Chapter 1 Description....................................... 5
Chapter 2 Installation..................................... 18
Chapter 3 Start-Up......................................... 30
Chapter 4 Troubleshooting............................. 32
Chapter 5 Maintenance................................... 35
Chapter 6 Warranty........................................ 36
Parts List & Exploded Views............................... 38
Manufactured By:
*
*
*
*
IMPORTANT is used to point out helpful suggestions that will result in improved installation, reliability or operation.
Downloaded from www.Manualslib.com manuals search engine
ComPac 6/09-18
WARNING
If the information in these instructions are not followed exactly, a fire may result
causing property damage, personal injury or loss of life.
Read all instructions carefully prior to beginning the installation. Do not begin
installation if you do not understand any of the instructions.
Improper installation, adjustment, alteration, service or maintenance can cause
property damage, personal injury or loss of life.
Installation and service must be performed by a qualified installer or service agency in
accordance with these instructions and in compliance with all codes and requirements
of authorities having jurisdiction.
INSTALLER: Affix the instructions on the inside of the building adjacent to the
thermostat.
END USER: Retain these instructions for future reference.
Table of Contents
Chapter 1 ComPac A/C Description & Specifications
1.1 General Description..................................................................................................................................5
1.2 Model Identification..................................................................................................................................5
1.3 Serial Number Date Code.........................................................................................................................5
1.4 Ratings and Specifications........................................................................................................................6
1.5 General Operation.....................................................................................................................................9
1.6 Electronic Control Board Mode of Operation.........................................................................................10
1.7 Optional Controls....................................................................................................................................12
1.8 Electrical Diagrams.................................................................................................................................13
1.9 Economizer Components........................................................................................................................16
Chapter 2 Installation
2.1 Equipment Inspection..............................................................................................................................18
2.2 Installation Requirements........................................................................................................................18
2.3 Installation Materials . ...........................................................................................................................19
2.4 Porting and Duct Work . .........................................................................................................................21
2.5 Fresh Air Hood Installation . ..................................................................................................................22
2.6 Bracket Installation ................................................................................................................................23
2.7 Mounting the Unit ..................................................................................................................................23
2.8 Electrical Connections............................................................................................................................24
Chapter 3 Start-Up
3.1 Check-Out of Cooling Cycle . ................................................................................................................30
3.2 Check-Out of Heating Cycle...................................................................................................................30
3.3 A/C Testing with LL357D4.....................................................................................................................31
Chapter 4 Troubleshooting
4.1 Overview.................................................................................................................................................32
4.2 Failure Symptoms Guide.........................................................................................................................32
4.3 Compressor Troubleshooting..................................................................................................................33
4.4 Control Board Diagnosis.........................................................................................................................34
Downloaded from www.Manualslib.com manuals search engine
ComPac 6/09-18
Table of Contents
Chapter 5 Maintenance
5.1 Scheduled Maintenance..........................................................................................................................35
Chapter 6 Warranty
6.1 Limited Product Warranty.......................................................................................................................36
6.2 Optional Silver Service Program............................................................................................................37
Parts List and Exploded Views......................................................................................................................38
Illustrations
Figure 1a.
1b.
1c.
Figure 2.
Figure 3a.
3b.
Figure 4.
Figure 5.
Figure 6.
Figure 7.
Figure 8a.
Figure 8b.
Figure 8c.
Figure 8d.
Tables
Table 1
Table 2
Table 3
Table 4
Table 5
Table 6
Downloaded from www.Manualslib.com manuals search engine
ComPac 6/09-18
Model Identification
The model identification number is found on the data sticker. Rating plate located on side panel.
