CALC EXAMPLE

ITEM
1
2
3
4
5
6
7
8
9
10

Octave band center

Procedure
Sound pressure level criterion
Room and terminal effect
Allowance for end reflection
Ductwork attenuation, terminal to checkpoint
Elbow attenuation, terminal to checkpoint
Power-level split, branch to terminals
Power-level split, main duct to branch duct
Totals
Sound power level of fan - Lw
Safety factors
Total sound power level of fan - Lw
Silencer requirements
3

125
57
5
10
6.96
6
6
10
100.96
87
3
90
-13.96

250
49
5
6
4.25
8
6
10
88.25
82.3
3
85.3
-5.95

Octave band center frequency, Hz


500
1000
2000
44
40
37
5
5
5
2
0
0
1.95
1.95
1.95
4
3
3
6
6
6
10
10
10
72.95
65.95
62.95
82.4
80.8
79
3
3
3
85.4
83.8
82
9.45
14.85
16.05

5
4000
35
5
0
1.95
3
6
10
60.95
76.9
3
79.9
15.95

8000
35
5
0
1.95
3
6
10
60.95
76.9
3
79.9
15.95

S-ar putea să vă placă și