IT Cooling
IT Cooling 2015/2016
start here
G_ITC_RCW8.4_1015_GB
RC Group is a Company of
Technical data and dimensions are not binding. RC GROUP S.p.A. reserves the right for changes and / or modifications without notice.
English
rcgroupairconditioning
rcgroupairconditioning
Index
IT Cooling
INTRODUCTION
Certifications
References
Company profile
Production plants
Web & Social media
Legenda
Products selection
RC Group Software
RC Group for IT Cooling
Highlights
NEW GO GREEN Solutions
.......................................................................................................................................... 5
.......................................................................................................................................... 6
.......................................................................................................................................... 7
.......................................................................................................................................... 9
........................................................................................................................................ 10
........................................................................................................................................ 11
........................................................................................................................................ 12
.............................................................................................................................. 20
.............................................................................................................................. 21
.............................................................................................................................. 27
.............................................................................................................................. 30
compressors ...................................161
compressors - HFO1234ze ..............167
compressors ...................................171
compressors - HFO1234ze ..............175
DRY COOLERS
DRY COOLER
DRY COOLER PF
SELECTION SOFTWARE
RC WORLD
SPECTRUM
SPECTRUM tutorial
f i f t y c o o l y e a r s
G_CHL_RCW8.4
G_ITC_RCW8.4 RCGROUP SpA 19632013 fiftycoolyears
Certifications
ISO 9001:2008 CERTIFICATION
For production plants of Valle Salimbene (PV) and Zeccone (PV) Italy
RC GROUP S.p.A. has been the first European company in HVAC field to get
the ISO 9001 certification in 1991: all the processes are certified to assure
products and services in compliance with the corporate policy.
P.E.D. CERTIFICATION
For production plants of Valle Salimbene (PV) and Zeccone (PV) Italy
RC GROUP S.p.A. products meet the requirements of module H category II
and III of the European directive 97 / 23CE and subsequent modifications for
pressure equipment.
CE MARKING
For production plants of Valle Salimbene (PV) and Zeccone (PV) Italy
The Liquid Chillers and the Air Conditioners produced by RC GROUP S.p.A.
are in compliance with the European Directives 2006 / 42CE, 2006 / 95CE,
2004 / 108CE, 97 / 23CE and subsequent modifications.
EUROVENT CERTIFICATION
For production plants of Valle Salimbene (PV) and Zeccone (PV) Italy
RC GROUP S.p.A. participated in the EUROVENT certification program for
LCP and HP (Liquid Chilling Packages and Heat Pumps).
References
Senato
della Repubblica
Istat
EEC Ardenne Atrium
European Parliament
Bruxelles
McDonalds
GRUPPO BANCARIO
Credito
Valtellinese
Logos, Trade Marks and Companies Name are property of respective Owners
6
Company Profile
TIME
SATISFACTION
Only a short time later RC Group opens a new universe with a wide range of
refrigeration, heat pump and multifunction units able to satisfy every possible
demand for comfort and to satisfy several industrial cooling processes.
Since 2011, RC Group has joined DeLclima SpA, the holding company of De
Longhi group, mainly devoted to the production and sale of air conditioning
equipment.
www.del-clima.com
www.rcgroup.it
TAILOR-MADE SOLUTIONS
All the design, production and test procedures are in accordance with ISO
9001 norms. In the respect of the environmental protection RC Group is
certified in accordance with ISO14001 norms.
Company Profile
TECHNOLOGICAL EVOLUTION
SPACE
IT cooling
Chillers
Artificial Intelligence
IT cooling
Precision air conditioners designed for data centers, telephone exchanges, shelters.
Chillers
Liquid chillers for food, textile, pharmaceutical and electronic big industries.
Heat pumps & Multifunction
Multifunction liquid chillers and heat pumps suitable for installation in supermarkets and business centers, banks, public offices, airports, hospitals.
Artificial Intelligence
Advanced software tools for units selection, energy efficiency calculation, networking and remote monitoring.
Since over fifty years, RC Group supplies reliable and flexible solutions and it is today considered the market leading company in precision air conditioning and
refrigeration with high-tech content.
8
Production plants
RC GROUP - VALLE SALIMBENE
valle salimbene
valle salimbene
RC GROUP - ZECCONE
zeccone
foshan
f i f t y c o o l y e a r s
1963
1970
1980
2013
10
RC GROUP WEB
http://www.rcgroup.it/EN/
http://www.youtube.com/user/RCGroupSpA1
http://www.linkedin.com/company/rc-group
Legenda
Symbols used
in the catalogue.
REFRIGERANT CHARGE
HFO 1234 ZE
NEW PRODUCT
RANGE EXTENSION
NEW SOFTWARE
A CLASS, A+ CLASS ENERGY EFFICIENCY
NEWSOFTWARE
ACLASS
A+
CHILLED WATER
FEEDING
FREE-COOLING SYSTEM
CLASS
Only cooling
Only heating
NOODP
XCOILS
MICRO
CHANNEL
PLATE
SHELL
FLOODED
Cooling/Heating
Domestic hot water
EC
AC
EC
AC
INVERTER
OIL
FREE
R410A
R134a
R407C
1234ze
CHILLED
WATER
Free-cooling system
FREE
COOLING
UP
FLOW
DOWN
FLOW
DISPLA
CEMENT
FRONT
FLOW
Close loop
CLOSE
LOOP
Indoor installation
Outdoor installation
Split-system machine
SPLIT
SYSTEM
Touch screen
TOUCH
SCREEN
11
INVERTER
NEW
NEW
NEW
INVERTER
CHILLEDWATER
CHILLEDWATER
NEXT EVO CW S
Under/Over versions
NEXT EVO CW K
Under/Over versions
series
50
NEW
X TYPE
100
kW
150
52
7
102
NEW
NEXT EVO CW S
NEW
NEXT EVO CW K
NEW
NEW
NEW
NEXT EVO DX
NEW
119
138
15
125
102
42
55
20
14
COOLROW DX Inv
COOLROW CW
40
50
kW
50
61
100
150
INVERTER
12
CHILLEDWATER
COOLSIDE EVO CW
in row/in rack versions
NEW
NEW
NEW
NEW
XCOILS
CHILLEDWATER
NEWSOFTWARE
CHILLEDWATER
CHILLEDWATER
NEXT EVO DX
Under/Over versions
X TYPE
Under version
200
150
250
300
main features
EC
DOWN
FLOW
INVERTER
R410A
INVERTER
R410A
CHILLED
WATER
EC
UP
FLOW
DOWN
FLOW
CHILLED
WATER
EC
UP
FLOW
DOWN
FLOW
CHILLED
WATER
EC
DOWN
FLOW
CHILLED
WATER
EC
DOWN
FLOW
CHILLED
WATER
182
172
225
279
152
R410A
CHILLED
WATER
CHILLED
WATER
150
200
250
EC
EC
UP
FLOW
DOWN
FLOW
EC
UP
FLOW
DOWN
FLOW
UP
FLOW
DOWN
FLOW
AC
INVERTER
R410A
EC
FRONT
FLOW
CLOSED
LOOP
INVERTER
R410A
EC
FRONT
FLOW
EC
EC
FRONT
FLOW
CLOSED
LOOP
FRONT
FLOW
300
INVERTER
CHILLEDWATER
COOLROW DX Inv
in row version
COOLROW CW
in row version
13
NEXT DW
Under/Over versions
NEXT MTR
Over version
NEXT DL
Displacement air delivery version
series
0
kW
50
108
NEXT DW
NEXT MTR
NEXT DL
8
0
100
15
14
R410A
R407c
52
kW
50
R410A
EC
AC
EC
UP
FLOW
CHILLED
WATER
EC
UP
FLOW
DOWN
FLOW
DISPLA
CEMENT
100
TEAM MATE
12,1 307,0 kW
Air cooled condensers equipped
with axial fans.
main features
DRY COOLERS
TEAM MATE PF
12,1 154,0 kW
Air cooled condensers equipped
with plug fans.
DRY COOLER
8,3 172,0 kW
Dry coolers equipped with axial
fans.
DRY COOLER PF
8,8 89,0 kW
Dry coolers equipped with plug
fans.
UPS48VDC
UPS48VDC
UPS48VDC
UPS48VDC
FREECOOLING
FREECOOLING
FREECOOLING
FREECOOLING
ENERGY SPLIT
Horizontal or vertical air flow
MINIPAC
Horizontal air delivery
ENERTEL
Under/Over versions
ENERTEL DL
Displacement air delivery
series
0
kW
10
ENERGY SPLIT
MINIPAC
19
ENERTEL DL
6
MARK
0
main features
15
ENERTEL
20
kW
R407c
SPLIT
SYSTEM
FREE
COOLING
UPS
48VDC
R407c
FREE
COOLING
FRONT
FLOW
UPS
48VDC
15
R407c
R134a
FREE
COOLING
UP
FLOW
DOWN
FLOW
15
R407c
R134a
FREE
COOLING
DISPLA
CEMENT
UPS
48VDC
INVERTER
10
R410A
FREE
COOLING
FRONT
FLOW
FRONT
FLOW
UPS
48VDC
20
INVERTER
UPS48VDC
FREECOOLING
MARK
Horizontal air delivery
Packaged air conditioners with
free-cooling system for outdoor or
indoor installation.
15
FREECOOLING
FREECOOLING
MAXIMO
EAGLE FREE
series
MAXIMO
250
kW
22
197
331
69
47
194
314
308
319
323
402
NEW
358
402
750
299
19
EAGLE FREE
500
350
21
18
277
176
kW
250
500
750
AIR COOLED LIQUID CHILLERS WITH FREE-COOLING SYSTEM WITH PLUG FAN
FREECOOLING
MAXIMO PF
Air cooled liquid chillers with
free-cooling system equipped with
scroll compressors and plug fan.
16
FREECOOLING
HIGHEFFICIENCY
FREECOOLING
GLIDER EVO FREE
800
1000
1250
main features
R410A
FREE
COOLING
1343
R134a
938
1583
1548
1300
800
1000
1250
PLATE
AC
AC
FREE
COOLING
SHELL
INVERTER
OIL
FREE
R134a
INVERTER
OIL
FREE
1234ze
R410A
FREE
COOLING
PLATE
CLASS
1180
R410A
EC
CLASS
1180
PLATE
SHELL
R134a
1370
FREE
COOLING
CLASS
AC
FREE
COOLING
AC
AC
FLOODED
MICRO
FREE
CHANNEL COOLING
FLOODED
MICRO
FREE
CHANNEL COOLING
EC
mechanical cooling
free cooling
AIR COOLED LIQUID CHILLERS WITH FREE-COOLING SYSTEM WITH AXIAL FANS
AND CENTRIFUGAL OIL-FREE COMPRESSORS
NEW
INVERTER
INVERTER
HIGHEFFICIENCY
HIGHEFFICIENCY
LOWGWP
FREECOOLING
FREECOOLING
HFO1234ze
LOWNOISE
LOWNOISE
Air cooled liquid chillers in A-class energy efficiency equipped with oil-free
centrifugal compressors with magnetic levitation bearings, flooded evaporator
and microchannel condensing coils.
Air cooled liquid chillers in A-class energy efficiency equipped with oil-free
centrifugal compressors with magnetic levitation bearings, flooded evaporator
and microchannel condensing coils.
17
NEW
INVERTER
INVERTER
LOWGWP
LOWNOISE
LOWNOISE
HFO1234ze
HIGHEFFICIENCY
HIGHEFFICIENCY
UNICO TURBO FL
Air cooled liquid chillers in A-class energy efficiency equipped with oil-free
centrifugal compressors with magnetic levitation bearings, flooded evaporator
and microchannel condensing coils.
Air cooled liquid chillers in A-class energy efficiency equipped with oil-free
centrifugal compressors with magnetic levitation bearings, flooded evaporator
and microchannel condensing coils.
series
500
1000
260
280
FRIGO TURBO FL
NEW
1000
280
UNICO TURBO FL
NEW
500
250
270,0
kW
INVERTER
NEW
INVERTER
HIGHEFFICIENCY
LOWGWP
HIGHEFFICIENCY
LOWNOISE
HFO1234ze
LOWNOISE
FRIGO TURBO FL
Water cooled liquid chillers equipped with A-class energy efficiency equipped
with oil-free centrifugal compressors with magnetic levitation bearings
and flooded evaporator.
18
main features
1000
1500
1900
1500
1300
INVERTER
OIL
FREE
R134a
INVERTER
OIL
FREE
1234ze
INVERTER
OIL
FREE
R134a
FLOODED
INVERTER
OIL
FREE
1234ze
FLOODED
INVERTER
OIL
FREE
CLASS
1840
CLASS
1240
1000
CLASS
CLASS
1500
R134a
AC
AC
FLOODED
MICRO
CHANNEL
FLOODED
MICRO
CHANNEL
PLATE
cooling
heat recovery
1900
INVERTER
LOWNOISE
FRIGO TURBO K
Water cooled liquid chillers equipped
with oil-free centrifugal compressor
with magnetic levitation bearings and
plate type heat exchanger.
19
RC Group software
SOFTWARE
RCWORLD
RCSPECTRUM
RC WORLD
SPECTRUM
COOLNET
SEQUENCER
COOLNET
SEQUENCER
RC CLOUD
PLATFORM
RC CLOUD PLATFORM
Performance and quality remote monitoring.
GPRS solution for unattended monitoring.
20
for
THE PRECISION AIR CONDITIONINGS MAIN APPLICATION:
DATA CENTER
Data Center represents the precision air conditioning s main and most
widespread application. In the latest years we witnessed the increase of data
processing and the resulting growth in dimensions and energy consumption.
The current financial and economical heavy crisis started at the beginning of
the XXI century has dramatically highlighted the issue of energy efficiencies
and environmental sustainability. The current Data Center managers showed
great awareness towards this matter and transmitted their needs to suppliers.
The message has been acknowledged by the whole industry: the precision air
conditioning has been able to provide the most suitable answers to the needs
of systems with increasingly higher energy efficiency coming from designers
and current Data Center managers.
These pages has the aim to inform about and update the technology state of
the art, to furnish details on the methods, the indexes and the institutions of
classification and certification and to provide a view of RC Groups products
series and systems for the current high efficiency Data Center.
TECHNOLOGY STATE OF THE ART
From the beginning of the XXI century, industry has provided air conditioning
systems and liquid chillers manufacturers with a new generation of
components which take full advantage of electronics and the new heat
exchange technologies to maximize energy efficiency.
Nowadays all air conditioning systems by RC Group for Data Center
extensively use these components; in detail:
As for air conditioning, it means to grant a constant cooling air temperature for
the equipment (cold aisle temperature), supply air temperature, ranging from
20C and 24C, and to accept a return air temperature to the a/c unit (hot
aisle temperature) often at 35C if not higher.
The machine selection has to be done firstly considering the needed air flow,
and once identified the cabinet size suitable for such air flow, it is possible to
proceed with the evaluation using RC World selection software.
I
INVERTER
NEXT EVO CW
Under Version
COOLROW DX Inv
in row version
The high efficiency achieved by current RC Group air conditioning systems
allows to apply them in the latest Data Center that require:
cooling capacity control on supply air temperature;
uniform load distribution on all machines (load sharing).
All these machines are equipped with the new control system with
microprocessor MP.COM whose main features are:
Cooling capacity control on supply air temperature set point;
Fans speed control on return air temperature or underfloor pressure set
point;
Dew-point calculation on heat Exchange coil;
Serial management of main components.
21
Energy savings achieved are significant, as the schemes below clearly show.
RC Group has developed COOL NET software for the creation of an
intelligent NET that optimizes the LOAD SHARING, maximizing the energy
savings.
Example for a plant with nr. 4 NEXT EVO CW 128 E8 4R units for chilled
water feeding equipped with EC plug fans (cooling capacity 106kW each):
Infrastructure
Total Power
Power
Switch
UPS
Battery backup
IT Systems
Servers
IT Systems Memory
Equipment
Power
Cooling
Chillers
CRAC
TRADITIONAL
PUE
3.0
2.5
2.0
1.5
1.2
100%
Stand-by
LOAD SHARING
DCiE
33%
40%
50%
67%
83%
Efficiency level
Very low
Low
Medium
High
Very high
Cooling systems represent over 40% of the data center energy consumption
and they have an incisive impact on the efficiency level of the data center.
Energy consumption
Chiller 33%
Humidifiers 3%
Close Control Air Conditioners 9%
IT Systems 30%
PDU 5%
UPS 18%
Switches/generator 1%
Lighting 1%
75%
Air flow: 16.500 m3/h
Fans power input:
1,62kW x 4 = 6,48kW x 8.760 h/y = 56.764 kWh/y
Load sharing allows an high energy savings even increasing with the
increasing of the parzialization.
22
Uptime Institute has tested and keeps on developing several innovations that
have then become standards in the Data Center:
hot / cold aisle layout;
energy calculation parameters;
cost analysis models;
double power input specifications;
TIER classification for reliability evaluation.
TIER I: Data Center with single distribution line/network, respectively one for
Power and one for Cooling; no redundant component.
Availability: 99,671% (8731.18 h/year of uninterrupted operation; down time:
28.82 h/year).
TIER II: Data Center with single distribution line/network, respectively one for
Power, one for Cooling; redundant components make possible maintenance
during operation. Availability: 99.741 % (8737.31 h/year of uninterrupted
operation; down time: 28,69 h/year).
TIER CLASSIFICATION
Functional and design features of the data center infrastructure are uniquely
defined by TIER classification, developed by Uptime Institute and it is
nowadays an international standard.
Uptime Institute, founded in 1993, has been a pioneer in creating and
promoting a final users community and they made available their own
knowledge in order to improve reliability and the 24h availability in the data
center and in IT organizations.
TIER III: Data Center with multiple distribution line/network, respectively for
Power and Cooling and only one is active; redundant components make
possible maintenance during operation. Availability: 99.982 % (8758.42 h/year
of uninterrupted operation; down time: 1.58 h/year).
TIER IV: Data Center with multiple distribution line/network respectively
for Power and cooling, all active with redundant components. Possibility of
maintenance during operation and fault tolerance. All cooling systems, chillers
e HVAC, have double power supply. Availability: 99.995 % (8759.56 h/year of
uninterrupted operation: down time: 0.44 h/year).
CLASS
TIER I
TIER II
TIER III
TIER IV
N+1=needed +1 active
component in addition to those
required to support the IT load,
1 redundant component.
N+1=needed +1 component
in addition to those required
to support the IT load, 1
redundant component.
Single network/system
No
Yes
Yes
No
No
No
Yes
Partitioning
No
No
No
Yes
Continuous cooling
Yes (A Class)
Availability
99,671% (8.731.18 h / year of 99,741% (8.737.31 h / year of 99,982% (8.758.42 h / year of 99,995% (8.759.56 h / year of
operation without interruptions) operation without interruptions) operation without interruptions) operation without interruptions)
Stop time
28.82 h/year
28.69 h/year
1.58 h/year
0.44 h/year
23
TECHNICAL SYNERGY
RC Group proposes itself as the sole supplier by offering both air
conditioning units and liquid chillers.
This offers the opportunity to reduce at minimum the time designated by the
customers for the units selection, avoiding cross-searches within various
direct or indirect manufacturers. Furthermore this characteristic offers the
possibility to have an accurate energy analysis for what concerns the energy
consumption of the selected system and the relative obtainable energy
savings.
PACKAGED LIQUID CHILLERS
These units are characterized by a complete set of components that reduce
installation times and cost. Main switch with door lock safety, electric motor
thermal protection, refrigerant charge
and LAN connection are supplied as
standard.
NEXT EVO CW
Under Version
PACKAGED FREE-COOLING
LIQUID CHILLERS
These units have the same
characteristics of the packaged liquid
UNICO TURBO FL FREE
chillers but are characterized by an
integrated free-cooling system that includes the heat exchanger coils,
the free-cooling valve and the relative pipes connection. This solution allows
for high floor space savings and for reduction of the hydraulic plant realization
cost.
A CLASS ENERGY EFFICIENCY
All chillers shown are available in A class energy efficiency with EER up to
3,60 in mechanical working conditions. Furthermore, the control software of
these units, developed by RC Group, are designed to maximize the energy
savings and to manage the chiller/air conditioner system according to the
current temperature control standards for these technological ambients.
Liquid chillers:
- With very high energy efficiency:
UNICO TURBO FL series (280 1500 kW) in A class energy
efficiency, equipped with EC
axial fans (option), oil free
centrifugal compressors with
magnetic levitation bearings,
shell and tube type flooded
evaporator and microchannel
condensing coils.
UNICO TURBO FL
- With free-cooling section:
UNICO TURBO FL FREE series (402 1548 kW) in
A class energy efficiency, with EC axial fans (option), oil free
centrifugal compressors with magnetic levitation bearings, shell and
tube type flooded evaporator, microchannel condensing coil and
Cu/Al condensing coils.
GLIDER EVO FREE series (288
1339 kW) equipped with EC
axial fans (option) and screw
compressors with modulating
capacity control, dry expansion
shell and tube evaporator,
condensing and free-cooling coil
contained in single coil Cu/Al;
GLIDER EVO FREE
GLIDER EVO FREE CLA series
(319 1579 kW) with the same characteristics of the GLIDER EVO
FREE series, but in A class energy efficiency.
Energy analysis is needed to choose the most suitable chiller.
SPECTRUM, RC Group energy performance estimation software for chillers
is available for this purpose.
24
DX 10
MCAI 10
MULTI SPLIT
DX 10
DX 10
DX 10
MCAI 40
One of the main features of NEXT EVO INV series is the high energy
efficiency both at design conditions and at partial load conditions that are
variable during the year.
The units are equipped with inverter driven scroll compressors granting a
proportional control on supplied cooling power, while the fans are matched to
EC brushless type electric motors with built-in electronic commutation system.
These motors grant high performances with minimum energy consumption
and total absence of electromagnetic noise.
Additional energy savings can be reach with an air return plenum with Free
cooling damper for direct free-cooling (option).
25
Despite a wide standard products series for models numbers and multifunctions features, not all Users needs can be satisfied. In these cases RC
Group, with its high skilled team, is willing to implement changes on current
products or to manufacture ad hoc products for a particular installation.
CONSULTANTS
DISTRIBUTOR
MARK
Air conditioner for
telecommunication
CUSTOMERS
INFORMATION
Many ad hoc requests have then been developed and now they are included
in machine standard equipment.
The taylor-made service, available for chillers and air conditioners, has
represented RC Group trump card in taking projects of large Data Centers of
important International Banks, TLC Operators, cloud computing owners .
Most of installations need the use of a limited number of close control air
conditioning, so all current RC Group series can be used.
The direct expansion solution is the most suitable, if we consider heat load
to be dissipated, but the incidental availability of chilled water used for other
rooms with higher heat load makes convenient the installation of chilled water
air precision conditioning. This is the case of power/UPS/battery/trafo rooms
of large Data Centers using the same CHW close control air conditioners
widely installed in Data Halls.
Another interesting opportunity belongs to seasonal availability of chilled
water for summer air conditioning in the offices; in this case the best solution
is represented by direct expansion machines with one additional coil (extracircuit EC) fed by chilled water from chiller and not needed for offices.
Conditioner will use chilled water coil in hot season; compressors is stand-by
and it works if needed and when chiller stops. Also in all of these cases, a
pay-back time evaluation is necessary.
26
Highlights
ELECTRONIC EXPANSION VALVES
The electronic expansion valves have many benefits. They grant a higher
energy efficiency combined with a better stability of the system.
IT COOLING
I
INVERTER
FEATURES
Capacity modulation
FEATURES
Precision control
Bi-directional flow
BENEFITS
Energy saving
AC motor
EC motor
(%) 100
Engaged power
80
60
40
20
0
0
20
40
60
80
100 (% RPM)
EC MOTORS FEATURES
No electromagnetic noise
27
Highlights
PLUG FANS FEATURES
FREE COOLING
FREECOOLING
BENEFITS
According to the set-point and the energy saving logic the controller activates
a more affordable free-cooling system.
AVAILABLE VERSIONS
RC Group air conditioners are available in Over, Under and Displacement
versions
UP-FLOW AIR DELIVERY (OVER)
The air distribution goes from the top of the unit directly in to the room.
The air flow in each area is predetermined during the design stage and it is
not dependent on the actual state of the load to be dissipated.
The system is normally applied in Comfort plants and in those plants having a
defined low/medium room thermal loads density.
DOWN-FLOW AIR DELIVERY (UNDER)
The air distribution goes from the bottom through the plenum between the
building floor and the raised floor.
This solution is usually applied in Hi-Tech room air conditioning and it is most
favourable when load is uniformly distributed in all the areas of the room.
DISPLACEMENT AIR DELIVERY (DL)
The air-conditioning system with displacement air delivery is based on the
principle that the air is distributed at a very low speed, while enabling a
cooling effect by convection.
Every electronic equipment will absorb the amount of cold required to
maintain a correct temperature level inside, through a natural convection
effect. The greater is the load inside the electronic equipment, the greater is
this effect.
Therefore, every electronic equipment uses only the amount required to
dissipate its own thermal load, which is generated by maximising the result
and the energy efficiency of the system.
FEATURES
The direct free cooling system consists in the direct entry of the outside
air into the room, if the outside air has a lower temperature than indoor
air.
BENEFITS
Energy saving.
28
Highlights
AN EFFICIENT ENERGY USE
One of the most important characteristics of TURBO FL chillers is their high
energy efficiency and consequently high ESEER values, both at design and at
the various operating conditions experienced during the year.
The diagram compare the EER curves of TURBO FL with centrifugal
compressors vs. screw compressors.
The considerable improvement of the centrifugal unit under all load conditions
is well illustrated.
The following charts have been prepared in accordance with EUROVENT
standards. Therefore, the air and water temperatures specified by these
standards have been considered at partial load.
Water cooled liquid chiller
7,5
12,0
7,0
UNICO TURBO FL
6,0
5,5
5,0
4,5
4,0
10,0
9,0
8,0
7,0
6,0
SCREW CHILLER
3,5
5,0
3,0
4,0
25%
50%
FRIGO TURBO FL
11,0
EER [kW/kW]
EER [kW/kW]
6,5
75%
Cooling Load
100%
SCREW CHILLER
25%
50%
75%
100%
Cooling Load
INVERTER
RELIABILITY
With their reliable operation the TURBO FL series is well suited for every
application from comfort cooling, through the high-tech industrial sector
and especially mission critical strategic applications (like hospitals, clean
rooms, web farms, data centres, telecommunication exchanges,
air-traffic control centres).
Their operating reliability is guaranteed 24 hours/day for 365 days/year.
FLOODED EVAPORATOR
The TURBO FL liquid chillers are equipped with flooded evaporator, where
the refrigerant in the evaporation
phase is outside of the tube bundle.
This heat exchange solution allows
to obtain a greater energy efficiency
of the system because it reduces the
differential between the refrigerant
expansion temperature and the
liquid cooled temperature.
Moreover the circulation of the liquid inside the tubes of the heat exchanger
can be varied considerably in relation to the cooling load, reducing the energy
engaged by the pumping system.
A CLASS ENERGY EFFICIENCY
The best and most accurate components applied to the chillers grants high
energy efficiency with EER higher than 3,1 for air cooled units and even
higher than 5,05 for water cooled units.
This values satisfy the Eurovent conditions to join the energy efficiency A
class.
HIGHEFFICIENCY ACLASS
GLYCOLFREE
LOWNOISE
PUMPING GROUPS
RC Group propose a complete sets of
optional accessories for chilled water
pumping.
To satisfy different plant needs are available
pumping groups with one, two, three pumps
with low, medium and high discharge heads.
29
GO GREEN solutions
GOGREEN
solutions
RELIABLE
The Artificial Intelligence of RC Group goes green with SPECTRUM, software
able to turn a simple technical selection in a projection into the future, by
allowing the choice of the most environmentally friendly and more economical
solution. Thanks to RC Cloud Platform, the most modern form of remote
control, the product reliability is always guaranteed.
ECOLOGIC
The focus on the latest regulations in the field of environmental sustainability
and energy saving, led RC Group to adopt refrigerants with low environmental
impact, making its products, as well as efficient, even friends of the
environment.
GOGREEN
solutions
THE EFFICIENT ENERGY USE
Today, environmental respect is the core value and guideline to develop new
technologies.
The environmental sustainability makes its appearance in every sector
through research techniques for the renewal of the resources of our planet
Earth. Mankind has the duty to defend and preserve the delicate balance of
the Earth.
Sustainability for RC Group is the commitment of the present generations
to leave to future generations the same quantity and quality of resources
especially.
Since 1997 (from the Kyoto Protocol) to today, the first aspect is the reduction
of global warming, gradually limiting the use of HCFC refrigerants and, later,
of F gases as well..
The high efficiency of the products together with the study and design of
tailored solution, translate into energy savings, and consequently in cost
reduction.
RC Group solutions arise from synergies between RC Group hardware and
software, through analysis and energy management.
Calculating it in advance and carefully, drive us to system design compatible
with requirements and environment.
At the same time, we can also determine which will be the return of the initial
investment in terms of economies of exercise..
It is thanks to his experience that RC Group has been able to integrate and
merge the design excellence that distinguishes it for years, with the needs of
the environment.
The result is a series of solutions arising from the study on efficient energy
use:
GOGREEN
solutions
RC GROUP products and solutions for the high efficiency air conditioning
for Data Center, Telephone exchangers, Server Farm and in all applications
where are required affability of operation, continuous operation and high
energy efficiency.
30
EVOLVED
Always in step with the continuous and rapid technological developments,
RC Group uses the best components and cutting-edge techniques and tools,
such as compressors driven by Inverter and software for the selection and
management of the facilities.
NATURAL
As pioneer of Free-Cooling technology since the early eighties and still not
for everyone, RC Group has always placed an emphasis on the development
of this technique. Another system at the base of energy-saving is the GlycolFree, which allows the use of pure water instead of antifreeze solutions.
GO
Reliable
Ecologic
Evolved
Natural
LIGHT WEIGHT SOLUTION FOR ENVIRONMENT
Environmentally.
Energy Saving.
Eco-sustainability.
RC Group makes use of refrigerants innocuous to the atmosphere, first of
all the hydrofluoroolefin HFO1234ze that, thanks to its high environmental
compatibility joined to a high energy efficiency, results to be an excellent
SOLUTION for replacement of R134a.
Another point in its favor is the much higher critical temperature which allows
to operate at much higher condensation temperatures retaining a good
thermodynamic efficiency.
LOWGWP
HFO1234ze
NOODP
LOWTEWI
G_ITC_RCW_8.4 RCGROUP SpA 19632013 fiftycoolyears
IT cooling
start here
GOGREEN
solutions
RC Group makes use of refrigerants innocuous to the atmosphere, first of all
HFO1234ze that, thanks to its high environmental compatibility joined to a
high energy efficiency, results to be an excellent SOLUTION for replacement
of R134a.
RC Group liquid chillers with HFO1234ze refrigerant charge:
H
HF
HFO1234ze
UNICO TURBO FLG
pg:167
X Type
pg:33
32
X Type
X Type: Close control air conditioners for chilled water feeding with down-flow air delivery.
Cooling Capacity: 52 182 kW
CHILLEDWATER
XCOILS
HIGHEFFICIENCY
COOLNET
GOGREEN
solutions
X Type
CHILLED
WATER
rcgroupairconditioning
MAIN FEATURES
Chilled water feeding precision air conditioner.
4 models, 2 versions available.
Machine designed according to a CFD analysis (Computational Fluid
Dynamics).
Chilled water feeding.
Operation with T10C.
X Type heat exchangers.
SHR ratio = 1.
EER up to 80.
Variable air flow.
Variable water flow.
Two-way chilled water valve.
Cooling density up to 47,6 kW/m2.
Downflow UNDER air delivery.
Suitable for indoor installation.
MAIN BENEFITS
Technical synergy with RC Group liquid chillers.
New plug fans with EC electric motors and composite impeller of the
latest generation, which guarantees a reduction of power consumption
(ERP 2015 certification).
Improvement of the control software, developed by RC Group, with
advanced control logic.
Bag filters of large surface that reduce replacement operations to once
a year.
Panels fully removable to facilitate the operations of extraordinary
maintenance;
Software Advanced: intelligent NET for IT Cooling, that maximizes the
energy saving in LOAD SHARING (on request).SHARING (a richiesta).
Complete set of optional accessories: filters, plenum, panels, stand.
RCGROUP SpA G_ITC_RCW8.4
EC
DOWN
FLOW
INDOOR INSTALLATION
The machines are designed for indoor installation.
LIMITI DI FUNZIONAMENTO
Deviations, even in small quantities, by the nominal operating conditions
Air return conditions: 35C 30%rH
Air delivery temperature: 25C
Chilled water inlet temperature: 18C
Chilled water outlet temperature: 28C
require a verification of the unit to the new working conditions.
For operating conditions different than the nominal, please contact
your local Agent or the RC Group Sales Department to verify your
requirements and provide the solution for your system.
f i f t y c o o l y e a r s
33
X Type
GOGREEN
solutions
MAIN COMPONENTS
FANS SECTION
The section is divided into several boxes each containing its own fan with
safety net. The boxes are to be installed and assembled on site in the void
of the raised floor, creating the foundation on which will be based the air
handling section.
Frame in galvanized steel sheet with protective surfaces treatment in
compliance with UNI ISO 9227/ASTMB117 and ISO 7253, and painted with
epoxy powders. Colour RAL 7016 hammered;
Height adjusting rubber holders.
Centrifugal fans with backward curved blades with wing profile, single
suction and without scroll housings (Plug-fans), directly coupled to external
rotor electric motor.
- Impeller in composite material exempt from rust formation.
- Brushless type synchronous EC motor with integrated electronic
commutated system and continuous variation of the rotation speed.
The motor rotation control is obtained with the EC system (Electronic
Commutation) that manage the motor according to the signal coming
from the microprocessor control.
Fan guard on air delivery.
Connecting cables with the unit electrical panel for power and control
signals for fan motors.
Fans control through ModBus.
Supports for the tiles of the raised floor. The supports are adjustable in
height to adapt to the thickness of the tiles.
IT Cooling
FILTERS SECTION
The section is divided into several boxes, each containing two bag filters
removable from the unit front. The boxes are to be installed and assembled
on site over the air handling section.
Disposable bag filters with G4 efficiency, with cells in synthetic fibre and
metallic frame (EN 779-2002).
- Filters are not rigenerable.
- The high filtering surface ensures a year of operation before replacement.
CONTROL SYSTEM
Microprocessor control system with graphic display for control and monitor of
operating and alarms status. The system includes:
Built-in clock for alarms date and time displaying and storing;
Built-in memory for the storing of the intervened events (up to 100 events
recorded);
Predisposition for connectivity board housing ( RCcom MBUS/JBUS,
LON, BACnet for Ethernet (SNMP- TCP/IP), BACnet for MS/TP). The
electronic cards are optional accessories;
Main components hour-meter;
Non-volatile Flash memory for data storage in case of power supply
faulty;
Menu with protection password;
LAN connection (max 15 units).
34
X Type
GOGREEN
solutions
IT Cooling
OPTIONAL ACCESSORIES
T1 S
X Type
1021 - Pressure independent two way motorized valve
851 - Dual power supply
1022-Telaio di sostegno 0-400mm
808 - Sandwich panels
Disposal M5 efficiency air filter
Disposal M6 efficiency air filter
Disposal F7 efficiency air filter
843 - Motorized damper with frame
204 - Differential pressure air control
909 - Clogged filters alarm
911 - Water presence alarm
913 - Additional water sensor (kit)
1020-External main switch
860 - T/rH sensor on air return
866 - T/rH external sensor
867 - T/rH remote sensor
923 - RC-Com MBUS/JBUS Serial board
926 - LON Serial board
931 - BACnet Ethernet - SNMP - TCP/IP Serial board
932 - BACnet MS/TP Serial board
958 - Emergency microprocessor supply
863 - Remote terminal shared
962 - Kit modem GSM
957 - Plantwatch without modem
930 - Remote graphic terminal kit
1016 - SOFTWARE ADVANCED - COOLNET
RC CLOUD PLATFORM
T2 S
T3 S
T4 S
AERAULIC DIAGRAM
35C
T1
M1
23C
HE
CFD Analysis
LEGENDA
T2
T3
T4
PF
18C
28C
25C
M1
HE
PF
T1
T2
T3
T4
35
X Type
GOGREEN
solutions
IT Cooling
kW
kW
kW/kW
kW
n.
m3/h
Pa
Pa
T1 S
T2 S
T3 S
T4 S
52,4
52,4
1
1,2
43,31
1
11000
30
330
99,2
99,2
1
2,9
33,97
2
21200
30
280
141,0
141,0
1
4,5
31,06
3
30600
30
270
182,0
182,0
1
6,2
29,21
4
40000
30
260
4,5
8,6
12,2
15,8
32
65
67
52
4
6
8
10
G4
G4
G4
G4
2
m
11,8
17,6
23,5
29,4
V/Ph/Hz 400/3/50+N 400/3/50+N 400/3/50+N 400/3/50+N
A
4,4
8,7
13,1
17,4
m3/h
kPa
n.
kg
74,2
63,1
55,6
494
357
64
73
75,7
67,2
60
765
525
94
146
76,8
68,3
61,4
1042
703
120
219
77,7
69
62,3
1330
892
146
292
1+1/2"
1/2"
2"
1/2"
2"
1/2"
2+1/2"
1/2"
dB(A)
dB(A)
dB(A)
kg
THE COOLING CAPACITY DOES NOT CONSIDER THE SUPPLY FAN MOTOR THERMAL LOAD
1. Characteristics referred to entering air at 35C - 30%RH; chilled water temperature 18-28C - 0% glycol
2. Noise level at 1 meter in free field.
DIMENSIONS (mm)
XT1
SIZE
XT1
XT2
XT3
XT4
XT2
a
1620
2260
2900
3540
b
1100
1100
1100
1100
c
2375
2375
2375
2375
d
525
525
525
525
XT3
XT4
36
INVERTER
ECFAN
MAIN FEATURES
Direct expansion precision air conditioner.
13 models available, 2 versions for a wide selection opportunity.
Modulating cooling capacity control.
EER up to 4,82.
BLCD inverter and on/off scroll compressors.
Single and double refrigerant circuit.
R410A Refrigerant charge.
EC plug-fans.
OVER and UNDER versions.
Suitable for indoor installation.
MAIN BENEFITS
Units with single and double refrigerant circuits.
Availability of remote condensers with axial fans (TEAM MATE series)
and with plug fans (TEAM MATE PF series).
High EER.
High efficiency at partial load.
Availability of electric heater.
Availability of steam humidifier.
Availability of hot water heating coil.
Availability of extra circuit heating coil.
Complete set of optional accessories: filters, plenum, panels, stand.
Easily of maintenance.
R410A
INVERTER
UP
FLOW
EC
DOWN
FLOW
INDOOR INSTALLATION
The machines are designed for indoor installation.
REMOTE CONDENSER
The units are designed to be matched with remote condensers with axial
fans (TEAM MATE series) or plug-fans (TEAM MATE PF series).
WORKING LIMITS
Room air temperature:
14C
minimum temperature with wet bulb.
24C
maximum temperature with wet bulb.
35C
maximum temperature with dry bulb.
Room air humidity:
20%RH minimum relative humidity.
75%RH maximum relative humidity.
f i f t y c o o l y e a r s
37
38
IT Cooling
FANS SECTION
Centrifugal fans with backward curved blades with wing profile, single
suction and without scroll housings (Plug-fans), directly coupled to external
rotor electric motor.
- Impeller in composite material, PA6 plastic reinforced with glass-fibre,
exempt from rust formation.
- Brushless type synchronous EC motor with integrated electronic
commutated system and continuous variation of the rotation speed.
The motor rotation control is obtained with the EC system (Electronic
Commutation) that manage the motor according to the signal coming from
the microprocessor control.
Fans control through ModBus.
Temperature sensors on air intake and air delivery with control, regulation
and limitation functions.
Fan guard with rubber support (UNDER version)
REFRIGERANT CIRCUIT
Components for each refrigerant circuit:
Electronic expansion valve.
Sight glass.
Filter dryer on liquid line.
Pressure transducers with indication, control and protection functions, on
low and high refrigerant pressure.
High pressure safety switch with manual reset.
Liquid receiver with accessories.
Refrigerant circuit with copper tubing with anticondensate insulation of the
suction line.
Plastic capillary hoses for pressure sensors connection.
R410A refrigerant charge and lubricant oil type PVE (Polyvinyl ether).
Valves on gas delivery and liquid return for coupling to remote air cooled
condenser.
010V proportional signal to manage the condensing control system of the
remote air cooled condenser.
Oil separator on gas discharge.
ELECTRICAL PANEL
In accordance with EN60204-1 norms complete with:
Main switch with door lock safety.
Magnetothermic switches for fans.
Magnetothermic switches for compressors.
Contactors for each load. The inverter driven compressors and the EC fans
dont require contactors.
Transformer for auxiliary circuit and microprocessor supply.
Terminals:
OUTLETS
- Voltage free deviating contact for General Alarm 1
- Voltage free contact for machine operating status.
INLETS
- Emergency unit stop with signalling on display (external alarm).
- External enabling.
Power supply 400/3/50+N
CONTROL SYSTEM
Microprocessor system with graphic display for control and monitor of
operating and alarms status. The system includes:
- Real time clock.
- Predisposition for connectivity board housing ( RCcom MBUS/JBUS,
LON, BACnet for Ethernet (SNMP- TCP/IP), BACnet for MS/TP).
- Main components hour-meter.
- Nonvolatile Flash memory for data storage in case of power supply
faulty and for alarms status recording (2MB).
- Menu with protection password.
- LAN connection.
IT Cooling
COMMON OPTIONAL ACCESSORIES
NEXT EVO INV DX
SIZE
TEAM MATE remote condenser
TEAM MATE PF remote condenser
213 - Team Mate electrical power supply by internal unit
810 - Floor stand Hmax=350 mm
811 - Floor stand Hmax=450 mm
812 - Floor stand Hmax=510 mm
215 - Disposal F5 efficiency air filter
832 - Air supply plenum with F6 filters
833 - Air supply plenum with F7 filters
835 - Air supply plenum with F9 filters
836 - Air supply plenum with sound absorber
945 -Air return plenum with Free Cooling damper
761 - Air supply plenum with 5 closed sides
808 - Sandwich panels
843 - Motorized damper with frame
405 - Extra-Circuit system
321 - Steam humidifier
773 - Dehumification system
310 - Electric heater
1014- Increased electrical heater
514 - Water heater + 2 way valve
204 - Differential pressure air control
909 - Clogged filters alarm
911 - Water presence alarm
913 - Additional water sensor (kit)
860 - T/rH sensor on air return
866 - T/rH external sensor
867 - T/rH remote sensor
1013 - Contact enabling the smoke / fire
83 - Compressor operation indicator
923 - RC-Com MBUS/JBUS Serial board
926 - LON Serial board
931 - BACnet Ethernet - SNMP - TCP/IP Serial board
932 - BACnet MS/TP Serial board
1011 - Double serial interface
958 - Emergency microprocessor supply
851 - Dual power supply
863 - Remote terminal shared
930 - Remote graphic terminal kit
962 - Kit modem GSM
957 - Plantwatch without modem
RC CLOUD PLATFORM
007
S M1
E0
010
S M1
E1
016
S M1
E2
020
S M1
E3
028
S M1
E4
034
S M2
E4
040
S M2
E5
053
S M3
E5
057
S M3
E6
040
D M2
E5
065
D M2
E7
080
D M4
E8
100
D M4
E9
007
S M1
E0
010
S M1
E1
016
S M1
E2
020
S M1
E3
028
S M1
E4
034
S M2
E4
040
S M2
E5
SIZE
848 - Condensate discharge system (kit)
849 - Condensate discharge system
1015 - Incresed umidifier
057
S M3
E6
040
D M2
E5
065
D M2
E7
080
D M4
E8
100
D M4
E9
053
S M3
E5
007
S M1
E0
010
S M1
E1
016
S M1
E2
020
S M1
E3
028
S M1
E4
034
S M2
E4
040
S M2
E5
053
S M3
E5
057
S M3
E6
040
D M2
E5
065
D M2
E7
080
D M4
E8
100
D M4
E9
TEAM MATE
19632013 fiftycoolyears RCGROUP SpA G_ITC_RCW8.4
TEAM MATE PF
39
IT Cooling
CONTROL OF THE COOLING CAPACITY ACCORDING TO AIR DELIVERY
TEMPERATURE
The cooling capacity control is made on the air delivery temperature.
Cooling capacity
COOLING SECTION
Units are equipped with scroll compressors BLDC inverter that allow a
modulating cooling capacity.
The scroll compressor BLDC Inverter can change the load continuously
and the regulation of the refrigerant circuit can be easily adapted, without
oscillations and transients, to the operating conditions required.
The system is highly efficient because it is supplying only the energy
necessary to satisfy the required thermal load; furthermore the system can
supply cooling capacity even in case of overload conditions.
Models with double refrigerant circuit (D version) are equipped with one scroll
compressor BLDC inverter for each refrigerant circuit. This solution ensures
extreme precision in the delivery of the cooling capacity required, together
with a drastic reduction of power input from the compressors.
The exchanger finned coils of large surface is provided with fins with
hydrophilic treatment that guarantees optimum falling water of condensation,
high thermal conductivity and prevents the development of micro-organisms.
Thermal load
Cut off
threshold
Setpoint
Models with double refrigerant circuit (D version) are equipped with interlaced
finned coil that maximizes the heat exchange in the operating condition with a
single cooling circuit, cancelling the by-pass effect on the exchanger.
Air flow
FAN SECTION
The Plug fans of the air handling section of the NEXT EVO INV series are
directly coupled to brushless type electric motors with built-in electronic
commutation system (EC) and driven by microprocessor control via MODBus;
this allows a unit operation with variable air flow.
These EC electric motors ensuring high performances, minimum energy
consumption and total absence of electromagnetic noise.
The management software of the machine, specifically developed by RC
Group for their precision air conditioners, allowing the better management
of the system machine with a modulating logic of ventilation, cooling
performances and the accessory system of direct free-cooling.
Cooling
Heating
Air flow
Setpoint
differential
40
Setpoint
Return
temperature (C)
Air flow
Setpoint
LOGIC 2
Cooling performance control as a function of the air delivery temperature and
the air flow as a function of the underfloor / duct pressure.
differential
Cooling
request
Heating
request
Differential
pressure (Pa)
IT Cooling
GRAPHIC FOR UNITS SELECTION
This graph allows you to select the model as a function of cooling capacity
and its EER.
The EER values include the remote condenser series TEAM MATE.
5,5
028
4,5
5,0
040
4,5
034
020
010
4,0
016
007
4,0
3,5
3,5
007
016
3,0
028
2,5
Cooling Capacity - kW
010
10
15
20
5,5
25
30
040
3,0
020
35
40
2,5
034
Cooling Capacity - kW
0
10
20
30
40
50
60
5,0
053
057
4,5
4,0
3,5
053
3,0
2,5
057
Cooling Capacity - kW
0
10
20
30
40
50
60
70
80
5,0
5,5
100
065
4,5
4,5
4,0
4,0
3,5
3,5
065
040
3,0
10
20
30
40
50
60
70
080
3,0
Cooling Capacity - kW
2,5
080
5,0
040
Cooling Capacity- kW
2,5
80
100
20
40
60
80
100
120
41
IT Cooling
TECHNICAL DATA
MODEL
SIZE
COOLING CAPACITY (1)
Total
Sensible
SHR
Unit power input Over (*)
Unit power input Under (*)
Supply fans
Air flow
Nominal external static pressure Over
Nominal external static pressure Under
Fans max external static pressure
Scroll compressors
BLCD inverter type
On/Off type
Cooling capacity control
Air filters
Efficiency
Refrigerant
Refrigerant charge (2)
Gas circuits
Power supply (**)
Max operating current (FLA)
Unit starting current (LRA)
Energy efficiency indexes (1)
EER Over (1) (*)
EER Under (1) (*)
Sound pressure level - ISO 3744 (3)
On air delivery Over
On air delivery Under
On air intake Over
Irradiated Over
On air intake Under
On front side Under
Net weight Over
Net weight Under
Remote condenser (4)
TEAM MATE (*)
TEAM MATE PF
Refrigerant connections
Gas delivery
Liquid return
Hydraulic connections - Condensate discharge
MODEL
SIZE
COOLING CAPACITY (1)
Total
Sensible
SHR
Unit power input Over (*)
Unit power input Under (*)
Supply fans
Air flow
Nominal external static pressure Over
Nominal external static pressure Under
Fans max external static pressure
Scroll compressors
BLCD inverter type
On/Off type
Cooling capacity control
Air filters
Efficiency
Refrigerant
Refrigerant charge (2)
Gas circuits
Power supply (**)
Max operating current (FLA)
Unit starting current (LRA)
Energy efficiency indexes (1)
EER Over (1) (*)
EER Under (1) (*)
Sound pressure level - ISO 3744 (3)
On air delivery Over
On air delivery Under
On air intake Over
Irradiated Over
On air intake Under
On front side Under
Net weight Over
Net weight Under
Remote condenser (4)
TEAM MATE (*)
TEAM MATE PF
Refrigerant connections
Gas delivery
Liquid return
Hydraulic connections - Condensate discharge
42
kW
kW
kW/kW
kW
kW
n.
m3/h
Pa
Pa
Pa
min
7,3
6,5
0,88
1,98
1,98
1
1800
20
20
80
007 S M1
E0
nom
8,5
7,0
0,83
2,69
2,69
1
1800
20
20
80
max
9,5
7,6
0,80
3,45
3,45
1
1800
20
20
80
min
8,7
8,7
1,00
2,18
2,17
1
2700
30
20
52
1
-Mod.
1
G2
R410A
2,5
1
400/3/50+N
7,2
4,2
n.
n.
n.
kg
n.
A
A
010 S M1
E1
nom
11,6
10,3
0,89
3,45
3,44
1
2700
30
20
52
max
17,3
13,3
0,77
8,01
8,01
1
2700
30
20
52
min
13,5
13,4
0,99
3,67
3,63
1
4000
50
20
175
1
-Mod.
1
G4
R410A
2,8
1
400/3/50+N
18,0
5,2
016 S M1
E2
nom
18,0
16,4
0,91
6,00
5,94
1
4475
50
20
175
max
21,3
18,1
0,85
8,39
8,32
1
4475
50
20
175
min
15,2
15,2
1,00
3,63
3,57
1
5500
50
20
628
1
-Mod.
1
G4
R410A
3,1
1
400/3/50+N
25,8
5,7
020 S M1
E3
nom
22,5
21,3
0,95
6,74
6,68
1
6000
50
20
628
max
31,0
26,6
0,86
12,76
12,70
1
6600
50
20
628
1
-Mod.
2
G4
R410A
3,7
1
400/3/50+N
28,4
8,2
kW/kW
kW/kW
3,69
3,69
3,17
3,17
2,75
2,75
4,00
4,02
3,36
3,37
2,16
2,16
3,68
3,72
3,00
3,03
2,54
2,56
4,19
4,26
3,34
3,37
2,43
2,44
dB(A)
dB(A)
dB(A)
dB(A)
dB(A)
dB(A)
kg
kg
51,0
51,0
45,1
35,0
45,1
45,1
51,0
51,0
45,1
35,0
45,1
45,1
170
170
51,0
51,0
45,1
35,0
45,1
45,1
58,4
58,2
47,3
40,3
49,9
40,5
58,4
58,2
47,3
40,3
49,9
40,5
230
230
58,4
58,2
47,3
40,3
49,9
40,5
61,1
60,6
49,5
43,0
52,3
42,9
63,3
63,0
51,1
45,2
54,5
45,1
270
270
63,3
63,0
51,1
45,2
54,5
45,1
61,1
60,8
49,5
43,0
52,4
43,0
62,9
62,6
50,8
44,8
54,2
44,8
310
310
64,9
64,7
52,3
46,8
56,1
46,7
n. x Mod.
n. x Mod.
ODS
ODS
F
kW
kW
kW/kW
kW
kW
n.
m3/h
Pa
Pa
Pa
min
16,7
16,7
1,00
3,80
3,64
1
7500
50
20
131
1xM11
1xT11
1xM20
1xT21
1xM25
1xT24
1xM35
1xT33
12
12
1/2"
12
12
1/2"
16
12
1/2"
16
16
1/2"
028 S M1
E4
nom
max
28,1
37,0
28,1
37,0
1,00
1,00
8,17
13,75
7,94
13,36
1
1
9500
12200
50
50
20
20
131
131
min
16,9
16,9
1,00
4,03
3,87
1
7500
50
20
258
1
-Mod.
3
G4
R410A
4,9
1
400/3/50+N
28,6
8,3
n.
n.
n.
kg
n.
A
A
034 S M2
E4
nom
max
35,0
50,2
35,0
45,5
1,00
0,91
9,97
19,53
9,64
19,16
1
1
11000
12200
50
50
20
20
258
258
min
16,8
16,8
1,00
3,71
3,63
2
6500
50
20
775
1
1
Mod.
3
G4
R410A
5,2
1
400/3/50+N
42,3
67,1
040 S M2
E5
nom
max
40,8
52,9
40,8
52,7
1,00
1,00
11,93
20,19
11,83
20,04
2
2
12500
15500
50
50
20
20
775
775
min
17,0
17,0
1,00
4,13
4,05
2
6500
50
20
520
1
1
Mod.
3
G4
R410A
7,5
1
400/3/50+N
46,6
71,2
053 S M3
E5
nom
max
54,2
69,1
53,0
60,3
0,98
0,87
15,94
24,42
15,76
24,25
2
2
15500
15500
50
50
20
20
520
520
1
2
Mod.
3
G4
R410A
7,6
1
400/3/50+N
60,3
84,3
kW/kW
kW/kW
4,39
4,59
3,44
3,54
2,69
2,77
4,19
4,37
3,51
3,63
2,57
2,62
4,53
4,63
3,42
3,45
2,62
2,64
4,12
4,20
3,40
3,44
2,83
2,85
dB(A)
dB(A)
dB(A)
dB(A)
dB(A)
dB(A)
kg
kg
59,4
57,7
48,5
41,3
49,7
40,3
64,1
62,8
51,7
46,0
54,3
44,9
420
420
69,3
68,2
56,2
51,2
59,6
50,2
59,4
57,7
49,6
41,5
50,0
40,7
67,1
65,9
54,5
49,0
57,5
48,0
460
460
69,3
68,2
56,3
51,2
59,6
50,2
53,0
52,1
47,8
37,0
46,3
37,2
66,1
66,0
53,7
48,0
57,5
48,1
540
540
70,7
70,6
57,6
52,6
62,0
52,6
53,0
52,1
48,7
37,5
46,8
37,7
70,7
70,6
57,7
52,6
62,0
52,6
590
590
70,7
70,6
57,7
52,6
62,0
52,6
n. x Mod.
n. x Mod.
ODS
ODS
F
1xM45
1xT44
1xM60
1xT58
1 x M 60
1 x T 69
1 x M 95
1 x T 86
16
16
1/2"
18
16
1/2"
18
18
1/2"
22
18
1/2"
IT Cooling
TECHNICAL DATA
MODEL
SIZE
COOLING CAPACITY (1)
Total
Sensible
SHR
Unit power input Over (*)
Unit power input Under (*)
Supply fans
Air flow
Nominal external static pressure Over
Nominal external static pressure Under
Fans max external static pressure
Scroll compressors
BLCD inverter type
On/Off type
Cooling capacity control
Air filters
Efficiency
Refrigerant
Refrigerant charge (2)
Gas circuits
Power supply (**)
Max operating current (FLA)
Unit starting current (LRA)
Energy efficiency indexes (1)
EER Over (1) (*)
EER Under (1) (*)
Sound pressure level - ISO 3744 (3)
On air delivery Over
On air delivery Under
On air intake Over
Irradiated Over
On air intake Under
On front side Under
Net weight Over
Net weight Under
Remote condenser (4)
TEAM MATE (*)
TEAM MATE PF
Refrigerant connections
Gas delivery
Liquid return
Hydraulic connections - Condensate discharge
MODEL
SIZE
COOLING CAPACITY (1)
Total
Sensible
SHR
Unit power input Over (*)
Unit power input Under (*)
Supply fans
Air flow
Nominal external static pressure Over
Nominal external static pressure Under
Fans max external static pressure
Scroll compressors
BLCD inverter type
On/Off type
Cooling capacity control
Air filters
Efficiency
Refrigerant
Refrigerant charge (2)
Gas circuits
Power supply (**)
Max operating current (FLA)
Unit starting current (LRA)
Energy efficiency indexes (1)
EER Over (1) (*)
EER Under (1) (*)
Sound pressure level - ISO 3744 (3)
On air delivery Over
On air delivery Under
On air intake Over
Irradiated Over
On air intake Under
On front side Under
Net weight Over
Net weight Under
Remote condenser (4)
TEAM MATE (*)
TEAM MATE PF
Refrigerant connections
Gas delivery
Liquid return
Hydraulic connections - Condensate discharge
kW
kW
kW/kW
kW
kW
n.
m3/h
Pa
Pa
Pa
min
17,7
17,7
1,00
4,22
4,13
2
8000
50
20
511
057 S M3
E6
nom
max
60,6
71,4
59,7
65,3
0,99
0,91
18,36
24,97
18,20
24,79
2
2
18000
18000
50
50
20
20
511
511
min
19,0
19,0
1,00
4,07
3,99
2
6500
50
20
775
1
2
Mod.
4
G4
R410A
8,2
1
400/3/50+N
60,9
84,8
n.
n.
n.
kg
n.
A
A
040 D M2
E5
nom
max
38,2
42,8
38,2
42,8
1,00
1,00
14,31
18,69
14,15
18,53
2
2
12500
14500
50
50
20
20
775
775
min
29,6
28,6
0,97
6,24
6,14
2
8000
50
20
375
2
-Mod.
3
G4
R410A
8,2
2
400/3/50+N
42,8
14,4
065 D M2
E7
nom
max
62,5
69,3
62,5
69,3
1,00
1,00
21,78
27,28
21,55
27,07
2
2
20000
21100
50
50
20
20
375
375
min
25,1
25,0
1,00
5,52
5,43
3
8000
50
20
475
2
-Mod.
4
G4
R410A
10
2
400/3/50+N
61,3
16,6
080 D M4
E8
nom
max
77,1
81,3
77,1
80,2
1,00
0,99
27,54
30,80
27,34
30,56
3
3
24200
24200
50
50
20
20
475
475
2
2
Mod.
5
G4
R410A
14
2
400/3/50+N
73,2
147,3
kW/kW
kW/kW
4,19
4,29
3,30
3,33
2,86
2,88
4,67
4,76
2,67
2,7
2,29
2,31
4,74
4,82
2,87
2,9
2,54
2,56
4,55
4,62
2,80
2,82
2,64
2,66
dB(A)
dB(A)
dB(A)
dB(A)
dB(A)
dB(A)
kg
kg
50,8
50,3
48,5
36,7
46,1
37,0
67,8
67,9
55,3
49,7
59,3
49,9
630
630
67,8
67,9
55,3
49,7
59,3
49,9
53,0
52,1
47,4
36,7
46,8
37,7
66,1
66,0
53,6
48,0
57,5
48,1
565
565
69,3
69,2
56,3
51,2
60,6
51,2
49,8
47,8
48,4
36,4
45,4
36,4
67,2
67,0
54,7
49,1
58,5
49,1
650
650
68,3
68,2
55,7
50,2
59,6
50,2
51,2
49,7
47,1
35,9
44,9
35,9
73,3
73,2
60,1
55,2
64,6
55,1
835
835
73,3
73,2
60,1
55,2
64,6
55,1
n. x Mod.
n. x Mod.
ODS
ODS
F
kW
kW
kW/kW
kW
kW
n.
m3/h
Pa
Pa
Pa
min
30,5
29,3
0,96
7,04
6,96
3
8000
50
20
450
n.
n.
1 x M 95
1 x T 86
2 x M 20
2 x T 21
2 x M 35
2 x T 33
2 x M 45
2 x T 44
22
18
1/2"
16
12
1/2"
18
16
1/2"
22
18
1/2"
100 D M4
E9
nom
max
96,8
102,0
96,1
99,5
0,99
0,98
36,25
41,30
35,99
40,96
3
3
28680
28680
50
50
20
20
450
450
2
2
Mod.
6
G4
R410A
15,1
2
400/3/50+N
92,3
164,3
n.
kg
n.
A
A
kW/kW
kW/kW
4,33
4,38
2,67
2,69
2,47
2,49
dB(A)
dB(A)
dB(A)
dB(A)
dB(A)
dB(A)
kg
kg
45,5
43,5
48,2
35,8
44,6
35,8
70,9
71,0
58,2
52,8
62,4
53,0
910
910
70,9
71,0
58,2
52,8
62,4
53,0
n. x Mod.
n. x Mod.
ODS
ODS
F
2 x M 50
2 x T 58
22
18
1/2"
THE COOLING CAPACITY DOES NOT CONSIDER THE SUPPLY FAN MOTOR
THERMAL LOAD
1. Characteristics referred to entering air at 24C-50%RH; 35C ambient temperature.
2. Unit refrigerant charge. Remote condenser, connections pipes and optional are
excluded.
3. Noise level at 1 meter in free field (external static pressure at nominal conditions)
4. For matching to other remote air cooled condensers please refer to RC WORLD
selection program
(*) The value includes the TEAM MATE remote condenser shown in the table.
(**) The remote condenser has separated power supply. Please refer to TEAM MATE
and TEAM MATE PF chapters.
43
IT Cooling
007
S M1
E0
010
S M1
E1
016
S M1
E2
020
S M1
E3
028
S M1
E4
034
S M2
E4
040
S M2
E5
053
S M3
E5
057
S M3
E6
040
D M2
E5
065
D M2
E7
080
D M4
E8
100
D M4
E9
kW
n.
2,5
1
5,1
1
5,1
1
6,0
2
9,0
3
9,0
3
13,5
3
13,5
3
13,5
3
13,5
3
13,5
3
18,0
3
18,0
3
kg/h
kW
2
1,4
3
2,3
3
2,3
3
2,3
8
6,0
8
6,0
8
6,0
8
6,0
8
6,0
8
6,0
15
11,3
15
11,3
15
11,3
kW
kW
11,0
10,0
18,1
16,5
24,7
22,4
39,0
35,4
43,3
39,4
55,4
49,7
64,2
59,0
69,5
63,3
63,3
52,5
94,2
80,0
117,0
98,3
135,0
115,0
kW
24,1
36,2
50,5
81,4
89,8
109,0
126,0
148,0
109,0
160,0
193,0
232,0
THE COOLING/HEATING CAPACITY DOES NOT CONSIDER THE SUPPLY FAN MOTOR THERMAL LOAD
Accessories technical data are referred to nominal conditions.
1.
2.
Characteristics referred to entering air at 24C 50%RH with chiller water at 7/12,5 C and 0% glycol
Characteristics referred to entering air at 20C with hot water at 75/60C
DIMENSIONS (mm)
SIZE
E0
E1
E2
E3
E4
E5
E6
E7
E8
E9
44
a
655
650
785
1085
1305
1630
1875
2175
2499
2899
b
445
675
675
775
930
930
930
930
930
930
c
1680
1925
1925
1925
1980
1980
1980
1980
1980
1980
INVERTER
ECFAN
MAIN FEATURES
Direct expansion precision air conditioner.
13 models available, 2 versions for a wide selection opportunity.
Modulating cooling capacity control.
EER up to 7,33.
BLCD inverter and on/off scroll compressors.
Built-in water cooled condenser.
Single and double refrigerant circuit.
R410A Refrigerant charge.
EC plug-fans.
OVER and UNDER versions.
Suitable for indoor installation.
MAIN BENEFITS
Units with single and double refrigerant circuits.
Availability of remote condensers with axial fans (TEAM MATE series)
and with plug fans (TEAM MATE PF series).
High EER.
High efficiency at partial load.
Availability of electric heater.
Availability of steam humidifier.
Availability of hot water heating coil.
Availability of extra circuit heating coil.
Availability of indirect free-cooling coil, esigned to be matched with DRY
COOLER series with axial fans or DRY COOLER PF series with plugfans.
Complete set of optional accessories: filters, plenum, panels, stand.
Easily of maintenance.
