LHMI. Each LED can
indicate three states with the colors: green, yellow and red. The alarm texts related
to each three-color LED are divided into three pages. Altogether, the 15 physical
three-color LEDs can indicate 45 different alarms. The LEDs can be configured
with PCM600 and the operation mode can be selected with the LHMI, WHMI or
PCM600.
2.4.3
Keypad
The LHMI keypad contains push-buttons which are used to navigate in different
views or menus. With the push-buttons you can control objects in the single-line
diagram, for example, circuit breakers or disconnectors The push-buttons are also
used to acknowledge alarms, reset indications, provide help and switch between
local and remote control mode.
The keypad also contains programmable push-buttons that can be configured either
as menu shortcut or control buttons.
GUID-3D031D0A-D1C3-4758-8A22-AC3CEC70B09D V1 EN
Figure 5:
2.5
LHMI keypad with object control, navigation and command pushbuttons and RJ-45 communication port
Web HMI
The WHMI enables the user to access the IED via a web browser. The supported
Web browser version is Internet Explorer 7.0 or later.
RET630
Application Manual
19
Section 2
RET630 overview
1MRS756786 D
The menu tree structure on the WHMI is almost identical to the one on the LHMI.
A071242 V3 EN
Figure 6:
20
Locally by connecting the user's computer to the IED via the front
communication port.
Remotely over LAN/WAN.
RET630
Application Manual
Section 2
RET630 overview
1MRS756786 D
2.6
Authorization
The user categories are predefined for the LHMI and WHMI, each with different
rights.
The IED users can be created, deleted and edited only with PCM600. One user can
belong to one or several user categories.
At delivery, the IED user has full access as SuperUser until users
are created with PCM600. Logging on is not required for the LHMI.
Table 3:
User category
User rights
SystemOperator
ProtectionEngineer
All settings
DesignEngineer
Application configuration
UserAdministrator
2.7
Communication
The IED supports communication protocols IEC 61850-8-1, IEC 60870-5-103 and
DNP3 over TCP/IP.
All operational information and controls are available through these protocols.
However, some communication functionality, for example, horizontal
communication (GOOSE) between the IEDs, is only enabled by the IEC 61850-8-1
communication protocol.
Disturbance files are accessed using the IEC 61850 or IEC 60870-5-103 protocols.
Disturbance files are also available to any Ethernet based application in the
standard COMTRADE format. The IED can send binary signals to other IEDs (so
called horizontal communication) using the IEC 61850-8-1 GOOSE (Generic
Object Oriented Substation Event) profile. Binary GOOSE messaging can, for
example, be employed for protection and interlocking-based protection schemes.
The IED meets the GOOSE performance requirements for tripping applications in
distribution substations, as defined by the IEC 61850 standard. Further, the IED
supports the sending and receiving of analog values using GOOSE messaging.
Analog GOOSE messaging enables fast transfer of analog measurement values
RET630
Application Manual
21
Section 2
RET630 overview
1MRS756786 D
over the station bus, thus facilitating for example sharing of RTD input values,
such as surrounding temperature values, to other IED applications. The IED
interoperates with other IEC 61850 compliant IEDs, tools and systems and
simultaneously reports events to five different clients on the IEC 61850 station bus.
For a system using DNP3 over TCP/IP, events can be sent to four different masters.
For systems using IEC 60870-5-103 IED can be connected to one master in a
station bus with star-topology.
All communication connectors, except for the front port connector, are placed on
integrated communication modules. The IED is connected to Ethernet-based
communication systems via the RJ-45 connector (10/100BASE-TX) or the fibreoptic multimode LC connector (100BASE-FX).
IEC 60870-5-103 is available from optical serial port where it is possible to use
serial glass fibre (ST connector) or serial plastic fibre (snap-in connector).
The IED supports SNTP, DNP3 and IRIG-B time synchronization methods with a
time-stamping resolution of 1 ms.
The IED supports the following time synchronization methods with a timestamping
resolution of 1 ms:
Ethernet communication based:
IRIG-B
22
RET630
Application Manual
Section 3
RET630 variants
1MRS756786 D
Section 3
RET630 variants
3.1
Presentation of preconfigurations
The 630 series IEDs are offered with optional factory-made preconfigurations for
various applications. The preconfigurations contribute to faster commissioning and
less engineering of the IED. The preconfigurations include default functionality
typically needed for a specific application. Each preconfiguration is adaptable
using the Protection and Control IED Manager PCM600. By adapting the
preconfiguration the IED can be configured to suit the particular application.
The adaptation of the preconfiguration may include adding or removing of
protection, control and other functions according to the specific application,
changing of the default parameter settings, configuration of the default alarms and
event recorder settings including the texts shown in the HMI, configuration of the
LEDs and function buttons, and adaptation of the default single-line diagram.
