Electrical

STANDARD NETA MTS-2007 Standard for Maintenance


Testing Specifications for Electrical
ENGINEERING Distribution Equipment and Systems

Celanese PRACTICES Revision: 1


Date: 1/7/2009
Chemicals Page 1 of 4

Comply with International Electrical Testing Association 2007 Standard for Maintenance
Testing Specifications on Electrical Distribution Equipment and Systems (NETA MTS-
2007) amended for Celanese and specific sites as follows.

Comply with all requirements of Sections 1, 2, 3, 4, 5, 7, and 8. All or part or the requirements in
Sections 9 and 10 can be applied on a voluntary basis.

This standard defines Celanese minimum requirements for electrical equipment maintenance
testing. In jurisdictions where an international, national, or local governing authority have
established more stringent requirements, these requirements shall take precedence over those
defined in this standard. If a discrepancy or difference is identified between this standard and an
international, national, or local standard, code, or ordinance the more stringent requirement and/or
action shall prevail.

Section 3.3.1 Supercede with the following: Testing Certification can be in accordance with
ANSI/NETA ETT-2000, any equivalent electrical testing certification program, or specific
national, regional, or local requirements.

Section 5.1.1 Supercede with the following: Safety practices shall include, but not be limited
too, all specific national, regional, and local requirements.

Section 5.3.3 Supercede with the following: Calibration accuracy shall be traceable and
confirmable.

Section 7.3.3.2.4.1 The Celanese approved methods for Overpotential Withstand testing of
Medium Voltage Cable is as follows:

Dielectric Insulated Cable Very Low Frequency Overpotential (0.1Hz minimum to 1Hz
maximum)
Paper Insulated Lead Covered Cable Direct Current Overpotential

Section 7.3.3.3.2.4.2 - Supercede with the following: Based on the test methodology chosen, refer
to manufacturers recommendations, current version of IEEE Std 400 IEEE Guide for Field
Testing of the Insulation of Shielded Power Cable Systems, or IEC 60060 High Voltage Test
Techniques for acceptable test result values.

Appendix B Supercede Table Inspections and Tests Frequency in Months with the following
table:

The electronic version of this Celanese Chemicals SEP is the only official version. Before using any printed 1
copies, the electronic version must be checked to insure the use of the most current approved version.
Electrical
STANDARD NETA MTS-2007 Standard for Maintenance
Testing Specifications for Electrical
ENGINEERING Distribution Equipment and Systems

Celanese PRACTICES Revision: 1


Date: 1/7/2009
Chemicals Page 2 of 4

Inspections and Tests Intervals in Months


(Multiply These Values by the Factor in the Maintenance Frequency Matrix)
Visual & Visual,
Section Description Visual Mechanic Mechanic
7.1 Switchgear and Switchboard 12 al
Not al,60&
7.2 Transformers
7.2.1.1 Small Dry-Type Transformers Condition Based Maintenance Only
7.2.1.2 Large Dry-Type Transformers 3 Not 60
7.2.2 Liquid Filled Transformers 3 Not 60
Sampling 12
7.3 Cables
7.3.2 Low-Voltage Cables Condition Based Maintenance Only
7.3.3 Medium and High-Voltage Cables 12 Not 60
Inspections and Tests Intervals in Months - Continued
(Multiply These Values by the Factor in the Maintenance Frequency Matrix)
Visual & Visual,
Section Description Visual Mechanic Mechanic
7.4 Metal-Enclosed Busways 12 al
Not al,60&
7.5 Switches
7.5.1.1 Low-Voltage Air Switches Condition Based Maintenance Only
7.5.1.2 Medium-Voltage Metal Enclosed 12 Not 60
7.5.1.3 Medium and High-Voltage Open 12 Not 60
7.5.2 Medium-Voltage Oil Switches 12 Not 60
Sampling 12
7.5.3 Medium-Voltage Vacuum Switches 12 Not 60
7.5.4 Medium Voltage SF6 Switches 12 Not 60
7.5.5 Cutouts Condition Based Maintenance Only
7.6 Circuit Breakers
7.6.1.1 Low-Voltage Insulated-Case/Molded- Condition Based Maintenance Only
7.6.1.2 Low-Voltage Power CB 12 Not 60
7.6.1.3 Medium-Voltage Air CB 12 Not 60
7.6.2 Medium-Voltage Oil CB 12 Not 60
Sampling 12
7.6.2 High-Voltage Oil CB 12 Not 60
Sampling 12
7.6.3 Medium-Voltage Vacuum CB 12 Not 60
7.6.4 Extra-High-Voltage SF6 CB 12 Not 60
7.7 Circuit Switchers 12 Not 60
7.8 Network Protectors 12 Not 60
7.9 Protective Relays
The electronic version of this Celanese Chemicals SEP is the only official version. Before using any printed 2
copies, the electronic version must be checked to insure the use of the most current approved version.
Electrical
STANDARD NETA MTS-2007 Standard for Maintenance
Testing Specifications for Electrical
ENGINEERING Distribution Equipment and Systems