AVP ** AC * * * *
E = 380V, 3, 50 Hz
F = 220V, 1, 50 Hz
G = 220V, 3, 50 Hz
1.3
E = May
F = June
G = July
H = August
Downloaded from www.Manualslib.com manuals search engine
J = September
K = October
L = November
M = December
L = 2000
M = 2001
N = 2002
P = 2003
R = 2004
S = 2005
T = 2006
U = 2007
V = 2008
Y = 2009
ComPac 6/09-18
1.4
0.10
860
1100
1310
0.20
810
1000
1220
1650
1900
1900
2100
0.25
740
960
1185
1585
1830
1830
1950
0.30
670
920
1150
1520
1760
1760
1800
0.40
0.50
810
1060
1450
1700
1700
1730
1360
1620
1620
1660
MODEL
COMPAC I A/C
COMPAC II A/C
30/36
LBS/KG
355/160
365/170
42
LBS/KG
495/225
527/240
48
LBS/KG
521/240
552/250
60
LBS/KG
535/245
565/260
72
LBS/KG
625/284
640/290
24
16 x 25 x 2
406 x 635 x 51
Downloaded from www.Manualslib.com manuals search engine
30/36
16 x 30 x 2
406 x 762 x 51
42/48/60
22 x 36-1/2 x 2
559 x 927 x 51
72
18 x 24 x 2*
452 x 610 x 51
ComPac 6/09-18
Figure 1a. ComPac I & ComPac II A/C Dimensions- Models AVP20-36 (in inches)
Figure 1b. ComPac I A/C & ComPac II A/C Dimensions- Models AVP42-60 (in inches)
Downloaded from www.Manualslib.com manuals search engine
ComPac 6/09-18
Figure 1c. ComPac I A/C & ComPac II A/C Dimensions- Models AVP72 (in inches & mm)
Downloaded from www.Manualslib.com manuals search engine
ComPac 6/09-18
1.5
General Operation
Refrigerant Cycle (Cooling Mode)
The ComPac I & ComPac II A/C use R-22 refrigerant in a conventional vapor-compression refrigeration cycle to transfer heat from air in an enclosed space to the outside. A double blower assembly blows
indoor air across the evaporator. Cold liquid refrigerant passing through the evaporator is boiled into gas
by heat removed from the air. The warmed refrigerant gas enters the compressor where its temperature
and pressure are increased. The hot refrigerant gas condenses to liquid as heat is transferred to outdoor
air drawn across the condenser by the condenser fan. Liquid refrigerant is metered into the evaporator
through capillary tubes to repeat the cycle.
Evaporator (Indoor Coil)
Distributor &
Capillary
Tubes
Filter
Drier
Twin Blowers
Suction
Line
Compressor
Discharge Line
Condenser Fan
Heating Mode
A wall-mounted thermostat controls the heating cycle of models which incorporate resistance heating
elements. On a call for heat, the thermostat closes the heat relay to energize the indoor fan and the
resistance elements. Except on units with the optional dehumidification kit, the compressor is locked
out during the heating cycle.
Economizer Operation (ComPac II A/C Only)
The economizer is a regulated damper system with controls. The damper regulates the circulation
of outside air into the enclosure (when the outdoor air conditions are suitable) to reduce the need for
mechanical cooling, save energy, and extend compressor life.
Depending upon the options selected, the damper responds to the enthalpy of the outdoor air. On a call
for cooling from a space thermostat, it operates as follows:
When the enthalpy of the outdoor air is below the set point, the outdoor air damper is proportionally open (and return air damper is proportionally closed) to maintain between 50F and 56F at the
mixed/discharge air sensor. Integral pressure relief allows the indoor air to exit the shelter through the
air conditioner.
When the enthalpy of the outdoor air is above the set point, the outdoor air damper closes to its minimum
position. A call for cooling from the space thermostat brings on mechanical cooling.
An optional built-in adjustable minimum position potentiometer (part number 70012) controls the
amount of outdoor air admitted to meet minimum ventilation requirements.
Downloaded from www.Manualslib.com manuals search engine
ComPac 6/09-18
TYPE
Power
Status
Status
Status
STATUS
Constant On
Constant On
1 Blink
2 Blinks
Downloaded from www.Manualslib.com manuals search engine
DESCRIPTION
24 VAC power has been applied
Normal operation
High pressure switch has opened twice
Low pressure switch has opened twice
10
ComPac 6/09-18
POST PURGE
WHEEL
LEDs
Downloaded from www.Manualslib.com manuals search engine
11
DELAY ON MAKE
(COMPRESSOR TIME DELAY)
WHEEL
ComPac 6/09-18
12
ComPac 6/09-18
electric reheat operate to temper the air and lower the humidity. If the temperature in the controlled
environment rises above the set point of the thermostat and the unit is operating in the dehumidification
mode, the call for cooling will override the call for dehumidification and the strip heat is disengaged
until the thermostat is satisfied. This assures the environment temperature is maintained as first priority
and humidity control is second.
In applications where a shelter has redundant air conditioning units and is controlled by a lead lag
controller (Marvair's LL357D4 or CommStat3 Controller), most times the dehumidification option
is only necessary on one of the two units. It is possible for one unit to be operating in the cooling mode
while the unit with dehumidification is operating at the same time. If the cooling unit does not maintain
the shelter temperature set point, the unit with dehumidification will go into the cooling mode. It does
not matter whether the unit with dehumidification is the lead or lag unit.