In addition, the adaptation of the preconfiguration always includes communication
engineering to configure the communication according to the functionality of the
IED. The communication engineering is done using the communication
configuration function of PCM600.
If none of the offered preconfigurations fulfill the needs of the
intended area of application, 630 series IEDs can also be ordered
without any preconfiguration. In this case the IED needs to be
configured from the ground up.
The functional diagrams describe the IED's functionality from the protection,
measuring, condition monitoring, disturbance recording, control and interlocking
perspective. Diagrams show the default functionality with simple symbol logics
forming principle diagrams. The external connections to primary devices are also
shown, stating the default connections to measuring transformers. The positive
measuring direction of directional protection functions is towards the low voltage
side.
The functional diagrams are divided into sections which each constitute one
functional entity. The external connections are also divided into sections. Only the
relevant connections for a particular functional entity are presented in each section.
Protection function blocks are part of the functional diagram. They are identified
based on their IEC 61850 name but the IEC based symbol and the ANSI function
number are also included. Some function blocks, such as PHHPTOC, are used
several times in the configuration. To separate the blocks from each other, the IEC
RET630
Application Manual
23
Section 3
RET630 variants
1MRS756786 D
61850 name, IEC symbol and ANSI function number are appended with a running
number, an instance number, from one onwards.
3.1.1
Preconfigurations
Table 4:
Description
Preconfiguration
Table 5:
Functions used in preconfigurations. Column 'n' shows the total number of available
function instances regardless of the preconfiguration selected
Description
Protection
2
2
2
4
RET630
Application Manual
Section 3
RET630 variants
1MRS756786 D
Description
Overfrequency protection
Underfrequency protection
protection1)
protection1)
16
Bay control
Interlocking interface
10
10
Circuit breaker
Disconnector
Synchrocheck
15
64
15
10
10
Event counter
Trip-circuit supervision
Energy monitoring
Overexcitation
Three-phase underimpedance
Control
RET630
Application Manual
25
Section 3
RET630 variants
1MRS756786 D
Description
40
Binary receive
10
32
Interlock receive
59
Integer receive
32
60
64
Measurement
2
3.2
3.2.1
Application
The functionality of the IED is designed to be used for three-phase differential, shortcircuit, overcurrent, earth-fault, thermal overload and negative-phase sequence,
26
RET630
Application Manual
Section 3
RET630 variants
1MRS756786 D
RET630
Application Manual
Control functions
Current protection functions
Voltage protection functions
Supervision functions
Disturbance recorders
LEDs' configuration
Measurement functions
27
Section 3
RET630 variants
1MRS756786 D
3I
3I>
51P-1
3I>>
51P-2
3I>>>
50P
51P
I >
46
3I >T
49T
I0
I0>
51N-1
I0>>
51N-2
3I> / 51BF /
I0>BF 51NBF
3I>
51P-1
3I>>
51P-2
3I>>>
50P
51P
FUSEF
60
I >
46
3U<
27
3I
3U>
59
87T
RET630 (PRECONFIGURATION A)
For two-winding HV/MV transformer
3U
GUID-FD724103-823D-4443-ACAE-412BB7906240 V3 EN
Figure 7:
28
RET630
Application Manual
Section 3
RET630 variants
1MRS756786 D
3.2.2
Functions
Table 6:
Description
IEC 61850
IEC 60617
ANSI
Protection
Three-phase non-directional overcurrent
protection, low stage (LV side)
PHLPTOC
3I>
51P-1
PHLPTOC
3I>
51P-1
PHHPTOC
3I>>
51P-2
PHHPTOC
3I>>
51P-2
PHIPTOC
3I>>>
50P/51P
PHIPTOC
3I>>>
50P/51P
EFLPTOC
I0>
51N-1
EFHPTOC
I0>>
51N-2
NSPTOC
I2>
46
NSPTOC
I2>
46
T2PTTR
3Ith>T/G
49T/G
TR2PTDF
3dI>T
87T
PHPTOV
3U>
59
PHPTUV
3U<
27
CCBRBRF
3I>/I0>BF
51BF/51NBF
TRPPTRC
IO
94
TRPPTRC
IO
94
Bay control
QCCBAY
CBAY
CBAY
Interlocking interface
SCILO
GNRLCSWI
I O CB/DC
I O CB/DC
Circuit breaker
DAXCBR
I O CB
I O CB
Disconnector
DAXSWI
I O DC
I O DC
SSCBR
CBCM
CBCM
SEQRFUF
FUSEF
60
Trip-circuit supervision
TCSSCBR
TCS
TCM
Energy monitoring
EPDMMTR
Control
29
Section 3
RET630 variants
1MRS756786 D
Description
IEC 61850
IEC 60617
ANSI
Measurement
Three-phase current measurement (LV side)
CMMXU
3I
3I
CMMXU
3I
3I
VPHMMXU
3Upe
3Upe
VPPMMXU
3Upp
3Upp
RESCMMXU
I0
I0
PWRMMXU
PQf
PQf
A1RADR
ACH1
ACH1
B1RBDR
BCH1
BCH1
B2RBDR
BCH2
BCH2
B3RBDR
BCH3
BCH3
B4RBDR
BCH4
BCH4
3.2.3
Description
COM
BI1
COM
BI2
COM
BI3
Disconnector 1 closed
COM
BI4
Disconnector 1 open
COM
BI5
COM
BI6
COM
BI7
Disconnector 2 closed
COM
BI8
Disconnector 2 open
COM
BI9
Incoming blocking
COM
BI10
Buchholz alarm
COM
BI11
Buchholz trip
COM
BI12
COM
BI13
COM
BI14
The outputs of the IED are categorized as power outputs (POx) and signal outputs
(SOx). The power outputs can be used for closing and tripping of circuit breakers
and disconnector control. The signal outputs are not heavy-duty outputs. They are
used for alarm or signaling purposes.
