www.elek.com.au/safegrid.htm
Background
The purpose of transmission line grounding is
to (a) provide adequate lightning performance
of the line; and (b) effectively dissipate fault
current avoiding the build-up of unsafe step
and touch potentials around the tower base.
The tower earthing system is provided by an
electrically
interconnected
system
of
conductors and rods, connectors, foundation
and the local soil.
400 A
0.25 m
100 .m
2m
500 .m
162 A
0.25 m
393 .m
1.16 m
897 .m
Case Studies
The safety of two transmission tower designs
has been assessed using analytical modelling
software.
Case 1 - Single potential control ring:
Page 1 of 5
Conductor radius
0.01 m
Frequency of supply
50 Hz
Conductivity of buried conductor 57E6 S/m
Results
The calculation results of the two case studies
are given below.
Step and touch potentials are calculated for
up to 1 m and 5 m, respectively, from the
perimeter set by the outside control ring.
Case 1 - Single potential control ring:
5.23
2093 V
2033 V
Page 2 of 5
12.48
2022 V
1967 V
Page 3 of 5
Safety criteria
The allowable safety criteria limits are
calculated using SafeGrid in accordance with
both IEEE Std-80 and IEC 60479.
Table 6 Common inputs for safety criteria calculations
0.22 s
None
None
20
Inputs:
Fibrillation current calculation
Foot resistance calculation
Safe limits:
Touch voltage limit
Step voltage limit
Permissible body current
Body resistance
50 kg - IEEE
IEEE Std-80:
2000
250.5 V
348.5 V
0.2473 A
1000
Inputs:
Fibrillation current calculation
Foot resistance calculation
Safe limits:
Touch voltage limit
Step voltage limit
Permissible body current
Body resistance
C1 - IEC
IEEE Std-80:
2000
295.4 V
442.6 V
0.3713 A
753.4
Touch voltages
Generally for this situation the touch voltages
which need to be assessed are for those areas
Page 4 of 5
[3]
IEC 60479 Effects of current on
human beings and animals.
[4]
IEEE Std-80 Guide for safety in AC
substation grounding.