Three Phase Voltage Monitor, Marvair
Continuously measures the voltage of each of the three phases. The monitor separately senses low
and high voltage, voltage unbalance including phase loss and phase reversal. An LED indicator glows
when all voltages are acceptable. Automatically resets when voltages and phases are within operating
tolerances.
Dirty Filter Indicators
A diaphragm type of indicator measures the air pressure on either side of the filter and when the pressure
drops below the set point, an LED is illuminated.
Minimum Potential Potentiometer
Used in the ComPac II units with the factory installed economizer. The potentiometer prevents the
economizer from closing completely, assuring that outside air will be brought into the shelter and exhausted whenever the indoor blower is operating. This prevents negative pressurization of the building.
The minimum potential potentiometer is adjustable.
Downloaded from www.Manualslib.com manuals search engine
13
ComPac 6/09-18
TRANSFORMER
Downloaded from www.Manualslib.com manuals search engine
14
ComPac 6/09-18
TRANSFORMER
Downloaded from www.Manualslib.com manuals search engine
15
ComPac 6/09-18
Downloaded from www.Manualslib.com manuals search engine
16
ComPac 6/09-18
The controller modulates the position of the outside air damper in response to input from the enthalpy
and mixed air sensors. The controller is designed to maintain the supply air temperature between 50
to 56F by mixing warm indoor air with cooler outdoor air.
On a call for cooling from the wall-mounted thermostat, if outdoor conditions are suitable, the controller
will open the damper and admit outside air (i.e., economizer cooling). If the outdoor ambient is too
hot or humid, the controller will place the actuator in the closed or minimum open position and activate
mechanical cooling. The compressor is locked out during the economizer cooling mode.
54.4 Degrees
Scaleplate
and Knob
Between
C
B
Index Mark
on Controller
Flat on Shaft
Perpendicular
to Index Mark
on Controller
Downloaded from www.Manualslib.com manuals search engine
17
ComPac 6/09-18
Chapter 2 Installation
WARNING
Failure to observe and follow Warnings and Cautions and these Instructions could result in
death, bodily injury or property damage. Read this manual and follow its instructions and
adhere to all Cautions and Warnings in the manual and on the Marvair unit..
18
ComPac 6/09-18
Duct work should be designed and installed in accordance with all applicable safety codes and
standards. Marvair strongly recommends referring to the current edition of the National Fire
Protection Association Standards 90A and 90B before designing and installing duct work. The duct
system must be engineered to insure sufficient air flow through the unit to prevent over-heating of
the heater element. This includes proper supply duct sizing, sufficient quantity of supply registers,
and adequate return and filter areas. Duct work must be of correct material and must be properly
insulated. Duct work must be constructed of galvanized steel with a minimum thickness of .019
inches. Duct work must be firmly attached, secured, and sealed to prevent air leakage. See section
2.4 for additional duct work requirements.
5. Clearances:
Note the minimum clearances required for proper operation and service.
MIN. CLEARANCE AROUND
SIDES (SINGLE UNIT)
MIN. SPACE
ABOVE UNIT
24
30 inches
18 inches
24 inches
30/36
30 inches
18 inches
24 inches
42/48/60
30 inches
30 inches
24 inches
72
30 inches
30 inches
12 inches
MODEL
6. Codes:
Make sure your installation conforms to all applicable electrical, plumbing, building, and municipal
codes. Some codes may limit installation to single story structures.
7. Electrical Supply:
The power supply must have the appropriate voltage, phase, and ampacity for the model selected.
Voltage must be maintained above minimum specified values listed below. Refer to the data sticker
on the unit for ampacity requirements.
Electrical Rating Designations*
Nominal Voltage
208/230
208/230
460
Phase
Minimum Voltage
197
197
414
Maximum Voltage
253
253
506
2.3
19
ComPac 6/09-18
P/N
Description
S/04581
S/07529
LL357D4, Lead/Lag Controller with T'stat & Sub-Base; Controls 2 A/C Units
50123
Digital thermostat. 1 stage heat, 1 stage cool. 7 day programmable. Fan switch: Auto &
On. Auto-change over. Keypad lockout. Non-volatile program memory.
50107
Digital thermostat. 2 stage heat, 2 stage cool. 7 day programmable. Fan switch: Auto &
On. Auto-change over. Status LEDs. Backlit display. Programmable fan. Non-volatile
program memory.
80674
VPG - 20S, 20 x 8" Adjustable, Aluminum, Double Deflection Supply Grill for
AVP24
VPG - 30S, 28 x 8" Adjustable, Aluminum, Double Deflection Supply Grill for
AVP30-36
VPG - 40S, 30 x 10" Adjustable, Aluminum, Double Deflection Supply Grill for
AVP42-48-60-72
80675
80676
80677
80678
80679
06777
Start Relay and Capacitor for AVP24-36 (Field Installed) (Not recommended for scroll
compressors.)
