Sunteți pe pagina 1din 14

MP Inlet Separator

Flowing temperature (C)


Required discharge area of the valve (mm2)
Required discharge area of the valve (inch2)
Orifice type
Selected discharge area (in2)
Selected discharge area (mm2)
Selected scenario for sizing
FLOW, kg/h

Blocked outlet
89
1124.16
1.742
K
1.838
1185.80
X
5095.800

HP Inlet Separator

Flowing temperature (C)


Required discharge area of the valve (mm2)
Required discharge area of the valve (inch2)
Orifice type
Selected discharge area (in2)
Selected discharge area (mm2)
Selected scenario for sizing
FLOW, kg/h

Wet Gas Separator

Flowing temperature (C)


Required discharge area of the valve (mm2)
Required discharge area of the valve (inch2)
Orifice type
Selected discharge area (in2)
Selected discharge area (mm2)
Selected scenario for sizing
FLOW, kg/h

Molecular sieve inlet header

Flowing temperature (C)


Required discharge area of the valve (mm2)
Required discharge area of the valve (inch2)
Orifice type

Blocked outlet
47
172.14
0.267
F
0.307
198.06
X
2460.000

No condensate flow.
Dimensions of vessle not aveilable.
Blocked outlet
68
426.03
0.660
H
0.785
506.45
X
9637.500

No condensate flow.
Blocked outlet
68
426.03
0.660
H

Selected discharge area (in2)


Selected discharge area (mm )
2

Selected scenario for sizing


FLOW, kg/h

Molecular sieve outlet header

Flowing temperature (C)


Required discharge area of the valve (mm2)
Required discharge area of the valve (inch2)
Orifice type
Selected discharge area (in2)
Selected discharge area (mm2)
Selected scenario for sizing
FLOW, kg/h

Water Knockout Drum

Flowing temperature (C)


Required discharge area of the valve (mm2)
Required discharge area of the valve (inch2)
Orifice type
Selected discharge area (in2)
Selected discharge area (mm2)
Selected scenario for sizing
FLOW, kg/h

Propane Compressor Suction Drum

Flowing temperature (C)


Required discharge area of the valve (mm2)
Required discharge area of the valve (inch2)
Orifice type
Selected discharge area (in2)
Selected discharge area (mm2)

0.785
506.45
X
9637.500

No condensate flow.
Blocked outlet
68
426.03
0.660
H
0.785
506.45
X
9637.500

No condensate flow.
Dimensions of vessle not aveilable.
Blocked outlet
78
189.14
0.293
F
0.307
198.06
X
1070.000

No condensate flow.
Wet fire heat of vap 50 Btu/h and proper
Blocked outlet
81
47.32
0.073
D
0.110
70.97

Selected scenario for sizing


FLOW, kg/h

882.100

Low Temperature Separator


Blocked outlet

Flowing temperature (C)


Required discharge area of the valve (mm )
2

Required discharge area of the valve (inch2)


Orifice type
Selected discharge area (in2)
Selected discharge area (mm2)
Selected scenario for sizing
FLOW, kg/h

Flash Vessel

Flowing temperature (C)


Required discharge area of the valve (mm2)
Required discharge area of the valve (inch2)
Orifice type
Selected discharge area (in2)
Selected discharge area (mm2)

22
480.89
0.745
H
0.785
506.45
X
9570.000

No gas flow.
Blocked outlet
22
8.51
0.013
D
0.110
70.97

Selected scenario for sizing


FLOW, kg/h

Three Phase Separator

Flowing temperature (C)


Required discharge area of the valve (mm2)
Required discharge area of the valve (inch2)
Orifice type
Selected discharge area (in2)
Selected discharge area (mm2)

Blocked outlet
52
2.76
0.004
D
0.110
70.97

Selected scenario for sizing


FLOW, kg/h

155.000

Condensate Stabilizer

Flowing temperature (C)


Required discharge area of the valve (mm2)
Required discharge area of the valve (inch2)
Orifice type
Selected discharge area (in2)
Selected discharge area (mm2)

Blocked outlet
72
2.40
0.004
D
0.110
70.97

Selected scenario for sizing


FLOW, kg/h

149.125

LPG Storage

Flowing temperature (C)


Required discharge area of the valve (mm2)
Required discharge area of the valve (inch2)
Orifice type
Selected discharge area (in2)
Selected discharge area (mm2)

Blocked outlet
68
2.24
0.003
D
0.110
70.97

Selected scenario for sizing


FLOW, kg/h

140.830

HEADER SIZING
Blocked Outlet
Wet Fire Area 1

Wet Fire Area 2

Cond Stab
3 phase sep
TOTAL
LTS
Wet gas sep
Propane comp
water KO drum
TOTAL

LPG Storage
Header sizing for
Condensate Stabilizer mass flow
Condensate Stabilizer flowing temp.
Condensate Stabilizer pressure
3 Phase Separator mass flow
3 Phase Separator flowing temp.
3 Phase Separator pressure
Average flowing temp. for Area 1
Averege Molecular Weith for Area 1
Volume flow
Velocity in pipe
Pipe area
Inside diameter
Header length
KO DRUM SIZING