Celanese PRACTICES Revision: 1


Date: 1/7/2009
Chemicals Page 3 of 4

7.9.1 Electromechanical and Solid State 12 Not 60


7.9.2 Microprocessor-Based 12 Not 60
7.10 Instrument Transformers 12 Not 60
7.11 Metering Devices Condition Based Maintenance Only
7.12 Regulating Apparatus
7.12.1. Step-Voltage Regulators 3 Not 60
Sampling 12
7.12.1. Induction Regulators 3 Not 60
7.12.2 Current Regulators 3 Not 60
7.12.3 Load-Tap Changers 3 Not 60
Sampling 12
7.13 Grounding Systems 12 Not 60
Inspections and Tests Intervals in Months - Continued
(Multiply These Values by the Factor in the Maintenance Frequency Matrix)
Visual & Visual,
Section Description Visual Mechanic Mechanic
7.14 Ground-Fault Protection Systems al al, &
7.15 Rotating Machinery
7.15.1 AC Induction Motors and Generators < Condition Based Maintenance Only
7.15.1 AC Induction Motors and Generators 12 Not 60
7.15.2 Synchronous Motors and Generators 12 Not 60
7.15.3 DC Motors and Generators < Condition Based Maintenance Only
7.15.3 DC Motors and Generators
7.16 Motor Control
7.16.1. Low-Voltage Motor Starters Condition Based Maintenance Only
7.16.1. Medium-Voltage Motor Starters 12 Not 60
7.16.2. Low-Voltage Motor Control Centers 12 Not 60
7.16.2. Medium-Voltage Motor Control Centers 12 Not 60
7.17 Adjustable Speed Drive Systems Condition Based Maintenance Only
7.18 Direct-Current Systems
7.18.1 Batteries 12 Not 60
7.18.2 Battery Chargers 12 Not 60
7.18.3 Rectifiers 12 Not 60
7.19 Surge Arrestors
7.19.1 Low-Voltage Devices Condition Based Maintenance Only
7.19.2 Medium and High-Voltage Devices 12 Not 60
7.20 Capacitors and Reactors
7.20.1 Capacitors 12 Not 60
7.20.2 Capacitor Control Devices 12 Not 60
7.20.3. Reactors, Dry-Type 12 Not 60
7.20.3. Reactors, Liquid-Filled 12 Not 60
The electronic version of this Celanese Chemicals SEP is the only official version. Before using any printed 3
copies, the electronic version must be checked to insure the use of the most current approved version.
Electrical
STANDARD NETA MTS-2007 Standard for Maintenance
Testing Specifications for Electrical
ENGINEERING Distribution Equipment and Systems

Celanese PRACTICES Revision: 1


Date: 1/7/2009
Chemicals Page 4 of 4

Sampling 12
7.21 Outdoor-Bus Structures Condition Based Maintenance Only
7.22 Emergency Systems
7.22.1 Engine Generator 12 Not 60
Functional Testing 12
7.22.2 Uninterruptible Power Systems 12 Not 60
Functional Testing 12
7.22.3 Automatic Transfer Switches 12 Not 60
Functional Testing 12
7.23 Telemetry/Pilot Wire SCADA
7.24 Automatic Circuit Reclosers
7.24.1 Automatic Circuit Reclosers, 12 Not 60