RCGROUP SpA G_ITC_RCW8.4
R410A
INVERTER
UP
FLOW
EC
DOWN
FLOW
INDOOR INSTALLATION
The machines are designed for indoor installation.
BUILT IN WATER COOLED CONDENSER
Water temperature:
30/50C Outlet temperature range.
WORKING LIMITS
Room air temperature:
14C
minimum temperature with wet bulb.
24C
maximum temperature with wet bulb.
35C
maximum temperature with dry bulb.
Room air humidity:
20%RH minimum relative humidity.
75%RH maximum relative humidity.
f i f t y c o o l y e a r s
45
IT Cooling
REFRIGERANT CIRCUIT
Components for each refrigerant circuit:
Electronic expansion valve.
Sight glass.
Filter dryer on liquid line.
Pressure transducers with indication, control and protection functions, on
low and high refrigerant pressure.
High pressure safety switch with manual reset.
Liquid receiver with accessories.
Refrigerant circuit with copper tubing with anticondensate insulation of the
suction line.
Plastic capillary hoses for pressure sensors connection.
R410A refrigerant charge and lubricant oil type PVE (Polyvinyl ether).
Oil separator on gas discharge.
ELECTRICAL PANEL
In accordance with EN60204-1 norms complete with:
Main switch with door lock safety.
Magnetothermic switches for fans.
Magnetothermic switches for compressors.
Contactors for each load. The inverter driven compressors and the EC fans
dont require contactors.
Transformer for auxiliary circuit and microprocessor supply.
Terminals:
OUTLETS
- Voltage free deviating contact for General Alarm 1
- Voltage free contact for machine operating status.
INLETS
- Emergency unit stop with signalling on display (external alarm).
- External enabling.
Power supply 400/3/50+N
CONTROL SYSTEM
Microprocessor system with graphic display for control and monitor of
operating and alarms status. The system includes:
- Real time clock.
- Predisposition for connectivity board housing ( RCcom MBUS/JBUS,
LON, BACnet for Ethernet (SNMP- TCP/IP), BACnet for MS/TP).
- Main components hour-meter.
- Nonvolatile Flash memory for data storage in case of power supply
faulty and for alarms status recording (2MB).
- Menu with protection password.
- LAN connection.
EVAPORATING SECTION
Heat exchanger coil with internally corrugated copper tubes and high
efficiency aluminium fins, specifically developed to provide high heat
transfer and lower pressure drops.
Finned pack with hydrophilic treatment that assure the condensate water
drop, high thermal conductivity and does not favour the growth of microorganisms.
Frame in galvanized steel.
Condensate tray in peraluman with PVC flexible discharge pipe.
CONDENSING SECTION
Copper brazed plate type with cover plates, plates and connections in AISI
316 stainless steel.
010V proportional signal to manage the condensing control system.
FANS SECTION
Centrifugal fans with backward curved blades with wing profile, single
suction and without scroll housings (Plug-fans), directly coupled to external
rotor electric motor.
- Impeller in composite material, PA6 plastic reinforced with glass-fibre,
exempt from rust formation.
- Brushless type synchronous EC motor with integrated electronic
commutated system and continuous variation of the rotation speed.
The motor rotation control is obtained with the EC system (Electronic
Commutation) that manage the motor according to the signal coming from
the microprocessor control.
Fans control through ModBus.
Temperature sensors on air intake and air delivery with control, regulation
and limitation functions.
Fan guard with rubber support (UNDER version)
46
IT Cooling
COMMON OPTIONAL ACCESSORIES
NEXT EVO INV DW
SIZE
DRY COOLER
DRY COOLER PF
409 - Free Cooling System FC
512 - Water regulating valve
810 - Floor stand Hmax=350 mm
811 - Floor stand Hmax=450 mm
812 - Floor stand Hmax=510 mm
215 - Disposal F5 efficiency air filter
832 - Air supply plenum with F6 filters
833 - Air supply plenum with F7 filters
835 - Air supply plenum with F9 filters
836 - Air supply plenum with sound absorber
945 -Air return plenum with Free Cooling damper
761 - Air supply plenum with 5 closed sides
808 - Sandwich panels
843 - Motorized damper with frame
405 - Extra-Circuit system
321 - Steam humidifier
773 - Dehumification system
310 - Electric heater
1014- Increased electrical heater
514 - Water heater + 2 way valve
204 - Differential pressure air control
909 - Clogged filters alarm
911 - Water presence alarm
913 - Additional water sensor (kit)
860 - T/rH sensor on air return
866 - T/rH external sensor
867 - T/rH remote sensor
1013 - Contact enabling the smoke / fire
83 - Compressor operation indicator
923 - RC-Com MBUS/JBUS Serial board
926 - LON Serial board
931 - BACnet Ethernet - SNMP - TCP/IP Serial board
932 - BACnet MS/TP Serial board
1011 - Double serial interface
958 - Emergency microprocessor supply
851 - Dual power supply
863 - Remote terminal shared
930 - Remote graphic terminal kit
962 - Kit modem GSM
957 - Plantwatch without modem
RC CLOUD PLATFORM
007
M1
E0
010
M1
E1
016
M1
E2
020
M1
E3
028
M1
E4L
034
M2
E4L
040
M2
E5L
053
M3
E5L
057
M3
E6L
040
D M2
E5L
065
D M2
E7L
080
D M4
E8L
100
D M4
E9L
007
S M1
E0
010
S M1
E1
016
S M1
E2
020
S M1
E3
028
S M1
E4
034
S M2
E4
040
S M2
E5
053
S M3
E5
057
S M3
E6
040
065
080
100
D M11 D M11 D M22 D M22
E5
E7
E8
E9
007
S M1
E0
010
S M1
E1
016
S M1
E2
020
S M1
E3
028
S M1
E4
034
S M2
E4
040
S M2
E5
053
S M3
E5
057
S M3
E6
040
065
080
100
D M11 D M11 D M22 D M22
E5
E7
E8
E9
47
IT Cooling
CONTROL OF THE COOLING CAPACITY ACCORDING TO AIR DELIVERY
TEMPERATURE
The cooling capacity control is made on the air delivery temperature.
Cooling capacity
COOLING SECTION
Units are equipped with scroll compressors BLDC inverter that allow a
modulating cooling capacity.
The scroll compressor BLDC Inverter can change the load continuously
and the regulation of the refrigerant circuit can be easily adapted, without
oscillations and transients, to the operating conditions required.
The system is highly efficient because it is supplying only the energy
necessary to satisfy the required thermal load; furthermore the system can
supply cooling capacity even in case of overload conditions.
Models with double refrigerant circuit (D version) are equipped with one scroll
compressor BLDC inverter for each refrigerant circuit. This solution ensures
extreme precision in the delivery of the cooling capacity required, together
with a drastic reduction of power input from the compressors.
The exchanger finned coils of large surface is provided with fins with
hydrophilic treatment that guarantees optimum falling water of condensation,
high thermal conductivity and prevents the development of micro-organisms.
Thermal load
Cut off
threshold
Setpoint
Models with double refrigerant circuit (D version) are equipped with interlaced
finned coil that maximizes the heat exchange in the operating condition with a
single cooling circuit, cancelling the by-pass effect on the exchanger.
Air flow
FAN SECTION
The Plug fans of the air handling section of the NEXT EVO INV series are
directly coupled to brushless type electric motors with built-in electronic
commutation system (EC) and driven by microprocessor control via MODBus;
this allows a unit operation with variable air flow.
These EC electric motors ensuring high performances, minimum energy
consumption and total absence of electromagnetic noise.
The management software of the machine, specifically developed by RC
Group for their precision air conditioners, allowing the better management
of the system machine with a modulating logic of ventilation, cooling
performances and the accessory system of direct free-cooling.
Cooling
Heating
Air flow
Setpoint
differential
48
Setpoint
Return
temperature (C)
Air flow
Setpoint
LOGIC 2
Cooling performance control as a function of the air delivery temperature and
the air flow as a function of the underfloor / duct pressure.
differential
Cooling
request
Heating
request
Differential
pressure (Pa)
IT Cooling
INDIRECT FREE-COOLING SYSTEM (optional accessory)
The control system also manages the operation of the air conditioner
equipped with an INDIRECT FREE-COOLING system (optional).
This system consists of one water cooling coil with water 2-way proportional
valve, condensing control valve.
The cooling coil is installed in the return air stream just after the filter section.
In this way the air is partially or totally cooled before entering the main cooling
coil ensuring a drastic reduction of power consumption of the machine.
This working mode can be obtained by integrating the FREE-COOLING
system with the water circuit of the DW machine and connecting them to an
external dissipation system (option, DRY COOLER series or DRY COOLER
PF series) and to a pumping group (PWU, option).
028
7,0
034
6,5
010
6,0
020
007
040
6,5
6,0
016
5,5
5,5
5,0
5,0
4,5
007
4,5
028
016
4,0
020
3,5
3,0
040
034
4,0
010
Cooling Capacity - kW
0
7,5
10
15
20
25
057
053
30
35
40
Cooling Capacity - kW
45
3,5
20
10
30
40
50
70
60
7,0
6,5
6,0
5,5
5,0
4,5
057
053
4,0
3,5
Cooling Capacity - kW
0
10
20
30
40
50
60
70
80
90
8,5
040
080
8,0
7,0
065
7,5
6,5
100
7,0
6,0
6,5
5,5
6,0
5,5
5,0
5,0
4,5
4,5
065
040
4,0
080
4,0
Cooling Capacity - kW
3,5
0
10
20
30
40
50
60
70
80
3,5
90
100
Cooling Capacity- kW
0
20
40
60
80
100
120
140
49
IT Cooling
TECHNICAL DATA
MODEL
SIZE
COOLING CAPACITY (1)
Total
Sensible
SHR
Unit power input Over
Unit power input Under
Condenser water flow rate
Condenser pressure drop
Supply fans
Air flow
Nominal external static pressure Over
Nominal external static pressure Under
Fans max external static pressure
Scroll compressors
BLCD inverter type
On/Off type
Cooling capacity control
Air filters
Efficiency
Refrigerant
Refrigerant charge (2)
Gas circuits
Power supply (**)
Max operating current (FLA)
Unit starting current (LRA)
Energy efficiency indexes (1)
EER Over (1)
EER Under (1)
Sound pressure level - ISO 3744 (3)
On air delivery Over
On air delivery Under
On air intake Over
Irradiated Over
On air intake Under
On front side Under
Net weight Over
Net weight Under
Connections - ISO 228/1 G
Condenser water inlet/outlet
Condensate discharge - Rubber pipe
MODEL
SIZE
COOLING CAPACITY (1)
Total
Sensible
SHR
Unit power input Over
Unit power input Under
Condenser water flow rate
Condenser pressure drop
Supply fans
Air flow
Nominal external static pressure Over
Nominal external static pressure Under
Fans max external static pressure
Scroll compressors
BLCD inverter type
On/Off type
Cooling capacity control
Air filters
Efficiency
Refrigerant
Refrigerant charge (2)
Gas circuits
Power supply
Max operating current (FLA)
Unit starting current (LRA)
Energy efficiency indexes (1)
EER Over (1)
EER Under (1)
Sound pressure level - ISO 3744 (3)
On air delivery Over
On air delivery Under
On air intake Over
Irradiated Over
On air intake Under
On front side Under
Net weight Over
Net weight Under
Connections - ISO 228/1 G
Condenser water inlet/outlet
Condensate discharge - Rubber pipe
50
kW
kW
kW/kW
kW
kW
m3/h
kPa
n.
m3/h
Pa
Pa
Pa
min
6,3
5,8
0,93
1,25
1,25
1,1
13
1,00
1700
20
20
80
007 M1
E0
nom
8,0
6,8
0,84
1,45
1,45
1,4
19
1,00
1800
20
20
80
max
9,6
7,5
0,78
1,96
1,96
1,7
28
1,00
1800
20
20
80
min
9,2
9,1
0,99
1,61
1,60
1,5
10
1,00
2700
30
20
52
1
-Mod.
1
G2
R410A
2,5
1
400/3/50+N
7,2
4,2
n.
n.
n.
kg
n.
A
A
010 M1
E1
nom
11,0
10,0
0,91
2,10
2,09
1,9
14
1,00
2700
30
20
52
max
20,1
14,5
0,72
5,79
5,78
3,7
49
1,00
2700
20
20
52
min
11,4
11,4
1,00
2,30
2,26
1,9
8
1,00
3500
50
20
175
1
-Mod.
1
G4
R410A
2,8
1
400/3/50+N
18,0
5,2
016 M1
E2
nom
17,4
16,0
0,92
3,73
3,67
2,9
18
1,00
4475
50
20
175
max
24,5
19,7
0,80
6,09
6,03
4,3
37
1,00
4475
30
20
175
min
15,8
15,8
1,00
2,84
2,78
2,6
8
1,00
5500
50
20
628
1
-Mod.
1
G4
R410A
3,1
1
400/3/50+N
10,0
5,7
020 M1
E3
nom
21,6
20,8
0,96
4,56
4,49
3,7
15
1,00
6000
50
20
628
max
35,9
28,9
0,81
9,52
9,47
6,4
41
1,00
6600
50
20
628
1
-Mod.
2
G4
R410A
3,7
1
400/3/50+N
28,4
8,2
kW/kW
kW/kW
5,04
5,04
5,53
5,53
4,91
4,91
5,74
5,78
5,24
5,26
3,47
3,48
4,96
5,04
4,66
4,74
4,02
4,06
5,56
5,68
4,74
4,81
3,77
3,79
dB(A)
dB(A)
dB(A)
dB(A)
dB(A)
dB(A)
kg
kg
49,7
49,7
44,8
34,3
44,8
44,8
51,0
51,0
45,1
35,0
45,1
45,1
175
185
51,0
51,0
45,1
35,0
45,1
45,1
58,4
58,2
47,3
40,3
49,9
40,5
58,4
58,2
47,3
40,3
49,9
40,5
250
260
58,4
58,2
47,3
40,3
49,9
40,5
61,1
60,6
49,5
43,0
52,3
42,9
63,3
63,0
51,1
45,2
54,5
45,1
280
290
63,3
63,0
51,1
45,2
54,5
45,1
61,1
60,8
49,5
43,0
52,4
43,0
62,9
62,6
50,8
44,8
54,2
44,8
325
345
64,9
64,7
52,3
46,8
56,1
46,7
M
F
1"
1/2''
1"
1/2''
1"
1/2''
1"
1/2''
1"
1/2''
1"
1/2''
1"
1/2''
1"
1/2''
1"
1/2''
1+1/4"
1/2''
1+1/4"
1/2''
1+1/4"
1/2''
min
17,2
17,2
1,00
2,84
2,68
2,8
3
1,00
7500
50
20
131
028 M1
E4L
nom
29,1
29,1
1,00
6,93
6,69
5,0
9
1,00
9500
50
20
131
min
17,4
17,4
1,00
2,77
2,61
2,8
2
1,00
7500
50
20
258
034 M2
E4L
nom
39,4
38,7
0,98
9,34
8,97
6,8
8
1,00
11500
50
20
258
min
20,6
20,6
1,00
3,15
3,07
3,4
4
2,00
6500
50
20
775
040 M2
E5L
nom
45,5
43,7
0,96
8,94
8,82
7,7
17
2,00
12500
50
20
775
min
27,1
27,1
1,00
4,85
4,77
4,6
4
2,00
8000
50
20
520
053 M3
E5L
nom
58,8
57,5
0,98
12,84
12,67
10,0
19
2,00
17000
50
20
520
max
77,8
68,2
0,88
19,35
19,16
13,7
34
2,00
18000
50
20
520
kW
kW
kW/kW
kW
kW
m3/h
kPa
n.
m3/h
Pa
Pa
Pa
max
38,6
37,7
0,98
11,70
11,32
6,9
16
1,00
11000
50
20
131
1
-Mod.
3
G4
R410A
4,9
1
400/3/50+N
28,6
8,3
n.
n.
n.
kg
n.
A
A
max
54,4
47,1
0,87
16,14
15,77
9,9
16
1,00
12200
50
20
258
1
1
Mod.
3
G4
R410A
5,2
1
400/3/50+N
42,3
67,1
max
58,1
54,8
0,94
16,55
16,37
10,4
15
2,00
15500
50
20
775
1
1
Mod.
3
G4
R410A
7,5
1
400/3/50+N
46,6
71,2
1
2
Mod.
3
G4
R410A
7,6
1
400/3/50+N
60,3
84,3
kW/kW
kW/kW
6,06
6,42
4,20
4,35
3,30
3,41
6,28
6,67
4,22
4,39
3,37
3,45
6,54
6,71
5,09
5,16
3,51
3,55
5,59
5,68
4,58
4,64
4,02
4,06
dB(A)
dB(A)
dB(A)
dB(A)
dB(A)
dB(A)
kg
kg
59,4
57,7
48,5
41,3
49,7
40,3
64,1
62,8
51,7
46,0
54,3
44,9
480
490
69,3
68,2
56,2
51,2
59,6
50,2
59,4
57,7
49,6
41,5
50,0
40,7
68,1
66,9
55,3
50,0
58,4
49,0
520
530
69,3
68,2
56,3
51,2
59,6
50,2
53,0
52,1
47,8
37,0
46,3
37,2
66,1
66,0
53,7
48,0
57,5
48,1
610
620
70,7
70,6
57,6
52,6
62,0
52,6
55,7
55,1
49,1
38,9
48,4
39,2
70,7
70,6
57,7
52,6
62,0
52,6
660
670
70,7
70,6
57,7
52,6
62,0
52,6
M
F
1+1/2"
1/2''
1+1/2"
1/2''
1+1/2"
1/2''
1+1/2"
1/2''
1+1/2"
1/2''
1+1/2"
1/2''
2"
1/2''
2"
1/2''
2"
1/2''
2"
1/2''
2"
1/2''
2"
1/2''
IT Cooling
TECHNICAL DATA
MODEL
SIZE
COOLING CAPACITY (1)
Total
Sensible
SHR
Unit power input Over
Unit power input Under
Condenser water flow rate
Condenser pressure drop
Supply fans
Air flow
Nominal external static pressure Over
Nominal external static pressure Under
Fans max external static pressure
Scroll compressors
BLCD inverter type
On/Off type
Cooling capacity control
Air filters
Efficiency
Refrigerant
Refrigerant charge (2)
Gas circuits
Power supply (**)
Max operating current (FLA)
Unit starting current (LRA)
Energy efficiency indexes (1)
EER Over (1)
EER Under (1)
Sound pressure level - ISO 3744 (3)
On air delivery Over
On air delivery Under
On air intake Over
Irradiated Over
On air intake Under
On front side Under
Net weight Over
Net weight Under
Connections - ISO 228/1 G
Condenser water inlet/outlet
Condensate discharge - Rubber pipe
MODEL
SIZE
COOLING CAPACITY (1)
Total
Sensible
SHR
Unit power input Over
Unit power input Under
Condenser water flow rate
Condenser pressure drop
Supply fans
Air flow
Nominal external static pressure Over
Nominal external static pressure Under
Fans max external static pressure
Scroll compressors
BLCD inverter type
On/Off type
Cooling capacity control
Air filters
Efficiency
Refrigerant
Refrigerant charge (2)
Gas circuits
Power supply
Max operating current (FLA)
Unit starting current (LRA)
Energy efficiency indexes (1)
EER Over (1)
EER Under (1)
Sound pressure level - ISO 3744 (3)
On air delivery Over
On air delivery Under
On air intake Over
Irradiated Over
On air intake Under
On front side Under
Net weight Over
Net weight Under
Connections - ISO 228/1 G
Condenser water inlet/outlet
Condensate discharge - Rubber pipe
kW
kW
kW/kW
kW
kW
m3/h
kPa
n.
m3/h
Pa
Pa
Pa
min
21,3
21,3
1,00
3,33
3,24
3,5
2
2,00
8000
50
20
511
057 M3
E6L
nom
62,8
60,7
0,97
13,89
13,71
10,7
21
2,00
18000
50
20
511
max
79,1
68,3
0,86
19,58
19,43
13,8
35
2,00
18000
50
20
511
min
20,3
20,3
1,00
2,85
2,77
3,3
5
2,00
6500
50
20
775
1
2
Mod.
4
G4
R410A
8,2
1
400/3/50+N
60,3
84,3
n.
n.
n.
kg
n.
A
A
040 D M2
E5L
nom
max
45,3
52,8
43,6
50,5
0,96
0,96
10,07
12,91
9,28
12,75
7,8
9,2
26
36
2,00
2,00
12500
14500
50
50
20
20
775
775
min
30,8
29,3
0,95
4,69
4,59
5,1
5
2,00
8000
50
20
375
2
-Mod.
3
G4
R410A
8,2
2
400/3/50+N
42,8
14,4
065 D M2
E7L
nom
max
70,5
80,4
68,5
75,1
0,97
0,93
16,43
20,05
16,21
19,80
12,2
14,1
28
37
2,00
2,00
20000
21100
50
50
20
20
375
375
min
25,8
25,8
1,00
3,66
3,57
4,2
3
3,00
8000
50
20
475
2
-Mod.
4
G4
R410A
10
2
400/3/50+N
61,3
16,6
080 D M4
E8L
nom
max
88,2
94,5
83,4
86,1
0,95
0,91
20,90
22,99
20,66
22,72
15,2
16,4
31
36
3,00
3,00
24200
24200
50
50
20
20
475
475
2
2
Mod.
5
G4
R410A
14
2
400/3/50+N
73,2
147,3
kW/kW
kW/kW
6,40
6,57
4,52
4,58
4,04
4,07
7,12
7,33
4,50
4,88
4,09
4,14
6,57
6,71
4,29
4,35
4,01
4,06
7,05
7,23
4,22
4,27
4,11
4,16
dB(A)
dB(A)
dB(A)
dB(A)
dB(A)
dB(A)
kg
kg
50,8
50,3
48,5
36,7
46,1
37,0
67,8
67,9
55,3
49,7
59,3
49,9
700
710
67,8
67,9
55,3
49,7
59,3
49,9
53,0
52,1
47,4
36,7
46,8
37,7
66,1
66,0
53,6
48,0
57,5
48,1
635
645
69,3
69,2
56,3
51,2
60,6
51,2
49,8
47,8
48,4
36,4
45,4
36,4
67,2
67,0
54,7
49,1
58,5
49,1
730
785
68,3
68,2
55,7
50,2
59,6
50,2
51,2
49,7
47,1
35,9
44,9
35,9
73,3
73,2
60,1
55,2
64,6
55,1
930
990
73,3
73,2
60,1
55,2
64,6
55,1
M
F
2"
1/2''
2"
1/2''
2"
1/2''
2"
1/2''
2"
1/2''
2"
1/2''
2"+1/2"
1/2''
2"+1/2"
1/2''
2"+1/2"
1/2''
2"+1/2"
1/2''
2"+1/2"
1/2''
2"+1/2"
1/2''
kW
kW
kW/kW
kW
kW
m3/h
kPa
n.
m3/h
Pa
Pa
Pa
min
31,4
29,8
0,95
4,56
4,48
5,2
2
3,00
8000
50
20
450
100 D M4
E9
nom
max
112,0
119,0
103,0
106,0
0,92
0,89
26,54
30,75
26,29
30,43
19,3
20,9
31
45
3,00
3,00
28680
28680
50
50
20
20
450
450
2
2
Mod.
6
G4
R410A
15,1
2
400/3/50+N
92,3
164,3
n.
n.
n.
kg
n.
A
A
kW/kW
kW/kW
6,89
7,01
4,22
4,26
3,87
3,91
dB(A)
dB(A)
dB(A)
dB(A)
dB(A)
dB(A)
kg
kg
45,5
43,5
48,2
35,8
44,6
35,8
70,9
71,0
58,2
52,8
62,4
53,0
1020
1095
70,9
71,0
58,2
52,8
62,4
53,0
M
F
2"+1/2"
1/2''
2"+1/2"
1/2''
2"+1/2"
1/2''
THE COOLING CAPACITY DOES NOT CONSIDER THE SUPPLY FAN MOTOR
THERMAL LOAD
1. Characteristics referred to entering air at 24C-50%RH; water to the condenser
30-36C.
2. Unit refrigerant charge. Optional are excluded.
3. Noise level at 1 meter in free field (external static pressure at nominal conditions)
51
IT Cooling
007
M1
E0
010
M1
E1
016
M1
E2
020
M1
E3
028
M1
E4L
034
M2
E4L
040
M2
E5L
053
M3
E5L
057
M3
E6L
040
D M2
E5L
065
D M2
E7L
080
D M4
E8L
100
D M4
E9L
kW
n.
2,5
1
5,1
1
5,1
1
6,0
2
9,0
3
9,0
3
13,5
3
13,5
3
13,5
3
13,5
3
13,5
3
18,0
3
18,0
3
kg/h
kW
2
1,4
3
2,3
3
2,3
3
2,3
8
6,0
8
6,0
8
6,0
8
6,0
8
6,0
8
6,0
15
11,3
15
11,3
15
11,3
kW
kW
11,0
10,0
18,1
16,5
24,7
22,4
39,0
35,4
44,7
40,7
55,4
49,7
68,7
62,3
69,5
63,3
63,3
52,5
94,2
80,0
117,0
98,3
135,0
115,0
kW
24,1
36,2
50,5
81,4
92,5
109,0
126,0
148,0
109,0
160,0
193,0
232,0
kW
kW
11,0
10,0
18,1
16,5
24,7
22,4
39,0
35,4
44,7
40,7
55,4
49,7
68,7
62,3
69,5
63,3
63,3
52,5
94,2
80,0
117,0
98,3
135,0
115,0
THE COOLING/HEATING CAPACITY DOES NOT CONSIDER THE SUPPLY FAN MOTOR THERMAL LOAD
Accessories technical data are referred to nominal conditions.
1.
2.
Characteristics referred to entering air at 24C 50%RH with chiller water at 7/12,5 C and 0% glycol
Characteristics referred to entering air at 20C with hot water at 75/60C
DIMENSIONS (mm)
SIZE
E0
E1
E2
E3
E4L
E5L
E6L
E7L
E8L
E9L
52
a
655
650
785
1085
1630
1955
2198
2499
2899
3299
b
445
675
675
775
930
930
930
930
930
930
c
1680
1925
1925
1925
1980
1980
1980
1980
1980
1980
NEXT EVO CW S
NEXT EVO CW S: Close control air conditioners for chilled water feeding with upflow or downflow air delivery
Cooling Capacity: 7 225 kW
CHILLEDWATER
ECFAN
COOLNET
NEXT EVO CW S
rcgroupairconditioning
MAIN FEATURES
Chilled water feeding precision air conditioner.
15 models available, 2 versions for a wide selection opportunity.
Chilled water feeding.
Two-way chilled water valves.
EC plug-fans.
Variable air flow.
Variable water flow.
SHR ratio 0,94.
Plug fans certified ERP 2015.
Cooling density up to 68,9 kW/m2.
Upflow (OVER) or downflow (UNDER) air delivery.
Suitable for indoor installation.
MAIN BENEFITS
Technical synergy with RC Group liquid chillers.
Availability of electric heater.
Availability of steam humidifier.
Availability of hot water heating coil.
Availability of extra circuit heating coil.
Availability of units with separate fan section, PLUS.
Complete set of optional accessories: filters, plenum, panels, stand.
Easily of maintenance.
CHILLED
WATER
EC
UP
FLOW
DOWN
FLOW
INDOOR INSTALLATION
The machines are designed for indoor installation.
WORKING LIMITS
Room air temperature:
14C
minimum temperature with wet bulb.
24C
maximum temperature with wet bulb.
35C
maximum temperature with dry bulb.
Room air humidity:
20%RH minimum relative humidity.
75%RH maximum relative humidity.
Chilled water temperature:
T 7C Maximum temperature difference between chilled water inlet
and outlet
f i f t y c o o l y e a r s
53
NEXT EVO CW S
MAIN COMPONENTS
FRAMEWORK
Base in aluminium extrusion, painted with epoxy powders. Colour RAL
9005;
Frame in aluminium profile, painted with epoxy powders. The inner frame is
provided with seals for the panels. Colour RAL 9005;
Panels in galvanized steel sheet with protective surfaces treatment in
compliance with UNI ISO 9227/ASTMB117 and ISO 7253, and painted with
epoxy powders. Colour RAL 7016 hammered;
Panels insulated with polyurethane foam and seals to ensure air tight.
Hinged front panels with quick release removal system.
Total front access for routine maintenance.
Removable lateral and back side panels.
Air flow OVER version:
- Air intake from the front through honeycomb type grille and air delivery
from the top.
- Washable air pre-filters with G2 efficiency, with cells in synthetic fibre
(size F0 excluded).
Air flow UNDER version:
Machine size F0:
- Air intake from the front through honeycomb type grille and air delivery
from the bottom.
Machine size F1, F2, F3, F3P, F4, F5, F6, F7, F8, F9 and all PLUS
series:
- Air intake from the top and air delivery from the bottom.
Compartment for electrical panel on unit front for direct access to control
and regulation devices;
FILTER SECTION
Size F0:
- Washable air filters with G2 efficiency, with cells in synthetic fibre and
metallic frame (EN 779-2002).
Size F1, F2, F3, F3P, F4, F5, F6, F7, F8, F9 and all PLUS series:
- Washable air filters with G4 efficiency, with cells in synthetic fibre and
metallic frame (EN 779-2002).
Air filters access:
OVER version
- Frontal access for all machines
UNDER version
- For machines size F0 - F1 F2 F3 frontal access.
For
machine size F3P - F4 F5 F6 F7 F8 F9 and all PLUS series
access from upper side.
COOLING SECTION
Heat exchanger coil with internally corrugated copper tubes and high
efficiency aluminium fins, specifically developed to provide high heat
transfer and lower pressure drops.
Finned pack with hydrophilic treatment that assure the condensate water
drop, high thermal conductivity and does not favour the growth of microorganisms.
2-way motorized valve for water flow regulation with 010 VDC control
actuator and emergency manual control.
Frame in galvanized steel.
Condensate tray in peralluman with PVC flexible discharge pipe.
Air temperature sensors upstream and downstream the cooling section,
with control, regulation and limitation functions.
Temperature probes on chilled water inlet / outlet.
IT Cooling
NEXT EVO CW S & K PLUS
The fan section is separated and is designed to be fixed under the machine.
The fan section provides the air discharge from the front and can be installed
in the raised floor void or directly on the floor for downflow air delivery.
It is possible to provide the air flow towards the rear of the machine by
moving the panels and the fan guard see chapter NEXT EVO CW PLUS
installation diagram.
The fans section includes:
Height adjusting rubber holders.
Centrifugal fans with backward curved blades with wing profile, single
suction and without scroll housings (Plug-fans), directly coupled to external
rotor electric motor.
- Impeller in composite material exempt from rust formation.
- Brushless type synchronous EC motor with integrated electronic
commutated system and continuous variation of the rotation speed.
The motor rotation control is obtained with the EC system (Electronic
Commutation) that manage the motor according to the signal coming
from the microprocessor control.
Fans control through ModBus.
Fan guard with rubber support on air intake and delivery
ELECTRICAL PANEL
In accordance with EN60204-1 norms, suitable for indoor installation,
complete wit:
Main switch with door lock safety on frontal panel;.
Magnetothermic switches for supply fans. The supply fans equipped with
EC electric motor and dont require contactors.
Transformer for auxiliary circuit and microprocessor supply.
Terminals:
OUTLETS
- Voltage free deviating contact for General Alarm 1
- Voltage free contact for supply fans status.
INLETS
- Emergency unit stop with signalling on display (external alarm).
- External enabling.
Power supply 400/3/50+N.
CONTROL SYSTEM
Microprocessor control system with graphic display for control and monitor of
operating and alarms status. The system includes:
Built-in clock for alarms date and time displaying and storing;
Built-in memory for the storing of the intervened events (up to 100 events
recorded);
Predisposition for connectivity board housing ( RCcom MBUS/JBUS, LON,
BACnet for Ethernet (SNMP- TCP/IP), BACnet for MS/TP). The electronic
cards are optional accessories;
Main components hour-meter;
Non-volatile Flash memory for data storage in case of power supply faulty;
Analogue set point compensation (01 Vdc) according to an external
analogue signal at Customer care;
Menu with protection password;
LAN connection (max 15 units).
FANS SECTION
NEXT EVO CW S & K OVER / UNDER
The fan section is contained within the machine and includes:
Centrifugal fans with backward curved blades with wing profile, single
suction and without scroll housings (Plug-fans), directly coupled to external
rotor electric motor.
- Impeller in composite material exempt from rust formation.
- Brushless type synchronous EC motor with integrated electronic
commutated system and continuous variation of the rotation speed.
The motor rotation control is obtained with the EC system (Electronic
Commutation) that manage the motor according to the signal coming
from the microprocessor control.
Fans control through ModBus.
Fan guard with rubber support (UNDER version)
54
NEXT EVO CW S
IT Cooling
COMMON OPTIONAL ACCESSORIES
NEXT EVO CW S
SIZE
102 - AC fan - DOWNGRADE
935 - H2O deviation valve (3 way)
810 - Floor stand Hmax=350 mm
811 - Floor stand Hmax=450 mm
812 - Floor stand Hmax=510 mm
215 - Disposal F5 efficiency air filter
832 - Air supply plenum with F6 filters
833 - Air supply plenum with F7 filters
835 - Air supply plenum with F9 filters
836 - Air supply plenum with sound absorber
Air return plenum with sound absorber
Air discharge plenum with frontal and lateral grilles
Air discharge plenum with frontal grille
761 - Air supply plenum with 5 closed sides
808 - Sandwich panels
945 -Air return plenum with Free Cooling damper
405 - Extra-Circuit system
321 - Steam humidifier
773 - Dehumification system
310 - Electric heater
1014- Increased electrical heater
514 - Water heater + 2 way valve
204 - Differential pressure air control
508 - Automatic S/W operation
909 - Clogged filters alarm
911 - Water presence alarm
913 - Additional water sensor (kit)
860 - T/rH sensor on air return
866 - T/rH external sensor
867 - T/rH remote sensor
1013 - Contact enabling the smoke / fire
923 - RC-Com MBUS/JBUS Serial board
926 - LON Serial board
931 - BACnet Ethernet - SNMP - TCP/IP Serial board
932 - BACnet MS/TP Serial board
1011 - Double serial interface
958 - Emergency microprocessor supply
851 - Dual power supply
863 - Remote terminal shared
930 - Remote graphic terminal kit
962 - Kit modem GSM
957 - Plantwatch without modem
1016 - SOFTWARE ADVANCED - COOLNET
RC CLOUD PLATFORM
7
F0
S
13
F1
S
21
F2
S
32
F3
S
45
F3P
S
53
F4
S
72
F5
S
81
F6
S
100
F7
S
120
F8
S
138
F9
S
7
F0
S
13
F1
S
21
F2
S
32
F3
S
45
F3P
S
53
F4
S
72
F5
S
81
F6
S
100
F7
S
120
F8
S
138
F9
S
7
F0
S
13
F1
S
21
F2
S
32
F3
S
45
F3P
S
53
F4
S
72
F5
S
81
F6
S
100
F7
S
120
F8
S
138
F9
S
55
NEXT EVO CW S
IT Cooling
kW
kW
kW/kW
kW
n.
m3/h
Pa
Pa
m3/h
kPa
n.
A
7
F0
S
13
F1
S
21
F2
S
32
F3
S
45
F3P
S
53
F4
S
72
F5
S
81
F6
S
100
F7
S
120
F8
S
138
F9
S
6,7
5,8
0,87
0,10
1
1800
20
75
12,7
11,9
0,94
0,34
1
2900
20
20
20,8
19,4
0,93
0,88
1
4920
20
50
31,8
29,9
0,94
1,66
1
7800
20
370
44,9
42,1
0,94
2,20
1
10800
20
195
52,8
49,8
0,94
2,15
1
13100
20
115
71,5
67,7
0,95
2,90
2
16350
20
430
80,7
76,1
0,94
3,47
2
20000
20
350
100,0
94,0
0,94
3,98
2
24200
20
160
120,0
114,0
0,95
6,22
3
28300
20
150
138,0
130,0
0,94
6,42
3
33100
20
200
1,2
44
2,2
27
3,6
73
5,5
64
7,7
90
9,1
54
12,3
74
13,9
52
17,2
83
20,5
83
23,7
74
G2
230/1/50
1,29
G4
G4
G4
G4
G4
G4
G4
G4
G4
G4
400/3/50+N 400/3/50+N 400/3/50+N 400/3/50+N 400/3/50+N 400/3/50+N 400/3/50+N 400/3/50+N 400/3/50+N 400/3/50+N
2,31
1,79
4,39
4,65
4,52
8,78
9,30
9,03
13,17
13,95
dB(A)
dB(A)
dB(A)
dB(A)
dB(A)
dB(A)
kg
kg
55,0
55,0
47,8
35,4
42,1
35,4
150
150
61,1
61,1
46,6
42,4
51,7
42,4
196
209
67,0
67,0
47,1
43,2
52,6
43,2
230
248
70,2
70,2
50,6
46,5
56,1
46,5
290
313
70,8
70,8
52,7
48,7
58,2
48,7
312
320
75,8
75,8
56,5
52,9
61,9
52,9
332
366
73,8
73,8
54,1
50,0
59,6
50,0
410
452
72,2
72,2
54,1
50,1
59,5
50,1
465
513
77,2
77,2
57,8
54,3
63,3
54,3
515
569
78,6
78,6
58,9
54,8
64,4
54,8
578
640
76,1
76,1
58,0
54,0
63,5
54,0
656
730
M
F
3/4"
1/2"
1"
1/2"
1"
1/2"
1+1/4"
1/2"
1+1/4"
1/2"
1+1/2"
1/2"
2"
1/2"
2"
1/2"
2+1/2"
1/2"
2+1/2"
1/2"
3"
1/2"
148
F8
PLUS
S
173
F9
PLUS
S
226
F10
PLUS
S
127
F7
PLUS
S
VERSION
COOLING CAPACITY (1)
125,0
148,0
173,0
225,0
Total
kW
118,0
139,0
162,0
212,0
Sensible
kW
0,94
0,94
0,94
0,94
SHR
kW/kW
6,57
6,34
7,00
8,73
Power input Under
kW
3
3
3
4
Supply fans
n.
30000
34000
41000
52000
Air flow
m3/h
20
20
20
20
Nominal external static pressure Under Pa
80
195
60
110
Max external static pressure
Pa
Cooling coil
21,5
25,3
29,6
38,7
Water flow rate
m3/h
64
93
91
93
Pressure drop - coil + valve
kPa
8
10
12
12
Air filters
n.
G4
G4
G4
G4
Efficiency
400/3/50+N 400/3/50+N 400/3/50+N 400/3/50+N
Power supply
13,17
13,95
13,55
18,06
Max operating current (FLA)
A
Sound level - ISO 3744 (2)
79,8
76,8
81,5
81,7
On air delivery Under
dB(A)
65,6
64,2
67,6
67,8
On air intake Under
dB(A)
56,0
54,8
58,6
58,8
On front side Under
dB(A)
695
795
910
1103
Net weight Under
kg
495
555
635
755
Net weight - Separate fan section
kg
Connections
2+1/2"
3"
3"
3"
Water inlet/outlet - ISO 7/1 - R
M
1/2"
1/2"
1/2"
1/2"
Condensate discharge Rubber pipe F
THE COOLING CAPACITY DOES NOT CONSIDER THE SUPPLY FAN MOTOR THERMAL LOAD
1. Characteristics referred to entering air at 24C-50%RH with chilled water temperature 7-12C - 0% glycol.
2. Noise level at 1 meter in free field.
56
NEXT EVO CW S
IT Cooling
TECHNICAL DATA - OPTIONAL ACCESSORIES
NEXT EVO CW S
SIZE
Electric heater
Capacity
Capacity steps
Oversized Electric heater
Capacity
Capacity steps
Humidifier
Steam capacity
Power input
Oversized Humidifier
Steam capacity
Power input
Extra circuit coil (1)
Total cooling capacity
Sensible cooling capacity
Heating coil (2)
Heating capacity
7
F0
-
13
F1
-
21
F2
-
32
F3
-
45
F3P
-
53
F4
-
72
F5
-
81
F6
-
100
F7
-
120
F8
-
138
F9
-
127
148
173
226
F7
F8
F9
F10
PLUS PLUS PLUS PLUS
kW
n.
2,6
1
5,1
1
5,1
1
6,0
2
6,0
2
9,0
3
13,5
3
13,5
3
13,5
3
18,0
3
18,0
3
18,0
3
18,0
3
27,0
3
27,0
3
kW
n.
---
---
---
9,0
2
9,0
2
13,5
3
18,0
2
18,0
2
18,0
2
27,0
3
27,0
3
---
---
---
---
kg/h
kW
2
1,4
3
2,3
3
2,3
3
2,3
3
2,3
8
6,0
8
6,0
8
6,0
15
11,3
15
11,3
15
11,3
15
11,3
15
11,3
15
11,3
15
11,3
kg/h
kW
---
8
6,0
15
11,3
15
11,3
15
11,3
---
---
---
---
---
---
---
kW
kW
---
12,6
11,8
18,1
17,0
28,6
27,0
39,4
37,0
49,8
47,4
65,5
62,2
74,3
70,6
95,1
90,0
101,0
95,5
121,0
114,0
103,0
97,4
129,0
122,0
169,0
160,0
216,0
203,0
kW
12,2
26,7
35,4
57,0
78,7
101,0
126,0
155,0
181,0
190,0
236,0
198,0
242,0
327,0
405,0
8 (*)
8 (*)
8 (*)
6,0 (*) 6,0 (*) 6,0 (*)
THE COOLING CAPACITY DOES NOT CONSIDER THE SUPPLY FAN MOTOR THERMAL LOAD
1. Characteristics referred to entering air at 24C 50%RH with chiller water at 7-12,5 C and 0% glycol
2. Characteristics referred to entering air at 20C with hot water at 75-60C
(*) Only OVER version
57
NEXT EVO CW S
IT Cooling
655
650
785
1085
1085
1305
1630
1875
2175
2499
2899
445
675
675
775
930
930
930
930
930
930
930
1680
1925
1925
1925
1925
1980
1980
1980
1980
1980
1980
a
2175
2499
2899
3510
b
930
930
930
930
c1
1980
1980
1980
1980
c2
600
600
600
600
c1
c2
a
58
NEXT EVO CW K
NEXT EVO CW K: Close control air conditioners for chilled water feeding with upflow or downflow air delivery
Cooling Capacity: 15 279 kW
CHILLEDWATER
ECFAN
COOLNET
NEXT EVO CW K
rcgroupairconditioning
MAIN FEATURES
Chilled water feeding precision air conditioner.
14 models available, 2 versions for a wide selection opportunity.
Chilled water feeding.
Two-way chilled water valves.
EC plug-fans.
Variable air flow.
Variable water flow.
SHR ratio 0,89.
Plug fans certified ERP 2015.
Cooling density up to 85,7kW/m2.
Upflow (OVER) or downflow (UNDER) air delivery.
Suitable for indoor installation.
MAIN BENEFITS
Technical synergy with RC Group liquid chillers.
Availability of electric heater.
Availability of steam humidifier.
Availability of units with separate fan section, PLUS.
Complete set of optional accessories: filters, plenum, panels, stand.
Easily of maintenance.
CHILLED
WATER
EC
UP
FLOW
DOWN
FLOW
INDOOR INSTALLATION
The machines are designed for indoor installation.
WORKING LIMITS
Room air temperature:
14C
minimum temperature with wet bulb.
24C
maximum temperature with wet bulb.
35C
maximum temperature with dry bulb.
Room air humidity:
20%RH minimum relative humidity.
75%RH maximum relative humidity.
Chilled water temperature:
T 7C Maximum temperature difference between chilled water inlet
and outlet
f i f t y c o o l y e a r s
59
NEXT EVO CW K
MAIN COMPONENTS
FRAMEWORK
Base in aluminium extrusion, painted with epoxy powders. Colour RAL
9005;
Frame in aluminium profile, painted with epoxy powders. The inner frame is
provided with seals for the panels. Colour RAL 9005;
Panels in galvanized steel sheet with protective surfaces treatment in
compliance with UNI ISO 9227/ASTMB117 and ISO 7253, and painted with
epoxy powders. Colour RAL 7016 hammered;
Panels insulated with polyurethane foam and seals to ensure air tight.
Hinged front panels with quick release removal system.
Total front access for routine maintenance.
Removable lateral and back side panels.
Air flow OVER version:
- Air intake from the front through honeycomb type grille and air delivery
from the top.
- Washable air pre-filters with G2 efficiency, with cells in synthetic fibre
(size F0 excluded).
Air flow UNDER version:
Machine size F0:
- Air intake from the front through honeycomb type grille and air delivery
from the bottom.
Machine size F1, F2, F3, F3P, F4, F5, F6, F7, F8, F9 and all PLUS
series:
- Air intake from the top and air delivery from the bottom.
Compartment for electrical panel on unit front for direct access to control
and regulation devices;
FILTER SECTION
Size F0:
- Washable air filters with G2 efficiency, with cells in synthetic fibre and
metallic frame (EN 779-2002).
Size F1, F2, F3, F3P, F4, F5, F6, F7, F8, F9 and all PLUS series:
- Washable air filters with G4 efficiency, with cells in synthetic fibre and
metallic frame (EN 779-2002).
Air filters access:
OVER version
- Frontal access for all machines
UNDER version
- For machines size F0 - F1 F2 F3 frontal access.
For
machine size F3P - F4 F5 F6 F7 F8 F9 and all PLUS series
access from upper side.
COOLING SECTION
Heat exchanger coil with internally corrugated copper tubes and high
efficiency aluminium fins, specifically developed to provide high heat
transfer and lower pressure drops.
Finned pack with hydrophilic treatment that assure the condensate water
drop, high thermal conductivity and does not favour the growth of microorganisms.
2-way motorized valve for water flow regulation with 010 VDC control
actuator and emergency manual control.
Frame in galvanized steel.
Condensate tray in peralluman with PVC flexible discharge pipe.
Air temperature sensors upstream and downstream the cooling section,
with control, regulation and limitation functions.
Temperature probes on chilled water inlet / outlet.
IT Cooling
NEXT EVO CW S & K PLUS
The fan section is separated and is designed to be fixed under the machine.
The fan section provides the air discharge from the front and can be installed
in the raised floor void or directly on the floor for downflow air delivery.
It is possible to provide the air flow towards the rear of the machine by
moving the panels and the fan guard see chapter NEXT EVO CW PLUS
installation diagram.
The fans section includes:
Height adjusting rubber holders.
Centrifugal fans with backward curved blades with wing profile, single
suction and without scroll housings (Plug-fans), directly coupled to external
rotor electric motor.
- Impeller in composite material exempt from rust formation.
- Brushless type synchronous EC motor with integrated electronic
commutated system and continuous variation of the rotation speed.
The motor rotation control is obtained with the EC system (Electronic
Commutation) that manage the motor according to the signal coming
from the microprocessor control.
Fans control through ModBus.
Fan guard with rubber support on air intake and delivery
ELECTRICAL PANEL
In accordance with EN60204-1 norms, suitable for indoor installation,
complete wit:
Main switch with door lock safety on frontal panel;.
Magnetothermic switches for supply fans. The supply fans equipped with
EC electric motor and dont require contactors.
Transformer for auxiliary circuit and microprocessor supply.
Terminals:
OUTLETS
- Voltage free deviating contact for General Alarm 1
- Voltage free contact for supply fans status.
INLETS
- Emergency unit stop with signalling on display (external alarm).
- External enabling.
Power supply 400/3/50+N.
CONTROL SYSTEM
Microprocessor control system with graphic display for control and monitor of
operating and alarms status. The system includes:
Built-in clock for alarms date and time displaying and storing;
Built-in memory for the storing of the intervened events (up to 100 events
recorded);
Predisposition for connectivity board housing ( RCcom MBUS/JBUS, LON,
BACnet for Ethernet (SNMP- TCP/IP), BACnet for MS/TP). The electronic
cards are optional accessories;
Main components hour-meter;
Non-volatile Flash memory for data storage in case of power supply faulty;
Analogue set point compensation (01 Vdc) according to an external
analogue signal at Customer care;
Menu with protection password;
LAN connection (max 15 units).
FANS SECTION
NEXT EVO CW S & K OVER / UNDER
The fan section is contained within the machine and includes:
Centrifugal fans with backward curved blades with wing profile, single
suction and without scroll housings (Plug-fans), directly coupled to external
rotor electric motor.
- Impeller in composite material exempt from rust formation.
- Brushless type synchronous EC motor with integrated electronic
commutated system and continuous variation of the rotation speed.
The motor rotation control is obtained with the EC system (Electronic
Commutation) that manage the motor according to the signal coming
from the microprocessor control.
Fans control through ModBus.
Fan guard with rubber support (UNDER version)
60
NEXT EVO CW K
IT Cooling
COMMON OPTIONAL ACCESSORIES
NEXT EVO CW K
SIZE
102 - AC fan - DOWNGRADE
935 - H2O deviation valve (3 way)
810 - Floor stand Hmax=350 mm
811 - Floor stand Hmax=450 mm
812 - Floor stand Hmax=510 mm
215 - Disposal F5 efficiency air filter
832 - Air supply plenum with F6 filters
833 - Air supply plenum with F7 filters
835 - Air supply plenum with F9 filters
836 - Air supply plenum with sound absorber
Air return plenum with sound absorber
Air discharge plenum with frontal and lateral grilles
Air discharge plenum with frontal grille
761 - Air supply plenum with 5 closed sides
808 - Sandwich panels
945 -Air return plenum with Free Cooling damper
321 - Steam humidifier
310 - Electric heater
1014- Increased electrical heater
204 - Differential pressure air control
508 - Automatic S/W operation
909 - Clogged filters alarm
911 - Water presence alarm
913 - Additional water sensor (kit)
860 - T/rH sensor on air return
866 - T/rH external sensor
867 - T/rH remote sensor
1013 - Contact enabling the smoke / fire
923 - RC-Com MBUS/JBUS Serial board
926 - LON Serial board
931 - BACnet Ethernet - SNMP - TCP/IP Serial board
932 - BACnet MS/TP Serial board
1011 - Double serial interface
958 - Emergency microprocessor supply
851 - Dual power supply
863 - Remote terminal shared
930 - Remote graphic terminal kit
962 - Kit modem GSM
957 - Plantwatch without modem
1016 - SOFTWARE ADVANCED - COOLNET
RC CLOUD PLATFORM
15
F1
K
25
F2
K
39
F3
K
59
F3P
K
66
F4
K
88
F5
K
109
F6
K
125
F7
K
150
F8
K
172
F9
K
15
F1
K
25
F2
K
39
F3
K
59
F3P
K
66
F4
K
88
F5
K
109
F6
K
125
F7
K
150
F8
K
172
F9
K
15
F1
K
25
F2
K
39
F3
K
59
F3P
K
66
F4
K
88
F5
K
109
F6
K
125
F7
K
150
F8
K
172
F9
K
154
180
210
280
F7
F8
F9
F10
PLUS PLUS PLUS PLUS
154
180
210
280
F7
F8
F9
F10
PLUS PLUS PLUS PLUS
61
NEXT EVO CW K
IT Cooling
15
F1
K
25
F2
K
39
F3
K
59
F3P
K
66
F4
K
88
F5
K
109
F6
K
125
F7
K
150
F8
K
172
F9
K
15,5
12,9
0,83
0,32
1
2700
20
30
24,7
21,4
0,87
0,91
1
4700
20
35
38,7
34,0
0,88
1,78
1
7600
20
320
58,4
50,1
0,86
2,51
1
10800
20
100
65,6
58,1
0,89
2,58
1
13100
20
25
88,1
75,7
0,86
3,36
2
16350
20
345
109,0
93,4
0,86
4,06
2
20000
20
260
125,0
109,0
0,87
4,85
2
24200
20
65
150,0
130,0
0,87
7,22
3
28300
20
50
172,0
150,0
0,87
7,45
3
33100
20
400
2,7
34
4,2
43
6,6
42
10,0
86
11,3
64
15,1
70
18,8
79
21,4
54
25,7
82
29,5
80
G2
230/1/50
2,31
G4
400/3/50+N
1,79
G4
400/3/50+N
4,39
G4
400/3/50+N
4,65
G4
400/3/50+N
4,52
G4
400/3/50+N
8,78
G4
400/3/50+N
9,30
G4
400/3/50+N
9,03
G4
400/3/50+N
13,17
G4
400/3/50+N
13,95
dB(A)
dB(A)
dB(A)
dB(A)
dB(A)
dB(A)
kg
kg
60,3
60,3
45,7
41,6
50,8
41,6
196
196
66,9
66,9
47,0
43,1
52,6
43,1
230
230
70,2
70,2
50,5
46,5
56,0
46,5
290
290
70,8
70,8
52,7
48,7
58,2
48,7
332
332
75,9
75,9
56,6
53,0
62,0
53,0
332
332
74,0
74,0
54,3
50,2
59,8
50,2
410
410
72,1
72,1
54,1
50,1
59,5
50,1
465
465
77,5
77,5
58,1
54,6
63,6
54,6
515
515
78,8
78,8
59,1
55,0
64,6
55,0
578
578
76,0
76,0
57,9
53,9
63,4
53,9
656
656
M
F
1"
1/2"
1+1/4"
1/2"
1+1/2"
1/2"
1+1/2"
1/2"
2"
1/2"
2"
1/2"
2+1/2"
1/2"
2+1/2"
1/2"
3"
1/2"
3"
1/2"
154
F7
PLUS
K
180
F8
PLUS
K
210
F9
PLUS
K
280
F10
PLUS
K
180,0
154,0
0,86
6,90
3
33300
20
170
211,0
183,0
0,87
7,73
3
40100
20
20
279,0
240,0
0,86
10,41
4
51700
20
20
30,9
95
3
G4
400/3/50+N
13,95
36,2
46
3
G4
400/3/50+N
13,55
47,9
86
4
G4
400/3/50+N
18,06
76,0
63,4
53,9
795
555
81,1
67,2
58,1
910
635
81,7
67,8
58,8
1103
755
3"
1/2"
80
1/2"
80
1/2"
kW
kW
kW/kW
kW
n.
m3/h
Pa
Pa
m3/h
kPa
n.
A
VERSION
COOLING CAPACITY (1)
152,0
Total
kW
132,0
Sensible
kW
0,87
SHR
kW/kW
6,92
Power input Under
kW
3
Supply fans
n.
3
29000
Air flow
m /h
20
Nominal external static pressure Under Pa
70
Max external static pressure
Pa
Cooling coil
3
26,1
Water flow rate
m /h
65
Pressure drop - coil + valve
kPa
3
Air filters
n.
G4
Efficiency
400/3/50+N
Power supply
13,17
Max operating current (FLA)
A
Sound level - ISO 3744 (2)
79,1
On air delivery Under
dB(A)
65,0
On air intake Under
dB(A)
55,4
On front side Under
dB(A)
695
Net weight Under
kg
495
Net weight - Separate fan section
kg
Connections
3"
Water inlet/outlet - ISO 7/1 - R
M
Water inlet/outlet - DN - PN10 (3)
1/2"
Condensate discharge Rubber pipe F
THE COOLING CAPACITY DOES NOT CONSIDER THE SUPPLY FAN MOTOR THERMAL LOAD
1. Characteristics referred to entering air at 24C-50%RH with chilled water temperature 7-12C - 0% glycol.
2. Noise level at 1 meter in free field.
3. The counter-flange is not supplied. It is at Customer charge
62
NEXT EVO CW K
IT Cooling
TECHNICAL DATA - OPTIONAL ACCESSORIES
NEXT EVO CW K
SIZE
Electric heater
Capacity
Capacity steps
Oversized Electric heater
Capacity
Capacity steps
Humidifier
Steam capacity
Power input
Oversized Humidifier
Steam capacity
Power input
15
F1
-
25
F2
-
39
F3
-
59
F3P
-
66
F4
-
88
F5
-
109
F6
-
125
F7
-
150
F8
-
172
F9
-
154
F7
PLUS
180
F8
PLUS
210
F9
PLUS
280
F10
PLUS
kW
n.
5,1
1
5,1
1
6,0
2
6,0
2
9,0
3
13,5
3
13,5
3
13,5
3
18,0
3
18,0
3
18,0
3
18,0
3
27,0
3
27,0
3
kW
n.
3
2,3
3
2,3
3
2,3
3
2,3
8
6,0
8
6,0
8
6,0
15
11,3
15
11,3
15
11,3
15
11,3
15
11,3
15
11,3
15
11,3
kg/h
kW
---
11,0
10,0
18,1
16,5
26,4
24,0
36,8
33,4
46,5
42,5
64,2
59,0
69,5
63,3
84,7
76,9
101,0
92,6
109,0
98,8
129,0
118,0
150,0
136,0
193,0
176,0
kg/h
kW
12,6
6,0 (*)
24,1
6,0 (*)
36,2
6,0 (*)
53,8
6,0
75,3
11,3
95,1
11,3
126,0
11,3
148,0
--
166,0
--
193,0
--
212,0
--
247,0
--
297,0
--
--
THE COOLING CAPACITY DOES NOT CONSIDER THE SUPPLY FAN MOTOR THERMAL LOAD
(*) Only OVER version
63
NEXT EVO CW K
IT Cooling
650
785
1085
1085
1305
1630
1875
2175
2499
2899
675
675
775
930
930
930
930
930
930
930
1925
1925
1925
1925
1980
1980
1980
1980
1980
1980
a
2175
2499
2899
3510
b
930
930
930
930
c1
1980
1980
1980
1980
c2
600
600
600
600
c1
c2
a
64
NEXT EVO DX
NEXT EVO DX: Direct expansion close control air conditioners
with up-flow or down-flow air delivery.
Cooling Capacity: 7 102 kW
NEWSOFTWARE
NEXT EVO DX
rcgroupairconditioning
MAIN FEATURES
Precision air conditioner.
20 models available, 2 versions for a wide selection opportunity.
EER up to 4,47.
On/off scroll compressors.
Single and double refrigerant circuit.
R410A Refrigerant charge.
rotary compressor (size E1, E2).
AC plug-fans (size E3, E4, E5, E6, E7, E8).
OVER and UNDER versions.
Suitable for indoor installation.
MAIN BENEFITS
Units with single and double refrigerant circuits.
Availability of remote condensers with axial fans (TEAM MATE series)
and with plug fans (TEAM MATE PF series).
High EER.
Availability of EC plug-fans.
Availability of electronic expansion valves.
Availability of electric heater.
Availability of steam humidifier.
Availability of hot water heating coil.
Availability of extra circuit heating coil.
Complete set of optional accessories: filters, plenum, panels, stand.
Easily of maintenance.
R410A
EC
UP
FLOW
AC
DOWN
FLOW
INDOOR INSTALLATION
The machines are designed for indoor installation.
REMOTE CONDENSER
The units are designed to be matched with remote condensers with axial
fans (TEAM MATE series) or plug-fans (TEAM MATE PF series).
WORKING LIMITS
Room air temperature:
14C
minimum temperature with wet bulb.
24C
maximum temperature with wet bulb.
35C
maximum temperature with dry bulb.
Room air humidity:
20%RH minimum relative humidity.
70%RH maximum relative humidity.
f i f t y c o o l y e a r s
65
NEXT EVO DX
MAIN COMPONENTS
FRAMEWORK
Base in aluminium extrusion, painted with epoxy powders. Colour RAL
9005;
Frame in aluminium profile, painted with epoxy powders. The inner frame is
provided with seals for the panels. Colour RAL 9005;
Panels in galvanized steel sheet with protective surfaces treatment in
compliance with UNI ISO 9227/ASTMB117 and ISO 7253, and painted with
epoxy powders. Colour RAL 7016 hammered;
Panels insulated with polyurethane foam and seals to ensure air tight.
Hinged front panels with quick release removal system.
Total front access for routine maintenance.
Removable lateral and back side panels.
Air flow OVER version:
- Air intake from the front through honeycomb type grille and air delivery
from the top.
Air flow UNDER version:
- Air intake from the top and air delivery from the bottom.
Compartment for electrical panel on unit front for direct access to control
and regulation devices;
FILTER SECTION
Washable air filters with G4 efficiency, with cells in synthetic fibre and
metallic frame (EN 779-2002).
Air filters access:
OVER version
- Frontal access for all machines
UNDER version
- For machines size E1 E2 E3 frontal access
- For machine size E4 E5 E67 E7 E8 access from upper side
IT Cooling
ELECTRICAL PANEL
In accordance with EN60204-1 norms, suitable for indoor installation,
complete wit:
Main switch with door lock safety on frontal panel;.
Magnetothermic switches for supply fans. The supply fans equipped with
EC electric motor and dont require contactors.
Transformer for auxiliary circuit and microprocessor supply.
Terminals:
OUTLETS
- Voltage free deviating contact for General Alarm 1
- Voltage free contact for supply fans status.
INLETS
- Emergency unit stop with signalling on display (external alarm).
- External enabling.
Power supply 400/3/50+N.
CONTROL SYSTEM
Microprocessor control system with graphic display for control and monitor of
operating and alarms status. The system includes:
Built-in clock for alarms date and time displaying and storing;
Built-in memory for the storing of the intervened events (up to 100 events
recorded);
Predisposition for connectivity board housing ( RCcom MBUS/JBUS, LON,
BACnet for Ethernet (SNMP- TCP/IP), BACnet for MS/TP). The electronic
cards are optional accessories;
Main components hour-meter;
Non-volatile Flash memory for data storage in case of power supply faulty;
Menu with protection password;
LAN connection (max 15 units).
66
TEAM MATE
TEAM MATE PF
NEXT EVO DX
IT Cooling
COMMON OPTIONAL ACCESSORIES
SIZE
TEAM MATE remote condenser
TEAM MATE PF remote condenser
213 - Team Mate electrical power supply by internal unit
810 - Floor stand Hmax=350 mm
811 - Floor stand Hmax=450 mm
812 - Floor stand Hmax=510 mm
215 - Disposal F5 efficiency air filter
832 - Air supply plenum with F6 filters
833 - Air supply plenum with F7 filters
835 - Air supply plenum with F9 filters
836 - Air supply plenum with sound absorber
Air discharge plenum with frontal and lateral grilles
Air discharge plenum with frontal grille
761 - Air supply plenum with 5 closed sides
808 - Sandwich panels
945 -Air return plenum with Free Cooling damper
405 - Extra-Circuit system
514 - Water heater + 2 way valve
321 - Steam humidifier
1015 - Incresed umidifier
865 - Phases sequence relay
310 - Electric heater
1014- Increased electrical heater
909 - Clogged filters alarm
911 - Water presence alarm
913 - Additional water sensor (kit)
860 - T/rH sensor on air return
866 - T/rH external sensor
867 - T/rH remote sensor
610 - Noise deading cup on compressor
606 - Compr. power factor capacitor - 0,9
260 - Liquid solenoid valve
220 - Electronic expansion valve
101 - EC fan
923 - RC-Com MBUS/JBUS Serial board
926 - LON Serial board
931 - BACnet Ethernet - SNMP - TCP/IP Serial board
932 - BACnet MS/TP Serial board
1011 - Double serial interface
958 - Emergency microprocessor supply
863 - Remote terminal shared
930 - Remote graphic terminal kit
962 - Kit modem GSM
957 - Plantwatch without modem
RC CLOUD PLATFORM
E2
E3
E4
E5
E6
E7
E8
H0
H1
H2
H3
H4
H5
H5
H0
H1
H2
H3
H4
H5
H5
67
NEXT EVO DX
IT Cooling
TECHNICAL DATA
MODEL
007 P1
009 P1
011 P1
014 P1
016 P1
020 P1
022 P1
026 P1
032 P1
037 P1
041 P1
SIZE
E1
E1
E1
E2
E2
E3
E3
E3
E4
E4
E4
COOLING CAPACITY (1)
Total
kW
7,3
8,8
10,2
13,5
14,5
19,7
21,7
25,8
31,9
36,0
40,7
Sensible
kW
7,0
8,4
9,7
12,8
13,8
18,8
20,6
24,3
30,4
33,0
38,8
SHR
kW/kW
0,95
0,95
0,95
0,95
0,95
0,95
0,95
0,94
0,95
0,92
0,95
Unit power input
kW
1,73
2,16
2,62
3,39
3,78
4,41
5,34
6,55
7,42
8,35
9,78
Supply fans
n.