30
RET630
Application Manual
Section 3
RET630 variants
1MRS756786 D
Table 8:
Description
PSM
BO1_PO
PSM
BO2_PO
PSM
BO3_PO
PSM
BO4_PO
Disconnector 1 open
PSM
BO5_PO
Disconnector 1 closed
PSM
BO6_PO
Not connected
PSM
BO7_SO
OC operate alarm
PSM
BO8_SO
EF operate alarm
PSM
BO9_SO
Common start
BIO_3
BO1_PO
Disconnector 2 open
BIO_3
BO2_PO
Disconnector 2 closed
BIO_3
BO3_PO
Backup trip
BIO_3
BO4_SO
BIO_3
BO5_SO
Common operate
BIO_3
BO6_SO
External trip
BIO_3
BO7_SO
BIO_3
BO8_SO
BIO_3
BO9_SO
Not connected
The IED measures the analog signals needed for protection and measuring
functions via galvanically isolated matching transformers. The matching
transformer input channels 17 are intended for current measuring and channels
8...10 for voltage measuring.
Table 9:
RET630
Application Manual
Description
AIM_2
CH1
AIM_2
CH2
AIM_2
CH3
AIM_2
CH4
AIM_2
CH5
AIM_2
CH6
AIM_2
CH7
AIM_2
CH8
AIM_2
CH9
AIM_2
CH10
31
Section 3
RET630 variants
3.2.4
1MRS756786 D
3.2.5
Control functions
3.2.5.1
3.2.5.2
32
RET630
Application Manual
Section 3
RET630 variants
1MRS756786 D
which checks for operator place selector before providing the final open or close
signal to DAXCBR function.
The open, closed and undefined states of the circuit breaker are indicated on the
LHMI.
GUID-8A74818A-C7CC-41CF-A8B0-DEB618EA784F V1 EN
Figure 8:
RET630
Application Manual
33
Section 3
RET630 variants
1MRS756786 D
GUID-80EB2D95-6BEA-40CF-84CF-B54AAE610D5B V1 EN
Figure 9:
Disconnector control
3.2.6
Protection functions
3.2.6.1
34
RET630
Application Manual
Section 3
RET630 variants
1MRS756786 D
Harmonic blocking outputs from the second harmonic and waveform are connected
to an OR-gate to form inrush blocking signal which can be used for multiplying
start values of the overcurrent and earth fault protection on the high-voltage side.
The default multiplier setting in overcurrent and earth fault functions is 1.0.
The operate signal from the low and high stages are used to provide a LED
indication on the LHMI. Low stage and high stage operate outputs, along with
second harmonic and wave harmonic inrush blocking signals, are connected to the
disturbance recorder.
3.2.6.2
RET630
Application Manual
35
Section 3
RET630 variants
1MRS756786 D
GUID-803DB1A7-0570-4BEA-877D-B8FF26C70C0B V1 EN
Figure 10:
3.2.6.3
3.2.6.4
36
RET630
Application Manual
Section 3
RET630 variants
1MRS756786 D
the differential protection function can increase the start value of instantaneous earthfault function.
A common operate and start signal from the high-stage and low-stage earth-fault
protection functions are connected to an OR-gate to form a combined nondirectional earth-fault operate and start signal which is used to provide a LED
indication on the LHMI. Also separate start and operate signals from all of these
functions are connected to the disturbance recorder.
3.2.6.5
RET630
Application Manual
37
Section 3
RET630 variants
1MRS756786 D
GUID-ACA16E63-3512-49B8-B05B-FAF22CC0336C V1 EN
Figure 11:
3.2.6.6
38
RET630
Application Manual
Section 3
RET630 variants
1MRS756786 D
Also separate start and operate signals from both instances are connected to the
disturbance recorder.
