PCS-9691E
Overcurrent Relay
Functions
Protection
Three-stage phase overcurrent protection. (50/51P)
Three-stage neutral overcurrent protection. (50/51G)
Three-stage negative sequence overcurrent protection. (51Q)
Directional ground time overcurrent protection. (67G)
Breaker failure protection. (51BF)
Thermal overload protection. (49)
75
Control
10 configurable binary inputs
7 binary outputs for DC voltage (including 4 configurable
contacts), 9 binary outputs for AC voltage (including 6
configurable contacts)
8 LEDs, including 4 configurable LEDs
Local/remote opening/closing logic of breaker
Faceplate buttons for local control of breaker
76
Features
O n t h e p r e m i s e o f 3 2 s a m p l e s p e r c y c l e , a l l d a ta
measurement, calculation and logic discrimination could be
done within one sampling period. The event recording and
protection logic calculation are completed simultaneously.
Definite time and inverse time of phase overcurrent
protection are both provided.
Definite time and inverse time of zero sequence overcurrent
protection are both provided.
This relay constantly measures and calculates analog
quantities for metering including phase current and zero
sequence current.
This relay is equipped with two EIA RS-485 standardized
electrical interfaces for uplink communication.
This relay can communication with SAS or RTU, the
communication protocol of this device is IEC60870-5-103,
Modbus or DNP3.0.
Event recording function: 32 latest fault reports (up to 8
records in a report), 64 alarm records and 256 records of
time tagged sequence of event can be recorded.
Perfect fault and disturbance recording function: 3 latest fault
waves. the fault and disturbance file format is COMTRADE.
This device can store settings, history reports and fault
waves in a 2Mbit FRAM, which means the information will
not be lost even if the power supply is switched off.