1
1
1
1
1
1
1
1
1
1
1
Air flow
m3/h
2500
2700
2800
4000
4200
5700
6100
6400
8450
8450
10350
Nominal external static pressure
Pa
20
20
20
20
20
20
20
20
20
20
20
Fans max external static pressure Pa
180
130
110
100
55
310
240
190
20
20
20
Compressors
rotary
rotary
rotary
rotary
rotary
scroll
scroll
scroll
scroll
scroll
scroll
Quantity
n.
1
1
1
1
1
1
1
1
1
1
1
Capacity steps
n.
1
1
1
1
1
1
1
1
1
1
1
Air filters
n.
1
1
1
1
1
2
2
2
2
2
2
Efficiency
G4
G4
G4
G4
G4
G4
G4
G4
G4
G4
G4
Refrigerant
R410A
R410A
R410A
R410A
R410A
R410A
R410A
R410A
R410A
R410A
R410A
Refrigerant charge (2)
kg
3,2
3,2
3,2
3,4
3,4
4,0
4,0
4,0
5,7
5,7
8,6
Gas circuits
n.
1
1
1
1
1
1
1
1
1
1
1
Power supply (**)
400/3/50+N 400/3/50+N 400/3/50+N 400/3/50+N 400/3/50+N 400/3/50+N 400/3/50+N 400/3/50+N 400/3/50+N 400/3/50+N 400/3/50+N
Max operating current (FLA)
A
6,1
7,0
7,2
8,5
9,1
15,4
18,8
20,1
22,2
25,7
30,4
Unit starting current (LRA)
A
33,3
40,3
37,5
54,5
54,5
66,9
77,9
103,9
130,9
141,9
122,0
Energy efficiency indexes (1)
EER
kW/kW
4,22
4,07
3,89
3,98
3,84
4,47
4,06
3,94
4,30
4,31
4,16
Sound pressure level - ISO 3744 (3)
On air delivery Under/Over
dB(A)
58,0
59,6
60,4
62,6
63,6
63,5
65,0
66,0
72,0
75,1
71,2
On air intake Over
dB(A)
49,8
50,2
51,9
51,3
53,0
53,9
57,7
55,1
57,8
58,9
58,8
Irradiated Over
dB(A)
40,2
41,4
42,4
40,4
41,7
42,4
45,5
44,0
48,6
51,3
49,4
On air intake Under
dB(A)
50,1
52,3
52,3
50,5
52,0
52,5
55,2
54,3
58,9
61,4
59,7
On front side Under
dB(A)
40,9
42,1
43,2
41,3
42,9
43,4
46,3
45,1
49,6
52,0
50,5
Net weight Over
kg
220
221
228
260
265
300
305
305
410
415
427
Net weight Under
kg
230
231
238
270
275
320
325
325
420
425
437
Remote condenser (4)
n.
TEAM MATE
Mod.
M 11
M 11
M 11
M 14
M 17
M 25
M 25
M 30
M 35
M 45
M 45
TEAM MATE PF
Mod.
T 11
T 11
T 11
T 14
T 21
T 24
T 24
T 33
T 38
T 44
T 44
Refrigerant connections
Gas delivery
ODS
16
16
16
16
16
18
18
18
22
22
28
Liquid return
ODS
12
12
12
12
12
16
16
16
16
16
22
Hydraulic connections - Condensate discharge F
1/2"
1/2"
1/2"
1/2"
1/2"
1/2"
1/2"
1/2"
1/2"
1/2"
1/2"
MODEL
045 P1
039 P2
D
E5
048 P2
D
E5
055 P2
D
E6
062 P2
D
E6
075 P2
D
E7
082 P2
D
E7
092 P2
D
E8
102 P2
D
E8
SIZE
E4
COOLING CAPACITY (1)
Total
kW
44,3
36,5
47,1
54,5
61,3
74,6
81,3
89,9
102,0
Sensible
kW
40,5
34,1
42,9
51,9
58,4
71,1
76,2
81,4
89,6
SHR
kW/kW
0,91
0,93
0,91
0,95
0,95
0,95
0,94
0,91
0,88
Unit power input
kW
10,78
8,59
11,69
13,20
14,77
17,68
19,59
21,56
25,37
Supply fans
n.
1
1
1
2
2
2
2
2
2
Air flow
m3/h
10350
8750
10850
15000
15600
20000
20000
20900
20900
20
20
20
20
20
20
20
20
20
Nominal external static pressure
Pa
20
20
20
137
70
20
20
20
20
Fans max external static pressure Pa
scroll
scroll
scroll
scroll
scroll
scroll
scroll
scroll
scroll
Compressors
1
2
2
2
2
2
2
2
2
Quantity
n.
1
2
2
2
2
2
2
2
2
Capacity steps
n.
2
3
3
3
3
4
4
5
5
Air filters
n.
G4
G4
G4
G4
G4
G4
G4
G4
G4
Efficiency
R410A
R410A
R410A
R410A
R410A
R410A
R410A
R410A
R410A
Refrigerant
8,6
9,0
9,0
9,8
9,8
16,2
16,2
17,4
17,4
Refrigerant charge (2)
kg
Gas circuits
n.
1
2
2
2
2
2
2
2
2
Power supply (**)
400/3/50+N 400/3/50+N 400/3/50+N 400/3/50+N 400/3/50+N 400/3/50+N 400/3/50+N 400/3/50+N 400/3/50+N
Max operating current (FLA)
A
36,7
27,8
35,7
40,1
44,3
53,7
60,9
73,5
79,8
Unit starting current (LRA)
A
144,0
78,7
94,0
123,0
152,0
168,6
151,0
179,0
216,0
Energy efficiency indexes (1)
EER
kW/kW
4,11
4,25
4,03
4,13
4,15
4,22
4,15
4,17
4,02
Sound pressure level - ISO 3744 (3)
On air delivery Under/Over
dB(A)
71,2
75,2
74,1
71,8
72,6
72,3
72,3
74,7
74,7
On air intake Over
dB(A)
57,6
59,0
59,2
58,5
60,3
60,6
61,3
62,6
63,4
Irradiated Over
dB(A)
48,0
51,5
50,5
48,7
49,9
50,7
51,0
53,0
53,3
On air intake Under
dB(A)
59,9
61,6
60,8
59,0
60,1
61,0
61,3
63,3
63,6
On front side Under
dB(A)
50,8
52,1
51,4
49,7
50,9
51,8
52,2
54,1
54,4
Net weight Over
kg
435
520
530
610
630
688
695
785
785
Net weight Under
kg
435
530
540
620
640
745
750
845
845
Remote condenser (4)
n.
TEAM MATE
Mod.
M 50
M 25
M 25
M 30
M 35
M 45
M 45
M 50
M 60
TEAM MATE PF
Mod.
T 58
T 24
T 33
T 33
T 38
T 38
T 58
T 58
T69
Refrigerant connections
Gas delivery
ODS
28
2x18
2x18
2x18
2x18
2x22
2x28
2x28
2x28
Liquid return
ODS
22
2x12
2x16
2x16
2x16
2x16
2x22
2x22
2x22
Hydraulic connections - Condensate discharge F
1/2"
1/2"
1/2"
1/2"
1/2"
1/2"
1/2"
1/2"
1/2"
THE COOLING CAPACITY DOES NOT CONSIDER THE SUPPLY FAN MOTOR THERMAL LOAD
1. Characteristics referred to entering air at 24C-45%RH; 45C condensing temperature.
2. Unit refrigerant charge. Remote condenser, connections pipes and optional are excluded.
3. Noise level at 1 meter in free field (external static pressure 50 Pa)
4. For matching to other remote air cooled condensers please refer to RC WORLD selection program
(**) The remote condenser has separated power supply
68
NEXT EVO DX
IT Cooling
TECHNICAL DATA - OPTIONAL ACCESSORIES
NEXT EVO DX
SIZE
Electric heater
Capacity
Capacity steps
Humidifier
Steam capacity
Power input
Extra circuit coil (1)
Total cooling capacity
Sensible cooling capacity
Heating coil (2)
Heating capacity
007 P1
009 P1
011 P1
014 P1
016 P1
020 P1
022 P1
026 P1
032 P1
037 P1
E1
E1
E1
E2
E2
E3
E3
E3
E4
E4
kW
n.
5,1
1,0
5,1
1,0
5,1
1,0
5,1
1,0
5,1
1,0
6,0
2,0
6,0
2,0
6,0
2,0
9,0
3,0
9,0
3,0
kg/h
kW
3
2,3
3
2,3
3
2,3
3
2,3
3
2,3
3
2,3
3
2,3
3
2,3
8
6,0
8
6,0
kW
kW
10,4
9,6
11,0
10,0
11,3
10,3
16,7
15,3
17,4
15,7
23,7
21,8
25,0
22,7
25,8
23,5
35,8
32,7
35,8
32,7
kW
22,9
24,1
24,7
33,6
34,7
48,8
51,1
52,7
75,1
75,1
041 P1
045 P1
039 P2 D
048 P2 D
055 P2 D
062 P2 D
075 P2 D
082 P2 D
092 P2 D
102 P2 D
E4
E4
E5
E5
E6
E6
E7
E7
E8
E8
kW
n.
9,0
3,0
9,0
3,0
13,5
3,0
13,5
3,0
13,5
3,0
13,5
3,0
18,0
3,0
18,0
3,0
18,0
3,0
18,0
3,0
kg/h
kW
8
6,0
8
6,0
8
6,0
8
6,0
8
6,0
8
6,0
8
6,0
8
6,0
8
6,0
8
6,0
kW
kW
41,5
37,7
41,5
37,7
42,4
36,8
50,0
44,2
61,1
55,4
61,1
55,4
94,2
80,0
94,2
80,0
105,0
87,1
105,0
87,1
kW
86,2
86,2
85,0
98,8
131,0
134,0
160,0
160,0
175,0
175,0
NEXT EVO DX
SIZE
Electric heater
Capacity
Capacity steps
Humidifier
Steam capacity
Power input
Extra circuit coil (1)
Total cooling capacity
Sensible cooling capacity
Heating coil (2)
Heating capacity
1.
2.
Characteristics referred to entering air at 24C 50%RH with chiller water at 7/12,5 C and 0% glycol
Characteristics referred to entering air at 20C with hot water at 75/60C
69
NEXT EVO DX
IT Cooling
a
650
785
1085
1305
1630
1875
2175
2499
b
675
675
775
930
930
930
930
930
c
1925
1925
1925
1980
1980
1980
1980
1980
70
NEXT DW
NEXT DW: Direct expansion close control air conditioners with built-in water cooled condenser
equipped with scroll compressors and Plug-fans.
Cooling Capacity: 7 108 kW
NEXT DW
rcgroupairconditioning
MAIN FEATURES
Precision air conditioner.
41 models available, 2 versions for a wide selection opportunity.
EER up to 4,89.
On/off scroll compressors.
Single and double refrigerant circuit.
Built in water cooled condenser.
R410A Refrigerant charge.
EC plug-fans (size H0, H1, H2, H3).
AC plug-fans (size H4, H5, H6, H7).
OVER and UNDER versions.
Suitable for indoor installation.
MAIN BENEFITS
Units with single and double refrigerant circuits.
High EER.
High efficiency at partial load.
Availability of electric heater.
Availability of steam humidifier.
Availability of hot water heating coil.
Availability of extra circuit heating coil.
Availability of indirect Free Cooling system.
Complete set of optional accessories: filters, plenum, panels, stand.
Easily of maintenance.
R410A
EC
UP
FLOW
AC
DOWN
FLOW
INDOOR INSTALLATION
The machines are designed for indoor installation.
WORKING LIMITS
Room air temperature:
14C
minimum temperature with wet bulb.
24C
maximum temperature with wet bulb.
35C
maximum temperature with dry bulb.
Room air humidity:
20%RH minimum relative humidity.
75%RH maximum relative humidity.
Water cooled condenser:
Water temperature:
30/50C Outlet temperature range.
f i f t y c o o l y e a r s
71
NEXT DW
IT Cooling
MAIN COMPONENTS
FRAMEWORK
Base in aluminium extrusion, painted with epoxy powders.
Inner frame and upper frame in aluminium profile, painted with epoxy
powders. The inner frame is provided with seals to ensure air tight with the
panels.
Galvanized steel sheet panels externally coated with PVC film and
internally insulated with noise absorption material.
The panels are fixed to the frame with non visible mounting system.
Electric board in separate technical compartment on the machine front
(Size H0, H1, H2, H3).
Separate technical compartment on machine front for electric board,
refrigerant and hydraulic connections and control and regulation devices
(size H4, H5, H6, H7)
Colour: RAL 9005 for base and frame
Similar to RAL7015 for panels, with hammered finish
OVER version
- Air intake from the front through honeycomb type grille and air delivery
from the top.
- Washable air pre-filters with G2 efficiency, with cells in synthetic fibre
(size H0 excluded).
UNDER version
Machine size H0
- Air intake from the front through honeycomb type grille and air delivery
from the bottom.
Machine size H1, H2, H3, H4, H5, H6, H7
- Air intake from the top and air delivery from the bottom.
REFRIGERANT CIRCUIT
Components for each refrigerant circuit:
Thermostatic expansion valve.
Sight glass.
Filter dryer on liquid line.
Pressure transducers with indication, control and protection functions, on
low and high refrigerant pressure.
High pressure safety switch with manual reset.
Liquid receiver with accessories.
Refrigerant circuit with copper tubing with anticondensate insulation of the
suction line.
Plastic capillary hoses for pressure sensors connection.
R410A refrigerant charge.
COMPRESSORS
Orbiting spiral (SCROLL) hermetic compressors with spiral profile optimized
for R410A refrigerant.
ON / OFF capacity control (0 / 100% each compressor).
2-pole 3-phase electric motor with direct on line starting.
Crankcase heater.
Electric motor thermal protection via internal winding temperature sensors.
Terminal box with IP54 enclosure class.
Rubber supports.
CONTROL SYSTEM
MP.COM microprocessor system with graphic display for control and
monitor of operating and alarms status. The system includes:
- Voltage free contact for remote general alarm.
- Main components hour-meter.
- Nonvolatile Flash memory for data storage.
- Menu with protection password.
- LAN connection.
ELECTRICAL PANEL
In accordance with EN60204-1 norms complete with:
Main switch with door lock safety.
Magnetothermic switch for each compressor.
Magnetothermic switches for fans.
Contactors for each load.
The supply fans equipped with EC electric motor are not supplied with
contactors.
Transformer for auxiliary circuit and microprocessor supply.
Panel with machine controls.
Power supply:
- 230/1/50 for model 006 P1 S H0.
- 400/3/50 for the other models.
FILTER SECTION
Size H0
Washable air filters with G3 efficiency, with cells in synthetic fibre and
metallic frame (EN 779-2002).
Size H1, H2, H3, H4, H5, H6, H7
Washable air filters with G4 efficiency, with cells in synthetic fibre and
metallic frame (EN 779-2002).
EVAPORATING SECTION
Heat exchanger coil with internally corrugated copper tubes and high
efficiency aluminium fins, specifically developed to provide high heat
transfer and lower pressure drops.
- With single refrigerant circuit for S version machines.
- With double refrigerant circuit for DC version machines.
Frame in galvanized steel.
Condensate tray in peraluman with PVC flexible discharge pipe.
CONDENSING SECTION
Copper brazed plate type with cover plates, plates and connections in AISI
316 stainless steel.
010V proportional signal to manage the condensing control system of the
2-way motorized valve. The valve is an optional accessory.
FANS SECTION
Centrifugal fans with backward curved blades, single suction and without
scroll housings (Plug-fans), directly coupled to external rotor electric motor.
- Size H0, H1, H2, H3:
Brushless type synchronous EC motor with integrated electronic
commutated system and continuous variation of the rotation speed.
The motor rotation control is obtained with the EC system (Electronic
Commutation) that manage the motor according to the 010V
proportional signal coming from the microprocessor control.
- Size H4, H5, H6, H7:
Fans fed through an autotransformer that allows the manual selection of
7 rotation speed.
Temperature sensors on air intake.
Fan guard with rubber support (UNDER version)
72
NEXT DW
IT Cooling
COMMON OPTIONAL ACCESSORIES
SIZE
VERSION
DRY COOLER
DRY COOLER PF
409 - FC Free Cooling system
540 - Pumping group single pump
541 - Pumping group double pump
512 - Water regulating valve
810 - Floor stand Hmax=350 mm
811 - Floor stand Hmax=450 mm
812 - Floor stand Hmax=510 mm
215 - Disposal F5 efficiency air filter
832 - Air supply plenum with F6 filters
833 - Air supply plenum with F7 filters
835 - Air supply plenum with F9 filters
836 - Air supply plenum with sound absorber
945 -Air return plenum with Free Cooling damper
843 - Motorized damper with frame
101 - EC fan
912 -Air flow loss alarm EC Fan
220 - Electronic expansion valve
260 - Liquid solenoid valve
505 - ON-OFF Hot gas reh.system
405 - Extra-Circuit system
321 - Steam humidifier
322 - Dehumification system
310 - Electric heater
509 - Hot water heating coil + 3 way valve
909 - Clogged filters alarm
910 - Air flow loss alarm
913 - Additional water sensor (kit)
911 - Water presence alarm
610 - Noise deading cup on compressor
606 - Compr. power factor capacitor - 0,9
211 - Capacity control
865 - Phase control relay
919 - Clock card
922 - Driver card
923 - RC-Com MBUS/JBUS Serial board
926 - LON Serial board
931 - BACnet Ethernet - SNMP - TCP/IP Serial board
932 - BACnet MS/TP Serial board
934 - MP.COM expansion card
942 - Serial card for GSM Modem
943 - Data Logger
904 - Temperature/Humidity sensor
906 - Outlet air temperature indication
907 - Current indication
908 - Voltage indication
863 - Remote terminal shared
930 - Remote graphic terminal kit
962 - Kit modem GSM
957 - Plantwatch without modem
RC CLOUD PLATFORM
H0
S
H1
S
H2
S
H3
S
H4
S
H5
S
H5
D
H6
S
H6
D
H7
S
H7
D
H7
S
H7
D
H0
S
H1
S
H2
S
H3
S
H4
S
H5
S
H5
S
H5
S
H5
DC
H6
S
H6
DC
H7
S
H7
DC
H0
S
H1
S
H2
S
H3
S
H4
S
H5
S
H5
S
H5
S
H5
DC
H6
S
H6
DC
H7
S
H7
DC
73
NEXT DW
IT Cooling
TECHNICAL DATA
MODEL
SIZE
COOLING CAPACITY (1)
Total
Sensible
SHR
Unit power input
Condenser water flow rate
Condenser pressure drop
Supply fans
Air flow
Nominal external static pressure
Fans max external static pressure
Compressors
Quantity
Capacity steps
Air filters
Efficiency
Refrigerant
Refrigerant charge (2)
Gas circuits
Power supply
Max operating current (FLA)
Unit starting current (LRA)
Energy efficiency indexes (1)
EER
Sound pressure level - ISO 3744 (3)
On air delivery Under/Over
On air intake Over
Irradiated Over
On air intake Under
On front side Under
Net weight Over
Net weight Under
Connections - ISO 228/1 G
Condenser water inlet/outlet
Condensate discharge - Rubber pipe
kW
kW
kW/kW
kW
m3/h
kPa
n.
m3/h
Pa
Pa
n.
n.
n.
kg
n.
A
A
008.P1
S
H0
010.P1
S
H0
007.P1
S
H1
009.P1
S
H1
011.P1
S
H1
013.P1
S
H1
014.P1
S
H2
015.P1
S
H2
017.P1
S
H2
019.P1
S
H3
6,9
5,8
0,84
1,5
1,2
13
1
1580
30
186
8,2
6,7
0,82
1,8
1,4
18
1
1800
30
110
9,9
7,7
0,78
2,2
1,7
15
1
2000
30
32
7,6
7,2
0,95
1,6
1,3
15
1
2273
50
215
9,0
8,6
0,95
1,9
1,5
20
1
2653
50
118
10,6
9,4
0,89
2,3
1,8
16
1
2653
50
118
12,0
10,0
0,83
2,6
2,1
21
1
2653
50
118
13,1
12,5
0,95
2,7
2,2
18
1
3955
50
282
15,8
14,0
0,89
3,3
2,7
26
1
3955
50
282
18,4
15,3
0,83
3,8
3,1
35
1
3955
50
282
18,4
17,4
0,95
4,3
3,2
8
1
5460
50
600
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
2
G3
G3
G3
G4
G4
G4
G4
G4
G4
G4
G4
R410A
R410A
R410A
R410A
R410A
R410A
R410A
R410A
R410A
R410A
R410A
2,6
2,6
2,6
4,8
4,8
4,8
4,8
5,9
5,9
5,9
7,5
1
1
1
1
1
1
1
1
1
1
1
230/1/50 400/3/50+N 400/3/50+N 400/3/50+N 400/3/50+N 400/3/50+N 400/3/50+N 400/3/50+N 400/3/50+N 400/3/50+N 400/3/50+N
14,8
7,7
8,7
7,2
8,6
9,7
10,7
10,4
12,8
14,4
16,9
61,3
39,3
47,3
30,2
40,2
48,2
45,2
44,9
53,9
65,9
68,3
kW/kW
4,49
4,60
4,49
4,89
4,65
4,57
4,56
4,85
4,77
4,83
4,30
dB(A)
dB(A)
dB(A)
dB(A)
dB(A)
kg
kg
55,7
50,7
39,5
50,7
50,7
161
161
58,3
52,5
41,5
52,5
52,5
161
161
60,4
54,6
43,6
54,6
54,6
161
161
56,7
49,7
39,7
49,7
40,4
187
193
59,7
50,6
41,9
51,9
42,6
190
197
59,7
51,9
42,4
51,9
42,6
191
198
59,7
51,9
42,4
52,4
43,1
192
199
64,7
53,9
46,6
56,5
47,1
245
255
64,7
53,9
46,6
56,5
47,1
247
257
64,7
55,5
46,8
56,9
47,6
248
259
65,2
55,7
47,2
57,3
48,0
304
315
M
F
1"
1/2"
1"
1/2"
1"
1/2"
1"
1/2"
1"
1/2"
1"
1/2"
1"
1/2"
1+1/2"
1/2"
1+1/2"
1/2"
1+1/2"
1/2"
1+1/2"
1/2"
021.P1
S
H3
023.P1
S
H3
025.P1
S
H4
029.P1
S
H4
033.P1
S
H4
038.P1
S
H5
040.P1
S
H5
045.P1
S
H5
049.P1
S
H5
026.P2
DC
H5
028.P2
DC
H5
20,1
18,7
0,93
5,2
3,6
9
1
5460
50
600
22,4
19,6
0,88
5,9
4,0
12
1
5460
50
600
27,2
24,9
0,92
6,2
4,6
13
1
7160
50
95
30,7
26,7
0,87
6,8
5,2
17
1
7440
50
50
35,9
29,4
0,82
7,7
6,1
22
1
7440
50
50
37,7
35,5
0,94
8,5
6,4
15
1
10440
50
136
41,4
37,0
0,89
9,4
7,0
18
1
10440
50
136
45,1
38,4
0,85
10,5
7,7
21
1
10440
50
136
52,5
40,5
0,77
12,2
9,0
19
1
10440
50
136
25,7
23,8
0,93
5,7
4,4
11
1
7110
50
172
32,7
31,1
0,95
7,9
5,6
17
1
10440
50
136
MODEL
SIZE
COOLING CAPACITY (1)
Total
Sensible
SHR
Unit power input
Condenser water flow rate
Condenser pressure drop
Supply fans
Air flow
Nominal external static pressure
Fans max external static pressure
Compressors
Quantity
Capacity steps
Air filters
Efficiency
Refrigerant
Refrigerant charge (2)
Gas circuits
Power supply
Max operating current (FLA)
Unit starting current (LRA)
Energy efficiency indexes (1)
EER
Sound pressure level - ISO 3744 (3)
On air delivery Under/Over
On air intake Over
Irradiated Over
On air intake Under
On front side Under
Net weight Over
Net weight Under
Connections - ISO 228/1 G
Condenser water inlet/outlet
Condensate discharge - Rubber pipe
006.P1
S
H0
kW
kW
kW/kW
kW
m3/h
kPa
n.
m3/h
Pa
Pa
n.
n.
n.
kg
n.
A
A
1
1
1
1
1
1
1
1
1
2
2
1
1
1
1
1
1
1
1
1
2
2
2
2
2
2
2
2
2
2
2
2
2
G4
G4
G4
G4
G4
G4
G4
G4
G4
G4
G4
R410A
R410A
R410A
R410A
R410A
R410A
R410A
R410A
R410A
R410A
R410A
7,5
7,5
9,3
9,3
9,3
15,3
15,4
15,5
15,9
9,9
10,2
1
1
1
1
1
1
1
1
1
2
2
400/3/50+N 400/3/50+N 400/3/50+N 400/3/50+N 400/3/50+N 400/3/50+N 400/3/50+N 400/3/50+N 400/3/50+N 400/3/50+N 400/3/50+N
20,3
20,3
19,5
24,7
25,7
27,5
30,7
37,0
40,1
19,5
26,0
79,3
105,3
97,6
113,5
120,5
122,2
122,2
144,2
178,2
53,6
66,2
kW/kW
3,90
3,82
4,37
4,49
4,67
4,41
4,39
4,31
4,31
4,52
4,14
dB(A)
dB(A)
dB(A)
dB(A)
dB(A)
kg
kg
65,2
58,4
48,2
58,2
49,0
307
318
65,2
56,3
47,4
57,5
48,2
308
319
69,2
58,1
51,1
61,0
51,6
422
442
72,2
60,7
54,1
62,6
53,3
422
45
72,2
60,7
54,1
62,6
53,3
423
443
74,9
62,6
56,8
66,4
57,0
478
494
74,9
62,9
56,8
66,5
57,1
478
494
74,9
63,2
56,8
66,5
57,2
478
494
74,9
63,5
56,8
67,2
57,8
486
502
69,1
57,7
51,0
61,1
51,8
456
472
74,9
62,6
56,8
66,5
57,0
458
474
M
F
1+1/2"
1/2"
1+1/2"
1/2"
1+1/2"
1/2"
1+1/2"
1/2"
1+1/2"
1/2"
2"
1/2"
2"
1/2"
2"
1/2"
2"
1/2"
1+1/2"
1/2"
1+1/2"
1/2"
THE COOLING CAPACITY DOES NOT CONSIDER THE SUPPLY FAN MOTOR THERMAL LOAD
1. Characteristics referred to entering air at 24C-50%RH; water to the condenser 30-36C
2. Unit refrigerant charge optional excluded.
3. Noise level at 1 meter in free field (external static pressure 50 Pa)
4. Characteristics referred to entering air at 24C 50%RH with chiller water at 7/12,5 C and 0% glycol
5. Characteristics referred to entering air at 20C with hot water at 75/60C
74
NEXT DW
IT Cooling
TECHNICAL DATA
MODEL
SIZE
COOLING CAPACITY (1)
Total
Sensible
SHR
Unit power input
Condenser water flow rate
Condenser pressure drop
Supply fans
Air flow
Nominal external static pressure
Fans max external static pressure
Compressors
Quantity
Capacity steps
Air filters
Efficiency
Refrigerant
Refrigerant charge (2)
Gas circuits
Power supply
Max operating current (FLA)
Unit starting current (LRA)
Energy efficiency indexes (1)
EER
Sound pressure level - ISO 3744 (3)
On air delivery Under/Over
On air intake Over
Irradiated Over
On air intake Under
On front side Under
Net weight Over
Net weight Under
Connections - ISO 228/1 G
Condenser water inlet/outlet
Condensate discharge - Rubber pipe
kW
kW
kW/kW
kW
m3/h
kPa
n.
m3/h
Pa
Pa
n.
n.
n.
kg
n.
A
A
036.P2
DC
H5
042.P2
DC
H6
048.P2
S
H6
048.P2
DC
H6
052.P2
S
H6
052.P2
DC
H6
060.P2
S
H6
060.P2
DC
H6
064.P2
S
H6
064.P2
DC
H6
35,7
33,5
0,94
8,9
6,1
21
1
10440
50
136
41,7
37,1
0,89
10,2
7,2
29
1
10440
50
136
44,7
40,9
0,91
10,0
7,6
21
2
11310
50
313
50,0
42,9
0,86
11,2
8,6
26
2
11310
50
313
50,2
43,0
0,86
11,1
8,6
23
2
11310
50
313
54,7
48,8
0,89
12,7
9,4
30
2
13480
50
170
55,0
48,9
0,89
12,6
9,4
27
2
13480
50
170
62,6
53,8
0,86
13,9
10,7
25
2
14500
50
94
62,7
53,8
0,86
13,9
10,7
25
2
14500
50
94
64,4
58,9
0,91
13,9
11,0
27
2
16000
50
50
65,2
58,9
0,90
13,9
11,0
27
2
16000
50
50
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
3
3
3
3
3
3
3
3
3
G4
G4
G4
G4
G4
G4
G4
G4
G4
G4
G4
R410A
R410A
R410A
R410A
R410A
R410A
R410A
R410A
R410A
R410A
R410A
10,7
10,9
19,9
19,7
19,9
20,2
20,4
20,8
20,9
21,4
21,5
2
2
2
1
2
1
2
1
2
1
2
400/3/50+N 400/3/50+N 400/3/50+N 400/3/50+N 400/3/50+N 400/3/50+N 400/3/50+N 400/3/50+N 400/3/50+N 400/3/50+N 400/3/50+N
29,2
35,9
37,0
37,0
37,0
39,1
39,1
49,6
49,6
49,6
49,6
80,2
94,2
95,2
121,2
121,2
116,2
116,2
137,2
137,2
137,2
137,2
kW/kW
4,01
4,07
4,48
4,47
4,52
4,31
4,37
4,50
4,50
4,63
4,68
dB(A)
dB(A)
dB(A)
dB(A)
dB(A)
kg
kg
74,9
62,6
56,8
66,6
57,2
458
474
74,9
64,0
57,0
67,1
57,8
461
477
67,3
61,3
52,4
62,0
53,0
565
591
67,3
59,0
50,7
60,6
51,5
567
593
67,3
59,0
50,7
60,6
51,5
567
593
70,8
60,3
53,0
63,1
53,9
670
696
70,8
60,3
53,0
63,1
53,9
670
696
72,5
62,2
54,8
66,6
57,3
670
696
72,5
62,2
54,8
66,6
57,3
670
696
75,4
63,8
57,3
67,3
58,0
685
711
75,4
63,8
57,3
67,3
58,0
685
711
M
F
1+1/2"
1/2"
1+1/2"
1/2"
2"
1/2"
2"
1/2"
2"
1/2"
2"
1/2"
2"
1/2"
2"
1/2"
2"
1/2"
2"
1/2"
2"
1/2"
072.P2
S
H7
072.P2
DC
H7
082.P2
S
H7
082.P2
DC
H7
092.P2
S
H7
092.P2
DC
H7
100.P2
S
H7
100.P2
DC
H7
76,6
67,3
0,88
16,6
13,0
37
2
17610
50
346
76,8
67,3
0,88
16,5
13,0
37
2
17610
50
346
86,9
77,7
0,89
19,1
14,7
36
2
20870
50
136
87,3
77,8
0,89
18,9
14,7
21
2
20870
50
136
95,9
83,4
0,87
21,0
16,3
23
2
22040
50
50
96,1
83,5
0,87
21,0
16,3
25
2
22040
50
50
108,0
84,6
0,78
24,7
18,5
29
2
22040
50
50
108,0
84,7
0,78
24,5
18,5
32
2
22040
50
50
MODEL
SIZE
COOLING CAPACITY (1)
Total
Sensible
SHR
Unit power input
Condenser water flow rate
Condenser pressure drop
Supply fans
Air flow
Nominal external static pressure
Fans max external static pressure
Compressors
Quantity
Capacity steps
Air filters
Efficiency
Refrigerant
Refrigerant charge (2)
Gas circuits
Power supply
Max operating current (FLA)
Unit starting current (LRA)
Energy efficiency indexes (1)
EER
Sound pressure level - ISO 3744 (3)
On air delivery Under/Over
On air intake Over
Irradiated Over
On air intake Under
On front side Under
Net weight Over
Net weight Under
Connections - ISO 228/1 G
Condenser water inlet/outlet
Condensate discharge - Rubber pipe
032.P2
DC
H5
kW
kW
kW/kW
kW
m3/h
kPa
n.
m3/h
Pa
Pa
n.
n.
n.
kg
n.
A
A
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
4
4
4
4
4
4
4
4
G4
G4
G4
G4
G4
G4
G4
G4
R410A
R410A
R410A
R410A
R410A
R410A
R410A
R410A
27,7
27,8
28
28,7
28,6
28,7
28,8
28,9
1
2
1
2
1
2
1
2
400/3/50+N 400/3/50+N 400/3/50+N 400/3/50+N 400/3/50+N 400/3/50+N 400/3/50+N 400/3/50+N
55,0
55,0
61,3
61,3
73,9
73,9
80,2
80,2
148,4
148,4
151,4
151,4
179,4
179,4
216,4
216,4
kW/kW
4,62
4,66
4,55
4,62
4,56
4,57
4,38
4,40
dB(A)
dB(A)
dB(A)
dB(A)
dB(A)
kg
kg
73,1
62,5
55,3
65,4
56,1
772
805
73,1
62,5
55,3
65,4
56,1
772
805
77,9
65,9
59,8
69,7
60,3
778
812
77,9
65,9
59,8
69,7
60,3
779
813
79,7
67,5
61,6
71,4
62,0
786
819
79,7
67,5
61,6
71,4
62,0
786
819
79,7
67,7
61,6
71,5
62,1
815
848
79,7
67,7
61,6
71,5
62,1
815
848
M
F
2"
1/2"
2"
1/2"
2"
1/2"
2"
1/2"
2"
1/2"
2"
1/2"
2"
1/2"
2"
1/2"
THE COOLING CAPACITY DOES NOT CONSIDER THE SUPPLY FAN MOTOR THERMAL LOAD
1. Characteristics referred to entering air at 24C-50%RH; water to the condenser 30-36C
2. Unit refrigerant charge optional excluded.
3. Noise level at 1 meter in free field (external static pressure 50 Pa)
4. Characteristics referred to entering air at 24C 50%RH with chiller water at 7/12,5 C and 0% glycol
5. Characteristics referred to entering air at 20C with hot water at 75/60C
75
NEXT DW
IT Cooling
006.P1 008.P1 010.P1 007.P1 009.P1 011.P1 013.P1 014.P1 015.P1 017.P1 019.P1 021.P1 023.P1 025.P1 029.P1
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
H0
H0
H0
H1
H1
H1
H1
H2
H2
H2
H3
H3
H3
H4
H4
---- ON-OFF ON-OFF ON-OFF ON-OFF ON-OFF ON-OFF ON-OFF ON-OFF ON-OFF ON-OFF ON-OFF ON-OFF
5,4
6,6
8,3
9,9
9,6
12,6 14,4
14
16,5 19,7 20,8 24,3
----
kW
kW
n.
2,6
1
2,6
1
2,6
1
5,1
1
5,1
1
5,1
1
5,1
1
5,1
1
5,1
1
5,1
1
5,1
2
5,1
2
5,1
2
9
2
9
2
kg/h
kW
2
1,4
2
1,4
2
1,4
3
2,3
3
2,3
3
2,3
3
2,3
3
2,3
3
2,3
3
2,3
3
2,3
3
2,3
3
2,3
8
6
8
6
kW
kW
---
---
---
9,4
8,3
10,6
9,2
10,6
9,2
10,6
9,2
15,0
13,1
15,0
13,1
15,0
13,1
22,8
20,1
22,8
20,1
22,8
20,1
29,2
25,5
30,0
26,2
kW
10,3
11,1
11,9
16,6
18,3
18,3
18,3
25,1
25,1
26,9
39,1
39,1
39,1
49,5
50,7
NEXT DW
SIZE
Hot gas reheating system
Heating capacity
Electric heater
Capacity
Capacity steps
Humidifier
Steam capacity
Power input
Extra circuit coil (1)
Total cooling capacity
Sensible cooling capacity
Heating coil (2)
Heating capacity
033.P1 038.P1 040.P1 045.P1 049.P1 026.P2 028.P2 032.P2 036.P2 042.P2 048.P2 048.P2 052.P2 052.P2 060.P2
S
S
S
S
S
DC
DC
DC
DC
DC
S
DC
S
DC
S
H4
H5
H5
H5
H5
H5
H5
H5
H5
H6
H6
H6
H6
H6
H6
ON-OFF ON-OFF ON-OFF ON-OFF ON-OFF ON-OFF ON-OFF ON-OFF ON-OFF ON-OFF ON-OFF ON-OFF ON-OFF ON-OFF ON-OFF
36,1 42,1 14,5 14,5 16,5 16,5 16,3 16,3 16,3 20,7 20,7 24,3
28,2
28
32
kW
kW
n.
9
2
13,5
2
13,5
2
13,5
2
13,5
2
13,5
2
13,5
2
13,5
2
13,5
2
13,5
2
13,5
2
13,5
2
13,5
2
13,5
2
13,5
2
kg/h
kW
8
6
8
6
8
6
8
6
8
6
8
6
8
6
8
6
8
6
15
11,3
15
11,3
15
11,3
15
11,3
15
11,3
15
11,3
kW
kW
30,0
26,2
40,4
35,3
40,4
35,3
40,4
35,3
40,4
35,3
30,5
26,8
40,4
35,3
40,4
35,3
40,4
35,3
48,9
42,8
49,2
43,0
49,2
43,0
55,7
48,6
55,7
48,6
58,7
51,3
kW
50,7
72,3
72,3
72,3
72,3
56,2
72,1
72,3
72,3
91,0
91,0
91,4
102,0
102,0
107,0
NEXT DW
SIZE
Hot gas reheating system
Heating capacity
Electric heater
Capacity
Capacity steps
Humidifier
Steam capacity
Power input
Extra circuit coil (1)
Total cooling capacity
Sensible cooling capacity
Heating coil (2)
Heating capacity
1.
2.
060.P2 064.P2 064.P2 072.P2 072.P2 082.P2 082.P2 092.P2 092.P2 100.P2 100.P2
DC
S
DC
S
DC
S
DC
S
DC
S
DC
H6
H6
H6
H7
H7
H7
H7
H7
H7
H7
H7
ON-OFF ON-OFF ON-OFF ON-OFF ON-OFF ON-OFF ON-OFF ON-OFF ON-OFF ON-OFF ON-OFF
24,3 23,8 23,8 27,7 27,7 31,3 31,3 35,5 35,5 42,2 42,2
kW
kW
n.
13,5
2
13,5
2
13,5
2
13,5
2
13,5
2
13,5
2
13,5
2
13,5
2
13,5
2
13,5
2
13,5
2
kg/h
kW
15
11,3
15
11,3
15
11,3
15
11,3
15
11,3
15
11,3
15
11,3
15
11,3
15
11,3
15
11,3
15
11,3
kW
kW
58,7
51,3
62,9
55,0
62,9
55,0
80,4
69,0
80,4
69,0
90,9
79,3
90,9
79,3
94,4
82,8
94,4
82,8
94,4
82,8
94,4
82,8
kW
107,0
114,0
114,0
131,0
131,0
146,0
146,0
152,0
152,0
152,0
152,0
Characteristics referred to entering air at 24C 50%RH with chiller water at 7/12,5 C and 0% glycol
Characteristics referred to entering air at 20C with hot water at 75/60C
a
655
650
785
1085
1320
1620
2155
2690
b
420
650
650
750
860
860
860
860
c
1680
1925
1925
1925
1980
1980
1980
1980
76
NEXT DL
NEXT DL: Close control air conditioners with displacement air delivery
with remote condenser, or built in water cooled condenser
or for chilled water feeding
Cooling capacity: 7,7 51,4 kW
NEXT DL
rcgroupairconditioning
MAIN FEATURES
Precision air conditioner.
Displacement air delivery (DL).
35 models available, 3 versions for a wide selection opportunity.
Available in three versions: for matching with remote air cooled
condenser (DX), with built-in water cooled condenser (DW), for chilled
water feeding (CW).
EC plug fans.
Suitable for indoor installation
DX Version:
EER up to 3,74.
On/off scroll compressors
Single refrigerant circuit.
R410A refrigerant charge.
DW Version:
EER up to 5,25.
On/off scroll compressors
Single refrigerant circuit.
R410A refrigerant charge.
Built in water cooled condenser
CW Version:
Chilled water feeding
Two way chilled water valve
MAIN BENEFITS
Wide selection opportunity.
High EER
High efficiency at partial load.
Availability of electric heater.
Availability of steam humidifier.
Complete set of optional accessories: filters, plenum, panels, stand.
RCGROUP SpA G_ITC_RCW8.4
CHILLED
WATER
R410A
EC
DISPLA
CEMENT
Easily of maintenance.
INDOOR INSTALLATION
The machines are designed for indoor installation.
WORKING LIMITS
Room air temperature:
14C
minimum temperature with wet bulb.
24C
maximum temperature with wet bulb.
35C
maximum temperature with dry bulb.
Room air humidity:
20%RH minimum relative humidity.
75%RH maximum relative humidity.
Water cooled condenser:
Water temperature:
30/50C Outlet temperature range.
f i f t y c o o l y e a r s
77
NEXT DL
NEXT DX DL / NEXT DW DL MAIN COMPONENTS
FRAMEWORK
Base in aluminium extrusion, painted with epoxy powders.
Inner frame and upper frame in aluminium profile, painted with epoxy
powders. The inner frame is provided with seals to ensure air tight with the
panels.
Galvanized steel sheet panels externally coated with PVC film and
internally insulated with noise absorption material.
The panels are fixed to the frame with non visible mounting system.
Electric board in separate technical compartment on the machine front.
Colour: RAL 9005 for base and frame
Similar to RAL7015 for panels, with hammered finish
Air intake from the top and air delivery from the front (displacement).
COMPRESSORS
Orbiting spiral (SCROLL) hermetic compressors with spiral profile optimized
for R410A refrigerant.
ON / OFF capacity control (0 / 100% each compressor).
2-pole 3-phase electric motor with direct on line starting.
Crankcase heater.
Electric motor thermal protection via internal winding temperature sensors.
Terminal box with IP54 enclosure class.
Rubber supports.
IT Cooling
CONTROL SYSTEM
MP.COM microprocessor system with graphic display for control and
monitor of operating and alarms status. The system includes:
- Voltage free contact for remote general alarm.
- Main components hour-meter.
- Nonvolatile Flash memory for data storage.
- Menu with protection password.
- LAN connection.
TO BE MATCHED WITH REMOTE CONDENSER
The NEXT DX DL are designed to be matched with remote condensers with
axial fans (TEAM MATE series) or plug-fans (TEAM MATE PF series).
TEAM MATE
TEAM MATE PF
FILTER SECTION
Washable air filters with G4 efficiency, with cells in synthetic fibre and
metallic frame (EN 779-2002).
EVAPORATING SECTION
Heat exchanger coil with internally corrugated copper tubes and high
efficiency aluminium fins, specifically developed to provide high heat
transfer and lower pressure drops.
Single refrigerant circuit.
Frame in galvanized steel.
Condensate tray in peraluman with PVC flexible discharge pipe.
FANS SECTION
Centrifugal fans with backward curved blades, single suction and without
scroll housings (Plug-fans), directly coupled to external rotor electric motor.
Brushless type synchronous EC motor with integrated electronic
commutated system and continuous variation of the rotation speed.
The motor rotation control is obtained with the EC system (Electronic
Commutation) that manage the motor according to the 010V proportional
signal coming from the microprocessor control.
Temperature sensors on air intake.
Temperature sensor on air delivery.
REFRIGERANT CIRCUIT
Thermostatic expansion valve.
Sight glass.
Filter dryer on liquid line.
Pressure transducers with indication, control and protection functions, on
low and high refrigerant pressure.
High pressure safety switch with manual reset.
Liquid receiver with accessories.
Refrigerant circuit with copper tubing with anticondensate insulation of the
suction line.
Plastic capillary hoses for pressure sensors connection.
R410A refrigerant charge.
NEXT DX DL:
- Valves on gas delivery and liquid return for coupling to remote air cooled
condenser.
- 010V proportional signal to manage the condensing control system of the
remote air cooled condenser.
NEXT DW DL:
- Copper brazed plate type with cover plates, plates and connections in AISI
316 stainless steel.
- 010V proportional signal to manage the condensing control system of the
2-way motorized valve.
ELECTRICAL PANEL
In accordance with EN60204-1 norms complete with:
Main switch with door lock safety.
Magnetothermic switch for each compressor.
Magnetothermic switches for fans.
Contactors for each load.
The supply fans equipped with EC electric motor are not supplied with
contactors.
Transformer for auxiliary circuit and microprocessor supply.
Panel with machine controls.
Power supply 400/3/50+N
78
NEXT DL
IT Cooling
COMMON OPTIONAL ACCESSORIES - NEXT DX DL - NEXT DW DL
MODEL
SIZE
220 - Electronic expansion valve
260 - Liquid solenoid valve
321 - Steam humidifier
310 - Electric heater
606 - Compr. power factor capacitor - 0,9
865 - Phase control relay
610 - Noise deading cup on compressor
215 - Disposal F5 efficiency air filter
810 - Floor stand Hmax=350 mm
811 - Floor stand Hmax=450 mm
812 - Floor stand Hmax=510 mm
849 - Condensate discharge system
808 - Sandwich panels
909 - Clogged filters alarm
912 - Air flow loss alarm EC Fan
911 - Water presence alarm
913 - Additional water sensor (kit)
904 - Temperature/Humidity sensor
945 - Air return plenum with Free Cooling damper
939 - Fresh air kit
919 - Clock card
923 - RC-Com MBUS/JBUS Serial board
926 - LON Serial board
931 - BACnet Ethernet - SNMP - TCP/IP Serial board
932 - BACnet MS/TP Serial board
942 - Serial card for GSM Modem
943 - Data Logger
962 - Kit modem GSM
957 - Plantwatch without modem
930 - Remote graphic terminal kit
863 - Remote terminal shared
RC CLOUD PLATFORM
008 P1 009 P1 011 P1 012 P1 016 P1 018 P1 020 P1 021 P1 023 P1 026 P1 029 P1 034 P1 037 P1 043 P1 046 P1
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
H1
H1
H1
H1
H2
H2
H2
H3
H3
H3
H3
H3S H3S H3L H3L
008 P1 009 P1 011 P1 012 P1 016 P1 018 P1 020 P1 021 P1 023 P1 026 P1 029 P1 034 P1 037 P1 043 P1 046 P1
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
H1
H1
H1
H1
H2
H2
H2
H3
H3
H3
H3
H3S H3S H3L H3L
008 P1 009 P1 011 P1 012 P1 016 P1 018 P1 020 P1 021 P1 023 P1 026 P1 029 P1 034 P1 037 P1 043 P1 046 P1
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
H1
H1
H1
H1
H2
H2
H2
H3
H3
H3
H3
H3S H3S H3L H3L
014
H1
020
H2
028
H3
036
H3S
049
H3L
NEXT DL
IT Cooling
008 P1
S
H1
009 P1
S
H1
011 P1
S
H1
012 P1
S
H1
016 P1
S
H2
029 P1
S
H3
034 P1
S
H3S
037 P1
S
H3S
043 P1
S
H3L
046 P1
S
H3L
018 P1
S
H2
020 P1
S
H2
021 P1
S
H3
023 P1
S
H3
026 P1
S
H3
SIZE
COOLING CAPACITY (1)
Total
kW
7,7
9,0
10,5
11,5
15,4
17,0
19,2
21,2
23,2
25,2
Sensible
kW
7,4
8,6
10,0
10,6
14,7
15,6
17,0
20,2
21,9
22,9
SHR
kW/kW
0,95
0,96
0,95
0,92
0,95
0,92
0,89
0,95
0,94
0,91
Unit power input (*)
kW
2,1
2,6
3,0
3,5
4,5
5,0
6,0
5,8
6,7
7,3
Supply fans
n.
1
1
1
1
1
1
1
1
1
1
3
Air flow
m /h
2150
2500
2500
2500
3700
3700
3700
5100
5100
5100
scroll
scroll
scroll
scroll
scroll
scroll
scroll
scroll
scroll
scroll
Compressors
1
1
1
1
1
1
1
1
1
1
Quantity
n.
1
1
1
1
1
1
1
1
1
1
Capacity steps
n.
1
1
1
1
1
1
1
2
2
2
Air filters
n.
G4
G4
G4
G4
G4
G4
G4
G4
G4
G4
Efficiency
R410A
R410A
R410A
R410A
R410A
R410A
R410A
R410A
R410A
R410A
Refrigerant
2,6
2,6
2,7
2,7
2,9
3,0
3,2
3,5
3,5
4,0
Refrigerant charge (2)
kg
1
1
1
1
1
1
1
1
1
1
Gas circuits
n.
400/3/50+N 400/3/50+N 400/3/50+N 400/3/50+N 400/3/50+N 400/3/50+N 400/3/50+N 400/3/50+N 400/3/50+N 400/3/50+N
Power supply (**)
8,1
9,4
10,4
11,4
13,7
16,3
19,5
21,8
21,8
22,8
Max operating current (FLA) (*)
A
31,4
41,4
49,4
46,4
54,9
68,5
79,5
81,8
107,8
101,8
Unit starting current (LRA)
A
Energy efficiency indexes (1)
3,74
3,50
3,50
3,28
3,46
3,41
3,19
3,64
3,48
3,45
EER (*)
kW/kW
Sound pressure level - ISO 3744 (3)
On air intake
dB(A)
49,0
52,0
52,0
52,0
54,0
54,0
54,0
55,0
55,0
55,0
On front side
dB(A)
54,0
58,0
58,0
58,0
60,0
60,0
60,0
60,0
60,0
60,0
Net weight
kg
187
191
192
193
246
248
252
302
303
307
Remote condenser (4)
n.
1
1
1
1
1
1
1
1
1
1
TEAM MATE
Mod.
M 11
M 11
M 14
M 14
M 20
M 25
M 25
M 30
M 30
M 30
Refrigerant connections
Gas delivery
ODS
12
12
12
12
18
18
18
18
18
22
Liquid return
ODS
12
12
12
12
12
12
16
16
16
16
1/2"
1/2"
1/2"
1/2"
1/2"
1/2"
1/2"
1/2"
1/2"
1/2"
Hydraulic connections - Condensate discharge F
MODEL
SIZE
COOLING CAPACITY (1)
Total
kW
28,3
34,4
37,0
40,8
43,8
Sensible
kW
24,3
30,9
32,0
39,0
40,5
SHR
kW/kW
0,86
0,90
0,86
0,96
0,92
Unit power input (*)
kW
8,0
9,4
10,8
11,0
12,3
Supply fans
n.
1
2
2
2
2
3
Air flow
m /h
5100
7000
7000
9500
9500
scroll
scroll
scroll
scroll
scroll
Compressors
1
1
1
1
1
Quantity
n.
1
1
1
1
1
Capacity steps
n.
2
2
2
2
2
Air filters
n.
G4
G4
G4
G4
G4
Efficiency
R410A
R410A
R410A
R410A
R410A
Refrigerant
4,1
4,4
4,4
7,2
7,2
Refrigerant charge (2)
kg
1
1
1
1
1
Gas circuits
n.
400/3/50+N 400/3/50+N 400/3/50+N 400/3/50+N 400/3/50+N
Power supply (**)
27,8
28,8
31,8
38,5
44,5
Max operating current (FLA) (*)
A
117,8
124,8
124,8
131,5
153,5
Unit starting current (LRA)
A
Energy efficiency indexes (1)
3,52
3,65
3,43
3,71
3,55
EER (*)
kW/kW
Sound pressure level - ISO 3744 (3)
55,0
56,0
56,0
56,0
56,0
On air intake
dB(A)
60,0
62,0
62,0
62,0
62,0
On front side
dB(A)
311
364
364
440
445
Net weight
kg
1
1
1
1
1
Remote condenser (4)
n.
M 35
M 45
M 45
M 50
M 50
TEAM MATE
Mod.
Refrigerant connections
22
22
28
28
28
Gas delivery
ODS
16
18
18
18
18
Liquid return
ODS
1/2"
1/2"
1/2"
1/2"
1/2"
Hydraulic connections - Condensate discharge F
THE COOLING CAPACITY DOES NOT CONSIDER THE SUPPLY FAN MOTOR THERMAL LOAD
1. Characteristics referred to entering air at 28C-40%RH; 35C ambient temperature.
2. Unit refrigerant charge. Remote condenser, connections pipes and optional are excluded.
3. Noise level at 1 meter in free field (external static pressure 50 Pa)
4. For matching to other remote air cooled condensers please refer to RC WORLD selection program
(*) The value includes the remote condenser as shown in the table.
(**) The remote condenser has separated power supply
008 P1 009 P1 011 P1 012 P1 016 P1 018 P1 020 P1 021 P1 023 P1 026 P1 029 P1 034 P1 037 P1 043 P1 046 P1
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
H1
H1
H1
H1
H2
H2
H2
H3
H3
H3
H3
H3S H3S
H3L
H3L
kW
n.
5,1
1
5,1
1
5,1
1
5,1
1
5,1
1
5,1
1
5,1
1
6,0
1
6,0
1
6,0
1
6,0
1
6,0
1
6,0
1
6,0
1
6,0
1
kg/h
kW
3
2,3
3
2,3
3
2,3
3
2,3
3
2,3
3
2,3
3
2,3
3
2,3
3
2,3
3
2,3
3
2,3
3
2,3
3
2,3
3
2,3
3
2,3
NEXT DL
IT Cooling
TECHNICAL DATA - NEXT DW DL
MODEL
008 P1
S
H1
009 P1
S
H1
011 P1
S
H1
012 P1
S
H1
016 P1
S
H2
029 P1
S
H3
034 P1
S
H3S
037 P1
S
H3S
043 P1
S
H3L
046 P1
S
H3L
018 P1
S
H2
020 P1
S
H2
021 P1
S
H3
023 P1
S
H3
026 P1
S
H3
SIZE
COOLING CAPACITY (1)
Total
kW
8,4
9,9
12,0
13,6
17,4
18,1
21,7
22,5
24,1
29,7
Sensible
kW
7,3
8,5
9,2
9,8
14,7
14,0
15,4
18,1
19,6
21,2
SHR
kW/kW
0,87
0,85
0,77
0,72
0,84
0,77
0,71
0,80
0,81
0,71
Unit power input
kW
1,5
1,8
2,2
2,5
3,7
4,0
4,9
5,0
5,0
5,4
Condenser water flow rate
m/h
1,4
1,7
2,0
2,3
3,0
3,1
3,8
3,9
4,2
5,0
Condenser pressure drop
kPa
17
23
20
25
7
8
11
11
40
15
Supply fans
n.
1
1
1
1
1
1
1
1
1
1
Air flow
m3/h
2150
2500
2500
2500
3700
3700
3700
5100
5100
5100
Compressors
scroll
scroll
scroll
scroll
scroll
scroll
scroll
scroll
scroll
scroll
Quantity
n.
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Capacity steps
n.
1
1
1
1
1
1
1
2
2
2
Air filters
n.
G4
G4
G4
G4
G4
G4
G4
G4
G4
G4
Efficiency
R410A
R410A
R410A
R410A
R410A
R410A
R410A
R410A
R410A
R410A
Refrigerant
2,8
2,8
2,9
2,9
3,8
3,8
4,1
4,4
4,8
5,3
Refrigerant charge (2)
kg
1
1
1
1
1
1
1
1
1
1
Gas circuits
n.
Power supply
400/3/50+N 400/3/50+N 400/3/50+N 400/3/50+N 400/3/50+N 400/3/50+N 400/3/50+N 400/3/50+N 400/3/50+N 400/3/50+N
7,2
8,6
9,7
10,7
12,8
14,4
17,7
20,3
20,3
21,3
Max operating current (FLA)
A
30,2
40,2
48,2
45,2
53,4
65,9
76,9
79,3
105,3
99,3
Unit starting current (LRA)
A
Energy efficiency indexes (1)
5,64
5,46
5,38
5,35
4,72
4,57
4,46
4,49
4,78
5,46
EER
kW/kW
Sound pressure level - ISO 3744 (3)
49,0
52,0
52,0
52,0
54,0
54,0
54,0
55,0
55,0
55,0
On air intake
dB(A)
54,0
58,0
588,0
58,0
60,0
60,0
60,0
60,0
60,0
60,0
On front side
dB(A)
206
211
213
216
261
265
272
324
324
333
Net weight
kg
Hydraulic connections
1"
1"
1"
1"
1" 1/2
1" 1/2
1" 1/2
1" 1/2
1" 1/2
1" 1/2
Condenser water inlet/outlet
1/2"
1/2"
1/2"
1/2"
1/2"
1/2"
1/2"
1/2"
1/2"
1/2"
Hydraulic connections - Condensate discharge F
MODEL
SIZE
COOLING CAPACITY (1)
Total
kW
31,0
40,2
43,9
47,2
51,4
Sensible
kW
22,3
28,5
29,9
35,7
37,3
SHR
kW/kW
0,72
0,71
0,68
0,76
0,73
Unit power input
kW
6,3
7,0
7,9
8,1
9,2
Condenser water flow rate
m/h
5,3
6,7
7,4
7,9
8,6
Condenser pressure drop
kPa
6
11
13
14
17
Supply fans
n.
1
2
2
2
2
Air flow
m3/h
5100
7000
7000
9500
9500
Compressors
scroll
scroll
scroll
scroll
scroll
Quantity
n.
1
1
1
1
1
Capacity steps
n.
1
1
1
1
1
Air filters
n.
2
2
2
2
2
Efficiency
G4
G4
G4
G4
G4
Refrigerant
R410A
R410A
R410A
R410A
R410A
Refrigerant charge (2)
kg
5,8
6,6
6,6
9,4
9,4
Gas circuits
n.
1
1
1
1
1
Power supply
400/3/50+N 400/3/50+N 400/3/50+N 400/3/50+N 400/3/50+N
26,6
27,1
30,2
35,3
41,6
Max operating current (FLA)
A
115,3
121,8
121,8
126,6
148,6
Unit starting current (LRA)
A
Energy efficiency indexes (1)
4,91
5,76
5,59
5,81
5,58
EER
kW/kW
Sound pressure level - ISO 3744 (3)
55,0
56,0
56,0
56,0
56,0
On air intake
dB(A)
60,0
62,0
62,0
62,0
62,0
On front side
dB(A)
337
396
396
480
485
Net weight
kg
Hydraulic connections
1" 1/2
2"
2"
2"
2"
Condenser water inlet/outlet
1/2"
1/2"
1/2"
1/2"
1/2"
Hydraulic connections - Condensate discharge F
THE COOLING CAPACITY DOES NOT CONSIDER THE SUPPLY FAN MOTOR THERMAL LOAD
1. Characteristics referred to entering air at 28C-50%RH; water to the condenser 30-36C
2. Unit refrigerant charge optional excluded.
3. Noise level at 1 meter in free field (external static pressure 50 Pa)
008 P1 009 P1 011 P1 012 P1 016 P1 018 P1 020 P1 021 P1 023 P1 026 P1 029 P1 034 P1 037 P1 043 P1 046 P1
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
H1
H1
H1
H1
H2
H2
H2
H3
H3
H3
H3
H3S H3S
H3L
H3L
kW
n.
5,1
1
5,1
1
5,1
1
5,1
1
5,1
1
5,1
1
5,1
1
6,0
1
6,0
1
6,0
1
6,0
1
6,0
1
6,0
1
6,0
1
6,0
1
kg/h
kW
3
2,3
3
2,3
3
2,3
3
2,3
3
2,3
3
2,3
3
2,3
3
2,3
3
2,3
3
2,3
3
2,3
3
2,3
3
2,3
3
2,3
3
2,3
81
NEXT DL
IT Cooling
14
H1
20
H2
28
H3
36
H3S
49
H3L
14,1
13,4
0,95
0,2
1
2500
1
G4
400/3/50+N
2,3
19,9
19,2
0,96
0,29
1
3700
1
G4
400/3/50+N
2,0
29,2
27,9
0,96
0,42
1
5100
2
G4
400/3/50+N
4,1
36,8
35,4
0,96
0,57
2
7000
2
G4
400/3/50+N
4,0
49,2
47,6
0,97
0,77
2
9500
2
G4
400/3/50+N
9,0
58,2
55
166
60,2
57
204
60,9
57,7
257
62,6
59,4
295
66,2
63
360
1"
1/2"
1"
1/2"
1" 1/4
1/2"
1 1/2"
1/2"
1 1/2"
1/2"
THE COOLING CAPACITY DOES NOT CONSIDER THE SUPPLY FAN MOTOR THERMAL LOAD
1. Characteristics referred to entering air at 24C-40%RH with chilled water temperature 7-12C - 0% glycol.
2. Noise level at 1 meter in free field.
014
H1
020
H2
028
H3
036
H3S
049
H3L
kW
n.
5,1
1
5,1
1
6,0
1
6,0
1
6,0
1
kg/h
kW
3
2,3
3
2,3
3
2,3
3
2,3
3
2,3
a
650
785
1085
1295
1620
b
650
650
750
750
750
c
1925
1925
1925
1925
1925
82
NEXT MTR
NEXT MTR: Air conditioners for Metrology Labs with upflow air delivery
for matching with remote air cooled condenser (DX) or with built-in water cooled condenser (DW)
Cooling capacity: 7 15 kW
NEXT MTR
rcgroupairconditioning
MAIN FEATURES
Precision air conditioner for metrology labs.
10 models available, 2 versions for a wide selection opportunity.
Available in two versions: for matching with remote air cooled condenser
(DX) or with built-in water cooled condenser (DW)
On/off scroll compressors
Single refrigerant circuit.
R407C refrigerant charge.
EC plug fans.
Steam humidifier.
Dehumidification system with automatic air flow reduction.
3 working steps electric heater.
Upflow air delivery, Over version.
Suitable for indoor installation
DX version:
EER up to 3,92.
DW version:
EER up to 5,30
Built in water cooled condenser..
MAIN BENEFITS
Wide selection opportunity.
High precision in maintaining the characteristics of temperature-humidity
of the air conditioned room.
Humidifier, De-Humidifier, Electric heater supplied as standard.
High EER.
High efficiency at partial load.
Complete set of optional accessories: filters, plenum, panels, stand.
Easily of maintenance.
RCGROUP SpA G_ITC_RCW8.4
R407c
EC
UP
FLOW
INDOOR INSTALLATION
The machines are designed for indoor installation.
WORKING RANGE
The machines are designed to maintain a room temperature between 20
and 26 C (0.5C) with a relative humidity between 45 and 55% RH (
3%).
The room has to be closed and with a good thermal insulation as clean
rooms, metrology labs, etc.
It is possible to extend the operating range from a minimum of 16C up to a
maximum of 32C with relative humidity from 40 to 60% RH.
CAUTION:
In these operating conditions precision and accuracy of the control are
reduced:
- Temperature: 1C
- Humidity: 5%rH.
f i f t y c o o l y e a r s
83
NEXT MTR
IT Cooling
MAIN COMPONENTS
FRAMEWORK
Base in aluminium extrusion, painted with epoxy powders.
Inner frame and upper frame in aluminium profile, painted with epoxy
powders. The inner frame is provided with seals to ensure air tight with the
panels.
Galvanized steel sheet panels externally coated with PVC film and
internally insulated with noise absorption material.
The panels are fixed to the frame with non visible mounting system.
Electric board in separate technical compartment on the machine front.
Colour: RAL 9005 for base and frame
Similar to RAL7015 for panels, with hammered finish
Air intake from the front through honeycomb type grille and air delivery from
the top.
Washable air pre-filters with G2 efficiency, with cells in synthetic fibre .
COMPRESSORS
Orbiting spiral (SCROLL) hermetic compressors with spiral profile optimized
for R407C refrigerant.
Continuous control of the cooling capacity by hot gas by-pass.
2-pole 3-phase electric motor with direct on line starting.
Crankcase heater.
Electric motor thermal protection via internal winding temperature sensors.
Terminal box with IP54 enclosure class.
Rubber supports.
FILTER SECTION
Washable air filters with G4 efficiency, with cells in synthetic fibre and
metallic frame (EN 779-2002).
EVAPORATING SECTION
Heat exchanger coil with internally corrugated copper tubes and high
efficiency aluminium fins, specifically developed to provide high heat
transfer and lower pressure drops.
Cooling capacity control.
Frame in galvanized steel.