Downloaded from www.Manualslib.com manuals search engine
20
ComPac 6/09-18
Warning
FIRE HAZARD
Downloaded from www.Manualslib.com manuals search engine
21
ComPac 6/09-18
BASIC MODEL
24
.30
30/36
.40
42/48/60/72
.50
2.5
2.6
Downloaded from www.Manualslib.com manuals search engine
22
ComPac 6/09-18
2.7
GRILLE
SUPPLY AIR
DUCT EXTENSIONS (Not Supplied with Unit)
COMPAC II A/C
ONLY
RETURN AIR
GRILLE
FOAM SEAL
Downloaded from www.Manualslib.com manuals search engine
23
ComPac 6/09-18
24
ComPac 6/09-18
4. For units designed for operation on 208/230v, 60Hz power supply, the transformer is factory wired
for a 230v power supply. For a 208v power supply, remove the orange lead from the transformer
and connect the red lead. Insulate the orange lead.
Dual Unit Phasing
For applications where one controller operates two units, e.g., the CommStat 3 or LL357D.
The LL357D4 and the LL357D3 do not require unit phasing. However, if other devices are connected
to the control system, phasing of the air conditioner is required. Earlier models; i.e., LL357, LL357A,
LL357D2 require the unit to be properly phased.
1. Wire each unit as described in steps 1 through 4 above.
2. Test for proper phasing as follows:
A. Power up the units.
B. Using an AC volt meter set to the 300 volt scale, measure voltage between terminal L1 on the
compressor contactor of unit #1 and terminal L1 on the compressor contactor of unit #2 If
voltage is present, units are wired out of phase and must be rewired.
C. If units are not in phase, turn off power and reverse the field power leads connected to the
internal circuit breaker on one of the units only.
D. Restore power and retest the phase (step B). When the voltage reads "0", the units are in
phase.
E. Turn off power and proceed.
Low Voltage Wiring
1. On single units, pull the low voltage wiring (e.g., 18 gauge 4-conductor Class 2 thermostat wire)
from the ComPac A/C into the thermostat / subbase assembly. See Figure 8d for connections to
various thermostats.
2. Mount the thermostat on the wall of the shelter. The thermostat should be located so that the supply air from the unit does NOT blow directly on to the thermostat. Connect the thermostat to the
terminal block in the ComPac air conditioner as shown in Figures 8a and 8b.
3. On dual units, refer to the Marvair LL357D4 Lead/Lag Controller Specification Sheet or CommStat 3 Controller Specification sheet. Level and install the LL357D4 or CommStat 3 subbase.
Wire the two ComPac units to the Lead/Lag Controller, according to the wiring diagram on the
specification sheet and as shown in Figure 8c or 8d (note: the diagram also appears on the back
cover of the controller).
Remote Signalling: Terminals 5 & 7(N.O.) and 6 & 7 (N.C.) on the ComPac A/C terminal board are
dry contacts which can be used for remote signalling in the event of a/c cutoff on low or high pressure
limit.
Continuous fan operation: For continuous indoor fan operation on single units, install a jumper between
terminals 8 and 3. For continuous indoor fan operation on dual units using the LL357D4, install jumper
between 8 and 3 and remove jumper between 1 and 3.
CommStat 3 Controller (See Figure 8c)
The CommStat 3 Controller by Marvair is a solid state control package designed to operate a
fully or partially redundant air conditioning system for a telecommunication cabinet or shelter. The
CommStat 3 Controller is factory programmed with standard industry set points to facilitate installation. If desired, each of the set points can be quickly and easily changed in the field by the installer.
Downloaded from www.Manualslib.com manuals search engine
25
ComPac 6/09-18
It can be used with Marvairs ComPac I or II unique vertical packaged wall mount air conditioners
or Marvairs environmental control units. See CommStat 3 Product Data Sheet for installation and
programming instructions.
LL357D4 Lead/Lag Controller (See Figure 8b)
The Marvair LL357D4 is a complete control package designed to operate a fully or partially redundant
air conditioning system. It consists of a two-stage heat and two-stage cool electronic thermostat and
a solid state timer. It can be used with either the Marvair ComPac I vertical packaged wall mount air
conditioner or our unique ComPac II air conditioner with built-in economizer. The LL357D4 provides
environmental control and the security demanded by the communication shelter industry for a backup
unit. The lead/lag controller insures equal wear on both air conditioners while allowing the lag unit
to assist upon demand. The LL357D4 is factory wired, tested, and mounted in an enclosure for quick
installation. Refer to the LL357D4 Product Data Sheet for complete installation instructions.
