Sunteți pe pagina 1din 62

REPLY TO NTPC COMMENTS VIDE TRANSMITTAL REF ANPARA D: 156 2690 DTD.

01/01/10

NTPC Comments

S.No

This document is the property of SIEMENS and must not be passed on to any third person or firm not authorised by us, nor be copied/made use of in full or part by such person or firm without our prior permission writing

Our Reply

2 Nos 80X80X10mm Vibration Pad shall be provided

Incorporated

04.01.10

REVISED IN LINE WITH THE COMMENTS VIDE TRANSMITTAL NO


ANPARAD: 156: 2690 DATED 01.01.10

RAA

ER

MKS

17.12.09

REVISED IN LINE WITH THE COMMENTS VIDE TRANSMITTAL NO


ANPARAD: 156: 2306 DATED 27.11.09

RAA

ER

MKS

25.11.09

FIRST ISSUE

RAA

ER

MKS

REV

DATE

DESCRIPTION

DSGN

CHKD

APPD

REVISIONS
NTPC DRAWING NO:

9464-001-PVE-B-0105

L&T DRAWING NO:

O9075-E-BM-CS-DD-0105

CLIENT:

CONSULTANT:

PROJECT:

ANPARA THERMAL POWER PROJECT STAGE - D (2x500) - COAL HANDLING PLANT


SPECIFICATION NO.: CW - CM - 9464 - C - 0 - 001

CONTRACTOR:

Digitally signed

JOB NO.: 09075

by Srikrishna S
LARSEN & TOUBRO LIMITED
ECC DIVISION - EDRC Date: 2010.02.01
08:49:07
GMT+05:30
Reason: CAT
I
NAME
Location:
RAA
DSGN
NTPCEOC

SUB-CONTRACTOR:
JOB NO.: 4083
IS-MT-MI-PS-SR
TITLE :

SCALE
HT Motor data sheets, G.A., curves, T.Box drawing

DRWN
CHKD

RAA
ER

APPD

MKS

DATE

04.01.10
04.01.10
04.01.10
04.01.10
REV

DOC. No.

(4)

RELEASED FOR

PRELIMINARY

4
2

TENDER

X
2

INFORMATION

Z
3

APPROVAL

6 -

2
2

CONSTRUCTION

LARSEN & TOUBRO LIMITED - ECC GROUP

Project :

ANPARA THERMAL POWER PROJECT, STAGE-D.

Title :

HT MOTOR DATASHEET, GA, CURVES AND T.BOX DRAWING

Sub title :

INDEX

Doc No. :

(4)G71400-X4083-Z046-2
O9075-E-BM-CS-DD-0105 - Rev-2

L&T Doc No. :


NTPC Doc No :

9464-001-PVE-B-0105 Rev-2

Rev. :

Dated :

04.01.10

INDEX

S.No

LIST OF DOCUMENTS

220kW 4pole DC280F710

Datasheet

GA Drawing

Current vs Speed Curve

Efficiency and Power Factor vs % Load curve

Negative Sequence Curve

Thermal withstand characteristic

Torque vs Speed Curve

Starting Current vs Time curve

345kW 4pole DC355F3

Datasheet

GA Drawing

Current vs Speed Curve

Efficiency and Power Factor vs % Load curve

Page 1 OF 3

LARSEN & TOUBRO LIMITED - ECC GROUP

Project :

ANPARA THERMAL POWER PROJECT, STAGE-D.

Title :

HT MOTOR DATASHEET, GA, CURVES AND T.BOX DRAWING

Sub title :

INDEX

Doc No. :

(4)G71400-X4083-Z046-2
O9075-E-BM-CS-DD-0105 - Rev-2

L&T Doc No. :

Negative Sequence Curve

Thermal withstand characteristic

Torque vs Speed Curve

Starting Current vs Time curve

430kW 4pole DC355F3

Datasheet

GA Drawing

Current vs Speed Curve

Efficiency and Power Factor vs % Load curve

Negative Sequence Curve

Thermal withstand characteristic

Torque vs Speed Curve

Starting Current vs Time curve

595kW 4pole DC400F3

Datasheet

GA Drawing

Current vs Speed Curve

Efficiency and Power Factor vs % Load curve

5
6

Negative Sequence Curve


Thermal withstand characteristic

NTPC Doc No :

9464-001-PVE-B-0105 Rev-2

Rev. :

Dated :

04.01.10

Page 2 OF 3

LARSEN & TOUBRO LIMITED - ECC GROUP

Project :

ANPARA THERMAL POWER PROJECT, STAGE-D.

Title :

HT MOTOR DATASHEET, GA, CURVES AND T.BOX DRAWING

Sub title :

INDEX

Doc No. :

(4)G71400-X4083-Z046-2
O9075-E-BM-CS-DD-0105 - Rev-2

L&T Doc No. :

Torque vs Speed Curve

Starting Current vs Time curve

510kW 10pole DC500U

Datasheet

GA Drawing

Current vs Speed Curve

Efficiency and Power Factor vs % Load curve

Negative Sequence Curve

Thermal withstand characteristic

Torque vs Speed Curve

Starting Current vs Time curve

Common Drawings for the above 5 motors

PSTB Drawing

2
3

Space heater Terminal Box Assembly


Arrangement of RTD and BTD terminal box

NTPC Doc No :

9464-001-PVE-B-0105 Rev-2

Rev. :

Dated :

04.01.10

Page 3 OF 3

LARSEN & TOUBRO LIMITED - ECC GROUP

Project :

ANPARA THERMAL POWER PROJECT, STAGE-D.

Title :

HT MOTOR DATASHEET, GA, CURVES AND T.BOX DRAWING

Sub title :

TECHNICAL DATASHEET FOR 3.3kV 220kW MOTOR

Doc No. :

(4)G71400-X4083-Z046-2
O9075-E-BM-CS-DD-0105 - Rev-2

L&T Doc No. :


NTPC Doc No :

9464-001-PVE-B-0105 Rev-2

Rev. :

Dated :

04.01.10

TECHNICAL DATASHEET FOR 3.3kV 220kW MOTOR

S.No

FEATURE

GENERAL

i)

Manufacturer & Country of origin

ii)

Equipment driven by motor

DESCRIPTION

MARATHON Electric Motors (India) Ltd


Conveyor

iii) Motor type

Sq. Cage Ind. Motor

iv) Quantity
2

9 Nos.

DESIGN AND PERFORMANCE DATA

i)

Frame size

ii)

Type of duty

DC280F710
S1(CMR)

iii) Type of enclosure and method of cooling, Degree of protection


iv) Applicable standard to which motor generally conforms
v) Type of mounting
vi) Direction of rotation as viewed from DE END
Standard continuous rating at 40 deg.C.
vii) ambient temp. as per Indian Standard (KW)
Derated rating for specified normal condition
viii) i.e. 50 deg. C ambient temperature (KW
xi) Rated Voltage (volts)
x) Permissible variation of
a) Voltage (Volts
b) Frequency (Hz)
c)Combined voltage and frequency3
xi) Minimum permissible starting Voltage (Volts)
xii) Rated speed at rated voltage and frequency
xiii) At rated Voltage and frequency
a)
Full load current
b)
No load current
xiv) Power Factor at
a) 100% /75%/50% load
b) NO load
c) Starting.
d) At Consumed power for 9A&B
e) At Consumed power for 3A/B
f) At Consumed power for 10A/B
f) At Consumed power for 6A/B
xv) Efficiency at rated voltage and frequency,
a) 100% load
b) 75% load
c) 50% load
d) At Consumed power for 9A&B
e) At Consumed power for 3A/B
f) At Consumed power for 10A/B
f) At Consumed power for 6A/B
xvi) Starting current (amps) at
a) 100 % voltage
b) 85% voltage
c) 80% voltage

Page 1 OF 4

TEFC/IC 411/IP55
IS:325,1996
Horizontal Foot ( B3)
Bi-directional
230KW
220KW
3300
(+/-)10%
(+/-)5%
10%
80% Vr
1485
47 Amps
15 Amps. (+10%)
0.88/0.86/0.76
0.13
0.21
0.83
0.86
0.77
0.79
94.00%
93.50%
92.50%
93.30%
93.50%
92.60%
92.90%
600% FLC
510% FLC
480% FLC

LARSEN & TOUBRO LIMITED - ECC GROUP

Project :

ANPARA THERMAL POWER PROJECT, STAGE-D.