Condensate tray in peraluman with PVC flexible discharge pipe.
HEATING SECTION
3 working steps electric heater consisting of aluminium armoured elements
with integral fins and safety thermostat (binary control logic).
Modulating type hot gas reheating system.
HUMIDIFICATION SECTION
Proportional controlled steam humidifier with immersed electrodes fitted
with safety and running accessories.
DEHUMIDIFICATION SECTION
Dehumidification system with automatic air flow reduction.
FANS SECTION
Centrifugal fans with backward curved blades, single suction and without
scroll housings (Plug-fans), directly coupled to external rotor electric motor.
Brushless type synchronous EC motor with integrated electronic
commutated system and continuous variation of the rotation speed.
The motor rotation control is obtained with the EC system (Electronic
Commutation) that manage the motor according to the 010V proportional
signal coming from the microprocessor control.
Temperature/humidity sensors on air intake.
REFRIGERANT CIRCUIT
Thermostatic expansion valve.
Sight glass.
Filter dryer on liquid line.
Pressure transducers with indication, control and protection functions, on
low and high refrigerant pressure.
High pressure safety switch with manual reset.
Safety valve.
Liquid receiver with accessories.
3-way modulating valve for hot gas re-heating system.
Check valve for hot gas re-heating system.
Hot gas injection valve for capacity control.
Balancing valve for hot gas capacity control.
Refrigerant circuit with copper tubing with anticondensate insulation of the
suction line.
Plastic capillary hoses for pressure sensors connection.
R407C refrigerant charge.
NEXT MTR DX:
- Valves on gas delivery and liquid return for coupling to remote air cooled
condenser.
- 010V proportional signal to manage the condensing control system of
the remote air cooled condenser.
NEXT MTR DW:
- Copper brazed plate type with cover plates, plates and connections in
AISI 316 stainless steel.
- 010V proportional signal to manage the condensing control system of
the 2-way motorized valve.
ELECTRICAL PANEL
In accordance with EN60204-1 norms complete with:
Main switch with door lock safety.
Magnetothermic switch for supply fan, compressor, electric heaters and
humidifier.
Contactors for each load.
The supply fans equipped with EC electric motor are not supplied with
contactors.
Transformer for auxiliary circuit and microprocessor supply.
Panel with machine controls.
Power supply: 400/3/50.
CONTROL SYSTEM
MP.COM microprocessor system with graphic display for control and
monitor of operating and alarms status. The system includes:
- Voltage free contact for remote general alarm.
- Main components hour-meter.
- Nonvolatile Flash memory for data storage.
- Menu with protection password.
- LAN connection.
TO BE MATCHED WITH REMOTE CONDENSER
The DX units are designed to be matched with remote condensers with axial
fans (TEAM MATE series) or plug-fans (TEAM MATE PF series).
TEAM MATE
TEAM MATE PF
007 Z1
S
H2
009 Z1
S
H2
011 Z1
S
H2
013 Z1
015 Z1
S
S
H3
H3
NEXT MTR
IT Cooling
COMMON OPTIONAL ACCESSORIES
NEXT MTR
007 Z1
S
H2
SIZE
220 - Electronic expansion valve
606 - Compr. power factor capacitor - 0,9
865 - Phase control relay
610 - Noise deading cup on compressor
215 - Disposal F5 efficiency air filter
811 - Floor stand Hmax=450 mm
848 - Condensate discharge system (kit)
808 - Sandwich panels
807 - Blind frontal pannel
805 - Bottom panel
909 - Clogged filters alarm
912 -Air flow loss alarm EC Fan
911 - Water presence alarm
913 - Additional water sensor (kit)
843 - Motorized damper with frame
830 - Air discharge plenum with grilles
831 - Plenum with frontal grille and sound absorber
832 - Air supply plenum with F6 filters
833 - Air supply plenum with F7 filters
835 - Air supply plenum with F9 filters
836 - Air supply plenum with sound absorber
906 - Outlet air temperature indication
919 - Clock card
907 - Current indication
908 - Voltage indication
923 - RC-Com MBUS/JBUS Serial board
926 - LON Serial board
932 - BACnet MS/TP Serial board
931 - BACnet Ethernet - SNMP - TCP/IP Serial board
942 - Serial card for GSM Modem
943 - Data Logger
922 - Driver card
962 - Kit modem GSM
957 - Plantwatch without modem
930 - Remote graphic terminal kit
863 - Remote terminal shared
RC CLOUD PLATFORM
009 Z1
S
H2
011 Z1
S
H2
013 Z1
S
H3
015 Z1
S
H3
007 Z1
S
H2
009 Z1
S
H2
011 Z1
S
H2
013 Z1
S
H3
015 Z1
S
H3
6,7
6,7
1,00
1,78
1
2300
50
625
scroll
1
Modulating
1
G4
R407C
5,4
1
400/3/50+N
6,4
25,9
3,78
8,8
8,8
1,00
2,23
1
3000
50
530
scroll
1
Modulating
1
G4
R407C
5,4
1
400/3/50+N
7,3
33,9
3,92
9,9
9,9
1,00
2,72
1
3300
50
480
scroll
1
Modulating
1
G4
R407C
5,4
1
400/3/50+N
8,6
41,9
3,65
11,5
11,5
1,00
3,21
1
4000
50
600
scroll
1
Modulating
1
G4
R407C
6,8
1
400/3/50+N
11,9
50,3
3,58
14,3
14,3
1,00
4,45
1
5500
50
640
scroll
1
Modulating
1
G4
R407C
6,8
1
400/3/50+N
15,0
54,3
3,21
kW
55,0
54,4
235
1
M 11
Modulating
7,7
59,8
54,8
242
1
M 17
Modulating
8,4
61,6
55,1
249
1
M 17
Modulating
9,0
59,3
55,9
300
1
M 17
Modulating
10,6
65,6
57,1
312
1
M 20
Modulating
11,9
kW
n.
5,1
2
5,1
2
5,1
2
6,0
2
6,0
2
kg/h
kW
3
2,3
3
2,3
3
2,3
3
2,3
3
2,3
ODS
ODS
16
12
16
12
16
12
18
16
18
16
F
F
3/4"
1/2
3/4"
1/2
3/4"
1/2
3/4"
1/2
3/4"
1/2
kW
kW
kW/kW
kW
n.
m3/h
Pa
Pa
n.
n.
n.
kg
n.
V/Ph/Hz
A
A
kW/kW
dB(A)
dB(A)
kg
n.
Mod.
THE COOLING CAPACITY DOES NOT CONSIDER THE SUPPLY FAN MOTOR THERMAL LOAD
1.
Characteristics referred to entering air at 24C-50%RH; 35C ambient temperature.
2.
Unit refrigerant charge. Remote condenser, connections pipes and optional are excluded.
3.
Noise level at 1 meter in free field (external static pressure 50 Pa)
4.
For matching to other remote air cooled condensers please refer to RC WORLD selection program
(*)
The value includes the remote condenser as shown in the table.
(**)
The remote condenser has separated power supply
19632013 fiftycoolyears RCGROUP SpA G_ITC_RCW8.4
85
NEXT MTR
IT Cooling
007 Z1
S
H2
009 Z1
S
H2
011 Z1
S
H2
013 Z1
S
H3
015 Z1
S
H3
kg
n.
V/Ph/Hz
A
A
7,1
7,1
1,00
1,33
1,2
19
1
2300
50
625
Scroll
1
Modulating
1
G4
R407C
5,8
1
400/3/50+N
6,4
25,9
9,0
9,0
1,00
1,81
1,5
24
1
3000
50
530
Scroll
1
Modulating
1
G4
R407C
5,8
1
400/3/50+N
7,3
33,9
10,3
10,3
1,00
2,20
1,8
23
1
3300
50
480
Scroll
1
Modulating
1
G4
R407C
5,8
1
400/3/50+N
8,6
41,9
12,4
12,4
1,00
2,52
2,1
21
1
4000
50
600
Scroll
1
Modulating
1
G4
R407C
7,5
1
400/3/50+N
11,9
50,3
15,4
15,4
1,00
3,33
2,6
15
1
5500
50
640
Scroll
1
Modulating
1
G4
R407C
7,5
1
400/3/50+N
15,0
54,3
kW/kW
5,30
4,99
4,68
4,92
4,62
dB(A)
dB(A)
kg
kW
55,0
54,4
239
Modulating
7,7
59,8
54,8
242
Modulating
8,4
61,6
55,1
249
Modulating
9,0
59,3
55,9
300
Modulating
10,6
65,6
57,1
312
Modulating
11,9
kW
n.
5,1
2
5,1
2
5,1
2
6,0
2
6,0
2
kg/h
kW
3
2,3
3
2,3
3
2,3
3
2,3
3
2,3
M
F
F
1 1/4"
3/4"
1/2
1 1/4"
3/4"
1/2
1 1/4"
3/4"
1/2
1 1/4"
3/4"
1/2
1 1/4"
3/4"
1/2
kW
kW
kW/kW
kW
m3/h
kPa
n.
m3/h
Pa
Pa
n.
n.
n.
THE COOLING CAPACITY DOES NOT CONSIDER THE SUPPLY FAN MOTOR THERMAL LOAD
1.
Characteristics referred to entering air at 24C-50%RH; water to the condenser 30-36C
2.
Unit refrigerant charge optional excluded.
3.
Noise level at 1 meter in free field (external static pressure 50 Pa)
a
785
1085
b
650
750
c
1925
1925
86
COOLROW
COOL ROW: Direct expansion or chilled water air conditioners
for high density racks and blade servers.
Cooling Capacity: 14 61 kW
INVERTER
CHILLEDWATER
ECFAN
COOLNET
COOLROW
rcgroupairconditioning
MAIN FEATURES
Direct expansion or chilled water feeding air conditioner for high density
racks and blade servers.
4 models, 2 versions available for a wide selection opportunity.
Plug-fan EC.
Frontal air delivery.
Suitable for indoor installation.
DX VERSION:
BLDC inverter scroll compressor.
R410A refrigerant charge.
EER up to 5,78.
Designed for matching with TEAM MATE, TEAM MATE PF remote
condensers.
CW VERSION:
Chilled water feeding.
Two-way chilled water valve.
Designed for matching with RC Group liquid chillers
MAIN BENEFITS
Suitable for cooling system for rows of racks (hot/cold aisle or in-row).
High EER.
BLDC Inverter compressors and plug-fan EC for a higher energy
efficiency.
Availability of connection on the top or on the bottom of the unit.
Availability of chilled water pressure independent characterized control
valve (CW version).
Availability of extra-circuit coil.
Easily of maintenance.
19632013 fiftycoolyears RCGROUP SpA G_ITC_RCW8.4
CHILLED
WATER
R410A
INVERTER
EC
FRONT
FLOW
INDOOR INSTALLATION
The machines are designed for indoor installation.
REMOTE CONDENSER
The units are designed to be matched with remote condensers with axial
fans (TEAM MATE series) or plug-fans (TEAM MATE PF series).
WORKING LIMITS
INDOOR UNIT
Room air temperature:
14C
minimum temperature with wet bulb
26C
minimum temperature with wet bulb.
40C
maximum temperature with dry bulb.
Room air humidity:
20%rH minimum relative humidity.
70%rH maximum relative humidity.
f i f t y c o o l y e a r s
87
COOLROW
MAIN COMPONENTS
FRAMEWORK
Framework in galvanized steel sheet externally painted with epoxy
powders.
Panels in galvanized steel sheet externally painted with epoxy powders and
internal thermal insulation.
Access doors. The doors are equipped with handle with security lock.
Holders for unit height adjusting.
Colour RAL 7016 (anthracite grey) textured.
Air flow for cooling system for rows of racks with air intake from the
back side through honeycomb type grille and frontal air delivery through
honeycomb type grille.
FILTER SECTION
Washable air filters with G2 efficiency, with cells in synthetic fibre, on air
suction panel.
FANS SECTION
Centrifugal fans with backward curved blades with wing profile, single
suction and without scroll housings (Plug-fans), directly coupled to external
rotor electric motor.
- Impeller in composite material, PA6 plastic reinforced with glass-fibre,
exempt from rust formation.
- Brushless type synchronous EC motor with integrated electronic
commutated system and continuous variation of the rotation speed.
The motor rotation control is obtained with the EC system (Electronic
Commutation) that manage the motor according to the signal coming
from the microprocessor control.
Fans control through ModBus.
Temperature sensor on air delivery.
Temperature sensor on air intake.
Current detector for loss of air flow alarm through ModBus.
Fans quick installation system for a fast replacement.
Fan guard IP20
IT Cooling
ELECTRICAL PANEL
Electrical panel, in accordance with EN60204-1 norms, complete with:
Magnetothermic switch on power supply
Magnetothermic switches for fans.
Magnetothermic switch for compressor (DX version).
Transformer for auxiliary circuit and microprocessor supply.
Terminals for external enabling, external alarm, general alarm and LAN
connection.
Power supply: 230/1/50.
CONTROL SYSTEM
Microprocessor system with graphic display for control and monitor of
operating and alarms status. The system includes:
- Real time clock.
- Predisposition for connectivity board housing ( RCcom MBUS/JBUS,
LON, BACnet for Ethernet (SNMP- TCP/IP), BACnet for MS/TP).
- Main components hour-meter.
- Nonvolatile Flash memory for data storage in case of power supply
faulty and for alarms status recording (2MB up to 100 alarms).
- Menu with protection password.
- LAN connection.
COOLING SECTION
Heat exchanger coil with internally corrugated copper tubes and high
efficiency aluminium fins, specifically developed to provide high heat
transfer and lower pressure drops.
Finned pack with hydrophilic treatment that assure the condensate water
drop, high thermal conductivity and does not favour the growth of microorganisms.
Condensate tray in peraluman with connection (external diameter 16) for
a discharge tube or for a pump for condensate drain (option).
INVERTER DRIVEN COMPRESSOR (series COOLROW DX)
scroll compressor BLDC inverter with spiral profile optimized for R410A
refrigerant.
Synchronous brushless inverter driven motor.
Inverter for modulating capacity control.
Reactance for the reduction of electromagnetic noise and interference.
Crankcase heater.
Rubber supports.
Soundproof cap.
REFRIGERANT CIRCUIT (series COOLROW DX)
Electronic expansion valve.
Pressure transducers with indication, control and protection functions, on
low and high refrigerant pressure.
High pressure safety switch with manual reset.
Refrigerant temperature sensor for expansion valve.
Filter dryer on liquid line.
Oil separator on gas discharge.
Refrigerant circuit with copper tubing with anticondensate insulation.
Rotalock valves on liquid and suction line placed on bottom side of the unit
for coupling to remote condenser unit.
010V proportional signal to manage the condensing control system of the
remote air cooled condenser.
R410A refrigerant charge and lubricant oil type PVE (Polyvinyl ether).
88
TEAM MATE PF
COOLROW
IT Cooling
OPTIONAL ACCESSORIES - COOLROW DX Inv
MODEL
SIZE
TEAM MATE remote condenser
TEAM MATE PF remote condenser
213 -TEAM MATE electrical power supply by internal unit
1012 - Unit handling kit
310 - Electric heater
321 - Steam humidifier
773 - Dehumification system
405 - Extra-Circuit system
850 - Condensate discharge pump
211 - G4 Filters
854 - Refrigerant connection from the top - DX
909 - Clogged filters alarm
911 - Water presence alarm
913 - Additional water sensor (kit)
860 - T/rH sensor on air return
867 - T/rH remote sensor
204 - Differential air pressure control
851 - Dual power supply
958 - Temporary microprocessor supply
923 - RC-Com MBUS/JBUS Serial board
926 - LON Serial board
931 - BACnet Ethernet - SNMP - TCP/IP Serial board
932 - BACnet MS/TP Serial board
1011 - Doble serial interface
863 - Remote terminal shared
962 - Kit modem GSM
957 - Plantwatch without modem
930 - Remote graphic terminal kit
RC CLOUD PLATFORM
25
B6 BF
40
B6 BF
MODEL
SIZE
1012 - Unit handling kit
310 - Electric heater
321 - Steam humidifier
773 - Dehumification system
405 - Extra-Circuit system
850 - Condensate discharge pump
211 - G4 Filters
858 - Chilled water connections from the top
935 - H20 Deviation valve (3 way)
936 - Pressure independent Two-way chilled water valve
909 - Clogged filters alarm
911 - Water presence alarm
913 - Additional water sensor (kit)
860 - T/rH sensor on air return
867 - T/rH remote sensor
204 - Differential air pressure control
851 - Dual power supply
958 - Temporary microprocessor supply
923 - RC-Com MBUS/JBUS Serial board
926 - LON Serial board
931 - BACnet Ethernet - SNMP - TCP/IP Serial board
932 - BACnet MS/TP Serial board
1011 - Doble serial interface
1013 - Power supply with cable (3m) and IP44 IEC 309 plug
962 - Kit modem GSM
957 - Plantwatch without modem
930 - Remote graphic terminal kit
863 - Remote terminal shared
1016 - Software Advanced - COOLNET
RC CLOUD PLATFORM
50
B6 BF
60
B6 BF
kW
kW
kW/kW
kW
n.
m3/h
Min
14,4
14,4
1,00
2,5
4
3450
n.
n.
n.
kg
n.
V/Ph/Hz
A
A
25
B6 BF
Nom
23,1
23,1
1,00
5,3
4
5800
scroll
1
MOD
1
G2
R410A
4,5
1
400/3/50+N
21,6
8,4
Max
28,5
28,5
1,00
7,9
4
7400
Min
18,0
18,0
1,00
3,4
4
4400
40
B6 BF
Nom
36,5
36,5
1,00
10,7
4
9400
scroll
1
MOD
1
G2
R410A
4,6
1
400/3/50+N
30,8
8,4
Max
39,7
39,7
1,00
13,0
4
9400
kW/kW
5,78
4,34
3,60
5,29
3,40
3,06
dB(A)
kg
n.
n. x Mod.
43,6
54,9
290
1
M 35
60,2
48,9
65,4
290
1
M 45
65,4
ODS
ODS
16
16
18
16
THE COOLING CAPACITY DOES NOT CONSIDER THE SUPPLY FAN MOTOR THERMAL LOAD
1. Characteristics referred to entering air at 24C-50%RH; 35C ambient temperature.
2. Unit refrigerant charge. Remote condenser, connections pipes and optional are excluded.
3. The Energy Efficiency Index consider also the remote air cooled condenser as shown in the table.
4. Noise level at 1 meter in free field (external static pressure at nominal conditions)
5. For matching to other remote air cooled condensers please refer to RC WORLD selection program
(*) The value includes the remote condenser
(**) The remote condenser has separated power supply
89
COOLROW
IT Cooling
50
B6 BF
60
B6 BF
49,7
49,7
1,00
1,13
4
10000
61,1
61,1
1,00
1,51
4
10000
8,5
33
1
G2
230/1/50
4,62
10,5
33
1
G2
230/1/50
4,62
dB(A)
kg
66,7
246
67,5
262
mm
mm
48,3
16
48,3
16
kW
kW
kW/kW
kW
n.
m3/h
m3/h
kPa
n.
V/Ph/Hz
A
THE COOLING CAPACITY DOES NOT CONSIDER THE SUPPLY FAN MOTOR THERMAL LOAD
1. Characteristics referred to entering air at 35C-25%RH with chilled water temperature 10-15C - 0% glycol.
2. Noise level at 1 meter in free field.
3. Hydraulic connection with grooved end, supplied as standard with flexible joint and adapter pipe.
4. Condensate discharge of the condensate tray. External diameter.
25
B6 BF
40
B6 BF
50
B6 BF
60
B6 BF
kg/h
kW
2
1,4
2
1,4
2
1,4
2
1,4
kW
kW
47,5
47,5
47,5
47,5
47,5
47,5
Characteristics referred to entering air at 35C-25%RH with chilled water temperature 10-15C - 0% glycol.
DIMENSIONS (mm)
SIZE
B6 BF
a
600
b
1200
c
2000
c
90
INVERTER
ECFAN
MAIN FEATURES
Direct expansion air conditioning system for high density racks and blade
servers.
6 models, 2 versions available for a wide selection opportunity.
6 combinations (in-room unit-outdoor unit) available.
EER up to 4,45.
Rotary or Scroll BLDC Inverter compressors.
R410A refrigerant charge.
EC Plug-fans.
F Version, frontal air delivery, L version, side air delivery.
Evaporating unit suitable for indoor installation.
Motocondensing unit MCAI, suitable for outdoor installation.
Microchannel condensing coil.
MAIN BENEFITS
High EER.
Suitable for direct cooling system (close loops) or cooling system for
rows of racks (hot/cold aisle).
BLDC Inverter compressors and plug-fan EC for a higher energy
efficiency.
High energy efficiency at partial loads.
Availability of connection on the top or on the bottom of the unit.
Availability of dual power supply.
Availability of box-server rack.
Easily of maintenance.
R410A
INVERTER
FRONT
FLOW
EC
CLOSED
LOOP
WORKING LIMITS
INDOOR UNIT
Room air temperature:
14C
minimum temperature with wet bulb
26C
minimum temperature with wet bulb.
40C
maximum temperature with dry bulb.
Room air humidity:
20%rH minimum relative humidity.
70%rH maximum relative humidity.
OUTDOOR UNIT - AIR COOLED MOTOCONDENSING UNIT
Ambient air temperature:
-30C
minimum temperature
45C
maximum temperature.
f i f t y c o o l y e a r s
91
92
IT Cooling
COMPONENTS - OUTDOOR UNIT - MCAI MOTOCONDENSING UNIT
FRAMEWORK
Base, self supporting frame and panelling in steel plate with protective
surfaces treatment in compliance with UNI ISO 9227/ASTMB117 and ISO
7253, and painted with epoxy powders.
Colour: RAL 9002
COMPRESSOR
Motocondensing unit model MCAI 10:
Twin rotary hermetic compressors BLDC inverter type optimized for R410A
refrigerant.
Motocondensing unit models MCAI 20 / MCAI 40:
Orbiting spiral (SCROLL) hermetic compressors BLDC inverter type with
spiral profile optimized for R410A refrigerant.
Common characteristics:
Inverter driven brushless type electric motor.
Modulating capacity control.
Crankcase heater.
Terminal box with IP54 enclosure class.
Rubber supports.
CONDENSING COIL
All-aluminium microchannel heat exchanger coil, specifically developed to
provide high heat transfer and lower pressure drops. Moreover microchannel
technology reduces the weight of the component and the refrigerant charge.
FANS SECTION
Axial fans with sickle-shaped blades, fan guard and optimized for low noise
levels.
Brushless type synchronous EC motor with integrated electronic commutated
system and continuous variation of the rotation speed. The motor rotation
control is obtained with the EC system (Electronic Commutation) that manage
the motor according to the 010V proportional signal coming from the
microprocessor control.
IP54 enclosure class.
REFRIGERANT CIRCUIT
Liquid separator on suction line.
Oil separator on delivery line with oil recovery capillary hose.
Check valve on gas delivery.
Liquid receiver.
Filter dryer on liquid line.
Sight glass.
Pressure transducers with indication, control and protection functions, on low
and high refrigerant pressure.
High pressure safety switch with manual reset.
Refrigerant circuit with copper tubing with anticondensate insulation of the
suction line.
Rotalock valves for coupling to indoor units:
- MCAI 10: Rotalock valves for connection to 1 indoor unit
- MCAI 20: Rotalock valves for connection to 2 indoor units
- MCAI 40: Rotalock valves for connection to 3 indoor units. In case of
connection to a single COOLSIDE EVO DX 040 unit, are available as
option the indoor evaporating unit #2 suction line collectors for a single
suction line realization.
R410A refrigerant charge.
ELECTRICAL PANEL
In accordance with EN60204-1 norms, suitable for outdoor installation, IP54
enclosure class, complete with:
Main switch with door lock safety
Inverter to drive the compressor motor.
Magnetothermic switch for fans motor protection
Magnetothermic switch for inverter protection
Transformer for auxiliary circuit and microprocessor supply.
Terminals for external enabling and smoke/fire alarm.
RJ45 connector for microprocessor terminal connection (the microprocessor
terminal is not installed on the unit).
Power supply:
- 230/1/50 for model MCAI 10
- 400/3/50+N for models MCAI 20 and MCAI 40
CONTROL SYSTEM
Microprocessor system with graphic display for control and monitor of
operating and alarms status. The system includes:
- Voltage free contact for remote general alarm.
- Main components hour-meter.
- Nonvolatile Flash memory for data storage.
- Menu with protection password.
- LAN connection.
G_ITC_RCW8.4 RCGROUP SpA 19632013 fiftycoolyears
IT Cooling
OPTIONAL ACCESSORIES - COOLSIDE EVO DX
COOLSIDE EVO DX
SIZE
214 - BOX-server rack
215 - Kit BOX 8 connections cabling
216 - Kit BOX 16 connections cabling
Baseboard for machine holders
850 - Condensate discharge pump
905 - Remote temperature sensor
202 - Timed stop button kit
854 - Connections from the top COOLSIDE EVO DX
263 - Kit single suction
852 - COOLSIDE humidifier kit
851 - Dual power supply
962 - Kit modem GSM
957 - Plantwatch without modem
930 - Remote graphic terminal kit
863 - Remote terminal shared
RC CLOUD PLATFORM
10
A3 F
10
A3 L
10
B3 F
10
20
40
10
B3 L
20
A3 F
20
A3 L
20
B3 F
20
B3 L
40
A6 F
40
A6 L
40
B6 F
40
B6 L
93
IT Cooling
POSSIBLE CONFIGURATIONS
MONO SPLIT
DX 10
MONO SPLIT
MCAI 20
DX 20
MONO SPLIT
MCAI 40
DX 40
MCAI 10
MULTI SPLIT
DX 10 DX 10
MCAI 20
MCAI 40
MULTI SPLIT
DX 20 DX 20
MCAI 40
DX 10 DX 10 DX 10
IN-ROW
IN-RACK
COOLSIDE EVO DX F
Frontal air delivery
COOLSIDE EVO DX L
Side air delivery
IT Cooling
TECHNICAL DATA - COOLSIDE EVO DX
MODEL
SIZE
Cooling Capacity (1)
Total
Sensible
SHR
Fans
Total air flow rate
Air filters
Efficiency
Refrigerant
Evaporating coil volume
Gas circuits
Power supply
Max operating current (FLA)
Sound pressure level (2)
On air delivery COOLSIDE EVO F
Irradiated COOLSIDE EVO L
Net weight
COOLSIDE EVO F
COOLSIDE EVO L
Refrigerant connections
Liquid line
Suction line
10
20
40
A3 - B3
A3 - B3
A6 B6
Nominal Reduced Medium Maximum Nominal Reduced Medium Maximum Nominal Reduced Medium Maximum
kW
kW
kW/kW
n.
m3/h
n.
10,1
10,1
1,00
3
2800
4,5
4,5
1,00
3
1300
8,1
8,1
1,00
3
2100
11,1
11,1
1,00
3
2900
20,3
20,3
1,00
5
4700
10,0
10,0
1,00
5
2200
15,0
15,0
1,00
5
3500
22,5
22,5
1,00
5
4850
41,1
41,1
1,00
10
9400
20,0
20,0
1,00
10
4300
28,0
28,0
1,00
10
7000
41,7
41,7
1,00
10
9700
67,6
60,9
51,0
44,3
61,2
54,5
68,3
61,6
69,8
63,1
53,3
46,6
63,4
56,7
70,4
63,7
72,3
65,6
55,4
48,7
65,9
59,2
72,9
66,2
1
G2
R410A
2
1
230/1/50
2,3
l
n.
V/Ph/Hz
A
dB(A)
dB(A)
kg
kg
1
G2
R410A
2,8
1
230/1/50
3,8
1
G2
R410A
5,8
1
230/1/50
7,5
A3 = 165 / B3 = 175
A3 = 163 / B3 = 173
A3 = 170 / B3 = 180
A3 = 168 / B3 = 178
A6 = 224 / B6 = 237
A6 = 222 / B6 = 235
10
16
12
22
16
2 x 22
ODS
ODS
THE COOLING CAPACITY DOES NOT CONSIDER THE SUPPLY FANS MOTOR THERMAL LOAD
1. Characteristics referred to entering air at 35C d.b. (20.1C w.b.) - unit coupled to a MCAI motocondensing unit
operating at nominal conditions with equivalent length of refrigerant pipes connecting 3m.
2. Sound pressure level at 1 meter in free field (ISO EN 3744).
kg
n.
V/Ph/Hz
A
MCAI 10
1 x 010
10,1
2,3
Twin Rotary
1
30100
1
5500
R410A
3,5
1
230/1/50
26,3
MCAI 20
1 x 020
20,3
5,6
Scroll
1
30100
2
11000
R410A
5
1
400/3/50+N
24,0
MCAI 20
2 x 010
21,6
5,7
Scroll
1
30100
2
11000
R410A
5
1
400/3/50+N
24,0
MCAI 40
3 x 010
39,9
11,9
Scroll
1
30100
2
19000
R410A
6
1
400/3/50+N
38,5
MCAI 40
2 x 020
40,6
11,9
Scroll
1
30100
2
19000
R410A
6
1
400/3/50+N
39,1
MCAI 40
1 x 040
41,1
11,5
Scroll
1
30100
2
19000
R410A
6
1
400/3/50+N
38,2
kW/kW
4,45
3,64
3,82
3,36
3,42
3,58
dB(A)
86,2
89,2
89,2
87,9
87,9
87,9
dB(A)
dB(A)
dB(A)
kg
70,4
60,1
54,7
96
73,4
63,1
57,7
178
73,4
63,1
57,7
178
71,8
61,7
56,4
228
71,8
61,7
56,4
228
71,8
61,7
56,4
228
1 x 10
1 x 16
2 x 12
2 x 22
2 x 12
2 x 22
3 x 12
3 x 22
3 x 12
3 x 22
3 x 12 (1x16)*
3 x 22
n x modello
kW
KW
n.
%
n.
m/h
n x ODS
n x ODS
Characteristics referred to ambient temperature at 35C with indoor units operating at nominal conditions with
equivalent length of refrigerant pipes connecting 3m for each unit.
Unit refrigerant charge, connection pipes excluded.
Sound power level [Lw] according to ISO EN 9614 - 2.
Average sound pressure level [Lpm] 1 meter far according to ISO EN 3744.
For monosplit version (with kit single suction optional accessory).
95
IT Cooling
SIDE
10 A3
10 B3
20 A3
20 B3
40 A6
40 B6
a
300
300
300
300
600
600
b
1000
1200
1000
1200
1000
1200
c
2000
2000
2000
2000
2000
2000
SIDE
BOX A
BOX B
a
600
600
b
1000
1200
c
2000
2000
DIMENSIONS (mm)
MCAI 40
MCAI 20
MCAI 10
1400
1395
900
1050
96
500
1050
523
1610
495
COOLSIDE EVO CW
COOLSIDE EVO CW: Chilled water air conditioners for high density racks and blade servers.
Cooling Capacity: 20 55 kW
CHILLEDWATER
ECFAN
COOLSIDE EVO CW
rcgroupairconditioning
MAIN FEATURES
Chilled water air conditioners for high density racks and blade servers.
4 models, 2 versions available for a wide selection opportunity.
Synergy with RC Group liquid chillers.
Chilled water feeding.
EC Plug-fans.
F Version, frontal air delivery, L version, side air delivery.
Suitable for indoor installation.
MAIN BENEFITS
Suitable for direct cooling system (close loops) or cooling system for
rows of racks (hot/cold aisle).
Plug-fan EC for a higher energy efficiency.
Availability of refrigerant connections on the top or on the bottom of the
unit.
Availability of dual power supply.
Availability of box-server rack.
Easily of maintenance.
CHILLED
WATER
FRONT
FLOW
EC
CLOSED
LOOP
WORKING LIMITS
INDOOR UNIT
Room air temperature:
14C
minimum temperature with wet bulb
26C
minimum temperature with wet bulb.
40C
maximum temperature with dry bulb.
Room air humidity:
20%rH minimum relative humidity.
70%rH maximum relative humidity.
f i f t y c o o l y e a r s
97
COOLSIDE EVO CW
IT Cooling
COMPONENTS
FRAMEWORK
Framework in galvanized steel sheet externally painted with epoxy
powders.
Panels in galvanized steel sheet externally painted with epoxy powders and
internally insulated with noise absorption material.
Access doors. The doors are equipped with handle with security lock.
Holders for unit height adjusting.
Colour:
- RAL 7016 (anthracite grey) textured.
Air flow:
- A3 / A6 size Cooling system for rows of racks (in-row):
o Air intake from the back side through honeycomb type grille and frontal
air delivery through honeycomb type grille.
- B3 / B6 size Direct cooling system of racks (in-racks):
o Air intake from side through honeycomb type grille and air delivery from
side through honeycomb type grille.
FILTER SECTION COOLSIDE EVO F
The filter section is not supplied for COOLSIDE EVO L unit.
Washable air filters with G2 efficiency, with cells in synthetic fibre, on air
suction panel.
Differential pressure switch on the air side for clogged filters signal.
COOLING SECTION
Heat exchanger coil with internally corrugated copper tubes and high
efficiency aluminium fins, specifically developed to provide high heat
transfer and lower pressure drops.
Finned pack with hydrophilic treatment that assure the condensate water
drop, high thermal conductivity and does not favour the growth of microorganisms.
2-way modulating valve for water flow regulation with 010V servomotor
and emergency manual control.
Hydraulic connections arranged for connection from bottom side of the unit.
Condensate tray in peraluman with connection (external diameter 16) for
a discharge tube or for a pump for condensate drain (option).
FANS SECTION
Centrifugal fans with backward curved blades, single suction and without
scroll housings (Plug-fans), directly coupled to brushless type synchronous
EC motor with integrated electronic commutated system and continuous
variation of the rotation speed. The motor rotation control is obtained with
the EC system (Electronic Commutation) that manage the motor according
to the 010V proportional signal coming from the microprocessor control.
Fans quick installation system for a fast replacement.
#2 temperature sensors on air delivery.
Temperature sensor on air intake.
Current detector for loss of air flow alarm.
ELECTRICAL PANEL
Extractable electrical panel, in accordance with EN60204-1 norms, complete
with:
Power supply with 10A plugs.
Magnetothermic switch on power supply
Terminals for external enabling, smoke/fire alarm, general alarm and LAN
connection.
Power supply: 230/1/50
CONTROL SYSTEM
Microprocessor system with graphic display for control and monitor of
operating and alarms status. The system includes:
- Voltage free contact for remote general alarm.
- Main components hour-meter.
- Non-volatile Flash memory for data storage.
- Menu with protection password.
- LAN connection.
20
A3 F
20
A3 L
20
B3 F
20
B3 L
40
A6 F
40
A6 L
40
B6 F
40
B6 L
98
COOLSIDE EVO CW
IT Cooling
OPTIONAL ACCESSORIES - BOX - Server Rack
Standard 19 server rack to match to COOLSIDE EVO CW 20 L.
POSSIBLE CONFIGURATIONS
LIQUID CHILLER
The system sucks hot air directly from the rear side of the racks, and, once
cooled, enters it in the front side of the rack.
Thanks to the closed cooling system the electronic equipment contained in
racks do not require fans for air circulation.
COOLSIDE EVO CW
IN-ROW
COOLSIDE EVO CW F
Frontal air delivery
COOLING SYSTEM FOR ROWS OF RACKS (IN ROW).
COOLSIDE EVO CW F
COOLSIDE EVO units and the racks are placed in rows that are arranged so
as to obtain alternate cold and hot aisles.
Electronic equipments contained in racks independently provide to aspire the
necessary air for cooling.
IN-RACK
COOLSIDE EVO CW L
Side air delivery
DIRECT COOLING SYSTEM (IN RACK).
COOLSIDE EVO CW L
The system sucks hot air directly from the rear side of the racks, and, once
cooled, enters it in the front side of the rack.
Thanks to the closed cooling system the electronic equipment contained in
racks do not require fans for air circulation.
99
COOLSIDE EVO CW
IT Cooling
Nom
20
A3 B3
Med
Max
kW
kW
kW/kW
n.
m3/h
25,0
25,0
1,00
5
4700
19,6
19,6
1,00
5
3500
m3/h
kPa
n.
4,3
42,0
69,8
63,1
V/Ph/Hz
A
dB(A)
dB(A)
kg
kg
Nom
40
A6 B6
Med
Max
25,5
25,5
1,00
5
4850
53,4
53,4
1,00
10
9400
41,7
41,7
1,00
10
7000
54,8
54,8
1,00
10
9700
3,4
26,6
1
G2
230/1/50
3,6
4,4
44,0
9,2
58,0
7,2
36,5
1
G2
230/1/50
7,1
9,4
60,6
63,4
56,7
70,4
63,7
72,3
65,6
65,9
59,2
72,9
66,2
A3 = 168 / B3 = 178
A3 = 166 / B3 = 176
A6 = 219 / B6 = 232
A6 = 217 / B6 = 230
1 1/4
16
1
16
THE COOLING CAPACITY DOES NOT CONSIDER THE SUPPLY FANS MOTOR THERMAL LOAD
1. Characteristics referred to entering air at 35C d.b. (20.1C w.b.) - chilled water temperature 7/12C - 0% glycol.
2. Noise pressure level at 1 meter in free field (ISO EN 3744).
3. Condensate discharge of the condensate tray. External diameter.
SIZE
20 A3
20 B3
40 A6
40 B6
a
300
300
600
600
b
1000
1200
1000
1200
c
2000
2000
2000
2000
100
ENERGY SPLIT
ENERGY SPLIT: Split system air conditioners with free-cooling system.
Cooling Capacity: 4 15 kW
UPS48VDC
FREECOOLING
ENERGY SPLIT
rcgroupairconditioning
MAIN FEATURES
Telecommunication split-system air conditioners.
Proportional automatic free-cooling system. Three working mode.
8 models available for a wide selection opportunity.
Average step of 1,5kW.
Rotary or scroll compressor.
R407c refrigerant charge.
Supply fans directly coupled to brushless type electric motors.
Horizontal or Vertical air flow.
Double power supply (Network + 48VDC UPS)
Evaporating unit suitable for indoor installation.
Moto-condensing unit suitable for outdoor installation.
SPLIT
SYSTEM
R407c
FREE
COOLING
UPS
48VDC
FRONT
FLOW
MAIN BENEFITS
The proprietary software foresees unit working with the lowest noise
emission during the night.
Working continuity even during black-out periods.
Automatic restart of the unit.
Availability of electric heater.
Easily of maintenance.
PROPORTIONAL FREE-COOLING SYSTEM
The cooling system is totally proportional and allows
three working modes:
total free-cooling: only fresh air is used to cool the ambient;
partial free-cooling: the fresh air is used for a pre-cooling and the
compressor or the chilled water are used to balance the load;
mechanical cooling: the compressor or the chilled water are used to cool
the ambient
19632013 fiftycoolyears RCGROUP SpA G_ITC_RCW8.4
f i f t y c o o l y e a r s
101
ENERGY SPLIT
MAIN COMPONENTS
INDOOR UNIT
FRAMEWORK
Frame in galvanized steel sheet, painted with epoxy powders.
Galvanized steel sheet panels painted with epoxy powders, internally
insulated with noise absorption material and seals to ensure air tight with
the panels.
Colour RAL 9002
The frame can be installed on the ceiling (horizontal air flow) or wall
mounting installation (vertical air flow).
FILTER SECTION
Washable air filters with G3 efficiency, with cells in synthetic fibre and
metallic frame (EN 779-2002).
EVAPORATING SECTION
Heat exchanger coil with internally corrugated copper tubes and high
efficiency aluminium fins, specifically developed to provide high heat
transfer and lower pressure drops.
Frame in galvanized steel.
Condensate tray in peraluman with PVC flexible discharge pipe.
REFRIGERANT CIRCUIT
Thermostatic expansion valve.
Pressure transducer with indication, control and protection functions, on
high pressure.
Low pressure safety switch.
Refrigerant circuit with copper tubing with anticondensate insulation of the
suction line.
Refrigerant connection valves on liquid line and suction line.
R407C refrigerant charge.
SUPPLY FANS SECTION
Power supply 48VDC from UPS
Double suction centrifugal fans with forward curved vanes directly coupled
to external rotor electric motor.
Brushless type electric motor with continuous variation of the rotation
speed. The motor rotation control is obtained by signal coming from the
microprocessor control.
Temperature sensor on room air intake
Temperature sensor on room air delivery.
Grille on room air suction.
Double row adjustable grille on air delivery.
System for air flow loss alarm
DIRECT FREE-COOLING SECTION
Power supply 48VDC from UPS
Deviating damper on ambient air.
Proportional servomotor directly driven by microprocessor control.
Grille on ambient air suction.
Temperature sensor on ambient air.
ELECTRICAL PANEL
In accordance with EN60204-1 norms complete with:
Double power supply, from network and from UPS 48VDC
Models 4 R1, 5 R1, 6 Z1, 7 Z1, 8 Z1:
- 230/1/50 power supply for compressor, condenser fan and eventual
electric heater.
Models 10 Z1, 13 Z1, 15 Z1:
- 400/3/50+N power supply for compressor, condenser fan and eventual
electric heater.
For all models:
- 48 VDC power supply from UPS for supply fans, free-cooling damper
servomotor, auxiliary circuit and microprocessor control.
Magnetothermic switch for 230/1/50 power supply line (from network)
Magnetothermic switch for 48VDC power supply line (from UPS)
Auxiliary circuit 48VDC (from UPS).
Contactor for compressor
Phases monitoring relay (only models 10.Z1, 13.Z1, 15.Z1)
Terminals for General Alarm 1
Terminals for General Alarm 2
Wall mounting remote terminal kit that includes containing box, terminal,
telephone cable for connection to the unit (length 10m).
102
IT Cooling
CONTROL SYSTEM
Power supply 48VDC from UPS
Microprocessor system with graphic display for control and monitor of
operating and alarms status. The system includes:
- Real time clock.
- Main components hour-meter.
- Menu with protection password.
- LAN connection.
- LN function to obtain a low noise unit running. The system works
proportionally to the load on the fan rotation speed either of the
condenser fan or the supply fan. The system allows a low noise unit
running during night time anyway according to the programmed sets.
- Automatic restart of the unit in case of power failure
OUTDOOR UNIT
FRAMEWORK
Base and frame in galvanized steel sheet, painted with epoxy powders.
Colour RAL 9002
ON / OFF COMPRESSOR
Rotary compressor with rotary vane (model R1) optimized for R407C
refrigerant.
Scroll compressor (model Z1) with spiral profile optimized for R410A
refrigerant.
Electric motor with direct on line starting.
Rubber supports.
REFRIGERANT CIRCUIT
Sight glass.
Filter dryer on liquid line.
Refrigerant circuit with copper tubing with anticondensate insulation of the
suction line.
Refrigerant connection valves on liquid line and suction line.
R407C refrigerant charge and lubricant oil.
CONDENSING COIL
Heat exchanger coil with high efficiency aluminium fins, specifically
developed to provide high heat transfer and lower pressure drops. The
combination of two factors, special tubes and fins, allow to optimally
combine the following aspects:
- Maximum capacity relative to the size of the exchanger.
- Minimum charge of refrigerant.
- Reduction of the air flow required for the heat exchange.
Frame in galvanized steel.
CONDENSER FAN SECTION
Axial fan with sickle-shaped blade, fan guard and optimized for low noise
levels.
External rotor AC type electric motor with stepless variable speed for
condensing pressure control.
IP54 enclosure class.
ELECTRICAL PANEL
In accordance with EN60204-1 norms, suitable for outdoor installation,
complete with:
Main switch with door lock safety and remote signalling for open/close
switch
Terminals for compressor and condenser fan power supply
ENERGY SPLIT
IT Cooling
OPTIONAL ACCESSORIES
ENERGY SPLIT
MODEL
SIZE
311 - Electric heater
408 - FC system removal detraction
909 - Clogged filters alarm
923 - RC-Com MBUS/JBUS Serial board
925 - Terminal removal detraction
931 - BACnet Ethernet - SNMP - TCP/IP Serial board
932 - BACnet MS/TP Serial board
939 - Fresh air kit
04 R1
S0 XS
05 R1
S1 XS
06 Z1
S1 XS
08 Z1
S1/S XS
09 Z1
S1/S XS
11 Z1
S2 XS
13 Z1
S2 XS
16 Z1
S3 XS
TECHNICAL DATA
ENERGY SPLIT
Model
04 R1
05 R1
06 Z1
07 Z1
08 Z1
10 Z1
13 Z1
15 Z1
Size
S0 XS
S0 XS
S0 XS
S1 XS
S1 XS
S1 XS
S2 XS
S2 XS
Cooling capacity(1)
Total
kW
4,2
5,3
6,0
7,0
9,6
11,4
12,8
15,6
Sensible
kW
3,9
4,9
5,4
6,2
8,3
9,9
12,0
14,2
SHR
kW/kW
0,93
0,93
0,90
0,89
0,87
0,87
0,94
0,91
Unit power input
48VDC power supply from UPS
kW
0,31
0,31
0,34
0,44
0,58
0,61
0,65
0,90
Power supply from network
kW
0,91
1,39
1,83
1,82
2,12
2,46
3,02
3,78
Treatment fans
n.
2
2
2
2
2
2
2
2
Air flow
m3/h
1400
1400
1400
2000
2400
2800
3500
3900
30
30
30
30
30
30
30
30
Nominal external static pressure
Pa
Rotary
Rotary
Scroll
Scroll
Scroll
Scroll
Scroll
Scroll
Compressors
1
1
1
1
1
1
1
1
Quantity
n.
1
1
1
1
1
1
1
1
Capacity steps
n.
Condenser fans
n.
1
1
1
1
1
1
1
1
3
Air flow
m /h
1800
1800
2600
2600
3250
3450
3450
4400
Air filter
n.
1
1
1
1
1
1
1
1
Efficiency
G3
G3
G3
G3
G3
G3
G3
G3
Refrigerant
R407C
R407C
R407C
R407C
R407C
R407C
R407C
R407C
Total refrigerant charge
kg
2,0
2,0
2,0
2,0
2,0
2,9
3,1
3,1
Gas circuits
n.
1
1
1
1
1
1
1
1
Power supply - in-room unit
V/Ph/Hz 230/1/50+48VDC 230/1/50+48VDC 230/1/50+48VDC 230/1/50+48VDC 230/1/50+48VDC 230/1/50+48VDC 230/1/50+48VDC 230/1/50+48VDC
Power supply - outdoor unit
V/Ph/Hz 230/1/50
230/1/50
230/1/50
230/1/50
230/1/50
400/3/50+N
400/3/50+N
400/3/50+N
Max operating current (FLA)
48VDC power supply from UPS
A
5,5
5,5
5,5
7,5
10,3
11,0
11,7
15,0
Power supply from network
A
7,1
10,1
12,1
12,1
15,5
6,9
7,7
9,2
Starting current (LRA)
48VDC power supply from UPS
A
6,0
6,0
6,0
8,0
10,8
11,5
12,2
15,5
Power supply from network
A
23,6
33,6
47,7
47,7
61,7
40,7
46,7
50,2
EER (1)
kW/kW
3,42
3,11
2,75
3,08
3,56
3,71
3,49
3,33
Sound pressure - Indoor unit - ISO 3744 (2) dB(A)
55,0
55,0
55,0
54,0
57,5
61,0
63,0
65,0
Sound pressure - Outdoor unit - ISO 3744 (2)dB(A)
55,0
55,0
53,0
53,0
57,0
57,0
57,0
58,0
Net weight - Indoor unit
kg
42
45
45
80
80
80
103
103
Net weight - Outdoor unit
kg
55
65
70
70
75
95
98
105
Refrigerant connections
Liquid line - SAE Flare
1/2"
1/2"
1/2"
1/2"
1/2"
1/2"
1/2"
1/2"
Suction line - SAE Flare
5/8"
5/8"
5/8"
5/8"
3/4"
3/4"
7/8"
7/8"
Hydraulic connections
Condensate discharge
mm
16
16
16
16
16
16
16
16
THE COOLING CAPACITY DOES NOT CONSIDER THE SUPPLY FANS MOTOR THERMAL LOAD
(1) Referred to entering air at 28C with 40% RH and outdoor air temperature 35C
(2) Sound pressure 1m far in free field according to ISO3744 norm.
kW
n.
04 R1
S0 XS
05 R1
S0 XS
06 Z1
S0 XS
07 Z1
S1 XS
08 Z1
S1 XS
10 Z1
S1 XS
13 Z1
S2 XS
15 Z1
S2 XS
1,0
1
1,0
1
1,0
1
3,0
1
3,0
1
3,0
1
3,0
1
3,0
1
103
ENERGY SPLIT
IT Cooling
a
784
980
1380
b
1171
1293
1349
c
294
361
392
b
a
a
805
1048
1307
b
326
415
535
c
669
841
890
104
MINIPAC
MINIPAC: Telecommunication packaged air conditioners with free-cooling system for outdoor installation.
Cooling Capacity: 4 19 kW
UPS48VDC
FREECOOLING
MINIPAC
rcgroupairconditioning
MAIN FEATURES
Telecommunication packaged air conditioners.
Proportional automatic free-cooling system. Three working mode.
9 models available for a wide selection opportunity.
Average step of 1,5kW.
Rotary or scroll compressor.
R407c refrigerant charge.
Supply fans directly coupled to brushless type electric motors.
Horizontal air flow.
Double power supply (Network + 48VDC UPS)
Suitable for outdoor installation.
FREE
COOLING
R407c
FRONT
FLOW
UPS
48VDC
mechanical cooling: the compressor or the chilled water are used to cool
the ambient
DOUBLE POWER SUPPLY
(Network + 48VDC UPC)
WORKING LIMITS
Room humidity from 20 up to 75% rH
Room temperature from 16 up to 35C
Ambient temperature from -30 up to 45C
MAIN BENEFITS
The proprietary software foresees unit working with the lowest noise
emission during the night.
Working continuity even during black-out periods.
Automatic restart of the unit.
Availability of electric heater.
Full frontal inspection.
Easily of maintenance.
PROPORTIONAL FREE-COOLING SYSTEM
The cooling system is totally proportional and allows three working
modes:
total free-cooling: only fresh air is used to cool the ambient;
partial free-cooling: the fresh air is used for a pre-cooling and the
compressor or the chilled water are used to balance the load;
f i f t y c o o l y e a r s
105
MINIPAC
MAIN COMPONENTS
FRAMEWORK
Base and frame in galvanized steel sheet, painted with epoxy powders.
Galvanized steel sheet panels painted with epoxy powders, internally insulated
with noise absorption material and seals to ensure air tight with the panels.
Panels fixed with safety screws.
Total front access for routine maintenance.
Colour RAL 9002
ON / OFF COMPRESSOR
Rotary compressor with rotary vane (model R1) optimized for R407C refrigerant.
Scroll compressor (model Z1) with spiral profile optimized for R410A refrigerant.
Electric motor with direct on line starting.
Rubber supports.
FILTER SECTION
Washable air filters with G4 efficiency, with cells in synthetic fibre and metallic
frame (EN 779-2002).
EVAPORATING SECTION
Heat exchanger coil with internally corrugated copper tubes and high efficiency
aluminium fins, specifically developed to provide high heat transfer and lower
pressure drops.
Frame in galvanized steel.
Condensate tray in peraluman with PVC flexible discharge pipe.
SUPPLY FANS SECTION
Power supply 48VDC from UPS
Axial fans with sickle-shaped blade and fan guard, directly coupled to external
rotor electric motor (units size S0, S1, S1S).
Double suction centrifugal fans with forward curved vanes directly coupled to
external rotor electric motor (units size S2, S3).
Brushless type electric motor with continuous variation of the rotation speed.
The motor rotation control is obtained by signal coming from the microprocessor
control.
Temperature sensor on room air intake
Temperature sensor on room air delivery.
Grille on room air suction.
Double row adjustable grille on air delivery.
System for air flow loss alarm
IT Cooling
ELECTRICAL PANEL
In accordance with EN60204-1 norms, suitable for outdoor installation, complete with:
Double power supply, from network and from UPS 48VDC
Units size S0, S1, S1S:
- 230/1/50 power supply for compressor, condenser fan and eventual electric
heater.
Units size S2, S3:
- 400/3/50+N power supply for compressor, condenser fan and eventual electric
heater.
For all units:
- 48 VDC power supply from UPS for supply fans, free-cooling damper
servomotor, auxiliary circuit and microprocessor control.
Magnetothermic switch for 230/1/50 or 400/3/50+N power supply line (from
network)
Magnetothermic switch for 48VDC power supply line (from UPS)
Contactor on compressor.
Phases monitoring relay (only S2, S3 units)
Auxiliary circuit 48VDC (from UPS).
Terminals for General Alarm 1
Terminals for General Alarm 2
CONTROL SYSTEM
Power supply 48VDC from UPS
Microprocessor system with graphic display for control and monitor of operating
and alarms status. The system includes:
- Real time clock.
- Main components hour-meter.
- Menu with protection password.
- LAN connection.
- LN function to obtain a low noise unit running. The system works proportionally
to the load on the fan rotation speed either of the condenser fan or the supply
fan. The system allows a low noise unit running during night time anyway
according to the programmed sets.
- Automatic restart of the unit in case of power failure
REFRIGERANT CIRCUIT
Thermostatic expansion valve.
Sight glass.
Filter dryer on liquid line.
Pressure transducer with indication, control and protection functions, on high
pressure.
Low pressure safety switch.
Refrigerant circuit with copper tubing with anticondensate insulation of the suction
line.
R407C refrigerant charge and lubricant oil.
CONDENSING COIL
Heat exchanger coil with high efficiency aluminium fins, specifically developed
to provide high heat transfer and lower pressure drops. The combination of two
factors, special tubes and fins, allow to optimally combine the following aspects:
- Maximum capacity relative to the size of the exchanger.
- Minimum charge of refrigerant.
- Reduction of the air flow required for the heat exchange.
Frame in galvanized steel.
Grille on air suction/discharge.
CONDENSER FANS SECTION
Axial fan with sickle-shaped blade, fan guard and optimized for low noise levels.
External rotor AC type electric motor with stepless variable speed for condensing
pressure control.
IP54 enclosure class.
DIRECT FREE-COOLING SECTION
Power supply 48VDC from UPS
Deviating damper on ambient air.
Proportional servomotor directly driven by microprocessor control.
Grille on ambient air suction.
Temperature sensor on ambient air.
106
MINIPAC
IT Cooling
OPTIONAL ACCESSORIES
MINIPAC
MODEL
SIZE
169 - Mounting brackets
311 - Electric heater
909 - Clogged filters alarm
923 - RC-Com MBUS/JBUS Serial board
931 - BACnet Ethernet - SNMP - TCP/IP Serial board
932 - BACnet MS/TP Serial board
04 R1
S0 XS
05 R1
S1 XS
06 Z1
S1 XS
08 Z1
S1/S XS
09 Z1
S1/S XS
11 Z1
S2 XS
13 Z1
S2 XS
16 Z1
S3 XS
20 Z1
S3 XS
TECHNICAL DATA
MINIPAC
MODEL
SIZE
Cooling capacity(1)
Total
Sensible
SHR
Unit power input
48VDC power supply from UPS
Power supply from network
Treatment fans
Air flow
Nominal external static pressure
Compressors
Quantity
Capacity steps
Condenser fans
Air flow
Air filter
Efficiency
Refrigerant
Total refrigerant charge
Gas circuits
Power supply
Max operating current (FLA)
48VDC power supply from UPS
Power supply from network
Starting current (LRA)
48VDC power supply from UPS
Power supply from network
EER (1)
Sound pressure - ISO 3744 (2)
On air intake
On front side
Net weight
kW
kW
kW/kW
04 R1
S0 XS
05 R1
S1 XS
06 Z1
S1 XS
08 Z1
S1/S XS
09 Z1
S1/S XS
11 Z1
S2 XS
13 Z1
S2 XS
16 Z1
S3 XS
20 Z1
S3 XS
4,2
4,2
1,00
5,6
5,5
0,99
6,3
6,3
1,00
8,6
8,2
0,96
9,3
9,3
1,00
11,6
11,3
0,97
12,4
12,4
1,00
16,5
16,1
0,98
18,9
18,9
1,00
kW
kW
n.
m3/h
Pa
0,11
0,22
0,22
0,39
0,39
0,48
0,63
0,67
1,09
1,18
1,43
1,88
2,21
2,79
3,00
4,00
4,81
6,50
2
2
2
2
2
2
2
2
2
1100
1750
1750
2200
2200
3200
3700
4300
5000
20
20
20
20
20
30
30
30
30
rotary
rotary
scroll
scroll
scroll
scroll
scroll
scroll
scroll
1
1
1
1
1
1
1
1
1
n.
1
1
1
1
1
1
1
1
1
n.
n.
1
1
1
1
1
1
1
1
1
m3/h
1600
1400
1900
2750
3600
4400
4400
4400
6200
n.
1
1
1
1
1
1
1
2
2
G4
G4
G4
G4
G4
G4
G4
G4
G4
R407C
R407C
R407C
R407C
R407C
R407C
R407C
R407C
R407C
kg
1,3
1,6
1,6
1,7
1,7
3,0
3,3
4,0
4,5
n.
1
1
1
1
1
1
1
1
1
V/Ph/Hz 230/1/50+48VDC 230/1/50+48VDC 230/1/50+48VDC 230/1/50+48VDC 230/1/50+48VDC 400/3/50+48VDC 400/3/50+48VDC 400/3/50+48VDC 400/3/50+48VDC
A
A
3,7
8,6
6,0
9,9
6,0
12,1
9,7
15,5
9,7
18,8
11,5
8,2
14,6
9,2
15,5
13,6
24,0
19,0
A
A
kW/kW
2,0
32,6
3,29
2,0
33,4
3,36
2,0
47,7
3,00
2,0
61,7
3,30
2,0
77,5
2,91
2,0
47,2
3,33
2,0
53,2
2,68
2,0
67,2
3,01
2,0
104,0
2,49
dB(A)
dB(A)
kg
63,0
54,0
135
55,0
52,0
155
55,0
57,0
165
60,0
57,0
195
60,0
62,0
200
64,0
58,0
220
67,0
58,0
235
69,0
58,0
270
71,5
64,0
290
THE COOLING CAPACITY DOES NOT CONSIDER THE SUPPLY FANS MOTOR THERMAL LOAD
(1) Referred to entering air at 28C with 40% RH and outdoor air temperature 35C
(2) Sound pressure 1m far in free field according to ISO3744 norm.
kW
n.
04 R1
S0 XS
05 R1
S1 XS
06 Z1
S1 XS
08 Z1
S1/S XS
09 Z1
S1/S XS
11 Z1
S2 XS
13 Z1
S2 XS
16 Z1
S3 XS
20 Z1
S3 XS
1,0
1
1,5
1
1,5
1
1,5
1
1,5
1
4,5
1
4,5
1
4,5
1
4,5
1
107
MINIPAC
IT Cooling
DIMENSIONS (mm)
SIZE
S0
S1
S1S
S2
S3
a
660
831
903
1000
1000
b
500
535
620
700
700
c
1303
1500
1760
2004
2352
108
ENERTEL
ENERTEL: Telecommunication packaged air conditioners
with free-cooling system for indoor installation.
Cooling Capacity: 5 15 kW
ENERTEL
rcgroupairconditioning
MAIN FEATURES
Telecommunication packaged air conditioners.
Proportional automatic free-cooling system. Three working mode.
22 models, 3 versions available for a wide selection opportunity.
Average step of 1,5kW.
Scroll compressor.
R407c refrigerant charge, Over version.
R134a refrigerant charge, Under version and DL version.
Supply centrifugal fans directly coupled to the electric motors.
Upflow air delivery (Over version), Downflow air delivery (Under version),
Displacement air delivery (DL version).
Double power supply (Network + 48VDC UPS)
Suitable for indoor installation.
R407c
R134a
FREE
COOLING
UP
FLOW
DOWN
FLOW
DISPLA
CEMENT
UPS
48VDC
MAIN BENEFITS
The proprietary software foresees unit working with the lowest noise
emission during the night.
Working continuity even during black-out periods.
Automatic restart of the unit.
Availability of electric heater.
Full frontal inspection.
Easily of maintenance.
PROPORTIONAL FREE-COOLING SYSTEM.
The cooling system is totally proportional and allows three working
modes:
total free-cooling: only fresh air is used to cool the ambient;
partial free-cooling: the fresh air is used for a pre-cooling and the
19632013 fiftycoolyears RCGROUP SpA G_ITC_RCW8.4
f i f t y c o o l y e a r s
109
ENERTEL
MAIN COMPONENTS
FRAMEWORK
Galvanized steel sheet base externally painted with epoxy powders.
Housing consisting of aluminium profile frame, jointed with reinforced PVC
corners and galvanized steel sheet panels externally coated with PVC film.
Panels internally insulated by noise absorption material fixed by special PVC
gasket, granting also the panels air tightness. The panels are fixed by stainless
steel screws contained in a small cage not projecting from the housing.
Total front access for routine maintenance.
ON / OFF COMPRESSOR
Scroll compressor.
Electric motor with direct on line starting.
Rubber supports.
FILTER SECTION
Washable air filters with G3 efficiency, with cells in synthetic fibre and metallic
frame (EN 779-2002).
EVAPORATING SECTION
Heat exchanger coil with internally corrugated copper tubes and high efficiency
aluminium fins, specifically developed to provide high heat transfer and lower
pressure drops.
Frame in galvanized steel.
Condensate tray in peraluman with PVC flexible discharge pipe.
SUPPLY FANS SECTION
Power supply 48VDC from UPS
ENERTEL O (Over)
Centrifugal fans with backward curved blades, single suction and without scroll
housings (Plug-fan), directly coupled to external rotor electric motor.
ENERTEL U (Under) ENERTEL DL (Displacement)
Double suction centrifugal fans with forward curved vanes directly coupled to
external rotor electric motor.
FOR ALL SERIES
Brushless type electric motor with continuous variation of the rotation speed.
The motor rotation control is obtained by signal coming from the microprocessor
control.
Temperature sensor on room air intake
Temperature sensor on room air delivery.
Grille on room air suction.
Double row adjustable grille on air delivery (ENERTEL O).
System for air flow loss alarm
Air delivery:
o ENERTEL U: Downflow air delivery for raised floor
o ENERTEL O. Frontal air delivery or upflow air delivery
o ENERTEL DL: Displacement air delivery
IT Cooling
DIRECT FREE-COOLING SECTION
Power supply 48VDC from UPS
Deviating damper on ambient air.
Proportional servomotor directly driven by microprocessor control.
Grille on ambient air suction.
Temperature sensor on ambient air.
ELECTRICAL PANEL
In accordance with EN60204-1 norms, suitable for outdoor installation, complete
with:
Double power supply, from network and from UPS 48VDC
Units size S1:
- 230/1/50 power supply for compressor, condenser fan and eventual electric
heater.
Units size S2, S3:
- 400/3/50+N power supply for compressor, condenser fan and eventual electric
heater.
For all units:
- 48 VDC power supply from UPS for supply fans, free-cooling damper
servomotor, auxiliary circuit and microprocessor control.
Magnetothermic switch for 230/1/50 or 400/3/50+N power supply line (from
network)
Magnetothermic switch for 48VDC power supply line (from UPS)
Contactor on compressor.
Phases monitoring relay (only S2, S3 units)
Auxiliary circuit 48VDC (from UPS).
Terminals for General Alarm 1
Terminals for General Alarm 2
CONTROL SYSTEM
Power supply 48VDC from UPS
Microprocessor system with graphic display for control and monitor of operating
and alarms status. The system includes:
- Real time clock.
- Main components hour-meter.
- Menu with protection password.
- LAN connection.
- LN function to obtain a low noise unit running. The system works proportionally to
the load on the fan rotation speed either of the condenser fan or the supply fan.
The system allows a low noise unit running during night time anyway according
to the programmed sets.
- Automatic restart of the unit in case of power failure
REFRIGERANT CIRCUIT
Thermostatic expansion valve.
Sight glass.
Filter dryer on liquid line.
Pressure transducer with indication, control and protection functions, on high
pressure.
Low pressure safety switch.
Refrigerant circuit with copper tubing with anticondensate insulation of the suction
line.
ENERTEL O (Over)
R407C refrigerant charge and lubricant oil.
ENERTEL U (Under) ENERTEL DL (Displacement)
R134a refrigerant charge and lubricant oil.