Operational Specifications
Thermostat Range: 45F to 90F (7C to 32C)
Accuracy: 1F ( C)
Changeover Temperature Differential (separation between the heat set point and the cool set point):
2F to 9F (1.0C to 4.5C)
First Stage Temperature Differential (number of degrees between the set point temperature and the
turn on temperature): 1F to 3F (.5C to 1.5C)
Second Stage Temperature Differential (number of degrees between when stage 1 turns on and
when stage 2 turns on): 1F to 6F (.5C to 3.0C).
Minimum Cool Temperature Set Point: Adjustable from 45F to 75F (7C to 24.0C).
Maximum Heat Temperature Set Point: Adjustable from 55F to 90F (13C to 32.0C)
Staged OFF Outputs: Air conditioners will turn off independently.
Timing Device
Solid state timer with both 3.5 and 7 day changeover capability.
NOTE: Cut timer circuit wire to provide 3.5 day changeover. Timing accuracy 5%.
Momentary push button for accelerated manual timer advance. (9 seconds = 7 days)
Light emitting diode indicates power on and identifies the lead unit.
Unit Shutdown/Fire Alarm Systems
Immediate shutdown of the air conditioning system can be accomplished by wiring the normally closed
set of contacts in the fire extinguishing or alarm system across terminals 8 and 10 on the low voltage
terminal board inside the air conditioner. Note: The factory jumper between these terminals must be
removed.
This function cannot be accomplished at the wall thermostat because the fan purge on the electronic
control board inside the unit allows the indoor blower to operate from 10 to 90 seconds following each
cool "on" cycle.
NOTE: The fan purge on the electronic control board allows the indoor fan to run for approximately
10 to 90 seconds after the compressor is off. This operation provides a small improvement in system
efficiency.
Downloaded from www.Manualslib.com manuals search engine
26
ComPac 6/09-18
10
Y
A
G
W2
Thermostat
Field Supplied
Y
A
O
G
W2
C
Humidity Controller
Downloaded from www.Manualslib.com manuals search engine
27
ComPac 6/09-18
50124/
SC3001
Rc
RH
50123/
SC5011-SL
Rc
RH
Y1
W1
Y2
W2
LOW VOLTAGE
TERMINAL BOARD
COMPRESSOR
FAN
POWER
50121/
SC2010-SL
MODPAC II
ALL COMPAC 10
UNITS
O/B
LOW VOLTAGE
TERMINAL BOARD
COMMON
50107/
SC5811-SL
Downloaded from www.Manualslib.com manuals search engine
28
ComPac 6/09-18
COMMSTAT 3
E2
E3
E1
THERMOSTAT
SWITCH TERMINALS
E4
LOR G W C Y R
LOR G W C Y R
POWER
ALARM
NC
DRY
CONTACTS
C
NO
THERMISTOR CONTACTS
#1
NO
HIGH BLDG TEMP
ALARM
#2
NC
DRY
CONTACTS
C
#3
NO
#4 (FACTORY
INSTALLED)
NC
HP/LP LOCKOUT
DRY
CONTACTS
C
NO
CONNECT TO
NORMALLY CLOSED
DRY CONTACTS FROM
SMOKE ALARM
SMOKE ALARM
SMOKE
NC
JUMPER
DRY
CONTACTS
NO
COMPAC
CONNECTION
DESIGNATIONS
TERMINAL BOARD
TERMINAL BOARD
UNIT 1
UNIT 2
COMPAC
CONNECTION
DESIGNATIONS
NOTE:
1. 24 VAC connections only.
2.
For immediate shutdown of air conditioner upon a signal from the smoke alarm, the jumper between terminals 8 and 10 in the ComPac I
and ComPac II units must be removed and a jumper placed from terminals 8 and 3.
3.
When connecting a smoke alarm to the smoke alarm input terminals (normally closed), remove the factory installed jumper wire and
install the smoke alarm leads.
IF LINE VOLTAGE IS BELOW 220 VAC, USE THE 208 TRANSFORMER TAP.
Downloaded from www.Manualslib.com manuals search engine
29
ComPac 6/09-18
Chapter 3 Start-Up
Important: Be sure that the crankcase heater (if used) has been energized for at least 24 hours
before starting the unit(s). Double-check all electrical connections before applying power.