3.2.6.7
RET630
Application Manual
39
Section 3
RET630 variants
1MRS756786 D
GUID-ECD0828B-94B2-4606-9732-EA020E229180 V1 EN
Figure 12:
3.2.6.8
40
RET630
Application Manual
Section 3
RET630 variants
1MRS756786 D
3.2.6.9
The circuit breaker of the low-voltage side is open on receipt of operate signal from
the protection function or retrip signal. Master tripping signals for high-voltage and
low-voltage circuit breaker are available at binary output PSM PO1 and PSM PO2
respectively.
GUID-31108EFA-5CE9-46FE-9D96-0CB9FFA03FA7 V1 EN
Figure 13:
3.2.6.10
Tripping logic
RET630
Application Manual
41
Section 3
RET630 variants
1MRS756786 D
3.2.6.11
3.2.7
Supervision functions
3.2.7.1
3.2.7.2
42
RET630
Application Manual
Section 3
RET630 variants
1MRS756786 D
3.2.7.3
GUID-39CF8939-91C1-4F5A-B841-DCAAC81B6B03 V2 EN
Figure 14:
3.2.8
RET630
Application Manual
Winding 1
Winding 2
43
Section 3
RET630 variants
1MRS756786 D
Winding 1
Winding 2
The measured quantities can be viewed in the measurement menu on the LHMI.
All analog input channels are connected to the analog disturbance recorder. When
any of these analog values violate the upper or lower threshold limits, the recorder
unit is triggered which in turn will record all the signals connected to the recorder.
Table 10:
Channel ID
Channel 1
Channel 2
Channel 3
Channel 4
Channel 5
Channel 6
Channel 7
Channel 8
Channel 9
Channel 10
44
RET630
Application Manual
Section 3
RET630 variants
1MRS756786 D
GUID-B035E4A0-A836-4325-95E6-62ACD8C242B8 V1 EN
Figure 15:
3.2.9
Channel 1
Channel 2
Channel 3
Channel 4
Channel 5
Channel 6
Channel 7
Channel 8
Channel 9
45
Section 3
RET630 variants
1MRS756786 D
Channel ID
Description
Channel 10
Channel 11
Channel 12
Channel 13
Channel 14
Channel 15
Channel 16
Channel 17
Channel 18
Channel 19
Channel 20
Channel 21
Channel 22
Channel 23
Channel 24
Channel 25
Channel 26
Channel 27
Channel 28
Channel 29
Channel 30
Channel 31
Channel 32
Channel 33
Channel 34
Channel 35
Channel 36
Channel 37
Channel 38
Channel 39
Channel 40
Channel 41
Channel 42
Channel 43
Channel 44
Channel 45
Channel 46
Channel 47
Channel 48
46
RET630
Application Manual
Section 3
RET630 variants
1MRS756786 D
Channel ID
Description
Channel 49
Channel 50
Channel 51
Buchholz alarm
Channel 52
Buchholz trip
Channel 53
RET630
Application Manual
Description
LED 1
Red
LED 2
Red
LED 3
Yellow
LED 3
Red
LED 4
Yellow
LED 4
Red
LED 5
Yellow
LED 5
Red
LED 6
Yellow
LED 6
Red
LED 7
Yellow
LED 7
Red
LED 8
Yellow
LED 8
Red
LED 9
Yellow
LED 9
Red
LED 10
Yellow
LED 10
Red
LED 11
Red
Supervision alarms
LED 12
Red
External trip
LED 13
Red
47
Section 3
RET630 variants
1MRS756786 D
3.3
3.3.1
Application
The functionality of the IED is designed to be used for three-phase differential, shortcircuit, overcurrent, earth-fault, thermal overload and negative-phase sequence,
overvoltage and undervoltage protection in power transformer feeders with
transformer of type YNyn.
The apparatuses controlled by the IED are the high voltage-side circuit breaker and
disconnectors. The earth switch is considered to be operated manually. The open,
close and undefined states of the circuit breaker, disconnectors, and earth switch
are indicated on the LHMI.
Required interlocking is configured in the IED.