CONDENSING COIL
Heat exchanger coil with high efficiency aluminium fins, specifically developed
to provide high heat transfer and lower pressure drops. The combination of two
factors, special tubes and fins, allow to optimally combine the following aspects:
- Maximum capacity relative to the size of the exchanger.
- Minimum charge of refrigerant.
- Reduction of the air flow required for the heat exchange.
Frame in galvanized steel.
Grille on air suction/discharge.
CONDENSER FANS SECTION
Double suction centrifugal fans with forward curved vanes directly coupled to
external rotor electric motor.
External rotor AC type electric motor with stepless variable speed for condensing
pressure control.
110
ENERTEL
IT Cooling
OPTIONAL ACCESSORIES - ENERTEL O
ENERTEL O
MODEL
SIZE
311 - Electric heater
909 - Clogged filters alarm
919 - Clock card
923 - RC-Com MBUS/JBUS Serial board
931 - BACnet Ethernet - SNMP - TCP/IP Serial board
932 - BACnet MS/TP Serial board
939 - Fresh air kit
940 - Fresh air kit with plenum
05 Z1
S1 XS
06 Z1
S1 XS
07 Z1
S1 XS
08 Z1
S2 XS
10 Z1
S2 XS
11 Z1
S2 XS
13 Z1
S3 XS
15 Z1
S3 XS
06 Q1
S1 XS
07 Q1
S1 XS
08 Q1
S1 XS
09 Q1
S2 XS
10 Q1
S2 XS
13 Q1
S3 XS
15 Q1
S3 XS
05 Z1
S1 XS
06 Z1
S1 XS
07 Z1
S1 XS
08 Z1
S2 XS
10 Z1
S2 XS
11 Z1
S2 XS
13 Z1
S3 XS
15 Z1
S3 XS
5,4
5,4
1,00
6,1
6,1
1,00
7,0
7,0
1,00
10,0
9,4
0,94
11,0
10,4
0,95
12,2
11,5
0,94
14,4
14,3
0,99
15,4
15,2
0,99
0,12
1,80
1
1700
0
scroll
1
1
1
2200
200
1
G3
R407C
2,2
1
230/1/50+48VDC
0,12
2,18
1
1700
0
scroll
1
1
1
2200
200
1
G3
R407C
2,2
1
230/1/50+48VDC
A
A
4,0
11,0
4,0
14,0
4,0
17,4
6,5
10,1
6,5
11,2
6,5
12,0
6,5
13,2
6,5
17,6
A
A
kW/kW
1,0
37,6
2,83
1,0
49,6
2,63
1,0
63,6
2,42
3,0
37,0
3,21
2,0
45,0
3,06
2,0
51,0
3,07
2,0
57,2
3,03
2,0
71,2
2,70
dB(A)
dB(A)
kg
62,0
65,0
215
62,0
65,0
220
62,0
65,0
235
65,0
68,0
320
65,0
68,0
330
65,0
68,0
340
65,0
68,0
390
65,0
68,0
400
kW
kW
kW/kW
kW
kW
n.
m3/h
Pa
n.
n.
n.
m3/h
Pa
n.
kg
n.
0,12
0,24
0,24
0,23
0,23
0,23
2,76
2,87
3,35
3,74
4,52
5,47
1
2
2
2
2
2
1700
3000
3000
3000
3400
3400
0
0
0
0
0
0
scroll
scroll
scroll
scroll
scroll
scroll
1
1
1
1
1
1
1
1
1
1
1
1
1
2
2
2
2
2
2200
4000
4000
3900
4200
4200
200
200
200
200
200
200
1
2
2
2
2
2
G3
G3
G3
G3
G3
G3
R407C
R407C
R407C
R407C
R407C
R407C
2,2
3,5
3,5
3,7
5,0
5,0
1
1
1
1
1
1
230/1/50+48VDC 400/3/50+N +48VDC 400/3/50+N +48VDC 400/3/50+N +48VDC 400/3/50+N +48VDC 400/3/50+N + 48VDC
THE COOLING CAPACITY DOES NOT CONSIDER THE SUPPLY FANS MOTOR THERMAL LOAD
(1) Referred to entering air at 28C with 40% RH and outdoor air temperature 35C
(2) Sound pressure 1m far in free field according to ISO3744 norm.
kW
n.
05 Z1
S1 XS
06 Z1
S1 XS
07 Z1
S1 XS
08 Z1
S2 XS
10 Z1
S2 XS
11 Z1
S2 XS
13 Z1
S3 XS
15 Z1
S3 XS
1,7
1
1,7
1
1,7
1
4,5
1
4,5
1
4,5
1
4,5
1
4,5
1
111
ENERTEL
IT Cooling
06 Q1
S1 XS
07 Q1
S1 XS
08 Q1
S1 XS
10 Q1
S2 XS
11 Q1
S2 XS
13 Q1
S3 XS
15 Q1
S3 XS
6,5
6,0
0,92
7,3
6,7
0,92
7,8
7,2
0,93
9,9
9,1
0,92
10,8
10,3
0,95
14,7
13,7
0,93
15,4
14,6
0,95
0,3
1,9
1
1850
50
scroll
1
1
1
2100
200
1
G3
R134a
2,2
1
230/1/50+48VDC
0,3
2,2
1
1850
50
scroll
1
1
1
2100
200
1
G3
R134a
2,2
1
230/1/50+48VDC
0,3
2,6
1
1850
50
scroll
1
1
1
2100
200
1
G3
R134a
2,2
1
230/1/50+48VDC
0,3
3,0
2
2400
50
scroll
1
1
1
2500
150
2
G3
R134a
3,5
1
400/3/50+N +48VDC
0,3
3,7
2
2400
50
scroll
1
1
1
2500
150
2
G3
R134a
3,5
1
400/3/50+N +48VDC
0,6
4,5
2
3800
50
scroll
1
1
2
4000
200
2
G3
R134a
5,0
1
400/3/50+N +48VDC
0,6
5,0
2
3800
50
scroll
1
1
2
4000
200
2
G3
R134a
5,0
1
400/3/50+N +48VDC
A
A
7,7
17,4
7,7
19,9
7,7
25,7
8,5
10,8
8,5
15,2
15,0
18,5
15,0
21,0
A
A
kW/kW
1,0
63,6
3,00
1,0
78,6
2,97
1,0
102,6
2,67
2,0
51,8
2,93
2,0
68,8
2,67
2,0
79,0
2,90
2,0
106,0
2,73
dB(A)
dB(A)
kg
51,0
63,0
215
54,0
65,0
230
54,0
65,0
240
55,0
65,0
320
55,0
65,0
320
57,0
68,0
380
57,0
68,0
390
kW
kW
kW/kW
kW
kW
n.
m3/h
Pa
n.
n.
n.
m3/h
Pa
n.
kg
n.
THE COOLING CAPACITY DOES NOT CONSIDER THE SUPPLY FANS MOTOR THERMAL LOAD
(1) Referred to entering air at 28C with 40% RH and outdoor air temperature 35C
(2) Sound pressure 1m far in free field according to ISO3744 norm.
kW
n.
06 Q1
S1 XS
07 Q1
S1 XS
08 Q1
S1 XS
10 Q1
S2 XS
11 Q1
S2 XS
13 Q1
S3 XS
15 Q1
S3 XS
3,0
1
3,0
1
3,0
1
3,0
1
3,0
1
4,5
1
4,5
1
SIZE
S1
S2
S3
a
650
990
1190
b
650
650
650
c
2000
2000
2000
c
DIMENSIONS - ENERTEL DL, ENERTEL U (mm)
SIZE
S1
S2
S3
112
a
750
950
1200
b
625
625
625
c
2250
2250
2250
MARK
MARK: Telecommunication packaged air conditioners
with free-cooling system for indoor or outdoor installation.
Cooling Capacity: 5,8 9,1 kW
INVERTER
UPS48VDC
FREECOOLING
MARK
rcgroupairconditioning
MAIN FEATURES
Telecommunication packaged air conditioners.
Proportional automatic free-cooling system. Three working mode.
3 models available for a wide selection opportunity.
Modulating cooling capacity control.
Rotary or On/off or BLDC scroll compressor.
EER up to 4,3.
R410A refrigerant charge.
EC plug-fans.
Horizontal air flow.
Double power supply (Network + 48VDC UPS)
Suitable for indoor or outdoor installation.
MAIN BENEFITS
The proprietary software foresees unit working with the lowest noise
emission during the night.
Working continuity even during black-out periods.
Automatic restart of the unit.
BLDC Inverter scroll compressor and EC plug-fans for a higher energy
efficiency.
Availability of electric heater.
Choice between indoor and outdoor installation.
Free-cooling operation with +45% of air flow compared to the mechanical
cooling operation. This allows to transfer more cooling power to the air
conditioned room, maximizing energy savings.
Easily of maintenance.
INVERTER
FREE
COOLING
R410A
FRONT
FLOW
UPS
48VDC
f i f t y c o o l y e a r s
113
MARK
MAIN COMPONENTS
FRAMEWORK
Base and frame in galvanized steel sheet, painted with epoxy powders.
Galvanized steel sheet panels painted with epoxy powders, internally
insulated with noise absorption material and seals to ensure air tight with
the panels.
Panels fixed with safety screws.
Total front access for routine maintenance.
Brackets for unit wall mounting.
Colour RAL 9002
ON / OFF COMPRESSOR
MARK 06
Rotary compressor with rotary vane optimized for R410A refrigerant.
Electric motor with direct on line starting.
Rubber supports.
MARK 09
Scroll compressor with spiral profile optimized for R410A refrigerant.
Electric motor with direct on line starting.
Rubber supports.
INVERTER DRIVEN COMPRESSOR
MARK 10 INV
scroll compressor BLDC inverter with spiral profile optimized for R410A
refrigerant.
Synchronous brushless inverter driven motor.
Inverter for modulating capacity control.
Reactance for the reduction of electromagnetic noise and interference.
Crankcase heater.
Rubber supports.
Soundproof cap.
FILTER SECTION
Washable air filters with G4 efficiency, with cells in synthetic fibre and
metallic frame (EN 779-2002).
EVAPORATING SECTION
Heat exchanger coil with internally corrugated copper tubes and high
efficiency aluminium fins, specifically developed to provide high heat
transfer and lower pressure drops.
Frame in galvanized steel.
Condensate tray in peraluman with PVC flexible discharge pipe.
SUPPLY FANS SECTION
Power supply 48VDC from UPS
Centrifugal fans with backward curved blade, single suction and without
scroll housings (Plug-fan), directly coupled to external rotor electric motor.
- Impeller in aluminium exempt from rust formation.
- Brushless type synchronous EC motor with integrated electronic
commutated system and continuous variation of the rotation speed.
The motor rotation control is obtained with the EC system (Electronic
Commutation) that manage the motor according to the signal coming from
the microprocessor control.
Temperature sensor on room air intake
Temperature sensor on room air delivery.
Grille on room air suction.
Grille on room air delivery.
System for air flow loss alarm
REFRIGERANT CIRCUIT
Thermostatic expansion valve for models MARK 06 and MARK 09.
Electronic expansion valve for model MARK 10 INV
Sight glass.
Filter dryer on liquid line.
Pressure transducer with indication, control, protection and limit functions
on high pressure.
Pressure transducer with indication, control and protection functions on low
pressure.
Refrigerant circuit with copper tubing with anticondensate insulation of the
suction line.
R410A refrigerant charge and lubricant oil
IT Cooling
- Maximum capacity relative to the size of the exchanger.
- Minimum charge of refrigerant.
- Reduction of the air flow required for the heat exchange.
Frame in galvanized steel.
Grille on air suction/discharge.
CONDENSER FANS SECTION
Power supply 48VDC from UPS
Centrifugal fans with backward curved blades, single suction and without
scroll housings (Plug-fan), directly coupled to external rotor electric motor.
- Impeller in aluminium exempt from rust formation.
- Brushless type synchronous EC motor with integrated electronic
commutated system and continuous variation of the rotation speed.
The motor rotation control is obtained with the EC system (Electronic
Commutation) that manage the motor according to the signal coming from
the microprocessor control.
DIRECT FREE-COOLING SECTION
Power supply 48VDC from UPS
Deviating damper on ambient air.
Proportional servomotor directly driven by microprocessor control.
Grille on ambient air suction.
Temperature sensor on ambient air.
The free-cooling system does not require the installation of overpressure
damper or air expulsion system, into the room.
ELECTRICAL PANEL
In accordance with EN60204-1 norms, suitable for outdoor installation,
complete with:
Double power supply, from network and from UPS 48VDC
MARK 06 MARK 10 INV:
- 230/1/50 power supply for compressor and eventual electric heater.
MARK 09:
- 400/3/50 power supply for compressor and eventual electric heater.
For all units:
- 48 VDC power supply from UPS for supply fan, condenser fan, freecooling damper servomotor, auxiliary circuit and microprocessor control.
Magnetothermic switch for 230/1/50 or 400/3/50 power supply line (from
network)
Magnetothermic switch for 48VDC power supply line (from UPS)
Contactor on compressor (models MARK 06 and MARK 09)
Phases monitoring relay (model MARK 09)
Auxiliary circuit 48VDC (from UPS).
Terminals for General Alarm
CONTROL SYSTEM
Power supply 48VDC from UPS
Microprocessor system for control and monitor of operating and alarms
status. The system includes:
- 8-line remote display with keyboard. The display is supplied with a cable
for connection to the controller and integrated magnetic plate. IP65 class
protection.
- Real time clock.
- Main components hour-meter.
- Menu with protection password.
- Integrated Ethernet port
- Automatic restart of the unit in case of power failure
- LN function to obtain a low noise unit running. The system works
proportionally to the load on the fan rotation speed either of the
condenser fan or the supply fan. The system allows a low noise unit
running during night time anyway according to the programmed sets.
- AIO (All In One) function of the Free-Cooling system. During free-cooling
operation are used at the same time the supply fan and the condenser
fan at higher speeds (+45% of air flow) compared to the mechanical
cooling operation. This allows to transfer more cooling power to the air
conditioned room, maximizing energy savings.
The layout of the unit allows the expulsion of air injected with the freecooling system directly from the machine avoiding the installation of
overpressure damper.
- NBC (No Break Cooling) function to ensure continuity of cooling in alarm
condition. The free-cooling system automatically activates the case of
alarm / lock of the compressor or black-out of the electricity grid.
CONDENSING COIL
Heat exchanger coil with high efficiency aluminium fins, specifically
developed to provide high heat transfer and lower pressure drops. The
combination of two factors, special tubes and fins, allow to optimally
combine the following aspects:
114
MARK
IT Cooling
OPTIONAL ACCESSORIES - MARK
MARK
MODEL
310 - Electric heater
909 - Clogged filters alarm
912 - Air flow loss alarm EC fan
1014 - Indoor installation
220 - Electronic expansion valve
06
09
10 INV
TECHNICAL DATA
Model
Cooling capacity(1)
Total
Sensible
SHR
Unit power input
Treatment fans
Air flow
Compressors
Quantity
Capacity steps
Condenser fans
Air flow
Refrigerant
Total refrigerant charge
Gas circuits
Power supply
Max operating current (FLA)
Starting current (LRA)
EER (1)
Sound pressure - ISO 3744 (2)
In-room side
Ambient side
Net weight
06
09
kW/kW
5,8
5,8
1,0
1,9
1
1200
rotary
1
1
1
2000
R410A
1,7
1
230-1-50 + 48 VDC
20,6
67
3,06
dB(A)
dB(A)
Kg
42,8
53,7
196
kW
kW
kW/kW
kW
n.
m/h
n.
n.
n.
m/h
Kg
n.
V/Ph/Hz
9,0
9,0
1,0
3,2
1
2000
scroll
1
1
1
3200
R410A
1,7
1
400-3-50 + 48 VDC
29,6
67,2
2,79
10 INV
min
4,3
4,3
1,0
1,0
1
2000
scoll inverter
1
MOD
1
3200
R410A
1,7
1
230-1-50 + 48 VDC
45,3
24,2
4,30
10 INV
nom
7,1
7,1
1,0
1,9
1
2000
scroll inverter
1
MOD
1
3200
R410A
1,7
1
230-1-50 + 48 VDC
45,3
24,2
3,65
10 INV
max
9,1
9,1
1,0
3,4
1
2000
scroll inverter
1
MOD
1
3200
R410A
1,7
1
230-1-50 + 48 VDC
45,3
24,2
2,64
52,6
62,3
200
52,6
62,3
187
52,6
62,3
187
52,6
62,3
187
THE COOLING CAPACITY DOES NOT CONSIDER THE SUPPLY FANS MOTOR THERMAL LOAD
(1) Referred to entering air at 30C with 35% RH and outdoor air temperature 35C
(2) Sound pressure 1m far in free field according to ISO3744 norm.
INDOOR
OUTDOOR
OUTDOOR
INDOOR
OUTDOOR
MECHANICAL COOLING
INDOOR
MECHANICAL COOLING +
FREE - COOLING
FREE - COOLING
115
MARK
IT Cooling
INDOOR
OUTDOOR
MECHANICAL COOLING
INDOOR
OUTDOOR
MECHANICAL COOLING +
FREE - COOLING
INDOOR
OUTDOOR
FREE - COOLING
DIMENSIONS (mm)
SIZE
MARK
a
750
b
660
c
1995
116
RCGROUP
19632013
Technical data and dimensions are not binding. RC GROUP S.p.A. reserves the right for G_ITC_RCW8.4
changes and / or modifi
cations SpA
without
notice. fiftycoolyears
MAXIMO
MAXIMO: Packaged air cooled liquid chillers with free-cooling system
for outdoor installation, equipped with scroll compressors and axial fans
Cooling Capacity: 22 299 kW
Free-Cooling Capacity: 20 197 kW
FREECOOLING
MAXIMO
rcgroupairconditioning
MAIN FEATURES
Air cooled liquid chiller with free-cooling system.
29 models available, for a wide selection opportunity.
Average step of 12,5kW.
EER up to 2,92.
ESEER up to 3,80.
Scroll compressors.
R410A Refrigerant charge.
Single or double refrigerant circuit.
Plate type heat exchangers.
EC Axial fans.
Single air circuit.
Electronic expansion valve.
Suitable for outdoor installation.
MAIN BENEFITS
Units equipped with two scroll compressors for refrigerant circuit to reach
a high efficiency.
Units with single and double refrigerant circuits.
Indirect free cooling system.
High EER and ESEER.
EC axial fans for a high efficiency.
Availability of kit for the reduction and the extreme reduction of the noise.
Availability of pumping groups.
Availability of partial heat recovery system.
Easily of maintenance.
Complete set of components dedicated to the safety of the unity.
Eurovent Certification.
19632013 fiftycoolyears RCGROUP SpA G_ITC_RCW8.4
FREE
COOLING
R410A
PLATE
EC
f i f t y c o o l y e a r s
117
MAXIMO
MAIN COMPONENTS
FRAMEWORK
Base, self supporting frame and panelling in steel plate with protective
surfaces treatment in compliance with UNI ISO 9227/ASTMB117 and ISO
7253, and painted with epoxy powders.
Colour: RAL 9002
COMPRESSORS
Orbiting spiral (SCROLL) hermetic compressors with spiral profile optimized
for R410A refrigerant.
ON / OFF capacity control (0 / 100% each compressor).
2-pole 3-phase electric motor with direct on line starting.
Phase sequence electronic relay.
Crankcase heater.
Electric motor thermal protection via internal winding temperature sensors.
Rubber supports.
EVAPORATOR
Copper brazed plate type with cover plates, plates and connections in AISI
316 stainless steel:
- With single refrigerant circuit for S version machines.
- With double refrigerant circuit for D version machines.
Anticondensate insulation made of polyurethane.
Temperature sensors on water inlet and outlet.
Differential water pressure switch for water flow control.
Antifreeze heater.
CONDENSING COIL
Heat exchanger coil with internally corrugated copper tubes and high
efficiency aluminium fins, specifically developed to provide high heat
transfer and lower pressure drops. The combination of two factors, special
tubes and fins, allow to optimally combine the following aspects:
- Maximum capacity relative to the size of the exchanger.
- Minimum charge of refrigerant.
- Reduction of the air flow required for the heat exchange.
Sub-cooling circuit to allow a significant increase in cooling capacity.
Frame in galvanized steel.
FREE-COOLING COIL
Heat exchanger coil with copper tubes and high efficiency aluminium fins,
specifically developed to provide high heat transfer and lower pressure
drops. The combination of two factors, special tubes and fins, allow to
optimally combine the following aspects:
- Maximum capacity relative to the size of the exchanger.
- Reduction of the air flow required for the heat exchange.
Frame in galvanized steel.
Motorized valves for free-cooling water circuit control.
Temperature sensor on ambient air.
IT Cooling
REFRIGERANT CIRCUIT
Components for each refrigerant circuit:
Thermostatic expansion valve up to model 76 P2 C3 D included.
Electronic expansion valve from model 98 P2 C4 S included.
The valve allows high performance and system efficiency thanks to a
timely and accurate response to changes in temperature and pressure. The
electronic expansion valve exclude the installation of the electromagnetic
valve on liquid line.
Sight glass.
Liquid receiver.
Electromagnetic valve on liquid line. The electromagnetic valve is not
installed when the electronic expansion valve is present.
Filter dryer on liquid line.
Service valves on liquid line and gas discharge.
Safety valve on low pressure side.
Safety valve on high pressure side.
Pressure transducers with indication, control and protection functions, on
low and high refrigerant pressure.
High pressure safety switch with manual reset.
Refrigerant circuit with copper tubing with anticondensate insulation of the
suction line.
Plastic capillary hoses for pressure sensors connection.
R410A refrigerant charge.
ELECTRICAL PANEL
In accordance with EN60204-1 norms, suitable for outdoor installation,
complete with:
Main switch with door lock safety.
Magnetothermic switch or fuses for each compressor.
Magnetothermic switches for fans or water pumps (if scheduled).
Contactors for each load.
Transformer for auxiliary circuit and microprocessor supply.
Panel with machine controls.
Power supply: 400/3/50.
CONTROL SYSTEM
MP.COM microprocessor system with graphic display for control and
monitor of operating and alarms status. The system includes:
- Voltage free contact for remote general alarm.
- Main components hour-meter.
- Nonvolatile Flash memory for data storage.
- Menu with protection password.
- LAN connection.
FANS SECTION
Axial fans with sickle-shaped blades, fan guard and optimized for low noise
levels.
Brushless type synchronous EC motor with integrated electronic
commutated system and continuous variation of the rotation speed.
The motor rotation control is obtained with the EC system (Electronic
Commutation) that manage the motor according to the 010V proportional
signal coming from the microprocessor control.
Maintenance-free bearings
IP54 enclosure class.
118
MAXIMO
IT Cooling
OPTIONAL ACCESSORIES
MAXIMO
SIZE
739 - Pumping group (1 pump)
740 - Pumping group (2 pumps)
768 - Chilled water storage tank
150 - LNO kit (noise reduction)
151 - ELN kit (extremely noise reduction)
170 - Spring antivibration holders (kit)
172 - Rubber support (kit)
118 - Kit brine A (for glycol solution production up to -6C)
119 - Kit brine B (for glycol solution production up to -12C)
79 - Electrical panel heating system
450 - Partial heat recovery
251 - Coils protection nets
351 - Coils with pre-painted fins
Condensing coil in special execution
160 - Silencing plenum on condensing air discharge
731 - Safety water flow switch
143 - Glycol free
605 - Compr. power factor capacitor - 0,9
1002 - Soft Starter
83 - Compressor operation indicator
Expansion valve energy reserve module
Ambient temperature sensor
81 - Phases sequence control
1003 - Analogic flowmeter
1005 - Power supply analyzer
1009 - Multimeter kit
919 - Clock card
923 - RC-Com MBUS/JBUS Serial board
926 - LON Serial board
931 - BACnet Ethernet - SNMP - TCP/IP Serial board
932 - BACnet MS/TP Serial board
942 - Serial card for GSM Modem
943 - Data Logger
962 - Kit modem GSM
957 - Plantwatch without modem
930 - Remote graphic terminal kit
889 - Master plant SEQUENCER
RC CLOUD PLATFORM
C1
C2
C3
C4
C5
C5H
119
MAXIMO
IT Cooling
ELN KIT
OPTIONAL
STANDARD
MAXIMO
1.
2.
3.
4.
5.
6.
120
SIZE
Cooling capacity (1)
Unit power input
Free-Cooling capacity (2)
Total water flow rate
Total pressure drop
Compressors
Quantity
Capacity steps
Axial fans EC
Total air flow
Air circuits
Refrigerant
Total refrigerant charge (optional excluded)
Gas circuits
Power supply
Max unit operating current (FLA)
Unit starting current (LRA)
EER (1)
ESEER
Sound power level [Lw] (3)
Average sound pressure level [LPm] (4)
Net weight
Hydraulic connections
Evaporator IN/OUT - ISO 7/1 R
Evaporator IN/OUT - OD (5)
Partial heat recovery (6)
Heating capacity
Pumping group
1 pump - 2 poles electric motor
2 pump - 2 poles electric motor
Water tank - volume
Cooling capacity (1)
Unit power input
Free-Cooling capacity (2)
Total air flow
EER (1)
Sound power level [Lw] (3)
Average sound pressure level [LPm] (4)
Cooling capacity (1)
Unit power input
Free-Cooling capacity (2)
Total air flow
EER (1)
Sound power level [Lw] (3)
Average sound pressure level [LPm] (4)
Cooling capacity (1)
Unit power input
Free-Cooling capacity (2)
Total air flow
EER (1)
Sound power level [Lw] (3)
Average sound pressure level [LPm] (4)
dB(A)
dB(A)
kg
21 P1
S
C1
22,2
7,9
19,8
4,1
102
scroll
1
1
1
7500
1
R410A
11,3
1
400/3/50
18,4
96,5
2,81
3,31
80,8
64,2
430
24 P1
S
C1
25,0
9,3
20,6
4,6
128
scroll
1
1
1
7500
1
R410A
11,3
1
400/3/50
23,6
112,5
2,69
3,20
81,2
64,6
440
28 P1
S
C1
29,6
11,7
24,9
5,5
161
scroll
1
1
1
9650
1
R410A
11,3
1
400/3/50
24,8
119,6
2,52
3,18
82,6
66,0
440
30 P1
S
C1
32,4
13,1
25,7
6,0
170
scroll
1
1
1
9650
1
R410A
11,5
1
400/3/50
27,9
119,6
2,47
3,07
81,8
65,2
440
34 P1
S
C2
39,0
13,4
33,3
7,2
146
scroll
1
1
2
12000
1
R410A
13,7
1
400/3/50
35,7
143,0
2,92
3,52
83,6
66,4
600
40 P1
S
C2
43,9
16,1
37,5
8,1
168
scroll
1
1
2
14000
1
R410A
13,7
1
400/3/50
38,9
177,0
2,72
3,22
86,6
69,4
600
50 P1
S
C2
54,0
21,6
44,7
10,0
169
scroll
1
1
2
17300
1
R410A
15,0
1
400/3/50
45,4
228,2
2,50
3,00
89,8
72,5
740
52 P2
S
C2
56,0
22,5
45,1
10,3
180
scroll
2
2
2
17300
1
R410A
15,3
1
400/3/50
49,6
143,2
2,49
3,13
87,2
70,0
700
mm
1 1/2"
-
1 1/2"
-
1 1/2"
-
1 1/2"
-
2"
-
2"
-
2"
-
2"
-
7,7
8,6
10,2
11,1
13,4
15,1
18,6
19,3
1,1
130
22,2
8,0
19,8
7500
2,79
80,3
63,7
21,7
8,0
19,6
6375
2,70
76,7
60,1
20,9
8,3
19,3
5250
2,52
72,8
56,2
1,1
130
25,0
9,4
20,6
7500
2,67
80,4
63,8
24,3
9,5
20,4
6375
2,55
76,9
60,3
23,3
9,9
20,1
5250
2,36
73,3
56,8
1,1
130
29,6
11,7
24,9
9650
2,52
82,1
65,5
28,8
11,9
24,7
8203
2,42
78,5
61,9
27,6
12,2
24,4
6755
2,26
74,6
58,0
1,1
130
32,4
13,1
25,7
9650
2,47
81,1
64,5
31,3
13,3
25,4
8203
2,36
77,6
61,0
29,8
13,8
25,0
6755
2,16
73,9
57,3
1,5
210
39,0
13,4
33,3
12000
2,91
83,0
65,8
37,9
13,6
33,0
10200
2,78
79,4
62,2
36,4
14,1
32,6
8400
2,58
75,7
58,5
1,5
210
43,9
16,3
37,5
14000
2,70
86,2
69,0
42,8
16,3
37,2
11900
2,62
82,5
65,3
41,1
16,7
36,8
9800
2,46
78,5
61,3
1,5
210
54,0
21,6
44,7
17300
2,50
88,4
71,2
52,6
21,7
44,4
14705
2,42
85,2
68,0
50,5
22,4
43,9
12110
2,25
82,3
65,1
1,5
210
56,0
22,5
45,1
17300
2,49
87,0
69,8
54,2
22,9
44,8
14705
2,37
83,2
66,0
51,7
23,6
44,2
12110
2,19
79,0
61,8
kW
kW
kW
m/h
kPa
n.
n.
n.
m/h
n.
kg
n.
V/Ph/Hz
A
A
kW/kW
kW
kW
kW
l
kW
kW
kW
m/h
kW/kW
dB(A)
dB(A)
kW
kW
kW
m/h
kW/kW
dB(A)
dB(A)
kW
kW
kW
m/h
kW/kW
dB(A)
dB(A)
Referred to glycol solution temperature 15/10C; 20% Ethylene glycol solution; air temperature to the condenser 35C. Fouling factor of the exchangers 0,043 mK/kW.
Referred to glycol solution inlet temperature 15C; 20% Ethylene glycol solution; ambient temperature 3C. Fouling factor of the exchangers 0,043 mK/kW.
Sound power level [Lw] according to ISO EN 9614 2.
Average sound pressure level [LPm] 1m far according to ISO EN 3744.
Hydraulic connection with grooved end complete with flexible joint and adapter pipe for solder connection.
Referred to glycol solution temperature 15/10C; 20% Ethylene glycol solution; air temperature to the condenser 35C. Water temperature heat recovery 40/45C 0% glycol
solution; Fouling factor of the exchangers 0,043 mK/kW.
MAXIMO
IT Cooling
TECHNICAL DATA MAXIMO
ELN KIT
OPTIONAL
STANDARD
MAXIMO
1.
2.
3.
4.
5.
6.
SIZE
Cooling capacity (1)
Unit power input
Free-Cooling capacity (2)
Total water flow rate
Total pressure drop
Compressors
Quantity
Capacity steps
Axial fans EC
Total air flow
Air circuits
Refrigerant
Total refrigerant charge (optional excluded)
Gas circuits
Power supply
Max unit operating current (FLA)
Unit starting current (LRA)
EER (1)
ESEER
Sound power level [Lw] (3)
Average sound pressure level [LPm] (4)
Net weight
Hydraulic connections
Evaporator IN/OUT - ISO 7/1 R
Evaporator IN/OUT - OD (5)
Partial heat recovery (6)
Heating capacity
Pumping group
1 pump - 2 poles electric motor
2 pump - 2 poles electric motor
Water tank - volume
Cooling capacity (1)
Unit power input
Free-Cooling capacity (2)
Total air flow
EER (1)
Sound power level [Lw] (3)
Average sound pressure level [LPm] (4)
Cooling capacity (1)
Unit power input
Free-Cooling capacity (2)
Total air flow
EER (1)
Sound power level [Lw] (3)
Average sound pressure level [LPm] (4)
Cooling capacity (1)
Unit power input
Free-Cooling capacity (2)
Total air flow
EER (1)
Sound power level [Lw] (3)
Average sound pressure level [LPm] (4)
dB(A)
dB(A)
kg
52 P2
D
C2
55,8
22,6
45,1
10,3
159
scroll
2
2
2
17300
1
R410A
16,0
2
400/3/50
49,6
143,2
2,47
3,55
87,2
70,0
700
58 P2
S
C3
65,1
23,6
56,7
12,0
157
scroll
2
2
3
21000
1
R410A
21,7
1
400/3/50
57,2
147,5
2,76
3,44
88,2
70,3
930
58 P2
D
C3
65,3
23,9
56,7
12,0
134
scroll
2
2
3
21000
1
R410A
19,3
2
400/3/50
57,2
147,5
2,73
3,80
88,2
70,3
920
62 P1
S
C3
69,3
26,1
59,2
12,8
163
scroll
1
1
3
22000
1
R410A
18,9
1
400/3/50
55,7
276,5
2,66
3,16
93,0
75,1
970
65 P2
S
C3
73,1
27,2
61,6
13,5
182
scroll
2
2
3
23000
1
R410A
22,1
1
400/3/50
69,8
175,5
2,69
3,34
88,1
70,2
940
65 P2
D
C3
72,8
27,0
61,6
13,4
161
scroll
2
2
3
23000
1
R410A
19,6
2
400/3/50
69,8
175,5
2,70
3,68
88,1
70,2
930
76 P2
S
C3
83,4
33,2
68,1
15,4
173
scroll
2
2
3
25750
1
R410A
28,6
1
400/3/50
76,4
212,8
2,51
3,09
87,3
69,4
1000
76 P2
D
C3
83,1
32,8
68,0
15,3
154
scroll
2
2
3
25750
1
R410A
25,5
2
400/3/50
76,4
212,8
2,53
3,47
87,3
69,4
1000
mm
2"
-
76,1
76,1
76,1
76,1
76,1
76,1
76,1
19,2
22,4
22,5
23,8
25,1
25,0
28,7
28,6
1,5
210
55,8
22,6
45,1
17300
2,47
87,0
69,8
54,0
22,8
44,7
14705
2,37
83,2
66,0
51,5
23,6
44,2
12110
2,18
79,0
61,8
3,0
3,0
360
65,1
23,8
56,7
21000
2,74
87,9
70,0
63,2
24,1
56,2
17850
2,62
84,2
66,3
60,6
25,0
55,5
14700
2,42
79,9
62,0
3,0
3,0
360
65,3
24,1
56,7
21000
2,71
87,9
70,0
63,4
24,5
56,3
17850
2,59
84,2
66,3
60,8
25,4
55,6
14700
2,39
79,9
62,0
3,0
3,0
360
69,3
26,2
59,2
22000
2,65
91,5
73,6
67,4
26,3
58,8
18700
2,56
88,4
70,5
64,8
27,2
58,1
15400
2,38
85,6
67,7
3,0
3,0
360
73,1
27,4
61,6
23000
2,67
87,9
70,0
71,0
27,5
61,1
19550
2,58
84,1
66,2
67,9
28,3
60,4
16100
2,40
79,8
61,9
3,0
3,0
360
72,8
27,2
61,6
23000
2,68
87,9
70,0
70,7
27,3
61,1
19550
2,59
84,1
66,2
67,6
28,3
60,3
16100
2,39
79,8
61,9
3,0
3,0
360
83,4
33,2
68,1
25750
2,51
87,0
69,2
81,0
33,3
67,5
21888
2,43
83,3
65,4
77,5
34,1
66,8
18025
2,27
79,1
61,2
3,0
3,0
360
83,1
32,8
68,0
25750
2,53
87,0
69,2
80,6
32,9
67,5
21888
2,45
83,3
65,4
77,2
33,9
66,7
18025
2,28
79,1
61,2
kW
kW
kW
m/h
kPa
n.
n.
n.
m/h
n.
kg
n.
V/Ph/Hz
A
A
kW/kW
kW
kW
kW
l
kW
kW
kW
m/h
kW/kW
dB(A)
dB(A)
kW
kW
kW
m/h
kW/kW
dB(A)
dB(A)
kW
kW
kW
m/h
kW/kW
dB(A)
dB(A)
Referred to glycol solution temperature 15/10C; 20% Ethylene glycol solution; air temperature to the condenser 35C. Fouling factor of the exchangers 0,043 mK/kW.
Referred to glycol solution inlet temperature 15C; 20% Ethylene glycol solution; ambient temperature 3C. Fouling factor of the exchangers 0,043 mK/kW.
Sound power level [Lw] according to ISO EN 9614 2.
Average sound pressure level [LPm] 1m far according to ISO EN 3744.
Hydraulic connection with grooved end complete with flexible joint and adapter pipe for solder connection.
Referred to glycol solution temperature 15/10C; 20% Ethylene glycol solution; air temperature to the condenser 35C. Water temperature heat recovery 40/45C 0% glycol
solution; Fouling factor of the exchangers 0,043 mK/kW.
121
MAXIMO
IT Cooling
ELN KIT
OPTIONAL
STANDARD
MAXIMO
1.
2.
3.
4.
5.
6.
122
SIZE
Cooling capacity (1)
Unit power input
Free-Cooling capacity (2)
Total water flow rate
Total pressure drop
Compressors
Quantity
Capacity steps
Axial fans EC
Total air flow
Air circuits
Refrigerant
Total refrigerant charge (optional excluded)
Gas circuits
Power supply
Max unit operating current (FLA)
Unit starting current (LRA)
EER (1)
ESEER
Sound power level [Lw] (3)
Average sound pressure level [LPm] (4)
Net weight
Hydraulic connections
Evaporator IN/OUT - ISO 7/1 R
Evaporator IN/OUT - OD (5)
Partial heat recovery (6)
Heating capacity
Pumping group
1 pump - 2 poles electric motor
2 pump - 2 poles electric motor
Water tank - volume
Cooling capacity (1)
Unit power input
Free-Cooling capacity (2)
Total air flow
EER (1)
Sound power level [Lw] (3)
Average sound pressure level [LPm] (4)
Cooling capacity (1)
Unit power input
Free-Cooling capacity (2)
Total air flow
EER (1)
Sound power level [Lw] (3)
Average sound pressure level [LPm] (4)
Cooling capacity (1)
Unit power input
Free-Cooling capacity (2)
Total air flow
EER (1)
Sound power level [Lw] (3)
Average sound pressure level [LPm] (4)
dB(A)
dB(A)
kg
98 P2
S
C4
109,0
41,1
88,0
20,0
131
scroll
2
2
4
35000
1
R410A
33,9
1
400/3/50
90,7
271,4
2,65
3,25
87,0
68,4
1470
98 P2
D
C4
108,0
40,1
87,7
19,8
116
scroll
2
2
4
35000
1
R410A
31,3
2
400/3/50
90,7
271,4
2,69
3,64
87,0
68,4
1470
124 P2
S
C4
133,0
54,1
103,0
24,6
113
scroll
2
2
4
42000
1
R410A
38,6
1
400/3/50
113,8
331,9
2,46
3,01
90,9
72,3
1610
124 P2
D
C4
131,0
52,2
103,0
24,2
102
scroll
2
2
4
42000
1
R410A
42,1
2
400/3/50
113,8
331,9
2,51
3,41
90,9
72,3
1610
158 P2
S
C4
171,0
71,0
118,0
31,5
142
scroll
2
2
4
46800
1
R410A
50,9
1
400/3/50
149,3
386,8
2,41
2,96
93,0
74,4
1660
158 P2
D
C4
173,0
72,7
118,0
31,9
134
scroll
2
2
4
46800
1
R410A
42,9
2
400/3/50
149,3
386,8
2,38
3,30
93,0
74,4
1640
180 P2
S
C5
196,0
76,6
140,0
36,2
102
scroll
2
2
5
53000
1
R410A
73,7
1
400/3/50
169,8
473,7
2,56
3,12
93,3
74,1
2240
180 P2
D
C5
198,0
77,6
141,0
36,4
106
scroll
2
2
5
53000
1
R410A
65,8
2
400/3/50
169,8
473,7
2,55
3,51
93,3
74,1
2210
mm
88,9
88,9
88,9
88,9
88,9
88,9
88,9
88,9
kW
37,4
37,0
45,8
45,1
58,8
59,5
67,6
67,9
3,0
4,0
520
109,0
41,1
88,0
35000
2,65
86,2
67,6
106,0
41,4
87,2
29750
2,56
82,7
64,1
102,0
42,9
86,1
24500
2,38
79,2
60,6
3,0
4,0
520
108,0
40,1
87,7
35000
2,69
86,2
67,6
105,0
40,5
86,9
29750
2,59
82,7
64,1
101,0
41,9
85,7
24500
2,41
79,2
60,6
3,0
4,0
520
133,0
54,1
103,0
42000
2,46
90,6
72,0
129,0
54,0
103,0
35700
2,39
86,8
68,2
124,0
55,4
101,0
29400
2,24
82,7
64,1
3,0
4,0
520
131,0
52,2
103,0
42000
2,51
90,6
72,0
127,0
52,0
102,0
35700
2,44
86,8
68,2
122,0
53,3
101,0
29400
2,29
82,7
64,1
3,0
4,0
520
171,0
71,0
118,0
46800
2,41
92,8
74,2
165,0
70,8
117,0
39780
2,33
89,0
70,4
157,0
73,0
115,0
32760
2,15
84,6
66,0
3,0
4,0
520
173,0
72,7
118,0
46800
2,38
92,8
74,2
167,0
72,6
117,0
39780
2,30
89,0
70,4
159,0
75,0
116,0
32760
2,12
84,6
66,0
5,5
7,5
720
196,0
76,6
140,0
53000
2,56
93,2
73,9
190,0
76,9
139,0
45050
2,47
89,4
70,1
181,0
80,1
136,0
37100
2,26
85,0
65,7
5,5
7,5
720
198,0
77,6
141,0
53000
2,55
93,2
73,9
191,0
78,0
139,0
45050
2,45
89,4
70,1
182,0
80,9
136,0
37100
2,25
85,0
65,7
kW
kW
kW
m/h
kPa
n.
n.
n.
m/h
n.
kg
n.
V/Ph/Hz
A
A
kW/kW
kW
kW
l
kW
kW
kW
m/h
kW/kW
dB(A)
dB(A)
kW
kW
kW
m/h
kW/kW
dB(A)
dB(A)
kW
kW
kW
m/h
kW/kW
dB(A)
dB(A)
Referred to glycol solution temperature 15/10C; 20% Ethylene glycol solution; air temperature to the condenser 35C. Fouling factor of the exchangers 0,043 mK/kW.
Referred to glycol solution inlet temperature 15C; 20% Ethylene glycol solution; ambient temperature 3C. Fouling factor of the exchangers 0,043 mK/kW.
Sound power level [Lw] according to ISO EN 9614 2.
Average sound pressure level [LPm] 1m far according to ISO EN 3744.
Hydraulic connection with grooved end complete with flexible joint and adapter pipe for solder connection.
Referred to glycol solution temperature 15/10C; 20% Ethylene glycol solution; air temperature to the condenser 35C. Water temperature heat recovery 40/45C 0% glycol
solution; Fouling factor of the exchangers 0,043 mK/kW.
MAXIMO
IT Cooling
TECHNICAL DATA MAXIMO
dB(A)
dB(A)
kg
197 P2
S
C5
215,0
90,3
151,0
39,7
147
scroll
2
2
5
54000
1
R410A
83,1
1
400/3/50
187,2
490,3
2,38
2,96
93,7
74,4
2220
197 P2
D
C5
212,0
87,2
150,0
39,1
138
scroll
2
2
5
54000
1
R410A
102,2
2
400/3/50
187,2
490,3
2,43
3,43
93,7
74,4
2230
230 P3
S
C5
242,0
109,5
159,0
44,7
168
scroll
3
3
5
56300
1
R410A
83,7
1
400/3/50
221,0
455,1
2,21
3,52
94,7
75,4
2370
240 P4
D
C5H
270,0
107,6
171,0
49,8
159
scroll
4
4
5
69000
1
R410A
127,0
2
400/3/50
218,7
431,8
2,51
3,66
93,4
74,1
2510
270 P4
D
C5H
299,0
126,2
197,0
54,5
171
scroll
4
4
5
69000
1
R410A
126,6
2
400/3/50
254,2
486,7
2,37
3,64
93,4
74,1
2510
mm
88,9
88,9
88,9
88,9
88,9
kW
73,9
72,9
83,2
92,8
103,0
5,5
7,5
720
215,0
90,3
151,0
54000
2,38
93,6
74,3
207,0
92,0
150,0
45900
2,25
89,8
70,5
196,0
96,1
148,0
37800
2,04
85,4
66,1
5,5
7,5
720
212,0
87,2
150,0
54000
2,43
93,6
74,3
204,0
88,3
149,0
45900
2,31
89,8
70,5
193,0
92,8
147,0
37800
2,08
85,4
66,1
5,5
7,5
720
242,0
109,5
159,0
56300
2,21
94,5
75,2
232,0
112,1
157,0
47855
2,07
90,7
71,4
217,0
116,0
155,0
39410
1,87
86,3
67,1
5,5
7,5
720
270,0
107,6
171,0
69000
2,51
93,0
73,8
261,0
108,3
169,0
58650
2,41
89,3
70,0
248,0
111,7
168,0
48300
2,22
85,2
65,9
5,5
7,5
720
299,0
126,2
197,0
69000
2,37
93,0
73,8
287,0
128,7
195,0
58650
2,23
89,3
70,0
270,0
134,3
193,0
48300
2,01
85,2
65,9
ELN KIT
OPTIONAL
STANDARD
MAXIMO
1.
2.
3.
4.
5.
6.
SIZE
Cooling capacity (1)
Unit power input
Free-Cooling capacity (2)
Total water flow rate
Total pressure drop
Compressors
Quantity
Capacity steps
Axial fans EC
Total air flow
Air circuits
Refrigerant
Total refrigerant charge (optional excluded)
Gas circuits
Power supply
Max unit operating current (FLA)
Unit starting current (LRA)
EER (1)
ESEER
Sound power level [Lw] (3)
Average sound pressure level [LPm] (4)
Net weight
Hydraulic connections
Evaporator IN/OUT - ISO 7/1 R
Evaporator IN/OUT - OD (5)
Partial heat recovery (6)
Heating capacity
Pumping group
1 pump - 2 poles electric motor
2 pump - 2 poles electric motor
Water tank - volume
Cooling capacity (1)
Unit power input
Free-Cooling capacity (2)
Total air flow
EER (1)
Sound power level [Lw] (3)
Average sound pressure level [LPm] (4)
Cooling capacity (1)
Unit power input
Free-Cooling capacity (2)
Total air flow
EER (1)
Sound power level [Lw] (3)
Average sound pressure level [LPm] (4)
Cooling capacity (1)
Unit power input
Free-Cooling capacity (2)
Total air flow
EER (1)
Sound power level [Lw] (3)
Average sound pressure level [LPm] (4)
kW
kW
kW
m/h
kPa
n.
n.
n.
m/h
n.
kg
n.
V/Ph/Hz
A
A
kW/kW
kW
kW
l
kW
kW
kW
m/h
kW/kW
dB(A)
dB(A)
kW
kW
kW
m/h
kW/kW
dB(A)
dB(A)
kW
kW
kW
m/h
kW/kW
dB(A)
dB(A)
Referred to glycol solution temperature 15/10C; 20% Ethylene glycol solution; ambient temperature 35C. Fouling factor of the exchangers 0,043 mK/kW.
Referred to glycol solution inlet temperature 15C; 20% Ethylene glycol solution; ambient temperature 3C. Fouling factor of the exchangers 0,043 mK/kW.
Sound power level [Lw] according to ISO EN 9614 2.
Average sound pressure level [LPm] 1m far according to ISO EN 3744.
Hydraulic connection with grooved end complete with flexible joint and adapter pipe for solder connection.
Referred to chiller water temperature 12/7C; 35C ambient temperature and hot water temperature 40/45C.
123
MAXIMO
IT Cooling
DIMENSIONS (mm)
SIZE C
C1
C2
C3
C4
C5
C5H
a
1250
1800
2600
3700
4950
4950
b
1010
1180
1340
1490
1500
1500
c
2010
2060
2060
2050
2090
2090
124
MAXIMO PF
MAXIMO PF: Packaged air cooled liquid chillers with free-cooling system
for indoor installation, equipped with scroll compressors and plug fan
Cooling Capacity: 21 277 kW
Free-Cooling Capacity: 18 176 kW
FREECOOLING
MAXIMO PF
rcgroupairconditioning
FREE
COOLING
R410A
PLATE
EC
MAIN FEATURES
Air cooled liquid chiller with free-cooling system.
29 models available, for a wide selection opportunity.
Average step of 12,5kW.
EER up to 2,79.
ESEER up to 3,40.
Scroll compressors.
R410A Refrigerant charge.
Single or double refrigerant circuit.
Plate type heat exchangers.
EC Plug fan.
Single air circuit.
Electronic expansion valve.
Suitable for outdoor installation.
MAIN BENEFITS
Units equipped with two scroll compressors for refrigerant circuit to reach
a high efficiency.
Units with single and double refrigerant circuits.
Indirect free cooling system.
High ESEER.
EC Plug fan for a high efficiency.
Availability of kit for the reduction of the noise.
Availability of pumping groups.
Availability of partial heat recovery system.
Easily of maintenance.
Components dedicated to the safety of the unity.
Eurovent Certification.
INDOOR INSTALLATION
The machines are designed for indoor installation and ducting for
air suction and discharge. For outdoor installation the use of the
dedicated optional kit is mandatory. The machine must be installed
under a cover or anyway protected against atmospherics agent.
WORKING LIMITS IN COOLING MODE
Chilled water outlet temperature: 415C
Ambient temperature: -1045C
f i f t y c o o l y e a r s
125
MAXIMO PF
MAIN COMPONENTS
FRAMEWORK
Base, self supporting frame and panelling in steel plate with protective
surfaces treatment in compliance with UNI ISO 9227/ASTMB117 and ISO
7253, and painted with epoxy powders.
Colour: RAL 9002
COMPRESSORS
Orbiting spiral (SCROLL) hermetic compressors with spiral profile optimized
for R410A refrigerant.
ON / OFF capacity control (0 / 100% each compressor).
2-pole 3-phase electric motor with direct on line starting.
Phase sequence electronic relay.
Crankcase heater.
Electric motor thermal protection via internal winding temperature sensors.
Rubber supports.
EVAPORATOR
Copper brazed plate type with cover plates, plates and connections in AISI
316 stainless steel:
- With single refrigerant circuit for S version machines.
- With double refrigerant circuit for D version machines.
Anticondensate insulation made of polyurethane.
Temperature sensors on water inlet and outlet.
Differential water pressure switch for water flow control.
Antifreeze heater.
CONDENSING COIL
Heat exchanger coil with internally corrugated copper tubes and high
efficiency aluminium fins, specifically developed to provide high heat
transfer and lower pressure drops. The combination of two factors, special
tubes and fins, allow to optimally combine the following aspects:
- Maximum capacity relative to the size of the exchanger.
- Minimum charge of refrigerant.
- Reduction of the air flow required for the heat exchange.
Sub-cooling circuit to allow a significant increase in cooling capacity.
Frame in galvanized steel.
FREE-COOLING COIL
Heat exchanger coil with copper tubes and high efficiency aluminium fins,
specifically developed to provide high heat transfer and lower pressure
drops. The combination of two factors, special tubes and fins, allow to
optimally combine the following aspects:
- Maximum capacity relative to the size of the exchanger.
- Reduction of the air flow required for the heat exchange.
Frame in galvanized steel.
Motorized valves for free-cooling water circuit control.
Temperature sensor on ambient air.
IT Cooling
REFRIGERANT CIRCUIT
Components for each refrigerant circuit:
Thermostatic expansion valve up to model 85 P2 C3 D included.
Electronic expansion valve from model 107 P2 C3 D included.
The valve allows high performance and system efficiency thanks to a
timely and accurate response to changes in temperature and pressure. The
electronic expansion valve exclude the installation of the electromagnetic
valve on liquid line.
Sight glass.
Electromagnetic valve on liquid line. The electromagnetic valve is not
installed when the electronic expansion valve is present.
Filter dryer on liquid line.
Service valves on liquid line and gas discharge.
Safety valve on low pressure side.
Pressure transducers with indication, control and protection functions, on
low and high refrigerant pressure.
High pressure safety switch with manual reset.
Refrigerant circuit with copper tubing with anticondensate insulation of the
suction line.
Plastic capillary hoses for pressure sensors connection.
R410A refrigerant charge.
ELECTRICAL PANEL
In accordance with EN60204-1 norms complete with:
Main switch with door lock safety.
Magnetothermic switch or fuses for each compressor.
Magnetothermic switches for fans or water pumps (if scheduled).
Contactors for each load.
Transformer for auxiliary circuit and microprocessor supply.
Panel with machine controls.
Power supply: 400/3/50.
CONTROL SYSTEM
MP.COM microprocessor system with graphic display for control and
monitor of operating and alarms status. The system includes:
- Voltage free contact for remote general alarm.
- Main components hour-meter.
- Nonvolatile Flash memory for data storage.
- Menu with protection password.
- LAN connection.
FANS SECTION
Centrifugal fans with backward curved blades, single suction and without
scroll housings (Plug-fan).
Brushless type synchronous EC motor with integrated electronic
commutated system and continuous variation of the rotation speed.
The motor rotation control is obtained with the EC system (Electronic
Commutation) that manage the motor according to the 010V proportional
signal coming from the microprocessor control.
Maintenance-free bearings
IP54 enclosure class.
126
MAXIMO PF
IT Cooling
OPTIONAL ACCESSORIES
MAXIMO PF
SIZE
739 - Pumping group (1 pump)
740 - Pumping group (2 pumps)
768 - Chilled water storage tank
150 - LNO kit (noise reduction)
170 - Spring antivibration holders (kit)
172 - Rubber support (kit)
118 - Kit brine A (for glycol solution production up to -6C)
119 - Kit brine B (for glycol solution production up to -12C)
79 - Electrical panel heating system
460 - Kit for outdoor installation
450 - Partial heat recovery
251 - Coils protection nets
351 - Coils with pre-painted fins
Condensing coil in special execution
160 - Discharge air plenum with sound attenuators
731 - Safety water flow switch
143 - Glycol free
605 - Compr. power factor capacitor - 0,9
1002 - Soft Starter
83 - Compressor operation indicator
Expansion valve energy reserve module
Ambient temperature sensor
81 - Phases sequence control
1003 - Analogic flowmeter
1005 - Power supply analyzer
1009 - Multimeter kit
919 - Clock card
923 - RC-Com MBUS/JBUS Serial board
926 - LON Serial board
931 - BACnet Ethernet - SNMP - TCP/IP Serial board
932 - BACnet MS/TP Serial board
942 - Serial card for GSM Modem
943 - Data Logger
962 - Kit modem GSM
957 - Plantwatch without modem
930 - Remote graphic terminal kit
889 - Master plant SEQUENCER
RC CLOUD PLATFORM
C1
C2
C3
C4
C5
127
MAXIMO PF
IT Cooling
OPTIONAL
STANDARD
MAXIMO PF
1.
2.
3.
4.
5.
6.
128
SIZE
Cooling capacity (1)
Unit power input
Free-Cooling capacity (2)
Total water flow rate
Total pressure drop
Compressors
Quantity
Capacity steps
Centrifugal fans EC
Total air flow
External static pressure
Air circuits
Refrigerant
Total refrigerant charge (optional excluded)
Gas circuits
Power supply
Max unit operating current (FLA)
Unit starting current (LRA)
EER (1)
ESEER
Sound power level [Lw] (3)
Average sound pressure level [Lpm] (4)
Net weight
Hydraulic connections
Evaporator IN/OUT - ISO 7/1 R
Evaporator IN/OUT - OD (5)
Partial heat recovery (6)
Heating capacity
Pumping group
1 pump - 2 poles electric motor
2 pump - 2 poles electric motor
Water tank - volume
Cooling capacity (1)
Unit power input
Free-Cooling capacity (2)
Total air flow
External static pressure
EER (1)
Sound power level [Lw] (3)
Average sound pressure level [Lpm] (4)
Cooling capacity (1)
Unit power input
Free-Cooling capacity (2)
Total air flow
External static pressure
EER (1)
Sound power level [Lw] (3)
Average sound pressure level [Lpm] (4)
Cooling capacity (1)
Unit power input
Free-Cooling capacity (2)
Total air flow
External static pressure
EER (1)
Sound power level [Lw] (3)
Average sound pressure level [Lpm] (4)
dB(A)
dB(A)
kg
22 P1
S
C1
21,4
7,7
18,1
4,0
98
scroll
1
1
1
6500
50
1
R410A
11,3
1
400/3/50
21,3
99,3
2,79
3,17
87,3
70,7
450
24 P1
S
C1
23,9
9,0
19,5
4,4
123
scroll
1
1
1
7000
50
1
R410A
11,3
1
400/3/50
26,6
115,3
2,66
3,03
88,9
72,3
460
28 P1
S
C1
27,9
10,9
22,9
5,2
151
scroll
1
1
1
8500
50
1
R410A
11,3
1
400/3/50
27,6
122,3
2,55
2,95
93,0
76,4
460
32 P1
S
C1
31,6
11,8
26,0
5,8
166
scroll
1
1
1
10000
50
1
R410A
11,5
1
400/3/50
31,4
122,9
2,68
3,14
92,1
75,5
470
36 P1
S
C1
35,2
14,2
28,2
6,5
150
scroll
1
1
1
11000
50
1
R410A
11,6
1
400/3/50
37,7
144,9
2,48
2,86
94,5
77,9
470
42 P1
S
C1
39,6
17,2
29,9
7,3
174
scroll
1
1
1
11500
50
1
R410A
11,6
1
400/3/50
40,8
178,9
2,30
2,60
95,5
78,9
480
53 P1
S
C2
51,4
20,8
42,3
9,5
160
scroll
1
1
2
16000
50
1
R410A
18
1
400/3/50
51,0
233,6
2,47
2,84
95,0
77,8
750
67 P1
S
C2
64,4
26,0
52,1
11,9
212
scroll
1
1
2
21000
50
1
R410A
18,5
1
400/3/50
59,7
280,4
2,48
2,97
97,2
80,0
790
mm
1 1/2"
--
1 1/2"
--
1 1/2"
--
1 1/2"
--
1 1/2"
--
1 1/2"
--
2"
--
2"
--
7,4
8,2
9,6
10,9
12,1
13,6
17,7
22,2
1,1
130
21,4
7,7
18,1
6500
50
2,79
87,1
70,5
20,8
7,7
17,9
5525
36
2,69
83,6
67,0
19,9
8,0
17,6
4550
25
2,49
80,4
63,8
1,1
130
23,9
9,0
19,5
7000
50
2,66
88,7
72,1
23,2
9,0
19,4
5950
36
2,57
85,2
68,6
22,1
9,4
19,1
4900
25
2,36
82,0
65,4
1,1
130
27,9
10,9
22,9
8500
50
2,55
92,8
76,2
27,0
10,8
22,7
7225
36
2,49
89,3
72,7
25,8
11,1
22,3
5950
25
2,33
86,1
69,5
1,1
130
31,6
11,8
26,0
10000
50
2,68
92,1
75,5
30,6
11,9
25,7
8500
36
2,58
88,2
71,6
29,2
12,3
25,3
7000
25
2,37
83,6
67,1
1,1
130
35,2
14,2
28,2
11000
50
2,48
94,1
77,5
34,0
13,9
28,0
9350
36
2,45
90,6
74,0
32,5
14,0
27,6
7700
25
2,32
87,4
70,8
1,1
130
39,6
17,2
29,9
11500
50
2,30
96,0
79,4
38,2
16,9
29,6
9775
36
2,26
92,5
75,9
36,3
17,2
29,2
8050
25
2,11
89,3
72,7
1,5
210
51,4
20,8
42,3
16000
50
2,47
94,6
77,4
50,0
20,7
41,9
13600
36
2,42
91,2
74,0
47,9
21,2
41,5
11200
25
2,26
88,2
71,0
1,5
210
64,4
26,0
52,1
21000
50
2,48
96,4
79,2
62,6
25,9
51,7
17850
36
2,42
93,0
75,8
59,9
26,5
51,1
14700
25
2,26
90,1
72,9
kW
kW
kW
m/h
kPa
n.
n.
n.
m/h
Pa
n.
kg
n.
V/Ph/Hz
A
A
kW/kW
kW
kW
kW
l
kW
kW
kW
m/h
Pa
kW/kW
dB(A)
dB(A)
kW
kW
kW
m/h
Pa
kW/kW
dB(A)
dB(A)
kW
kW
kW
m/h
Pa
kW/kW
dB(A)
dB(A)
Referred to glycol solution temperature 15/10C; 20% Ethylene glycol solution; air temperature to the condenser 35C. Fouling factor of the exchangers 0,043 mK/kW.
Referred to glycol solution inlet temperature 15C; 20% Ethylene glycol solution; ambient temperature 3C. Fouling factor of the exchangers 0,043 mK/kW.
Sound power level [Lw] according to ISO EN 9614 2.
Average sound pressure level [LPm] 1m far according to ISO EN 3744.
Hydraulic connection with grooved end complete with flexible joint and adapter pipe for solder connection.
Referred to glycol solution temperature 15/10C; 20% Ethylene glycol solution; air temperature to the condenser 35C. Water temperature heat recovery 40/45C 0% glycol
solution; Fouling factor of the exchangers 0,043 mK/kW.
MAXIMO PF
IT Cooling
TECHNICAL DATA MAXIMO PF
OPTIONAL
STANDARD
MAXIMO PF
1.
2.
3.
4.
5.
6.
SIZE
Cooling capacity (1)
Unit power input
Free-Cooling capacity (2)
Total water flow rate
Total pressure drop
Compressors
Quantity
Capacity steps
Centrifugal fans EC
Total air flow
External static pressure
Air circuits
Refrigerant
Total refrigerant charge (optional excluded)
Gas circuits
Power supply
Max unit operating current (FLA)
Unit starting current (LRA)
EER (1)
ESEER
Sound power level [Lw] (3)
Average sound pressure level [Lpm] (4)
Net weight
Hydraulic connections
Evaporator IN/OUT - ISO 7/1 R
Evaporator IN/OUT - OD (5)
Partial heat recovery (6)
Heating capacity
Pumping group
1 pump - 2 poles electric motor
2 pump - 2 poles electric motor
Water tank - volume
Cooling capacity (1)
Unit power input
Free-Cooling capacity (2)
Total air flow
External static pressure
EER (1)
Sound power level [Lw] (3)
Average sound pressure level [Lpm] (4)
Cooling capacity (1)
Unit power input
Free-Cooling capacity (2)
Total air flow
External static pressure
EER (1)
Sound power level [Lw] (3)
Average sound pressure level [Lpm] (4)
Cooling capacity (1)
Unit power input
Free-Cooling capacity (2)
Total air flow
External static pressure
EER (1)
Sound power level [Lw] (3)
Average sound pressure level [Lpm] (4)
dB(A)
dB(A)
kg
55 P2
S
C2
54,1
22,1
45,7
10,0
175
scroll
2
2
2
18000
50
1
R410A
18,3
1
400/3/50
56,5
149,8
2,45
3,28
93,6
76,4
740
55 P2
D
C2
54,2
21,9
45,7
10,0
153
scroll
2
2
2
18000
50
1
R410A
16
2
400/3/50
56,5
149,8
2,48
3,01
93,6
76,4
740
62 P2
S
C2
60,7
24,3
50,6
11,2
203
scroll
2
2
2
20500
50
1
R410A
18,3
1
400/3/50
61,3
151,4
2,50
3,33
87,5
70,3
810
62 P2
D
C2
60,9
24,1
50,6
11,2
179
scroll
2
2
2
20500
50
1
R410A
16
2
400/3/50
61,3
151,4
2,53
2,84
87,5
70,3
810
71 P2
S
C2
68,4
28,9
55,6
12,6
239
scroll
2
2
2
23000
50
1
R410A
18,7
1
400/3/50
73,9
179,4
2,37
2,83
89,8
72,6
820
71 P2
D
C2
68,3
28,6
55,5
12,6
218
scroll
2
2
2
23000
50
1
R410A
16,2
2
400/3/50
73,9
179,4
2,39
3,09
89,8
72,6
820
85 P2
S
C3
80,5
31,3
67,1
14,9
167
scroll
2
2
3
25500
50
1
R410A
28,7
1
400/3/50
86,8
222,7
2,57
3,01
94,4
76,5
1050
85 P2
D
C3
80,1
31,2
67,0
14,8
147
scroll
2
2
3
25500
50
1
R410A
25,5
2
400/3/50
86,8
222,7
2,57
3,25
94,4
76,5
1050
mm
2"
--
2"
--
2"
--
2"
--
2"
--
2"
--
-76,1
-76,1
18,6
18,6
20,9
21,0
23,5
23,5
27,7
27,6
1,5
210
54,1
22,1
45,7
18000
50
2,45
93,1
75,9
52,5
21,9
45,3
15300
36
2,40
89,6
72,4
50,2
22,4
44,8
12600
25
2,24
86,4
69,2
1,5
210
54,2
21,9
45,7
18000
50
2,48
93,1
75,9
52,6
21,6
45,4
15300
36
2,43
89,6
72,4
50,3
22,2
44,8
12600
25
2,27
86,4
69,2
1,5
210
60,7
24,3
50,6
20500
50
2,50
86,5
69,3
58,9
23,9
50,2
17425
36
2,46
83,1
65,9
56,3
24,4
49,6
14350
25
2,31
80,2
63,0
1,5
210
60,9
24,1
50,6
20500
50
2,53
86,5
69,3
59,0
23,9
50,2
17425
36
2,47
83,1
65,9
56,4
24,4
49,6
14350
25
2,31
80,2
63,0
1,5
210
68,4
28,9
55,6
23000
50
2,37
89,0
71,8
66,3
28,0
55,1
19550
36
2,37
85,5
68,3
63,3
28,3
54,4
16100
25
2,24
82,5
65,3
1,5
210
68,3
28,6
55,5
23000
50
2,39
89,0
71,8
66,2
27,7
55,1
19550
36
2,39
85,5
68,3
63,2
28,0
54,4
16100
25
2,26
82,5
65,3
3,0
3,0
360
80,5
31,3
67,1
25500
50
2,57
93,7
75,8
78,2
31,0
66,5
21675
36
2,52
90,3
72,4
74,9
31,6
65,8
17850
25
2,37
87,2
69,3
3,0
3,0
360
80,1
31,2
67,0
25500
50
2,57
93,7
75,8
77,8
30,9
66,4
21675
36
2,52
90,3
72,4
74,5
31,6
65,7
17850
25
2,36
87,2
69,3
kW
kW
kW
m/h
kPa
n.
n.
n.
m/h
Pa
n.
kg
n.