Title :

HT MOTOR DATASHEET, GA, CURVES AND T.BOX DRAWING

Sub title :

TECHNICAL DATASHEET FOR 3.3kV 220kW MOTOR

Doc No. :

(4)G71400-X4083-Z046-2
O9075-E-BM-CS-DD-0105 - Rev-2

L&T Doc No. :


NTPC Doc No :

9464-001-PVE-B-0105 Rev-2

Rev. :

Dated :

04.01.10

xvii) Starting time with minimum permissible voltage


a) Without driven equipment coupled
b) With driven equipment coupled
xviii) Safe stall time with 110% of rated voltage
a) From hot condition
b) From cold condition
xix) Torques :
a) Starting torque at min. permissible voltage/rated volt (kg-mtr.)
b) Pull up torque at rated voltage.
c) Pull out torque
d) Min accelerating torque (kg.m) available
e) Rated torque (kg.m)
Stator winding resistance per phase (ohms at 20
xx) Deg.C.)
xxi) GD2 value of motors
No of permissible successive starts when
xxii) & motor is in hot condition.
xxiii) a. Locked rotor KVA input
b. Locked rotor KVA/KW
xxiv) Bearings
a) Type
b) Manufacturer
c) Self Lubricated or forced Lubricated
d) Recommended Lubricants
e) Guaranteed Life in Hours
f) Whether Dial Type thermometer provided
g) Oil pressure Gauge/switch
i. Range
ii. Contact Nos. & ratings
iii. Accuracy
xxv) Vibration
a) Velocity (mm/s)
b) Displacement (microns)
xxvi) Noise level (DB)
3 CONSTRUCTIONAL FEATURES
i) Stator winding insulation
a. Class & Type
b. Tropicalised (Yes/No)
c. Temperature rise over specified max.
i Cold water temperature of 38 DEG. C.
ii. Ambient Air 50 DEG. C.
d. Method of temperature measurement
e.Stator winding connection
f.Number of terminals brought out
ii) Type of terminal box for
a. stator leads
b. space heater
c. Temperature detectors
d. Instrument switch etc.
iii) For main terminal box
a. Location
b. Entry of cables
c.Recommended cable size (To be matched with cable size envisaged by
owner)
d.Fault level (MVA)

Page 2 OF 4

Less than 2 Secs


9 Secs..
12Secs
16 Secs.
90%/140 % FLT
130 % FLT
260 % FLT
58
145
0.268 ( +5%)
18 KgM2
3 Hot
Subject to max 750 starts per yr.
1595
7.25
Anti-Friction
NTN/FAG/SKF
Self
Grease
50,000 Hrs.
Yes
NA

As per IS:12075
As per IS:12075
85 dB (A) @ 1.5M

Cl`F / Resin poor VPI


Yes
NA
70 Deg. C
Resistance method
Star
3 for main & 3 for star point
PSTB
Separate T. Box
Separate T. Box
NA
As per GAD Drawing
Bottom
1 x 3C x 150 mm2, Al. XLPE
250MVA for 0.25 Secs. (See note 2)

LARSEN & TOUBRO LIMITED - ECC GROUP

Project :

ANPARA THERMAL POWER PROJECT, STAGE-D.

Title :

HT MOTOR DATASHEET, GA, CURVES AND T.BOX DRAWING

Sub title :

TECHNICAL DATASHEET FOR 3.3kV 220kW MOTOR

Doc No. :

(4)G71400-X4083-Z046-2
O9075-E-BM-CS-DD-0105 - Rev-2

L&T Doc No. :


NTPC Doc No :

9464-001-PVE-B-0105 Rev-2

Rev. :

Dated :

04.01.10

iv) Temperature detector for stator winding


a. Type
b. Nos. provided
c. Location
d. Make
e. Resistance value at 0 deg. C. (ohms)
v) Space Heaters
a. Number
b. Location
c. Power requirement (KW)
vi) Paint shade
vii) Weight of
a. Motor stator (KG)
b. Motor Rotor (KG)
c. Total weight (KG)
4 CHARACTERISTIC CURVES
i) Torque speed characteristic of the motor
ii) Thermal withstand characteristic
iii) Starting. current Vs. Time
iv) Starting. current Vs speed
v) Neg. sequence current vs Time..
vi) P.F. and Effi. Vs Load
vii) Temperature Switch (for CACA/CACW motors)
a. Type
b. Make
c. Nos. provided
d. Range
e. Accuracy
f. Connection type & size
g. Number of NO contact
h. Rating of NO contact
viii) Flow switch for forced oil in forced oil lubricated motors (for Alarm)
a. If provided number
b. Make
c. Type
d. Range
e. Accuracy
f. Connection type & size
g. Number of NO contacts
h. Rating of NO contact
ix) Cooling water requirement for CACW motors
a. Quantity Required (cubic metre/hr.)
b. Maximum permissible inlet water Temperature (degree cent)
c. Pressure of water at inlet to coolers (kg/metre sq. Gauge)
d. Outlet Temperature of water at full load (anticipated value)
x) Air Cooler
a. Type
b. Number Provided
c. Temperature of cold air at the outlet (deg. C)
xi) Oil Cooler
a. Type
b. Number provided
c. Temperature of cold air at the outlet (deg. C)
xii) Temperature detector for bearing
a. Make
b. Nos. provided
c. Resistance value at 0 deg. C. (ohms)

Page 3 OF 4

Pt.100, Simplex type


4 Nos. per phase
Between windings
Reputed make
100
2 Nos
Both ends
2 x 43 Watts
RAL 5012 (Blue)

2500 Kg
Enclosed
Enclosed
Enclosed
Enclosed
Enclosed
Enclosed

NA

NA

NA

No

NA

Reputed make
1 No. for each bearing
100

LARSEN & TOUBRO LIMITED - ECC GROUP

Project :

ANPARA THERMAL POWER PROJECT, STAGE-D.

Title :

HT MOTOR DATASHEET, GA, CURVES AND T.BOX DRAWING

Sub title :

TECHNICAL DATASHEET FOR 3.3kV 220kW MOTOR

Doc No. :

(4)G71400-X4083-Z046-2
O9075-E-BM-CS-DD-0105 - Rev-2

L&T Doc No. :

xiii) Temperature switch for bearing (DTT)


a. Type
b. Make
c. Accuracy
d. Range
e. Connection type and size
xiv) Speed switch provided Yes/No
xv) Neutral CT details (for motors above 2000 KW)
- Ratio
- Accuracy
class
(

NTPC Doc No :

9464-001-PVE-B-0105 Rev-2

Rev. :

Dated :

04.01.10

Dial Type thermometer


Reputed make
1 Deg.C
0 150 Deg.C
No

- selected control cable size


xvi) Surge Withstand Voltage
a. 0.3/3 Micro Second Surge (KVP)
b. 1.2/50 Micro-Second (KVP)

NA

12KV
18.2 KV

List of instruments and control items other than those covered in the
above clauses giving full particulars such as make, Type, range, accuracy
xvii) contact rating, connection type, size etc.
Note : 1) All above performance figures are subject to IS tolerance.
2) Our terminal box is suitable for 250 MVA for 0.25 sec. which is equivalent to 360MVA
for 0.12 sec.

Page 4 OF 4

NA

0
10
20
30
66.8
7.00
91.6
97.5
98
97.7
996.00
100

6.00
5.99
5.93
5.93
5.5
4.5
3
2
2
1
1

Current
-Speed
curve for 220KW,4 POLE,3300 V, DC280F710 Motor
4.8
6.6
4.792
4.744
4.744
4.4
3.6
2.4
2
2
1
1

6.589
6.523
6.523
6.05
4.95
3.3
2
2
1 % Volts
At 100
1

At 110% Volts

5.00

Current (xFLC)

At 80% Volts

4.00

3.00

285.4
300
2.00

1.00

0.00
0

20

40

Speed(%)
60

80

100

120

EFFICIENCY & POWER FACTOR VS % LOAD CURVE


220KW,4 POLE, 3300 V, DC280F710 Motor

96

0.9

94

0.85

% EFFICIENCY

90

88

0.8

86

84

POWER FACTOR

92

0.75

82

80

0.7
50

75

100

% LOAD
EFFICIENCY

MARATHON ELECTRIC MOTORS (INDIA) LTD.

POWER FACTOR

EFF-PF

Page 1

1
2
3
4
5
6

783.43
98.628
40.551
27.29
20.137
15

665.27
174.98
77.09
46.345
30.409
20

THERMAL WITHSTAND CHARACTERISTICS CURVE


220 KW, 4 POLE, 3300 V, DC280F710 Motor

TIME ( SECONDS )

1000

100

10
0

CURRENT ( X FLC )

Thermal_withstand

Marathon Electric Motors (I) Ltd.

Page 1

0
15.9
38.2
64.8
83.9
90
92.8
94.1
97
97.2

1.4
1.328
1.361
1.729
2.372
2.589
2.547
2.3
0.991
0

0.896
0.8499
0.871
1.1066
1.5181
1.657
1.6301
1.472
0.6342
0

0.02
1.694
0
0.193 1.60688
0.045
0.354TORQUE
1.64681
0.055CHARACTERISTIC CURVE
Vs. SPEED
0.38 2.09209
0.059 3300 V, DC280F710
220 KW, 4 POLE,
0.351 2.87012
0.06
0.342 3.13269
0.075
0.342 3.08187
0.08
0.342
2.783
0.09
0.334 1.19911
0.092
0.351
0
0.1

3.5

TORQUE ( X FLT )

2.5

1.5

0.5

0
0

20

40

60

80

100

% SPEED ( RPM )

Marathon Electric Motors (India) Ltd.

T-S

Page 1

Negative Sequence Curve


for 220KW, 4Pole, 3.3KV, DC280F710 Motor

8 2343.75
10
1500
20
375
30 166.6667
40
93.75
2000
50
60
1950
1900
1850
1800
1750
1700
1650
1600
1550
1500
1450
1400
1350
1300
1250

Time in Secs.