5450
183
15
9550
171.9
16
165.7
52.91
6710.452
18.000
0.104
363.114
14.296
1000

Diameter
Length

2
4.5

FLARE SIZING
Diameter
Height
Flame length

203.2
8
19
16.05

Dry fire
636
100.39
0.156
E
0.196
126.45

Wet fire
636
516.58
0.801
J
1.287
830.32

Remarks

3889.000

Dry fire
216
77.38
0.120
E
0.196
126.45

Wet fire
216
119.73
0.186
E
0.196
126.45

955.100

2213.200

Remarks

ensate flow.
ons of vessle not aveilable.

ensate flow.

Dry fire
164
144.24
0.224
F
0.307
198.06

Wet fire
164
20.52
0.032
D
0.110
70.97

3058.400

448.900

Remarks

ensate flow.

ensate flow.
ons of vessle not aveilable.
Dry fire
216
0.00
0.000
D
0.110
70.97

Wet fire
216
24.47
0.038
D
0.110
70.97

701.900

255.110

Remarks

ensate flow.
heat of vap 50 Btu/h and properties of Gas stream
Dry fire
3346
20.58
0.032
D
0.110
70.97

Wet fire
3346
841.68
1.305
K
1.838
1185.80
X
5352.200

Remarks

Dry fire

Wet fire

Remarks

140
37.07
0.057
D
0.110
70.97

140
48.74
0.076
D
0.110
70.97

655.000

1256.000

Dry fire
140
37.07
0.057
D
0.110
70.97

Wet fire
902
114.18
0.177
E
0.196
126.45
X
1005.694

Remarks

Dry fire
172
220.64
0.342
G
0.503
324.52

Wet fire
172
507.68
0.787
J
1.287
830.32
X
9547.190

Remarks

Wet fire
183
294.08
0.456
G
0.503
324.52
X
5318.275

Remarks

2812.400

Dry fire
183
203.87
0.316
G
0.503
324.52
2618.600

Dry fire
0
0.00
0.000
D
0.110
70.97

10000.000
5318.275
9547.190
14865.465
1256.000
448.900
5352.200
255.110
7312.210
13810.000

Wet fire
200
670.26
1.039
J
1.287
830.32
X
13810.000

kg/h

15000.000

kg/h

kg/h
C
bar_g
kg/h
C
bar_g

From PSV
calculation
spreadsheet

C
Sm/h
m/s
m
mm
inch
m

From PSV
calculation
spreadsheet

Remarks

m
m

mm
inch
m
m

PSV Sizing
PRV location
MP Inlet Separator
HP Inlet Separator
Wet Gas Separator
Molecular sieve inlet header
Molecular sieve outlet header
Water Knockout Drum
Propane Compressor Suction Drum
Low Temperature Separator
Flash Vessel
Three Phase Separator
Condensate Stabilizer
LPG Storage

Flow rate
kg/h
5095.800
2460.000
9637.500
9637.500
9637.500
1070.000
5352.200
9570.000
1005.694
9547.190
5318.275
13810.000

PRV set
pressure
bar_g
6
16
30
30
30
8
18
24
24
16
15
15.5

Orifice type

Inlet

Outlet

Selected
discharge
area

mm

mm

mm

K
F
H
H
H
F
K
H
E
J
G
J

150.00
300.00
300.00
300.00
300.00
150.00
300.00
300.00
300.00
300.00
300.00
300.00

150.00
150.00
150.00
150.00
150.00
150.00
150.00
150.00
150.00
150.00
150.00
150.00

1185.80
198.06
506.45
506.45
506.45
198.06
1185.80
506.45
126.45
830.32
324.52
830.32

Flare Sizing
Mass rate to flare
Flowing gas temperature to flare
Lower heating value
Pressure at flare tip
Design wind velocity
Flame length
Flare tip velocity
Flame distorcion ratio
Distance from flame center to grade level
Calculated stack diameter
Stack diameter
Stack height

20000
112.1
15016
0.02
10
16.05
132
0.0758
31.3
178.8
8
19

kg/h
C
Btu/lb
bar_g
m/s
m
m/s
m
mm
inch
m

2
4.5

m
m

419.29
16.5
1000

mm
inch
m

KO Drum Sizing
Diameter
Length

Header Sizing
Inside diameter
Header length

Pipe length
to header
m
250.00
200.00
45.00
40.00
40.00
25.00
30.00
25.00
130.00
40.00
25.00
2x40

S-ar putea să vă placă și