Generator G1
X0
X1
X2
0.05
0.3
0.2
Generator G2
0.03
0.25
0.15
Line 1
0.70
0.3
0.3
Line 2
0.70
0.3
0.3
Transformer T1
0.12
0.12
0.12
Transformer T2
0.1
0.1
0.1
6) Draw the equivalent circuit for line to line fault when fault occurs through impedance Z f
on line a & b. Line c is healthy.
7) A 3 phase, 10 MVA, 11 kV generator with a solidly earthed neutral point supplies a
feeder the relevant impedances of generator and feeders in ohms are
Generator: X0= j0.4, X1= j1.2, X2= j0.9
Feeder: X0= j3.0, X1= j1.0, X2= j1.0
If a line to ground fault occurs on the far end of feeder, calculate i) the magnitude of
current, ii) line to neutral voltage at generator terminal.
8) A double line to ground fault occurs on phases b & c, at pt. P in the circuit whose single
line diagram is shown below. Determine sub transient current in all phases of machine 1
and voltages at fault pt. Neglect prefault current. Assume that machine 1 is alternator and
machine 2 is synchronous motor operating rated voltage. Both the machines are rated
1.25 MVA, 600 V with reactances X"= X 2= 8%, X0= 4%. Each 3 phase transformer is
rated 1.25 MVA, 600 V delta/4160 V star with leakage reactance of 5%. The reactances
of transmission line are, X1=X2= 12%, X0= 40% on a base of 1.25 MVA, 600 V.