The preconfiguration includes:
48
Control functions
Current protection functions
Voltage protection functions
Supervision functions
Disturbance recorders
LEDs' configuration
Measurement functions
RET630
Application Manual
Section 3
RET630 variants
1MRS756786 D
3I
3I>
51P-1
3I>>
51P-2
3I>>>
50P
51P
87NL
I >
46
3I >T
49T
I0>
51N-1
I0>>
51N-2
3I>
51P-1
I0
3I> / 51BF /
I0>BF 51NBF
1
87T
3I>>
51P-2
I >
46
3I>>>
50P
51P
87NL
I0>
51N-1
I0>>
51N-2
59
3U<
27
1
I0
3I
0
3U>
RET630 (PRECONFIGURATION B)
For two-winding HV/MV transformer
3U
GUID-2825EF67-84B7-4039-B34E-8A0BA237AE1E V3 EN
Figure 16:
RET630
Application Manual
49
Section 3
RET630 variants
3.3.2
1MRS756786 D
Functions
Table 13:
Description
IEC 61850
IEC 60617
ANSI
Protection
Three-phase non-directional overcurrent
protection, low stage (LV side)
PHLPTOC
3I>
51P-1
PHLPTOC
3I>
51P-1
PHHPTOC
3I>>
51P-2
PHHPTOC
3I>>
51P-2
PHIPTOC
3I>>>
50P/51P
PHIPTOC
3I>>>
50P/51P
EFLPTOC
I0>
51N-1
EFLPTOC
I0>
51N-1
EFHPTOC
I0>>
51N-2
EFHPTOC
I0>>
51N-2
LREFPNDF
dI0Lo>
87NL
LREFPNDF
dI0Lo>
87NL
NSPTOC
I2>
46
NSPTOC
I2>
46
T2PTTR
3Ith>T/G
49T/G
TR2PTDF
3dI>T
87T
PHPTOV
3U>
59
PHPTUV
3U<
27
CCBRBRF
3I>/I0>BF
51BF/51NBF
TRPPTRC
IO
94
TRPPTRC
IO
94
Bay control
QCCBAY
CBAY
CBAY
Interlocking interface
SCILO
GNRLCSWI
I O CB/DC
I O CB/DC
Control
RET630
Application Manual
Section 3
RET630 variants
1MRS756786 D
Description
IEC 61850
IEC 60617
Circuit breaker
DAXCBR
I O CB
ANSI
I O CB
Disconnector
DAXSWI
I O DC
I O DC
SSCBR
CBCM
CBCM
Trip-circuit supervision
TCSSCBR
TCS
TCM
Energy monitoring
EPDMMTR
CMMXU
3I
3I
CMMXU
3I
3I
VPHMMXU
3Upe
3Upe
VPPMMXU
3Upp
3Upp
RESCMMXU
I0
I0
PWRMMXU
PQf
PQf
A1RADR
ACH1
ACH1
B1RBDR
BCH1
BCH1
B2RBDR
BCH2
BCH2
B3RBDR
BCH3
BCH3
B4RBDR
BCH4
BCH4
Measurement
3.3.3
RET630
Application Manual
Description
COM
BI1
COM
BI2
COM
BI3
Disconnector 1 closed
COM
BI4
Disconnector 1 open
COM
BI5
COM
BI6
COM
BI7
Disconnector 2 closed
COM
BI8
Disconnector 2 open
COM
BI9
Incoming blocking
COM
BI10
Buchholz alarm
COM
BI11
Buchholz trip
COM
BI12
COM
BI13
COM
BI14
51
Section 3
RET630 variants
1MRS756786 D
The outputs of the IED are categorized as power outputs (POx) and signal outputs
(SOx). The power outputs can be used for closing and tripping of circuit breakers
and disconnector control. The signal outputs are not heavy-duty outputs. They are
used for alarm or signaling purposes.
Table 15:
Description
PSM
BO1_PO
PSM
BO2_PO
PSM
BO3_PO
PSM
BO4_PO
Disconnector 1 open
PSM
BO5_PO
Disconnector 1 closed
PSM
BO6_PO
Not connected
PSM
BO7_SO
OC operate alarm
PSM
BO8_SO
PSM
BO9_SO
Common start
BIO_3
BO1_PO
Disconnector 2 open
BIO_3
BO2_PO
Disconnector 2 closed
BIO_3
BO3_PO
Backup trip
BIO_3
BO4_SO
BIO_3
BO5_SO
Common operate
BIO_3
BO6_SO
External trip
BIO_3
BO7_SO
BIO_3
BO8_SO
BIO_3
BO9_SO
Not connected
The IED measures the analog signals needed for protection and measuring
functions via galvanically isolated matching transformers. The matching
transformer input channels 18 are intended for current measuring and channels
9...10 for voltage measuring.
Table 16:
Description
AIM_2
CH1
AIM_2
CH2
AIM_2
CH3
AIM_2
CH4
AIM_2
CH5
AIM_2
CH6
AIM_2
CH7
52
RET630
Application Manual
Section 3
RET630 variants
1MRS756786 D
3.3.4
Description
AIM_2
CH8
AIM_2
CH9
AIM_2
CH10
3.3.5
Control functions
3.3.5.1
3.3.5.2
RET630
Application Manual
53
Section 3
RET630 variants
1MRS756786 D
limit. Closing of the circuit breaker is always prevented if the gas pressure inside
the circuit breaker is below the lockout limit. In case the disconnectors are closed,
it is required that the earth switch is open before the circuit breaker closes.
SCILO function checks for the interlocking conditions and provides closing and
opening enable signals. The enable signal is used by GNRLCSWI function block
which checks for operator place selector before providing the final open or close
signal to DAXCBR function.