ComPac air conditioners with scroll compressors running on 3 power must be checked for
proper rotation during the initial start-up. Please refer to Section 2.8 for determining if the 3
compressors are rotating correctly. Incorrect rotation can damage the compressor and is not
covered by the warranty
Procedure:
1. Set the cooling temperature on the wall thermostat to a point higher than the ambient temperature.
Set the heating temperature to a temperature that is lower than the ambient.
2. Set the thermostat system switch in the AUTO position. Nothing should operate at this time.
3. Set the time delay in the ComPac I or ComPac II A/C control box to three minutes. Check the
changeover setting of the H205A or dry bulb sensor and reset it if needed (ComPac II A/C only).
See Section 1.6.
4. Slowly lower the thermostat's cooling temperature until the switch closes. The indoor fan should
operate.
Once the indoor fan turns on, allow approximately three minutes for the compressor to start. Note that
the outdoor fan may not come on immediately, because it is cycled by refrigerant pressures.
NOTE: (ComPac II A/C only) To check the system operation under different ambient conditions, the
air temperature and enthalpy sensors must be "tricked". When outdoor ambient conditions are higher
than the control setting, a component cooler aerosol may be sprayed directly into the enthalpy sensor
to simulate low enthalpy conditions, causing the economizer damper to open.
Alternately, when outdoor conditions are lower than the set point, a source of heat such as a hair dryer
can be directed on the air temperature sensor to simulate warmer conditions, which will bring on
mechanical cooling and start the compressor.
5. To stop cooling, slowly raise the thermostat cooling to a temperature higher than the ambient.
If the unit fails to operate, refer to the troubleshooting information in Chapter 4.
Follow the same procedure for additional units.
NOTE: The fan purge allows the indoor fan to run for approximately 90 seconds after the compressor
is off. This operation provides a small improvement in system S.E.E.R.
30
ComPac 6/09-18
1. Set the cooling temperature on the wall thermostat to a point higher than the ambient temperature.
Set the heating temperature to a temperature that is lower than the ambient temperature. Turn the
selector switch to the off position.
2. Set the time delay on unit No. 1 to 3 minutes, and No. 2 to 5 minutes.
3. Set the change over setting of the enthalpy control to the d setting (ComPac II A/C only).
4. Provide power to A/C units and turn disconnects on.
5. Check incoming power to each unit. For units designed for operation on 208/230v, 60hz power
supply, the transformer is factory wired for a 230 power supply. For a 208 power supply remove
the orange lead from the transformer and connect the red lead. Insulate the orange lead.
6. Cooling. Turn the selector switch on the thermostat to the auto position. Slowly lower the cooling
temperature until the switch closes. The indoor fan should operate on the lead unit. Once the indoor
fan turns on, allow approximately 3 to 5 minutes for the compressor to start. Note that the outdoor
fan may not come on immediately because it is cycled by refrigerant pressures. Next, lower the
temperature until the switch closes. Follow the above procedures for the lag unit.
The green light on the lead lag control should be on. One amber light will be on to identify the lead
unit. The other light should be off. If the lag unit comes on with the lead unit the light for the lag
unit will not come on. You should never have all 3 lights on at one time.
Allow the units to run for 2 to 3 minutes then check the temperature differential between the return
air and the supply air with digital thermometer. The temperature differential should be between 12
and 20 degrees depending on ambient temperature.
Next, slowly raise the cooling temperature until the switch opens. The compressor and outdoor
fan should turn off. The indoor fan will continue to run for 90 seconds until the fan purge times
out. Raise the temperature until the switch opens. The lead unit will shut down accordingly to the
same procedures as outlines above.
Note: (ComPac II A/C only) To check the system operation under different ambient conditions,
the air temperature and enthalpy sensors must be tricked. When outdoor ambient conditions are
higher than the control setting, a component cooler aerosol may be sprayed directly into the enthalpy
sensor to stimulate low enthalpy conditions, causing the economizer damper to open.
Alternately, when outdoor conditions are lower than the set point, a source of heat such as a hair
dryer can be directed on the enthalpy sensor to simulate warm conditions, which will bring on
mechanical cooling and start the compressor.
7. Heating. Slowly raise the heating temperature until the switch closes. The fan and electrical heat
should immediately cycle on. The unit should start blowing warm air in 2 to 3 minutes. Next, raise
the temperature until the switch closes. Follow the above procedures for lag unit.
Hold the manual advance button in for nine seconds the lead lag lights should switch. Next, slowly
lower the temperature until the switches open. The lag unit should shut down immediately. Next,
slowly lower the temperature until the switch opens, the lead unit should shut down immediately.