1200
1150
1100
1050
1000
950
900
850
800
750
700
650
600
550
500
450
400
350
300
250
200
150
100
50
0

10

20
30 Current ( %)
40
Negative Sequence

50

60

Starting
Current7.26
-%
6
5.1
5.99
5.0915
7.2479
5.93
5.0405
7.1753
5.93
5.0405
7.1753
5.88
4.998
7.1148
5.75
4.8875
3.7375
5.64
4.794
2
5.38
4.69
1
4.94
4.6
1.14
4.53
1
4.5
4.32
4.2
4.04
3.83
3.6
2.7
1.03
0.98
1

0
10
20
30
39.5
56.2
66.8
78.9
85
99.2
103.2
122.6
130
148.2
162.8
170.8
176.6
181.7
182.7
181.2
220
240
260
285.4
300

Current (xFLC)

6
5
4

Time curve for 220 KW, 4Pole, 3.3KV,DC280F710 Motor


(100% Time = 6 Sec)

At 100 % Volts
= 6 sec

At 80% Volts

3
2
1
0
0

50

Time ( %)
100
150

200

250

REV:01

LARSEN & TOUBRO LIMITED - ECC GROUP

Project :

ANPARA THERMAL POWER PROJECT, STAGE-D.

Title :

HT MOTOR DATASHEET, GA, CURVES AND T.BOX DRAWING

Sub title :

TECHNICAL DATASHEET FOR 3.3kV 345kW MOTOR

Doc No. :

(4)G71400-X4083-Z046-2

L&T Doc No. :

O9075-E-BM-CS-DD-0105 - Rev-2

NTPC Doc No :

9464-001-PVE-B-0105 Rev-2

Rev. :

Dated :

04.01.10

TECHNICAL DATASHEET FOR 3.3kV 345kW MOTOR

S.No

FEATURE

GENERAL

i)

Manufacturer & Country of origin

ii)

Equipment driven by motor

DESCRIPTION

MARATHON Electric Motors (India) Ltd


Conveyor
Sq. Cage Ind. Motor

iii) Motor type

5 Nos.

iv) Quantity
2

DESIGN AND PERFORMANCE DATA

i)

Frame size

DC355F3

ii)

Type of duty

S1(CMR)

iii) Type of enclosure and method of cooling, Degree of protection


iv) Applicable standard to which motor generally conforms
v) Type of mounting
vi) Direction of rotation as viewed from DE END
Standard continuous rating at 40 deg.C.
vii) ambient temp. as per Indian Standard (KW)
Derated rating for specified normal condition
viii) i.e. 50 deg. C ambient temperature (KW
xi) Rated Voltage (volts)
x) Permissible variation of
a) Voltage (Volts
b) Frequency (Hz)
c)Combined voltage and frequency3
xi) Minimum permissible starting Voltage (Volts)
xii) Rated speed at rated voltage and frequency
xiii) At rated Voltage and frequency
a)
Full load current
b)
No load current
xiv) Power Factor at
a) 100% /75%/50% load
b) NO load
c) Starting.
d) At Consumed power for 9A/B
e) At Consumed power for 5A/B
xv) Efficiency at rated voltage and frequency,
a) 100% load
b) 75% load
c) 50% load
d) At Consumed power for 9A/B
e) At Consumed power for 5A/B
xvi) Starting current (amps) at
a) 100 % voltage
b) 85% voltage
c) 80% voltage
xvii) Starting time with minimum permissible voltage
a) Without driven equipment coupled

Page 1 OF 4

TEFC/IC 411/IP55
IS:325,1996
Horizontal Foot ( B3)
Bi-directional
355KW
345KW
3300
(+/-)10%
(+/-)5%
10%
80% Vr
1489
74 Amps
24 Amps. (+10%)
0.86/0.84/0.74
0.11
0.21
0.76
0.85
94.30%
93.80%
92.80%
93.00%
94.00%
600% FLC
510% FLC
480% FLC
Less than 2 Secs

LARSEN & TOUBRO LIMITED - ECC GROUP

Project :

ANPARA THERMAL POWER PROJECT, STAGE-D.

Title :

HT MOTOR DATASHEET, GA, CURVES AND T.BOX DRAWING

Sub title :

TECHNICAL DATASHEET FOR 3.3kV 345kW MOTOR

Doc No. :

(4)G71400-X4083-Z046-2

L&T Doc No. :

O9075-E-BM-CS-DD-0105 - Rev-2

NTPC Doc No :

9464-001-PVE-B-0105 Rev-2

Rev. :

Dated :

04.01.10

b) With driven equipment coupled


xviii) Safe stall time with 110% of rated voltage
a) From hot condition
b) From cold condition
xix) Torques :
a) Starting torque at min. permissible voltage/rated volt (kg-mtr.)
b) Pull up torque at rated voltage.
c) Pull out torque
d) Min accelerating torque (kg.m) available
e) Rated torque (kg.m)
Stator winding resistance per phase (ohms at 20
xx) Deg.C.)
xxi) GD2 value of motors
No of permissible successive starts when
xxii) & motor is in hot condition.
xxiii) a. Locked rotor KVA input
b. Locked rotor KVA/KW
xxiv) Bearings
a) Type
b) Manufacturer
c) Self Lubricated or forced Lubricated
d) Recommended Lubricants
e) Guaranteed Life in Hours
f) Whether Dial Type thermometer provided
g) Oil pressure Gauge/switch
i. Range
ii. Contact Nos. & ratings
iii. Accuracy
xxv) Vibration
a) Velocity (mm/s)
b) Displacement (microns)
xxvi) Noise level (DB)
3 CONSTRUCTIONAL FEATURES
i) Stator winding insulation
a. Class & Type
b. Tropicalised (Yes/No)
c. Temperature rise over specified max.
i Cold water temperature of 38 DEG. C.
ii. Ambient Air 50 DEG. C.
d. Method of temperature measurement
e.Stator winding connection
f.Number of terminals brought out
ii) Type of terminal box for
a. stator leads
b. space heater
c. Temperature detectors
d. Instrument switch etc.
iii) For main terminal box
a. Location
b. Entry of cables
c.Recommended cable size (To be matched with cable size envisaged by
owner)
d.Fault level (MVA)

Page 2 OF 4

9 Secs..
12Secs
16 Secs.
82%/130 % FLT
120 % FLT
250 % FLT
89
226
0.15 ( +5%)
30 KgM2
3 Hot
Subject to max 750 starts per yr.
2503
7.4
Anti-Friction
NTN/FAG/SKF
Self
Grease
50,000 Hrs.
Yes
NA

As per IS:12075
As per IS:12075
85 dB (A) @ 1.5M

Cl`F / Resin poor VPI


Yes
NA
70 Deg. C
Resistance method
Star
3 for main & 3 for star point
PSTB
Separate T. Box
Separate T. Box
NA
As per GAD Drawing
Bottom
1 x 3C x 150 mm2, Al. XLPE
250MVA for 0.25 Secs. (See note 2)

LARSEN & TOUBRO LIMITED - ECC GROUP

Project :

ANPARA THERMAL POWER PROJECT, STAGE-D.

Title :

HT MOTOR DATASHEET, GA, CURVES AND T.BOX DRAWING

Sub title :

TECHNICAL DATASHEET FOR 3.3kV 345kW MOTOR

Doc No. :

(4)G71400-X4083-Z046-2

L&T Doc No. :

O9075-E-BM-CS-DD-0105 - Rev-2

NTPC Doc No :

9464-001-PVE-B-0105 Rev-2

Rev. :

Dated :

04.01.10

iv) Temperature detector for stator winding


a. Type
b. Nos. provided
c. Location
d. Make
e. Resistance value at 0 deg. C. (ohms)
v) Space Heaters
a. Number
b. Location
c. Power requirement (KW)
vi) Paint shade
vii) Weight of
a. Motor stator (KG)
b. Motor Rotor (KG)
c. Total weight (KG)
4 CHARACTERISTIC CURVES
i) Torque speed characteristic of the motor
ii) Thermal withstand characteristic
iii) Starting. current Vs. Time
iv) Starting. current Vs speed
v) Neg. sequence current vs Time..
vi) P.F. and Effi. Vs Load
vii) Temperature Switch (for CACA/CACW motors)
a. Type
b. Make
c. Nos. provided
d. Range
e. Accuracy
f. Connection type & size
g. Number of NO contact
h. Rating of NO contact
viii) Flow switch for forced oil in forced oil lubricated motors (for Alarm)
a. If provided number
b. Make
c. Type
d. Range
e. Accuracy
f. Connection type & size
g. Number of NO contacts
h. Rating of NO contact
ix) Cooling water requirement for CACW motors
a. Quantity Required (cubic metre/hr.)
b. Maximum permissible inlet water Temperature (degree cent)
c. Pressure of water at inlet to coolers (kg/metre sq. Gauge)
d. Outlet Temperature of water at full load (anticipated value)

Page 3 OF 4

Pt.100, Simplex type


4 Nos. per phase
Between windings
Reputed make
100
2 Nos
Both ends
2 x 43 Watts
RAL 5012 (Blue)

3000 Kg
Enclosed
Enclosed
Enclosed
Enclosed
Enclosed
Enclosed

NA

NA

NA

LARSEN & TOUBRO LIMITED - ECC GROUP

x)

xi)

xii)

xiii)

xiv)
xv)

Project :

ANPARA THERMAL POWER PROJECT, STAGE-D.