The open, closed and undefined states of the circuit breaker are indicated on the
LHMI.
GUID-8A74818A-C7CC-41CF-A8B0-DEB618EA784F V1 EN
Figure 17:
54
RET630
Application Manual
Section 3
RET630 variants
1MRS756786 D
GUID-80EB2D95-6BEA-40CF-84CF-B54AAE610D5B V1 EN
Figure 18:
Disconnector control
3.3.6
Protection functions
3.3.6.1
RET630
Application Manual
55
Section 3
RET630 variants
1MRS756786 D
Harmonic blocking outputs from the second harmonic and waveform are connected
to an OR-gate to form inrush blocking signal which can be used for multiplying
start values of the overcurrent and earth fault protection on the high-voltage side.
The default multiplier setting in overcurrent and earth fault functions is 1.0.
The operate signal from the low and high stages are used to provide a LED
indication on the LHMI. Low stage and high stage operate outputs, along with
second harmonic and wave harmonic inrush blocking signals, are connected to the
disturbance recorder.
3.3.6.2
3.3.6.3
56
RET630
Application Manual
Section 3
RET630 variants
1MRS756786 D
GUID-75AF723C-41B1-442C-A0F9-94E0B37D309A V1 EN
Figure 19:
3.3.6.4
RET630
Application Manual
57
Section 3
RET630 variants
1MRS756786 D
A common operate and start signal from both NSPTOC functions are connected to
an OR-gate to form a combined negative-sequence overcurrent operate and start
signal which is used to provide a LED indication on the LHMI. Also separate start
and operate signals from the NSPTOC function is connected to the disturbance
recorder.
3.3.6.5
58
RET630
Application Manual
Section 3
RET630 variants
1MRS756786 D
GUID-B70C44A9-BF39-4453-B147-C3D0AB870C6A V1 EN
Figure 20:
3.3.6.6
RET630
Application Manual
59
Section 3
RET630 variants
1MRS756786 D
GUID-32941305-FEDA-4A0A-BBED-6B57FC183CC2 V1 EN
Figure 21:
3.3.6.7
60
RET630
Application Manual
Section 3
RET630 variants
1MRS756786 D
3.3.6.8
RET630
Application Manual
61
Section 3
RET630 variants
1MRS756786 D
GUID-ECD0828B-94B2-4606-9732-EA020E229180 V1 EN
Figure 22:
3.3.6.9
62
RET630
Application Manual
Section 3
RET630 variants
1MRS756786 D
3.3.6.10
The circuit breaker of the low-voltage side is open on receipt of operate signal from
the protection function or retrip signal. Master tripping signals for high-voltage and
low-voltage circuit breaker are available at binary output PSM PO1 and PSM PO2
respectively.
GUID-31108EFA-5CE9-46FE-9D96-0CB9FFA03FA7 V1 EN
Figure 23:
3.3.6.11
Tripping logic
RET630
Application Manual
63
Section 3
RET630 variants
1MRS756786 D
3.3.6.12
3.3.7
Supervision functions
3.3.7.1
3.3.7.2
64
RET630
Application Manual
Section 3
RET630 variants
1MRS756786 D
GUID-7F0BAF73-D94F-4423-BC59-D953DE7673FB V2 EN
Figure 24:
3.3.8
Winding 1
Winding 2
Winding 1
Winding 2
The measured quantities can be viewed in the measurement menu on the LHMI.
All analog input channels are connected to the analog disturbance recorder. When
any of these analog values violate the upper or lower threshold limits, the recorder
unit is triggered which in turn will record all the signals connected to the recorder.