31
ComPac 6/09-18
4.1
Chapter 4 Troubleshooting
Overview
A comprehensive understanding of the operation of the ComPac A/C is a prerequisite to troubleshooting. Please read the Chapter 1 for basic information about the unit.
Marvair's ComPac air conditioners are thoroughly tested before they are shipped from the factory.
Of course, it is possible that a defect may escape undetected, or damage may have occurred during
transportation. However, the great majority of problems result from installation errors.
If you experience difficulties with the ComPac A/C, please review the installation steps in Chapter
2.
Much time can be saved by taking a thoughtful and orderly approach to troubleshooting. Start with a
visual check - are there loose wires, crimped tubing, missing parts, etc? Begin deeper analysis only
after making this initial inspection.
The troubleshooting information in this manual is basic. The troubleshooting section contains problem/solution charts for general problems, followed by a compressor section.
Not every problem can be anticipated. If you discover a problem that is not covered in this manual, we
would be very grateful if you would bring it to the attention of our service department for incorporation
in future revisions.
As always, please exercise caution and good judgement when servicing the ComPac A/C. Use only safe
and proven service techniques. Use refrigeration goggles when servicing the refrigeration circuit.
WARNING
The refrigerant circuit has hot surfaces, and the electrical voltages inside of
the unit may be hazardous or lethal. SERVICE MAY BE PERFORMED ONLY BY
QUALIFIED AND EXPERIENCED PERSONS.
4.2
LIKELY CAUSE(S)
CORRECTION
2. Low refrigerant.
3. Component failure.
Downloaded from www.Manualslib.com manuals search engine
32
ComPac 6/09-18
PROBLEM/SYMPTOM
C. Unit cycles on high/low pressure
limit.
LIKELY CAUSE(S)
CORRECTION
4.3
3. Check wiring in unit. See wiring and schematic diagrams. Test components (especially the compressor)
for shorts.
3. Level unit.
Compressor Troubleshooting
NOTE: It is important to rule out other component failures before condemning the compressor.
The following electrical tests will aid diagnosis:
1. Start-Up Voltage: Measure the voltage at the compressor terminals during start-up. The voltage
must exceed the minimum shown in Table 5, section 2.2, or compressor failure is likely. A low
voltage condition must be corrected.
2. Running Amperage: Connect a clip-on type ammeter to the (common) lead to the compressor.
Turn on the supply voltage and energize the unit. The compressor will initially draw high amperage;
it should soon drop to the RLA value or less. If the amperage stays high, check the motor winding
resistances.
33
ComPac 6/09-18
NOTE: Feel the top of the compressor to see if it has overheated. If it is hot, the internal overload
may be open. You may have to wait several hours for it to reset.
3. Motor Winding Resistances: Using a digital volt-ohm meter (VOM), measure the resistance
across the compressor windings as shown below.
SINGLE
PHASE
C
R2
S
R1
R3
R3 > R2 > R1
R3 = R2 + R1
THREE
PHASE
T1
R2
T2
R1
R3
R3 = R2 = R1
T3
Resistance can be measured as shown above. Any deviation from above values could indicate a
defective compressor.
4. High Voltage/Insulation Test: Test internal leakage with a megohmeter. Attach one lead to the
compressor case on a bare metal tube and to each compressor terminal to test the motor windings.
A short circuit at high voltages indicates a motor defect. Do not do this test under vacuum.
5. On single phase models, check the capacitor by substitution.
Downloaded from www.Manualslib.com manuals search engine
34
ComPac 6/09-18
Chapter 5 Maintenance
5.1 Scheduled Maintenance
Marvair strongly recommends that the air conditioner be serviced a minimum of twice a year once
prior to the heating season and once prior to the cooling season. At this time the filters, evaporator coil,
condenser coil, the cabinet, and condensate drains should be serviced as described below. Also at this
time, the air conditioner should be operated in the cooling and heating cycles as described in Chapter 3,
Start-Up. In addition to this seasonal check-out, the ComPac A/C should be maintained as follows:
Air Filter
Replace the air filter whenever it is visibly dirty.
Evaporator
If the evaporator becomes clogged or dirty, it may be cleaned by careful vacuuming or with a commercial evaporator cleaning spray. DO NOT use a solvent containing bleach, acetone, or flammable
substances. Turn off power before cleaning.. Be careful not to wet any of the electrical components.
Be sure the unit has dried before restarting.
Condenser
Periodically inspect the outdoor condenser coil and the cabinet air reliefs for dirt or obstructions.
Remove foreign objects such as leaves, paper, etc.
