Model LHS4800
Consolidated Alarm
Management Software
CAMS for HIS

General
Specications
GS 33Q02N03-31E

GENERAL

Consolidated Alarm Management Software (hereinafter called CAMS for HIS) is optional software which operates on
HIS of CENTUM CS 3000 (hereinafter called CS 3000). It acquires various kinds of alarms and events in real-time
which occur in CS 3000 system and other systems connected to CS 3000. Those alarms and events are notied
to an operator with identiers (e.g., purposes, user name, allowed time for response and alarm priority) used for
sorting and value-added information (e.g., cause of alarms and how to handle them). Operators sort by identiers
a wide variety of alarms and events used at plants, using CAMS for HIS ltering and sort functions, so that they
can receive only information they need in the most suitable timing. As a result, operators are able to perform safer,
more efcient operation.
This package offers environment in which engineering can be done in accordance with EEMUA No.191 (a guideline
concerning engineering, management and procurement of alarm system, issued by EEMUA).

FUNCTIONS

CAMS for HIS deliver optimal alarm to the right person at the right time. CAMS for HIS representative functions are
shown in the following:

Acquire a Wide Variety of Alarms and Events


It acquires alarms and events generated by CS 3000 as well as the systems connected to CS 3000, and integrate
them on HIS.
Systems that can be integrated
System

How to acquire alarms and events

CENTUM CS 3000
ProSafe-RS
CENTUM CS 1000
CENTUM CS
CENTUM-XL
XL
PRM
STARDOM

Via control bus

Via OPC A&E server

Dene Alarms and Events Attribute


For acquired alarms and events, it additionally denes value-added information including each attribute used for
message ltering and sorting (e.g., purposes, alarm priority and allowed time for response), cause of alarms and
countermeasures as new attributes.

Suppress Unnecessary Alarms and Events Issuance


It is a function to suppress unnecessary alarm and event issuance. Suppressed alarms and events here are not
displayed on CAMS for HIS message monitor (CAMS for HIS window). There are two control functions as follows:
Grouping
It consolidates associated alarms into an alarm group. The user denes the conditions for grouping alarms.
Suppression
A function to suppress unnecessary alarms all at once which are generated during plant equipment maintenance
and changeover. Operators can suppress the alarms according to the pre-dened alarm groups.

Yokogawa Electric Corporation


2-9-32, Nakacho, Musashino-shi, Tokyo, 180-8750 Japan
Tel.: 81-422-52-5634 Fax.: 81-422-52-8902

GS 33Q02N03-31E
Copyright Oct. 27, 2006(YK)
8th Edition Jun. 1, 2009(YK)

<<Contents>> <<Index>>

Supervise Alarm and Event Messages

Test (EEMUA No.191 Compliant)

By using CAMS for HIS, operators can integrate


process alarms, system alarms and operation guide
messages, which used to be supervised on different
windows, on one window (CAMS for HIS message
monitor). In order to enable operators to monitor only
necessary information for themselves in the most
suitable timing out of a great variety of alarms and
events given out from plants, CAMS for HIS Message
Monitor has the following functions:
Filtering
A function to lter (narrow down) displayed/monitored
messages by each attribute (user name, plant
hierarchy title, purpose alarm priority, etc.) included
in messages. Each lter is displayed in tree-view
on CAMS for HIS Message Monitor. Depending on
operators service, various sorts of lters are dened
in advance and registered on the window. It is
possible to create a new lter online by combining
already registered lters and to register it additionally
on the window.
Sorting
A function to sort messages to be displayed/
monitored by each attribute (time of occurrence,
allowed time for response, alarm priority, etc.)
included in messages.
Eclipsing
A function to fold and display a number of alarm
messages given out from one same tag in the most
important alarm message. It is effective to limit the
display of repeated alarms (HI alarm chattering, etc.)
and less important alarms (HI alarms during HH
alarm issuance, etc.).
Shelving
A function to move messages with low monitoring
priority to another folder to shelve them temporarily
or for a certain period of time. By specifying the
shelving time, it is possible to clear repeated alarms
out of main A&E Message Pane collectively.
Load Shedding
A function to automatically activate ltering specied
beforehand to prevent oods of alarms and events
in order to reduce operators monitoring load and
to prevent overlook of important alarms and false
operation, in case a number of alarms and events
happen to be given out in a short period of time.

A function to give out virtual alarms and events to test


if an alarm system is designed properly or not. It is
possible to use past alarm and event messages saved
by CAMS for HIS in addition to using CS 3000 test
function.

All Rights Reserved. Copyright 2006, Yokogawa Electric Corporation

Alarm and Event Historian Saving


A function to save alarm and event as a historical le
for a certain period of time including attributes added
by CAMS for HIS. CAMS for HIS operation history
including suppression, shelving, conrmation and
manual recovery is also saved as event messages.

Congurator
A function to dene detailed information regarding each
alarm and event given out.
There is a function to automatically specify
recommended value for alarm detection and
priority from alarm attributes such as purpose and
consequence.
There is also a function of performance report to verify
if alarm is correctly dened.

Real-Time Alarm Monitor


It displays the number of alarms, events and the
recovered during a certain period of time (1H, 8H, 24H)
on CAMS for HIS Message Monitor.

GS 33Q02N03-31E Oct. 27, 2006-00

<<Contents>> <<Index>>

SYSTEM CONFIGURATION USING CAMS FOR HIS

An example of system conguration using CAMS for HIS is shown below.