Table 17:
Channel ID
Channel 1
Channel 2
Channel 3
Channel 4
Channel 5
65
Section 3
RET630 variants
1MRS756786 D
Channel ID
Description
Channel 6
Channel 7
Channel 8
Channel 9
Channel 10
GUID-D51C84DD-66A0-4C67-A825-96EFDAD013C4 V1 EN
Figure 25:
3.3.9
66
RET630
Application Manual
Section 3
RET630 variants
1MRS756786 D
Table 18:
Channel ID
Channel 1
Channel 2
Channel 3
Channel 4
Channel 5
Channel 6
Channel 7
Channel 8
Channel 9
Channel 10
Channel 11
Channel 12
Channel 13
Channel 14
Channel 15
Channel 16
Channel 17
Channel 18
Channel 19
Channel 20
Channel 21
Channel 22
Channel 23
Channel 24
Channel 25
Channel 26
Channel 27
Channel 28
Channel 29
Channel 30
Channel 31
Channel 32
Channel 33
Channel 34
Channel 35
Channel 36
Channel 37
Channel 38
RET630
Application Manual
67
Section 3
RET630 variants
1MRS756786 D
Channel ID
Description
Channel 39
Channel 40
Channel 41
Channel 42
Channel 43
Channel 44
Channel 45
Channel 46
Channel 47
Channel 48
Channel 49
Circuit breaker maintenance alarm: accumulated energy exceeds the set limit
Channel 50
Channel 51
Channel 52
Channel 53
Channel 54
Channel 55
Channel 56
Circuit breaker maintenance alarm: number of operations exceeds the set limit
Channel 57
Channel 58
Buchholz alarm
Channel 59
Buchholz trip
Channel 60
Description
LED 1
Red
LED 2
Red
LED 3
Yellow
LED 3
Red
LED 4
Yellow
LED 4
Red
LED 5
Yellow
LED 5
Red
LED 6
Yellow
LED 6
Red
LED 7
Yellow
LED 7
Red
68
RET630
Application Manual
Section 3
RET630 variants
1MRS756786 D
LED No
RET630
Application Manual
LED color
Description
LED 8
Yellow
LED 8
Red
LED 9
Yellow
LED 9
Red
LED 10
Yellow
LED 10
Red
LED 11
Yellow
LED 11
Red
LED 12
Yellow
LED 12
Red
LED 13
Red
Supervision alarms
LED 14
Red
External trip
LED 15
Red
69
70
Section 4
Requirements for measurement transformers
1MRS756786 D
Section 4
4.1
Current transformers
4.1.1
4.1.1.1
Composite error at
rated accuracy limit
primary current (%)
5P
60
1.8
10P
10
The accuracy classes 5P and 10P are both suitable for non-directional overcurrent
protection. The 5P class provides a better accuracy. This should be noted also if
there are accuracy requirements for the metering functions (current metering,
power metering, and so on) of the IED.
RET630
Application Manual
71
Section 4
Requirements for measurement transformers
1MRS756786 D
The CT accuracy primary limit current describes the highest fault current
magnitude at which the CT fulfils the specified accuracy. Beyond this level, the
secondary current of the CT is distorted and it might have severe effects on the
performance of the protection IED.
In practise, the actual accuracy limit factor (Fa) differs from the rated accuracy
limit factor (Fn) and is proportional to the ratio of the rated CT burden and the
actual CT burden.
The actual accuracy limit factor is calculated using the formula:
Fa Fn
Sin + Sn
Sin + S
A071141 V1 EN
4.1.1.2
Fn
Sin
72
RET630
Application Manual
1MRS756786 D
Section 4
Requirements for measurement transformers
The factor 0.7 takes into account the protection IED inaccuracy, current
transformer errors, and imperfections of the short circuit calculations.
The adequate performance of the CT should be checked when the setting of the
high set stage overcurrent protection is defined. The operate time delay caused by
the CT saturation is typically small enough when the overcurrent setting is
noticeably lower than Fa.
When defining the setting values for the low set stages, the saturation of the CT
does not need to be taken into account and the start current setting is simply
according to the formula.
4.1.1.3
RET630
Application Manual
73
Section 4
Requirements for measurement transformers
1MRS756786 D
A071142 V1 EN
Figure 26:
The maximum three-phase fault current is 41.7 kA and the minimum three-phase
short circuit current is 22.8 kA. The actual accuracy limit factor of the CT is
calculated to be 59.
The start current setting for low-set stage (3I>) is selected to be about twice the
nominal current of the cable. The operate time is selected so that it is selective with
the next IED (not visible in the figure above). The settings for the high-set stage
and instantaneous stage are defined also so that grading is ensured with the
downstream protection. In addition, the start current settings have to be defined so
that the IED operates with the minimum fault current and it does not operate with
the maximum load current. The settings for all three stages are as in the figure above.
For the application point of view, the suitable setting for instantaneous stage (I>>>)
in this example is 3 500 A (5.83 x I2n). For the CT characteristics point of view, the
criteria given by the current transformer selection formula is fulfilled and also the
IED setting is considerably below the Fa. In this application, the CT rated burden
could have been selected much lower than 10 VA for economical reasons.
4.1.2
74
RET630
Application Manual
Section 4
Requirements for measurement transformers
1MRS756786 D
The approximate value of the accuracy limit factor Fa corresponding to the actual
current transformer burden can be calculated on the basis of the rated accuracy
limit factor Fn at the rated burden, the rated burden Sn, the internal burden Sinand
the actual burden Sa of the current transformer.
Fa = Fn
Sin + Sn
Sin + Sa
GUID-26DEE538-9E1A-49A2-9C97-F69BD44591C9 V2 EN
(Equation 1)
Fa
The approximate value of the accuracy limit factor (ALF) corresponding to the actual CT burden
Fn
The rated accuracy limit factor at the rated burden of the current transformer
Sn
Example 1
The rated burden Sn of the current transformer 5P20 is 10 VA, the secondary rated
current is 5A, the internal resistance Rin= 0.07 and the accuracy limit factor Fn
corresponding to the rated burden is 20 (5P20). Thus the internal burden of the
current transformer is Sin= (5A)2 * 0.07 = 1.75 VA. The input impedance of the
IED at a rated current of 5A is < 20 m. If the measurement conductors have a
resistance of 0.113 , the actual burden of the current transformer is Sa=(5A)2 *
(0.113 + 0.020) = 3.33 VA. Thus the accuracy limit factor Fa corresponding to
the actual burden is approximately 46.