Title :

HT MOTOR DATASHEET, GA, CURVES AND T.BOX DRAWING

Sub title :

TECHNICAL DATASHEET FOR 3.3kV 345kW MOTOR

Doc No. :

(4)G71400-X4083-Z046-2

L&T Doc No. :

O9075-E-BM-CS-DD-0105 - Rev-2

NTPC Doc No :

9464-001-PVE-B-0105 Rev-2

Rev. :

Dated :

04.01.10

Air Cooler
a. Type
b. Number Provided
c. Temperature of cold air at the outlet (deg. C)
Oil Cooler
a. Type
b. Number provided
c. Temperature of cold air at the outlet (deg. C)
Temperature detector for bearing
a. Make
b. Nos. provided
c. Resistance value at 0 deg. C. (ohms)
Temperature switch for bearing (DTT)
a. Type
b. Make
c. Accuracy
d. Range
e. Connection type and size
Speed switch provided Yes/No
Neutral CT details (for motors above 2000 KW)
- Ratio
- Accuracy class

No

NA

Reputed make
1 No. for each bearing
100
Dial Type thermometer
Reputed make
1 Deg.C
0 150 Deg.C
No

NA

- selected control cable size


xvi) Surge Withstand Voltage
a. 0.3/3 Micro Second Surge (KVP)
b. 1.2/50 Micro-Second (KVP)

12KV
18.2 KV

List of instruments and control items other than those covered in the
above clauses giving full particulars such as make, Type, range, accuracy
xvii) contact rating, connection type, size etc.
Note : 1) All above performance figures are subject to IS tolerance.
2) Our terminal box is suitable for 250 MVA for 0.25 sec. which is equivalent to 360MVA
for 0.12 sec.

Page 4 OF 4

NA

2 NOS.

0
10
20
30
66.8
91.6
7.00
97.5
98
97.7
99
6.00
100

6.00
5.99
5.93
5.93
5.5
4.5
3
2
2
1
1

Current
-Speed
curve for 345KW,4 POLE,3300 V, DC355F3 Motor
4.8
6.6
4.792
4.744
4.744
4.4
3.6
2.4
2
2
1
1

6.589
6.523
6.523
6.05
4.95
3.3
2
2
1 % Volts
At 100
1

Current (xFLC)

5.00

At 110% Volts

At 80% Volts

4.00

3.00

285.4
300
2.00

1.00

0.00
0

20

40

Speed(%)
60

80

100

120

EFFICIENCY & POWER FACTOR VS % LOAD CURVE


345KW,4 POLE, 3300 V, DC355F3 Motor

0.9

96

94
0.85

92

% EFFICIENCY

90

0.75

88

86

POWER FACTOR

0.8

0.7

84
0.65
82

80

0.6
50

75

100

% LOAD

EFFICIENCY

MARATHON ELECTRIC MOTORS (INDIA) LTD.

POWER FACTOR

EFF-PF

Page 1
rev:01

Negative Sequence Curve


for 345KW, 4Pole, 3.3KV, DC355F3 Motor

8 2343.75
10
1500
20
375
30 166.6667
40
93.75
2000
50
60
1950
1900
1850
1800
1750
1700
1650
1600
1550
1500
1450
1400
1350
1300
1250

Time in Secs.

1200
1150
1100
1050
1000
950
900
850
800
750
700
650
600
550
500
450
400
350
300
250
200
150
100
50
0

10

20
30 Current ( %)
40
Negative Sequence

50

60

THERMAL WITHSTAND CHARACTERISTICS CURVE


345 KW, 4 POLE, 3300 V, DC355F3 Motor

TIME ( SECONDS )

1000

100

10
0

CURRENT ( X FLC )
Marathon Electric Motors (I) Ltd.

Thermal_withstand Chart 3

Page 1

0
15.9
38.2
64.8
86.1
90
92.8
94.1
97
97.2

1.3
1.228
1.261
1.72
2.439
2.589
2.547
2.272
0.991
0

0.832
0.7859
0.807
1.1008
1.561
1.657
1.6301
1.4541
0.6342
0

0.02
1.573
0
0.193 1.48588
0.045
0.354TORQUE
1.52581
0.055CHARACTERISTIC CURVE
Vs. SPEED
0.38
2.0812
345 KW, 40.059
POLE, 3300 V, DC355F3
0.351 2.95119
0.06
0.342 3.13269
0.075
0.342 3.08187
0.08
0.342 2.74912
0.09
0.334 1.19911
0.092
0.351
0
0.1

3.5

TORQUE ( X FLT )

2.5

1.5

0.5

0
0

20

40

60

80

100

% SPEED ( RPM )

Marathon Electric Motors (India) Ltd.

T-S

Page 1

Starting
Current
-%
6
5.1
7.26
5.99
5.0915
7.2479
5.93
5.0405
7.1753
5.93
5.0405
7.1753
5.88
4.998
7.1148
5.75
4.8875
3.7375
5.64
4.794
2
5.38
4.69
1
4.94
4.6
1.14
4.53
1
4.5
4.32
4.2
4.04
3.83
3.6
2.7
1.03
0.98
1

0
10
20
30
39.5
56.2
66.8
78.9
85
99.2
103.2
122.6
130
148.2
162.8
170.8
176.6
181.7
182.7
181.2
220
240
260
285.4
300

Current (xFLC)

6
5
4

Time curve for 345 KW, 4Pole, 3.3KV,DC355F3 Motor


(100% Time = 6 Sec)

At 100 % Volts
= 6 sec

At 80% Volts

3
2
1
0
0

50

Time ( %)
100
150

200

250

REV:01

LARSEN & TOUBRO LIMITED - ECC GROUP

Project :

ANPARA THERMAL POWER PROJECT, STAGE-D.

Title :

HT MOTOR DATASHEET, GA, CURVES AND T.BOX DRAWING

Sub title :

TECHNICAL DATASHEET FOR 3.3kV 430kW MOTOR

Doc No. :

(4)G71400-X4083-Z046-2

L&T Doc No. :

O9075-E-BM-CS-DD-0105 - Rev-2

NTPC Doc No :

9464-001-PVE-B-0105 Rev-2

Rev. :

Dated :

04.01.10

TECHNICAL DATASHEET FOR 3.3kV 430kW MOTOR

S.No

FEATURE

GENERAL

i)

Manufacturer & Country of origin

ii)

Equipment driven by motor

DESCRIPTION

MARATHON Electric Motors (India) Ltd


Conveyor

iii) Motor type

Sq. Cage Ind. Motor

iv) Quantity
2

DESIGN AND PERFORMANCE DATA

i)

Frame size

ii)

Type of duty

3 Nos.
DC355F3
S1(CMR)

iii) Type of enclosure and method of cooling, Degree of protection


iv) Applicable standard to which motor generally conforms
v) Type of mounting
vi) Direction of rotation as viewed from DE END
Standard continuous rating at 40 deg.C.
vii) ambient temp. as per Indian Standard (KW)
Derated rating for specified normal condition
viii) i.e. 50 deg. C ambient temperature (KW
xi) Rated Voltage (volts)
x) Permissible variation of
a) Voltage (Volts
b) Frequency (Hz)
c)Combined voltage and frequency3
xi) Minimum permissible starting Voltage (Volts)
xii) Rated speed at rated voltage and frequency
xiii) At rated Voltage and frequency
a)
Full load current
b)
No load current
xiv) Power Factor at
a) 100% /75%/50% load
b) NO load
c) Starting.
d) At Consumed power for 2A/B
xv) Efficiency at rated voltage and frequency,
a) 100% load
b) 75% load
c) 50% load
d) At Consumed power for 2A/B
xvi) Starting current (amps) at
a) 100 % voltage
b) 85% voltage
c) 80% voltage
xvii) Starting time with minimum permissible voltage
a) Without driven equipment coupled
b) With driven equipment coupled

Page 1 OF 4

TEFC/IC 411/IP55
IS:325,1996
Horizontal Foot ( B3)
Bi-directional
440KW
430KW
3300
(+/-)10%
(+/-)5%
10%
80% Vr
1489
94 Amps
29 Amps. (+10%)
0.85/0.83/0.73
0.12
0.21
0.84
94.50%
94.00%
93.00%
94.10%
600% FLC
510% FLC
480% FLC
Less than 2 Secs
9 Secs..

LARSEN & TOUBRO LIMITED - ECC GROUP

Project :

ANPARA THERMAL POWER PROJECT, STAGE-D.