V/Ph/Hz
A
A
kW/kW
kW
kW
kW
l
kW
kW
kW
m/h
Pa
kW/kW
dB(A)
dB(A)
kW
kW
kW
m/h
Pa
kW/kW
dB(A)
dB(A)
kW
kW
kW
m/h
Pa
kW/kW
dB(A)
dB(A)
Referred to glycol solution temperature 15/10C; 20% Ethylene glycol solution; air temperature to the condenser 35C. Fouling factor of the exchangers 0,043 mK/kW.
Referred to glycol solution inlet temperature 15C; 20% Ethylene glycol solution; ambient temperature 3C. Fouling factor of the exchangers 0,043 mK/kW.
Sound power level [Lw] according to ISO EN 9614 2.
Average sound pressure level [LPm] 1m far according to ISO EN 3744.
Hydraulic connection with grooved end complete with flexible joint and adapter pipe for solder connection.
Referred to glycol solution temperature 15/10C; 20% Ethylene glycol solution; air temperature to the condenser 35C. Water temperature heat recovery 40/45C 0% glycol
solution; Fouling factor of the exchangers 0,043 mK/kW.
129
MAXIMO PF
IT Cooling
OPTIONAL
STANDARD
MAXIMO PF
1.
2.
3.
4.
5.
6.
130
SIZE
Cooling capacity (1)
Unit power input
Free-Cooling capacity (2)
Total water flow rate
Total pressure drop
Compressors
Quantity
Capacity steps
Centrifugal fans EC
Total air flow
External static pressure
Air circuits
Refrigerant
Total refrigerant charge (optional excluded)
Gas circuits
Power supply
Max unit operating current (FLA)
Unit starting current (LRA)
EER (1)
ESEER
Sound power level [Lw] (3)
Average sound pressure level [Lpm] (4)
Net weight
Hydraulic connections
Evaporator IN/OUT - ISO 7/1 R
Evaporator IN/OUT - OD (5)
Partial heat recovery (6)
Heating capacity
Pumping group
1 pump - 2 poles electric motor
2 pump - 2 poles electric motor
Water tank - volume
Cooling capacity (1)
Unit power input
Free-Cooling capacity (2)
Total air flow
External static pressure
EER (1)
Sound power level [Lw] (3)
Average sound pressure level [Lpm] (4)
Cooling capacity (1)
Unit power input
Free-Cooling capacity (2)
Total air flow
External static pressure
EER (1)
Sound power level [Lw] (3)
Average sound pressure level [Lpm] (4)
Cooling capacity (1)
Unit power input
Free-Cooling capacity (2)
Total air flow
External static pressure
EER (1)
Sound power level [Lw] (3)
Average sound pressure level [Lpm] (4)
dB(A)
dB(A)
kg
107 P2
S
C3
103,0
42,7
81,1
19,1
233
scroll
2
2
3
32000
50
1
R410A
32
1
400/3/50
99,4
279,7
2,41
2,82
99,2
81,3
1240
107 P2
D
C3
102,0
42,5
80,9
18,9
216
scroll
2
2
3
32000
50
1
R410A
29,3
2
400/3/50
99,4
279,7
2,40
3,08
99,2
81,3
1240
135 P2
S
C4
128,0
50,0
99,5
23,5
110
scroll
2
2
4
40000
50
1
R410A
35,1
1
400/3/50
119,5
337,3
2,56
2,96
92,7
74,1
1690
135 P2
D
C4
126,0
50,0
99,0
23,2
99
scroll
2
2
4
40000
50
1
R410A
38,6
2
400/3/50
119,5
337,3
2,52
3,40
92,7
74,1
1690
170 P2
S
C4
166,0
67,8
124,0
30,6
145
scroll
2
2
4
52000
50
1
R410A
50,9
1
400/3/50
155,0
392,2
2,45
2,84
96,2
77,6
1800
170 P2
D
C4
164,0
67,8
123,0
30,2
139
scroll
2
2
4
52000
50
1
R410A
42,6
2
400/3/50
155,0
392,2
2,42
3,14
96,2
77,6
1780
195 P2
S
C4
182,0
70,0
127,0
33,6
169
scroll
2
2
4
52000
50
1
R410A
51,9
1
400/3/50
172,4
456,2
2,60
2,72
96,2
77,6
1850
195 P2
D
C4
185,0
80,4
127,0
34,2
165
scroll
2
2
4
52000
50
1
R410A
44
2
400/3/50
172,4
456,2
2,30
3,37
96,2
77,6
1820
mm
-76,1
-76,1
-88,9
-88,9
-88,9
-88,9
-88,9
-88,9
kW
35,6
35,2
43,9
43,2
57,2
56,3
62,6
63,7
3,0
3,0
360
103,0
42,7
81,1
32000
50
2,41
98,5
80,6
101,0
41,7
80,6
27200
36
2,42
95,1
77,2
96,5
42,3
79,7
22400
25
2,28
92,0
74,1
3,0
3,0
360
102,0
42,5
80,9
32000
50
2,40
98,5
80,6
99,4
41,6
80,3
27200
36
2,39
95,1
77,2
95,5
42,1
79,5
22400
25
2,27
92,0
74,1
3,0
4,0
520
128,0
50,0
99,5
40000
50
2,56
90,2
71,6
124,0
50,0
98,6
34000
36
2,48
87,8
69,2
118,0
51,3
97,3
28000
25
2,30
86,9
68,3
3,0
4,0
520
126,0
50,0
99,0
40000
50
2,52
90,2
71,6
122,0
49,8
98,1
34000
36
2,45
87,8
69,2
117,0
51,1
96,8
28000
25
2,29
86,9
68,3
3,0
4,0
520
166,0
67,8
124,0
52000
50
2,45
95,0
76,4
161,0
66,3
123,0
44200
36
2,43
91,9
73,3
155,0
66,8
121,0
36400
25
2,32
89,7
71,1
3,0
4,0
520
164,0
67,8
123,0
52000
50
2,42
95,0
76,4
159,0
66,0
122,0
44200
36
2,41
91,9
73,3
153,0
66,5
121,0
36400
25
2,30
89,7
71,1
3,0
4,0
520
182,0
70,0
127,0
52000
50
2,60
95,7
77,1
176,0
68,2
126,0
44200
36
2,58
92,6
74,0
167,0
69,0
124,0
36400
25
2,42
90,3
71,7
3,0
4,0
520
185,0
80,4
127,0
52000
50
2,30
95,7
77,1
179,0
79,2
126,0
44200
36
2,26
92,6
74,0
170,0
81,0
125,0
36400
25
2,10
90,3
71,7
kW
kW
kW
m/h
kPa
n.
n.
n.
m/h
Pa
n.
kg
n.
V/Ph/Hz
A
A
kW/kW
kW
kW
l
kW
kW
kW
m/h
Pa
kW/kW
dB(A)
dB(A)
kW
kW
kW
m/h
Pa
kW/kW
dB(A)
dB(A)
kW
kW
kW
m/h
Pa
kW/kW
dB(A)
dB(A)
Referred to glycol solution temperature 15/10C; 20% Ethylene glycol solution; air temperature to the condenser 35C. Fouling factor of the exchangers 0,043 mK/kW.
Referred to glycol solution inlet temperature 15C; 20% Ethylene glycol solution; ambient temperature 3C. Fouling factor of the exchangers 0,043 mK/kW.
Sound power level [Lw] according to ISO EN 9614 2.
Average sound pressure level [LPm] 1m far according to ISO EN 3744.
Hydraulic connection with grooved end complete with flexible joint and adapter pipe for solder connection.
Referred to glycol solution temperature 15/10C; 20% Ethylene glycol solution; air temperature to the condenser 35C. Water temperature heat recovery 40/45C 0% glycol
solution; Fouling factor of the exchangers 0,043 mK/kW.
MAXIMO PF
IT Cooling
TECHNICAL DATA MAXIMO PF
dB(A)
dB(A)
kg
220 P2
S
C5
210,0
84,7
163,0
38,8
148
scroll
2
2
5
62500
50
1
R410A
83,1
1
400/3/50
194,3
477,0
2,48
2,96
96,8
77,6
2320
220 P2
D
C5
214,0
84,9
163,0
39,4
143
scroll
2
2
5
62500
50
1
R410A
102,2
2
400/3/50
194,3
477,0
2,52
3,21
96,8
77,6
2330
250 P3
S
C5
240,0
101,3
163,2
44,4
55
scroll
3
3
5
64000
50
1
R410A
83,7
1
400/3/50
228,1
461,8
2,37
3,35
97,2
77,9
2490
265 P4
D
C5
253,0
107,7
173,0
46,7
183
scroll
4
4
5
64000
50
1
R410A
113,3
2
400/3/50
225,8
438,5
2,35
3,32
97,3
78,0
2670
290 P4
D
C5
277,0
127,1
176,0
51,3
211
scroll
4
4
5
64000
50
1
R410A
113,2
2
400/3/50
331,6
607,8
2,18
3,29
97,3
78,0
2720
mm
-88,9
-88,9
-88,9
-88,9
-88,9
kW
72,3
73,5
82,7
87,0
95,4
5,5
7,5
720
210,0
84,7
163,0
62500
50
2,48
95,3
76,1
204,0
83,3
161,0
53125
36
2,45
92,4
73,1
195,0
85,2
159,0
43750
25
2,29
90,5
71,2
5,5
7,5
720
214,0
84,9
163,0
62500
50
2,52
95,3
76,1
207,0
83,8
162,0
53125
36
2,47
92,4
73,1
198,0
85,3
160,0
43750
25
2,32
90,5
71,2
5,5
7,5
720
240,0
101,3
163,2
64000
50
2,37
95,8
76,5
232,0
100,9
162,1
54400
36
2,30
92,8
73,5
220,0
103,8
160,1
44800
25
2,12
90,8
71,5
5,5
7,5
720
253,0
107,7
173,0
64000
50
2,35
96,4
77,1
244,0
107,0
171,0
54400
36
2,28
93,3
74,0
231,0
109,5
169,0
44800
25
2,11
91,2
71,9
5,5
7,5
720
277,0
127,1
176,0
64000
50
2,18
96,4
77,1
266,0
127,3
175,0
54400
36
2,09
93,3
74,0
248,0
132,6
172,0
44800
25
1,87
91,2
71,9
OPTIONAL
STANDARD
MAXIMO PF
1.
2.
3.
4.
5.
6.
SIZE
Cooling capacity (1)
Unit power input
Free-Cooling capacity (2)
Total water flow rate
Total pressure drop
Compressors
Quantity
Capacity steps
Centrifugal fans EC
Total air flow
External static pressure
Air circuits
Refrigerant
Total refrigerant charge (optional excluded)
Gas circuits
Power supply
Max unit operating current (FLA)
Unit starting current (LRA)
EER (1)
ESEER
Sound power level [Lw] (3)
Average sound pressure level [Lpm] (4)
Net weight
Hydraulic connections
Evaporator IN/OUT - ISO 7/1 R
Evaporator IN/OUT - OD (5)
Partial heat recovery (6)
Heating capacity
Pumping group
1 pump - 2 poles electric motor
2 pump - 2 poles electric motor
Water tank - volume
Cooling capacity (1)
Unit power input
Free-Cooling capacity (2)
Total air flow
External static pressure
EER (1)
Sound power level [Lw] (3)
Average sound pressure level [Lpm] (4)
Cooling capacity (1)
Unit power input
Free-Cooling capacity (2)
Total air flow
External static pressure
EER (1)
Sound power level [Lw] (3)
Average sound pressure level [Lpm] (4)
Cooling capacity (1)
Unit power input
Free-Cooling capacity (2)
Total air flow
External static pressure
EER (1)
Sound power level [Lw] (3)
Average sound pressure level [Lpm] (4)
kW
kW
kW
m/h
kPa
n.
n.
n.
m/h
Pa
n.
kg
n.
V/Ph/Hz
A
A
kW/kW
kW
kW
l
kW
kW
kW
m/h
Pa
kW/kW
dB(A)
dB(A)
kW
kW
kW
m/h
Pa
kW/kW
dB(A)
dB(A)
kW
kW
kW
m/h
Pa
kW/kW
dB(A)
dB(A)
Referred to glycol solution temperature 15/10C; 20% Ethylene glycol solution; air temperature to the condenser 35C. Fouling factor of the exchangers 0,043 mK/kW.
Referred to glycol solution inlet temperature 15C; 20% Ethylene glycol solution; ambient temperature 3C. Fouling factor of the exchangers 0,043 mK/kW.
Sound power level [Lw] according to ISO EN 9614 2.
Average sound pressure level [LPm] 1m far according to ISO EN 3744.
Hydraulic connection with grooved end complete with flexible joint and adapter pipe for solder connection.
Referred to glycol solution temperature 15/10C; 20% Ethylene glycol solution; air temperature to the condenser 35C. Water temperature heat recovery 40/45C 0% glycol
solution; Fouling factor of the exchangers 0,043 mK/kW.
131
MAXIMO PF
IT Cooling
DIMENSIONS (mm)
SIZE C
C1
C2
C3
C4
C5
a
1250
1800
2600
3700
4950
b
1010
1180
1340
1490
1500
c
1950
2000
2000
2000
2040
132
EAGLE FREE
EAGLE FREE: Packaged air cooled liquid chillers with free-cooling system
for outdoor installation, equipped with scroll compressors and axial fans
Cooling Capacity: 69 331 kW
Free-Cooling Capacity: 47 194 kW
FREECOOLING
EAGLE FREE
rcgroupairconditioning
MAIN FEATURES
Air cooled liquid chiller with free-cooling system.
17 models available, for a wide selection opportunity.
Average step of 20kW.
EER up to 2,92.
ESEER up to 3,85.
Scroll compressors.
R410A Refrigerant charge.
Single or double refrigerant circuit.
Plate type heat exchangers.
AC Axial fans.
Single air circuit.
Electronic expansion valve.
Suitable for outdoor installation.
MAIN BENEFITS
Units equipped with two scroll compressors for refrigerant circuit to reach
a high efficiency.
Units with single and double refrigerant circuits.
Indirect free cooling system.
Availability of EC axial fans for a high efficiency.
Availability of kit for the reduction and the extreme reduction of the noise.
Availability of pumping groups.
Availability of partial heat recovery system.
Easily of maintenance.
Components dedicated to the safety of the unity.
FREE
COOLING
R410A
PLATE
AC
f i f t y c o o l y e a r s
133
EAGLE FREE
MAIN COMPONENTS
FRAMEWORK
Base, self supporting frame and panelling in steel plate with protective
surfaces treatment in compliance with UNI ISO 9227/ASTMB117 and ISO
7253, and painted with epoxy powders.
Compressors compartment.
Colour: RAL 9002
COMPRESSORS
Orbiting spiral (SCROLL) hermetic compressors with spiral profile optimized
for R410A refrigerant.
ON / OFF capacity control (0 / 100% each compressor).
2-pole 3-phase electric motor with direct on line starting.
Phase sequence electronic relay.
Crankcase heater.
Electric motor thermal protection via internal winding temperature sensors.
Rubber supports.
EVAPORATOR
Copper brazed plate type with cover plates, plates and connections in AISI
316 stainless steel:
- With single refrigerant circuit for S version machines.
- With double refrigerant circuit for D version machines.
Anticondensate insulation made of polyurethane.
Temperature sensors on water inlet and outlet.
Water flow safety switch.
Antifreeze heater.
CONDENSING AND FREE-COOLING COIL
Heat exchangers contained in single coil with high efficiency aluminium
fins, specifically developed to provide high heat transfer and lower pressure
drops. The combination of two factors, special tubes and fins, allow to
optimally combine the following aspects:
- Maximum capacity relative to the size of the exchanger.
- Minimum charge of refrigerant.
- Reduction of the air flow required for the heat exchange.
Frame in galvanized steel.
Motorized valves for free-cooling water circuit control.
Temperature sensor on ambient air.
IT Cooling
ELECTRICAL PANEL
In accordance with EN60204-1 norms, suitable for outdoor installation,
complete with:
Main switch with door lock safety.
Magnetothermic switch or fuses for each compressor.
Magnetothermic switches for fans or water pumps (if scheduled).
Contactors for each load.
Transformer for auxiliary circuit and microprocessor supply.
Panel with machine controls.
Power supply 400/3/50.
CONTROL SYSTEM
MP.COM microprocessor system with graphic display for control and
monitor of operating and alarms status. The system includes:
- Voltage free contact for remote general alarm.
- Main components hour-meter.
- Nonvolatile Flash memory for data storage.
- Menu with protection password.
- LAN connection.
- Additional module with the following inlets / outlets:
INLETS
o External alarm 1
o External alarm 2
o Line current indication.
o Line voltage indication / Compensation
o Ambient air temperature
OUTLETS
o External alarm 1
o External alarm 2
o General alarm 2
o General alarm 3
- Driver for the additional module.
FANS SECTION
Axial fans with sickle-shaped blades, fan guard and optimized for low noise
levels.
External rotor AC type electric motor.
Stepless variable speed with phase-cut electronic controller for condensing
pressure control.
Stepless variable speed with phase-cut electronic controller for free-cooling
control.
IP54 enclosure class.
REFRIGERANT CIRCUIT
Components for each refrigerant circuit:
Electronic expansion valve. The valve allows high performance and
system efficiency thanks to a timely and accurate response to changes in
temperature and pressure.
Sight glass.
Filter dryer on liquid line.
Service valves on liquid line and gas discharge.
Liquid receiver with safety valve.
Safety valve on low pressure side.
Pressure transducers with indication, control and protection functions, on
low and high refrigerant pressure.
High pressure safety switch with manual reset.
Refrigerant circuit with copper tubing with anticondensate insulation of the
suction line.
Plastic capillary hoses for pressure sensors connection.
R410A refrigerant charge.
134
EAGLE FREE
IT Cooling
OPTIONAL ACCESSORIES
EAGLE FREE
SIZE
739 - Pumping group (1 pump)
740 - Pumping group (2 pumps)
150 - LNO kit (noise reduction)
151 - ELN kit (extremely noise reduction)
170 - Spring antivibration holders (kit)
172 - Rubber support (kit)
118 - Kit brine A (for glycol solution production up to -6C)
119 - Kit brine B (for glycol solution production up to -12C)
79 - Electrical panel heating system
101 - EC fan
450 - Partial heat recovery
251 - Coils protection nets
Condensing coil in special execution
143 - Glycol free
731 - Safety water flow switch
605 - Compr. power factor capacitor - 0,9
1002 - Soft Starter
83 - Compressor operation indicator
Expansion valve energy reserve module
1003 - Analogic flowmeter
1005 - Power supply analyzer
1009 - Multimeter kit
919 - Clock card
923 - RC-Com MBUS/JBUS Serial board
926 - LON Serial board
931 - BACnet Ethernet - SNMP - TCP/IP Serial board
932 - BACnet MS/TP Serial board
942 - Serial card for GSM Modem
943 - Data Logger
962 - Kit modem GSM
957 - Plantwatch without modem
930 - Remote graphic terminal kit
889 - Master plant SEQUENCER
RC CLOUD PLATFORM
N6
N7
N8
N9
N10
135
EAGLE FREE
IT Cooling
ELN KIT
OPTIONAL
STANDARD
EAGLE FREE
1.
2.
3.
4.
5.
6.
136
SIZE
Cooling capacity (1)
Unit power input
Free-Cooling capacity (2)
Total water flow rate
Total pressure drop
Compressors
Quantity
Capacity steps
Axial fans
Total air flow
Air circuits
Refrigerant
Total refrigerant charge (optional excluded)
Gas circuits
Power supply
Max unit operating current (FLA)
Unit starting current (LRA)
EER (1)
ESEER
Sound power level [Lw] (3)
Average sound pressure level [Lpm] (4)
Net weight
Hydraulic connections
Evaporator IN/OUT - ISO 7/1 R
Evaporator IN/OUT - OD (5)
Partial heat recovery (6)
Heating capacity
Pumping group
Power input
Cooling capacity (1)
Unit power input
Free-Cooling capacity (2)
Total air flow
EER (1)
Sound power level [Lw] (3)
Average sound pressure level [Lpm] (4)
Cooling capacity (1)
Unit power input
Free-Cooling capacity (2)
Total air flow
EER (1)
Sound power level [Lw] (3)
Average sound pressure level [Lpm] (4)
Cooling capacity (1)
Unit power input
Free-Cooling capacity (2)
Total air flow
EER (1)
Sound power level [Lw] (3)
Average sound pressure level [Lpm] (4)
dB(A)
dB(A)
kg
T 60 P2
S
N6
69,7
24,0
47,5
12,8
187
scroll
2
2
6
30000
1
R410A
31,6
1
400/3/50
67,6
173,4
2,90
3,78
83,3
66,3
830
T 60 P2
D
N6
69,7
23,9
47,5
12,8
165
scroll
2
2
6
30000
1
R410A
34,6
2
400/3/50
67,6
173,4
2,92
3,49
83,3
66,3
810
T 70 P2
S
N6
79,8
28,8
51,4
14,7
225
scroll
2
2
6
33000
1
R410A
32,0
1
400/3/50
73,9
209,4
2,77
3,68
83,8
66,4
870
T 70 P2
D
N6
79,6
28,5
51,4
14,7
204
scroll
2
2
6
33000
1
R410A
35,6
2
400/3/50
73,9
209,4
2,79
3,31
83,8
66,4
850
T 90 P2
S
N7
104,0
36,9
64,2
19,1
148
scroll
2
2
2
44000
1
R410A
42,0
1
400/3/50
92,2
272,8
2,82
3,58
92,3
74,2
1170
T 90 P2
D
N7
103,0
36,5
63,9
18,9
132
scroll
2
2
2
44000
1
R410A
40,8
2
400/3/50
92,2
272,8
2,82
3,31
92,3
74,2
1150
T 120 P2
S
N7
126,0
47,7
71,3
23,3
194
scroll
2
2
2
48000
1
R410A
42,9
1
400/3/50
110,0
328,3
2,64
3,53
92,5
74,4
1280
T 120 P2
D
N7
124,0
47,3
71,0
22,9
180
scroll
2
2
2
48000
1
R410A
41,4
2
400/3/50
110,0
328,3
2,62
3,15
92,5
74,4
1270
mm
2"
--
2"
--
2"
--
2"
--
-76,1
-76,1
-76,1
-76,1
24,0
--
27,5
--
35,7
--
43,4
--
1,1
69,7
24,0
47,5
30000
2,90
83,2
66,2
68,3
24,3
47,2
25500
2,81
79,9
62,8
66,3
24,0
46,8
21000
2,76
74,1
57,0
1,1
69,7
23,9
47,5
30000
2,92
83,2
66,2
68,3
24,1
47,2
25500
2,83
79,9
62,8
66,3
23,9
46,8
21000
2,77
74,1
57,0
2,2
79,8
28,8
51,4
33000
2,77
83,7
66,2
78,1
29,3
51,1
28050
2,67
80,3
62,9
75,7
29,1
50,7
23100
2,60
74,7
57,2
2,2
79,6
28,5
51,4
33000
2,79
83,7
66,2
78,0
29,0
51,1
28050
2,69
80,3
62,9
75,6
28,9
50,7
23100
2,62
74,7
57,2
2,2
104,0
36,9
64,2
44000
2,82
92,2
74,1
102,0
37,2
63,7
37400
2,74
88,8
70,7
98,8
35,9
63,0
30800
2,75
82,9
64,8
2,2
103,0
36,5
63,9
44000
2,82
92,2
74,1
101,0
37,0
63,4
37400
2,73
88,8
70,7
97,7
35,7
62,7
30800
2,74
82,9
64,8
2,2
126,0
47,7
71,3
48000
2,64
92,3
74,2
123,0
48,4
70,8
40800
2,54
89,0
70,9
119,0
47,8
70,0
33600
2,49
83,3
65,2
2,2
124,0
47,3
71,0
48000
2,62
92,3
74,2
122,0
48,2
70,5
40800
2,53
89,0
70,9
117,0
47,4
69,7
33600
2,47
83,3
65,2
kW
kW
kW
m/h
kPa
n.
n.
n.
m/h
n.
kg
n.
V/Ph/Hz
A
A
kW/kW
kW
kW
kW
kW
kW
m/h
kW/kW
dB(A)
dB(A)
kW
kW
kW
m/h
kW/kW
dB(A)
dB(A)
kW
kW
kW
m/h
kW/kW
dB(A)
dB(A)
Referred to glycol solution temperature 15/10C; 20% Ethylene glycol solution; air temperature to the condenser 35C. Fouling factor of the exchangers 0,043 mK/kW.
Referred to glycol solution inlet temperature 15C; 20% Ethylene glycol solution; ambient temperature 3C. Fouling factor of the exchangers 0,043 mK/kW.
Sound power level [Lw] according to ISO EN 9614 2.
Average sound pressure level [LPm] 1m far according to ISO EN 3744.
Hydraulic connection with grooved end complete with flexible joint and adapter pipe for solder connection.
Referred to glycol solution temperature 15/10C; 20% Ethylene glycol solution; air temperature to the condenser 35C. Water temperature heat recovery 40/45C 0% glycol
solution; Fouling factor of the exchangers 0,043 mK/kW.
EAGLE FREE
IT Cooling
TECHNICAL DATA EAGLE FREE
dB(A)
dB(A)
kg
T 135 P2
S
N7
141,0
55,7
73,8
26,1
230
scroll
2
2
2
50000
1
R410A
43,6
1
400/3/50
127,8
366,3
2,53
3,47
93,5
75,4
1350
T 150 P2
S
N8
168,0
60,4
108,0
31,0
193
scroll
2
2
3
66000
1
R410A
62,6
1
400/3/50
149,6
387,1
2,78
3,60
95,4
76,0
1560
T 150 P2
D
N8
171,0
60,6
109,0
31,4
184
scroll
2
2
3
66000
1
R410A
64,6
2
400/3/50
149,6
387,1
2,82
3,33
95,4
76,0
1580
T 190 P4
D
N9
202,0
76,2
117,0
37,3
146
scroll
4
4
3
72000
1
R410A
68,4
2
400/3/50
180,3
356,7
2,65
3,85
94,8
75,4
1840
T 200 P2
S
N8
203,0
79,0
118,0
37,4
193
scroll
2
2
3
72000
1
R410A
66,4
1
400/3/50
184,5
477,7
2,57
3,49
94,8
75,4
1710
T 200 P2
D
N8
208,0
80,6
119,0
38,4
193
scroll
2
2
4
76000
1
R410A
67,0
2
400/3/50
188,6
481,6
2,58
3,09
94,8
75,4
1730
T 240 P4
D
N9
247,0
99,2
132,0
45,6
202
scroll
4
4
4
88000
1
R410A
68,0
2
400/3/50
220,1
433,1
2,49
3,64
100,0
80,2
1850
T 270 P4
D
N10
292,0
112,7
176,0
53,9
241
scroll
4
4
6
108000
1
R410A
94,2
2
400/3/50
263,8
495,8
2,59
3,64
101,8
81,5
2260
T 300 P4
D
N10
331,0
126,8
194,0
60,9
288
scroll
4
4
6
126000
1
R410A
95,8
2
400/3/50
299,3
529,6
2,61
3,74
101,8
81,5
2710
mm
-76,1
-88,9
-88,9
-88,9
-88,9
-88,9
-88,9
-88,9
-88,9
kW
48,6
57,8
58,7
69,6
69,8
71,7
85,0
101,0
114,0
2,2
141,0
55,7
73,8
50000
2,53
93,3
75,2
138,0
56,8
73,3
42500
2,43
90,0
71,9
132,0
56,7
72,4
35000
2,33
84,3
65,7
4,0
168,0
60,4
108,0
66000
2,78
95,2
75,8
164,0
61,4
108,0
56100
2,67
91,9
72,5
159,0
59,8
107,0
46200
2,66
86,0
66,6
4,0
171,0
60,6
109,0
66000
2,82
95,2
75,8
167,0
61,6
108,0
56100
2,71
91,9
72,5
161,0
60,1
107,0
46200
2,68
86,0
66,6
4,0
202,0
76,2
117,0
72000
2,65
94,6
75,3
197,0
77,9
117,0
61200
2,53
91,3
71,9
190,0
78,2
115,0
50400
2,43
85,6
66,3
4,0
203,0
79,0
118,0
72000
2,57
94,6
75,3
198,0
80,5
118,0
61200
2,46
91,3
71,9
190,0
80,2
116,0
50400
2,37
85,6
66,3
4,0
208,0
80,6
119,0
76000
2,58
94,6
75,3
203,0
81,5
118,0
64600
2,49
91,3
71,9
195,0
79,6
117,0
53200
2,45
85,6
66,3
4,0
247,0
99,2
132,0
88000
2,49
96,3
76,5
240,0
101,3
131,0
74800
2,37
93,3
73,5
231,0
100,4
130,0
61600
2,30
88,2
68,4
5,5
292,0
112,7
176,0
108000
2,59
97,5
77,2
285,0
114,0
175,0
91800
2,50
94,6
74,2
275,0
110,4
174,0
75600
2,49
89,7
69,4
7,5
331,0
126,8
194,0
126000
2,61
97,5
77,2
323,0
129,2
193,0
107100
2,50
94,6
74,2
311,0
125,4
192,0
88200
2,48
89,7
69,4
ELN KIT
OPTIONAL
STANDARD
EAGLE FREE
1.
2.
3.
4.
5.
6.
SIZE
Cooling capacity (1)
Unit power input
Free-Cooling capacity (2)
Total water flow rate
Total pressure drop
Compressors
Quantity
Capacity steps
Axial fans
Total air flow
Air circuits
Refrigerant
Total refrigerant charge (optional excluded)
Gas circuits
Power supply
Max unit operating current (FLA)
Unit starting current (LRA)
EER (1)
ESEER
Sound power level [Lw] (3)
Average sound pressure level [Lpm] (4)
Net weight
Hydraulic connections
Evaporator IN/OUT - ISO 7/1 R
Evaporator IN/OUT - OD (5)
Partial heat recovery (6)
Heating capacity
Pumping group
Power input
Cooling capacity (1)
Unit power input
Free-Cooling capacity (2)
Total air flow
EER (1)
Sound power level [Lw] (3)
Average sound pressure level [Lpm] (4)
Cooling capacity (1)
Unit power input
Free-Cooling capacity (2)
Total air flow
EER (1)
Sound power level [Lw] (3)
Average sound pressure level [Lpm] (4)
Cooling capacity (1)
Unit power input
Free-Cooling capacity (2)
Total air flow
EER (1)
Sound power level [Lw] (3)
Average sound pressure level [Lpm] (4)
kW
kW
kW
m/h
kPa
n.
n.
n.
m/h
n.
kg
n.
V/Ph/Hz
A
A
kW/kW
kW
kW
kW
kW
m/h
kW/kW
dB(A)
dB(A)
kW
kW
kW
m/h
kW/kW
dB(A)
dB(A)
kW
kW
kW
m/h
kW/kW
dB(A)
dB(A)
Referred to glycol solution temperature 15/10C; 20% Ethylene glycol solution; air temperature to the condenser 35C. Fouling factor of the exchangers 0,043 mK/kW.
Referred to glycol solution inlet temperature 15C; 20% Ethylene glycol solution; ambient temperature 3C. Fouling factor of the exchangers 0,043 mK/kW.
Sound power level [Lw] according to ISO EN 9614 2.
Average sound pressure level [LPm] 1m far according to ISO EN 3744.
Hydraulic connection with grooved end complete with flexible joint and adapter pipe for solder connection.
Referred to glycol solution temperature 15/10C; 20% Ethylene glycol solution; air temperature to the condenser 35C. Water temperature heat recovery 40/45C 0% glycol
solution; Fouling factor of the exchangers 0,043 mK/kW.
137
EAGLE FREE
IT Cooling
DIMENSIONS (mm)
SIZE N
N6
N7
N8
N9
N10
a
2580
3020
4400
3600
4600
b
1200
1200
1800
2290
2290
c
1630
1950
1990
2250
2250
a
b
138
GLYCOL
FREECOOLING
MAIN FEATURES
Air cooled liquid chiller with free-cooling system.
21 models available, for a wide selection opportunity.
Average step of 50 kW.
EER up to 2,74.
ESEER up to 3,25.
Twin-Screw compressors.
R134a Refrigerant charge.
Double refrigerant circuit.
Shell and tube evaporator.
AC Axial fans.
Double air circuit.
Electronic expansion valve.
Suitable for outdoor installation.
R134a
SHELL
AC
FREE
COOLING
MAIN BENEFITS
Indirect free cooling system.
Availability of Glycol Free system.
Low footprint.
Availability of kit for the reduction and the extreme reduction of the noise.
Availability of pumping groups.
Availability of partial heat recovery system.
Availability of EC axial fans for a higher efficiency.
Complete set of components dedicated to the safety of the unity.
f i f t y c o o l y e a r s
139
IT Cooling
REFRIGERANT CIRCUIT
Component for each refrigerant circuit:
Electronic expansion valve that allows high performance and system
efficiency thanks to a timely and accurate response to changes in
temperature and pressure.
Energy reserve module for the electronic expansion valve to allow the
closure of the valve in the event of lack of power supply.
Sight glass.
Filter dryer on liquid line.
Service valves on liquid line.
Service valves on compressor gas discharge.
Double safety valve (only one in function) on high and low pressure side.
The system include two safety valves with manual changeover system.
Pressure transducers with indication, control and protection functions, on
low and high refrigerant pressure and oil pressure.
High pressure safety switch with manual reset.
Pressure gauge on high and low pressure.
Refrigerant circuit with copper tubing with anticondensate insulation of the
suction line.
Plastic capillary hoses for pressure sensors connection.
R134a refrigerant charge.
ELECTRICAL PANEL
In accordance with EN60204-1 norms, suitable for outdoor installation,
complete with:
Main switch with door lock safety.
Fuses for each compressor.
Magnetothermic switches for fans.
Fuses for water pumps (if scheduled).
Contactors for each load.
Compressor Part-Winding starting system from model 290 V2 F06 to model
470 V2 F08 included.
Compressor Star / Delta starting system from model 520 V2 F08 to model
1220 V2 F16 included.
Transformer for auxiliary circuit and microprocessor supply.
Panel with machine controls.
Power supply 400/3/50.
CONTROL SYSTEM
MP.COM microprocessor system with graphic display for control and
monitor of operating and alarms status. The system includes:
- Voltage free contact for remote general alarm.
- Main components hour-meter.
- Nonvolatile Flash memory for data storage.
- Menu with protection password.
- LAN connection.
Additional module 1 for ambient air temperature inlet.
Driver for the additional module 1.
FANS SECTION
Axial fans with sickle-shaped blades, fan guard and optimized for low noise
levels.
External rotor AC type electric motor.
Stepless variable speed with phase-cut electronic controller for condensing
pressure control.
Stepless variable speed with phase-cut electronic controller for free-cooling
control.
IP54 enclosure class.
140
IT Cooling
OPTIONAL ACCESSORIES
GLIDER EVO FREE
SIZE
739 - Pumping group (1 pump)
769 - Pumping group (1+1stby)
740 - Pumping group (2 pumps)
770 - Pumping group (2+1stby)
1004 - Antifreeazing heater for pumping group
118 - Kit brine A (for glycol solution production up to -6C)
119 - Kit brine B (for glycol solution production up to -12C)
786 - Pipes antifreezing kit
79 - Electrical panel heating system
150 - LNO kit (noise reduction)
151 - ELN kit (extremely noise reduction)
170 - Spring antivibration holders (kit)
171 - Rubber antivibration holders (kit)
101 - EC fan
Condensing pressure / free cooling control system
450 - Partial heat recovery
449 - Voltage free contact for partial heat recovery water pump activation
Condensing coil in special execution
251 - Coils protection nets
351 - Free Cooling Coils with pre-painted fins
731 - Safety water flow switch
1005- Safety oil flow switch
143 - Glycol free
650 - Compressor thermal relay
605 - Compr. power factor capacitor - 0,9
Supply network control relay
83 - Compressor operation indicator
550 - Stop valve on compressor suction line
85 - Demand limit
88 - Analog set point compensation
1003 - Analogic flowmeter
1005 - Power supply analyzer
1009 - Multimeter kit
919 - Clock card
923 - RC-Com MBUS/JBUS Serial board
926 - LON Serial board
931 - BACnet Ethernet - SNMP - TCP/IP Serial board
932 - BACnet MS/TP Serial board
934 - MP.COM expansion card
942 - Serial card for GSM Modem
943 - Data Logger
962 - Kit modem GSM
957 - Plantwatch without modem
930 - Remote graphic terminal kit
889 - Master plant SEQUENCER
RC CLOUD PLATFORM
F06
F08
F10
F12
F14
F16
*
*
**
**
141
IT Cooling
ELN KIT
OPTIONAL
STANDARD
1.
2.
3.
4.
5.
6.
142
dB(A)
dB(A)
kg
290 V2
F06
314
115,0
308
56,3
103
twin-screw
2
25...100%
6
119280
2
R134a
146
2
400/3/50
285,0
415,7
2,73
3,04
91,4
71,7
5751
310 V2
F06
340
124,5
315
61,0
93
twin-screw
2
25...100%
6
119280
2
R134a
146
2
400/3/50
306,0
475,7
2,73
3,09
91,6
71,8
5891
330 V2
F06
365
135,2
321
65,5
98
twin-screw
2
25...100%
6
119280
2
R134a
146
2
400/3/50
327,0
489,6
2,70
3,08
91,7
71,9
5906
350 V2
F06
387
144,9
326
69,3
87
twin-screw
2
25...100%
6
119280
2
R134a
146
2
400/3/50
345,9
562,6
2,67
3,10
91,7
72,0
5926
370 V2
F06
409
154,3
330
73,3
91
twin-screw
2
25...100%
6
119280
2
R134a
146
2
400/3/50
364,8
576,2
2,65
3,10
91,8
72,0
5931
410 V2
F08
452
169,9
439
81,1
121
twin-screw
2
25...100%
8
163168
2
R134a
145
2
400/3/50
358,3
611,2
2,66
3,07
92,1
71,9
7131
440 V2
F08
481
181,5
446
86,3
115
twin-screw
2
25...100%
8
163168
2
R134a
145
2
400/3/50
386,6
692,2
2,65
3,08
94,5
74,3
7158
470 V2
F08
510
195,4
452
91,6
124
twin-screw
2
25...100%
8
163168
2
R134a
145
2
400/3/50
415,0
714,6
2,61
3,08
96,1
75,9
7173
mm
139,7
139,7
139,7
139,7
139,7
139,7
139,7
139,7
kW
kW
230
5,5
235
5,5
240
5,5
244
5,5
247
5,5
328
5,5
333
5,5
338
5,5
kW
61,9
67,0
71,9
76,2
80,5
89,1
94,8
101,0
7,5
314
115,0
308
119280
2,73
89,4
69,7
308
115,8
306
101388
2,66
88,4
68,7
299
118,7
303
83496
2,52
85,4
65,7
299
118,7
303
83496
2,52
82,4
62,7
7,5
340
124,5
315
119280
2,73
89,6
69,8
333
125,7
313
101388
2,65
88,6
68,8
322
129,8
310
83496
2,48
85,6
65,8
322
129,8
310
83496
2,48
82,6
62,8
7,5
365
135,2
321
119280
2,70
89,7
69,9
357
136,8
320
101388
2,61
88,7
68,9
345
142,0
317
83496
2,43
85,7
65,9
345
142,0
317
83496
2,43
82,7
62,9
7,5
387
144,9
326
119280
2,67
89,7
70,0
377
147,8
324
101388
2,55
88,7
69,0
363
153,2
321
83496
2,37
85,7
66,0
363
153,2
321
83496
2,37
82,7
63,0
7,5
409
154,3
330
119280
2,65
89,8
70,0
398
157,9
328
101388
2,52
88,8
69,0
382
163,9
325
83496
2,33
85,8
66,0
382
163,9
325
83496
2,33
82,8
63,0
7,5
452
169,9
439
163168
2,66
90,1
69,9
443
171,7
437
138693
2,58
89,1
68,9
430
176,2
433
114218
2,44
86,1
65,9
430
176,2
433
114217
2,44
83,1
62,9
7,5
481
181,5
446
163168
2,65
92,5
72,3
470
185,0
443
138693
2,54
91,5
71,3
455
191,2
440
114218
2,38
88,5
68,3
455
191,2
440
114217
2,38
85,5
65,3
7,5
510
195,4
452
163168
2,61
94,1
73,9
497
198,8
450
138693
2,50
93,1
72,9
479
205,6
446
114218
2,33
90,1
69,9
479
205,6
446
114217
2,33
87,1
66,9
kW
kW
kW
m/h
kPa
n.
%
n.
m/h
n.
kg
n.
V/Ph/Hz
A
A
kW/kW
kW
kW
kW
kW
m/h
kW/kW
dB(A)
dB(A)
kW
kW
kW
m/h
kW/kW
dB(A)
dB(A)
kW
kW
kW
m/h
kW/kW
dB(A)
dB(A)
kW
kW
kW
m/h
kW/kW
dB(A)
dB(A)
Referred to glycol solution temperature 15/10C; 20% Ethylene glycol solution; air temperature to the condenser 35C. Fouling factor of the exchangers 0,043 mK/kW.
Referred to glycol solution inlet temperature 15C; 20% Ethylene glycol solution; ambient temperature 3C. Fouling factor of the exchangers 0,043 mK/kW.
Sound power level [Lw] according to ISO EN 9614 2.
Average sound pressure level [LPm] 1m far according to ISO EN 3744.
Hydraulic connection with grooved end complete with flexible joint and adapter pipe for solder connection.
Referred to glycol solution temperature 15/10C; 20% Ethylene glycol solution; air temperature to the condenser 35C. Water temperature heat recovery 40/45C 0% glycol
solution; Fouling factor of the exchangers 0,043 mK/kW.
IT Cooling
ELN KIT
OPTIONAL
STANDARD
1.
2.
3.
4.
5.
6.
dB(A)
dB(A)
kg
520 V2
F08
572
221,7
456
103
131
twin-screw
2
25...100%
8
159040
2
R134a
194
2
400/3/50
444,4
529,9
2,58
3,05
96,1
75,9
7637
550 V2
F08
600
235,3
460
108
144
twin-screw
2
25...100%
8
159040
2
R134a
194
2
400/3/50
463,3
556,9
2,55
3,05
97,5
77,3
7647
610 V2
F08
674
255,3
469
121
167
twin-screw
2
25...100%
8
159040
2
R134a
194
2
400/3/50
482,2
581,2
2,64
3,19
98,6
78,4
7657
670 V2
F10
736
271,6
574
132
67
twin-screw
2
25...100%
10
203960
2
R134a
181
2
400/3/50
559,7
684,0
2,71
3,18
99,3
78,7
8924
720 V2
F10
796
290,5
583
143
70
twin-screw
2
25...100%
10
203960
2
R134a
181
2
400/3/50
629,0
709,0
2,74
3,25
99,9
79,2
9344
770 V2
F10
845
309,5
583
152
85
twin-screw
2
25...100%
10
198800
2
R134a
241
2
400/3/50
660,5
738,0
2,73
3,21
99,8
79,1
9664
810 V2
F10
887
334,7
589
159
89
twin-screw
2
25...100%
10
198800
2
R134a
241
2
400/3/50
692,0
762,0
2,65
3,22
99,6
79,0
9674
870 V2
F12
952
366,2
693
171
110
twin-screw
2
25...100%
12
244752
2
R134a
217
2
400/3/50
710,6
890,8
2,60
3,17
100,0
79,0
10664
mm
139,7
139,7
139,7
168,3
168,3
168,3
168,3
168,3
kW
kW
341
7,5
344
7,5
351
15,0
429
15,0
435
15,0
436
15,0
441
15,0
519
15,0
kW
113
118
133
145
157
166
175
187
7,5
572
221,7
456
159040
2,58
94,1
73,9
556
227,9
453
135184
2,44
93,1
72,9
534
237,3
450
111328
2,25
90,1
69,9
534
237,3
450
111328
2,25
87,1
66,9
7,5
600
235,3
460
159040
2,55
95,5
75,3
583
241,9
457
135184
2,41
94,5
74,3
558
253,6
454
111328
2,20
91,5
71,3
558
253,6
454
111328
2,20
88,5
68,3
7,5
674
255,3
469
159040
2,64
96,6
76,4
653
263,3
467
135184
2,48
95,6
75,4
623
276,9
463
111328
2,25
92,6
72,4
623
276,9
463
111328
2,25
89,6
69,4
7,5
736
271,6
574
203960
2,71
97,3
76,7
715
279,3
570
173366
2,56
96,3
75,7
685
290,3
564
142772
2,36
93,3
72,7
685
290,3
564
142772
2,36
90,3
69,7
7,5
796
290,5
583
203960
2,74
97,9
77,2
770
298,4
578
173366
2,58
96,9
76,2
735
311,4
572
142772
2,36
93,9
73,2
735
311,4
572
142772
2,36
90,9
70,2
7,5
845
309,5
583
198800
2,73
97,8
77,1
817
319,1
580
168980
2,56
96,8
76,1
779
332,9
574
139160
2,34
93,8
73,1
779
332,9
574
139160
2,34
90,8
70,1
7,5
887
334,7
589
198800
2,65
97,6
77,0
856
345,2
586
168980
2,48
96,6
76,0
813
361,3
580
139160
2,25
93,6
73,0
813
361,3
580
139160
2,25
90,6
70,0
7,5
952
366,2
693
244752
2,60
98,0
77,0
923
375,2
690
208039
2,46
97,0
76,0
883
392,4
684
171326
2,25
94,0
73,0
883
392,4
684
171326
2,25
91,0
70,0
kW
kW
kW
m/h
kPa
n.
%
n.
m/h
n.
kg
n.
V/Ph/Hz
A
A
kW/kW
kW
kW
kW
kW
m/h
kW/kW
dB(A)
dB(A)
kW
kW
kW
m/h
kW/kW
dB(A)
dB(A)
kW
kW
kW
m/h
kW/kW
dB(A)
dB(A)
kW
kW
kW
m/h
kW/kW
dB(A)
dB(A)
Referred to glycol solution temperature 15/10C; 20% Ethylene glycol solution; air temperature to the condenser 35C. Fouling factor of the exchangers 0,043 mK/kW.
Referred to glycol solution inlet temperature 15C; 20% Ethylene glycol solution; ambient temperature 3C. Fouling factor of the exchangers 0,043 mK/kW.
Sound power level [Lw] according to ISO EN 9614 2.
Average sound pressure level [LPm] 1m far according to ISO EN 3744.
Hydraulic connection with grooved end complete with flexible joint and adapter pipe for solder connection.
Referred to glycol solution temperature 15/10C; 20% Ethylene glycol solution; air temperature to the condenser 35C. Water temperature heat recovery 40/45C 0% glycol
solution; Fouling factor of the exchangers 0,043 mK/kW.
143
IT Cooling
ELN KIT
OPTIONAL
STANDARD
1.
2.
3.
4.
5.
6.
dB(A)
dB(A)
kg
930 V2
F12
1017
394,2
702
183
114
twin-screw
2
25...100%
12
244752
2
R134a
217
2
400/3/50
721,1
938,8
2,58
3,19
99,2
78,2
10734
980 V2
F12
1071
416,7
709
193
127
twin-screw
2
25...100%
12
244752
2
R134a
217
2
400/3/50
763,1
1002,8
2,57
3,21
100,9
79,8
10774
1030 V2
F12
1128
438,9
703
203
139
twin-screw
2
25...100%
12
238560
2
R134a
289
2
400/3/50
805,1
1041,8
2,57
3,16
102,1
81,0
11146
1130 V2
F14
1238
470,7
819
220
130
twin-screw
2
25...100%
14
278320
2
R134a
337
2
400/3/50
924,6
1247,6
2,63
3,24
102,1
80,7
12126
1220 V2
F16
1343
512,6
938
241
172
twin-screw
2
25...100%
16
318080
2
R134a
389
2
400/3/50
1004,2
1402,4
2,62
3,13
102,4
80,6
13636
mm
168,3
168,3
168,3
168,3
168,3
kW
kW
525
15,0
531
15,0
526
15,0
613
15,0
702
15,0
kW
200
211
222
244
265
7,5
1017
394,2
702
244752
2,58
97,2
76,2
984
404,9
698
208039
2,43
96,2
75,2
938
424,4
692
171326
2,21
93,2
72,2
938
424,4
692
171326
2,21
90,2
69,2
15,0
1071
416,7
709
244752
2,57
98,9
77,8
1034
430,8
705
208039
2,40
97,9
76,8
982
452,5
699
171326
2,17
94,9
73,8
982
452,5
699
171326
2,17
91,9
70,8
15,0
1128
438,9
703
238560
2,57
100,1
79,0
1089
453,8
699
202776
2,40
99,1
78,0
1033
480,5
694
166992
2,15
96,1
75,0
1033
480,5
694
166992
2,15
93,1
72,0
15,0
1238
470,7
819
278320
2,63
100,1
78,7
1197
486,6
816
236572
2,46
99,1
77,7
1138
510,3
810
194824
2,23
96,1
74,7
1138
510,3
810
194824
2,23
93,1
71,7
15,0
1343
512,6
938
318080
2,62
100,4
78,6
1303
527,5
933
270368
2,47
99,4
77,6
1246
551,3
927
222656
2,26
96,4
74,6
1246
551,3
927
222656
2,26
93,4
71,6
kW
kW
kW
m/h
kPa
n.
%
n.
m/h
n.
kg
n.
V/Ph/Hz
A
A
kW/kW
kW
kW
kW
kW
m/h
kW/kW
dB(A)
dB(A)
kW
kW
kW
m/h
kW/kW
dB(A)
dB(A)
kW
kW
kW
m/h
kW/kW
dB(A)
dB(A)
kW
kW
kW
m/h
kW/kW
dB(A)
dB(A)
Referred to glycol solution temperature 15/10C; 20% Ethylene glycol solution; air temperature to the condenser 35C. Fouling factor of the exchangers 0,043 mK/kW.
Referred to glycol solution inlet temperature 15C; 20% Ethylene glycol solution; ambient temperature 3C. Fouling factor of the exchangers 0,043 mK/kW.
Sound power level [Lw] according to ISO EN 9614 2.
Average sound pressure level [LPm] 1m far according to ISO EN 3744.
Hydraulic connection with grooved end complete with flexible joint and adapter pipe for solder connection.
Referred to glycol solution temperature 15/10C; 20% Ethylene glycol solution; air temperature to the condenser 35C. Water temperature heat recovery 40/45C 0% glycol
solution; Fouling factor of the exchangers 0,043 mK/kW.
DIMENSIONS (mm)
SIZE F
F06
F08
F10
F12
F14
F16
144
3640
4610
5580
6550
7520
8720
2260
2260
2260
2260
2260
2260
2550
2550
2550
2550
2550
2250
HIGHEFFICIENCY
ACLASS
GLYCOL
FREECOOLING
MAIN FEATURES
Air cooled liquid chiller with free-cooling system in A class energy
efficiency.
24 models available, for a wide selection opportunity.
Average step of 50kW.
EER up to 3,34.
ESEER up to 3,83.
Twin-Screw compressors.
R134a Refrigerant charge.
Double refrigerant circuit.
Shell and tube evaporator.
AC Axial fans.
Double air circuit.
Electronic expansion valve.
Suitable for outdoor installation.
MAIN BENEFITS
Indirect free cooling system.
Availability of Glycol Free system.
High EER and ESEER, A class energy efficiency.
Availability of kit for the reduction and the extreme reduction of the noise.
Availability of pumping groups.
Availability of partial heat recovery system.
Availability of EC axial fans for a higher efficiency.
Complete set of components dedicated to the safety of the unity.
R134a
SHELL
CLASS
AC
FREE
COOLING
f i f t y c o o l y e a r s
145
IT Cooling
REFRIGERANT CIRCUIT
Component for each refrigerant circuit:
Electronic expansion valve that allows high performance and system
efficiency thanks to a timely and accurate response to changes in
temperature and pressure.
Energy reserve module for the electronic expansion valve to allow the
closure of the valve in the event of lack of power supply.
Sight glass.
Filter dryer on liquid line.
Service valves on liquid line.
Service valves on compressor gas discharge.
Double safety valve (only one in function) on high and low pressure side.
The system include two safety valves with manual changeover system.
Pressure transducers with indication, control and protection functions, on
low and high refrigerant pressure and oil pressure.
High pressure safety switch with manual reset.
Pressure gauge on high and low pressure.
Refrigerant circuit with copper tubing with anticondensate insulation of the
suction line.
Plastic capillary hoses for pressure sensors connection.
R134a refrigerant charge.
ELECTRICAL PANEL
In accordance with EN60204-1 norms, suitable for outdoor installation,
complete with:
Main switch with door lock safety.
Fuses for each compressor.
Magnetothermic switches for fans.
Fuses for water pumps (if scheduled).
Contactors for each load.
Compressor Part-Winding starting system from model 290 V2 F06 to model
590 V2 F10 included.
Compressor Star / Delta starting system from model 630 V2 F12 to model
1450 V2 F24 included.
Transformer for auxiliary circuit and microprocessor supply.
Panel with machine controls.
Power supply 400/3/50.
CONTROL SYSTEM
MP.COM microprocessor system with graphic display for control and
monitor of operating and alarms status. The system includes:
- Voltage free contact for remote general alarm.
- Main components hour-meter.
- Nonvolatile Flash memory for data storage.
- Menu with protection password.
- LAN connection.
Additional module 1 for ambient air temperature inlet.
Driver for the additional module 1.
FANS SECTION
Axial fans with sickle-shaped blades, fan guard and optimized for low noise
levels.
External rotor AC type electric motor.
Stepless variable speed with phase-cut electronic controller for condensing
pressure control.
Stepless variable speed with phase-cut electronic controller for free-cooling
control.
IP54 enclosure class.
146
IT Cooling
OPTIONAL ACCESSORIES
GLIDER EVO FREE CLA
SIZE
739 - Pumping group (1 pump)
769 - Pumping group (1+1stby)
740 - Pumping group (2 pumps)
770 - Pumping group (2+1stby)
1004 - Antifreeazing heater for pumping group
118 - Kit brine A (for glycol solution production up to -6C)
119 - Kit brine B (for glycol solution production up to -12C)
786 - Pipes antifreezing kit
79 - Electrical panel heating system
150 - LNO kit (noise reduction)
151 - ELN kit (extremely noise reduction)
170 - Spring antivibration holders (kit)
171 - Rubber antivibration holders (kit)
101 - EC fan
Condensing pressure / Free cooling control system
450 - Partial heat recovery
449 - Voltage free contact for partial heat recovery water pump activation
Condensing coil in special execution
250 - Coils protection nets (kit)
731 - Safety water flow switch
1005- Safety oil flow switch
143 - Glycol free
650 - Compressor thermal relay
605 - Compr. power factor capacitor - 0,9
Supply network control relay
83 - Compressor operation indicator
550 - Stop valve on compressor suction line
85 - Demand limit
88 - Analog set point compensation
1003 - Analogic flowmeter
1005 - Power supply analyzer
1009 - Multimeter kit
919 - Clock card
923 - RC-Com MBUS/JBUS Serial board
926 - LON Serial board
931 - BACnet Ethernet - SNMP - TCP/IP Serial board
932 - BACnet MS/TP Serial board
934 - MP.COM expansion card
942 - Serial card for GSM Modem
943 - Data Logger
962 - Kit modem GSM
957 - Plantwatch without modem
930 - Remote graphic terminal kit
889 - Master plant SEQUENCER
RC CLOUD PLATFORM
F06
F08
F10
F12
F14
F16
F18
F20
F22
F24
147
IT Cooling
ELN KIT
OPTIONAL
STANDARD
1.
2.
3.
4.
5.
6.
148
dB(A)
dB(A)
kg
290 V2
F06
319
95,5
323
57,2
54
twin-screw
2
25... 100%
6
122336
2
R134a
110
2
400/3/50
251,4
400,4
3,34
3,78
92,1
72,4
5330
310 V2
F06
335
100,9
325
60,0
53
twin-screw
2
25... 100%
6
119280
2
R134a
146
2
400/3/50
230,4
388,4
3,32
3,77
92,5
72,8
5923
330 V2
F08
361
109,1
397
64,6
69
twin-screw
2
25... 100%
7
142772
2
R134a
145
2
400/3/50
261,8
418,3
3,31
3,78
92,7
72,5
6633
360 V2
F08
386
117,7
435
69,2
74
twin-screw
2
25... 100%
8
163168
2
R134a
145
2
400/3/50
293,2
445,2
3,28
3,74
92,9
72,7
6638
380 V2
F08
409
124,7
438
73,2
76
twin-screw
2
25... 100%
8
159040
2
R134a
194
2
400/3/50
293,2
445,2
3,28
3,76
91,5
71,3
6857
420 V2
F08
451
138,3
452
80,8
89
twin-screw
2
25... 100%
8
159040
2
R134a
194
2
400/3/50
335,2
525,2
3,26
3,77
91,9
71,7
6895
460 V2
F10
501
151,4
520
89,8
54
twin-screw
2
25... 100%
10
198800
2
R134a
241
2
400/3/50
381,2
624,0
3,31
3,74
92,1
71,4
8018
490 V2
F10
532
162,2
533
95,2
68
twin-screw
2
25... 100%
10
198800
2
R134a
241
2
400/3/50
366,5
633,0
3,28
3,75
96,2
75,6
8030
mm
139,7
139,7
139,7
139,7
139,7
139,7
139,7
139,7
kW
kW
241
5,5
243
5,5
297
5,5
325
5,5
327
5,5
338
5,5
387
5,5
397
5,5
kW
62,9
66,0
71,1
76,1
80,6
88,9
98,8
105,0
7,5
319
95,5
323
122376
3,34
90,1
70,4
313
95,4
321
104019
3,28
89,1
69,4
305
96,5
318
85663
3,16
86,1
66,4
305
96,5
318
85663
3,16
83,1
63,4
7,5
335
100,9
325
119280
3,32
90,5
70,8
330
102,5
323
101388
3,22
89,5
69,8
322
106,3
321
83496
3,03
86,5
66,8
322
106,3
321
83496
3,03
83,5
63,8
7,5
361
109,1
397
142772
3,31
90,7
70,5
356
110,2
395
121356
3,23
89,7
69,5
349
112,6
393
99940
3,10
86,7
66,5
349
112,6
393
99940
3,10
83,7
63,5
7,5
386
117,7
435
163168
3,28
90,9
70,7
382
117,9
433
138692
3,24
89,9
69,7
375
120,2
431
114218
3,12
86,9
66,7
375
120,2
431
114218
3,12
83,9
63,7
7,5
409
124,7
438
159040
3,28
89,5
69,3
404
125,1
436
135184
3,23
88,5
68,3
397
128,5
434
111328
3,09
85,5
65,3
397
128,5
434
111328
3,09
82,5
62,3
7,5
451
138,3
452
159040
3,26
89,9
69,7
445
140,8
451
135184
3,16
88,9
68,7
436
144,4
448
111328
3,02
85,9
65,7
436
144,4
448
111328
3,02
82,9
62,7
7,5
501
151,4
520
198800
3,31
90,1
69,4
496
152,1
518
168980
3,26
89,1
68,4
487
156,1
514
139160
3,12
86,1
65,4
487
156,1
514
139160
3,12
83,1
62,4
7,5
532
162,2
533
198800
3,28
94,2
73,6
522
164,2
529
168980
3,18
93,2
72,6
509
168,5
524
139160
3,02
90,2
69,6
509
168,5
524
139160
3,02
87,2
66,6
kW
kW
kW
m/h
kPa
n.
%
n.
m/h
n.
kg
n.
V/Ph/Hz
A
A
kW/kW
kW
kW
kW
kW
m/h
kW/kW
dB(A)
dB(A)
kW
kW
kW
m/h
kW/kW
dB(A)
dB(A)
kW
kW
kW
m/h
kW/kW
dB(A)
dB(A)
kW
kW
kW
m/h
kW/kW
dB(A)
dB(A)
Referred to glycol solution temperature 15/10C; 20% Ethylene glycol solution; air temperature to the condenser 35C. Fouling factor of the exchangers 0,043 mK/kW.
Referred to glycol solution inlet temperature 15C; 20% Ethylene glycol solution; ambient temperature 3C. Fouling factor of the exchangers 0,043 mK/kW.
Sound power level [Lw] according to ISO EN 9614 2.
Average sound pressure level [LPm] 1m far according to ISO EN 3744.
Hydraulic connection with grooved end complete with flexible joint and adapter pipe for solder connection.
Referred to glycol solution temperature 15/10C; 20% Ethylene glycol solution; air temperature to the condenser 35C. Water temperature heat recovery 40/45C 0% glycol
solution; Fouling factor of the exchangers 0,043 mK/kW.
IT Cooling
ELN KIT
OPTIONAL
STANDARD
1.
2.
3.
4.
5.