The CT burden can grow considerably at the rated current 5A. The actual burden of
the current transformer decreases at the rated current of 1A while the repeatability
simultaneously improves.
At faults occurring in the protected area, the currents may be very high compared
to the rated currents of the current transformers. Due to the instantaneous stage of
the differential function block, it is sufficient that the current transformers are
capable of repeating the current required for instantaneous tripping during the first
cycle.
Thus the current transformers usually are able to reproduce the asymmetric fault
current without saturating within the next 10 ms after the occurrence of the fault to
secure that the operate times of the IED comply with the retardation time.
The accuracy limit factors corresponding to the actual burden of the phase current
transformer to be used in differential protection fulfill the requirement.
Fa > K r Ikmax (Tdc (1 eTm /Tdc ) + 1)
GUID-DA861DAD-C40E-4A82-8973-BBAFD15279C0 V1 EN
RET630
Application Manual
(Equation 2)
75
Section 4
Requirements for measurement transformers
1MRS756786 D
Ikmax The maximum through-going fault current (in p.u.) at which the protection is not allowed to operate
Tdc
Tm
The time-to-saturate, that is, the duration of the saturation free transformation
Kr
The remanence factor 1/(1-r), where r is the maximum remanence flux in p.u. from saturation flux
The accuracy limit factors corresponding to the actual burden of the phase current
transformer is used in differential protection.
The parameter r is the maximum remanence flux density in the CT core in p.u.
from saturation flux density. The value of the parameter r depends on the magnetic
material used and on the construction of the CT. For instance, if the value of r =
0.4, the remanence flux density can be 40 percent of the saturation flux density.
The manufacturer of the CT has to be contacted when an accurate value for the
parameter r is needed. The value r = 0.4 is recommended to be used when an
accurate value is not available.
The required minimum time-to-saturate Tm in TR2PTDF is half fundamental cycle
period (10 ms when fn = 50Hz).
Two typical cases are considered for the determination of the sufficient accuracy
limit factor (Fa):
1.
100 ms
100 Hz
Tm
10 ms
Kr
76
RET630
Application Manual
Section 4
Requirements for measurement transformers
1MRS756786 D
2.
50 ms
100 Hz
Tm
10 ms
Kr
1/(1-0.4) = 1.6667
When the values are substituted in the equation, the result is:
Fa > K r Ikmax 0.9 (Tdc (1 eTm / Tdc ) + 1) 40
GUID-9B859B2D-AC40-4278-8A99-3475442D7C67 V1 EN
Example 2
Assuming that the actions according to alternative two above are taken in order to
improve the actual accuracy limit factor:
Fa =
IrCT
* Fn
IrTR
GUID-31A3C436-4E17-40AE-A4EA-D2BD6B72034E V1 EN
(Equation 3)
RET630
Application Manual
77
Section 4
Requirements for measurement transformers
Fa
1MRS756786 D
(IrCT / IrTR) * Fn (actual accuracy limit factor due to oversizing the CT) = (1500/1000) * 30 = 45
In TR2PTDF, it is important that the accuracy limit factors Fa of the phase current
transformers at both sides correspond with each other, that is, the burdens of the
current transformers on both sides are to be as equal as possible. If high inrush or
start currents with high DC components pass through the protected object when it
is connected to the network, special attention is required for the performance and
the burdens of the current transformers and for the settings of the function block.
78
RET630
Application Manual
Section 5
Glossary
1MRS756786 D
Section 5
Glossary
100BASE-FX
ANSI
BI/O
Binary input/output
BIO
COMTRADE
CPU
CT
Current transformer
DNP3
EMC
Electromagnetic compatibility
Ethernet
GOOSE
HMI
Human-machine interface
HW
Hardware
IDMT
IEC
RET630
Application Manual
IEC 61850
IEC 61850-8-1
IED
IRIG-B
LAN
LC
LED
Light-emitting diode
79
Section 5
Glossary
80
1MRS756786 D
LHMI
PCM600
RET630
RJ-45
RMS
Root-mean-square (value)
RTD
SNTP
SW
Software
TCP/IP
TCS
Trip-circuit supervision
VT
Voltage transformer
WAN
WHMI
RET630
Application Manual
81
ABB Oy
Medium Voltage Products,
Distribution Automation
P.O. Box 699
FI-65101 VAASA, Finland
Phone
+358 10 22 11
Fax
+358 10 22 41094
www.abb.com/substationautomation
Contact us