Title :

HT MOTOR DATASHEET, GA, CURVES AND T.BOX DRAWING

Sub title :

TECHNICAL DATASHEET FOR 3.3kV 430kW MOTOR

Doc No. :

(4)G71400-X4083-Z046-2

L&T Doc No. :

O9075-E-BM-CS-DD-0105 - Rev-2

NTPC Doc No :

9464-001-PVE-B-0105 Rev-2

Rev. :

Dated :

04.01.10

xviii) Safe stall time with 110% of rated voltage


a) From hot condition
b) From cold condition
xix) Torques :
a) Starting torque at min. permissible voltage/rated volt (kg-mtr.)
b) Pull up torque at rated voltage.
c) Pull out torque
d) Min accelerating torque (kg.m) available
e) Rated torque (kg.m)
Stator winding resistance per phase (ohms at 20
xx) Deg.C.)
xxi) GD2 value of motors
No of permissible successive starts when
xxii) & motor is in hot condition.
xxiii) a. Locked rotor KVA input
b. Locked rotor KVA/KW
xxiv) Bearings
a) Type
b) Manufacturer
c) Self Lubricated or forced Lubricated
d) Recommended Lubricants
e) Guaranteed Life in Hours
f) Whether Dial Type thermometer provided
g) Oil pressure Gauge/switch
i. Range
ii. Contact Nos. & ratings
iii. Accuracy
xxv) Vibration
a) Velocity (mm/s)
b) Displacement (microns)
xxvi) Noise level (DB)
3 CONSTRUCTIONAL FEATURES
i) Stator winding insulation
a. Class & Type
b. Tropicalised (Yes/No)
c. Temperature rise over specified max.
i Cold water temperature of 38 DEG. C.
ii. Ambient Air 50 DEG. C.
d. Method of temperature measurement
e.Stator winding connection
f.Number of terminals brought out
ii) Type of terminal box for
a. stator leads
b. space heater
c. Temperature detectors
d. Instrument switch etc.
iii) For main terminal box
a. Location
b. Entry of cables
c.Recommended cable size (To be matched with cable size envisaged by
owner)
d.Fault level (MVA)

Page 2 OF 4

12Secs
16 Secs.
90%/140 % FLT
130 % FLT
240 % FLT
112
282
0.11 ( +5%)
34 KgM2
3 Hot
Subject to max 750 starts per yr.
3189
7.4
Anti-Friction
NTN/FAG/SKF
Self
Grease
50,000 Hrs.
Yes
NA

As per IS:12075
As per IS:12075
85 dB (A) @ 1.5M

Cl`F / Resin poor VPI


Yes
NA
70 Deg. C
Resistance method
Star
3 for main & 3 for star point
PSTB
Separate T. Box
Separate T. Box
NA
As per GAD Drawing
Bottom
1 x 3C x 150 mm2, Al. XLPE
250MVA for 0.25 Secs. (See note 2)

LARSEN & TOUBRO LIMITED - ECC GROUP

Project :

ANPARA THERMAL POWER PROJECT, STAGE-D.

Title :

HT MOTOR DATASHEET, GA, CURVES AND T.BOX DRAWING

Sub title :

TECHNICAL DATASHEET FOR 3.3kV 430kW MOTOR

Doc No. :

(4)G71400-X4083-Z046-2

L&T Doc No. :

O9075-E-BM-CS-DD-0105 - Rev-2

NTPC Doc No :

9464-001-PVE-B-0105 Rev-2

Rev. :

Dated :

04.01.10

iv) Temperature detector for stator winding


a. Type
b. Nos. provided
c. Location
d. Make
e. Resistance value at 0 deg. C. (ohms)
v) Space Heaters
a. Number
b. Location
c. Power requirement (KW)
vi) Paint shade
vii) Weight of
a. Motor stator (KG)
b. Motor Rotor (KG)
c. Total weight (KG)
4 CHARACTERISTIC CURVES
i) Torque speed characteristic of the motor
ii) Thermal withstand characteristic
iii) Starting. current Vs. Time
iv) Starting. current Vs speed
v) Neg. sequence current vs Time..
vi) P.F. and Effi. Vs Load
vii) Temperature Switch (for CACA/CACW motors)
a. Type
b. Make
c. Nos. provided
d. Range
e. Accuracy
f. Connection type & size
g. Number of NO contact
h. Rating of NO contact
viii) Flow switch for forced oil in forced oil lubricated motors (for Alarm)
a. If provided number
b. Make
c. Type
d. Range
e. Accuracy
f. Connection type & size
g. Number of NO contacts
h. Rating of NO contact
ix) Cooling water requirement for CACW motors
a. Quantity Required (cubic metre/hr.)
b. Maximum permissible inlet water Temperature (degree cent)
c. Pressure of water at inlet to coolers (kg/metre sq. Gauge)
d. Outlet Temperature of water at full load (anticipated value)
x) Air Cooler
a. Type
b. Number Provided
c. Temperature of cold air at the outlet (deg. C)
xi) Oil Cooler
a. Type
b. Number provided
c. Temperature of cold air at the outlet (deg. C)

Page 3 OF 4

Pt.100, Simplex type


4 Nos. per phase
Between windings
Reputed make
100
2 Nos
Both ends
2 x 43 Watts
RAL 5012 (Blue)

3200 Kg
Enclosed
Enclosed
Enclosed
Enclosed
Enclosed
Enclosed

NA

NA

NA

No

NA

LARSEN & TOUBRO LIMITED - ECC GROUP

Project :

ANPARA THERMAL POWER PROJECT, STAGE-D.

Title :

HT MOTOR DATASHEET, GA, CURVES AND T.BOX DRAWING

Sub title :

TECHNICAL DATASHEET FOR 3.3kV 430kW MOTOR

Doc No. :

(4)G71400-X4083-Z046-2

L&T Doc No. :

O9075-E-BM-CS-DD-0105 - Rev-2

NTPC Doc No :

9464-001-PVE-B-0105 Rev-2

Rev. :

Dated :

04.01.10

xii) Temperature detector for bearing


a. Make
b. Nos. provided
c. Resistance value at 0 deg. C. (ohms)
xiii) Temperature switch for bearing (DTT)
a. Type
b. Make
c. Accuracy
d. Range
e. Connection type and size
xiv) Speed switch provided Yes/No
xv) Neutral CT details (for motors above 2000 KW)
- Ratio
- Accuracy class

Reputed make
1 No. for each bearing
100
Dial Type thermometer
Reputed make
1 Deg.C
0 150 Deg.C
No

NA

- selected control cable size


xvi) Surge Withstand Voltage
a. 0.3/3 Micro Second Surge (KVP)
b. 1.2/50 Micro-Second (KVP)

12KV
18.2 KV

List of instruments and control items other than those covered in the
above clauses giving full particulars such as make, Type, range, accuracy
xvii) contact rating, connection type, size etc.
Note : 1) All above performance figures are subject to IS tolerance.
2) Our terminal box is suitable for 250 MVA for 0.25 sec. which is equivalent to 360MVA
for 0.12 sec.

Page 4 OF 4

NA

2 NOS.

0
10
20
30
66.8
91.67.00
97.5
98
97.7
996.00
100

6.00
5.99
5.93
5.93
5.5
4.5
3
2
2
1
1

Current
-Speed
curve for 430KW,4 POLE,3300 V, DC355F3 Motor
4.8
6.6
4.792
4.744
4.744
4.4
3.6
2.4
2
2
1
1

6.589
6.523
6.523
6.05
4.95
3.3
2
2
1 % Volts
At 100
1

Current (xFLC)

5.00

At 110% Volts

At 80% Volts

4.00

3.00

285.4
300
2.00

1.00

0.00
0

20

40

Speed(%)
60

80

100

120

EFFICIENCY & POWER FACTOR VS % LOAD CURVE


430KW,4 POLE, 3300 V, DC355F3 Motor

96

0.9

94

0.85

% EFFICIENCY

90

88

0.8

86

84

POWER FACTOR

92

0.75

82

80

0.7
50

75

100

% LOAD
EFFICIENCY

MARATHON ELECTRIC MOTORS (INDIA) LTD.

POWER FACTOR

EFF-PF

Page 1

Negative Sequence Curve


for 430KW, 4Pole, 3.3KV, DC355F3 Motor

8 2343.75
10
1500
20
375
30 166.6667
40
93.75
2000
50
60
1950
1900
1850
1800
1750
1700
1650
1600
1550
1500
1450
1400
1350
1300
1250

Time in Secs.

1200
1150
1100
1050
1000
950
900
850
800
750
700
650
600
550
500
450
400
350
300
250
200
150
100
50
0

10

20
30 Current ( %)
40
Negative Sequence

50

60

THERMAL WITHSTAND CHARACTERISTICS CURVE


430 KW, 4 POLE, 3300 V, DC355F3 Motor

TIME ( SECONDS )

1000

100

10
0

CURRENT ( X FLC )
Marathon Electric Motors (I) Ltd.

Thermal_withstand Chart 3

Page 1

0
15.9
38.2
64.8
85.8
90
92.2
94.1
97
97.2

1.4
1.3
1.395
1.737
2.288
2.389
2.364
2.23
0.991
0

0.896
0.832
0.8928
1.1117
1.4643
1.529
1.513
1.4272
0.6342
0

0.02
1.694
0
0.193
1.573
0.045
0.354TORQUE
1.68795
0.055CHARACTERISTIC CURVE
Vs. SPEED
0.38 2.10177
430 KW, 40.059
POLE, 3300 V, DC355F3
0.351 2.76848
0.06
0.342 2.89069
0.075
0.342 2.86044
0.08
0.342
2.6983
0.09
0.334 1.19911
0.092
0.351
0
0.1

3.5

TORQUE ( X FLT )

2.5

1.5

0.5

0
0

20

40

60

80

100

% SPEED ( RPM )

Marathon Electric Motors (India) Ltd.