If the condenser coil is dirty, it may be washed off with a commercial solvent intended for this purpose.
TURN OFF POWER BEFORE CLEANING! Be sure that all electrical components are thoroughly
dry before restoring power.
Cabinet
The cabinet may be cleaned with a sponge and warm, soapy water or a mild detergent. Do not use
bleach, abrasive chemicals or harmful solvents.
Drains
Regularly check the primary and secondary condensate drains. The secondary drain has a stand pipe
(on AVP24-72). An obstruction will force water to dump into the middle of the unit and drain out
the sides of the ComPac, causing discoloration of the side panels. If discoloration is noted, service
the drains.
If a commercial drain solvent is used, flush out the drain pan and system with plenty of fresh water to
prevent corrosion.
Lubrication
Oiling of the condenser fan motor or the evaporator blower motor is not recommended.
Downloaded from www.Manualslib.com manuals search engine
35
ComPac 6/09-18
Chapter 6 Warranty
If any part of your Marvair Air Conditioner, Heat Pump or Unit Ventilator fails because of a manufacturing defect within fifteen months from the date of original shipment from Marvair or within twelve
months from the date of original start-up, whichever is the earlier date, Marvair will furnish without
charge, EXW Cordele, Georgia, the required replacement part. Any transportation, related service
labor, diagnosis calls, filter, driers, and refrigerant are not included. The owner must provide proof
of the date of the original start-up. The owners registration card filed with Marvair, the contractors
invoice, the certificate of occupancy or similar document are examples of proof of the date of the
original start-up.
In addition, if the hermetic compressor fails because of a manufacturing defect within sixty months
from the date of original shipment from Marvair, Marvair will furnish without charge, EXW Cordele,
Georgia, the required replacement part. Any related service labor, diagnosis calls, filter, driers and
refrigerant are not included. Marvair will pay for non-priority shipping costs of the compressor during
the first twelve months of the warranty period. After the first twelve months of the warranty period, all
costs of shipment and risk of loss during the shipment of the compressor shall be the responsibility of
the owner.
The owner of the product may ship the allegedly defective or malfunctioning product or part to
Marvair, at such owners expense, and Marvair will diagnose the defect and, if the defect is covered
under this warranty, Marvair will honor its warranty and furnish the required replacement part. All
costs for shipment and risk of loss during shipment of the product to Marvair and back to the owner
shall be the responsibility and liability of the owner. Upon written request by an owner, Marvair may
arrange for remote diagnosis of the allegedly defective or malfunctioning product or part but all costs
for transportation, lodging and related expenses with regard to such diagnostic services shall be the
responsibility and liability of the owner.
An owner requesting performance under this Warranty shall provide reasonable access to the allegedly
defective or malfunctioning product or part to Marvair and its authorized agents and employees.
This warranty applies only to products purchased and retained for use within the U.S.A., Canada, and
Mexico. This warranty does not cover damage caused by improper installation, misuse of equipment
or negligent servicing.
THIS WARRANTY CONSTITUTES THE EXCLUSIVE REMEDY OF ANY PURCHASER OF
A MARVAIR HEAT PUMP OR AIR CONDITIONER AND IS IN LIEU OF ALL OTHER WARRANTIES, EXPRESSED OR IMPLIED, INCLUDING, WITHOUT LIMITATION, ANY IMPLIED
WARRANTY OF MERCHANTABILITY OR FITNESS FOR USE, TO THE FULLEST EXTENT
PERMITTED BY LAW. IN NO EVENT SHALL ANY IMPLIED WARRANTY OF MERCHANTABILITY OR FITNESS FOR USE EXCEED THE TERMS OF THE APPLICABLE WARRANTY
STATED ABOVE AND MARVAIR SHALL HAVE NO OTHER OBLIGATION OR LIABILITY. IN
NO EVENT SHALL MARVAIR BE LIABLE FOR INCIDENTAL OR CONSEQUENTIAL DAMAGES OR MONETARY DAMAGES.
THIS WARRANTY GIVES YOU SPECIFIC LEGAL RIGHTS, AND YOU MAY ALSO HAVE
OTHER RIGHTS WHICH VARY FROM STATE-TO-STATE. Some states do not allow limitations
or exclusions, so the above limitations and exclusions may not apply to you.
Downloaded from www.Manualslib.com manuals search engine
36
Rev. 6/04
Supersedes 9/02
ComPac 6/09-18
Downloaded from www.Manualslib.com manuals search engine
37
ComPac 6/09-18
Downloaded from www.Manualslib.com manuals search engine
38
ComPac 6/09-18