6.
dB(A)
dB(A)
kg
540 V2
F10
584
178,6
553
105,0
71
twin-screw
2
25... 100%
10
198800
2
R134a
241
2
400/3/50
394,8
714,0
3,27
3,75
96,5
75,8
8182
590 V2
F10
638
195,1
570
114,0
73
twin-screw
2
25... 100%
10
198800
2
R134a
241
2
400/3/50
423,2
741,0
3,27
3,75
96,7
76,0
8304
630 V2
F12
691
210,7
655
124,0
92
twin-screw
2
25... 100%
12
238560
2
R134a
289
2
400/3/50
460,7
556,8
3,28
3,71
97,7
76,7
9086
680 V2
F14
735
228,3
735
132,0
110
twin-screw
2
25... 100%
13
261794
2
R134a
294,5
2
400/3/50
483,7
587,7
3,22
3,72
99,3
77,9
9669
720 V2
F14
781
244,1
773
140,0
113
twin-screw
2
25... 100%
14
278320
2
R134a
337
2
400/3/50
506,7
609,6
3,20
3,77
100,4
79,0
9872
790 V2
F16
863
266,4
868
155,0
118
twin-screw
2
25... 100%
15
302070
2
R134a
339,5
2
400/3/50
580,1
708,5
3,24
3,74
101,1
79,3
11754
860 V2
F16
943
291,0
917
169,0
125
twin-screw
2
25... 100%
16
318080
2
R134a
389
2
400/3/50
653,5
778,4
3,24
3,72
101,7
79,9
12233
910 V2
F16
993
308,4
930
178,0
141
twin-screw
2
25... 100%
16
318080
2
R134a
389
2
400/3/50
685,0
808,4
3,22
3,71
101,6
79,8
12267
mm
139,7
139,7
139,7
139,7
139,7
168,3
168,3
168,3
kW
kW
412
5,5
425
7,5
490
7,5
549
7,5
578
7,5
649
15,0
686
15,0
696
15,0
kW
115,0
126,0
136,0
145,0
154,0
170,0
186,0
196,0
7,5
584
178,6
553
198800
3,27
94,5
73,8
574
181,6
550
168980
3,16
93,5
72,8
559
187,0
545
139160
2,99
90,5
69,8
559
187,0
545
139160
2,99
87,5
66,8
7,5
638
195,1
570
198800
3,27
94,7
74,0
627
197,8
567
168980
3,17
93,7
73,0
611
204,3
562
139160
2,99
90,7
70,0
611
204,3
562
139160
2,99
87,7
67,0
7,5
691
210,7
655
238560
3,28
95,7
74,7
681
213,5
653
202776
3,19
94,7
73,7
665
218,8
648
166992
3,04
91,7
70,7
665
218,8
648
166992
3,04
88,7
67,7
7,5
735
228,3
735
261794
3,22
97,3
75,9
723
231,0
732
222524
3,13
96,3
74,9
705
236,6
727
183256
2,98
93,3
71,9
705
236,6
727
183256
2,98
90,3
68,9
7,5
781
244,1
773
278320
3,20
98,4
77,0
768
246,2
770
236572
3,12
97,4
76,0
748
252,7
764
194824
2,96
94,4
73,0
748
252,7
764
194824
2,96
91,4
70,0
15,0
863
266,4
868
302070
3,24
99,1
77,3
850
269,8
864
256759
3,15
98,1
76,3
830
275,7
859
211449
3,01
95,1
73,3
830
275,7
859
211449
3,01
92,1
70,3
15,0
943
291,0
917
318080
3,24
99,7
77,9
929
294,9
913
270368
3,15
98,7
76,9
907
302,3
908
222656
3,00
95,7
73,9
907
302,3
908
222656
3,00
92,7
70,9
15,0
993
308,4
930
318080
3,22
99,6
77,8
976
312,8
926
270368
3,12
98,6
76,8
952
321,6
921
222656
2,96
95,6
73,8
952
321,6
921
222656
2,96
92,6
70,8
kW
kW
kW
m/h
kPa
n.
%
n.
m/h
n.
kg
n.
V/Ph/Hz
A
A
kW/kW
kW
kW
kW
kW
m/h
kW/kW
dB(A)
dB(A)
kW
kW
kW
m/h
kW/kW
dB(A)
dB(A)
kW
kW
kW
m/h
kW/kW
dB(A)
dB(A)
kW
kW
kW
m/h
kW/kW
dB(A)
dB(A)
Referred to glycol solution temperature 15/10C; 20% Ethylene glycol solution; air temperature to the condenser 35C. Fouling factor of the exchangers 0,043 mK/kW.
Referred to glycol solution inlet temperature 15C; 20% Ethylene glycol solution; ambient temperature 3C. Fouling factor of the exchangers 0,043 mK/kW.
Sound power level [Lw] according to ISO EN 9614 2.
Average sound pressure level [LPm] 1m far according to ISO EN 3744.
Hydraulic connection with grooved end complete with flexible joint and adapter pipe for solder connection.
Referred to glycol solution temperature 15/10C; 20% Ethylene glycol solution; air temperature to the condenser 35C. Water temperature heat recovery 40/45C 0% glycol
solution; Fouling factor of the exchangers 0,043 mK/kW.
149
IT Cooling
ELN KIT
OPTIONAL
STANDARD
1.
2.
3.
4.
5.
6.
dB(A)
dB(A)
kg
960 V2
F16
1043
324,9
943
187,0
147
twin-screw
2
25... 100%
16
318080
2
R134a
389
2
400/3/50
716,5
837,4
3,21
3,72
101,4
79,6
12277
1050 V2
F16
1146
358,1
965
205,0
133
twin-screw
2
25... 100%
16
318080
2
R134a
389
2
400/3/50
737,5
968,4
3,20
3,83
99,9
78,1
12376
1110 V2
F18
1215
379,7
1056
218,0
153
twin-screw
2
25... 100%
18
357840
2
R134a
436
2
400/3/50
787,7
1040,2
3,20
3,79
101,7
79,5
13934
1170 V2
F20
1285
394,2
1144
230,0
80
twin-screw
2
25... 100%
20
397600
2
R134a
482
2
400/3/50
837,9
1088,0
3,26
3,77
103,9
81,5
15142
1240 V2
F20
1361
418,8
1165
244,0
89
twin-screw
2
25... 100%
20
397600
2
R134a
482
2
400/3/50
893,6
1243,0
3,25
3,78
103,9
81,5
15402
1310 V2
F20
1438
442,5
1185
258,0
71
twin-screw
2
25... 100%
20
397600
2
R134a
482
2
400/3/50
949,2
1296,0
3,25
3,83
103,9
81,5
15422
1380 V2
F22
1508
465,4
1273
270,0
88
twin-screw
2
25... 100%
22
437360
2
R134a
530
2
400/3/50
993,1
1415,8
3,24
3,81
104,1
81,4
16101
1450 V2
F24
1583
488,6
1370
284,0
91
twin-screw
2
25... 100%
24
477120
2
R134a
578
2
400/3/50
1037,0
1457,6
3,24
3,79
104,2
81,3
16780
mm
168,3
168,3
168,3
168,3
168,3
168,3
168,3
168,3
kW
kW
705
15,0
722
15,0
790
15,0
854
15,0
870
15,0
885
15,0
951
15,0
1024
15,0
kW
206,0
226,0
239,0
253,0
268,0
283,0
297,0
312,0
15,0
1.043
324,9
943
318080
3,21
99,4
77,6
1.025
330,6
939
270368
3,10
98,4
76,6
997
340,3
934
222656
2,93
95,4
73,6
997
340,3
934
222656
2,93
92,4
70,6
15,0
1.146
358,1
965
318080
3,20
97,9
76,1
1.124
367,3
961
270368
3,06
96,9
75,1
1091
382,8
956
222656
2,85
93,9
72,1
1091
382,8
956
222656
2,85
90,9
69,1
15,0
1.215
379,7
1056
357840
3,20
99,7
77,5
1.193
387,3
1052
304164
3,08
98,7
76,5
1159
401,0
1046
250488
2,89
95,7
73,5
1159
401,0
1046
250488
2,89
92,7
70,5
15,0
1.285
394,2
1144
397600
3,26
101,9
79,5
1.262
400,6
1138
337960
3,15
100,9
78,5
1227
413,1
1129
278320
2,97
97,9
75,5
1227
413,1
1129
278320
2,97
94,9
72,5
15,0
1.361
418,8
1165
397600
3,25
101,9
79,5
1.334
426,2
1159
337960
3,13
100,9
78,5
1294
441,6
1149
278320
2,93
97,9
75,5
1294
441,6
1149
278320
2,93
94,9
72,5
15,0
1.438
442,5
1185
397600
3,25
101,9
79,5
1.407
452,4
1178
337960
3,11
100,9
78,5
1362
471,3
1168
278320
2,89
97,9
75,5
1362
471,3
1168
278320
2,89
94,9
72,5
15,0
1.508
465,4
1273
437360
3,24
102,1
79,4
1.477
474,9
1267
371756
3,11
101,1
78,4
1432
492,1
1257
306152
2,91
98,1
75,4
1432
492,1
1257
306152
2,91
95,1
72,4
15,0
1.583
488,6
1370
477120
3,24
102,2
79,3
1.553
497,8
1364
405552
3,12
101,2
78,3
1509
515,0
1354
333984
2,93
98,2
75,3
1509
515,0
1354
333984
2,93
95,2
72,3
kW
kW
kW
m/h
kPa
n.
%
n.
m/h
n.
kg
n.
V/Ph/Hz
A
A
kW/kW
kW
kW
kW
kW
m/h
kW/kW
dB(A)
dB(A)
kW
kW
kW
m/h
kW/kW
dB(A)
dB(A)
kW
kW
kW
m/h
kW/kW
dB(A)
dB(A)
kW
kW
kW
m/h
kW/kW
dB(A)
dB(A)
Referred to glycol solution temperature 15/10C; 20% Ethylene glycol solution; air temperature to the condenser 35C. Fouling factor of the exchangers 0,043 mK/kW.
Referred to glycol solution inlet temperature 15C; 20% Ethylene glycol solution; ambient temperature 3C. Fouling factor of the exchangers 0,043 mK/kW.
Sound power level [Lw] according to ISO EN 9614 2.
Average sound pressure level [LPm] 1m far according to ISO EN 3744.
Hydraulic connection with grooved end complete with flexible joint and adapter pipe for solder connection.
Referred to glycol solution temperature 15/10C; 20% Ethylene glycol solution; air temperature to the condenser 35C. Water temperature heat recovery 40/45C 0% glycol
solution; Fouling factor of the exchangers 0,043 mK/kW.
DIMENSIONS (mm)
SIZE F
F06
F08
F10
F12
F14
F16
F18
F20
F22
F24
150
a
3520
4490
5460
6430
7400
8720
9690
10660
11630
12600
b
2260
2260
2260
2260
2260
2260
2260
2260
2260
2260
c
2550
2550
2550
2550
2550
2550
2550
2550
2550
2550
FREECOOLING
HIGHEFFICIENCY
INVERTER
ACLASS
LOWNOISE
MAIN FEATURES
Air cooled liquid chiller with free-cooling system in A class energy
efficiency.
15 models available, for a wide selection opportunity.
Average step of 100kW.
EER up to 3,60.
ESEER up to 5,76.
Oil-free centrifugal compressors with magnetic levitation bearings driven
by built-in inverter.
R134a Refrigerant charge.
Single refrigerant circuit.
AC Axial fans.
Flooded evaporator.
Microchannel condensing coils in aluminium.
Electronic expansion valve.
Single air circuit.
Modular construction.
Suitable for outdoor installation.
MAIN BENEFITS
Up to four centrifugal compressors with magnetic levitation bearings on
the refrigerant circuit for an high efficiency.
No need of power factor correction.
Minimum starting current (LRA)
Low refrigerant charge.
Very high EER and ESEER. A Class energy efficiency.
Quiet operation.
Availability of double refrigerant circuit version.
Availability of kit for further reduction of the noise.
Availability of EC fans for a higher efficiency.
19632013 fiftycoolyears RCGROUP SpA G_ITC_RCW8.4
CLASS
INVERTER
OIL
FREE
R134a
FLOODED
AC
MICRO
FREE
CHANNEL COOLING
f i f t y c o o l y e a r s
151
IT Cooling
COMPONENTS
FRAMEWORK
Base, self supporting frame and panelling in steel plate with protective
surfaces treatment in compliance with UNI ISO 9227/ASTMB117 and ISO
7253, and painted with epoxy powders.
Colour: RAL 9002 textured.
FAN SECTION
Axial fans with sickle-shaped blades, fan guard and optimized for low noise
levels.
External rotor AC type electric motor with stepless variable speed for
condensing pressure control.
IP54 enclosure class.
COMPRESSORS
Twin-turbine centrifugal compressor, oil-free type, optimized for R134a
refrigerant. The term oil-free refers to the total absence of lubricating oil
within the compressor
Magnetic levitation bearings.
Manometric compression ratio: 1.5 5.0.
Stepless capacity control trough integrated inverter.
High efficiency permanent-magnet synchronous motor with integrated SoftStart system (starting current limited to 5A).
Power factor motor cos > 0.9 for a large part of the operating range.
Motor and electronic power section cooling by liquid refrigerant injection into
the integrated cooling circuit.
Electric motor thermal protection via internal winding temperature sensors.
Electronic integrated control for operation and alarms status.
Sensor on refrigerant discharge for temperature monitoring.
Inner sensors for electronic components and inverter temperature control.
Security system to protect the crankshaft and magnetic bearings in the
event of failure of power supply.
Installation with walls sound attenuators.
Degree of protection: IP54.
Electric resistance of the suction pipe, together with activated antifreeze
evaporator, to prevent the migration of refrigerant inside the compressor.
REFRIGERANT CIRCUIT
Components for each refrigerant circuit:
Capacitive level sensor connected to the driver of the expansion valve.
Electronic expansion valve that allows high performance and system
efficiency and for the refrigerant level control in the evaporator.
By-pass valve for start-up.
Electronic by-pass valve for compressor start.
Non return valve on by-pass line for compressor start.
Economizer for model 560 T2E, 810 T2E, 1070 T4E, 1120 T4E, 1200 T3E,
1500 T4E. The system includes:
- Copper brazed plate type with cover plates, plates and connections in
AISI 316 stainless steel.
- Anticondensate insulation made of polyurethane.
- Intermediate electronic expansion valve.
Sight glass.
Filter dryer on liquid line.
Service valve on liquid line.
Service valve on gas suction and discharge.
Non return valve on gas discharge.
Safety valve on low pressure side.
Safety valve on high pressure side.
Pressure transducers with indication, control and protection functions, on
low and high refrigerant pressure.
High pressure safety switch with manual reset.
Refrigerant circuit with copper tubing with anticondensate insulation of the
suction line.
Plastic capillary hoses for pressure sensors connection and cooling line of
the compressor
R134a refrigerant charge.
EVAPORATOR
Flooded shell and tube evaporator, optimized for R134a refrigerant.
Version two passes, characterized by low pressure losses on the water
side.
Water tubes with a helical rifled internal surface.
Integrated liquid drop separator.
Shell, header, tube sheets made of carbon steel, tubes in Cu.
Anticondensate insulation made of polyurethane.
Large liquid level indicator.
Temperature sensors on water inlet and outlet.
Water flow switch for water flow control on water outlet towards the plant,
not installed but supplied in kit.
Large liquid level indicator
Antifreeze heater.
Hydraulic connections with grooved end supplied as standard with flexible
joint and adapter pipe to be welded.
CONDENSING COIL
Microchannel condensing coil in aluminium perfectly suitable for the civil
and industrial applications cooling, while the protection function of the oxide
layer allows an optimum resistance to corrosion also in case of aggressive
ambient conditions.
Extremely light construction. The coil weight is only 50% compared to
traditional copper pipes and aluminium fins of the same capacity.
Low air side pressure drop and consequentially drastic reduction of the fans
motors electric energy consumption.
High heat exchange efficiency.
Reduced internal volume capable of reducing the total refrigerant charge.
At the same performances conditions, the micro-channels condensers
require up-to less than 75% refrigerant when compared to the traditional
heat exchangers.
Single air circuit.
Motorized valves for condenser partialization system.
Frame in painted galvanized steel.
ELECTRICAL PANEL
In accordance with EN60204-1 norms, suitable for outdoor installation,
complete with:
Main switch with door lock safety.
Fuses for each compressor.
Magnetothermic switches for fans or water pumps (if scheduled).
Contactors for each load.
Transformer for auxiliary circuit and microprocessor supply.
Panel with machine controls.
Power supply 400/3/50.
CONTROL SYSTEM
Microprocessor system with Touch Screen graphic display for control and
monitor of operating and alarms status. The system includes:
- Voltage free contact for remote general alarm.
- Voltage free contact for external alarm. The inlet is associable with
refrigerant gas leak detector (optional accessory).
- Main components hour-meter.
- Recording of the last 24 occurred alarms.
- Non-volatile Flash memory for data storage.
- Menu with protection password.
FREE-COOLING COIL
Heat exchanger coil with copper tubes and high efficiency aluminium fins,
specifically developed to provide high heat transfer and lower pressure
drops. The combination of two factors, special tubes and fins, allow to
optimally combine the following aspects:
- Maximum capacity relative to the size of the exchanger.
- Reduction of the air flow required for the heat exchange.
Frame in galvanized steel.
Motorized valves for free-cooling water circuit control.
Intermediate free-cooling sensor.
Temperature sensor on ambient air.
152
IT Cooling
OPTIONAL ACCESSORIES
UNICO TURBO FL FREE
SIZE
150 - LNO kit (noise reduction)
Active filters for containment of the harmonic distortion
172 - Rubber support (kit)
79 - Electrical panel heating system
179 - Double refrigerant circuit
101 - EC fan
350 -Kit TK PRO corrosion resistant painting treatment
351 - Free-cooling coils with pre-painted fins
1003 - Analogic flowmeter
1005 - Power supply analyzer
1009 - Multimeter kit
Refrigerant gas leak detector
943 - Data Logger
923 - RC-Com MBUS/JBUS Serial board
926 - LON Serial board
931 - BACnet Ethernet - SNMP - TCP/IP Serial board
932 - BACnet MS/TP Serial board
942 - Serial card for GSM Modem
962 - Kit modem GSM
957 - Plantwatch without modem
930 - Remote graphic terminal kit
889 - Master plant SEQUENCER
RC CLOUD PLATFORM
410 T2
VT4
490 T2
VT4
560 T2E
VT5
680 T2
VT6
810 T2E
VT7
740 T3
VT6
820 T3
VT7
153
IT Cooling
STANDARD
1.
2.
3.
4.
5.
(*)
154
dB(A)
dB(A)
kg
410 T2
VT4
402
111,7
358
71,9
92
centrifugal
2
37...100%
8
170360
1
R134a
135
1
400/3/50
316,2
41,2
3,60
5,07
94,8
74,8
3768
490 T2
VT4
510
153,6
392
91,3
144
centrifugal
2
33...100%
8
170360
1
R134a
157
1
400/3/50
316,2
41,2
3,32
5,05
94,8
74,8
4063
560 T2E
VT5
597
177,7
479
107,0
128
centrifugal
2
28...100%
10
212950
1
R134a
164
1
400/3/50
324,4
49,0
3,36
5,15
95,6
75,1
4705
680 T2
VT6
716
219,0
575
128,0
128
centrifugal
2
30...100%
12
255540
1
R134a
229
1
400/3/50
490,1
56,8
3,27
5,35
96,4
75,4
5681
810 T2E
VT7
852
263,0
675
152,0
132
centrifugal
2
26...100%
14
298130
1
R134a
237
1
400/3/50
498,3
61,8
3,24
5,47
97,0
75,6
6341
740 T3
VT6
771
215,4
589
138,0
146
centrifugal
3
25...100%
12
255540
1
R134a
229
1
400/3/50
474,3
64,6
3,58
5,34
96,5
75,5
5866
820 T3
VT7
856
253,3
676
153,0
134
centrifugal
3
23...100%
14
298130
1
R134a
237
1
400/3/50
482,5
69,6
3,38
5,03
97,1
75,7
6471
900 T3
VT8
929
261,0
758
166,0
120
centrifugal
3
22...100%
16
340720
1
R134a
365
1
400/3/50
727,0
77,4
3,56
5,23
97,8
76,1
7602
mm
kW
kW
kW
m/h
kW/kW
dB(A)
dB(A)
kW
kW
kW
m/h
kW/kW
dB(A)
dB(A)
kW
kW
kW
m/h
kW/kW
dB(A)
dB(A)
168,3
402
111,7
358
170360
3,60
93,7
73,7
376
105,9
348
144806
3,55
92,6
72,6
380
109,8
349
119252
3,46
90,9
70,9
168,3
510
153,6
392
170360
3,32
93,7
73,7
484
151,3
385
144806
3,20
92,6
72,6
446
142,0
374
119252
3,14
90,9
70,9
168,3
597
177,7
479
212950
3,36
94,5
74,0
562
172,4
468
181007
3,26
93,4
72,9
520
162,5
454
149065
3,20
91,7
71,2
168,3
716
219,0
575
255540
3,27
95,3
74,3
683
211,5
565
217209
3,23
94,2
73,2
626
195,0
546
178878
3,21
92,5
71,5
168,3
852
263,0
675
298130
3,24
95,9
74,5
805
263,1
661
253410
3,06
94,8
73,4
737
233,2
639
208691
3,16
93,1
71,7
168,3
771
215,4
589
255540
3,58
95,4
74,4
770
227,8
589
217209
3,38
94,3
73,3
713
216,1
574
178878
3,30
92,6
71,6
168,3
856
253,3
676
298130
3,38
96,0
74,6
813
247,9
664
253410
3,28
94,9
73,5
754
233,4
645
208691
3,23
93,2
71,8
168,3
929
261,0
758
340720
3,56
96,7
75,0
883
266,0
744
289612
3,32
95,6
73,9
796
249,5
713
238504
3,19
93,9
72,2
kW
kW
kW
m/h
kPa
n.
%
n.
m/h
n.
kg
n.
V/Ph/Hz
A
A
kW/kW
Referred to glycol solution temperature 15/10C; 20% Ethylene glycol solution; ambient temperature 35C. Fouling factor of the exchangers 0,043 mK/kW.
Referred to glycol solution inlet temperature 15C; 20% Ethylene glycol solution; ambient temperature 3C. Fouling factor of the exchangers 0,043 mK/kW.
Sound power level [Lw] according to ISO EN 9614 2.
Average sound pressure level [LPm] 1m far according to ISO EN 3744.
Hydraulic connection with grooved end, supplied as standard with flexible joint and adapter pipe.
Referred to the entire unit: evaporator + free-cooling system.
IT Cooling
STANDARD
1.
2.
3.
4.
5.
(*)
dB(A)
dB(A)
kg
1200 T3E
VT10
1261
390,4
976
226,0
142
centrifugal
3
18...100%
20
425900
1
R134a
415
1
400/3/50
743,4
82,4
3,23
5,35
98,6
76,2
9056
980 T4
VT8
1021
308,5
784
183,0
144
centrifugal
4
16...100%
16
340720
1
R134a
402
1
400/3/50
632,5
90,2
3,31
5,20
97,8
76,1
7895
1070 T4E
VT9
1125
337,8
876
201,0
138
centrifugal
4
15...100%
18
383310
1
R134a
408
1
400/3/50
640,7
98,0
3,33
5,27
98,2
76,1
8584
1120 T4E
VT10
1194
351,2
958
214,0
128
centrifugal
4
14...100%
20
425900
1
R134a
426
1
400/3/50
648,9
93,0
3,40
5,31
98,6
76,2
9189
1360 T4
VT11
1429
438,3
1084
256,0
150
centrifugal
4
15...100%
22
468490
1
R134a
436
1
400/3/50
972,0
105,8
3,26
5,56
99,1
76,4
10062
1380 T4
VT12
1453
426,1
1155
260,0
130
centrifugal
4
15...100%
24
511080
1
R134a
442
1
400/3/50
980,2
113,6
3,41
5,76
99,5
76,5
10667
1500 T4E
VT12
1548
463,5
1180
277,0
148
centrifugal
4
14...100%
24
511080
1
R134a
441
1
400/3/50
980,2
113,6
3,34
5,60
99,5
76,5
10777
mm
kW
kW
kW
m/h
kW/kW
dB(A)
dB(A)
kW
kW
kW
m/h
kW/kW
dB(A)
dB(A)
kW
kW
kW
m/h
kW/kW
dB(A)
dB(A)
219,1
1261
390,4
976
425900
3,23
97,5
75,1
1189
386,0
956
362015
3,08
96,4
74,0
1082
347,9
923
298130
3,11
94,7
72,3
219,1
1021
308,5
784
340720
3,31
96,7
75,0
966
302,8
769
289612
3,19
95,6
73,9
892
284,1
747
238504
3,14
93,9
72,2
219,1
1125
337,8
876
383310
3,33
97,1
75,0
1064
332,5
859
325813
3,20
96,0
73,9
976
310,8
831
268317
3,14
94,3
72,2
219,1
1194
351,2
958
425900
3,40
97,5
75,1
1122
340,0
936
362015
3,30
96,4
74,0
1037
319,1
907
298130
3,25
94,7
72,3
219,1
1429
438,3
1084
468490
3,26
98,0
75,3
1359
423,4
1066
398216
3,21
96,9
74,2
1243
376,7
1032
327943
3,30
95,2
72,5
219,1
1457
421,1
1156
511080
3,46
98,4
75,4
1378
412,6
1133
434418
3,34
97,3
74,3
1273
381,1
1099
357756
3,34
95,6
72,6
219,1
1548
463,5
1180
511080
3,34
98,4
75,4
1468
454,5
1159
434418
3,23
97,3
74,3
1330
446,3
1118
357756
2,98
95,6
72,6
kW
kW
kW
m/h
kPa
n.
%
n.
m/h
n.
kg
n.
V/Ph/Hz
A
A
kW/kW
Referred to glycol solution temperature 15/10C; 20% Ethylene glycol solution; ambient temperature 35C. Fouling factor of the exchangers 0,043 mK/kW.
Referred to glycol solution inlet temperature 15C; 20% Ethylene glycol solution; ambient temperature 3C. Fouling factor of the exchangers 0,043 mK/kW.
Sound power level [Lw] according to ISO EN 9614 2.
Average sound pressure level [LPm] 1m far according to ISO EN 3744.
Hydraulic connection with grooved end, supplied as standard with flexible joint and adapter pipe.
Referred to the entire unit: evaporator + free-cooling system.
155
IT Cooling
DIMENSIONS (mm)
SIZE VT
VT4
VT5
VT6
VT7
VT8
VT9
VT10
VT11
VT12
156
a
4780
5894
7014
8134
9254
10368
11488
12608
13728
b
2260
2260
2260
2260
2260
2260
2260
2260
2260
c
2304
2304
2304
2304
2304
2304
2304
2304
2304
a
b
H 34ze
HF
HFO1234ze
FREECOOLING
HIGHEFFICIENCY
HI
INVERTER
ACLASS
LOWNOISE
LLOWGWP
GOGREEN
N
solution
MAIN FEATURES
Air cooled liquid chiller with free-cooling system in A class energy
efficiency.
9 models, 2 versions available for a wide selection opportunity.
Average step of 100kW.
EER up to 3,50.
ESEER up to 5,60.
Oil-free centrifugal compressors with magnetic levitation bearings driven
by built-in inverter.
HFO1234ze refrigerant charge, LOW GWP, GWP < 6.
Single refrigerant circuit.
EC Axial fans.
Flooded evaporator.
Microchannel condensing coils in aluminium.
Electronic expansion valve.
Single air circuit.
Modular construction.
Suitable for outdoor installation.
MAIN BENEFITS
Up to four centrifugal compressors with magnetic levitation bearings on
the refrigerant circuit for an high efficiency.
No need of power factor correction.
Minimum starting current (LRA)
Low refrigerant charge.
Very high EER and ESEER. A Class energy efficiency.
Quiet operation.
Availability of double refrigerant circuit version.
Availability of kit for further reduction of the noise.
Microprocessor control system with 7 touch screen display.
19632013 fiftycoolyears RCGROUP SpA G_ITC_RCW8.4
CLASS
INVERTER
OIL
FREE
1234ze
FLOODED
AC
MICRO
FREE
CHANNEL COOLING
f i f t y c o o l y e a r s
157
IT Cooling
FAN SECTION
Axial fans with sickle-shaped blades and fan guard optimized for low noise
levels designed with bionical know how.
Optimized diffusor with static blades.
External rotor EC type electric motor with stepless variable speed for
condensing pressure control.
IP54 enclosure class.
REFRIGERANT CIRCUIT
Components for each refrigerant circuit:
Capacitive level sensor connected to the driver of the expansion valve.
Electronic expansion valve that allows high performance and system
efficiency and for the refrigerant level control in the evaporator.
By-pass valve for start-up.
Electronic by-pass valve for compressor start.
Non return valve on by-pass line for compressor start.
Economizer for models 520 T2E, 620 T2E, 780 T3E, 900 T3E, 1040 T4E,
1200 T4E, 1300 T4E. The system includes:
- Copper brazed plate type with cover plates, plates and connections in
AISI 316 stainless steel.
- Anticondensate insulation made of polyurethane.
- Intermediate electronic expansion valve.
Sight glass.
Filter dryer on liquid line.
Service valve on liquid line.
Service valve on gas suction and discharge.
Non return valve on gas discharge.
Safety valve on low pressure side.
Safety valve on high pressure side.
Pressure transducers with indication, control and protection functions, on
low and high refrigerant pressure.
High pressure safety switch with manual reset.
Refrigerant circuit with copper tubing with anticondensate insulation of the
suction line.
Plastic capillary hoses for pressure sensors connection and cooling line of
the compressor
HFO1234ze refrigerant charge.
ELECTRICAL PANEL
In accordance with EN60204-1 norms, suitable for outdoor installation,
complete with:
Main switch with door lock safety.
Fuses for each compressor.
Magnetothermic switches for fans or water pumps (if scheduled).
Contactors for each load.
Transformer for auxiliary circuit and microprocessor supply.
Panel with machine controls.
Power supply 400/3/50.
CONTROL SYSTEM
Microprocessor system with Touch Screen graphic display for control and
monitor of operating and alarms status. The system includes:
- Voltage free contact for remote general alarm.
- Voltage free contact for external alarm. The inlet is associable with
refrigerant gas leak detector (optional accessory).
- Main components hour-meter.
- Recording of the last 24 occurred alarms.
- Non-volatile Flash memory for data storage.
- Menu with protection password.
FREE-COOLING COIL
Heat exchanger coil with copper tubes and high efficiency aluminium fins,
specifically developed to provide high heat transfer and lower pressure
drops. The combination of two factors, special tubes and fins, allow to
optimally combine the following aspects:
- Maximum capacity relative to the size of the exchanger.
- Reduction of the air flow required for the heat exchange.
Frame in galvanized steel.
Motorized valves for free-cooling water circuit control.
Intermediate free-cooling sensor.
Temperature sensor on ambient air.
158
GOGREEN
solutions
IT Cooling
OPTIONAL ACCESSORIES
UNICO TURBO FLG FREE
SIZE
150 - LNO kit (noise reduction)
Active filters for containment of the harmonic distortion
172 - Rubber support (kit)
79 - Electrical panel heating system
179 - Double refrigerant circuit
350 -Kit TK PRO corrosion resistant painting treatment
351 - Free-cooling coils with pre-painted fins
1003 - Analogic flowmeter
1005 - Power supply analyzer
1009 - Multimeter kit
Refrigerant gas leak detector
943 - Data Logger
923 - RC-Com MBUS/JBUS Serial board
926 - LON Serial board
931 - BACnet Ethernet - SNMP - TCP/IP Serial board
932 - BACnet MS/TP Serial board
942 - Serial card for GSM Modem
962 - Kit modem GSM
957 - Plantwatch without modem
930 - Remote graphic terminal kit
889 - Master plant SEQUENCER
RC CLOUD PLATFORM
400 T2
VT4
520 T2E
VT5
620 T2E
VT6
700 T3
VT7
780 T3E
VT7
900 T3E
VT8
1040 T4E
VT9
1200 T4E
VT11
1300 T4E
VT12
159
IT Cooling
STANDARD
1.
2.
3.
4.
5.
6.
(*)
400 T2
520 T2E
620 T2E
700 T3
780 T3E
900 T3E
1040 T4E
VT4
VT5
VT6
VT7
VT7
VT8
VT9
kW
400
520
620
700
780
900
1040
kW
122,8
146,3
179,5
206,6
221,6
261,6
297,0
kW
497
621
746
870
870
994
1119
m/h
73,5
95,5
113,9
128,6
143,3
165,3
191,1
kPa
66
58
71
54
65
80
76
centrifugal centrifugal centrifugal centrifugal centrifugal centrifugal centrifugal
n.
2
2
2
3
3
3
4
%
15%...100% 14%...100% 14%...100% 10%...100% 10%...100% 10%...100% 7%...100%
n.
8
10
12
14
14
16
18
m/h
190000
237500
285000
332500
332500
380000
427500
n.
1
1
1
1
1
1
1
HFO1234ze HFO1234ze HFO1234ze HFO1234ze HFO1234ze HFO1234ze HFO1234ze
kg
190
216
224
360
360
368
469
n.
1
1
1
1
1
1
1
V/Ph/Hz 400/3/50
400/3/50
400/3/50
400/3/50
400/3/50
400/3/50
400/3/50
A
352
361
370
537
537
546
713
A
40
49
58
67
67
75
84
kW/kW
3,20
3,50
3,39
3,34
3,47
3,38
3,44
4,62
5,07
5,52
4,83
5,12
5,51
5,07
dB(A)
94,8
95,6
96,4
97,1
97,1
97,8
98,2
74,8
75,1
75,4
75,7
75,7
76,1
76,1
dB(A)
3742
4471
5065
6336
6431
7005
8588
kg
168,3
mm
168,3
168,3
168,3
168,3
168,3
219,1
1200 T4E
VT11
1200
342,3
1367
220,4
91
centrifugal
4
7%...100%
22
522500
1
HFO1234ze
485
1
400/3/50
732
102
3,43
5,43
99,1
76,4
9736
1300 T4E
VT12
1260
364,7
1492
231,5
96
centrifugal
4
7%...100%
24
570000
1
HFO1234ze
493
1
400/3/50
741
111
3,38
5,60
99,5
76,5
10310
219,1
219,1
Referred to glycol solution temperature 15/10C; 20% Ethylene glycol solution; ambient temperature 35C. Fouling factor of the exchangers 0,018 mK/kW.
Referred to glycol solution inlet temperature 15C; 20% Ethylene glycol solution; ambient temperature 0C. Fouling factor of the exchangers 0,018 mK/kW.
Sound power level [Lw] according to ISO EN 9614 2.
Average sound pressure level [LPm] 1m far according to ISO EN 3744.
Hydraulic connection with grooved end, supplied as standard with flexible joint and adapter pipe.
Referred to ambient air temperature at 18C.
Referred to the entire unit: evaporator + free-cooling system.
DIMENSIONS (mm)
SIZE VT
VT4
VT5
VT6
VT7
VT8
VT9
VT11
VT12
a
4880
5994
7114
8234
9354
10468
12708
13828
b
2260
2260
2260
2260
2260
2260
2260
2260
c
2370
2370
2370
2370
2370
2370
2370
2370
a
b
160
UNICO TURBO FL
UNICO TURBO FL: Packaged air cooled liquid chillers in A class energy efficiency for outdoor installation, equipped with
oil-free centrifugal compressors with magnetic levitation bearings, flooded evaporator and microchannel condensing coils.
Cooling Capacity: 280 1500 kW
HIGHEFFICIENCY
INVERTER
ACLASS
LOWNOISE
UNICO TURBO FL
rcgroupairconditioning
MAIN FEATURES
Air cooled liquid chiller in A class energy efficiency.
17 models, 2 versions available for a wide selection opportunity.
Average step of 70kW.
EER up to 3,48.
ESEER up to 5,88.
Oil-free centrifugal compressors with magnetic levitation bearings driven
by built-in inverter.
R134a Refrigerant charge.
Single refrigerant circuit.
AC Axial fans.
Flooded evaporator.
Microchannel condensing coils in aluminium.
Electronic expansion valve.
Single air circuit.
Modular construction.
Suitable for outdoor installation.
MAIN BENEFITS
Up to four centrifugal compressors with magnetic levitation bearings on
the refrigerant circuit for an high efficiency.
No need of power factor correction.
Minimum starting current (LRA)
Low refrigerant charge.
Very high EER and ESEER. A Class energy efficiency.
Quiet operation.
Availability of double refrigerant circuit version.
Availability of kit for further reduction of the noise.
Availability of EC fans for a higher efficiency.
Availability of pumping groups.
19632013 fiftycoolyears RCGROUP SpA G_ITC_RCW8.4
CLASS
INVERTER
OIL
FREE
R134a
FLOODED
AC
MICRO
CHANNEL
f i f t y c o o l y e a r s
161
UNICO TURBO FL
COMPONENTS
FRAMEWORK
Base, self supporting frame and panelling in steel plate with protective
surfaces treatment in compliance with UNI ISO 9227/ASTMB117 and ISO
7253, and painted with epoxy powders.
Colour: RAL 9002.
COMPRESSORS
Twin-turbine centrifugal compressor, oil-free type, optimized for R134a
refrigerant.
The term oil-free refers to the total absence of lubricating oil within the
compressor.
Magnetic levitation bearings.
Manometric compression ratio: 1.5 5.0.
Stepless capacity control trough integrated inverter.
High efficiency permanent-magnet synchronous motor with integrated SoftStart system (starting current limited to 5A).
Power factor motor cos > 0.9 for a large part of the operating range.
Motor and electronic power section cooling by liquid refrigerant injection into
the integrated cooling circuit.
Electric motor thermal protection via internal winding temperature sensors.
Electronic integrated control for operation and alarms status.
Sensor on refrigerant discharge for temperature monitoring.
Inner sensors for electronic components and inverter temperature control.
Security system to protect the crankshaft and magnetic bearings in the
event of failure of power supply.
Installation with walls sound attenuators.
Degree of protection: IP54.
Electric resistance of the suction pipe, together with activated antifreeze
evaporator, to prevent the migration of refrigerant inside the compressor.
EVAPORATOR
Flooded shell and tube evaporator, optimized for R134a refrigerant.
Version two passes, characterized by low pressure losses on the water
side.
Water tubes with a helical rifled internal surface.
Integrated liquid drop separator.
Shell, header, tube sheets made of carbon steel, tubes in Cu.
Anticondensate insulation made of polyurethane.
Large liquid level indicator.
Temperature sensors on water inlet and outlet.
Water flow switch for water flow control on water outlet towards the plant,
not installed but supplied in kit.
Large liquid level indicator
Antifreeze heater.
Hydraulic connections with grooved end supplied as standard with flexible
joint and adapter pipe to be welded.
CONDENSING COIL
Microchannel condensing coil in aluminium, perfectly suitable for the civil
and industrial applications cooling, while the protection function of the oxide
layer allows an optimum resistance to corrosion also in case of aggressive
ambient conditions.
Extremely light construction. The coil weight is only 50% compared to
traditional copper pipes and aluminium fins of the same capacity.
Low air side pressure drop and consequentially drastic reduction of the fans
motors electric energy consumption.
High heat exchange efficiency.
Reduced internal volume capable of reducing the total refrigerant charge.
At the same performances conditions, the micro-channels condensers
require up-to less than 75% refrigerant when compared to the traditional
heat exchangers.
Single air circuit.
Frame in painted galvanized steel.
IT Cooling
REFRIGERANT CIRCUIT
Components for each refrigerant circuit:
Capacitive level sensor connected to the driver of the expansion valve.
Electronic expansion valve that allows high performance and system
efficiency and for the refrigerant level control in the evaporator.
By-pass valve for start-up.
Non return valve on by-pass line for compressor start.
Economizer for model 280 T1E, 560 T2E, 810 T2E, 1070 T4E, 1120 T4E,
1200 T3E, 1500 T4E. The system includes:
- Copper brazed plate type with cover plates, plates and connections in
AISI 316 stainless steel.
- Anticondensate insulation made of polyurethane.
- Intermediate electronic expansion valve.
Sight glass.
Filter dryer on liquid line.
Service valve on liquid line.
Service valve on gas suction and discharge.
Non return valve on gas discharge.
Safety valve on low pressure side.
Safety valve on high pressure side.
Pressure transducers with indication, control and protection functions, on
low and high refrigerant pressure.
High pressure safety switch with manual reset.
Refrigerant circuit with copper tubing with anticondensate insulation of the
suction line.
Plastic capillary hoses for pressure sensors connection and cooling line of
the compressor
R134a refrigerant charge.
ELECTRICAL PANEL
In accordance with EN60204-1 norms, suitable for outdoor installation,
complete with:
Main switch with door lock safety.
Fuses for each compressor.
Magnetothermic switches for fans or water pumps (if scheduled).
Contactors for each load.
Transformer for auxiliary circuit and microprocessor supply.
Panel with machine controls.
Power supply 400/3/50.
CONTROL SYSTEM
Microprocessor system with Touch Screen graphic display for control
and monitor of operating and alarms status. The system includes:
- Voltage free contact for remote general alarm.
- Voltage free contact for external alarm. The inlet is associable with
refrigerant gas leak detector (optional accessory).
- Main components hour-meter.
- Recording of the last 24 occurred alarms.
- Non-volatile Flash memory for data storage.
- Menu with protection password.
FANS SECTION
Axial fans with sickle-shaped blades, fan guard and optimized for low noise
levels.
External rotor AC type electric motor with stepless variable speed for
condensing pressure control.
IP54 enclosure class.
162
UNICO TURBO FL
IT Cooling
OPTIONAL ACCESSORIES
UNICO TURBO FL
SIZE
739 - Pumping group (1 pump)
769 - Pumping group (1+1stby)
740 - Pumping group (2 pumps)
770 - Pumping group (2+1stby)
756 - Pumping group LN (1 pump)
771 - Pumping group LN (1+1stby)
757 - Pumping group LN (2 pumps)
772 - Pumping group LN (2+1stby)
150 - LNO kit (noise reduction)
Active filters for containment of the harmonic distortion
172 - Rubber support (kit)
Condenser partialization system
79 - Electrical panel heating system
179 - Double refrigerant circuit
101 - EC fan
350 -Kit TK PRO corrosion resistant painting treatment
1003 - Analogic flowmeter
1005 - Power supply analyzer
1009 - Multimeter kit
Refrigerant gas leak detector
943 - Data Logger
923 - RC-Com MBUS/JBUS Serial board
926 - LON Serial board
931 - BACnet Ethernet - SNMP - TCP/IP Serial board
932 - BACnet MS/TP Serial board
942 - Serial card for GSM Modem
962 - Kit modem GSM
957 - Plantwatch without modem
930 - Remote graphic terminal kit
889 - Master plant SEQUENCER
RC CLOUD PLATFORM
280 T1E
VT3
340 T1
VT3
410 T2
VT4
490 T2
VT4
560 T2E
VT5
680 T2
VT6
UNICO TURBO FL
SIZE
739 - Pumping group (1 pump)
769 - Pumping group (1+1stby)
740 - Pumping group (2 pumps)
770 - Pumping group (2+1stby)
756 - Pumping group LN (1 pump)
771 - Pumping group LN (1+1stby)
757 - Pumping group LN (2 pumps)
772 - Pumping group LN (2+1stby)
150 - LNO kit (noise reduction)
Active filters for containment of the harmonic distortion
172 - Rubber support (kit)
Condenser partialization system
79 - Electrical panel heating system
179 - Double refrigerant circuit
101 - EC fan
350 -Kit TK PRO corrosion resistant painting treatment
1003 - Analogic flowmeter
1005 - Power supply analyzer
1009 - Multimeter kit
Refrigerant gas leak detector
943 - Data Logger
923 - RC-Com MBUS/JBUS Serial board
926 - LON Serial board
931 - BACnet Ethernet - SNMP - TCP/IP Serial board
932 - BACnet MS/TP Serial board
942 - Serial card for GSM Modem
962 - Kit modem GSM
957 - Plantwatch without modem
930 - Remote graphic terminal kit
889 - Master plant SEQUENCER
RC CLOUD PLATFORM
810 T2E
VT7
740 T3
VT6
820 T3
VT7
163
UNICO TURBO FL
IT Cooling
OPT
STANDARD
1.
2.
3.
4.
164
UNICO TURBO FL
SIZE
Cooling capacity (1)
Unit power input
Evaporator water flow rate
Evaporator pressure drop
Compressors
Quantity
Cooling capacity control
Axial fans
Total air flow
Air circuits
Refrigerant
Total refrigerant charge (optional excluded)
Gas circuits
Power supply
Max unit operating current (FLA)
Unit starting current (LRA)
EER (1)
ESEER
Sound power level [Lw] (2)
Average sound pressure level [LPm] (3)
Net weight
Hydraulic connections
Evaporator IN/OUT - OD (4)
Pumping group
2 poles motor - Power input
4 poles motor - Power input
Cooling capacity (1)
Unit power input
Total air flow
EER (1)
Sound power level [Lw] (2)
Average sound pressure level [LPm] (3)
Cooling capacity (1)
Unit power input
Total air flow
EER (1)
Sound power level [Lw] (2)
Average sound pressure level [LPm] (3)
Cooling capacity (1)
Unit power input
Total air flow
EER (1)
Sound power level [Lw] (2)
Average sound pressure level [LPm] (3)
dB(A)
dB(A)
kg
280 T1E
VT3
280
81,2
48,2
25
centrifugal
1
55...100%
6
145500
1
R134a
143
1
400/3/50
166,3
28,4
3,45
4,95
93,3
73,8
2559
340 T1
VT3
340
99,7
58,5
24
centrifugal
1
60...100%
6
145500
1
R134a
129
1
400/3/50
245,1
28,4
3,41
5,38
93,4
73,9
2626
410 T2
VT4
410
121,3
70,5
34
centrifugal
2
37...100%
8
194000
1
R134a
135
1
400/3/50
316,3
41,2
3,38
5,10
94,8
74,8
3378
490 T2
VT4
490
152,2
84,3
25
centrifugal
2
33...100%
8
194000
1
R134a
157
1
400/3/50
316,3
41,2
3,22
5,32
94,8
74,8
3658
560 T2E
VT5
560
171,3
96,3
31
centrifugal
2
28...100%
10
242500
1
R134a
164
1
400/3/50
324,5
49,0
3,27
5,39
95,6
75,1
4203
680 T2
VT6
680
204,2
117,0
22
centrifugal
2
30...100%
12
291000
1
R134a
229
1
400/3/50
490,1
56,8
3,33
5,29
96,4
75,4
5056
810 T2E
VT7
810
252,3
139,0
31
centrifugal
2
26...100%
14
339500
1
R134a
237
1
400/3/50
498,3
64,6
3,21
5,51
97,0
75,6
5614
740 T3
VT6
740
212,6
127,0
25
centrifugal
3
25...100%
12
291000
1
R134a
229
1
400/3/50
474,4
61,8
3,48
5,88
96,5
75,5
5241
mm
114,3
114,3
168,3
168,3
168,3
168,3
168,3
168,3
kW
kW
kW
kW
m/h
kW/kW
dB(A)
dB(A)
kW
kW
m/h
kW/kW
dB(A)
dB(A)
kW
kW
m/h
kW/kW
dB(A)
dB(A)
--280
81,2
145500
3,45
92,2
72,7
268
74,0
123675
3,62
91,1
71,6
253
66,6
101850
3,80
89,4
69,9
--340
99,7
145500
3,41
92,3
72,8
324
90,3
123675
3,59
91,2
71,7
300
80,9
101850
3,71
89,5
70,0
5,5
5,5
410
121,3
194000
3,38
93,7
73,7
380
118,4
164900
3,21
92,6
72,6
368
110,5
135800
3,33
90,9
70,9
5,5
5,5
490
152,2
194000
3,22
93,7
73,7
465
139,6
164900
3,33
92,6
72,6
432
125,2
135800
3,45
90,9
70,9
5,5
5,5
560
171,3
242500
3,27
94,5
74,0
532
156,0
206125
3,41
93,4
72,9
495
140,2
169750
3,53
91,7
71,2
11,0
5,5
680
204,2
291000
3,33
95,3
74,3
650
186,8
247350
3,48
94,2
73,2
600
166,2
203700
3,61
92,5
71,5
11,0
11,0
810
252,3
339500
3,21
95,9
74,5
765
228,4
288575
3,35
94,8
73,4
708
203,4
237650
3,48
93,1
71,7
11,0
11,0
740
212,6
291000
3,48
95,4
74,4
740
204,4
247350
3,62
94,3
73,3
690
184,5
203700
3,74
92,6
71,6
kW
kW
m/h
kPa
n.
%
n.
m/h
n.
kg
n.
V/Ph/Hz
A
A
kW/kW
Referred to chilled water temperature 12/7C 0% glycol solution; air temperature to the condenser 35C. Fouling factor of the exchangers 0,043 mK/kW.
Sound power level [Lw] according to ISO EN 9614 2.
Average sound pressure level [LPm] 1m far according to ISO EN 3744.
Hydraulic connection with grooved end, supplied as standard with flexible joint and adapter pipe.
UNICO TURBO FL
IT Cooling
OPT
STANDARD
1.
2.
3.
4.
UNICO TURBO FL
SIZE
Cooling capacity (1)
Unit power input
Evaporator water flow rate
Evaporator pressure drop
Compressors
Quantity
Cooling capacity control
Axial fans
Total air flow
Air circuits
Refrigerant
Total refrigerant charge (optional excluded)
Gas circuits
Power supply
Max unit operating current (FLA)
Unit starting current (LRA)
EER (1)
ESEER
Sound power level [Lw] (2)
Average sound pressure level [LPm] (3)
Net weight
Hydraulic connections
Evaporator IN/OUT - OD (4)
Pumping group
2 poles motor - Power input
4 poles motor - Power input
Cooling capacity (1)
Unit power input
Total air flow
EER (1)
Sound power level [Lw] (2)
Average sound pressure level [LPm] (3)
Cooling capacity (1)
Unit power input
Total air flow
EER (1)
Sound power level [Lw] (2)
Average sound pressure level [LPm] (3)
Cooling capacity (1)
Unit power input
Total air flow
EER (1)
Sound power level [Lw] (2)
Average sound pressure level [LPm] (3)
dB(A)
dB(A)
kg
820 T3
VT7
820
250,8
141,0
32
centrifugal
3
23...100%
14
339500
1
R134a
237
1
400/3/50
482,6
69,6
3,27
5,17
97,1
75,7
5743
900 T3
VT8
900
262,4
155,0
37
centrifugal
3
22...100%
16
388000
1
R134a
365
1
400/3/50
727,0
77,4
3,43
5,62
97,8
76,1
6772
1200 T3E
VT10
1200
376,2
206,0
38
centrifugal
3
18...100%
20
485000
1
R134a
415
1
400/3/50
743,4
93,0
3,19
5,65
98,6
76,2
8021
980 T4
VT8
980
305,3
169,0
26
centrifugal
4
16...100%
16
388000
1
R134a
402
1
400/3/50
632,5
82,4
3,21
5,41
97,8
76,1
7065
1070 T4E
VT9
1070
329,2
184,0
31
centrifugal
4
15...100%
18
436500
1
R134a
408
1
400/3/50
640,7
90,2
3,25
5,32
98,2
76,1
7652
1120 T4E
VT10
1120
341,5
193,0
34
centrifugal
4
14...100%
20
485000
1
R134a
426
1
400/3/50
648,9
98,0
3,28
5,39
98,6
76,2
8154
1360 T4
VT11
1360
415,9
234,0
37
centrifugal
4
15...100%
22
533500
1
R134a
436
1
400/3/50
972,1
105,8
3,27
5,29
99,1
76,4
8925
1380 T4
VT12
1380
408,3
237,0
38
centrifugal
4
15...100%
24
582000
1
R134a
442
1
400/3/50
980,3
113,6
3,38
5,56
99,5
76,5
9427
1500 T4E
VT12
1500
461,5
258,0
44
centrifugal
4
14...100%
24
582000
1
R134a
441
1
400/3/50
980,3
113,6
3,25
5,58
99,5
76,5
9537
mm
168,3
168,3
219,1
219,1
219,1
219,1
219,1
219,1
219,1
kW
kW
kW
kW
m/h
kW/kW
dB(A)
dB(A)
kW
kW
m/h
kW/kW
dB(A)
dB(A)
kW
kW
m/h
kW/kW
dB(A)
dB(A)
11,0
11,0
820
250,8
339500
3,27
96,0
74,6
780
229,4
288575
3,40
94,9
73,5
727
206,5
237650
3,52
93,2
71,8
11,0
11,0
900
262,4
388000
3,43
96,7
75,0
848
238,9
329800
3,55
95,6
73,9
766
213,4
271600
3,59
93,9
72,2
22,0
15,0
1200
376,2
485000
3,19
97,5
75,1
1133
340,2
412250
3,33
96,4
74,0
1041
301,7
339500
3,45
94,7
72,3
11,0
11,0
980
305,3
388000
3,21
96,7
75,0
929
279,8
329800
3,32
95,6
73,9
863
250,9
271600
3,44
93,9
72,2
22,0
11,0
1070
329,2
436500
3,25
97,1
75,0
1010
299,7
371025
3,37
96,0
73,9
932
267,0
305550
3,49
94,3
72,2
22,0
15,0
1120
341,5
485000
3,28
97,5
75,1
1062
311,4
412250
3,41
96,4
74,0
987
278,8
339500
3,54
94,7
72,3
22,0
15,0
1360
415,9
533500
3,27
98,0
75,3
1295
377,6
453475
3,43
96,9
74,2
1196
335,0
373450
3,57
95,2
72,5
22,0
15,0
1380
408,3
582000
3,38
98,4
75,4
1311
370,3
494700
3,54
97,3
74,3
1214
329,9
407400
3,68
95,6
72,6
22,0
15,0
1500
461,5
582000
3,25
98,4
75,4
1404
419,1
494700
3,35
97,3
74,3
1279
370,7
407400
3,45
95,6
72,6
kW
kW
m/h
kPa
n.
%
n.
m/h
n.
kg
n.
V/Ph/Hz
A
A
kW/kW
Referred to chilled water temperature 12/7C 0% glycol solution; air temperature to the condenser 35C. Fouling factor of the exchangers 0,043 mK/kW.
Sound power level [Lw] according to ISO EN 9614 2.
Average sound pressure level [LPm] 1m far according to ISO EN 3744.
Hydraulic connection with grooved end, supplied as standard with flexible joint and adapter pipe.
165
UNICO TURBO FL
IT Cooling
DIMENSIONS (mm)
SIZE VT
VT3
VT4
VT5
VT6
VT7
VT8
VT9
VT10
VT11
VT12
166
a
3530
4650
5770
6890
8010
9130
10250
11370
12490
13610
b
2260
2260
2260
2260
2260
2260
2260
2260
2260
2260
c
2304
2304
2304
2304
2304
2304
2304
2304
2304
2304
a
b
H
HF
HFO1234ze
e
HHIGHEFFICIENCY
INVERTER
ACLASS
LOWNOISE
LOWGWP
GOGREEN
solutions
MAIN FEATURES
Air cooled liquid chiller in A class energy efficiency.
11 models available, for a wide selection opportunity.
Average step of 100kW.
EER up to 3,36.
ESEER up to 5,94.
Oil-free centrifugal compressors with magnetic levitation bearings driven
by built-in inverter.
HFO1234ze refrigerant charge, LOW GWP, GWP < 6.
Single refrigerant circuit.
EC Axial fans with optimized diffusor.
Flooded evaporator.
Microchannel condensing coils in aluminium.
Electronic expansion valve.
Single air circuit.
Modular construction.
Suitable for outdoor installation.
MAIN BENEFITS
Up to four centrifugal compressors with magnetic levitation bearings on
the refrigerant circuit for an high efficiency.
No need of power factor correction.
Minimum starting current (LRA)
Low refrigerant charge.
Very high EER and ESEER. A Class energy efficiency.
Quiet operation.
Availability of double refrigerant circuit version.
Availability of kit for further reduction of the noise.
Availability of pumping groups.
19632013 fiftycoolyears RCGROUP SpA G_ITC_RCW8.4
CLASS
INVERTER
OIL
FREE
1234ze
FLOODED
AC
MICRO
CHANNEL
f i f t y c o o l y e a r s
167
GOGREEN
solutions
COMPONENTS
FRAMEWORK
Base, self supporting frame and panelling in steel plate with protective
surfaces treatment in compliance with UNI ISO 9227/ASTMB117 and ISO
7253, and painted with epoxy powders.
Colour: RAL 9002.
COMPRESSORS
Twin-turbine centrifugal compressor, oil-free type, optimized for HFO1234ze
refrigerant.
The term oil-free refers to the total absence of lubricating oil within the
compressor.
Magnetic levitation bearings.
Manometric compression ratio: 1.5 5.0.
Stepless capacity control trough integrated inverter.
High efficiency permanent-magnet synchronous motor with integrated SoftStart system (starting current limited to 5A).
Power factor motor cos > 0.9 for a large part of the operating range.
Motor and electronic power section cooling by liquid refrigerant injection into
the integrated cooling circuit.
Electric motor thermal protection via internal winding temperature sensors.
Electronic integrated control for operation and alarms status.
Sensor on refrigerant discharge for temperature monitoring.
Inner sensors for electronic components and inverter temperature control.
Security system to protect the crankshaft and magnetic bearings in the
event of failure of power supply.
Installation with walls sound attenuators.
Degree of protection: IP54.
Electric resistance of the suction pipe, together with activated antifreeze
evaporator, to prevent the migration of refrigerant inside the compressor.
EVAPORATOR
Flooded shell and tube evaporator, optimized for HFO1234ze refrigerant.
Version two passes, characterized by low pressure losses on the water
side.
Water tubes with a helical rifled internal surface.
Integrated liquid drop separator.
Shell, header, tube sheets made of carbon steel, tubes in Cu.
Anticondensate insulation made of polyurethane.
Large liquid level indicator.
Temperature sensors on water inlet and outlet.
Water flow switch for water flow control on water outlet towards the plant,
not installed but supplied in kit.
Large liquid level indicator
Antifreeze heater.
Hydraulic connections with grooved end supplied as standard with flexible
joint and adapter pipe to be welded.
CONDENSING COIL
Microchannel condensing coil in aluminium, perfectly suitable for the civil
and industrial applications cooling, while the protection function of the oxide
layer allows an optimum resistance to corrosion also in case of aggressive
ambient conditions.
Extremely light construction. The coil weight is only 50% compared to
traditional copper pipes and aluminium fins of the same capacity.
Low air side pressure drop and consequentially drastic reduction of the fans
motors electric energy consumption.
High heat exchange efficiency.
Reduced internal volume capable of reducing the total refrigerant charge.
At the same performances conditions, the micro-channels condensers
require up-to less than 75% refrigerant when compared to the traditional
heat exchangers.
Single air circuit.
Frame in painted galvanized steel.
IT Cooling
REFRIGERANT CIRCUIT
Components for each refrigerant circuit:
Capacitive level sensor connected to the driver of the expansion valve.
Electronic expansion valve that allows high performance and system
efficiency and for the refrigerant level control in the evaporator.
By-pass valve for start-up.
Non return valve on by-pass line for compressor start.
Economizer for model 310 T1E, 520 T2E, 620 T2E, 780 T3E, 900 T3E,
1040 T4E, 1300 T4E. The system includes:
- Copper brazed plate type with cover plates, plates and connections in
AISI 316 stainless steel.
- Anticondensate insulation made of polyurethane.
- Intermediate electronic expansion valve.
Sight glass.
Filter dryer on liquid line.
Service valve on liquid line.
Service valve on gas suction and discharge.
Non return valve on gas discharge.
Safety valve on low pressure side.
Safety valve on high pressure side.
Pressure transducers with indication, control and protection functions, on
low and high refrigerant pressure.
High pressure safety switch with manual reset.
Refrigerant circuit with copper tubing with anticondensate insulation of the
suction line.
Plastic capillary hoses for pressure sensors connection and cooling line of
the compressor
HFO 1234ze refrigerant charge.
ELECTRICAL PANEL
In accordance with EN60204-1 norms, suitable for outdoor installation,
complete with:
Main switch with door lock safety.
Fuses for each compressor.
Magnetothermic switches for fans or water pumps (if scheduled).
Contactors for each load.
Transformer for auxiliary circuit and microprocessor supply.
Panel with machine controls.
Power supply 400/3/50.
CONTROL SYSTEM
Microprocessor system with Touch Screen graphic display for control
and monitor of operating and alarms status. The system includes:
- Voltage free contact for remote general alarm.
- Voltage free contact for external alarm. The inlet is associable with
refrigerant gas leak detector (optional accessory).
- Main components hour-meter.
- Recording of the last 24 occurred alarms.
- Non-volatile Flash memory for data storage.
- Menu with protection password.
FANS SECTION
Axial fans with sickle-shaped blades and fan guard optimized for low noise
levels designed with bionical know how.
Optimized diffusor with static blades.
External rotor EC type electric motor with stepless variable speed for
condensing pressure control.
IP54 enclosure class.
168
GOGREEN
solutions
IT Cooling
OPTIONAL ACCESSORIES
UNICO TURBO FLG
SIZE
739 - Pumping group (1 pump)
769 - Pumping group (1+1stby)
740 - Pumping group (2 pumps)
770 - Pumping group (2+1stby)
756 - Pumping group LN (1 pump)
771 - Pumping group LN (1+1stby)
757 - Pumping group LN (2 pumps)
772 - Pumping group LN (2+1stby)
150 - LNO kit (noise reduction)
Active filters for containment of the harmonic distortion
172 - Rubber support (kit)
Condenser partialization system
79 - Electrical panel heating system
179 - Double refrigerant circuit
350 -Kit TK PRO corrosion resistant painting treatment
1003 - Analogic flowmeter
1005 - Power supply analyzer
1009 - Multimeter kit
Refrigerant gas leak detector
943 - Data Logger
923 - RC-Com MBUS/JBUS Serial board
926 - LON Serial board
931 - BACnet Ethernet - SNMP - TCP/IP Serial board
932 - BACnet MS/TP Serial board
942 - Serial card for GSM Modem
962 - Kit modem GSM
957 - Plantwatch without modem
930 - Remote graphic terminal kit
889 - Master plant SEQUENCER
RC CLOUD PLATFORM
260 T1
VT2
310 T1E
VT3
400 T2
VT4
700 T3
VT7
780 T3E 900 T3E 1040 T4E 1200 T4E 1300 T4E
VT7
VT8
VT10
VT11
VT12
169
GOGREEN
solutions
IT Cooling
1040 T4E
VT9
kW
1040
kW
317,5
m/h
178,9
kPa
39,0
centrifugal
n.
4
%
7%...100%
n.
18
m/h
469800
n.
1
HFO1234ze
kg
469
n.
1
V/Ph/Hz 400/3/50
A
713,2
A
84,2
kW/kW
3,24
5,14
dB(A)
98,2
dB(A)
76,1
kg
7304
OPT
STANDARD
OPT
STANDARD
1.
2.
3.
4.
5.
mm
kW
kW
310 T1E
VT3
310
96,9
53,3
36,8
centrifugal
1
29%...100%
6
156600
1
HFO1234ze
191
1
400/3/50
185,2
31,4
3,16
5,47
93,4
73,9
2382
400 T2
VT4
400
124,9
68,8
37,0
centrifugal
2
15%...100%
8
208800
1
HFO1234ze
190
1
400/3/50
352,0
40,2
3,16
4,89
94,8
74,8
3182
520 T2E
VT5
520
153,3
89,4
28,5
centrifugal
2
14%...100%
10
261000
1
HFO1234ze
216
1
400/3/50
361,2
49,0
3,36
5,27
95,6
75,1
3773
620 T2E
VT6
620
194,1
106,6
40,5
centrifugal
2
14%...100%
12
313200
1
HFO1234ze
224
1
400/3/50
370,4
57,8
3,15
5,69
96,4
75,4
4206
700 T3
VT7
700
218,5
120,4
25,7
centrifugal
3
10%...100%
14
365400
1
HFO1234ze
360
1
400/3/50
537,2
66,6
3,18
5,08
97,1
75,7
5335
780 T3E
VT7
780
235,4
134,2
31,9
centrifugal
3
10%...100%
14
365400
1
HFO1234ze
360
1
400/3/50
537,2
66,6
3,28
5,16
97,1
75,7
5430
900 T3E
VT8
900
280,8
154,8
42,5
centrifugal
3
10%...100%
16
417600
1
HFO1234ze
368
1
400/3/50
546,4
75,4
3,16
5,77
97,8
76,1
5863
114,3
114,3
168,3
168,3
168,3
168,3
168,3
168,3
5,5
5,5
5,5
5,5
11,0
11,0
11,0
11,0
11,0
11,0
11,0
11,0
1200 T4E
VT11
1200
369,6
206,4
51,9
centrifugal
4
7%...100%
22
574200
1
HFO1234ze
485
1
400/3/50
731,6
101,8
3,20
5,60
99,1
76,4
8169
1300 T4E
VT12
1260
394,9
216,7
57,2
centrifugal
4
7%...100%
24
626400
1
HFO1234ze
493
1
400/3/50
740,9
110,6
3,14
5,94
99,5
76,5
8601
mm
219,1
219,1
219,1
kW
kW
22,0
11,0
22,0
15,0
22,0
15,0
Referred to chilled water temperature 12/7C 0% glycol solution; air temperature to the condenser 35C. Fouling factor of the exchangers 0,018 mK/kW.
Sound power level [Lw] according to ISO EN 9614 2.
Average sound pressure level [LPm] 1m far according to ISO EN 3744.
Hydraulic connection with grooved end, supplied as standard with flexible joint and adapter pipe.