CAMS for HIS, connected to OPC A&E server, manages messages given out not only from CENTUM but also from
STARDOM and PRM.
Alarms and events can be equalized among more than one HIS in which CAMS for HIS is installed. It is possible to
specify the range of HIS where alarms and events are equalized. In specied HIS, every alarm and event including
alarms via OPC is equalized.
There is only one download master for CAMS for HIS Congurator. Database is equalized and managed by
Download Master. Only HIS as download master can start CAMS for HIS Congurator.
HIS

Information which requires equalization


among CAMS for HIS is equalized via open bus.
CAMS
for HIS

Download Master
HIS

HIS

DB
CAMS
for HIS
Configurator

CAMS
for HIS

CAMS
for HIS
DB

DB
Subject to
equalization

Open bus
Control bus
A&E

A&E

Messages from CS 3000 are broadcast


simultaneously to every STN by control bus.
SCS

FCS

PRM OPC Server

OPC Server

Messages from OPC server is


noticed to specific CAMS for
HIS via open bus.

STARDOM
FCN/FCJ
F01E.ai

Figure System Conguration of CAMS for HIS

CAMS FOR HIS SPECIFICATION

CAMS for HIS major specications are shown below:


Number of HIS: Maximum 100 units/project
Number of alarms stored:
Maximum 2000
Disc capacity for historical data: 20GB
(Possible to save for approx. two months on the premise of 4 alarms given out per second)

All Rights Reserved. Copyright 2006, Yokogawa Electric Corporation

GS 33Q02N03-31E Feb. 4, 2008-00

<<Contents>> <<Index>>

HIS OPERATION WITH EFFECTIVE


CAMS FOR HIS

When CAMS for HIS function is made effective after


CAMS for HIS installation, CAMS for HIS is run. After
software installation, the functions can be switched
from effective to ineffective and vice versa.
In effective CAMS for HIS, windows related to alarms
and events are aggregated into alarm management
window (CAMS for HIS Message Monitor). The
following is the difference from ineffective CAMS for
HIS.

Operation to Call Various Message


Windows
When a process alarm window, system alarm window
and operation guide window shown below is called,
CAMS for HIS Message Monitor is always called.
Call from System Message Window
When a call button for process alarm window,
system alarm window and operation guide window
is pressed, CAMS for HIS Message Monitor is called
with lters for each alarm and event selected.
Call from Operation Keyboard
Window Call from Function Key
Call by Direct Specication of Window
Parameter specication such as window size and
position specication shall be ineffective.

System Message Window


In the latest alarm display eld, only one latest system
alarm and process alarm which is not conrmed on
CAMS for HIS Message Monitor window is displayed.
In pull-down display, the latest ve alarms are
displayed.
When an alarm is issued, a button to call a window for
issued alarm conrmation is ashing.

Instrument Faceplate, Tuning Window


Tag mark is displayed in a way to reect relevant tags
alarm status displayed on CAMS for HIS Message
Monitor.

REQUIREMENTS
Hardware Requirements
CPU:

Pentium 1GHz or more, Pentium 4


2.8GHz or more recommended
Main Memory: 256MB or more, 512MB or more
recommended
HDD:
4GB or more space area, 20GB or more
space area recommended

Software Requirements
OS:

Windows XP SP3
Windows Server 2003 Standard Edition
SP1
Windows Server 2003 Standard Edition
SP2
Windows Server 2003 R2 Standard
Edition
Windows Server 2003 R2 Standard
Edition SP2
Windows 2000 SP4
.Net Framework: Version 2.0 (*1)
WSH:
Version 5.6 (*1)
MSXML: Version 6 (*1)
CS 3000: R3.08.10 or later version Standard
Operation and Monitoring Function
(LHS1100 or LHM1101)
*1:

included in software media (LHSKM02).

The Consolidated Alarm Management Software


(CAMS for HIS) and the Advanced Alarm Filter
Package should not be installed in the same PC.

MODELS AND SUFFIX


Model

LHS4800
-S

Sufx
Codes

-C
1
1

Description
Consolidated Alarm Management
Software
[Media Model: LHSKM02-C11]
Basic software license
Multiple software licenses
(for 2 or more)
Always 1
English Version

Graphic Window
It is displayed in a way to reect relevant tags alarm
status displayed on CAMS for HIS Message Monitor
when graphic modier condition supports alarms.

ORDERING INFORMATION

Operation Keyboard LED

TRADEMARKS

It ashes during alarm issuance.

Message Printing
When an alarm is issued, every message is printed
out regardless of CAMS for HIS Message Monitor
operation.

All Rights Reserved. Copyright 2006, Yokogawa Electric Corporation


Subject to change without notice.

Specify model and sufx codes for ordering.

CENTUM and ProSafe are registered trademarks of


Yokogawa Electric Corporation.
STARDOM is a trademark of Yokogawa Electric
Corporation.
PRM is a registered trademark of Yokogawa Electric
Corporation in the United States and Japan.
Microsoft, Windows 2000, Windows Server 2003 and
Windows XP are registered trademarks of Microsoft
Corporation in the United States and/or other
countries.
Pentium is a registered trademark of Intel
Corporation.
Other product and company names appearing in this
document are trademarks or registered trademarks of
their respective holders.

GS 33Q02N03-31E

Jun. 1, 2009-00