Client : ONGC
DMM
FOUNDATION DESIGN Rev: R1
Date: 15/07/06
It is observed from output forces obtained that Normal Service condition (Loadcase 11 from STAAD Output)
is critical. Hence, the footings are deisigned for forces in service/normal condition.
INPUT DATA
1 Column C1
Loads
Depth (along x) = 0.70 m P1 = 657 kN
Width (along y) = 0.70 m Mx1 = 332 kN
My1 = 171 kN
2 Column C2
Loads
Depth (along x) = 0.70 m P2 = 436 kN
Width (along y) = 0.70 m Mx2 = 322 kN
My2 = 543 kN
3 Column C3
Loads
Depth (along x) = 0.70 m P3 = 656.7 kN
Width (along y) = 0.70 m Mx3 = 332 kN
My3 = 171 kN
14.78
+ My
3.0
C1 C2 C3 Mx
X X
Y
Project : Air Compressor Shed
Client : ONGC
DMM
FOUNDATION DESIGN Rev: R1
Date: 15/07/06
C/L C/L of C2
Footing
C1 C2 C3
P1 P2 P3
1.650 1.650
600
1749 x z =
( 657 x 0.0 + 436 x 5.4 + 657 x 10.8 ) + 885.3
= 22.2 m3
= 109.2 m3
= 92 kN/m2 OK
Average pressure from left edge upto C2 = ( 139 + 127) = 133 kN/m
2
Average pressure from left edge upto C3 = ( 133 + 118) = 126 kN/m
2
Geometry : Materials :
Length = 5390 mm Concrete - M 30
Breadth = 3000 mm Steel - Fe 500
Depth = 600 mm
Pt = 0.004
= 8.400
uc = 0.459
The critical section for punching shear is considered at a distance of d/2 from the periphery of the face
of the column.