T-S

Page 1

0
10
20
30
39.5
56.2
66.8
78.9
85
99.2
103.2
122.6
130
148.2
162.8
170.8
176.6
181.7
182.7
181.2
220
240
260
285.4
300

Starting
Current
- 7.26
% Time curve for 430 KW, 4Pole, 3.3KV,DC355F3 (100% Time =
6
5.1
5.99
5.0915
7.2479
6 Sec)
5.93
5.93
5.88
5.75
5.64
5.38
4.94
1.14
1

Current (xFLC)

6
5
4

5.0405
5.0405
4.998
4.8875
4.794
4.69
4.6
4.53
4.5
4.32
4.2
4.04
3.83
3.6
2.7
1.03
0.98
1

7.1753
7.1753
7.1148
3.7375
2
1

At 100 % Volts
= 6 sec

At 80% Volts

3
2
1
0
0

50

Time ( %)
100
150

200

250

REV:01

LARSEN & TOUBRO LIMITED - ECC GROUP

Project :

ANPARA THERMAL POWER PROJECT, STAGE-D.

Title :

HT MOTOR DATASHEET, GA, CURVES AND T.BOX DRAWING

Sub title :

TECHNICAL DATASHEET FOR 3.3kV 595kW MOTOR

Doc No. :

(4)G71400-X4083-Z046-2

L&T Doc No. :

O9075-E-BM-CS-DD-0105 - Rev-2

NTPC Doc No :

9464-001-PVE-B-0105 Rev-2

Rev. :

Dated :

04.01.10

TECHNICAL DATASHEET FOR 3.3kV 595kW MOTOR

S.No

FEATURE

GENERAL

i)

Manufacturer & Country of origin

ii)

Equipment driven by motor

DESCRIPTION

MARATHON Electric Motors (India) Ltd


Conveyor
Sq. Cage Ind. Motor

iii) Motor type


iv) Quantity
2

DESIGN AND PERFORMANCE DATA

i)

Frame size

ii)

Type of duty

3 Nos.
DC400F3
S1(CMR)

iii) Type of enclosure and method of cooling, Degree of protection


iv) Applicable standard to which motor generally conforms
v) Type of mounting
vi) Direction of rotation as viewed from DE END
Standard continuous rating at 40 deg.C.
vii) ambient temp. as per Indian Standard (KW)
Derated rating for specified normal condition
viii) i.e. 50 deg. C ambient temperature (KW
xi) Rated Voltage (volts)
x) Permissible variation of
a) Voltage (Volts
b) Frequency (Hz)
c)Combined voltage and frequency3
xi) Minimum permissible starting Voltage (Volts)
xii) Rated speed at rated voltage and frequency
xiii) At rated Voltage and frequency
a)
Full load current
b)
No load current
xiv) Power Factor at
a) 100% /75%/50% load
b) NO load
c) Starting.
d) At Consumed power for 4A/B
xv) Efficiency at rated voltage and frequency,
a) 100% load
b) 75% load
c) 50% load
d) At Consumed power for 4A/B
xvi) Starting current (amps) at
a) 100 % voltage
b) 85% voltage
c) 80% voltage
xvii) Starting time with minimum permissible voltage
a) Without driven equipment coupled
b) With driven equipment coupled

Page 1 OF 4

TEFC/IC 411/IP55
IS:325,1996
Horizontal Foot ( B3)
Bi-directional
605KW
595KW
3300
(+/-)10%
(+/-)5%
10%
80% Vr
1491
127 Amps
39 Amps. (+10%)
0.86/0.84/0.748
0.1
0.21
0.85
95.00%
94.50%
93.50%
94.70%
600% FLC
510% FLC
480% FLC
Less than 2 Secs
9 Secs..

LARSEN & TOUBRO LIMITED - ECC GROUP

Project :

ANPARA THERMAL POWER PROJECT, STAGE-D.

Title :

HT MOTOR DATASHEET, GA, CURVES AND T.BOX DRAWING

Sub title :

TECHNICAL DATASHEET FOR 3.3kV 595kW MOTOR

Doc No. :

(4)G71400-X4083-Z046-2

L&T Doc No. :

O9075-E-BM-CS-DD-0105 - Rev-2

NTPC Doc No :

9464-001-PVE-B-0105 Rev-2

Rev. :

Dated :

04.01.10

xviii) Safe stall time with 110% of rated voltage


a) From hot condition
b) From cold condition
xix) Torques :
a) Starting torque at min. permissible voltage/rated volt (kg-mtr.)
b) Pull up torque at rated voltage.
c) Pull out torque
d) Min accelerating torque (kg.m) available
e) Rated torque (kg.m)
Stator winding resistance per phase (ohms at 20
xx) Deg.C.)
xxi) GD2 value of motors
No of permissible successive starts when
xxii) & motor is in hot condition.
xxiii) a. Locked rotor KVA input
b. Locked rotor KVA/KW
xxiv) Bearings
a) Type
b) Manufacturer
c) Self Lubricated or forced Lubricated
d) Recommended Lubricants
e) Guaranteed Life in Hours
f) Whether Dial Type thermometer provided
g) Oil pressure Gauge/switch
i. Range
ii. Contact Nos. & ratings
iii. Accuracy
xxv) Vibration
a) Velocity (mm/s)
b) Displacement (microns)
xxvi) Noise level (DB)
3 CONSTRUCTIONAL FEATURES
i) Stator winding insulation
a. Class & Type
b. Tropicalised (Yes/No)
c. Temperature rise over specified max.
i Cold water temperature of 38 DEG. C.
ii. Ambient Air 50 DEG. C.
d. Method of temperature measurement
e.Stator winding connection
f.Number of terminals brought out
ii) Type of terminal box for
a. stator leads
b. space heater
c. Temperature detectors
d. Instrument switch etc.
iii) For main terminal box
a. Location
b. Entry of cables
c.Recommended cable size (To be matched with cable size envisaged by
owner)
d.Fault level (MVA)

Page 2 OF 4

12Secs
16 Secs.
76%/120 % FLT
110 % FLT
250 % FLT
156
390
0.07 ( +5%)
60 KgM2
3 Hot
Subject to max 750 starts per yr.
4338
7.3
Anti-Friction
NTN/FAG/SKF
Self
Grease
50,000 Hrs.
Yes
NA

As per IS:12075
As per IS:12075
85 dB (A) @ 1.5M

Cl`F / Resin poor VPI


Yes
NA
70 Deg. C
Resistance method
Star
3 for main & 3 for star point
PSTB
Separate T. Box
Separate T. Box
NA
As per GAD Drawing
Bottom
1 x 3C x 150 mm2, Al. XLPE
250MVA for 0.25 Secs. (See note 2)

LARSEN & TOUBRO LIMITED - ECC GROUP

Project :

ANPARA THERMAL POWER PROJECT, STAGE-D.

Title :

HT MOTOR DATASHEET, GA, CURVES AND T.BOX DRAWING

Sub title :

TECHNICAL DATASHEET FOR 3.3kV 595kW MOTOR

Doc No. :

(4)G71400-X4083-Z046-2

L&T Doc No. :

O9075-E-BM-CS-DD-0105 - Rev-2

NTPC Doc No :

9464-001-PVE-B-0105 Rev-2

Rev. :

Dated :

04.01.10

iv) Temperature detector for stator winding


a. Type
b. Nos. provided
c. Location
d. Make
e. Resistance value at 0 deg. C. (ohms)
v) Space Heaters
a. Number
b. Location
c. Power requirement (KW)
vi) Paint shade
vii) Weight of
a. Motor stator (KG)
b. Motor Rotor (KG)
c. Total weight (KG)
4 CHARACTERISTIC CURVES
i) Torque speed characteristic of the motor
ii) Thermal withstand characteristic
iii) Starting. current Vs. Time
iv) Starting. current Vs speed
v) Neg. sequence current vs Time..
vi) P.F. and Effi. Vs Load
vii) Temperature Switch (for CACA/CACW motors)
a. Type
b. Make
c. Nos. provided
d. Range
e. Accuracy
f. Connection type & size
g. Number of NO contact
h. Rating of NO contact
viii) Flow switch for forced oil in forced oil lubricated motors (for Alarm)
a. If provided number
b. Make
c. Type
d. Range
e. Accuracy
f. Connection type & size
g. Number of NO contacts
h. Rating of NO contact
ix) Cooling water requirement for CACW motors
a. Quantity Required (cubic metre/hr.)
b. Maximum permissible inlet water Temperature (degree cent)
c. Pressure of water at inlet to coolers (kg/metre sq. Gauge)
d. Outlet Temperature of water at full load (anticipated value)
x) Air Cooler
a. Type
b. Number Provided
c. Temperature of cold air at the outlet (deg. C)

Page 3 OF 4

Pt.100, Simplex type


4 Nos. per phase
Between windings
Reputed make
100
2 Nos
Both ends
2 x 65 Watts
RAL 5012 (Blue)

3900 Kg
Enclosed
Enclosed
Enclosed
Enclosed
Enclosed
Enclosed

NA

NA

NA

No

LARSEN & TOUBRO LIMITED - ECC GROUP

Project :

ANPARA THERMAL POWER PROJECT, STAGE-D.