Referred to ambient air temperature at 18C.
DIMENSIONS (mm)
SIZE VT
VT3
VT4
VT5
VT6
VT7
VT8
VT10
VT11
VT12
170
a
3760
4880
5994
7114
8234
9354
10468
12708
13828
b
2260
2260
2260
2260
2260
2260
2260
2260
2260
c
2370
2370
2370
2370
2370
2370
2370
2370
2370
a
b
FRIGO TURBO FL
FRIGO TURBO FL: Packaged water cooled liquid chillers in A class energy efficiency
for indoor installation, equipped with oil-free centrifugal compressors with magnetic levitation bearings,
flooded evaporator and shell and tube condenser.
Cooling Capacity: 280 1840 kW
HIGHEFFICIENCY
INVERTER
ACLASS
LOWNOISE
FRIGO TURBO FL
rcgroupairconditioning
MAIN FEATURES
Water cooled liquid chiller in A class energy efficiency.
11 models, 2 versions available, for a wide selection opportunity.
Average step of 150kW.
EER up to 5,23.
ESEER up to 8,88.
Oil-free centrifugal compressors with magnetic levitation bearings.
Inverter driven.
R134a Refrigerant charge.
Single refrigerant circuit.
Electronic expansion valve.
Shell and tube condenser.
Flooded evaporator.
Suitable for indoor installation.
MAIN BENEFITS
Up to four centrifugal compressors with magnetic levitation bearings on
the refrigerant circuit for an high efficiency.
No need of power factor correction.
Minimum starting current (LRA)
High EER and ESEER. A Class energy efficiency.
Quiet operation.
Microprocessor control system with 7 touch screen display.
Version with 4-passes condenser for a higher energy efficiency.
Extremely easily of maintenance.
Complete set of components dedicated to the safety of the unity.
Eurovent Certification.
OIL
FREE
INVERTER
CLASS
R134a
FLOODED
INDOOR INSTALLATION
The machines are designed for indoor installation.
MAGNETIC LEVITATION CENTRIFUGAL COMPRESSOR
The TURBO FL liquid chillers are equipped with two-stage centrifugal
compressor with variable speed, which is able to follow punctually plant
demands, obtaining values of energy efficiency ratio (EER) growing in
a narrowing of the cooling load. The compressors of the TURBO FL
liquid chillers are equipped with magnetic levitation oil-free bearings
which compared to traditional ball bearings, completely eliminate all the
maintenance procedures of lubrication.
A CLASS ENERGY EFFICIENCY
The best and most accurate components applied to the chillers.
WORKING LIMITS IN COOLING MODE
Chilled water outlet temperature: 418C
Condenser outlet water temperature: 2052C
f i f t y c o o l y e a r s
171
FRIGO TURBO FL
COMPONENTS
FRAMEWORK
Base and self supporting frame in steel plate with protective surfaces
treatment in compliance with UNI ISO 9227/ASTMB117 and ISO 7253, and
painted with epoxy powders.
Colour: RAL 9002
COMPRESSORS
Twin-turbine centrifugal compressor, oil-free type, optimized for R134a
refrigerant.
The term oil-free refers to the total absence of lubricating oil within the
compressor.
Magnetic levitation bearings.
Manometric compression ratio: 1.5 5.0
Stepless capacity control trough integrated inverter.
High efficiency permanent-magnet synchronous motor with integrated SoftStart system (starting current limited to 5A).
Power factor motor cos > 0.9 for a large part of the operating range
Motor and electronic power section cooling by liquid refrigerant injection into
the integrated cooling circuit.
Electric motor thermal protection via internal winding temperature sensors.
Electronic integrated control for operation and alarms status.
Sensor on refrigerant discharge for temperature monitoring.
Inner sensors for electronic components and inverter temperature control.
Security system to protect the crankshaft and magnetic bearings in the
event of failure of power supply.
Degree of protection: IP54.
IT Cooling
ELECTRICALPANEL
In accordance with EN60204-1 norms, suitable for indoor installation,
complete with:
Main switch with door lock safety.
Fuses for compressors.
Contactors for compressors.
Transformer for auxiliary circuit and microprocessor supply.
Panel with machine controls.
Power supply 400/3/50.
CONTROL SYSTEM
Microprocessor system with Touch Screen graphic display for control and
monitor of operating and alarms status. The system includes:
- Voltage free contact for remote general alarm.
- Voltage free contact for external alarm. The inlet is associable with
refrigerant gas leak detector (optional accessory).
- Main components hour-meter.
- Recording of the last 24 occurred alarms.
- Non-volatile Flash memory for data storage.
- Menu with protection password.
EVAPORATOR
Flooded shell and tube evaporator, optimized for R134a refrigerant.
Version two passes, characterized by low pressure losses on the water
side.
Water tubes with a helical rifled internal surface.
Integrated liquid drop separator.
Shell, header, tube sheets made of carbon steel, tubes in Cu.
Anticondensate insulation made of polyurethane.
Large liquid level indicator.
Temperature sensors on water inlet and outlet.
Water flow switch for water flow control on water outlet towards the plant,
not installed but supplied in kit.
Hydraulic connections with grooved end supplied as standard with flexible
joint and adapter pipe to be welded.
CONDENSER
Shell and tube 2-passes condenser optimized for R134a refrigerant.
- Machine type P4: 4-passes condenser.
Shell, header, tube sheets made of carbon steel, tubes in Cu.
Temperature sensors on condenser water inlet and outlet.
Hydraulic connections with grooved end supplied as standard with flexible
joint and adapter pipe to be welded.
From model 280 T1 to model 560 T2 included the connections are supplied
in mounting kit. Installation to be made by the customer.
REFRIGERANT CIRCUIT
Components for each refrigerant circuit:
Capacitive level sensor connected to the driver of the expansion valve.
Electronic expansion valve that allows high performance and system
efficiency and for the refrigerant level control in the evaporator.
Electronic by-pass valve for compressor start.
Non return valve on by-pass line for compressor start.
Sight glass.
Filter dryer on liquid line.
Service valve on liquid line.
Service valve on gas suction and discharge.
Non return valve on gas suction.
Safety valve on low pressure side.
Safety valve on high pressure side.
Pressure transducers with indication, control and protection functions, on
low and high refrigerant pressure.
High pressure safety switch with manual reset.
Refrigerant circuit with copper tubing with anticondensate insulation of the
suction line.
Plastic capillary hoses for pressure sensors connection.
R134a refrigerant charge.
172
FRIGO TURBO FL
IT Cooling
OPTIONAL ACCESSORIES
FRIGO TURBO FL
172 - Rubber support (kit)
611 - Noise absorption cap
Service valve on compressor group suction
1003 - Analogic flowmeter
1005 - Power supply analyzer
1009 - Multimeter kit
Refrigerant gas leak detector
943 - Data Logger
923 - RC-Com MBUS/JBUS Serial board
926 - LON Serial board
931 - BACnet Ethernet - SNMP - TCP/IP Serial board
932 - BACnet MS/TP Serial board
942 - Serial card for GSM Modem
962 - Kit modem GSM
957 - Plantwatch without modem
930 - Remote graphic terminal kit
889 - Master plant SEQUENCER
RC CLOUD PLATFORM
280 T1
380 T1
460 T1
560 T2
760 T2
840 T3
STANDARD
STANDARD
1.
2.
3.
4.
(*)
(**)
FRIGO TURBO FL
Cooling capacity (1)
Unit power input
Evaporator water flow rate
Evaporator pressure drop
Condenser water flow rate
Condenser pressure drop
Compressors
Quantity
Capacity control (**)
Refrigerant
Total refrigerant charge (optional excluded)
Gas circuits
Power supply
Max unit operating current (FLA)
Unit starting current (LRA)
EER (1)
ESEER
Sound power level [Lw] (2)
Average sound pressure level [Lpm] (3)
Net weight
Hydraulic connections
Evaporator IN/OUT - OD (4)
Condenser IN/OUT - OD (4)
FRIGO TURBO FL
Cooling capacity (1)
Unit power input
Evaporator water flow rate
Evaporator pressure drop
Condenser water flow rate
Condenser pressure drop
Compressors
Quantity
Capacity control (**)
Refrigerant
Total refrigerant charge (optional excluded)
Gas circuits
Power supply
Max unit operating current (FLA)
Unit starting current (LRA)
EER (1)
ESEER
Sound power level [Lw] (2)
Average sound pressure level [Lpm] (3)
Net weight
Hydraulic connections
Evaporator IN/OUT - OD (4)
Condenser IN/OUT - OD (4)
dB(A)
dB(A)
kg
280 T1
280
55,4
48,2
32
57,5
13
centrifugal
1
25100%
R134a
108
1
400/3/50
141,7
5
5,05
8,45
87,5
69,5
1800
380 T1
380
75,2
65,4
29
78,0
22
centrifugal
1
25100%
R134a
95
1
400/3/50
220,5
5
5,05
8,46
87,9
69,9
1871
460 T1
460
90,7
79,1
27
94,3
21
centrifugal
1
27100%
R134a
105
1
400/3/50
178,5
5
5,07
8,63
89,7
71,7
2111
560 T2
560
110,9
96,3
31
115,0
26
centrifugal
2
12100%
R134a
162
1
400/3/50
283,5
10
5,05
8,70
89,7
71,5
2573
760 T2
760
149,3
131,0
27
156,0
20
centrifugal
2
12100%
R134a
230
1
400/3/50
441,0
10
5,09
8,88
89,9
71,7
2939
840 T3
840
166,3
144,0
32
172,0
39
centrifugal
3
8100%
R134a
270
1
400/3/50
425,2
15
5,05
8,53
90,7
71,6
3771
920 T2
920
178,6
158,0
57
188,0
33
centrifugal
2
13100%
R134a
250
1
400/3/50
357,0
15
5,15
8,59
91,8
73,1
3077
1140 T3
1140
218,0
196,0
35
232,0
40
centrifugal
3
8100%
R134a
380
1
400/3/50
661,5
15
5,23
8,72
91,6
72,5
4628
mm
mm
114,3
139,7
114,3
139,7
168,3
139,7
168,3
139,7
168,3
168,3
168,3
168,3
168,3
168,3
219,1
168,3
dB(A)
dB(A)
kg
1380 T3
1380
269,5
237,0
39
282,0
50
centrifugal
3
9100%
R134a
410
1
400/3/50
535,5
15
5,12
8,57
92,2
73,1
4749
1520 T4
1520
290,6
261,0
29
310,0
50
centrifugal
4
6100%
R134a
410
1
400/3/50
882,0
20
5,23
8,78
92,5
73,1
5787
1840 T4
1840
358,0
316,0
36
376,0
50
centrifugal
4
6100%
R134a
450
1
400/3/50
714,0
20
5,14
8,73
94,0
74,6
6674
mm
mm
219,1
168,3
219,1
168,3
219,1
168,3
kW
kW
m/h
kPa
m/h
kPa
n.
%
kg
n.
V/Ph/Hz
A
A
kW/kW
kW
kW
m/h
kPa
m/h
kPa
n.
%
kg
n.
V/Ph/Hz
A
A
kW/kW
Referred to chilled water temperature 12/7C 0% glycol solution; water temperature to the condenser 30/35C. Fouling factor of the exchangers 0,043 mK/kW.
Sound power level [Lw] according to ISO EN 9614 - 2
Average sound pressure level [LPm] 1m far according to ISO EN 3744.
Hydraulic connection with grooved end, supplied as standard with flexible joint and adapter pipe.
Technical data refer to units equipped with 2-passes condenser.
Referred to condenser water inlet temperature 18C.
173
FRIGO TURBO FL
IT Cooling
DIMENSIONS (mm)
FRIGO TURBO FL
a
280 T1
3027
380 T1
3027
460 T1
3027
560 T2
3027
760 T2
3097
840 T3
4444
920 T2
3820
1140 T3
4444
1380 T3
4444
1520 T4
4935
4980
1840 T4
b
1360
1360
1360
1360
1360
1400
1360
1400
1400
1400
1400
c
1770
1770
1770
1929
1929
2059
2009
2059
2059
2090
2090
174
H
HF
HFO1234ze
4ze
HIGHEFFICIENCY
INVERTER
ACLASS
LOWNOISE
LOWGWP
GOGREEN
solutions
MAIN FEATURES
Water cooled liquid chiller in A class energy efficiency.
14 models available for a wide selection opportunity.
Average step of 75 kW.
EER up to 5,41.
ESEER up to 9,10.
Oil-free centrifugal compressors with magnetic levitation bearings.
Inverter driven.
HFO1234ze refrigerant charge, LOW GWP, GWP < 6.
Single refrigerant circuit.
Electronic expansion valve.
Shell and tube condenser.
Flooded evaporator.
Suitable for indoor installation.
MAIN BENEFITS
Up to four centrifugal compressors with magnetic levitation bearings on
the refrigerant circuit for an high efficiency.
No need of power factor correction.
Minimum starting current (LRA)
High EER and ESEER. A Class energy efficiency.
Quiet operation.
Microprocessor control system with 7 touch screen display.
Version with 4-passes condenser for a higher energy efficiency.
Extremely easily of maintenance.
Complete set of components dedicated to the safety of the unity.
OIL
FREE
INVERTER
CLASS
1234ze
FLOODED
INDOOR INSTALLATION
The machines are designed for indoor installation.
MAGNETIC LEVITATION CENTRIFUGAL COMPRESSOR
The TURBO FL liquid chillers are equipped with two-stage centrifugal
compressor with variable speed, which is able to follow punctually plant
demands, obtaining values of energy efficiency ratio (EER) growing in
a narrowing of the cooling load. The compressors of the TURBO FL
liquid chillers are equipped with magnetic levitation oil-free bearings
which compared to traditional ball bearings, completely eliminate all the
maintenance procedures of lubrication.
A CLASS ENERGY EFFICIENCY
The best and most accurate components applied to the chillers.
WORKING LIMITS IN COOLING MODE
Chilled water outlet temperature: 418C
Condenser outlet water temperature: 2052C
f i f t y c o o l y e a r s
175
GOGREEN
solutions
COMPONENTS
FRAMEWORK
Base and self supporting frame in steel plate with protective surfaces
treatment in compliance with UNI ISO 9227/ASTMB117 and ISO 7253, and
painted with epoxy powders.
Colour: RAL 9002
COMPRESSORS
Twin-turbine centrifugal compressor, oil-free type, optimized for HFO1234ze
refrigerant.
The term oil-free refers to the total absence of lubricating oil within the
compressor.
Magnetic levitation bearings.
Manometric compression ratio: 1.5 5.0
Stepless capacity control trough integrated inverter.
High efficiency permanent-magnet synchronous motor with integrated SoftStart system (starting current limited to 5A).
Power factor motor cos > 0.9 for a large part of the operating range
Motor and electronic power section cooling by liquid refrigerant injection into
the integrated cooling circuit.
Electric motor thermal protection via internal winding temperature sensors.
Electronic integrated control for operation and alarms status.
Sensor on refrigerant discharge for temperature monitoring.
Inner sensors for electronic components and inverter temperature control.
Security system to protect the crankshaft and magnetic bearings in the
event of failure of power supply.
Degree of protection: IP54.
IT Cooling
ELECTRICALPANEL
In accordance with EN60204-1 norms, suitable for indoor installation,
complete with:
Main switch with door lock safety.
Fuses for compressors.
Contactors for compressors.
Transformer for auxiliary circuit and microprocessor supply.
Panel with machine controls.
Power supply 400/3/50.
Refrigerant gas leak detector. Supplied in kit.
CONTROL SYSTEM
Microprocessor system with Touch Screen graphic display for control and
monitor of operating and alarms status. The system includes:
- Voltage free contact for remote general alarm.
- Voltage free contact for external alarm. The inlet is associable with
refrigerant gas leak detector.
- Main components hour-meter.
- Recording of the last 24 occurred alarms.
- Non-volatile Flash memory for data storage.
- Menu with protection password.
EVAPORATOR
Flooded shell and tube evaporator, optimized for HFO1234ze refrigerant.
Version two passes, characterized by low pressure losses on the water
side.
Water tubes with a helical rifled internal surface.
Integrated liquid drop separator.
Shell, header, tube sheets made of carbon steel, tubes in Cu.
Anticondensate insulation made of polyurethane.
Large liquid level indicator.
Temperature sensors on water inlet and outlet.
Water flow switch for water flow control on water outlet towards the plant,
not installed but supplied in kit.
Hydraulic connections with grooved end supplied as standard with flexible
joint and adapter pipe to be welded.
CONDENSER
Shell and tube 2-passes condenser optimized for HFO1234ze refrigerant.
- Machine type P4: 4-passes condenser.
Shell, header, tube sheets made of carbon steel, tubes in Cu.
Temperature sensors on condenser water inlet and outlet.
Hydraulic connections with grooved end supplied as standard with flexible
joint and adapter pipe to be welded.
From model 250 T1 P4 to model 560 T2 included the connections are
supplied in mounting kit. Installation to be made by the customer.
REFRIGERANT CIRCUIT
Components for each refrigerant circuit:
Capacitive level sensor connected to the driver of the expansion valve.
Electronic expansion valve that allows high performance and system
efficiency and for the refrigerant level control in the evaporator.
Electronic by-pass valve for compressor start.
Non return valve on by-pass line for compressor start.
Economizer for models 310 T1E, 620 T2E, 930 T3E, 1240 T4E.
The system includes:
- Copper brazed plate type with cover plates, plates and connections in
AISI 316 stainless steel.
- Anticondensate insulation made of polyurethane.
- Intermediate electronic expansion valve.
Sight glass.
Filter dryer on liquid line.
Service valve on liquid line.
Service valve on gas suction and discharge.
Non return valve on gas suction.
Safety valve on low pressure side.
Safety valve on high pressure side.
Pressure transducers with indication, control and protection functions, on
low and high refrigerant pressure.
High pressure safety switch with manual reset.
Refrigerant circuit with copper tubing with anticondensate insulation of the
suction line.
Plastic capillary hoses for pressure sensors connection.
HFO1234ze refrigerant charge.
176
IMPORTANT
HFO1234ze refrigerant is mildly flammable. For indoor installations is
important to foresee: proper ventilation; a refrigerant gas leak detector
(supplied as standard, in kit); pipes connected to the safety valves
outlets in order to exhaust vapours outside (not supplied, at customer
care).
G_ITC_RCW8.4 RCGROUP SpA 19632013 fiftycoolyears
GOGREEN
solutions
IT Cooling
OPTIONAL ACCESSORIES
FRIGO TURBO FLG
VERSIONE
172 - Rubber support (kit)
611 - Noise absorption cap
Service valve on compressor group suction
1003 - Analogic flowmeter
1005 - Power supply analyzer
1009 - Multimeter kit
943 - Data Logger
923 - RC-Com MBUS/JBUS Serial board
926 - LON Serial board
931 - BACnet Ethernet - SNMP - TCP/IP Serial board
932 - BACnet MS/TP Serial board
942 - Serial card for GSM Modem
962 - Kit modem GSM
957 - Plantwatch without modem
930 - Remote graphic terminal kit
889 - Master plant SEQUENCER
RC CLOUD PLATFORM
250 T1
P4
280 T1
310 T1E
400 T2
1000 T4
P4
400 T2
P4
500 T2
P4
560 T2
620 T2E
750 T3
P4
840 T3
930 T3E
177
GOGREEN
solutions
IT Cooling
STANDARD
STANDARD
1.
2.
3.
4.
(**)
250 T1 P4
280 T1
310 T1E
400 T2
400 T2 P4
500 T2 P4
560 T2
620 T2E
250
280
310
400
400
500
560
620
44,6
52,5
57,2
73,6
73,0
90,2
104,6
114,8
43,0
48,2
53,3
68,8
68,8
86,0
96,3
106,6
24
30
37
37
37
26
33
40
31,7
57,2
63,2
81,5
50,9
63,4
114,3
126,4
49
21
18
24
73
75
24
18
centrifugal
centrifugal
centrifugal
centrifugal
centrifugal
centrifugal
centrifugal
centrifugal
n.
1
1
1
2
2
2
2
2
%
25%100% 25%100% 25%100% 25%100% 25%100% 12%100% 12%100% 12%100%
HFO1234ze HFO1234ze HFO1234ze HFO1234ze HFO1234ze HFO1234ze HFO1234ze HFO1234ze
kg
167
166
164
152
156
188
183
197
n.
1
1
1
1
1
1
1
1
V/Ph/Hz
400/3/50
400/3/50
400/3/50
400/3/50
400/3/50
400/3/50
400/3/50
400/3/50
A
157,5
157,5
157,5
315,0
315,0
315,0
315,0
315,0
A
5
5
5
5
5
5
5
5
kW/kW
5,41
5,17
5,24
5,26
5,25
5,34
5,20
5,24
8,56
8,29
8,52
8,13
8,46
8,87
8,88
8,94
dB(A)
87,9
87,9
87,9
89,9
89,9
89,9
89,9
89,9
dB(A)
69,6
69,6
69,6
71,4
71,4
71,4
71,4
71,3
kg
2066
2065
2209
2700
2636
2949
3141
3526
kW
kW
m/h
kPa
m/h
kPa
mm
mm
114,3
88,9
dB(A)
dB(A)
kg
750 T3 P4
750
133,6
129,0
29
95,0
74
centrifugal
3
8%100%
HFO1234ze
322
1
400/3/50
472,5
5
5,41
9,10
91,6
72,8
4425
mm
mm
168,3
139,7
kW
kW
m/h
kPa
m/h
kPa
n.
%
kg
n.
V/Ph/Hz
A
A
kW/kW
114,3
114,3
114,3
114,3
168,3
114,3
840 T3
930 T3E
1000 T4 P4
840
930
1000
158,4
170,1
177,8
144,5
160,0
172,0
37
45
36
171,7
189,2
126,6
21
17
77
centrifugal
centrifugal
centrifugal
3
3
4
8%100% 13%100% 8%100%
HFO1234ze HFO1234ze HFO1234ze
314
328
436
1
1
1
400/3/50
400/3/50
400/3/50
472,5
472,5
630,0
5
5
5
5,16
5,31
5,41
8,92
8,92
8,89
91,6
91,6
92,5
72,8
72,8
73,3
4730
5211
6195
168,3
168,3
168,3
168,3
219,1
139,7
168,3
88,9
168,3
114,3
1120 T4
1120
208,5
192,6
45
228,5
44
centrifugal
4
8%100%
HFO1234ze
412
1
400/3/50
630,0
5
5,17
8,65
92,5
73,3
6376
1240 T4E
1240
226,7
213,3
55
252,3
36
centrifugal
4
9%100%
HFO1234ze
430
1
400/3/50
630,0
5
5,25
8,70
92,5
73,3
6964
219,1
168,3
219,1
168,3
168,3
139,7
168,3
168,3
Referred to chilled water temperature 12/7C 0% glycol solution; water temperature to the condenser 30/35C. Fouling factor of the exchangers 0,018 mK/kW.
Sound power level [Lw] according to ISO EN 9614 - 2
Average sound pressure level [LPm] 1m far according to ISO EN 3744.
Hydraulic connection with grooved end, supplied as standard with flexible joint and adapter pipe.
Referred to condenser water inlet temperature 18C.
DIMENSIONS (mm)
FRIGO TURBO FL
a
250 T1 P4
3465
280 T1
3465
310 T1E
3465
400 T2
3465
400 T2 P4
3465
500 T2 P4
3505
560 T2
3505
620 T2E
3685
750 T3 P4
3770
840 T3
3770
930 T3E
3770
1000 T4 P4 4520
1120 T4
4520
4520
1240 T4E
178
b
1360
1360
1360
1360
1360
1360
1360
1360
1360
1360
1400
1400
1360
1360
c
1770
1770
1770
1929
1929
1929
1929
1929
2059
2059
2059
2090
2090
2090
TEAM MATE
TEAM MATE: Air cooled condensers equipped with axial fans
Capacity: 12 307 kW
TEAM MATE
rcgroupairconditioning
MAIN FEATURES
Air cooled condensers.
19 models available, for a wide selection opportunity.
Average step of 15kW.
Multi-refrigerant charge.
Supplied with seal charge.
AC Axial fans.
Horizontal air flow.
Suitable for outdoor installation.
R134a
R407c
R410A
AC
SPLIT
SYSTEM
OUTDOOR INSTALLATION
The machines are made with weather resistant materials and suitable for
outdoor installation.
MAIN BENEFITS
Designed for the perfect match with RC Group motoevaporating units.
Availability of machine for the reduction and the extreme reduction of the
noise.
Availability of support leg for vertical air flow.
Easily of maintenance.
f i f t y c o o l y e a r s
179
TEAM MATE
IT Cooling
MAIN COMPONENTS
FRAMEWORK
Base, self supporting frame and panelling in steel plate with protective
surfaces treatment in compliance with UNI ISO 9227/ASTMB117 and ISO
7253, and painted with epoxy powders.
Colour: RAL 9002
FANS SECTION TEAM MATE
Axial fans with sickle-shaped blades, fan guard and optimized for low noise
levels.
External rotor electric motor, AC type, with stepless variable speed for
condensing pressure control.
The motor rotation control is obtained according to the 010V proportional
signal coming from the internal unit microprocessor control.
IP54 enclosure class.
ELECTRICAL PANEL
In accordance with EN60204-1 norms, suitable for outdoor installation, IP54
enclosure class, complete with:
Terminals for power supply (from network).
- 400/3/50+N for models T
- 230/1/50 for models M.
Terminals for 010V signal for condensing control system (connect to
indoor machine).
Terminals for alarm signal (connect to indoor machine).
Fans speed regulator for condensing control.
OPTIONAL ACCESSORY
Support legs for vertical air flow.
STANDARD
TEAM MATE
Capacity (1)
With refrigerant charge R410A
With refrigerant charge R407C
With refrigerant charge R134a
Unit power input
Axial fans
Total air flow
Air circuits
Total refrigerant charge (optional excluded)
Gas circuits
Power supply
Max unit operating current (FLA)
Sound power level [Lw] (2)
Average sound pressure level [Lpm] (3)
Net weight
Refrigerant connections
Liquid line ODS
Gas line ODS
Capacity (1)
With refrigerant charge R410A
With refrigerant charge R407C
With refrigerant charge R134a
Unit power input
Total air flow
Sound power level [Lw] (2)
Average sound pressure level [Lpm] (3)
Capacity (1)
With refrigerant charge R410A
With refrigerant charge R407C
With refrigerant charge R134a
Unit power input
Total air flow
Sound power level [Lw] (2)
Average sound pressure level [Lpm] (3)
1.
2.
3.
M 11
M 14
M 17
M 20
M 25
M 30
M 35
M 45
12,1
12,0
11,7
0,3
1
4900
1
0,8
1
230/1/50
1,2
76,8
63,0
51
14,7
14,7
14,4
0,3
1
4500
1
1,2
1
230/1/50
1,2
76,8
63,0
55
18,4
18,2
17,9
0,3
1
5200
1
1,7
1
230/1/50
1,2
77,1
63,0
66
20,7
20,4
20,0
0,4
1
6400
1
1,7
1
230/1/50
1,8
79,1
65,0
72
24,2
24,2
23,7
0,5
1
9600
1
2,0
1
230/1/50
2,9
81,8
67,0
102
32,7
32,3
31,7
0,5
1
9500
1
3,0
1
230/1/50
2,9
81,8
67,0
111
37,4
37,1
36,6
0,5
1
9100
1
4,0
1
230/1/50
2,9
81,8
67,0
120
47,6
47,1
46,5
0,8
2
12000
1
4,7
1
230/1/50
3,6
82,4
67,4
153
mm
mm
12
16
12
16
12
16
12
16
16
18
16
18
16
18
16
18
kW
kW
kW
kW
m/h
dB(A)
dB(A)
10,9
10,8
10,6
0,2
4165
72,9
59,1
13,1
13,1
12,9
0,2
3825
72,9
59,1
16,4
16,2
15,9
0,2
4420
73,2
59,1
18,5
18,2
17,9
0,3
5440
75,2
61,1
21,8
21,8
21,3
0,5
8160
77,9
63,1
29,1
28,7
28,3
0,5
8075
77,9
63,1
32,9
32,6
32,3
0,5
7735
77,9
63,1
42,0
41,6
41,1
0,7
10200
78,5
63,6
kW
kW
kW
kW
m/h
dB(A)
dB(A)
9,6
9,5
9,3
0,2
3430
68,2
54,5
11,4
11,4
11,2
0,2
3150
68,2
54,5
14,1
14,0
13,8
0,2
3640
68,6
54,5
16,1
15,8
15,6
0,3
4480
70,6
56,5
19,2
19,2
18,8
0,4
6720
73,3
58,5
25,2
24,9
24,5
0,4
6650
73,3
58,5
28,2
27,9
27,6
0,4
6370
73,3
58,5
36,1
35,7
35,3
0,6
8400
73,9
58,9
kW
kW
kW
kW
n.
m/h
n.
kg
n.
V/Ph/Hz
A
dB(A)
dB(A)
kg
180
TEAM MATE
IT Cooling
STANDARD
STANDARD
1.
2.
3.
TEAM MATE
Capacity (1)
With refrigerant charge R410A
With refrigerant charge R407C
With refrigerant charge R134a
Unit power input
Axial fans
Total air flow
Air circuits
Total refrigerant charge (optional excluded)
Gas circuits
Power supply
Max unit operating current (FLA)
Sound power level [Lw] (2)
Average sound pressure level [Lpm] (3)
Net weight
Refrigerant connections
Liquid line ODS
Gas line ODS
Capacity (1)
With refrigerant charge R410A
With refrigerant charge R407C
With refrigerant charge R134a
Unit power input
Total air flow
Sound power level [Lw] (2)
Average sound pressure level [Lpm] (3)
Capacity (1)
With refrigerant charge R410A
With refrigerant charge R407C
With refrigerant charge R134a
Unit power input
Total air flow
Sound power level [Lw] (2)
Average sound pressure level [Lpm] (3)
TEAM MATE
Capacity (1)
With refrigerant charge R410A
With refrigerant charge R407C
With refrigerant charge R134a
Unit power input
Axial fans
Total air flow
Air circuits
Total refrigerant charge (optional excluded)
Gas circuits
Power supply
Max unit operating current (FLA)
Sound power level [Lw] (2)
Average sound pressure level [Lpm] (3)
Net weight
Refrigerant connections
Liquid line ODS
Gas line ODS
Capacity (1)
With refrigerant charge R410A
With refrigerant charge R407C
With refrigerant charge R134a
Unit power input
Total air flow
Sound power level [Lw] (2)
Average sound pressure level [Lpm] (3)
Capacity (1)
With refrigerant charge R410A
With refrigerant charge R407C
With refrigerant charge R134a
Unit power input
Total air flow
Sound power level [Lw] (2)
Average sound pressure level [Lpm] (3)
M 50
M 60
M 70
M 95
M 110
M 130
M 140
T 185
56,1
55,5
54,8
1,1
2
17000
1
4,1
1
230/1/50
5,7
84,5
69,4
175
62,6
62,0
61,2
1,1
2
16000
1
5,5
1
230/1/50
5,7
84,5
69,4
188
74,0
73,3
72,4
1,1
2
18000
1
7,7
1
230/1/50
5,7
85,0
69,4
214
99,4
98,3
97,0
1,6
3
28200
1
8,7
1
230/1/50
8,5
86,9
70,5
240
111,0
110,0
109,0
1,6
3
27200
1
11,6
1
230/1/50
8,5
86,9
70,5
270
133,0
132,0
130,0
2,1
4
37800
1
11,6
1
230/1/50
11,4
88,1
71,1
320
151,0
150,0
149,0
2,1
4
36000
1
15,4
1
230/1/50
11,4
88,1
71,1
350
201,0
198,0
195,0
3,2
6
56000
1
20,8
1
400/3/50+N
17,1
88,8
71,5
470
mm
mm
18
22
18
22
18
22
22
35
22
35
28
35
28
35
35
42
kW
kW
kW
kW
m/h
dB(A)
dB(A)
50,1
49,6
48,9
0,9
14450
80,7
65,5
55,3
54,8
54,2
0,9
13600
80,7
65,5
65,1
64,6
63,8
0,9
15300
81,1
65,5
88,3
87,4
86,3
1,4
23970
83,0
66,6
97,7
97,3
96,2
1,4
23120
83,0
66,6
118,0
117,0
116,0
1,8
32130
84,2
67,2
133,0
132,0
131,0
1,8
30600
84,2
67,2
179,0
176,0
174,0
2,7
47600
84,9
67,7
kW
kW
kW
kW
m/h
dB(A)
dB(A)
43,5
43,1
42,6
0,8
11900
76,0
60,8
47,6
47,2
46,7
0,8
11200
76,0
60,8
55,8
55,3
54,7
0,8
12600
76,5
60,8
76,4
75,7
74,8
1,1
19740
78,4
61,9
83,7
83,3
82,5
1,1
19040
78,4
61,9
102,0
101,0
100,0
1,5
26460
79,6
62,5
114,0
113,0
112,0
1,5
25200
79,6
62,5
155,0
153,0
151,0
2,2
39200
80,3
63,0
T 210
T 250
T 280
232,0
231,0
228,0
3,2
6
54000
1
27,7
1
400/3/50+N
17,1
88,8
71,5
520
276,0
273,0
270,0
4,2
8
74600
1
27,7
1
400/3/50+N
22,8
90,1
72,2
630
307,0
304,0
301,0
4,2
8
72000
1
37,0
1
400/3/50+N
22,8
90,1
72,2
690
mm
mm
35
42
42
54
42
54
kW
kW
kW
kW
m/h
dB(A)
dB(A)
205,0
203,0
201,0
2,7
45900
84,9
67,7
245,0
243,0
240,0
3,6
63410
86,2
68,3
270,0
268,0
265,0
3,6
61200
86,2
68,3
kW
kW
kW
kW
m/h
dB(A)
dB(A)
175,0
173,0
172,0
2,2
37800
80,3
63,0
212,0
210,0
208,0
3,0
52220
81,5
63,7
231,0
229,0
227,0
3,0
50400
81,5
63,7
kW
kW
kW
kW
n.
m/h
n.
kg
n.
V/Ph/Hz
A
dB(A)
dB(A)
kg
kW
kW
kW
kW
n.
m/h
n.
kg
n.
V/Ph/Hz
A
dB(A)
dB(A)
kg
181
TEAM MATE
IT Cooling
DIMENSIONS (mm)
TEAM MATE
M 11
M 14
M 17
M 20
M 25
M 30
M 35
M 45
M 50
M 60
M 70
M 95
M 110
M 130
M 140
T 185
T 210
T 250
T 280
a
875
875
1200
1200
1400
1400
1400
1600
1850
1850
2320
3490
3490
4540
4540
3490
3490
4540
4540
b
540
540
540
540
665
665
665
665
665
665
665
665
665
665
665
665
665
665
665
c
727
727
727
727
1027
1027
1027
1027
1027
1027
1140
1150
1150
1150
1150
2200
2200
2200
2200
182
TEAM MATE PF
TEAM MATE PF: Air cooled condensers equipped with plug fan
Capacity: 12 154 kW
TEAM MATE PF
R407c
R410A
MAIN FEATURES
Air cooled condensers.
14 models available, for a wide selection opportunity.
Average step of 10kW.
Multi-refrigerant charge.
Supplied with seal charge.
EC Plug-fan.
Horizontal/Vertical air flow.
Suitable for indoor installation.
MAIN BENEFITS
Designed for the perfect match with RC Group motoevaporating units.
EC Plug fan for a high efficiency.
Availability of machine for the reduction and the extreme reduction of the
noise.
Availability of horizontal and vertical air delivery. To change air delivery
mode its simply required the change of position of a single panel.
Easily of maintenance.
R134a
EC
SPLIT
SYSTEM
f i f t y c o o l y e a r s
183
TEAM MATE PF
IT Cooling
MAIN COMPONENTS
FRAMEWORK
Base, self supporting frame and panelling in steel plate with protective
surfaces treatment in compliance with UNI ISO 9227/ASTMB117 and ISO
7253, and painted with epoxy powders.
Colour: RAL 9002
FANS SECTION TEAM MATE
Centrifugal fans with backward curved blades with wing profile, single
suction and without scroll housings (Plug-fan).
Brushless type synchronous EC motor with integrated electronic
commutated system and continuous variation of the rotation speed.
The motor rotation control is obtained with the EC system (Electronic
Commutation) that manage the motor according to the 010V proportional
signal coming from the internal unit microprocessor control.
Maintenance-free bearings
IP54 enclosure class.
REFRIGERANT CIRCUIT
Valves on gas and liquid line for coupling to refrigerant pipe. The valves are
supplied not installed. The condenser is supplied with nitrogen seal.
ELECTRICAL PANEL
In accordance with EN60204-1 norms, suitable for outdoor installation, IP54
enclosure class, complete with:
Terminals for power supply (from network).
- 380-480/3/50-60 for models T
Terminals for 010V signal for condensing control system (connect to
indoor machine).
Terminals for alarm signal (connect to indoor machine).
STANDARD
TEAM MATE PF
Capacity (1)
With refrigerant charge R410A
With refrigerant charge R407C
With refrigerant charge R134a
Unit power input
Plug-fans
Total air flow
Available static pressure
Max available static pressure
Air circuits
Total refrigerant charge (optional excluded)
Gas circuits
Power supply
Max unit operating current (FLA)
Sound power level [Lw] (2)
Average sound pressure level [Lpm] (3)
Net weight
Refrigerant connections
Liquid line ODS
Gas line ODS
Capacity (1)
With refrigerant charge R410A
With refrigerant charge R407C
With refrigerant charge R134a
Unit power input
Total air flow
Available static pressure
Sound power level [Lw] (2)
Average sound pressure level [Lpm] (3)
Capacity (1)
With refrigerant charge R410A
With refrigerant charge R407C
With refrigerant charge R134a
Unit power input
Total air flow
Available static pressure
Sound power level [Lw] (2)
Average sound pressure level [Lpm] (3)
1.
2.
3.
T 11
T 14
T 17
T 21
T 24
T 33
T 38
T 44
12,1
15,6
18,2
21,6
25,0
35,1
39,8
46,5
kW
12,0
15,6
18,2
21,6
25,0
35,1
39,8
46,5
kW
11,7
15,3
17,9
21,3
24,7
34,7
39,3
46,0
kW
0,4
0,4
0,5
0,5
0,6
1,3
1,1
1,2
kW
1
1
1
1
1
1
1
1
n.
4900
4900
4900
4900
6400
8000
10000
10000
m/h
50
50
50
50
50
50
50
50
Pa
375
350
332
290
748
474
298
268
Pa
1
1
1
1
1
1
1
1
n.
0,8
1,2
1,7
2,6
2,5
3,8
4,3
6,4
kg
1
1
1
1
1
1
1
1
n.
V/Ph/Hz 380-480/3/50-60 380-480/3/50-60 380-480/3/50-60 380-480/3/50-60 380-480/3/50-60 380-480/3/50-60 380-480/3/50-60 380-480/3/50-60
A
1,6
1,6
1,6
1,6
4,3
4,3
3,6
3,6
dB(A)
76,2
76,2
76,1
76,1
82,5
87,4
86,6
86,8
dB(A)
61,6
61,6
61,5
61,5
67,1
72,0
71,1
71,3
kg
143
148
153
163
210
222
284
310
mm
mm
16
18
16
18
16
22
16
22
18
22
18
22
18
22
18
22
kW
kW
kW
kW
m/h
Pa
dB(A)
dB(A)
10,8
10,5
10,2
0,3
4165
36
72,3
57,7
13,7
13,7
13,3
0,3
4165
36
72,3
57,7
15,9
15,9
15,5
0,3
4165
36
72,2
57,6
18,8
18,8
18,4
0,3
4165
36
72,2
57,6
21,6
21,6
21,0
0,4
5440
36
78,6
63,2
30,2
30,2
29,4
0,8
6800
36
83,5
68,1
34,5
34,5
33,7
0,7
8500
36
82,7
67,2
40,1
40,1
39,3
0,8
8500
36
82,9
67,4
kW
kW
kW
kW
m/h
Pa
dB(A)
dB(A)
9,5
9,3
9,1
0,2
3430
25
67,6
53,1
11,9
11,9
11,6
0,2
3430
25
67,6
53,1
13,7
13,7
13,4
0,2
3430
25
67,5
53,0
16,0
16,0
15,7
0,2
3430
25
67,5
53,0
18,7
18,7
18,2
0,3
4480
25
73,9
58,6
25,8
25,8
25,2
0,5
5600
25
78,8
63,5
29,7
29,7
29,1
0,5
7000
25
78,1
62,6
34,0
34,0
33,5
0,5
7000
25
78,3
62,8
184
TEAM MATE PF
IT Cooling
STANDARD
1.
2.
3.
TEAM MATE PF
Capacity (1)
With refrigerant charge R410A
With refrigerant charge R407C
With refrigerant charge R134a
Unit power input
Plug-fans
Total air flow
Available static pressure
Max available static pressure
Air circuits
Total refrigerant charge (optional excluded)
Gas circuits
Power supply
Max unit operating current (FLA)
Sound power level [Lw] (2)
Average sound pressure level [Lpm] (3)
Net weight
Refrigerant connections
Liquid line ODS
Gas line ODS
Capacity (1)
With refrigerant charge R410A
With refrigerant charge R407C
With refrigerant charge R134a
Unit power input
Total air flow
Available static pressure
Sound power level [Lw] (2)
Average sound pressure level [Lpm] (3)
Capacity (1)
With refrigerant charge R410A
With refrigerant charge R407C
With refrigerant charge R134a
Unit power input
Total air flow
Available static pressure
Sound power level [Lw] (2)
Average sound pressure level [Lpm] (3)
T 58
T 69
T 86
T108
T114
T144
kW
62,0
73,1
91,0
113,0
122,0
154,0
kW
62,0
73,1
91,0
113,0
122,0
154,0
kW
61,2
72,4
89,9
111,0
121,0
152,0
kW
2,2
2,4
3,3
4,7
5,6
7,4
n.
2
2
3
3
3
4
m/h
16000
16000
24000
32000
28000
36000
Pa
50
50
50
50
50
50
Pa
552
512
542
515
204
237
n.
1
1
1
1
1
1
kg
5,9
8,8
10,2
10,3
9,4
14,0
n.
1
1
1
1
1
1
V/Ph/Hz 380-480/3/50-60 380-480/3/50-60 380-480/3/50-60 380-480/3/50-60 380-480/3/50-60 380-480/3/50-60
A
8,6
8,6
12,9
17,2
12,9
17,2
dB(A)
93,4
93,5
96,9
98,7
100,3
101,4
dB(A)
77,3
77,4
80,3
81,8
83,7
84,5
kg
387
421
515
625
557
673
mm
mm
22
35
22
35
22
35
22
35
22
35
28
35
kW
kW
kW
kW
m/h
Pa
dB(A)
dB(A)
53,4
53,4
51,8
1,4
13600
36
89,5
73,4
62,7
62,7
61,3
1,5
13600
36
89,6
73,5
78,6
78,6
76,2
2,2
20400
36
93,0
76,4
98,9
98,9
96,2
3,0
27200
36
94,8
77,9
105,0
105,0
102,0
3,6
23800
36
96,4
79,8
131,0
131,0
127,0
4,7
30600
36
97,5
80,6
kW
kW
kW
kW
m/h
Pa
dB(A)
dB(A)
46,2
46,2
45,0
0,8
11200
25
84,8
68,8
53,4
53,4
52,4
0,9
11200
25
84,9
68,9
68,1
68,1
66,4
1,3
16800
25
88,3
71,8
85,9
85,9
83,8
1,8
22400
25
90,2
73,3
89,8
89,8
87,9
2,1
19600
25
91,7
75,2
113,0
113,0
110,0
2,8
25200
25
92,9
76,0
185
TEAM MATE PF
IT Cooling
DIMENSIONS (mm)
TEAM MATE PF
T 11
T 14
T 17
T 21
T 24
T 33
T 38
T 44
T 58
T 69
T 86
T108
T114
T144
a
890
890
890
890
1190
1190
1390
1390
1840
1840
2290
1840
2290
1840
b
880
880
880
880
880
880
880
880
880
880
880
880
880
880
c
900
900
900
900
900
900
1300
1300
1300
1300
1300
1800
1300
1800
186
DRY COOLER
IT Cooling
DRY COOLER
rcgroupairconditioning
MAIN FEATURES
Dry coolers.
10 models available, for a wide selection opportunity.
Average step of 15kW.
Water feeding.
AC Axial fans.
Horizontal air flow.
Suitable for outdoor installation.
AC
OUTDOOR INSTALLATION
The machines are made with weather resistant materials and suitable for
outdoor installation.
MAIN BENEFITS
Designed for the perfect match with RC Group water cooled liquid
chillers.
Availability of machine for the reduction and the extreme reduction of the
noise.
Availability of support leg for vertical air flow.
Easily of maintenance.
f i f t y c o o l y e a r s
187
DRY COOLER
IT Cooling
MAIN COMPONENTS
FRAMEWORK
Base, self supporting frame and panelling in steel plate with protective
surfaces treatment in compliance with UNI ISO 9227/ASTMB117 and ISO
7253, and painted with epoxy powders.
Colour: RAL 9002
FANS SECTION
Axial fans with sickle-shaped blades, fan guard and optimized for low noise
levels.
External rotor electric motor, AC type, with stepless variable speed for
condensing pressure control.
The motor rotation control is obtained according to the 010V proportional
signal coming from the internal unit microprocessor control.
IP54 enclosure class.
DISSIPATIVE COIL
Heat exchanger coil with copper tubes and high efficiency aluminium fins,
specifically developed to provide high heat transfer and lower pressure
drops.
The combination of two factors, special tubes and fins, allow to optimally
combine the following aspects:
- Maximum capacity relative to the size of the exchanger.
- Reduction of the air flow required for the heat exchange.
Frame in galvanized steel.
ELECTRICAL PANEL
In accordance with EN60204-1 norms, suitable for outdoor installation, IP54
enclosure class, complete with:
Terminals for power supply (from network).
- 400/3/50+N for models T
- 230/1/50 for models M.
Terminals for 010V signal for fan speed control (connect to indoor
machine).
Terminals for alarm signal (connect to indoor machine).
Fans speed regulator for fan speed control.
OPTIONAL ACCESSORY
Support legs for vertical air flow
LNO 70%
LNO 85%
STANDARD
DRY COOLER
Capacity (1)
Unit power input
Axial fans
Total air flow
Air circuits
Water flow
Pressure drops
Water content
Power supply
Max unit operating current (FLA)
Sound power level [Lw] (2)
Average sound pressure level [Lpm] (3)
Net weight
Hydraulic connections
Inlet / Outlet ISO 7/1 R
Capacity (1)
Unit power input
Total air flow
Water flow
Pressure drops
Sound power level [Lw] (2)
Average sound pressure level [Lpm] (3)
Capacity (1)
Unit power input
Total air flow
Water flow
Pressure drops
Sound power level [Lw] (2)
Average sound pressure level [Lpm] (3)
1.
2.
3.
(*)
kW
kW
n.
m/h
n.
m/h
kPa
l
V/Ph/Hz
A
dB(A)
dB(A)
kg
kW
kW
m/h
m/h
kPa
dB(A)
dB(A)
kW
kW
m/h
m/h
kPa
dB(A)
dB(A)
M 14
8,3
0,3
1
4500
1
1,5
24
4,0
230/1/50
0,7
76,8
63,0
56
M 20
11,7
0,4
1
6400
1
2,1
21
5,7
230/1/50
1,8
79,1
65,0
73
M 35
22,6
0,5
1
9100
1
4,0
26
15,7
230/1/50
2,9
81,8
67,0
122
M 45
26,4
0,8
2
12000
1
4,7
16
15,2
230/1/50
3,6
82,4
67,4
156
M 60
31,8
1,1
2
16000
1
5,7
8
17,9
230/1/50
5,7
84,5
69,4
191
M 70
40,2
1,1
2
18000
1
7,2
12
25,1
230/1/50
5,7
85,0
69,4
219
M 110
62,2
1,6
3
27200
1
11,1
17
37,7
230/1/50
8,5
86,9
70,5
227
1 1/4"
7,3
0,3
3825
1,3
19
72,9
59,1
6,4
0,2
3150
1,1
15
68,2
54,5
1 1/4"
10,4
0,4
5440
1,9
17
75,2
61,1
9,0
0,3
4480
1,6
13
70,6
56,5
1 1/2"
19,8
0,5
7735
3,5
21
77,9
63,1
16,9
0,4
6370
3,0
16
73,3
58,5
1 1/2"
23,3
0,8
10200
4,2
13
78,5
63,6
19,9
0,6
8400
3,6
10
73,9
58,9
2"
28,0
1,1
13600
5,0
6
80,7
65,5
23,8
0,8
11200
4,3
5
76,0
60,8
2"
35,3
0,9
15300
6,3
10
81,1
65,5
30,2
0,8
12600
5,4
7
76,5
60,8
2"
54,8
1,4
23120
9,8
14
83
66,6
46,9
1,1
19040
8,4
11
78,4
61,9
M 140
T 210
T 280
86,1
124,0
172,0
2,1
3,2
4,2
4
6
8
36000
54000
72000
1
1
1
15,4
22,1
30,8
40
17
40
72,8
75,3
100,4
230/1/50 400/3/50+N(*) 400/3/50+N(*)
11,4
17,1
22,8
88,1
88,8
90,1
71,1
71,5
72,2
359
533
708
2"
75,9
1,8
30600
13,6
32
84,2
67,2
65,0
1,5
25200
11,6
25
79,6
62,5
2 1/2"
109,0
2,7
45900
19,5
14
84,9
67,7
93,2
2,2
37800
16,7
10
80,3
63,0
3"
152,0
3,6
61200
27,1
32
86,2
68,3
130,0
3,0
50400
23,3
25
81,5
63,7
Characteristics referred to entering air at 35C with hot water inlet temperature 45C 20% glycol.
Sound power level [Lw] according to ISO EN 9614 - 2
Average sound pressure level [LPm] 1m far according to ISO EN 3744.
Available also with 230/1/50 power supply. Refer to the wiring diagram of the unit.
DIMENSIONS (mm)
DRY COOLER
M 14
M 20
M 35
M 45
M 60
M 70
M 110
M 140
T 210
T 280
a
875
1200
1400
1600
1850
2320
3490
4540
3490
4540
b
540
540
665
665
665
665
665
665
665
665
c
727
727
1027
1027
1027
1140
1150
1150
2200
2200
DRY COOLER PF
IT Cooling
DRY COOLER PF
rcgroupairconditioning
MAIN FEATURES
Dry coolers.
13 models available, for a wide selection opportunity.
Average step of 6kW.
Water feeding.
EC Plug-fan.
Horizontal/Vertical air flow.
Suitable for indoor installation.
MAIN BENEFITS
Designed for the perfect match with RC Group water cooled liquid
chillers.
EC Plug fan for a high efficiency.
Availability of machine for the reduction and the extreme reduction of the
noise.
Availability of horizontal and vertical air delivery. To change air delivery
mode its simply required the change of position of a single panel.
Easily of maintenance.
EC
f i f t y c o o l y e a r s
189
DRY COOLER PF
IT Cooling
MAIN COMPONENTS
FRAMEWORK
Base, self supporting frame and panelling in steel plate with protective
surfaces treatment in compliance with UNI ISO 9227/ASTMB117 and ISO
7253, and painted with epoxy powders.
Colour: RAL 9002
FANS SECTION TEAM MATE
Centrifugal fans with backward curved blades with wing profile, single
suction and without scroll housings (Plug-fan).
Brushless type synchronous EC motor with integrated electronic
commutated system and continuous variation of the rotation speed.
The motor rotation control is obtained with the EC system (Electronic
Commutation) that manage the motor according to the 010V proportional
signal coming from the internal unit microprocessor control.
Maintenance-free bearings
IP54 enclosure class.
DISSIPATIVE COIL
Heat exchanger coil with copper tubes and high efficiency aluminium fins,
specifically developed to provide high heat transfer and lower pressure
drops. The combination of two factors, special tubes and fins, allow to
optimally combine the following aspects:
- Maximum capacity relative to the size of the exchanger.
- Reduction of the air flow required for the heat exchange.
Frame in galvanized steel.
ELECTRICAL PANEL
In accordance with EN60204-1 norms, suitable for outdoor installation, IP54
enclosure class, complete with:
Terminals for power supply (from network).
- 380-480/3/50-60 for models T
Terminals for 010V signal for fan speed control (connect to indoor
machine).
Terminals for alarm signal (connect to indoor machine).
190
DRY COOLER PF
IT Cooling
LNO 70%
LNO 85%
STANDARD
LNO 70%
LNO 85%
STANDARD
1.
2.
3.
(*)
DRY COOLER PF
Capacity (1)
Unit power input
Axial fans
Total air flow
Available static pressure
Max available static pressure
Air circuits
Water flow
Pressure drops
Water content
Power supply
Max unit operating current (FLA)
Sound power level [Lw] (2)
Average sound pressure level [Lpm] (3)
Net weight
Hydraulic connections
Inlet / Outlet ISO 7/1 R
Capacity (1)
Unit power input
Total air flow
Water flow
Pressure drops
Sound power level [Lw] (2)
Average sound pressure level [Lpm] (3)
Capacity (1)
Unit power input
Total air flow
Water flow
Pressure drops
Sound power level [Lw] (2)
Average sound pressure level [Lpm] (3)
T 14
T 17
T 21
T 24
T 33
T 38
T 44
T 58
kW
8,8
10,5
12,6
13,7
20,6
24,3
28,0
31,8
kW
0,4
0,5
0,5
0,6
1,3
1,1
1,2
2,2
n.
1
1
1
1
1
1
1
2
m/h
4900
4900
4900
6400
8000
10000
10000
16000
Pa
50
50
50
50
50
50
50
50
Pa
350
332
290
748
474
298
268
552
n.
1
1
1
1
1
1
1
1
m/h
1,6
1,9
2,3
2,4
3,7
4,3
5,0
5,7
kPa
26
24
15
15
26
30
29
8
l
3,9
5,2
7,8
7,4
11,1
12,7
19,1
17,5
V/Ph/Hz 380-480/3/50-60 380-480/3/50-60 380-480/3/50-60 380-480/3/50-60 380-480/3/50-60 380-480/3/50-60 380-480/3/50-60 380-480/3/50-60
A
1,6
1,6
1,6
4,3
4,3
3,6
3,6
8,6
dB(A)
76,2
76,1
76,1
82,5
87,4
86,6
86,8
93,4
dB(A)
61,6
61,5
61,5
67,1
72
71,1
71,3
77,3
kg
149
154
165
209
224
287
314
391
DRY COOLER PF
Capacity (1)
Unit power input
Axial fans
Total air flow
Available static pressure
Max available static pressure
Air circuits
Water flow
Pressure drops
Water content
Power supply
Max unit operating current (FLA)
Sound power level [Lw] (2)
Average sound pressure level [Lpm] (3)
Net weight
Hydraulic connections
Inlet / Outlet ISO 7/1 R
Capacity (1)
Unit power input
Total air flow
Water flow
Pressure drops
Sound power level [Lw] (2)
Average sound pressure level [Lpm] (3)
Capacity (1)
Unit power input
Total air flow
Water flow
Pressure drops
Sound power level [Lw] (2)
Average sound pressure level [Lpm] (3)
T 69
T 86
T108
T114
T144
kW
41,9
50,0
60,3
68,8
89,0
kW
2,4
3,3
4,7
5,6
7,4
n.
2
3
4
3
4
m/h
16000
24000
32000
28000
36000
Pa
50
50
50
50
50
Pa
512
542
515
204
237
n.
1
1
1
1
1
m/h
7,5
9,0
10,8
12,3
15,9
kPa
18
18
10
15
31
l
26,2
24,5
28,0
36,7
41,9
V/Ph/Hz 380-480/3/50-60 380-480/3/50-60 380-480/3/50-60 380-480/3/50-60 380-480/3/50-60
A
8,6
12,9
17,2
12,09
17,2
dB(A)
93,5
96,9
98,7
100,3
101,4
dB(A)
77,4
80,3
81,8
83,7
84,5
kg
427
520
565
631
682
kW
kW
m/h
m/h
kPa
dB(A)
dB(A)
kW
kW
m/h
m/h
kPa
dB(A)
dB(A)
kW
kW
m/h
m/h
kPa
dB(A)
dB(A)
kW
kW
m/h
m/h
kPa
dB(A)
dB(A)
1 1/4"
7,8
0,3
4165
1,4
21
72,3
57,7
6,8
0,2
3430
1,2
17
67,6
53,1
2"
36,7
1,5
13600
6,6
14
89,6
73,5
31,1
0,9
11200
5,6
11
84,9
68,9
1 1/4"
9,2
0,3
4165
1,7
19
72,2
57,6
8,0
0,2
3430
1,4
15
67,5
53,0
2"
44,3
2,2
20400
7,9
14
93,0
76,4
38,1
1,3
16800
6,8
11
88,3
71,8
1 1/4"
11,0
0,3
4165
2,0
11
72,2
57,6
9,3
0,2
3430
1,7
9
67,5
53,0
2"
53,3
3,0
27200
9,5
8
94,8
77,9
45,8
1,8
22400
8,2
6
90,2
73,3
1 1/2"
12,1
0,4
5440
2,2
12
78,6
63,2
10,3
0,3
4480
1,9
9
73,9
58,6
2"
60,4
3,6
23800
10,8
12
96,4
79,8
51,4
2,1
19600
9,2
9
91,7
75,2
1 1/2"
18,0
0,8
6800
3,2
21
83,5
68,1
15,4
0,5
5600
2,8
16
78,8
63,5
1 1/2"
21,4
0,7
8500
3,8
24
82,7
67,2
18,3
0,5
7000
3,3
18
78,1
62,6
1 1/2"
24,5
0,8
8500
4,4
23
82,9
67,4
20,6
0,5
7000
3,7
17
78,3
62,8
2"
28,0
1,4
13600
5,0
6
89,5
73,4
23,8
0,8
11200
4,3
5
84,8
68,8
2"
78,3
4,7
30600
14,0
24
97,5
80,6
67,0
2,8
25200
12,0
19
92,9
76,0
Characteristics referred to entering air at 35C with hot water inlet temperature 45C 20% glycol.
Sound power level [Lw] according to ISO EN 9614 - 2
Average sound pressure level [LPm] 1m far according to ISO EN 3744.
Available also with 230/1/50 power supply. Refer to the wiring diagram of the unit.
191
DRY COOLER PF
IT Cooling
DIMENSIONS (mm)
DRY COOLER PF
a
T 14
890
T 17
890
T 21
890
T 24
1190
T 33
1190
T 38
1390
T 44
1390
T 58
1840
T 69
1840
T 86
2290
T108
1840
T114
2290
T144
1840
b
880
880
880
880
880
880
880
880
880
880
880
880
880
c
900
900
900
900
900
1300
1300
1300
1300
1300
1800
1300
1800
192
RC World
RCWORLD
rc world
rcgroupairconditioning
MAIN FEATURES
RC WORLD MAIN NEW FEATURES
5 applications:
Products selection.
Unit performances.
Price list.
Offer management.
Orders management.
8 languages:
Deutsch
English
Espanol
Francais
Italiano
Norsk
Polski
Russian
Suomi
Swedish
MAIN BENEFITS
RC World calculates the performance of all the RC Group product range
at every admitted working conditions.
RC World shows the descriptions and the technical drawings of the units.
RC World shows the optional accessory of the units.
193
Spectrum
RCSPECTRUM
spectrum
rcgroupairconditioning
MAIN FEATURES
WEB application able to predict the Energy performance of the units
(chillers and heat pumps) and to conduct a comprehensive energy
analysis.
Energy performance of whatever unit in a specific operating condition
(ONE SHOT mode):
Gross and net EER (chillers).
TER (chillers with heat recovery).
Gross and net COP (heat pumps, with estimation of defrost for air-towater units).
MAIN BENEFITS
For planners:
Aid in the choice of machines and their conduction.
Analysis of return on investment.
Easy integration of results into project documentation.
For Energy Managers:
Tool to verify predicted performances.
Integration with BMS/SEQ to optimize operational logic.
194
Spectrum Tutorial
RCSPECTRUM
TRAILER
tutorial
rcgroupairconditioning
VIDEO INDEX
CHAPTER 1
CHAPTER 3
CHAPTER 2
CHAPTER 4
195
Sequencer
SEQUENCER
sequencer
rcgroupairconditioning
MAIN FEATURES
The sequencer SEQ is designed as a master unit in a network of different
machines connected in a single hydronic network for the production of
chilled or heated water.
2-pipe, 4-pipe plants.
Machines different for type and size (with a maximum of 5 units).
Management of units made by others.
Designed to work alone or in combination with a supervisor (BMS).
MAIN BENEFITS
Active control:
Automatic activation / deactivation of the units depending on changeover,
alarms, temperature control, limit conditions, special events (e.g. restart
after power failure).
Plant temperature precision control.
Improvement and control of system energy efficiency.
Pumps control.
Others plant management functions:
Acoustic limiting, by the definition of reduced thresholds for fan
speed.
Demand limiting (limitation of electrical power absorption).
Time scheduling.
Changeover, with the goal of equalize the working hours of all
devices.
Antifreeze function integration.
Passive control:
Collection of all signal alarms coming from the units.
Report of faults and events.
Request of pre-programmed maintenance activities.
196
Cool Net
COOLNET
STAND BY - ZONE
FREE ZONE
C
Return air
temperature
Set-Point Coolnet
cool net
rcgroupairconditioning
MAIN FEATURES
COOLNET is a software that applies to chilled water air conditioners X TYPE,
NEXT EVO CW and COOLROW CW microprocessor control system. It
optimizes the LOAD SHARING working mode and maximizes the energy
savings.
FUNCTIONAL AND OPERATING CHARACTERISTICS
Manages up to 15 units in LAN, to optimize the temperature statistics. More
than 15 units can be managed in groups.
Minimizes power consumption, controlling uniformly units within the cooling
zone.
Increases energy saving of the units by a factor up to 40% when compared
with BAC standard solution.
Avoids the heating/cooling fighting. The units work together to efficiently
satisfy thermal load.
Optimizes the answer to unbalanced load through a smart self-adaptive
LOAD SHARING.
The master unit, through the application of heuristic algorithm, elaborates
the average return temperature of all of the linked units and defines a
Cooling Zone.
It then processes the common load signal that modulates the fan speed of
all the units within the operating band.
MAIN BENEFITS
Represents an RC Group offer extension for the IT cooling market
segment.
Answers to the main needs of the XXI century Data Center:
- Lower energy consumption. Savings on bills.
- Management of unbalanced load.
- Flexibility. Adaptability to the IT equipment evolution.
- Ease of use. Simple parameters to be set, just turn on Cool Net
function.
197
RC Cloud Platform
RC CLOUD
PLATFORM
rc cloud platform
rcgroupairconditioning
MAIN FEATURES
RC CLOUD PLATFORM is the most advanced solution in unattended
monitoring and remote management for an air conditioning plant.
Rilheva is able to analyse any physical quantity variation through RTU
Modbus protocol on RS485 network and transmits the data detected to a
control server. Each device can manage up to 31 units (a/c units/chillers)
for a total of 400 Modbus Registers.
Thanks to a simple web access (PC, Tablet or Smartphone), has an
interface available that allows him to directly operate on the field.
MAIN FUNCTIONS
Check of the plants status in real time.
Analysis in real time of each unit data.
Possibility to receive, for each single set parameter, specific warnings in
the preferred technology: SMS, Mail, Speech Synthesis, FAX and push
notification on APP (Android and iOS).
Creation and export of charts with historical data.
Data monitoring directly on a geographical map
Control transmission to the unit (start/stop, set point modification, alarms
reset).
Integration of different peripheral units in the system (pumps, movie
camera, etc.).
http://rcgroup.rilheva.it
Logos, Trade Marks and Companies Name are property of respective Owners
198
rcgroupairconditioning
IT Cooling
Via Roma 5, 27010 Valle Salimbene (PV) Italy +39 0382 433811 www.rcgroup.it info@rcgroup.it
rcgroupairconditioning
RC GROUP SpA
96
f i f t y c o o l y e a r s
IT Cooling
IT Cooling
start here
G_ITC_RCW8.4_1015_GB
RC Group is a Company of
Technical data and dimensions are not binding. RC GROUP S.p.A. reserves the right for changes and / or modifications without notice.
English
rcgroupairconditioning