Title :

HT MOTOR DATASHEET, GA, CURVES AND T.BOX DRAWING

Sub title :

TECHNICAL DATASHEET FOR 3.3kV 595kW MOTOR

Doc No. :

(4)G71400-X4083-Z046-2

L&T Doc No. :

O9075-E-BM-CS-DD-0105 - Rev-2

NTPC Doc No :

9464-001-PVE-B-0105 Rev-2

Rev. :

Dated :

04.01.10

xi) Oil Cooler


a. Type
b. Number provided
c. Temperature of cold air at the outlet (deg. C)
xii) Temperature detector for bearing
a. Make
b. Nos. provided
c. Resistance value at 0 deg. C. (ohms)
xiii) Temperature switch for bearing (DTT)
a. Type
b. Make
c. Accuracy
d. Range
e. Connection type and size
xiv) Speed switch provided Yes/No
xv) Neutral CT details (for motors above 2000 KW)
- Ratio
- Accuracy
class
(
p

NA

Reputed make
1 No. for each bearing
100
Dial Type thermometer
Reputed make
1 Deg.C
0 150 Deg.C
No

- selected control cable size


xvi) Surge Withstand Voltage
a. 0.3/3 Micro Second Surge (KVP)
b. 1.2/50 Micro-Second (KVP)

NA

12KV
18.2 KV

List of instruments and control items other than those covered in the
above clauses giving full particulars such as make, Type, range, accuracy
xvii) contact rating, connection type, size etc.
Note : 1) All above performance figures are subject to IS tolerance.
2) Our terminal box is suitable for 250 MVA for 0.25 sec. which is equivalent to 360MVA
for 0.12 sec.

Page 4 OF 4

NA

0
10
20
30
66.8
91.67.00
97.5
98
97.7
996.00
100

6.00
5.99
5.93
5.93
5.5
4.5
3
2
2
1
1

Current
-Speed
curve for 595KW,4 POLE,3300 V, DC400F3 Motor
4.8
6.6
4.792
4.744
4.744
4.4
3.6
2.4
2
2
1
1

6.589
6.523
6.523
6.05
4.95
3.3
2
2
1 % Volts
At 100
1

Current (xFLC)

5.00

At 110% Volts

At 80% Volts

4.00

3.00

285.4
300
2.00

1.00

0.00
0

20

40

Speed(%)
60

80

100

120

EFFICIENCY & POWER FACTOR VS % LOAD CURVE


595KW,4 POLE, 3300 V, DC400F3 Motor

0.9

96

94

% EFFICIENCY

90

0.8

88

86

POWER FACTOR

0.85

92

0.75

84

82

80

0.7
50

75

100

% LOAD
EFFICIENCY

MARATHON ELECTRIC MOTORS (INDIA) LTD.

POWER FACTOR

EFF-PF

Page 1

Negative Sequence Curve


for 595KW, 4Pole, 3.3KV, DC400F3 Motor

8 2343.75
10
1500
20
375
30 166.6667
40
93.75
2000
50
60
1950
1900
1850
1800
1750
1700
1650
1600
1550
1500
1450
1400
1350
1300
1250

Time in Secs.

1200
1150
1100
1050
1000
950
900
850
800
750
700
650
600
550
500
450
400
350
300
250
200
150
100
50
0

10

20
30 Current ( %)
40
Negative Sequence

50

60

THERMAL WITHSTAND CHARACTERISTICS CURVE


595 KW, 4 POLE, 3300 V, DC400F3 Motor

TIME ( SECONDS )

1000

100

10
0

CURRENT ( X FLC )
Marathon Electric Motors (I) Ltd.

Thermal_withstand Chart 3

Page 1

0
15.9
38.2
64.8
85.8
90
92
94.1
97
97.2

1.2
1.119
1.228
1.687
2.4
2.589
2.556
2.272
0.991
0

0.768
0.7162
0.7859
1.0797
1.536
1.657
1.6358
1.4541
0.6342
0

0.02
1.452
0
0.193 1.35399
0.045
0.354TORQUE
1.48588
0.055CHARACTERISTIC CURVE
Vs. SPEED
0.38 2.04127
595 KW, 40.059
POLE, 3300 V, DC400F3
0.351
2.904
0.06
0.342 3.13269
0.075
0.342 3.09276
0.08
0.342 2.74912
0.09
0.334 1.19911
0.092
0.351
0
0.1

3.5

TORQUE ( X FLT )

2.5

1.5

0.5

0
0

20

40

60

80

100

% SPEED ( RPM )

Marathon Electric Motors (India) Ltd.

T-S

Page 1

6Starting
5.1Current
7.265.99
5.0915
7.2479
5.93
5.0405
7.1753
5.93
5.0405
7.1753
5.88
4.998
7.1148
5.75
4.8875
3.7375
5.64
4.794
2
5.38
4.69
1
4.94
4.6
1.14
4.53
1
4.5
4.32
4.2
4.04
3.83
3.6
2.7
1.03
0.98
1

0
10
20
30
39.5
56.2
66.8
78.9
85
99.2
103.2
122.6
130
148.2
162.8
170.8
176.6
181.7
182.7
181.2
220
240
260
285.4
300

Current (xFLC)

6
5
4

% Time curve for 595 KW, 4Pole, 3.3KV,DC400F3 Motor


(100% Time = 6 Sec)

At 100 % Volts
= 6 sec

At 80% Volts

3
2
1
0
0

50

Time ( %)
100
150

200

250

REV:01

LARSEN & TOUBRO LIMITED - ECC GROUP

Project :

ANPARA THERMAL POWER PROJECT, STAGE-D.

Title :

HT MOTOR DATASHEET, GA, CURVES AND T.BOX DRAWING

Sub title :

TECHNICAL DATASHEET FOR 3.3kV 510kW MOTOR

Doc No. :

(4)G71400-X4083-Z046-2
O9075-E-BM-CS-DD-0105 - Rev-2

L&T Doc No. :


NTPC Doc No :

9464-001-PVE-B-0105 Rev-2

Rev. :

Dated :

04.01.10

TECHNICAL DATASHEET FOR 3.3kV 510kW MOTOR

S.No

FEATURE

GENERAL

i)

Manufacturer & Country of origin

ii)

Equipment driven by motor

DESCRIPTION

MARATHON Electric Motors (India) Ltd


Crusher
Sq. Cage Ind. Motor

iii) Motor type

5 Nos.

iv) Quantity
2

DESIGN AND PERFORMANCE DATA

i)

Frame size

ii)

Type of duty

DC500U
S1(CMR)

iii) Type of enclosure and method of cooling, Degree of protection


iv) Applicable standard to which motor generally conforms
v) Type of mounting
vi) Direction of rotation as viewed from DE END
Standard continuous rating at 40 deg.C.
vii) ambient temp. as per Indian Standard (KW)
Derated rating for specified normal condition
viii) i.e. 50 deg. C ambient temperature (KW
xi) Rated Voltage (volts)
x) Permissible variation of
a) Voltage (Volts
b) Frequency (Hz)
c)Combined voltage and frequency3
xi) Minimum permissible starting Voltage (Volts)
xii) Rated speed at rated voltage and frequency
xiii) At rated Voltage and frequency
a)
Full load current
b)
No load current
xiv) Power Factor at
a) 100% /75%/50% load
b) NO load
c) Starting.
d) At Consumed power
xv) Efficiency at rated voltage and frequency,
a) 100% load
b) 75% load
c) 50% load
d) At Consumed power
xvi) Starting current (amps) at
a) 100 % voltage
b) 85% voltage
c) 80% voltage
xvii) Starting time with minimum permissible voltage
a) Without driven equipment coupled
b) With driven equipment coupled

Page 1 OF 4

CACA/IC 611/IP55
IS:325,1996
Horizontal Foot ( B3)
Bi-directional
520KW
510KW
3300
(+/-)10%
(+/-)5%
10%
80% Vr
594
128 Amps
63 Amps. (+10%)
0.75/0.68/0.58
0.08
0.21
0.7
93.80%
93.00%
92.00%
93.10%
600% FLC
510% FLC
480% FLC
Less than 2 Secs
9 Secs..

LARSEN & TOUBRO LIMITED - ECC GROUP

Project :

ANPARA THERMAL POWER PROJECT, STAGE-D.

Title :

HT MOTOR DATASHEET, GA, CURVES AND T.BOX DRAWING

Sub title :

TECHNICAL DATASHEET FOR 3.3kV 510kW MOTOR

Doc No. :

(4)G71400-X4083-Z046-2
O9075-E-BM-CS-DD-0105 - Rev-2

L&T Doc No. :


NTPC Doc No :

9464-001-PVE-B-0105 Rev-2

Rev. :

Dated :

04.01.10

xviii) Safe stall time with 110% of rated voltage


a) From hot condition
b) From cold condition
xix) Torques :
a) Starting torque at min. permissible voltage/rated volt (kg-mtr.)
b) Pull up torque at rated voltage.
c) Pull out torque
d) Min accelerating torque (kg.m) available
e) Rated torque (kg.m)
Stator winding resistance per phase (ohms at 20
xx) Deg.C.)
xxi) GD2 value of motors
No of permissible successive starts when
xxii) & motor is in hot condition.
xxiii) a. Locked rotor KVA input
b. Locked rotor KVA/KW
xxiv) Bearings
a) Type
b) Manufacturer
c) Self Lubricated or forced Lubricated
d) Recommended Lubricants
e) Guaranteed Life in Hours
f) Whether Dial Type thermometer provided
g) Oil pressure Gauge/switch
i. Range
ii. Contact Nos. & ratings
iii. Accuracy
xxv) Vibration
a) Velocity (mm/s)
b) Displacement (microns)
xxvi) Noise level (DB)
3 CONSTRUCTIONAL FEATURES
i) Stator winding insulation
a. Class & Type
b. Tropicalised (Yes/No)
c. Temperature rise over specified max.
i Cold water temperature of 38 DEG. C.
ii. Ambient Air 50 DEG. C.
d. Method of temperature measurement
e.Stator winding connection
f.Number of terminals brought out
ii) Type of terminal box for
a. stator leads
b. space heater
c. Temperature detectors
d. Instrument switch etc.
iii) For main terminal box
a. Location
b. Entry of cables
c.Recommended cable size (To be matched with cable size envisaged
by owner)
d.Fault level (MVA)

Page 2 OF 4

12Secs
16 Secs.
64%/100 % FLT
90 % FLT
270 % FLT
252
839
0.246 ( +5%)
240 KgM2
3 Hot
Subject to max 750 starts per yr.
4355
8.54
Anti-Friction
NTN/FAG/SKF
Self
Grease
50,000 Hrs.
Yes
NA

As per IS:12075
As per IS:12075
85 dB (A) @ 1.5M

Cl`F / Resin poor VPI


Yes
NA
70 Deg. C
Resistance method
Star
3 for main & 3 for star point
PSTB
Separate T. Box
Separate T. Box
NA
As per GAD Drawing
Bottom
1 x 3C x 150 mm2, Al. XLPE
250MVA for 0.25 Secs. (See note 2)

LARSEN & TOUBRO LIMITED - ECC GROUP

Project :

ANPARA THERMAL POWER PROJECT, STAGE-D.

Title :

HT MOTOR DATASHEET, GA, CURVES AND T.BOX DRAWING

Sub title :

TECHNICAL DATASHEET FOR 3.3kV 510kW MOTOR

Doc No. :

(4)G71400-X4083-Z046-2
O9075-E-BM-CS-DD-0105 - Rev-2

L&T Doc No. :


NTPC Doc No :

9464-001-PVE-B-0105 Rev-2

Rev. :

Dated :

04.01.10

iv) Temperature detector for stator winding


a. Type
b. Nos. provided
c. Location
d. Make
e. Resistance value at 0 deg. C. (ohms)
v) Space Heaters
a. Number
b. Location
c. Power requirement (KW)
vi) Paint shade
vii) Weight of
a. Motor stator (KG)
b. Motor Rotor (KG)
c. Total weight (KG)
4 CHARACTERISTIC CURVES
i) Torque speed characteristic of the motor
ii) Thermal withstand characteristic
iii) Starting. current Vs. Time
iv) Starting. current Vs speed
v) Neg. sequence current vs Time..
vi) P.F. and Effi. Vs Load
vii) Temperature Switch (for CACA/CACW motors)
a. Type
b. Make
c. Nos. provided
d. Range
e. Accuracy
f. Connection type & size
g. Number of NO contact
h. Rating of NO contact
viii) Flow switch for forced oil in forced oil lubricated motors (for Alarm)
a. If provided number
b. Make
c. Type
d. Range
e. Accuracy
f. Connection type & size
g. Number of NO contacts
h. Rating of NO contact
ix) Cooling water requirement for CACW motors
a. Quantity Required (cubic metre/hr.)
b. Maximum permissible inlet water Temperature (degree cent)
c. Pressure of water at inlet to coolers (kg/metre sq. Gauge)
d. Outlet Temperature of water at full load (anticipated value)
x) Air Cooler
a. Type
b. Number Provided
c. Temperature of cold air at the outlet (deg. C)

Page 3 OF 4

Pt.100, Simplex type


4 Nos. per phase
Between windings
Reputed make
100
4 Nos
Both ends
4 x 140 Watts
RAL 5012 (Blue)

7000 Kg
Enclosed
Enclosed
Enclosed
Enclosed
Enclosed
Enclosed

NA

NA

NA

No

LARSEN & TOUBRO LIMITED - ECC GROUP

Project :

ANPARA THERMAL POWER PROJECT, STAGE-D.

Title :

HT MOTOR DATASHEET, GA, CURVES AND T.BOX DRAWING

Sub title :

TECHNICAL DATASHEET FOR 3.3kV 510kW MOTOR

Doc No. :

(4)G71400-X4083-Z046-2
O9075-E-BM-CS-DD-0105 - Rev-2

L&T Doc No. :


NTPC Doc No :

9464-001-PVE-B-0105 Rev-2

Rev. :

Dated :

04.01.10

xi) Oil Cooler


a. Type
b. Number provided
c. Temperature of cold air at the outlet (deg. C)
xii) Temperature detector for bearing
a. Make
b. Nos. provided
c. Resistance value at 0 deg. C. (ohms)
xiii) Temperature switch for bearing (DTT)
a. Type
b. Make
c. Accuracy
d. Range
e. Connection type and size
xiv) Speed switch provided Yes/No
xv) Neutral CT details (for motors above 2000 KW)
- Ratio
- Accuracy class

NA

Reputed make
1 No. for each bearing
100
Dial Type thermometer
Reputed make
1 Deg.C
0 150 Deg.C

- selected control cable size


xvi) Surge Withstand Voltage
a. 0.3/3 Micro Second Surge (KVP)
b. 1.2/50 Micro-Second (KVP)

No

NA

12KV
18.2 KV

List of instruments and control items other than those covered in the
above clauses giving full particulars such as make, Type, range,
xvii) accuracy contact rating, connection type, size etc.
Note : 1) All above performance figures are subject to IS tolerance.
2) Our terminal box is suitable for 250 MVA for 0.25 sec. which is equivalent to 360MVA
for 0.12 sec.

Page 4 OF 4

NA

0
10
20
30
66.8
91.67.00
97.5
98
97.7
996.00
100

6.00
5.99
5.93
5.93
5.5
4.5
3
2
2
1
1

Current
-Speed
curve for 510KW,10 POLE,3300 V, DC500U Motor
4.8
6.6
4.792
4.744
4.744
4.4
3.6
2.4
2
2
1
1

6.589
6.523
6.523
6.05
4.95
3.3
2
2
1 % Volts
At 100
1

Current (xFLC)

5.00

At 110% Volts

At 80% Volts

4.00

3.00

285.4
300
2.00

1.00

0.00
0

20

40

Speed(%)
60

80

100

120

96

0.85

94

0.8

92

0.75

90

0.7

88

0.65

86

0.6

84

0.55

82

0.5

80

0.45
50

75

POWER FACTOR

% EFFICIENCY

EFFICIENCY & POWER FACTOR VS % LOAD CURVE


510KW,10 POLE, 3300 V, DC500U Motor

100

% LOAD
EFFICIENCY

MARATHON ELECTRIC MOTORS (INDIA) LTD.

POWER FACTOR

EFF-PF

Page 1

Negative Sequence Curve


for 510KW, 10Pole, 3.3KV, DC500U Motor

8 2343.75
10
1500
20
375
30 166.6667
40
93.75
2000
50
60
1950
1900
1850
1800
1750
1700
1650
1600
1550
1500
1450
1400
1350
1300
1250

Time in Secs.

1200
1150
1100
1050
1000
950
900
850
800
750
700
650
600
550
500
450
400
350
300
250
200
150
100
50
0

10

20
30 Current ( %)
40
Negative Sequence

50

60

THERMAL WITHSTAND CHARACTERISTICS CURVE


510 KW, 10 POLE, 3300 V, DC500U Motor

TIME ( SECONDS )

1000

100

10
0

CURRENT ( X FLC )
Marathon Electric Motors (I) Ltd.

Thermal_withstand Chart 3

Page 1

0
15.9
44.4
73.2
83.9
90
92.8
94.1
97
97.2

1
0.919
1.136
1.971
2.422
2.673
2.7
2.3
0.991
0

0.64
0.5882
0.727
1.2614
1.5501
1.7107
1.728
1.472
0.6342
0

0.02
1.21
0
0.193 1.11199
0.045
0.354TORQUE
1.37456
0.055CHARACTERISTIC CURVE
Vs. SPEED
0.38 2.38491
0.059
510 KW, 10
POLE, 3300 V, DC500U
0.351 2.93062
0.06
0.342 3.23433
0.075
0.342
3.267
0.08
0.342
2.783
0.09
0.334 1.19911
0.092
0.351
0
0.1

3.5

TORQUE ( X FLT )

2.5

1.5

0.5

0
0

20

40

60

80

100

% SPEED ( RPM )

Marathon Electric Motors (India) Ltd.

T-S

Page 1

0
10
20
30
39.5
56.2
66.8
78.9
85
99.2
103.2
122.6
130
148.2
162.8
170.8
176.6
181.7
182.7
181.2
220
240
260
285.4
300

6
5.99
5.93
5.93
5.88
5.75
5.64
5.38
4.94
1.14
1

Current (xFLC)

6
5
4

Starting
5.1 Current
7.26 - % Time curve for 510 KW, 10Pole, 3.3KV,DC500U Motor
5.0915
7.2479
(100% Time = 6 Sec)
5.0405
5.0405
4.998
4.8875
4.794
4.69
4.6
4.53
4.5
4.32
4.2
4.04
3.83
3.6
2.7
1.03
0.98
1

7.1753
7.1753
7.1148
3.7375
2
1

At 100 % Volts
= 6 sec

At 80% Volts

3
2
1
0
0

50

Time ( %)
100
150

200

250

REV:01